high frequency model on an transformers

Upload: edgar-mauricio-aguilar-umbarila

Post on 05-Apr-2018

223 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/31/2019 High Frequency Model on an Transformers

    1/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 541

    1070-9878/11/$25.00 2011 IEEE

    Development of High Frequency Circuit Modelfor Oil-immersed Power Transformers and its Application

    for Lightning Surge Analysis

    Shigemitsu Okabe, Masanori Koto, Genyo UetaTokyo Electric Power Company

    4-1, Egasaki-cho, Tsurumi-ku, Yokohama, Kanagawa, 230-8510, Japan

    Toshiyuki Saida and Shin YamadaToshiba Corporation

    1-1, Shibaura 1-chome, Minato-ku, Tokyo, 105-8001, Japan

    ABSTRACTThe lightning impulse withstand voltage for an oil-immersed power transformer is

    determined by the value of the lightning surge overvoltage generated at the

    transformer terminal. This overvoltage value has been conventionally obtainedthrough lightning surge analysis using the electromagnetic transients program (EMTP),

    where the transformer is often simulated by a single lumped capacitance. However,

    since high frequency surge overvoltages ranging from several kHz to several MHz are

    generated in an actual system, a transformer circuit model capable of simulating the

    range up to this high frequency must be developed for further accurate analysis. In this

    paper, a high frequency circuit model for an oil-immersed transformer was developed

    and its validity was verified through comparison with the measurement results on the

    model winding actually produced. Consequently, it emerged that a high frequency

    model with three serially connected LC parallel circuits could adequately simulate the

    impedance characteristics of the winding up to a high frequency range of several MHz.

    Following lightning surge analysis for a 500 kV substation using this high frequency

    model, the peak value of the waveform was evaluated as lower than that simulated by

    conventional lumped capacitance even though the front rising was steeper. Thisphenomenon can be explained by the charging process of the capacitance circuit inside

    the transformer. Furthermore, the waveform analyzed by each model was converted

    into an equivalent standard lightning impulse waveform and the respective peak values

    were compared. As a result, the peak value obtained by the lumped capacitance

    simulation was evaluated as relatively higher under the present analysis conditions.

    Index Terms Oil-immersed transformer, lightning surge, high frequency circuit

    model, 500 kV substation, Electro-magnetic Transients Program.

    1 INTRODUCTION

    TO determine the lightning impulse withstand voltage for anoil-immersed power transformer, the value of the generated

    overvoltage has been conventionally obtained through lightning

    surge analysis using the Electro-magnetic Transients Program

    (EMTP). In such cases, the transformer is often simulated by a

    single lumped capacitance [1] called a surge intrusion

    capacitance. However, the value to which this capacitance

    should be set is not necessarily clear, nor is whether or not

    surges ranging from several kHz to several MHz actually

    generated can be simulated by a single capacitance.

    On the other hand, amid ongoing trends, such as the

    downsizing of substations and the direct connection to gas

    insulated switchgears (GIS), overvoltages with frequencies

    exceeding conventional ones are more likely to be generated.In addition, it is known that, with the introduction of, for

    example, a winding with a large series capacitance, a

    transformer itself exhibits resonance behavior at a high

    frequency of around 1 MHz [2].

    Under these circumstances, the development of a new

    transformer model within the frequency range of lightning

    surges is desirable. To precisely simulate the winding up to

    the high frequency range, a detailed equivalent circuit is

    required that provides the inductance and capacitance for each

    turn of the conductor [3]. However, such a detailed model isManuscript received on 4 November 2010, in final form 18 January 2011.

  • 7/31/2019 High Frequency Model on an Transformers

    2/12

    542 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Applicationfar too complicated for the whole transformer if its purpose is

    not to clarify the electric potential distribution within a

    winding but to obtain the voltage generated at the transformer

    terminal through surge analysis of the substation or overall

    system. The authors previously proposed a relatively

    simplified circuit model that could simulate a 275 kV gas

    insulated shunt reactor up to the high frequency range [4].

    In this paper, the above technique was applied to a 500 kV

    oil-immersed transformer and a high frequency circuit model

    for an oil-immersed transformer was developed, and its

    validity was evaluated through comparison with the

    measurement results of the actual model winding.

    Subsequently, the new model was used to perform a lightning

    surge analysis for a 500 kV substation. This result was

    compared with the conventional case where a transformer was

    simulated by an intrusion capacitance, and the level of the

    lightning surge overvoltage generated at the transformer

    terminal and its influence on the waveform were studied.

    Furthermore, each overvoltage waveform was converted into

    an equivalent standard lightning impulse waveform using the

    waveform evaluation method [5] to evaluate from the

    perspective of the severity for insulation.

    2 CIRCUITMODELFORWINDING

    As winding structures for a transformer, the present study

    uses interleaved and continuous disk windings respectively,

    for which circuit models are developed with the high

    frequency range up to several MHz taken into consideration.

    2.1 CIRCUIT MODEL FOR INTERLEAVED DISKWINDING

    2.1.1 CIRCUIT MODEL IN THE LOW FREQUENCY

    RANGE

    An interleaved disk winding is a kind of disk winding used

    for core type transformers and reactors. Since it has a large

    series capacitance, it is used as a kind of lightning-surge-proof

    winding mainly for high voltage winding. Figure 1 illustrates

    the cross-sectional structure of an interleaved disk winding.

    Two disks constitute a single structural unit, which comprise

    the whole winding when collectively stacked. Assuming that

    one disk is called a section, Figure 1 shows an example of a

    winding with 8 turns per section. The numbers in the figure

    indicate the order of winding. Assuming that the conductor of

    the winding order numbers 1 to 8 is called Group A and that

    of numbers 9 to 16 Group B, since the conductors of Groups

    A and B lie adjacent, with potential difference equivalent to

    that of the number of turns per section, the equivalent seriescapacitance of the winding is eventually large. The series

    capacitance of an interleaved disk winding can be obtained

    using what is called the stored energy method and given by

    equation (1) [6]:

    2)(n2

    CC

    r0 (1)

    Cr: Turn-to-turn capacitance

    n: Number of turns per section

    In this equation, each turn within the two sections is

    assumed to form a linear potential distribution, the

    electrostatic energy stored between individual turns is totaled

    and capacitance with electrostatic energy equal to this totaled

    energy is regarded as the series capacitance C0 for two

    sections. The value of n is about 5 to 30, while it varies

    depending on the capacity and voltage class of the transformer.

