harmonic solutions in electrical systems

31
Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Upload: others

Post on 26-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Harmonic Solutions in Electrical Systems

Harmonic Solutions in Electrical Systems

Raed Odeh – Application Specialist - Power Quality & Electrical Distribution

Page 2: Harmonic Solutions in Electrical Systems

2

Agenda

●I. Harmonic Basics

●II.Harmonic Mitigation Solutions

●III.Case Study

Page 3: Harmonic Solutions in Electrical Systems

3

Harmonic Basics

● Linear Loads

• Resistive heaters

• Lights

• Induction motors

● Non-linear Loads

• House hold appliances ( TVs, Microwave, etc.)

• Induction heaters & welders

• Lighting equipment with ballasts

• Variable Speed Drives

• Office equipment (PCs, Photocopiers, fax,etc.)

U

I

U

I

Page 4: Harmonic Solutions in Electrical Systems

4

Harmonic Basics

Non sinusoidal signal

3rd harmonic

5th harmonic

7th harmonic

9th harmonic

RMS value

Peak value

RMS value

Fundamental or 1st harmonic

Page 5: Harmonic Solutions in Electrical Systems

5

Harmonic Basics

Sinewave of a

specific

frequency supplied by

the utility (a “clean”

sinewave):

f(x) = sin(x)

…plus a “5th”

Harmonic

Sinewave: f(x) =

sin(5x)

5

…results in a

harmonic rich, non-

linear wave shape: f(x) = sin(x) +

sin(5x)

5

Page 6: Harmonic Solutions in Electrical Systems

6

Harmonic Basics

Line 1

Line 2

Line 3

D1 D2 D3

D4 D5 D6

LO

AD

Page 7: Harmonic Solutions in Electrical Systems

7

Harmonic Basics

●Why the concern?

●Current distortion ●Added heating = reduced capacity

●Equipment failures

– Transformers

– Conductors and cables

– Nuisance tripping of electronic circuit breakers (thermal

overload)

●Heating proportional to harmonic order in

cables

●Squared effect on transformers & motors

Loads

Ih

hhh ZIV

Page 8: Harmonic Solutions in Electrical Systems

8

Harmonic Basics

Page 9: Harmonic Solutions in Electrical Systems

9

Harmonic Basics

Page 10: Harmonic Solutions in Electrical Systems

10

Harmonic Basics

Page 11: Harmonic Solutions in Electrical Systems

11

Harmonic Basics

●Why the concern?

●Voltage distortion ●Interference with other electronic loads

– Malfunctions to failure

●Induces harmonic currents in linear loads

– i.e. AC motor winding over heating &

bearing failures

Loads

Ih

hhh ZIV

AC Motors

Page 12: Harmonic Solutions in Electrical Systems

12

Harmonic Basics

Vh = Harmonic voltage

Ih = Harmonic current

Zsh = Source impedance for

harmonic current

Zch = Cable impedance for

harmonic current

Vh = Ih * (Zsh + Zch)

Load Vs

Zsh Zch Ih

Vh

Page 13: Harmonic Solutions in Electrical Systems

13

Harmonic Basics

Total RMS Signal

=

Fundamental Signal

Harmonic Signal

+

Page 14: Harmonic Solutions in Electrical Systems

14

Harmonic Basics

●Interaction with PF caps

●PF caps interact with all frequencies

●Overheating of PFC capacitors ●Tripping of PF protection equipment

●Capacitor failures

●Cause resonance ●Shutdown to damage to electronic equipment

Page 15: Harmonic Solutions in Electrical Systems

15

Harmonic Mitigation Solutions

●Every method has its place

●Every method adds complexity

●Added costs

●Added heat losses

●Additional cooling requirements

●Larger footprint – needs more space

●Adds installation complexity

●Additional power cabling

●Current transformers

●Application performance may be impacted

●Too much impedance limits load performance

– di/dt (Di/Dt) defines speed of change of current over time

●Generator interaction difficulties

Page 16: Harmonic Solutions in Electrical Systems

16

Harmonic Mitigation Solutions

●Applied per device (VFD based discussion)

●Reduced harmonic designs

●Passive

●Line reactors/DC bus chokes/isolation transformers

●5th harmonic filters

●Broadband filters

●Multi-pulse transformers/converters

●Active front end (AFE) converter

●System solution

●Active harmonic filter (AHF)

Page 17: Harmonic Solutions in Electrical Systems

17

Harmonic Mitigation Solutions

● Reactors/chokes smooth the current shape

● Reduces the harmonic distortion

Page 18: Harmonic Solutions in Electrical Systems

18

Harmonic Mitigation Solutions

●Consist of a large series reactor

and shunt harmonics traps

● The series reactor reduces the thdi and

isolates the harmonics traps from the

network harmonics.

