hpa brochure

Upload: vurumuu

Post on 10-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Hpa Brochure

    1/8

    ABB Switchgear

    HPASF6-circuitbreaker

    HPA is a medium-voltage circuit breaker

    using SF6 gas as the insulation and break-

    ing medium. Its design is compact and

    space-saving.

    The breaker is also available in a ver-sion with synchronised making for maxi-

    mum damping of transients for different

    applications.

  • 8/8/2019 Hpa Brochure

    2/8

    The HPA circuit breaker

    HPA is a medium-voltage circuit breaker

    using SF6

    gas as the insulation and

    breaking medium. Its design is compactand space-saving.

    The HPA breaker works extremely

    smoothly, which means that no dange-

    rous overvoltages arise through current

    cut-off or restriking. It is therefore very

    suitable for the majority of operating

    situations, including the breaking of motor

    loads and capacitors.

    The breaker is also available in a ver-sion with synchronised making for maxi-

    mum damping of transients when switch-

    ing in parallel capacitor banks.

    The excellent electrical and mechanical

    lifetime of the HPA breaker means that it

    requires only a minimum of maintenance.

  • 8/8/2019 Hpa Brochure

    3/8

    The breaking pole in

    different positions.

    The HPA breaker works according to the

    puffer principle, implying that when

    breaking, the gas is compressed between afixed plunger and a moving cylinder and

    then blown on to the arc between the fixed

    and moving arc contacts (see figure).

    When the breaker is closed, the current

    flows via the main contacts and the cylinder.

    When a tripping impulse is given, the

    cylinder moves downwards, whereupon the

    upper main contact opens and the current

    commutes over to the arc contact. At thesame time, the gas in the cylinder is com-

    pressed. When the nozzle has left the arc

    contact, the compressed gas is blown along

    the arc and cools it. The breaking process is

    completed as the current passes through

    zero.

    Breaking principle

    Closed position Breaking Open position

    Main

    contactMovingcylinder

    Arccontact

    Fixedplunger

    Nozzle

  • 8/8/2019 Hpa Brochure

    4/8

    Breaking gasSF6 (sulphurhexafluoride) gas possesses a

    unique combination of properties that

    makes it extremely suitable for use in

    circuit breakers. This has been confirmed

    by service experience from more than

    25,000 HPA breakers installed throughout

    the world.SF6 gas has an insulation strength some

    three times higher than that of air at an

    overpressure of 2 bar, which is even

    higher than that of transformer oil.

    The casing for the breaking poles is made

    of cast epoxy resin. The poles are

    thoroughly

    vacuum-dried

    after assembly

    and then sub-

    jected to

    pressure and

    sealing tests. The

    low gas pressure

    (2.5 bar over-

    pressure) and the

    small volume (12

    dm 3) mean that the

    breaking poles

    casing can under no circumstances dis-

    integrate due to negligence, for instance

    if it should be dropped during transport.

    The worst that can happen is that the

    casing cracks and the gas p ressure d rops.

    To further increase their reliability, the

    breaking poles can be provided with

    temperature-compensating transducers

    that provide an alarm at the lowest gas

    pressure permissible upon breaking of full

    short-circuit current.

    However, the safety margins are so

    large that the poles can cope with

    breaking of rated current even without

    overpressure.

    Exploded HPA breaking

    pole.

    SF6 gas properties High insulation strength

    Excellent ability to quench arcs

    Chemically stable

    Non-toxic

    Non-flammable

    Model of SF6 molecule.

    Breaking poles

  • 8/8/2019 Hpa Brochure

    5/8

    HPA breaker with

    operating device and

    breaking pole dis-

    assembled.

    Operating device

    The HPA breaker is provided with a

    simple and dependable operating device

    based on well established principles in

    combination with many years of service

    experience.

    The maintenance-free bearings and the

    ease of dismantling and removing

    breaking poles and operating devices are

    examples of valuable properties that

    reduce maintenance costs.

    The HPA breaker is operated by a

    spring-loaded operating device that is

    normally tensioned by an electric motor. It

    can also be tensioned manually.

    The tripping spring is automatically

    tensioned when the breaker is switched

    on. After each make operation, the motor

    starts and tensions the making spring.

    A breaker that is switched on can then

    perform an Off-On-Off operation withouthaving to tension the making spring in

    between, which means that the breaker

    can also be used for fast reconnection (a

    further On-Off operation can be made

    with a normal time lag).

    The breaker has making and tripping

    coils for electric operation and can also be

    supplied with pushbuttons for manual

    operation. There is space for an under-

    voltage release or a further tripping coil.

    A counter for the number of operationsand indicators for tensioned/ untensioned

    making spring and open/closed breaker

    are included as standard.

    The operating device is easily accessible

    in the breakers rack and can be easily

    dismantled and replaced.

    The HPA breakers

    operating device.