    Compared with the series capacitance of a continuous disk

    winding expressed by equation (8), which is described later,the series capacitance of an interleaved disk winding is

    generally larger by approximately one digit.

    Figure 2 presents the equivalent circuit for two sections of

    an interleaved disk winding. Each turn is expressed by one

    inductance element in Figure 2a, while two sections are

    simulated by one inductance element in Figure 2b. The circuit

    model for an interleaved disk winding that holds in the low

    frequency range can be obtained if C0 in equation (1) is given

    as the capacitance for two sections in Figure 2b to structure

    the circuit of the whole winding. Here, L0 is the self-

    inductance of the whole coil with 2n turns, which is about

    (2n)2 times the value of the inductance per turn.

    2.1.2 CIRCUIT MODEL WITH RANGES UP TO THE

    HIGH FREQUENCY RANGE TAKEN INTO

    CONSIDERATION

    If the wavefront duration of the waveform applied to the

    winding is shorter than the charging time (approximately 0.2

    s to 0.5 s) for the turn-to-turn capacitance, the potential at

    each turn within the section does not form a linear distribution.

    Consequently, the capacitance in equation (1) obtained by the

    stored energy method alone cannot obtain a circuit model

    applicable to the high frequency range of several MHz.

    In the circuit in Figure 2a, the capacitance seen from both

    ends of the two sections at a high frequency (e.g. 10 MHz or

    : Group A

    : Group B

    12

    168157146135

    192103114

    Figure 1. Construction of an interleaved disk winding.

    Figure 2. Equivalent circuit of an interleaved disk winding.

    (a) Detailed circuit (b) Simplified circuit

    L0 C0

    CrCa/nEquipotential surface

    between sections

    Correspondingto the numberof the order ofwinding in Figure 1

    Ca: Section-to-section capacitance

    (1)(2)(3)(4)

    (5) (6) (7) (8)

    (9)(10)(11)(12)

    (13) (14) (15) (16)

  • 7/31/2019 High Frequency Model on an Transformers

    3/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 543

    more), where the inductance is negligible, is smaller than C0

    obtained by equation (1). In this process of the change in

    capacitance, a resonance phenomenon is observed within

    section [2].

    Pedersen assumed each section of an interleaved disk

    winding to be a spirally wound parallel plane capacitor and

    considered that the winding responded to steep front waves

    like a transmission line of capacitance C and inductance L per

    section [7]. Here, C is given by equation (2) because it

    indicates the capacitance between conductors in Groups A and

    B in Figure 1 and the number of locations where conductors

    face each other is (n1) per section.

    d/Db)1n(C 0 (2)

    : Relative permittivity of the turn-to-turn insulation

    0: Vacuum permittivity

    D: Average winding diameter

    b: Axial conductor width

    d: Turn-to-turn insulation thickness

    The value L is given by the inductance of the parallel

    conductors consisting of the conductors in Groups A and B

    and obtained in a simplified manner by equation (3) because

    the length of the parallel conductor in one section is

    equivalent to n/2 turns.

    b/Dd)2/n(L 0 (3)

    0: Vacuum magnetic permeability

    Assuming that surges reflect at the point connected to the

    next section on the inner periphery side of the section and thatthe oscillation is generated with the time of the round trip in

    the section as their period, the oscillation period is given by

    equation (4).

    )n

    11(

    2nD2LC2T 00

    (4)

    In order to express an oscillation circuit of resonance

    frequency f1 identical to this oscillation using the LC parallel

    circuit with a lumped constant, its inductance L1 and

    capacitance C1 can be replaced to equation (6) based on

    equation (5).

    11

    1

    CL2

    1

    LC2

    1f

    (5)

    /CC,/LL 11 (6)

    Consequently, the circuit displayed in Figure 3a was

    devised in order to simulate, via a simplified circuit, the fact

    that the value of the equivalent series capacitance of the

    interleaved disk winding given by Figure 2b is small in the

    high frequency range and that the resonance point is within

    the section in the high frequency range. The L1C1 parallel

    circuit, consisting of the inductance and capacitance obtained

    by equation (6), is serially connected to the capacitance

    branch of the L0C0 parallel circuit in Figure 2b. This circuit

    has a parallel resonance point at frequency f1. At higher

    frequencies, it is eventually expressed by the serially

    connected capacitance with C0 and C1. If C1 is adequately

    smaller than C0, the capacitance is almost determined by C1.

    As subsequently described in Clause 3.2, since L1 is

    adequately smaller than the inductance L0, which is for two

    sections, the impedance characteristics of the circuit barely

    changes, even if the L1C1 parallel circuit is serially connected

    directly to the L0C0 parallel circuit in Figure 2b. Furthermore,

    the oscillation caused by multiple reflections in the section

    includes not only the fundamental oscillation frequency given

    by equation (5) but also the higher order resonance

    frequencies at its integral multiple frequencies. To simulate

    higher order resonance frequencies up to the second order, the

    L2C2 parallel circuit given by equation (7) is connected.

    2/CC,2/LL 1212 (7)

    Based on the above, a three-stage LC circuit shown in

    Figure 3b is developed as a simplified circuit with ranges up

    to the high frequency range taken into consideration. Parallel

    resistors are connected in the second and third stage LC

    circuits, which simulate the oscillation in the high frequency

    range, and take the damping of high frequency oscillations

    into consideration. The damping resistance of this high

    frequency wave is expressed as k(L/C)1/2, and the value

    k is obtained through comparison of the analysis waveform

    of the equivalent circuit with the waveform actually measured.

    2.2 CIRCUIT MODEL FOR CONTINUOUS DISKWINDING

    A disk winding continuously wound without interleaving

    conductors with the cross sectional structure as demonstrated

    in Figure 4 is called a continuous disk winding and is used as

    a low voltage winding that does not particularly require

    lightning-surge-proof characteristics, as well as in the form of

    a combined interleaved disk winding on the line terminal side

    and a continuous disk winding on the neutral point side in the

    same winding.

