General Specifications <<Contents>> <<Index>> Integrated Production Control System CENTUM CS 3000 System Overview (Vnet/IP Edition) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 GS 33P01B10-31E GS 33P01B10-31E ©Copyright Sep. 2004 4th Edition Oct. 27, 2006 GENERAL Vnet/IP is a control network with high reliability and quick response and achieves steady response with little delay even under heavy load. Using general-purpose network equipment conforming to IEEE802.3 and UDP/IP standards, it realizes open-based communications. Vnet/IP can connect to a V net system with a V net router. This GS provides the system specifications, system configuration equipment, and network specifications for CENTUM CS 3000 Systems with Vnet/IP. SYSTEM CONFIGURATION F01E.EPS Boundary router PC for builder HIS Human Interface Station Vnet/IP (Subsystem) Enclosed Display Style Console HIS Open Display Style Console HIS APCS Advanced Process Control Station GSGW Generic Subsystem Gateway SIOS System Integration OPC Station Other Vnet/IP domains Remote network Other PCS Other V net domains V net router Vnet/IP domain Bus 1 Bus 2 L3SW Layer 3 switch L3SW Layer 3 switch SNTP Server SENG SCS ProSafe-RS Safety Instrumented System Other system FCS (for FIO) ER bus ESB bus Remote node Local node Figure Example of System Configuration R3

Upload: mervgilby

Post on 02-Oct-2014

126 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: GS33P01B10-31E

GeneralSpecifications

<<Contents>> <<Index>>

Integrated Production ControlSystem CENTUM CS 3000System Overview (Vnet/IP Edition)

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33P01B10-31E

GS 33P01B10-31E©Copyright Sep. 2004

4th Edition Oct. 27, 2006

■ GENERALVnet/IP is a control network with high reliability and quick response and achieves steady response with little delay evenunder heavy load. Using general-purpose network equipment conforming to IEEE802.3 and UDP/IP standards, it realizesopen-based communications. Vnet/IP can connect to a V net system with a V net router. This GS provides the systemspecifications, system configuration equipment, and network specifications for CENTUM CS 3000 Systems with Vnet/IP.

■ SYSTEM CONFIGURATION

F01E.EPS

Boundary router

PC for builder

HIS Human Interface Station

Vnet/IP

(Subsystem)

Enclosed Display Style Console HIS

Open Display Style Console HIS

APCS Advanced Process Control Station

GSGW Generic Subsystem Gateway

SIOS System Integration OPC Station

OtherVnet/IPdomains

Remotenetwork

Other PCS

OtherV net

domains

V net router

Vnet/IP domain

Bus 1

Bus 2

L3SWLayer 3 switch

L3SWLayer 3 switch

SNTP Server SENG

SCS

ProSafe-RSSafety

InstrumentedSystem

Other system

FCS (for FIO)

ER bus

ESB bus

Remote node

Local node

Figure Example of System Configuration

R3

Page 2: GS33P01B10-31E

2

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E Oct. 27, 2006-00

■ SYSTEM COMPONENTS

● Human Interface Station (HIS)An HIS serves as a human interface for operation,monitoring, and engineering. Software packages installedin a general-purpose personal computer (an IBM PC/ATcompatible computer, hereinafter referred to as a general-purpose PC) or in a console HIS, consisting of a general-purpose PC and Open Display Style Console Assembly,implement operation and monitoring functions as well asengineering functions.

Users can install and run operation and monitoringfunctions and/or engineering functions in an HIS asnecessary. For connections to the Vnet/IP, a VI701 ControlBus Interface Card is used.

As for HIS hardware requirements, refer to followingGeneral Specifications:

GS 33Q06B40-31E “Enclosed Display Style ConsoleAssembly”

GS 33Q06B50-31E “Open Display Style ConsoleAssembly”

GS 33Q02C10-31E “Standard Operation and Monitor-ing Function”

GS 33P06B10-31E “Vnet/IP Interface Card”

● Field Control Station (FCS)The FCS performs process control and manages commu-nications with subsystems such as PLCs. Two types offield control stations for Vnet/IP and FIO are available:

AFV10S: Field Control Unit (for Vnet/IP, FIO, rack-mounted)

AFV10D: Duplexed Field Control Unit (for Vnet/IP,FIO, rack-mounted)

By mounting ESB Bus Coupler Module on FCS, local nodecan be connected. By mounting ER Bus Interface MasterModule on FCS or local node, in addition, remote nodecan be connected.

