hpa brochure
TRANSCRIPT
-
8/8/2019 Hpa Brochure
1/8
ABB Switchgear
HPASF6-circuitbreaker
HPA is a medium-voltage circuit breaker
using SF6 gas as the insulation and break-
ing medium. Its design is compact and
space-saving.
The breaker is also available in a ver-sion with synchronised making for maxi-
mum damping of transients for different
applications.
-
8/8/2019 Hpa Brochure
2/8
The HPA circuit breaker
HPA is a medium-voltage circuit breaker
using SF6
gas as the insulation and
breaking medium. Its design is compactand space-saving.
The HPA breaker works extremely
smoothly, which means that no dange-
rous overvoltages arise through current
cut-off or restriking. It is therefore very
suitable for the majority of operating
situations, including the breaking of motor
loads and capacitors.
The breaker is also available in a ver-sion with synchronised making for maxi-
mum damping of transients when switch-
ing in parallel capacitor banks.
The excellent electrical and mechanical
lifetime of the HPA breaker means that it
requires only a minimum of maintenance.
-
8/8/2019 Hpa Brochure
3/8
The breaking pole in
different positions.
The HPA breaker works according to the
puffer principle, implying that when
breaking, the gas is compressed between afixed plunger and a moving cylinder and
then blown on to the arc between the fixed
and moving arc contacts (see figure).
When the breaker is closed, the current
flows via the main contacts and the cylinder.
When a tripping impulse is given, the
cylinder moves downwards, whereupon the
upper main contact opens and the current
commutes over to the arc contact. At thesame time, the gas in the cylinder is com-
pressed. When the nozzle has left the arc
contact, the compressed gas is blown along
the arc and cools it. The breaking process is
completed as the current passes through
zero.
Breaking principle
Closed position Breaking Open position
Main
contactMovingcylinder
Arccontact
Fixedplunger
Nozzle
-
8/8/2019 Hpa Brochure
4/8
Breaking gasSF6 (sulphurhexafluoride) gas possesses a
unique combination of properties that
makes it extremely suitable for use in
circuit breakers. This has been confirmed
by service experience from more than
25,000 HPA breakers installed throughout
the world.SF6 gas has an insulation strength some
three times higher than that of air at an
overpressure of 2 bar, which is even
higher than that of transformer oil.
The casing for the breaking poles is made
of cast epoxy resin. The poles are
thoroughly
vacuum-dried
after assembly
and then sub-
jected to
pressure and
sealing tests. The
low gas pressure
(2.5 bar over-
pressure) and the
small volume (12
dm 3) mean that the
breaking poles
casing can under no circumstances dis-
integrate due to negligence, for instance
if it should be dropped during transport.
The worst that can happen is that the
casing cracks and the gas p ressure d rops.
To further increase their reliability, the
breaking poles can be provided with
temperature-compensating transducers
that provide an alarm at the lowest gas
pressure permissible upon breaking of full
short-circuit current.
However, the safety margins are so
large that the poles can cope with
breaking of rated current even without
overpressure.
Exploded HPA breaking
pole.
SF6 gas properties High insulation strength
Excellent ability to quench arcs
Chemically stable
Non-toxic
Non-flammable
Model of SF6 molecule.
Breaking poles
-
8/8/2019 Hpa Brochure
5/8
HPA breaker with
operating device and
breaking pole dis-
assembled.
Operating device
The HPA breaker is provided with a
simple and dependable operating device
based on well established principles in
combination with many years of service
experience.
The maintenance-free bearings and the
ease of dismantling and removing
breaking poles and operating devices are
examples of valuable properties that
reduce maintenance costs.
The HPA breaker is operated by a
spring-loaded operating device that is
normally tensioned by an electric motor. It
can also be tensioned manually.
The tripping spring is automatically
tensioned when the breaker is switched
on. After each make operation, the motor
starts and tensions the making spring.
A breaker that is switched on can then
perform an Off-On-Off operation withouthaving to tension the making spring in
between, which means that the breaker
can also be used for fast reconnection (a
further On-Off operation can be made
with a normal time lag).
The breaker has making and tripping
coils for electric operation and can also be
supplied with pushbuttons for manual
operation. There is space for an under-
voltage release or a further tripping coil.
A counter for the number of operationsand indicators for tensioned/ untensioned
making spring and open/closed breaker
are included as standard.
The operating device is easily accessible
in the breakers rack and can be easily
dismantled and replaced.
The HPA breakers
operating device.