    Figure 3. Equivalent circuit with ranges up to the high frequency range taken

    into consideration. (a) Parallel resonance point at the frequency of f1considered (b) Resonance frequencies up to the second order considered.

    (a) (b)

    L0

    C1L1

    C0L0

    L1

    L2

    C0

    C1

    C2

    R1

    R2

  • 7/31/2019 High Frequency Model on an Transformers

    4/12

    544 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its ApplicationSimilarly to Figure 2a, an equivalent circuit with a lumped

    constant for two sections with one turn expressed by one

    inductance element is presented in Figure 5a. Here, consider

    the capacitance value in the case where this circuit is

    expressed by the LC parallel circuit in Figure 5b. Assuming

    that each turn in the section has a linear potential distribution,

    if the concept of the stored energy method is applied, the

    series capacitance for two sections can be obtained by

    equation (8) [8].

    2

    ra0

    2n

    C)1n(C

    3

    2C

    (8)

    Ca: Section-to-section capacitance

    Next, obtain the series capacitance when steep front wave

    surges are applied. Consider the circuit as given in Figure 6

    consisting of only capacitances sandwiched by equipotential

    surfaces between two sections. Here, the potential v(x) of each

    turn is expressed by equation (9).

    sinh

    )x1(sinhxsinh12Ev(x) (9)

    r

    a

    C

    C)1n(4

    E: Voltage distribution per section

    The series capacitance C0' for two sections obtained by the

    stored energy method based on equation (9) is expressed by

    equation (10).

    sinh

    )cosh1(21

    2

    C'C

    a0 (10)

    The ratio of C0' to C0 with respect to Ca/Cr with n as a

    parameter is exhibited in Figure 7. Since Ca/Cr is generally

    about 1 to 2, C0' is only about 10% smaller than C0 in the

    practical range. In other words, the series capacitance is

    considered to barely vary within a low to high frequency

    range covering several MHz. Consequently, in the case of a

    continuous disk winding, the circuit in Figure 5b can be used

    for the whole frequency range. For simulation up to the high

    frequency range in detail, the present study uses the value C0'

    based on equation (10).

    3 EVALUATIONOFCIRCUITMODEL

    3.1 MODEL WINDING AND MEASUREMENTMETHOD

    To evaluate the validity of the circuit models devised inChapter 2, an interleaved disk winding with two sections

    equivalent to those for a 500 kV actual transformer was

    produced (To be more specific: In comparison with an actual

    one, the axial conductor width b, the turn-to-turn insulation

    thickness d, and the oil-gap length between the sections were

    identical, and the average winding diameter D was scaled

    down to 75%) and the impedance frequency characteristics were

    measured. For measurement, a network analyzer (ANRITSU,

    MS3401A) was used. Sine waves were applied to the winding

    by sweeping the frequencies from 100 Hz to 10 MHz to

    8

    161514131211109

    1234567

    Figure 4. Construction of a continuous disk winding.

    0.6

    0.8

    1

    1.2

    0.5 1 1.5 2Ca / Cr

    C0'/C0

    n=10

    n=20

    Figure 7. Series capacitances of a continuous disc winding.

    Figure 5. Equivalent circuit of a continuous disk winding.

    (a) Detailed circuit (b) Simplified circuit

    Figure 6. Capacitance circuit of a continuous disc winding.

    L0 C0

    10x

    Equipotential surface (v(1)=E)

    Cr

    2Ca/n

    v(x)

    Equipotential surface (v(0)=0)

    CrCa/nEquipotential surface

    between sections

    Correspondingto the numberof the order of

    winding in Figure 4

    (1)(2)(3)(4)(5)(6)(7)(8)

    (9) (10) (11) (12) (13) (14) (15) (16)

  • 7/31/2019 High Frequency Model on an Transformers

    5/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 545

    measure the impedance at each frequency. Figure 8 shows the

    appearance of a two section model. The measurement was

    conducted in insulating oil. Furthermore, a ten section model

    winding was produced to measure like frequency characteristics

    as well as the response waveforms in various locations in the

    winding, an overview of which is carried in Figure 9. Similarly

    to the two-section model, this model was placed inside the

    insulating oil to conduct measurement.

    3.2 COMPARISON OF THE ANALYSIS RESULTSUSING CIRCUIT MODEL WITH ACTUAL

    MEASUREMENT RESULTS OF MODEL WINDING

    Using the size of the model winding with two sections

    produced for the present study as well as the material constant,each parameter of the equivalent circuit in Figure 3b was

    calculated as follows:

    L0=4.76 mH, C0=5570 pF

    L1=5.08 H, C1=1840 pF

    L2=2.54 H, C2=920 pF

    For the damping resistance of the high frequency wave

    (R1=R2=k(L/C)1/2), the oscillation waveforms of the potential

    to the ground inside the winding were observed when the

    impulse waveform (0.24/50 s) was applied to the model

    winding and the value k was determined so that the

    damping rate of the high frequency oscillation component

    coincided with the results of the analysis [4]. Meanwhile, the

    impulse waveform of 0.24/50 s was used because the rising

    frequency is approximately 1 MHz and this frequency

    corresponds to the aim of present study, which develops the

    circuit model in the high frequency range. Consequently, the

    value was determined to be k=10, which led to R1=R2=526 .

    Figure 10 represents the analysis results of the

    impedance frequency characteristics using the equivalent

    circuit with k=10 and the measurement results at the model

    winding. For the analysis, EMTP was used. The results of

    the comparison reveal that both the frequencies and values

    of the impedance coincide well at the first, parallel

    resonance as well as the second and third in the high

    frequency range. Therefore, it is clarified that k=10 is

    proper according to the frequency characteristics, as is the

    circuit model in Chapter 2. A low level parallel resonance

    can be observed at the series resonance point at around 700

    kHz. This is considered attributable to the influence of the

    stray capacitance of the model winding to the tank, which isnot taken into consideration in the circuit model in Figure

    3b.

