hawkeye 221transductor de alta corriente instalacion

Upload: jossi-perez-a

Post on 14-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Hawkeye 221Transductor de Alta Corriente Instalacion

    1/1

    ! CAUTION !

    Th i s p rodu ct i s no t i n t end ed f o r l i f e o r sa fe t y

    app l i c a t i o ns

    Ins ta l l i ng senso rs in an ene rg i zed mo to r con t ro l

    cen te r o r on any ene rg i zed cond uc to r can be haza rd - ous .

    Severe injur y or d eath can result fr om elect rical sho ck

    durin g cont act w ith h igh voltage cond uctors or related

    equipm ent. Disconn ect and lock-out al l pow er sources

    durin g in stal lat io n. Ap pl ication s show n are sugg ested

    mean s of inst all ing sensors, bu t it is th e respo nsibil i t y of

    th e instal ler to ensure th at t he instal lat io n is in compli-

    ance w ith al l nation al and local codes. Instal lat io n shou ld

    be att empt ed only by individuals fam il iar wit h codes,

    stand ards, and p roper safety p rocedures fo r h igh-voltage

    inst allatio ns. Do not rely on st atu s ind icat ion s of device

    exclusively to determ ine of pow er is present in conductor.

    1. Ensure pow er conductor to be monitored islocked out a nd disconne cted from t he pow er source!

    2. At ta ch sensor to conductor to be monitored:

    CALIBRATION

    SPECIFICATIONS

    Installation Instructions

    HAW KEYE 2 2 1Loop Powered Split-CoreAnalog Current Sensor

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8

    SENSOR

    OUTPUT

    4 ma

    ma20

    INSTALLATION

    Install on LINE side fo r w hen using w ith va riablefrequency drives.

    SPAN adjustment is used to set the full-scale of thesensor to ma tch to load b eing monitored. It ma y be setto correlat e the m aximum 20 mA out put to load s from100 TO 300 A. While opera ting ma ximum loa d, me a -

    sure sensor output current, adjust SPAN, such that thesensor out put current correlate s to 20 mA (or less, ifdesired, w hen m onitoring f or overcurrent).

    NOTE: On low a mp era g e a pplicat ion s (i.e., x < 2A) th emonitored conductor may be looped through t hesensor multiple times to increase measured current.Monitored current = init ially measured current Xnumber of w raps.

    0 A CURRENT 100A to 300 A(Span Adjust)

    Monitored Amperage Ratings...100 to 300 A continuous(in-rush prot ected )

    Sensor Supply Volta g e..................................10 t o 30 VDCSupply Current.................................................30 mA maxAccuracy........................................................2%, full scaleSpan Adjustment............................100 to 300A, full scaleIsolation..........................................................600 VAC rmsTem pera tu re Rang e...... ............ ............. ...........-15 to 85CHumidity Ra ng e............................0-95% no n-cond ensing

    Litera tu re re f. # L10179-597

    Zero

    Out

    +

    4-20 mA IN

    (Return)

    V+ (Com m)

    Sinking Panel (+ Common)

    Span

    Haw keye 221

    + 4-20 mA OUT

    (Comm)ZeroOut

    Span

    Haw keye 221

    Sourcing Panel ( Common)

    24 VDC

    -

    Out

    +

    + 1 to 5 V IN

    (Comm)-

    Span

    Haw keye-221

    250

    Zero

    External PowerVoltage Input

    COMM

    24 VDC

    OUT SPANZERO

    4 - 20

    +

    +

    External Power

    10831 S.W. CASCADE BLVD.PORTLAND, OREGON 97223

    (503) 598-4564 FAX (503) 598-46641-800-354-8556

    VERIS INDUSTRIES, INC.

    http:/ / www.veris.com email:[email protected]