group 2 brick masonry- 0506,1706,3006,5207

45
REPAIR AND RETROFITTING OF REPAIR AND RETROFITTING OF MASONRY STRUCTURES MASONRY STRUCTURES EFFORTS BY: EFFORTS BY: ABHISHEK BHATT (0506) ABHISHEK BHATT (0506) ANTARA MASHRUWALA (1706) ANTARA MASHRUWALA (1706) DISHITA SHAH (3006) DISHITA SHAH (3006) RAVI SONI (5207) RAVI SONI (5207)

Upload: sharadkadbhane

Post on 08-May-2015

3.319 views

Category:

Business


4 download

TRANSCRIPT

Page 1: Group 2 brick masonry- 0506,1706,3006,5207

REPAIR AND RETROFITTING OF REPAIR AND RETROFITTING OF MASONRY STRUCTURESMASONRY STRUCTURES

EFFORTS BY:EFFORTS BY:

ABHISHEK BHATT ABHISHEK BHATT (0506)(0506)ANTARA MASHRUWALA ANTARA MASHRUWALA (1706)(1706)DISHITA SHAH DISHITA SHAH (3006)(3006)RAVI SONI RAVI SONI (5207) (5207)

Page 2: Group 2 brick masonry- 0506,1706,3006,5207

Objective:To study different repair materials and

techniques to be adopted in various situation to repair defective structures of brick and stone masonry.

Repairs: Process to replace or correct deteriorated/damaged materials and components of a building.

Retrofitting: Upgrading of structural and non-structural systems to provide a higher level of resistance than existed before .

Page 3: Group 2 brick masonry- 0506,1706,3006,5207

HOW DAMAGE OCCURS IN BRICK-MASONRY STRUCTURES:

Effect of Aging on Brick-Work:

Rain ExposureTemperatureMoisture AbsorptionChemical AlterationContinuous Exposure to Chemicals

Construction Error:

Eccentrically Loaded Walls gives overturning effect (Decorative Panels on one side, Support of Working platforms on one side)

Usage of Poor quality of materials

Error due to saving in economy

Page 4: Group 2 brick masonry- 0506,1706,3006,5207

Maintenance:

Common maintenance to brick is to white wash or to paint them at regular intervals, preferably every 2 years.

To maintain all sanitary installation in a good condition, any leakage notice anywhere should be intended to immediately, since a small leakage from nani-trap would lead to a major damage in due course.

Any cracking wherever noticed should be attended immediately either by sealing the joints with cement mortar or by strengthening the cracks with reinforced bands.

Page 5: Group 2 brick masonry- 0506,1706,3006,5207

TYPES OF CRACKS IN MASONRY STRUCTURES:

1.Vertical cracks in sidewalls at corner

2.Vertical cracks around balconies

3.Vertical cracks below the openings in line with the window

jambs.

4.Vertical cracks at the junction of RCC column and masonry

wall.

5. Vertical cracks in the top most stories at corners of structures

having RCC slab.

6.Horizontal cracks at window lintel or sill level in the top most

story.

7.Horizontal cracks in the top most story below the RCC slab

level.

8. Horizontal cracks at eaves level in the buildings having

pitched roof with wooden joists and purlins.

9. Random cracks in all directions involving both external and

internal walls.

10. Diagonal cracks over RCC lintels spanning large openings.

11. Shrinkage cracks.

Page 6: Group 2 brick masonry- 0506,1706,3006,5207

TYPES OF CRACKS IN MASONRY STRUCTURES:TYPES OF CRACKS IN MASONRY STRUCTURES:

Typical Earthquake Damage - Wall Corner Failure (1993 Killari Earthquake)

Typical Earthquake Damage: In-Plane

Wall Cracking

Wall Cracking above the Door Opening (1993

Killari Earthquake)

Page 7: Group 2 brick masonry- 0506,1706,3006,5207

GENERAL CAUSES TO DEVELOP THE CRACKS:

Poor quality of bricks.

For masonry work,use the porous stones.

Absence of grading in before the use of fine aggregate fine mortar.

If percentage of clay and silt in fine aggregate exceed 3 percent.

Due to the excessive amount of soluble sulphate.

Plumb alignment.

The position of the element in the structure.

Differential loading.

Weak mortar.

Insufficient bond.

Improper curing.

Entered dampness from ground, roof and exterior faces.

High daily temperature variations.

Atmospheric pollutions.

Lack of strength at corner and at junction of walls.

Improper binding of thick walls.

Page 8: Group 2 brick masonry- 0506,1706,3006,5207

REPAIR TECHNIQUES

Sand / Cement Mortar:It is the most simplest and basic repair method. It is highly reliable but may fail under severe drying conditions.Thus cracks will appear as a result of shrinkage in the plastic state of mortar.Due to this shrinkage, debonding and delaminating frequently occurs.Due to high water cement, ratio strength decreases.High density of pores and capillaries allow water and acidic vapours to more easily penetrate the repair and attack to the reinforcement bars.

Polymer modified cementations mortars:Polymer modified cementitious mortars are factory controlled blend of specially graded fillers, cement and admixtures to control strength development in set time. To reduce the shrinkage they contain polymers to improve the low permeability, quality and to enhance adhesion.The thermal expansion properties are similar to normal concrete.Heat development is low so much larger volume repairs can be undertaken.Low impermeability can prevent ingress chlorides.