    Also in the case of the ten section model winding, the

    analysis results with k=10 were compared with the

    measurement results for the impedance frequency

    characteristics. The analysis model consisted of five of the

    models for two sections (Figure 3b) serially connected. In this

    analysis model, the inductances in the low frequency range

    were based on the calculation of self and mutual inductances

    for five coils with two sections, with their values as given in

    Table 1. Figure 11 shows the comparison results. Similarly to

    the results for two sections, analysis using the equivalent

    circuit was almost able to adequately express the resonance

    points within the high frequency range. Meanwhile, a little

    deviation was seen in the frequency range exceeding several

    MHz. This is considered attributable to the fact that the circuit

    model was constructed to simulate resonance frequencies up

    to the second order. Also, the effect of the measurement lead

    inductance was presumable.

    Figure 8. Overview of the two-section model winding.

    Figure 9. Overview of the ten-section model winding.

    100

    101

    102

    103

    104

    105

    103

    104

    105 106 107

    Frequency (Hz)

    Impedance()

    Calculation resultsMeasurement results

    Figure 10. Comparison in the impedance frequency characteristics between

    the analysis results using the circuit model and the measurement results of the

    model winding (two-section model).

  • 7/31/2019 High Frequency Model on an Transformers

    6/12

    546 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Application

    Table 2 summarizes the parallel and series resonance

    frequencies of the two- and ten-section winding models

    obtained from Figures 10 and 11. The fundamental resonance

    frequency for ten sections is about 15 kHz, which is half that

    for two sections, or about 30 kHz. This is considered

    attributable to the fact that the inductance L is about 20 times

    and the capacitance C about a fifth of the time for ten sections

    compared with two sections, which leads to LC being about

    four times (or 1/(LC)1/2=1/2). Conversely, there is no

    significant difference between the parallel and series

    resonance frequencies. Following detailed comparisonbetween the analysis values and the actual measurement

    values, it emerges that they coincide relatively well for both

    the fundamental resonance frequency and those in the high

    frequency range.

    3.3 RESPONSE CHARACTERISTICS WITHIN THEWINDING OF TEN SECTION WINDING MODEL TO

    IMPULSE VOLTAGE

    To investigate the potential distribution in the winding in

    response to the high frequency surges, the voltage response

    characteristics against a steep front voltage in various

    locations in the winding were obtained using the ten-section

    winding model. The applied voltage waveforms used included

    a standard lightning impulse waveform (1.2/50 s) and step

    waveforms (wavefront duration: 240 ns, 64 ns, and 32 ns)

    with a steeper wavefront. Measurement was conducted using

    the terminals (1 to 6, and E) displayed in Figure 12 for the

    turn-to-turn voltage (1-2) and the section-to-section voltage

    (1-3, 3-4, 4-5, 5-6, 6-E).

    Turn-to-turn and section-to-section voltages measured

    under the above conditions are normalized with respect to the

    applied voltage (ratio to the peak values: measured

    voltage/applied voltage 100 (%)) and summarized in Table 3.

    Figure 13 shows the turn-to-turn (1-2) and section-to-section

    (1-3) voltage at the terminal where the voltage is applied with

    the wavefront duration as a parameter. Figure 14 indicates the

    relationship of the location in the section-to-section direction

    with the voltage generated. According to the figures and table,

    the turn-to-turn and section-to-section voltages at the terminal

    where the voltage is applied intensively increase when the

    wavefront duration of the applied voltage is less than 0.1 s. It

    also emerges that, if the wavefront duration is 1.2 s or 240 ns,

    the section-to-section voltage is almost constant regardless of

    location. Conversely, if the wavefront duration is 64 ns or 32ns, the section-to-section voltage increases; not only at the

    terminal where the voltage is applied but also at the earth

    terminal. Based on these findings, it was confirmed that

    the potential distribution in the winding is not linear in the high

    L0_1 L0_2 L0_3 L0_4 L0_5

    L0_1 4.76

    L0_2 4.21 4.76

    L0_3 3.66 4.21 4.76

    L0_4 3.18 3.66 4.21 4.76

    L0_5 2.78 3.18 3.66 4.21 4.76

    Table 1. Matrix of inductances (self and mutual inductances) in the low

    frequency range of the analysis model winding; Unit: mH.

    Figure 11. Comparison in the impedance frequency characteristics between

    the analysis results using the circuit model and the measurement results of the

    model winding (ten-section model).

    Parallel resonancefrequency

    f0 - f1 - f2

    Series resonancefrequency

    - f1' - f2' -

    Two sections30.9 kHz 708 kHz 1.65 MHz 2.38 MHz 3.31 MHz

    30.1 kHz 618 kHz 1.83 MHz 2.46 MHz 3.53 MHz

    Ten sections14.9 kHz 708 kHz 1.53 MHz 2.38 MHz 2.97 MHz

    13.5 kHz 795 kHz 1.31 MHz 2.48 MHz 3.24 MHz

    Table 2. Comparison of the parallel and series resonance frequencies of the

    two- and ten-section winding models (Upper row: Analysis results; Lower

    row: Measurement results).

    Frequency (Hz)

    Impedance()

    101

    102

    103 104

    105

    103

    104

    105

    106

    102 106 107

    Calculation resultsMeasurement results

    Figure 12. Locations of the connection of lead wires for measurement of the

    voltage of the winding model with ten sections.

    Wavefront duration of theapplied voltage

    1.2 s 240 ns 64 ns 32 ns

    Turn-to-turn voltage 1-2 9.85 10.4 19.6 34.4

    Section-to-sectionvoltage

    1-318.9

    (20.6)20.1

    (21.8)27.8 34.5

    3-420.5

    (20.2)21.1

    (20.5)23.4 27.0

    4-522.2

    (19.9)24.4

    (20.1)28.2 30.7

    5-620.5

    (19.8)24.0

    (20.2)23.6 25.4

    6-E18.9

    (19.7)27.1

    (20.3)35.7 57.7

    Table 3. Measurement results of the potential distribution of the ten-section

    winding model represented by % of the applied voltage (Calculation results

    for wavefront duration of 1.2 s and 240 ns are shown in parentheses).