  • 8/8/2019 Hpa Brochure

    6/8

    Lifetime

    Principal dimensions for HPA

    The HPA breaker requires a minimum of

    maintenance. The gas and the breaking

    poles do not need to be replaced and burn-

    off of contacts and nozzle due to the arcs is

    insignificant. The breaking poles therefore

    have a very long lifetime. The high electrical

    lifetime is achieved through short breaking

    times. For example, the poles cope with 160

    breaks at 10 kA without maintenance of the

    contacts.

    The graph on the left shows the

    contact lifetime expressed in the

    number of possible breaks at various

    short-circuit currents. The fact that

    the main contacts are never affected

    by the arcs is also of great significan-

    ce for the long lifetime.

    In the unlikely event of the break-

    ing pole requiring repair, this has to

    take place at the factory since vacuum

    drying and pressure and sealing tests

    have to be carried out. The breaking pole

    can then be replaced by a spare pole that

    can be easily mounted on site.

    10 000

    1000

    100

    10

    10 20 30 40 kA

    Electrical endurance of

    the HPA circuit breaker.Number of interruptions

    Short-circuit current

    3.6 - 12 kV: 622 mm, 15 - 30 kV: 747 mm3.6 - 12 kV: 617 mm, 15 - 30 kV: 717 mm

    Phase distance

    185 or 210 mm

    90mm

    367mm

    640mm

    4.5mm

    139mm

  • 8/8/2019 Hpa Brochure

    7/8

    Type testing has been carried out in accord-

    ance with IEC 56 and ANSI c37.09.

    The short-circuit tests were performed at

    ABBs laboratory in Sweden, at KEMA in

    Holland, at IREQ in Canada and at Powertest

    in the U.S.A.

    A certificate and test report can be

    obtained upon request.

    Data according to ANSI c37.09

    Max. voltage kV 15 26 30

    K factor ....................................................................................................................................................................1.3....................................... 1.0......................................1.0

    Frequency..............................................................................................................Hz...........................................60 ..........................................60 .......................................60Rated holding voltage with alternating voltage testing......kV...........................................36 ..........................................50 .......................................60

    Rated holding voltage with surge testing .....................................kV...........................................95.......................................125 ....................................150

    Rated current .........................................................................................................A .................1200 3000.................1200 3000 ..............1200 3000

    Making capacity................................................................................................kA...........................................58 ..........................................37 .......................................41

    Short-circuit current ......................................................................................kA...........................................28 ..........................................18 .......................................20

    Operating cycle.....................................................................................................................O 0.3 s CO/P 15 s CO 1 h CO

    Breaking time ........................................................................................periods ..............................................5 .............................................5 ..........................................5

    Max. breaking capacity symmetrical ...............................................kA...........................................36 ..........................................18 .......................................20

    Short-time current, 3 sec. ........................................................................kA...........................................36 ..........................................18 .......................................20

    Data according to IEC 56

    Rated voltage kV 3.6 12 17 24 36

    Rated frequency ...............................................................................................Hz............................50...........................50..............................50 ................................50

    Rated power frequency withstand voltage .................................kV............................28...........................38..............................50 ................................70

    Rated lightning impulse withstand voltage ..................................kV............................75...........................95 ..........................125 .............................170

    Rated current .........................................................................................................A ..................3150................ 2500................... 2500 ..................... 1250

    Rated (peak) making current ...................................................kA peak ........................100 .......................100..............................79 ................................63

    Short circuit breaking current with operating cycle:

    O 0.3 s CO 3 min CO.................................................................kA............................40...........................40.........................31.5 ................................25

    O 3min CO 3 min CO ...............................................................kA............................50.......................... ........................... ..............................

    Opening time......................................................................................................ms............................38...........................38..............................38 ................................38

    Opening time for 12 kV 50 kA..............................................................ms............................70.......................... ........................... .............................

    Arcing time, max. ............................................................................................ms............................15...........................15..............................15 ................................15

    Breaking time .....................................................................................................ms............................53...........................53..............................53 ................................53

    Breaking time for 12 kV 50 kA .............................................................ms............................85.......................... ........................... .............................

    Making time, max...........................................................................................ms............................75...........................75..............................75 ................................75

    Short-time current .........................................................................................kA............................50...........................40.........................31.5 ................................25

    Principal data for HPA

  • 8/8/2019 Hpa Brochure

    8/8

    12

    Broschyr1VEB580901-914.

    Edition2b,

    98-0

    8.

    Production:Roos&CoVsters.

    StenbyOffset.2000ex.

    ABB Switchgear ABMedium Voltage Division

    Box 1023

    S-732 27 Arboga, Sweden

    Telephone: +46 589 851 00

    Telefax: +46 589 852 90

    E-mail: [email protected]

    We reserve the right to alter design, dimensions andtechnical data without prior notice.