As for FCS hardware requirements, refer to followingGeneral Specifications:

GS 33P06C10-31E “Field Control Unit (for Vnet/IP andFIO)”

GS 33Q06N06-31E “ESB Bus Coupler Module”GS 33Q06Q48-31E “ER Bus Interface Master Module

(for FIO)”GS 33Q06Q10-31E “Node Units (for FIO)”GS 33P06Q01-31E “FIO System Overview (for

AFV10�)”

● Advanced Process Control Station (APCS)An APCS advanced process control station implementscontrol functions with a general-purpose PC connected toa Vnet/IP, aimed at improving advanced control and plantefficiency. For this purpose, install LFS1200 APCS controlfunctions. Use VI701 Control Bus Interface Card forconnection to Vnet/IP. For more details, see APCS ControlFunctions General Specifications (publication GS33Q03M10-31E).

● Generic Subsystem Gateway Package(GSGW)

With a general-purpose PC connected to a Vnet/IP,GSGW packages can collect and set data of various typesof subsystems using an OPC DA server. They can easilycollect and set subsystem data without creating dedicatedcommunications programs.

Install LFS1250 Generic Subsystem Gateway Package.Use VI701 Control Bus Interface Card for connections toVnet/IP. For more details, see publication GS 33Q03P10-31E.

● Safety Instrumented Systems (ProSafe-RS)(*1)

ProSafe-RS has been approved by German safety testlabs TÜV (Technische Überwachungs Verein) as the SIS(Safety Instrumented System) that meets SIL (SafetyIntegrity Levels) 3 established by IEC 61508.

The SCS (Safety Control Station) for ProSafe-RS monitorsthe safety state of plants and performs predeterminedsafety operation according to each request for safetycontrol. The SENG (Safety Engineering PC) performsengineering and maintenance of SCS. Moreover, ProSafe-RS can be integrated with CENTUM CS 3000 R3 andenables operation and monitoring of SCS from HIS.

For details, refer to GS 32S51B10-01E “Safety Instru-mented Systems ProSafe-RS System Overview (Vnet/IPEdition)”.

*1: Supported by R3.08 or later versions

● System Integration OPC Station (SIOS)System Integration OPC Station (SIOS) is a station usedwhen other companies’ PCS (Process Control System) isintegrated to CENTUM CS 3000 system. It providesfunctions to import other companies’ PCS data toCENTUM CS 3000 using OPC (OLE for Process Control)and to have CENTUM CS 3000 receive alarms and eventsoccurred in other companies’ PCS.

LBC2100 System Integration OPC Client Package isinstalled. For connection with Vnet/IP, VI701 (Vnet/IPInterface Card) is used.

As for details, refer to GS 33Q05P10-31E “SystemIntegration OPC Client Package”.

Page 3: GS33P01B10-31E

3<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 33P01B10-31E

● Vnet/IPVnet/IP is IEEE802.3 compliant control bus configured withdual-redundant busses. Each dual-redundant bus isconfigured with a layer 2 switch (*1) with the maximumtransmission speed of 1Gbps and 1000BASE-T cablesand devices in a domain are connected in star connectionor tree connection.

Vnet/IP dual-redundant bus 1 is exclusively used forcontrol communication and bus 2 is used not only forcontrol communication but for open communication by avarious kind of standard protocol based on Ethernet. Bus2 enables data access by Exaopc OPC interface andcommunications based on TCP/IP protocol.

General-purpose, commercially available products areused for network device such as repeaters, cables, layer 2switches and layer 3 switches for Vnet/IP.

In Vnet/IP, IPv4, ClassC private address is used as IPaddress for communication. (Some ClassB privateaddress is also used.)

*1: Layer 2 switch is a switching HUB with a bridgefunction and it does not send data to terminals otherthan destination. Using layer 2 switch reduces bustraffic.

● Layer 3 SwitchLayer 3 switch is a network device to connect Vnet/IPdomains. It has path control by IP address and a routingfunction to relay communication frame in two domainswhen necessary. Use layer 3 switch which relayscommunication frame by hardware at high speed. Use all-purpose, commercially available layer 3 switch.

Oct. 27, 2006-00

● Boundary RouterBoundary router is a network device to connect Vnet/IPwith external network such as in-house LAN. Bus 2 isused for connection with external network. Boundaryrouter needs to have firewall function to protect CS 3000from the threat of external network. Use all-purpose,commercially available boundary router.