    1

    2

    3

    4

    5

    6

    Impulse voltage

    E

  • 7/31/2019 High Frequency Model on an Transformers

    7/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 547

    frequency range as described in Clause 2.1.2. Consequently,

    in order to analyze overvoltages generated in the transformer

    by steep-front lightning surges, it will be necessary to develop

    a circuit model capable of simulation up to a high frequency

    range of several MHz. Meanwhile, the calculation results for

    wavefront duration of 1.2 s and 240 ns using the circuit

    model of Figure 3b were also shown in Table 3. Although a

    little deviation was seen at the earth terminal side, when

    comparison was made between the measurement and

    calculation results, they agreed generally well. The deviation

    is considered attributable to the influences of the simulated

    method of the capacitance to the tank under the calculation

    and the inductance of the lead wire under the measurement.

    4 CIRCUITMODELFOR500KVOIL-IMMERSEDPOWERTRANSFORMER

    4.1 DEVELOPMENT OF CIRCUIT MODEL

    Figure 15 illustrates a circuit model for a 500 kV oil-

    immersed power transformer developed based on an

    assumption that it is a core type transformer with a high-

    voltage winding comprising interleaved disk windings and its

    medium-voltage winding and tertiary winding comprising

    continuous disk windings, respectively. Partial models, each

    with two sections, are produced using the method in Clause

    2.1 for an interleaved disk winding and that in Clause 2.2 for a

    continuous disk winding and the whole model is produced

    with a combination of both. The figure is simplified, with each

    of the one-stage LC parallel circuits of the high-voltage

    winding (interleaved disk winding) actually replaced with a

    three-stage LC parallel circuit in Figure 3b. In addition, whilethe inductance for the low frequency waves is omitted in the

    figure, it is actually expressed by the inductance matrix,

    including the winding-to-winding mutual inductance. The

    winding-to-winding electrostatic coupling and the earth

    capacity are also provided.

    4.2 IMPEDANCE FREQUENCY CHARACTERISTICS

    Figure 16 demonstrates the impedance frequency

    characteristics for one phase seen from the high-voltageterminal for the circuit model illustrated in Figure 15;

    developed by assuming a 500 kV core type transformer. The

    characteristics are based on circumstances whereby the

    medium-voltage and tertiary windings are grounded, and the

    damping resistance of the three-stage LC parallel circuit is

    calculated by k=10. The following characteristics are observed

    from the figure:

    (1) The fundamental resonance frequency f0 is 6.2 kHz.

    (2) The impedance at f0 or less exhibits inductivity.

    Figure 13. Relationship of the wavefront duration of the applied voltage with

    the turn-to-turn (1-2) and section-to-section (1-3) voltage at the terminal

    where the voltage is applied.

    0

    10

    20

    30

    40

    0.01 0.1 1 10

    Turn-to-turn voltage: 1-2

    Section-to-section voltage: 1-3

    Wavefront duration (s)

    Voltagegenerated(%)

    Figure 14. Relationship of the location in the section-to-section direction with

    the section-to-section voltage.

    0

    10

    20

    30

    40

    50

    60

    0 2 4 6 8 10

    1.2 s 240 ns

    64 ns 32 ns

    Location in the section-to-section direction

    Voltagegenerated(%

    )

    Figure 15. Circuit model of 500 kV power transformer.

    Neutralpoint

    Core

    Tank

    Side leg

    High-voltageterminal

    Medium-voltageterminal

    High-voltagewinding

    Medium-voltagewindingTertiary

    winding

  • 7/31/2019 High Frequency Model on an Transformers

    8/12

    548 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Application(3) There are four resonance points above f0 between 5

    kHz and 50 kHz, and capacitive impedance is exhibited

    at higher frequencies. At f=100 kHz, the capacitance is

    C=4080 pF.

    (4) In the high frequency range of f=300 kHz or more,

    there are three parallel resonance and series resonance

    frequency points, respectively.

    (5)

    In the high frequency range of f=2 MHz or more, thecapacitance is about 1500 pF.

    The earth capacitance of the high-voltage winding (sum of

    the capacitance to the medium-voltage winding and the

    capacitance to the tank) is 10410 pF.

    As mentioned above, the analysis results of the transformer

    model in Figure 15 correlate well to the characteristics of the

    actual measurement results in Figures 10 and 11 in that

    several resonance points emerge in the high frequency range

    of 500 kHz or more and the capacitance in the MHz range is

    smaller than that in the 100 kHz range.

    5 LIGHTNINGSURGEANALYSISOF500KV

    SUBSTATION

    A lightning surge analysis is performed using the model

    proposed in the present study (hereinafter the high frequency

    model) and various others, including conventional, to

    investigate the influence on the results.

    5.1 SUBSTATION CIRCUIT TO BE ANALYZED ANDVARIOUS CONDITIONS

    With reference to [9], the substation circuit to be analyzed

    was determined as the three-phase-in-one-tank GIS substation

    in the 500 kV system sketched in Figure 17. The main

    analysis conditions are listed as follows. The substation

    simulation method in (4) pertains to the content of the present

    study:

    (1) Lightning stroke conditions

    Lightning stroke current: 150 kA, 1/70 s ramp wave

    Point struck by lightning: Top of the first tower

    ac superposition: Crest value in reverse polarity

    (2) Power transmission facilities

    Transmission line: Multi-phase transmission line

    simulation (J. Marti model)

    Tower: Four-section tower

    (3) Substation facilities

    Circuit conditions: Consisting of two banks with four lines

    led in; One bank is in operation with one line led in (Figure

    17)

    Three-phase GIS: Multi phase simulation (K. C. Lee

    model)

    Surge arrester: 870 kV (10 kA)Figure 16. Impedance frequency characteristics of the circuit model of 500

    kV power transformer.

