honeywell yokogawa controllers - cei enterprises · system to honeywell udc 2500 modulation...

1
July 2015 Call today! 800.545.4034. Available FREE at ceienterprises.com, this new Service & Troubleshooting Guide shows you how to confirm and calculate 4–20mA output from Honeywell UDC 2500 controllers. These controllers are used on CEI hot oil heaters to control the burner modulation motor. The guide will help you determine if you may be experiencing a wiring error, or if you need a new controller. Use promo code HY715 (must be in-stock purchase over $500) Modulating Burner Control & 4–20mA Circuits NEW Service & Troubleshooting Guide: Verifying 4–20 Output on Honeywell UDC 2500 modulation controllers Modulating burner control is a key component of a CEI heater’s fuel efficiency. The concept is simple: the burner operates at a variable fire rate so that it only burns the amount of fuel necessary to maintain your heat demand. Modulating control conserves fuel, reduces temperature overshooting and eliminates constant on-off burner recycling. The key to modulating burner control is the communication between the modulating controller and the modulation motor that continually adjusts the burner’s fuel and air intake. This communication is dependent on a 4–20mA circuit originating from the controller. Happy 4th of July! If you do need a new controller, you can take advantage of our July sale on Honeywell and Yokogawa controllers: 15% off in-stock purchases over $500.00 through July 31! Use promo code “HY715” when ordering from our parts department. To download the Service & Troubleshooting Guide, click on “Tech Documents” under the Parts/Service button on our website. ©2015 CEI Enterprises, Inc | 245 Woodward Rd SE | Albuquerque, NM 87102 USA | ceienterprises.com FREE tech info, plus special discounts on parts and service work! just go to ceienterprises.com, click on Parts/Service, & sign up for our e-mail newsletter. No junk e-mail. Easily unsubscribe at any time! Honeywell & Yokogawa Controllers Sale Ends July 31, 2015 Service and Troubleshooting Guide Publication # 15-06-007 CEI Service & Parts: 800.545.4034 245 Woodward Rd. SE | Albuquerque, New Mexico 87102 | USA ©2015 CEI Enterprises, Inc. Verifying 4–20 Output on Honeywell UDC 2500 modulation controllers Following the completion of the burner purge cycle (at end of MTFI sequence), burner control will be transferred from Fireye flame control system to Honeywell UDC 2500 modulation controller. At this point, the controller uses a 4–20 milliamp signal to communicate with the burner and modulation motor (via the mod motor resistor board). Confirming 4-20 mA signal from Honeywell UDC modulation controller Remove wires from terminals 19 and 21 on the back of the modulation controller (Figure 1) and place a 250 ohm resistor between the two terminals. Place controller in manual operation mode (using the M-A Reset button) and drive output to 0% then to 50% and 100% (using up arrow). Measure voltage (in volts DC) between 19 and 21. Look for the following: 0% = 4 mA 50% = 12 mA 100% = 20 mA If these measurements are not recorded, check wiring or replace controller as needed. Calculating 4–20 mA output 1. Measure volts DC between terminals 19 and 21 on the back of the Honeywell UDC 2500 controller. 2. Record voltage (DC). 3. Divide recorded voltage by 250 and multiply by 1000 to get milliamps. Example: .999 ÷ 250 = 0.003996 x 1000 = 3.996 = 4. SHOCK HAZARD. High voltage is present on certain terminals and wires inside the main control panel, inside the mod motor and inside the burner panel. Touching them will cause death or serious injury. Do not work on these components unless you are a qualified technician familiar with the hazards of electricity. Some circuits in the main control panel may receive power from remote sources. Thus, the breaker operator on the door may not deenergize all exposed live parts. Always use a voltage tester to make sure there is no voltage on the terminals or bare wires you may touch. Figure 1. Honeywell UDC 2500 modulation controller and terminals. 250 Ohm Resistor Terminal 19 Terminal 21 Equipment. Parts. Service. Rely on CEI. A legacy of innovation and quality since 1969.