● V net RouterA V net router is a device to connect a Vnet/IP domain anda V net domain for relaying control communications. Thisrouter realizes operation and monitoring of a controlstation in one domain from another domain by connectingthe Vnet/IP and V net domains. The following product isavailable:

AVR10D: Duplexed V net Router (for redundant use ofcommunications and power supply modules)

For the hardware specifications, see publication GS33P06H10-31E.

● SNTP ServerWhen synchronizing the time of the Vnet/IP station withUTC (Coordinated Universal Time), the SNTP server isconnected.

● PeripheralsSince an HIS supports Microsoft Windows 2000, WindowsXP, Windows 2000 Server or Windows Server 2003,windows-compatible peripherals, such as printers, can beused. Consult Yokogawa for more details on peripheralsthat can be used with an HIS.

Page 4: GS33P01B10-31E

4

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E

■ SYSTEM SPECIFICATIONS

● HIS Operation/Monitoring Capacity (Tags)Number of tags: Up to 100,000 (when using LHS4000,

up to 1,000,000 per system)Number of tags that can be entered in one HIS: Up to

100,000 (*1)*1: When a system is configured as CENTUM CS 3000

Entry Class; however, the maximum number of tagsshall be 8,000.

● Minimum SystemA minimum system consists of one HIS and one FCS.

● Maximum SystemIn a CENTUM CS 3000 system, a system within an areathat does not communicate via devices such as routers,layer 3 switches, or the like is called a domain. Up to 64Vnet/IP-enabled devices per domain can be connected.Our Vnet/IP-enabled devices include equipment withVI701 (control bus interface cards) incorporated in ageneral-purpose PC, FCS for Vnet/IP and V net routers.The following lists our specific Vnet/IP-enabled devices:

Human Interface Station (HIS)Field Control Station (FCS)Advanced Process Control Station (APCS)Generic Subsystem Gateway (GSGW)System Integration OPC Station (SIOS)Safety Instrumented Systems (ProSafe-RS)OPC Interface Package (Exaopc) OPC server

Field Communications Server for Plant ResourceManager (PRM)

V net Router (AVR10D)On the bus-2 side, up to 124 general-use Ethernet devices(including intelligent network devices) other than listedabove can be connected.

● Expanded SystemA layer 3 switch allows a hierarchical construction withother Vnet/IP domains. In addition, a V net router allowsconnection to a system using other V nets or VL nets.Existing systems (via an HF-bus or RL-bus) cannot bedirectly connected to a Vnet/IP network. These systemscan be connected via a BCV on a V net. A hierarchicalconnection using a layer 3 switch and a V net router allowsa system expansion that exceeds the maximum systemindicated in the previous section. In other words, hierarchi-cal connections of other control systems allow hierarchicalsystem expansion at the core of CENTUM CS 3000.

Total number of interconnected domains: Up to 16(Vnet/IP domains + V net domains)

Hierarchical connections by V net router: Three-levelcontrol bus hierarchy, i.e., three control buslevels, linked by two bus converters

Number of tag names: Max. of 100,000 (up to 1,000,000per system when using LHS4000)

Connecting devices: V net routers and bus convertersNote that the levels of Vnet/IP domains on an accessrouter and the levels of V net routers are not counted whenhierarchical connections are restricted.

Oct. 27, 2006-00

HIS

FCS

FCS

BCV-V

FCS

Vnet/IP domain

V net domain

Bus converter (0 level)One control-bus level

One bus-converter level and one control-bus level that are connected via a V net router

Two bus-converter levels and three control-bus levels (max.) connected via a V net router

BCV-V: Bus converter(V net to V net)BCV-H: Bus converter(HF-bus to V net)

V net domain

HF-bus domain

HIS

BCV-V BCV-H

V net domain

V net router

EFCS

F02E.EPS

Layer 3 switch

Figure Expanded System Configuration

Vnet/IP domains and V net domains can be managed in the same project. In addition, these two domains can be integratedwith a multiple project connection package.

As for details of Multiple Project Connection Package, refer to GS 33Q02S10-31E “Multiple Project Connection Package”.

Page 5: GS33P01B10-31E

5<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 33P01B10-31E

● Installing of Server PCsCENTUM CS 3000 realizes many functions using filesharing function of Windows. The number of PCs to sharefiles simultaneously is restricted on the Windows Worksta-tion OS. Therefore, when there are 9 or more stations(HIS, ENG, Exaopc) in one project, the server PC may berequired.