    3 3

    3 5.5 3 5.53 333 33 1.5 31.5 1.531.5 1.531.55.5

    G2-7R G2-7S G2-7T

    BA-3 BA-2 BA-1

    BU-1

    BU-2

    BU-3

    BU-4

    BU-5

    BU-6

    BU-7 BU-8 BU-9 BU-10 BU-11

    BU-12

    BU-13 BU-14

    BU-15

    BU-16 BU-17

    BU-18 BU-19

    G3-7R G3-7S G3-7T

    2.5

    2.5

    2.5

    2.52.52.52.52.52.52.52.52.5

    BU-PDTBU-PDSBU-PDR

    PD200pF

    PD200pF

    PD200pF

    T1-7R T1-7S T1-7T B2-7R

    G1-1T

    G1-2T

    G1-LAT

    G1-8T

    G1-3TG1-4T

    G1-5T

    G1-6TG1-7TG1-7SG1-7R

    G1-1SG1-1R

    B1-7R B1-7S B1-7T

    B g200pF

    PD200pF

    B1-1R B1-1S

    B1-6T

    B1-5T

    B1-8TB1-4T

    B1-3T

    B1-2T

    B1-1T B1-LAT

    60

    3.7

    7.8

    1.5

    2.5

    5

    1.5

    6.5

    7.8

    4.7

    1.53

    0

    B2-7S B2-7T

    Transmission line

    Transformer (Simulated by the high-frequency model or the lumped C)

    Surge arrester

    The numbers indicate length.

    1 GIS

    3 GIS

    Figure 17. Substation analysis circuit.

    Impedance()

    101

    102

    105

    103

    104

    Frequency (Hz)

    103102 105 106 107104

  • 7/31/2019 High Frequency Model on an Transformers

    9/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 549

    (4) Transformer simulation

    Assuming a single-phase three-coil transformer typical for

    a 500 kV class, the following five cases were considered as

    simulation methods of a transformer:

    Case 1: High frequency model (Figure 15)

    Case 2: Lumped capacitance C=10730 pF (Windings earth

    capacitance 10410 pF + Bushing capacitance 320 pF)For the windings earth capacitance, the collective

    value of three coils is used.

    Case 3: Lumped capacitance C=3790 pF (Windings earth

    capacitance 10410 pF/3 + Bushing capacitance 320 pF),

    Conventional method

    For the windings earth capacitance, the value of one

    coil is used. Here, the collective windings earth

    capacitance for three coils is divided by three to obtain

    the equivalent capacitance for a single coil, assuming

    the potential of the winding to be linearly distributed.

    Case 4: Lumped capacitance C=4080 pF (Calculated based

    on the impedance of the high frequency model at f=100

    kHz)

    Case 5: Lumped capacitance C=1500 pF (Calculated based

    on the impedance of the high frequency model at f=2 MHz

    or more)

    5.2 ANALYSIS RESULTS

    Figure 18 summarizes the lightning surge waveforms at the

    transformer terminal corresponding to the above five cases of

    transformer simulation. The peak value of the generated

    voltage and dV/dt differ according to the difference in thesimulation method. Figure 19 highlights the front rising for

    Cases 1 and 3 with an enlarged time axis. For the analysis

    waveform in each case, the maximum potential gradient at the

    front rising of voltage is obtained as dV/dt and summarized in

    Table 4 together with the peak voltage value.

    In the case where the high frequency model (Case 1) is

    connected, the peak voltage value decreases to 84% but the

    voltage build-up rate increases up to 128% compared with that

    in which the lumped capacitance equivalent to 1/3 of the earth

    capacitance is connected in the conventional simulation

    method (Case 3).

    For simulation by the lumped capacitance, the voltage

    build-up rate increases in inverse proportion to capacitance;however, the peak voltage value does not monotonously

    increase or decrease with respect to the capacitance. Figure 20

    evaluates the relationship between the lumped capacitance

    value simulating the transformer and the peak voltage value

    generated. As the capacitance falls, the peak voltage reaches a

    local maximum value at 3000 pF, followed by a local

    minimum value at 1200 pF, subsequently peaking at 300 pF.

    In the surge waveform, with 1200 pF as a boundary, the peak

    value emerges in the first and second peaks with lower and

    higher capacitance respectively.

    (a) Case 1: High frequency model

    (d) Case 4: Lumped capacitance C=4080 pF

    (e) Case 5: Lumped capacitance C=1500 pF

    (b) Case 2: Lumped capacitance C=10730 pF

    (c) Case 3: Lumped capacitance C=3790 pF

    Figure 18. Lightning surge analysis waveform at the transformer terminal

    using each of the transformer simulation methods.

    Time (s)

    Voltage(kV)

    Time (s)

    Voltage(kV)

    Time (s)

    Voltage(kV)

    Time (s)

    Voltage(kV)

    Time (s)

    Voltage(kV)

  • 7/31/2019 High Frequency Model on an Transformers

    10/12

    550 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Application

    The frequency of the oscillation component that emerges at

    the front rising of the voltage waveform at the transformer

    terminal is determined by the oscillation of the capacitance of

    the GIS from the location of the surge arrester to the

    transformer and the transformer itself. Consequently, the

    oscillation frequency decreases as the value of the capacitance

    simulating the transformer increases. This frequency ranges

    from several hundred kHz to about 1 MHz. Since multiple

    reflections of surges elsewhere in the substation possibly

    cause oscillations in this frequency range, the peak value of

    the voltage waveform at the transformer terminal is

    considered to be influenced by the mutual interference with

    such oscillations.

    6 EVALUATIONOF

    LIGHTNING

    SURGE

    ANALYSISRESULTS

    A study is conducted on the influence of the transformer

    model and the configuration of the substation on the lightning

    surge analysis results. Furthermore, each overvoltage

    waveform is converted into an equivalent standard lightning

    impulse waveform using the waveform evaluation method [5]

    to perform an evaluation from the perspective of the severity

    for insulation.

    6.1 INFLUENCE OF TRANSFORMER MODEL

    As described before, if the high frequency model was used

    as a transformer model for lightning surge analysis, the

    voltage generated at the transformer terminal had a steeperfront rising but a lower peak value compared with when the

    conventional model was used. This difference is due to the

    capacitance charging process inside the transformer and can

    be explained as follows [4]:

    The conventional model is charged exponentially with the

    time constant of the product of the surge impedance of the line

    and the earth capacitance. In contrast, the high frequency model

    behaves in the same manner as the stage zero (parallel circuit of

    L0 and C0 in Figure 3b) that corresponds to the conventional

    model; however, it oscillates at about 700 kHz in the first stage

    (parallel circuit of L1 and C1 in Figure 3b) and at about 1.4 MHz

    in the second stage (parallel circuit of L2 and C2 in Figure 3b) of

    the high frequency. Consequently, the high frequency elemententers the discharge phase even when the stage zero is being

    charged, and the crest value is reduced. Since a small

    capacitance corresponding to the high frequency element is

    initially charged, the rising is sharp. This high frequency model

    was developed based on measurement, as described before,

    hence the surge waveform is influenced due to the fact that the

    capacitance seen from the transformer terminal in the high

    frequency range is small. Consequently, the analysis result in

    Case 1 is considered to be close to the actual lightning surge.