-
8/8/2019 Hpa Brochure
6/8
Lifetime
Principal dimensions for HPA
The HPA breaker requires a minimum of
maintenance. The gas and the breaking
poles do not need to be replaced and burn-
off of contacts and nozzle due to the arcs is
insignificant. The breaking poles therefore
have a very long lifetime. The high electrical
lifetime is achieved through short breaking
times. For example, the poles cope with 160
breaks at 10 kA without maintenance of the
contacts.
The graph on the left shows the
contact lifetime expressed in the
number of possible breaks at various
short-circuit currents. The fact that
the main contacts are never affected
by the arcs is also of great significan-
ce for the long lifetime.
In the unlikely event of the break-
ing pole requiring repair, this has to
take place at the factory since vacuum
drying and pressure and sealing tests
have to be carried out. The breaking pole
can then be replaced by a spare pole that
can be easily mounted on site.
10 000
1000
100
10
10 20 30 40 kA
Electrical endurance of
the HPA circuit breaker.Number of interruptions
Short-circuit current
3.6 - 12 kV: 622 mm, 15 - 30 kV: 747 mm3.6 - 12 kV: 617 mm, 15 - 30 kV: 717 mm
Phase distance
185 or 210 mm
90mm
367mm
640mm
4.5mm
139mm
-
8/8/2019 Hpa Brochure
7/8
Type testing has been carried out in accord-
ance with IEC 56 and ANSI c37.09.
The short-circuit tests were performed at
ABBs laboratory in Sweden, at KEMA in
Holland, at IREQ in Canada and at Powertest
in the U.S.A.
A certificate and test report can be
obtained upon request.
Data according to ANSI c37.09
Max. voltage kV 15 26 30
K factor ....................................................................................................................................................................1.3....................................... 1.0......................................1.0
Frequency..............................................................................................................Hz...........................................60 ..........................................60 .......................................60Rated holding voltage with alternating voltage testing......kV...........................................36 ..........................................50 .......................................60
Rated holding voltage with surge testing .....................................kV...........................................95.......................................125 ....................................150
Rated current .........................................................................................................A .................1200 3000.................1200 3000 ..............1200 3000
Making capacity................................................................................................kA...........................................58 ..........................................37 .......................................41
Short-circuit current ......................................................................................kA...........................................28 ..........................................18 .......................................20
Operating cycle.....................................................................................................................O 0.3 s CO/P 15 s CO 1 h CO
Breaking time ........................................................................................periods ..............................................5 .............................................5 ..........................................5
Max. breaking capacity symmetrical ...............................................kA...........................................36 ..........................................18 .......................................20
Short-time current, 3 sec. ........................................................................kA...........................................36 ..........................................18 .......................................20
Data according to IEC 56
Rated voltage kV 3.6 12 17 24 36
Rated frequency ...............................................................................................Hz............................50...........................50..............................50 ................................50
Rated power frequency withstand voltage .................................kV............................28...........................38..............................50 ................................70
Rated lightning impulse withstand voltage ..................................kV............................75...........................95 ..........................125 .............................170
Rated current .........................................................................................................A ..................3150................ 2500................... 2500 ..................... 1250
Rated (peak) making current ...................................................kA peak ........................100 .......................100..............................79 ................................63
Short circuit breaking current with operating cycle:
O 0.3 s CO 3 min CO.................................................................kA............................40...........................40.........................31.5 ................................25
O 3min CO 3 min CO ...............................................................kA............................50.......................... ........................... ..............................
Opening time......................................................................................................ms............................38...........................38..............................38 ................................38
Opening time for 12 kV 50 kA..............................................................ms............................70.......................... ........................... .............................
Arcing time, max. ............................................................................................ms............................15...........................15..............................15 ................................15
Breaking time .....................................................................................................ms............................53...........................53..............................53 ................................53
Breaking time for 12 kV 50 kA .............................................................ms............................85.......................... ........................... .............................
Making time, max...........................................................................................ms............................75...........................75..............................75 ................................75
Short-time current .........................................................................................kA............................50...........................40.........................31.5 ................................25
Principal data for HPA
-
8/8/2019 Hpa Brochure
8/8
12
Broschyr1VEB580901-914.
Edition2b,
98-0
8.
Production:Roos&CoVsters.
StenbyOffset.2000ex.
ABB Switchgear ABMedium Voltage Division
Box 1023
S-732 27 Arboga, Sweden
Telephone: +46 589 851 00
Telefax: +46 589 852 90
E-mail: [email protected]
We reserve the right to alter design, dimensions andtechnical data without prior notice.