Please count the total station number in one project usingthe equations shown below in order to judge whetherserver PC is required or not. If the number is eight orsmaller, a server PC is not required. If the number is largerthan 8, consult our sales rep for further examination.

In case of PCs storing master Engineering databasefileWhen not using Engineering Tool for Foundation Fieldbus(SSS5700)

Total station number = HIS + ((ENG - 1) x 2) + Exaopc

When using Engineering Tool for Foundation Fieldbus(SSS5700)

Total station number = HIS + ((ENG - 1) x 2) + Exaopc + 2

HIS : Number of PCs in which Standard Operationand Monitoring Function (LHS1100 orLHM1101) is installed

ENG: Number of PCs in which Standard BuilderFunction (LHS5100 or LHM5100) isinstalled.

Exaopc: Number of PCs with Exaopc InterfacePackage (NTPF100)

When using Multiple Project Connection Package(LHS4450), please see the specifications for MultipleProject Connection Package (GS 33Q02S10-31E).

When using Expanded Test Function (LHS5425), serverPC is always required for storing master Engineeringdatabase.

Oct. 27, 2006-00

In case of PCs storing Audit trail dataWhen using LHS5170 Access Administrator Package, onePC which is dedicated to the audit trail data must beprepared. When there are 9 or more stations (ENG,Recipe Management PC) in one project, the server PCmay be required for storing Audit trail data.

Please count the total station number in one project usingthe equations shown below in order to judge whetherserver PC is required or not. If the number is eight orsmaller, a server PC is not required. If the number is largerthan 8, consult our sales rep for further examination.

Total station number = ENG + Recipe Management

ENG: Number of PCs in which Standard BuilderFunction (LHS5100 or LHM5100) isinstalled.

Recipe Management: Number of PCs in which CSBatch 3000 Recipe Management package(LHS5161) is installed

Page 6: GS33P01B10-31E

6

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E

■ Vnet/IP NETWORK SPECIFICATIONSThe Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports two types ofcommunications: control-bus communications and open communications. The Vnet/IP is always dual-redundant. Usually,control bus communications are carried out via bus 1. Open communications are carried out via bus 2. If a control communi-cations error occurs at the bus-1 side, control bus communications will be carried out via bus 2. The Vnet/IP uses general-purpose communications devices for network connection.

F03E.EPS

Vnet router

Vnet/IP domain

Layer 2 switch

FFCS-L

Layer 2 switch

Layer 3 switch

Layer 3 switch

Vnetdomain

Vnet/IPdomain

Vnet/IPdomain

Wide-area connection enabled by dedicated-line connection

HF-busdomain

BCV-H

1000BASE-TMax. 100 m

HIS ENGAPCS GSGW

Exaopc

Up to seven levels of layer 2 switch

Bus 1

Bus 2

Figure Network Configuration

● Connection within a DomainIn a system used with the Vnet/IP, sections separated by communications devices, such as routers, layer 3 switches, etc.,are called domains. One domain allows the connection of up to 64 of our Vnet/IP-based devices including the FCS, HIS, etc.In addition, a maximum of 124 devices, which includes switches, routers, etc., can be connected in configuring a networkwith Ethernet devices other than our Vnet/IP-based devices.

Devices in a domain are connected in a star or tree-like fashion at the core of a layer 2 switch. A dual-redundant Vnet/IP busis an independent subnet for each line; therefore, a layer 2 switch should be installed in each line. Up to seven levels of layer2 switch connections can be connected in a domain.

● Inter-domain ConnectionGeneral-use layer 3 switches allow connections between Vnet/IP domains. Up to 16 domains can be connected.

Up to 15 level (16-hierarchical) connections of Vnet/IP domains can be connected.

Two types of Vnet/IP domain connections are possible: bidirectional and hierarchical connections. In bidirectional connec-tions, HIS's in both domains can perform operation and monitoring of the other domain.

Bidirectional ConnectionBoth HIS's can perform operation and monitoring of the other domain. Stations in both domains can receive and send FCSand HIS messages.

Hierarchical ConnectionHierarchical domain relations are established. The HIS of a high-order domain can operate and monitor a low-order domain.FCS and HIS messages generated in a low-order domain can be accepted by a station in a high-order domain. A V netconversion router allows connection to a system connected to a V net. Connection to an existing system (via an HF-bus orRL-bus) connected with a BCV via a V net is also possible.