    6.2 APPLICATION OF WAVEFORM EVALUATIONMETHOD

    The authors have developed a method to convert anovervoltage waveform (non-standard lightning impulse

    waveform) in various lightning surge ranges to the equivalent

    standard lightning impulse waveform (1.2/50 s) in terms of

    insulation in the previous study [5], the details of which are

    not described in the present paper. The results of the

    application of this waveform evaluation method to the

    lightning surge analysis waveform in the present study are

    summarized in Table 5. Here, the result obtained by dividing

    the peak value of the analysis waveform by the conversion

    ratio is the equivalent standard lightning impulse voltage.

    Time (s)

    Voltage(kV)

    (a) Case 1: High frequency model

    CaseTransformer simulation

    methodPeak voltage

    (kV)Voltage build-up rate

    dV/dt (kV/s)

    1 High frequency model 968 1474

    2 Lumped C (10730 pF) 910 562

    3 Lumped C (3790 pF) 1149 1156

    4 Lumped C (4080 pF) 1133 1127

    5 Lumped C (1500 pF) 1097 1950

    Table 4. Peak voltages and voltage build-up rates of the lightning surge

    analysis waveforms.

    Figure 19. Front rising of the lightning surge analysis waveforms.

    Figure 20. Relationship between the capacitance simulating the transformer

    and the peak value of the lightning surge analysis waveform.

    Time (s)

    Voltage(kV)

    (b) Case 3: Lumped capacitance C=3790 pF

    Capacitance (pF)

    Peakvalueofthegeneratedvoltage(kV)

    Maximum value at

    the second peak

    Maximum value

    at the first peak

  • 7/31/2019 High Frequency Model on an Transformers

    11/12

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 2; April 2011 551

    First, following comparison of the peak values of the

    analysis waveforms, the value in Case 3 is evaluated to be

    about 19% higher than Case 1, and the peak values of Cases 4

    and 5, where the capacitance is small, are also computed to be

    relatively high. Conversely, the values after waveform

    evaluation differ relatively little between transformer models.

    This is because, while the peak value is large, for example, in

    the waveform in Case 3, the conversion ratio to the standard

    lightning waveform is also large since the waveform isoscillatory. As in this case, due to the application of the

    waveform evaluation method and comparison from the

    perspective of the insulation severity, the difference was

    lessened. However, the value in Case 3, where the

    conventional simulation method is applied, is still evaluated at

    about 7% higher and hence as relatively severer (on the safety

    side), which will mean, conversely, that some potentiality

    remains for rationalization. To evaluate the overvoltage value

    more accurately within the frequency range handled in the

    lightning surge evaluation, a model must be developed in

    which the high frequency characteristics are taken into

    consideration in accordance with the winding structure.

    6.3 INFLUENCE OF SUBSTATION CIRCUIT

    As indicated in Figure 17, the substation circuit used in the

    present lightning surge analysis includes GIS with 30 m long

    from the surge arrester location to the transformer terminal.

    The 500 kV three-phase bus bar spreads 35 m on the right

    hand side of the BU-2, BU-4, and BU-6 nodes connected to

    the G1 lines, from which lightning surges are assumed to

    occur. Consequently, to clarify the influence of the lightning

    surge waves, which have intruded from the G1 lines, branched

    into the bus bar and reflected at its terminal on the voltage

    waveform at the transformer terminal, the lightning surge

    analysis was performed on the condition that the bus bar was

    separated at the BU-6 node in the circuit in Figure 17.

    The results when Cases 1 and 3 are used as the transformer

    simulation methods are compared in Figures 21a and 21b,

    respectively. The peak values of the generated voltage are

    1117 kV and 1270 kV, increases of 15% and 11%,

    respectively, compared with the results in Figure 18. As for

    the shape of the waveforms, the first peak is higher, which

    reveals that the phenomenon of the higher second peak as

    indicated in Figure 18 is due to the influence of the waves

    branched into and reflected at the bus bar. As in this case, if

    the transformer is far from the surge arrester location, the

    voltage generated at the transformer terminal exceeds the

    surge arrester residual voltage based on distance, and the

    voltage build-up rate is significantly influenced by the

    substation configuration.

    Attention needs to be paid when studying the lightning

    surge waveform at the transformer terminal because the

    waveform not only influences the development of the

    transformer model but is also dependent on the substation

    configuration.

    Following the application of the waveform evaluation to

    Figure 21, the voltages were 1013 kV and 1017 kV in Cases 1

    and 3, respectively, meaning minimal difference from the

    perspective of insulation severity.

    7 SUMMARY

    A relatively simplified circuit model was developed; capable

    of simulating the winding at frequencies up to the high

    frequency range of several MHz for a 500 kV oil-immersed

    transformer, and its validity was evaluated by comparison with

    the measurement results of the model winding. In addition,analysis of lightning surges to a 500 kV substation was

    performed using the new model to study its influence on the

    lightning surges generated at the transformer terminal in

    comparison with the conventional simulation method.

    The examination results are summarized as follows:

    (1) For the interleaved disk winding of an oil-immersed

    transformer, a simplified model with three serially connected

    LC parallel circuits can adequately simulate the impedance

    characteristics of the winding at frequencies up to the high

    frequency range.

    CasePeak voltage

    (Relative value on thebasis of case 1)

    Conversion ratioEquivalent standard-LI(Relative value on the

    basis of case 1)

    1 968 kV (1.00) 1.04 931 kV (1.00)

    2 910 kV (0.94) 0.98 929 kV (1.00)

    3 1149 kV (1.19) 1.16 993 kV (1.07)

    4 1133 kV (1.17) 1.15 986 kV (1.06)

    5 1097 kV (1.13) 1.14 959 kV (1.03)

    Table 5. Peak value of the lightning surge analysis waveform and equivalent

    standard lightning impulse through the application of the waveform

    evaluation method.