●The passive filter offer allows the

THDI level to be reduced from 16% to

10%, and down to 5% in combination

with inductance

●Can be used on single or multiple

drives

Passive Filters

Page 19: Harmonic Solutions in Electrical Systems

19

Harmonic Mitigation Solutions

●12-Pulse Transformers

• 11th, 13th, 17th, 19th.

• Current distortion: 10-12% THDI.

• Only available at design stage.

• Requires special transformers.

• Cancellation at primary side.

●18-Pulse Transformers

• 17th, 19th.

• Current distortion: 5-7% THDI.

• Only available at design stage.

• Requires special transformers.

• Cancellation at primary side.

Page 20: Harmonic Solutions in Electrical Systems

20

Harmonic Mitigation Solutions

Delta

Star

6 pulses

rectifier

6 pulses

rectifier

M

Drive

H5 and H7 attenuated

Phase shifted by 30°

12-Pulse Transformers

Page 21: Harmonic Solutions in Electrical Systems

21

Harmonic Mitigation Solutions

H5 , H7,H11 and

H13 attenuated

Phase shifted by +20°

Phase shifted by

-20°

18-Pulse Transformers

Page 22: Harmonic Solutions in Electrical Systems

22

Harmonic Mitigation Solutions

●Active filters

●Cancellation of harmonic currents by currents generated in opposition

0A

Page 23: Harmonic Solutions in Electrical Systems

23

Harmonic Mitigation Solutions

AS off AS on Order % I fund % I fund Fund 100.000% 100.000% 3 0.038% 0.478% 5 31.660% 0.674% 7 11.480% 0.679% 9 0.435% 0.297% 11 7.068% 0.710% 13 4.267% 0.521% 15 0.367% 0.052% 17 3.438% 0.464% 19 2.904% 0.639% 21 0.284% 0.263% 23 2.042% 0.409% 25 2.177% 0.489% 27 0.293% 0.170% 29 1.238% 0.397% 31 1.740% 0.243% 33 0.261% 0.325% 35 0.800% 0.279% 37 1.420% 0.815% 39 0.282% 0.240% 41 0.588% 0.120% 43 1.281% 0.337% 45 0.259% 0.347% 47 0.427% 0.769% 49 1.348% 0.590% % THD(I) 35.28% 2.67%

●Active filters

Source current

At VFD

Terminals

Active Filter

Injection

Page 24: Harmonic Solutions in Electrical Systems

24

THDv% = ?

THDi % = ?

PCC = ?

THDi % = ?

K FACTOR = ?

THDi % = ?

K FACTOR = ?

THDv% = ?

Harmonic Mitigation Solutions

Page 25: Harmonic Solutions in Electrical Systems

25

Harmonic Mitigation Case Study

●Background

• Induction heaters: 300 kw, 500kW,

800kW

• SCR control

• Limited supply

• 1MVAR Capacitor @11kV

● Issues

• High THDv % & THDi%

• Voltage Notching

• Low PF

• Limited supply

• Resonance @11kV

Page 26: Harmonic Solutions in Electrical Systems

26

Harmonic Mitigation Case Study

THDv% = 20%

THDi % = 45%

PCC = 11kV

THDv% = 20%

THDi % = 200%

Page 27: Harmonic Solutions in Electrical Systems

27

Harmonic Mitigation Case Study

Page 28: Harmonic Solutions in Electrical Systems

28

Harmonic Mitigation Case Study

●Solution

• Line reactors (3-5)%

• Active Harmonic Filter “900A”

●Result

• THDv %< 8%

• THDi%<7%

• Voltage Notching: eliminated

• PF =0.98 Lagging

• Resonance @11kV: eliminated

Page 29: Harmonic Solutions in Electrical Systems

29

Harmonic Mitigation Case Study

Page 30: Harmonic Solutions in Electrical Systems

30

Harmonic Mitigation Case Study

AHF eliminates at 11th harmonic order

Page 31: Harmonic Solutions in Electrical Systems

31

Thank you!

Questions?