Oct. 27, 2006-00

Page 7: GS33P01B10-31E

7<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 33P01B10-31E

● Communications Specifications

Control bus communicationsCommunication Method: Read/write communication,

message communication, and link transmis-sion

Link Transmission Period: 100 msec

Open communicationsOpen communications are executed via the bus-2 side.Connected with commercially available Ethernetcommunications devices.The bandwidth that can be used for open communica-tions via the bus-2 side is up to 300 Mbps.

Transmission Path SpecificationsNetwork Topology: Star formationTransmission Path Redundancy: Available (control bus

communications only)Transmission Cable: Unshielded twisted pair (UTP) at

enhanced category 5 or greater.

T01E.EPS

Connection

Between station and layer 2 switch

Between layer 2 switches

Between layer 2 switch and router

Cable Standard

100BASE-TX (IEEE802.3u)

1000BASE-T (IEEE802.3ab)

1000BASE-T (IEEE802.3ab)

1000BASE-LX (IEEE802.3z)

1000BASE-T (IEEE802.3ab)

1000BASE-LX (IEEE802.3z)

Speed

100 Mbps(*1)

1 Gbps

1 Gbps

1 Gbps

1 Gbps

1 Gbps

Maximum Distance

100 m

100 m

5 km

100 m

5 km

*1: For V net Router, SCS and Open communicationnetwork.

● Communications between DevicesMaximum distance between arbitrary stations: 40 kmOnly a couple of media converter between devices canbe connected.

Oct. 27, 2006-00

● Network Device Specifications

Layer 2 switchConnection Port: 1000BASE-T, full duplexConnection between switches: 1000BASE-T,

1000BASE-LX with speed, 1 Gbps (1.5Mpps@64 byte) or faster, full duplex

Auto-Negotiation: Essential

Layer 3 switchConnection Port: 1000BASE-T, full duplexConnection between switches: 1000BASE-T,

1000BASE-LX with speed, 1 Gbps (1.5Mpps@64 byte) or faster, full duplex

Unicast dynamic routing protocol: RIPv2 (RIPv compat-ible mode essential)

Multicast Protocol:IGMP: EssentialDVMRP or PIM-DM: Essential

Management functionSNMP

● Address Used for Vnet/IPClass C private address is used for communications forcontrol and open communications.For Yokogawa equipment supporting Vnet/IP, three IPaddressed are automatically provided: one for bus 1control communication; one for bus 2 control communi-cation; one for bus 2 open communication.Communications for control

Bus-1 side 192.168.(Domain No.).1 to 129, 254Bus-2 side 192.168.(128 + Domain No.).1 to 129, 254

Open CommunicationsBus-2 Side 192.168.(128 + Domain No.).130 to 253

The following addresses are used for multicast commu-nications.For stations within domains

Bus-1 side 239.192.24.0Bus-2 side 239.192.24.1

For all domainsBus-1 side 239.192.24.4Bus-2 side 239.192.24.5

Class B address is used for the TCP/IP protocolcommunications on Vnet/IP.Make sure that there are no overlaps in IP addresses.

Page 8: GS33P01B10-31E

8

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E

■ I/O COMMUNICATIONS BUS

● ESB Bus

ApplicationAn ESB bus is an I/O communications bus that connectsthe processing unit of an FCS to a local node.

Communication SpecificationsConnectable Devices: Node units (ANB10S and

ANB10D)Number of Connectable Devices: The number of local

node units that can be connected to an ESBbus varies according to the databaseselected.

T02E.EPS

Database

Control Function for Standard Field Control Unit

Control Function for Standard Field Control Unit plus Application Capacity Expansion Package

Maximum Number of Local Nodes

3

9

Total Number of Local and Remote Nodes (*1)

3

14

*1: The total should not exceed this number.*2: If local node units are connected to an AFV10S or

AFV10D FCU, ESB Bus Coupler Modules (EC401)should be installed in slots 7 and 8.

Transmission Path SpecificationsNetwork Topology: Bus formationTransmission Path Redundancy: AvailableTransmission Speed: 128 MbpsTransmission Cable: Dedicated cable (YCB301)Transmission Distance: 10 m max.

● ER Bus

ApplicationAn ER bus is a remote I/O communications bus to connectan FCU or local node unit to a remote node.

Communication SpecificationsConnectable Devices: Remote node units (ANR10S,

ANR10D)Number of ER buses: Max. 4 per FCUNumber of Connectable Devices: The number of remote

node units that can be connected to an ERbus varies according to the model anddatabase selected.