    Figure 21. Influence of the substation circuit.

    (a) Case 1: High frequency model

    (b) Case 3: Lumped capacitance C=3790 pF

    Time (s)

    Voltage(kV)

    Time (s)

    Voltage(kV)

  • 7/31/2019 High Frequency Model on an Transformers

    12/12

    552 S. Okabe et al.: Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Application(2) In the lightning surge analysis at a three-phase-in-one-

    tank GIS substation in a 500 kV system, if the high frequency

    model is connected, the peak voltage value decreases while

    the voltage build-up rate increases compared with the

    conventional simulation model. This phenomenon can be

    explained with the capacitance charging process inside the

    transformer taken into consideration. This is based on the

    transformer simulation method and considered generally

    applicable regardless of the substation configuration.

    (3) When the lightning surge analysis waveform by each

    transformer model is converted into the equivalent standard

    lightning impulse waveform and analyzed, the difference in

    the peak value decreases from that in the original waveform.

    This is because, if a transformer is simulated by a lumped

    capacitance, the conversion ratio to the standard lightning

    impulse waveform increases with the increase of the

    oscillatory component even though the waveform becomes

    more oscillatory and the peak value increases.

    (4) In the lightning surge analysis, the results obtained

    differ due to the change in conditions, such as branched waves

    and reflections, depending on the substation circuit including

    the bus bar length and connected lines. The waveform shape

    and the crest value vary due to the interference of these

    conditions with the transformer simulation method. Therefore,

    to accurately obtain the lightning surge waveform at the

    transformer terminal, it is effective to use a transformer

    simulation method that takes the characteristics in the high

    frequency range into consideration.

    The high frequency model developed in the present study is

    expected to be applied, not only to the lightning surge analysis

    but also widely to others such as that of the propagation

    characteristics of relatively high frequency partial discharge

    signals generated inside the transformer.

    REFERENCES

    [1] IEC60071-4, Insulation co-ordination Part 4: Computational guide to

    insulation co-ordination and modeling of electrical networks, 2004.

    [2] T. Terahishi, M. Ikeda, M. Honda, and T. Yanari, Local Voltage

    Oscillation in Interleaved Transformer Windigns, IEEE, Trans. Power

    Apparatus Syst., Vol. 100, pp. 873-881, 1981.

    [3] K. Cornick, B. Filliat, C. Kieny, and W. Muller, Distribution of Very

    Fast Transient Overvoltages in Transformer Windings, CIGRE, Report

    12-204, 1992.

    [4] S. Okabe, M. Koto, T. Teranishi, M. Ishikawa, and T. Saida, An

    Electric Model of Gas-Insulated Shunt Reactor and Analysis of Re-

    Ignition Surge Voltages, IEEE, Trans. Power Delivery, Vol. 14, pp.

    378-386, 1999.

    [5] S. Okabe and J. Takami, Evaluation of Breakdown Characteristics of

    Oil-immersed Transformers under Non-standard Lightning ImpulseWaveforms - Method for Converting Non-standard Lightning Impulse

    Waveforms into Standard Lightning Impulse Waveforms, IEEE, Trans.

    Dielectr. Electr. Insul., Vol. 15, pp. 1288-1296, 2008.

    [6] Y. Kawaguchi, Calculation of Circuit Constants for the Computation of

    Internal Oscillating Voltage in Transformer Windings, IEEJ Trans., Vol.

    89, pp. 115-124, 1969.

    [7] A. Pedersen, On the Response of Interleaved Transformer Windings to

    Surge Voltages, IEEE, Trans. Power Apparatus Syst. Vol. 66, pp. 349-

    356, 1963.

    [8] A. Schleich, Behaviour of Partially Interleaved Transformer Winding

    Subject to Impulse Voltages, Bulletin Oerikon, No.389/390, 41, 1958.

    [9] Central Research Institute of Electric Power Industry Report, The

    Suggestion of the Useful way to Analysis of Lightning Overvoltages and

    Application, T90068, 1991.

    Shigemitsu Okabe (M98) received B. Eng., M.Eng.and Dr. degrees in electrical engineering from the

    University of Tokyo in 1981, 1983 and 1986,

    respectively. He has been with Tokyo Electric Power

    Company since 1986, and presently is a group

    manager of the High Voltage & Insulation Group at

    the R & D center. He was a visiting scientist at the

    Technical University of Munich in 1992. He has been

    a guest professor at the Doshisha University since

    2005, at the Nagoya University since 2006, and a

    visiting lecturer at the Tokyo University. He works as a secretary/member at

    several WG/MT in CIGRE and IEC. He is an Associate Editor of the IEEE

    Dielectrics and Electrical Insulation.

    Masanori Koto received the B.Eng., M.Eng. degrees

    in electrical engineering from Kanazawa University in1987 and 1989. He has been with the Tokyo Electric

    Power Company since 1989, and was engaged in

    diagnosing deterioration in oil-immersed transformers

    when attached to the High Voltage & Insulation

    Group. Currently, He is a Senior Engineer of the

    Substation Engineering Group of Transmission

    Department.

    Genyo Ueta received the B.S. and M.S. degrees from

    Doshisha University in 2000 and 2002, respectively.

    He joined Tokyo Electric Power Company in 2002.

    Currently, He is a researcher at the High Voltage &

    Insulation Group of R & D Center and mainly

    engaged in research on insulation characteristics of

    GIS.

    Toshiyuki Saida received the B.S. and M.S. degrees

    in electrical engineering from Nagoya University in

    1989 and 1991, respectively. In 1991, he joined

    Toshiba Corporation, and has been engaged in

    substation engineering in the Power transmission &

    Substation Department.

    Shin Yamada received the B.Eng. and M.Eng.

    degrees in electrical engineering from Waseda

    University in 1988 and 1990, respectively. In 1990,

    he joined Power Industrial and Systems Research and

    Development Center of Toshiba Corporation. In 1997,

    he changed to the Transformer Department at

    Hamakawasaki Works, and has been engaged in the

    designing of power transformers.