Upload: vuongthu

Post on 09-Apr-2018

233 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Honeywell Yokogawa Controllers - CEI Enterprises · system to Honeywell UDC 2500 modulation controller. At this point, the controller uses a 4–20 milliamp signal to communicate

July 2015

Call today! 800.545.4034.

Available FREE at ceienterprises.com, this new Service & Troubleshooting Guide shows you how to confirm and calculate 4–20mA output from Honeywell UDC 2500 controllers. These controllers are used on CEI hot oil heaters to control the burner modulation motor.

The guide will help you determine if you may be experiencing a wiring error, or if you need a new controller.

Use promo code HY715(must be in-stock purchase over $500)

Modulating Burner Control & 4–20mA Circuits

NEW Service & Troubleshooting Guide:Verifying 4–20 Output

on Honeywell UDC 2500 modulation controllers

Modulating burner control is a key component of a CEI heater’s fuel efficiency. The concept is simple: the burner operates at a variable fire rate so that it only burns the amount of fuel necessary to maintain your heat demand. Modulating control conserves fuel, reduces temperature overshooting and eliminates constant on-off burner recycling.

The key to modulating burner control is the communication between the modulating controller and the modulation motor that continually adjusts the burner’s fuel and air intake.

This communication is dependent on a 4–20mA circuit originating from the controller.

Happy 4th of July!

If you do need a new controller, you can take advantage of our July sale on Honeywell and Yokogawa controllers: 15% off in-stock purchases over $500.00 through July 31! Use promo code “HY715” when ordering from our parts department.

To download the Service & Troubleshooting Guide, click on “Tech Documents” under the Parts/Service button on our website.

©2015 CEI Enterprises, Inc | 245 Woodward Rd SE | Albuquerque, NM 87102 USA | ceienterprises.com

FREE tech info, plus

special discounts on

parts and service work!

just go to ceienterprises.com,

click on Parts/Service, & sign

up for our e-mail newsletter.

No junk e-mail.

Easily unsubscribe

at any time!

Honeywell & Yokogawa Controllers

Sale Ends July 31, 2015

Service and Troubleshooting Guide

Publication # 15-06-007

CEI Service & Parts: 800.545.4034245 Woodward Rd. SE | Albuquerque, New Mexico 87102 | USA

©2015 CEI Enterprises, Inc.

Verifying 4–20 Outputon Honeywell UDC 2500 modulation controllers

Following the completion of the burner purge cycle (at end of MTFI sequence), burner control will be transferred from Fireye flame control system to Honeywell UDC 2500 modulation controller. At this point, the controller uses a 4–20 milliamp signal to communicate with the burner and modulation motor (via the mod motor resistor board).

Confirming 4-20 mA signal from Honeywell UDC modulation controller

Remove wires from terminals 19 and 21 on the back of the modulation controller (Figure 1) and place a 250 ohm resistor between the two terminals. Place controller in manual operation mode (using the M-A Reset button) and drive output to 0% then to 50% and 100% (using up arrow). Measure voltage (in volts DC) between 19 and 21. Look for the following:

0% = 4 mA50% = 12 mA100% = 20 mA

If these measurements are not recorded, check wiring or replace controller as needed.

Calculating 4–20 mA output

1. Measure volts DC between terminals 19 and 21 on the back of the Honeywell UDC 2500 controller.

2. Record voltage (DC).

3. Divide recorded voltage by 250 and multiply by 1000 to get milliamps.

Example: .999 ÷ 250 = 0.003996 x 1000 = 3.996 = 4.

SHOCK HAZARD. High voltage is present on certain terminals and wires inside the main control panel, inside the mod motor and inside the burner panel. Touching them will cause death or serious injury.Do not work on these components unless you are a qualified technician familiar with the hazards of electricity. Some circuits in the main control panel may receive power from remote sources. Thus, the breaker operator on the door may not deenergize all exposed live parts. Always use a voltage tester to make sure there is no voltage on the terminals or bare wires you may touch.

Figure 1. Honeywell UDC 2500 modulation controller and terminals.

250 Ohm Resistor

Terminal 19

Terminal 21

Equipment. Parts. Service. Rely on CEI. A legacy of innovation and quality since 1969.