T03E.EPS

Database

Control Function for Standard Field Control Unit

Control Function for Standard Field Control Unit plus Application Capacity Expansion Package

Maximum Number of Remote Nodes

3

14

Total Number of Local and Remote Nodes (*1)

3

14

*1: The total should not exceed this number.*2: Up to eight remote nodes per ER bus can be

connected.

Transmission Path SpecificationsNetwork Topology: Bus formationTransmission Path Redundancy: AvailableTransmission Speed: 10 MbpsTransmission Cable: Coaxial cable (YCB141, YCB311).

Use YCB147 ER-bus Adapter and YCB149ER Bus Converter Unit for connectingYCB141 and YCB311 cables.

Transmission Distance:

Max. 185 m (for YCB141)Extendable to 2 km when using Ethernetrepeaters (total transmission distance up to2370 m).Can use two (a set of) Ethernet repeatersper ER bus.

When mixing YCB141 and YCB311:Length of YCB141 + (185/500) x Length ofYCB311 � 185Number of bus adapter units: Max. 4 persegment (*3)Extendable to 2 km when using general-purpose Ethernet repeaters.

*3: If an ER bus is connected with a repeater, onesegment indicates the area between repeaters.

Oct. 27, 2006-00

Page 9: GS33P01B10-31E

9<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 33P01B10-31E

■ SOFTWARE

● Operation and Monitoring SoftwareLHS1100 Standard Operation and Monitoring FunctionLHS1120 Console HIS Support Package for Enclosed

Display StyleLHS1130 Console HIS Support Package for Open

Display StyleLHS1150 Server for Remote Operation and Monitoring

FunctionLHS2411 Exaopc OPC Interface Package (for HIS)LHS2412 CENTUM Data Access LibraryLHS4000 Million Tag Handling PackageLHS4100 Configured Information Reference PackageLHS4150 Recorder Output PackageLHS4190 Line Printer Support PackageLHS4200 Consolidated Historical Message Viewer

(Meeting FDA)LHS4410 Control Drawing Status Display PackageLHS4420 Logic Chart Status Display PackageLHS4450 Multi Project Connection PackageLHS4510 Expert Trend Viewer PackageLHS4600 Multiple-monitor PackageLHS4700 Advanced Alarm Filter PackageLHS4800 Consolidated Alarm Management Software

for HIS (CAMS for HIS)LHS6510 Long-term Data Archive PackageLHS6530 Report PackageLHS6600 CS Batch 3000 Process Management

PackageLHS6710 FCS Data Setting/Acquisition Package

(PICOT)LHS7110 Web Monitoring PackageSSS4510 Long-term Trend HistorianSSS4520 Event Viewer

For details on the above functions, see the respectiveGS's.

The operating system for an HIS is Windows 2000Professional or Windows XP Professional. If it is neces-sary to run other third-party software on the HIS, contactour sales representative to confirm that it is supported.

● Engineering SoftwareLHS5100 Standard Builder FunctionLHS5110 Access Control PackageLHS5150 Graphic BuilderLHS5160 CS Batch 3000 BuilderLHS5161 CS Batch 3000 Recipe Management

PackageLHS5170 Access Administrator Package (FDA: 21

CFR Part 11 compliant)LHS5420 Test FunctionLHS5425 Expanded Test FunctionsLHS5426 FCS Simulator PackageLHS5427 HIS Simulator PackageLHS5450 Multiple Project Connection BuilderLHS5490 Self-documentation Package

For details on the above functions, see the respectiveGS's.

● Standard FCS SoftwareLFS1500 Control Function for Standard Field Control

Unit (for Vnet/IP)LFS1530 Application Capacity Expansion Package

(for AFV10�)For details, see publication GS 33P03B10-31E.

● Optional FCS SoftwareLFS3132 Valve Pattern Monitor PackageLFS8620 Off-site Block Package

For details on these functions, see the respective GS's.

Oct. 27, 2006-00

Page 10: GS33P01B10-31E

10

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E

● Subsystem Communication SoftwareFor each subsystem, optional communications software isavailable.

LFS2420 FA-M3 Communication Package (forALR111, ALR121)

LFS2420 YS Communication Package (for ALR121)LFS2421 YS Communication Package with Direct

Connection (for ALR121)LFS2430 MELSEC Communication Package (for

ALE111)LFS2431 FA-M3 Communication Package (for

ALE111)LFS2432 DARWIN/DAQSTATION Communication

Package (for ALE111)LFS2433 PLC-5/SLC500 Communication Package

(for ALE111)LFS2453 Modbus Communication Package (for

ALE111)LFS2456 SLC500 Communication Package (for

ALR111, ALR121)LFS2457 PLC-5 Communication Package (for

ALR111, ALR121)LFS2542 PROFIBUS Communication Package (for

ALP111)LFS2610 Foundation Fieldbus Communication

Package (for ALF111)LFS2710 HART Communication Package (for AAIhhh-

H)LFS9153 Modbus Communication Package (for

ALR111, ALR121)LFS9162 MELSEC-A Communication Package (for

ALR111, ALR121)For details, see the respective GS's.

● Sequence of Events Manager SoftwareLPC6900 SOE Server PackageLPC6910 SOE Server Configurator PackageLPC6920 SOE Viewer PackageLPC6930 SEM OPC Interface Package

For details, see publication GS 33P02N80-31E “SEMSequence of Events Manager (for FIO and Vnet/IP)”.

● VTSPortal SoftwareLPC7800 VTSPortal Basic PackLPC7801 VTSPortal Multiple Client Builder License

As for details, refer to GS 33Q02N81-31E “VTSPortalBasic Pack, VTSPortal Multiple Client Builder License”.

● DocumentsLHS5495 Electronic Document

As for details, GS 33Q04N30-31E “Electronic InstructionManual”.

● Plant Resource ManagementSSS7700 Plant Resource Management ServerSSS7710 Plant Resource Management ClientSSS7720 Field Communications Server

As for details, refer to GS 33Y05Q10-31E “Plant ResourceManager”.

● Operation Support Software (for HIS)NTPS100 Exaplog Event Analysis PackageNTPS200 Exapilot Operation Efficiency Improvement

PackageAs for details of each function above, refer to GS36J06A10-01E “NTPS100 Exaplog Event AnalysisPackage” and GS 36J06B20-01E “NTPS200 ExapilotOperation Efficiency Improvement Package”.

● Safety Instrumented SystemCHS5100 Safety System Generation and Maintenance

PackageCFS1100 Safety Control Functions Package

As for details, refer to GS 32S51B10-01E “ProSafe-RSSafety Instrumented System Overview (for Vnet/IP)”.

■ INSTALLATION AND ENVIRONMEN-TAL CONDITIONS

The installation and environmental conditions forYokogawa's devices, except for general-purpose PCs,General-Purpose Network Device, console HIS's, nodeunits for FIO and I/O modules, are shown below. For ageneral-purpose PC and General-Purpose NetworkDevice, see their specifications. For an enclosed displaystyle console HIS, an open display style console HIS, anode unit for FIO, or an I/O module, see the generalspecifications for each device (publications GS 33Q06B40-31E, GS 33Q06B50-31E or GS 33Q06Q01-31E).

Ambient Temperature:5 to 40 �C (YAX101)5 to 35 �C (YAX801, YAX211)0 to 50 �C (FCS)

Ambient Humidity:20 to 80%RH10 to 90%RH (FCS)Non-condensation

Temperature Change Rate:� 10 �C per hour

Power Requirements:100 to 120 V AC � 10%, 50 or 60 Hz �3 Hz220 to 240 V AC, 50 or 60 Hz � 3 Hz24 V DC � 10%

Withstanding Voltage:1,500 V AC for 1 minute (for 100-V or 220-VAC model)500 V AC for 1 minute (for 24-V DC model)

Insulation Resistance:20 M� at 500 V DC10 M� at 500 V DC (YAX101, YAX801,YAX211)

Grounding:Independent ground of up to 100 �

Noise:Electric Field: Up to 3 V/m (26 MHz to 1 GHz)Magnetic Field: Up to 30 A/m (AC), 400 A/m (DC)Static: Up to 4 kV (direct discharge)

Continuous Vibration:Displacement amplitude: Up to 0.25 mm (1to 14 Hz)Acceleration: Up to 2 m/s2 (14 to 100 Hz)

Oct. 27, 2006-00

Page 11: GS33P01B10-31E

11<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 33P01B10-31E

■ CENTUM CS 3000 Entry ClassThe CENTUM CS 3000 Entry Class is available for small-scale systems.

● Components and SoftwareThe CENTUM CS 3000 Entry Class uses specific Entry Class packages such as built-in HIS packages. There is no restric-tion on FCS models.

● Operation and Monitoring SoftwareThe following software packages are provided for the Entry Class. Except for the packages listed below, current CS 3000system operation and monitoring software packages can be used. But, the LHS4000 Million Tag Handling Package cannotbe used in an HIS with the built-in LHM1101 Standard Operation and Monitoring Function.

Operation and Monitoring Software

T04E.EPS

Entry Class Model

LHM1101

Product

Standard Operation and Monitoring Function

Remarks

Number of operation and monitoring tags : up to 8000

LHM1150 Server for Remote Operation and Monitoring Function

LHM4410 Control Drawing Status Display Package —

LHM4420 Logic Chart Status Display Package —

LHM6600 CS Batch 3000 Process Management Package

Maximum number of active recipes: Type A: 4 Type B: 10 Type C: 999

LHM6710 FCS Data Setting/Acquisition Package (PICOT)

Engineering Software

T05E.EPS

Entry Class Model

LHM5100

Product

Standard Builder Function

Remarks

LHM5150 Test Function —

LHM5490 Self-documentation Package —

Oct. 27, 2006-00

Page 12: GS33P01B10-31E

12

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33P01B10-31E

■ REGULATORY COMPLIANCEThe standards to which CENTUM CS 3000 hardwaredevices conform are listed below. See the applicablegeneral specifications to ensure each device's compliance.

Safety Standards (*1)[CSA]

CSA C22.2 No. 1010.1 for 100 to 120 V AC and 24 VDC power supply

[CE Mark] Low Voltage Directive

EN 61010-1 for 220-240 V AC and 24 V DC powersupply (*6)

EMC Conformity Standards (*1)[CE Mark] EMC Directive

EN 55011 Group 1 Class A for 220-240 V AC and 24 VDC power supply

EN 61000-6-2 for 220-240 V AC and 24 V DC powersupply (*2)

EN 61000-3-2 for 220-240 V AC power supply (*3)EN 61000-3-3 for 220-240 V AC power supply (*4)

[C-Tick Mark]

AS/NZS 2064 for 220-240 V AC and 24 V DC powersupply

Standards for Hazardous Location Equipment[Non-incendive] (*5)

Class I, Division 2, Groups A, B, C and D Temperaturecode T4

CSA Standard C22.2 No. 157-92CSA Standard C22.2 No. 213-M1987ISA Standard ISA-S12.12 1994For 100-120 V AC and 24 V DC power supply

[Type n]

EN 60079-15: 2003IEC 60079-0: 1998IEC 60079-11: 1999(For 24 VDC power supply)

[Intrinsic Safety]

EN 50014 1997 +A1 +A2EN 50020 1994EN 50021 1999*1: To conform to safety standards and EMC conformity

standards, install 19-inch rack-mounted devices in akeyed metallic cabinet.

*2: A lightning arrestor or the like is required to meetthis surge immunity standard.

*3: An external device such as a power unit withharmonic current neutralizer and an activeharmonics conditioner must be connected to meetthis harmonic current emission standard.

*4: The specified limits of voltage drops across wiringmust be satisfied to meet this standard.

*5: To meet the standard for hazardous locationequipment, 19-inch rack-mounted devices must beapproved by CSA in Canada, or must be installed ina keyed metallic cabinet approved by non-incendiveregulator in your area.

*6: The analog input side of this equipment is measure-ment category 1.For details, see CENTUM CS 3000 InstallationGuidance (TI 33Q01J10-01E).

Subject to change without notice.Oct. 27, 2006-00

■ TRADEMARKS• CENTUM, Vnet/IP, DARWIN, DAQSTATION ProSafe

and Exaopc are registered trademarks of YokogawaElectric Corporation.

• Exaplog and Exapilot are trademarks of YokogawaElectric Corporation.

• Windows is a registered trademark of Microsoft Corpora-tion in the United States and/or other countries.

• Ethernet is a registered trademark of XEROX Corpora-tion.

• Modbus is a registered trademark of Schneider Electricand/or such related companies.

• PLC, PLC-5 and SLC500 are trademarks or registeredtrademarks of Rockwell Automation, Inc.

• MELSEC and MELSEC-A are registered trademarks ofMitsubishi Electric Corporation.

• SYSMAC is a registered trademark of Omron Corpora-tion.

• “FOUNDATION” of “FOUNDATION fieldbus” is a registeredtrademark of Fieldbus Foundation.

• Other product and company names appearing in thisdocument are trademarks or registered trademarks oftheir respective holders.