Page 9: Group 2 brick masonry- 0506,1706,3006,5207

Epoxy resin mortars:

Epoxy technology is based on the mixing of two liquid resins which react together to form a hard solid if aggregates are added the resin system acts to bind them together to create mortar.Achieves compressive strength of 60-80 N/mm2 and very heavy high flexural strength.Due to good adhesion repair will never fail along correctly prepared bond line.More strength gain occurs in one day in normal atmospheric conditions.Properly compact mortar is impermeable to water.Most epoxy mortar requires primer.

Page 10: Group 2 brick masonry- 0506,1706,3006,5207

Epoxy injection:

Narrow cracks of 0.05 mm cracks are repaired by this

method.

High strength, highly viscous material can be achieved.

In this, holes are drilled at closer interval repairs are done

under external force through pumps or greasing guns.

Normal pressure should be of 1 kg/cm2.We should not apply

too much pressure which propagates the cracks.

High degree of skills and executions are required to repair

these types of cracks.

Page 11: Group 2 brick masonry- 0506,1706,3006,5207

Crack stitching:

This method involves drilling holes on both sides of

crack and grouting in stitching dogs.

Stitching may be used when the tensile strength must

be re-established across major cracks.

Stitching a crack tends to stiffen the structure, causing

the concrete to crack elsewhere. therefore it may be

necessary to strengthen the adjacent section with

external reinforcement.

Page 12: Group 2 brick masonry- 0506,1706,3006,5207

1.Firstly slots are cut with cutter machine of length 500 mm on each side of crack. The depth of slot is 10 mm but it also depends on the plaster surfaces.

2.Clear loose detritus from slots ensuring exposed brick surfaces are cleaned of mortar and flush thoroughly with water, or treated with a suitable primer.

3. Now fill the slot with grout with pressure.

4.Push Helical 6mm reinforcement crack stitching tie into grout to approximately two thirds of slot depth.

5.Finish the surface and repair the crack on the wall with appropriate filler /grout chemical.

METHOD FOR ADVANCE RETROFIT TECHNIQUE METHOD FOR ADVANCE RETROFIT TECHNIQUE WITH HELICAL REINFORCEMENTWITH HELICAL REINFORCEMENT

Page 13: Group 2 brick masonry- 0506,1706,3006,5207

Tuck pointing:

Defective joints can usually be repaired by tuck-pointing with Portland cement mortar, with the help of skilled stonemason

In this method, all joints, vertical and horizontal, in the face of the wall should be tuck-pointed.

This procedure requires removing and replacing all mortar to a depth of at least 16mm throughout every joint. each joint is raked to a depth not greater than 26mm unless the old mortar is so defective then it is necessary to remove the mortar up to greater depth.

The depth of old mortar is removed first so that sound mortar acts as a base for new mortar.

All dust and dirt within the raked joints should be washed out. The mortar is mixed at least 1 hour prior to use to ensure pre-

hydration which stabilizes the plasticity and workability of mortar and minimizes any tendency to shrink after insertion into the joint opening.

The sand/cement ratio should be about 3 to 1 by volume.

Page 14: Group 2 brick masonry- 0506,1706,3006,5207

TUCK POINTING

Page 15: Group 2 brick masonry- 0506,1706,3006,5207

Grouting (cement mortar):

Masonry structures can be sealed effectively with less cost by using grout provided the cement-base stabilizing mixture contains an intrusion aid.The consistency of intrusion mixture is that of smooth slurry.Before the intrusion, grout is pumped, the holes are tested by pumping water to see the drilling is adequate and to determine correct consistency for the slurry repairs.Firstly plaster is removed near the cracks from inside and outside of walls and clean the cracks thoroughly with airjet and water.Wet the cracks ,if dry ,by sprinkling water.This mixture is pumped into holes previously drilled at various interval to various depths without damaging the integrity of structure.

Pumping the grout simultaneously into multiple series of drill holes ensures good penetration into any fissures within the structure and for making masonry structures watertight.

Page 16: Group 2 brick masonry- 0506,1706,3006,5207

Grouting (chemical):

Chemical grouts consist of solution of two or more chemicals (such as urethanes, sodium silicate) that react to form a gel. This grout opposed to cement grouts that consist of suspension of solid particles in a fluid.

Advantages of chemical grout include applicability in moist environment and their ability to be applied in very fine facture.

Disadvantage is high degree of skill needed for satisfactory use and their lack of strength.

Crack as narrow as 0.05 mm can been filled with chemical grout.

Page 17: Group 2 brick masonry- 0506,1706,3006,5207

Polymer coating:

Polymer coating is use for the job condition and can be an effective protective coating if properly applied.

Polymer coating should be selected from the material specifically for the intended application.

Some formulation will adhere to damp surfaces and even under water but may required a completely dry surface.

Mixing and applying polymers below 16 degree and above 32 degree Celsius will require special caution and procedure.

Moisture passing through the sub grade backfill or from rainwater can accumulate under the coating, which will be interrupted by freezing and thawing.

Page 18: Group 2 brick masonry- 0506,1706,3006,5207

REPAIR MATERIALS Epoxy resins

Epoxy resins are excellent binding agents with high tensile strength. The epoxy components are mixed just prior to application. The product is of low vis cosity and can be injected in small cracks too.

The higher viscosity epoxy resin can be used for surface coating or filling larger cracks or holes.

Epoxy mortar Epoxy resins when combined, with sand aggregate it forms

epoxy mortar. Epoxy mortar mixture has higher compressive strength, higher tensile strength and a lower modulus of elasticity than Portland cement concrete.

Quick-setting cement mortar It is a non-hydrous magnesium phosphate cement with two

components, a liquid and a dry, which can be mixed in a manner similar to portland cement concrete.

Gypsum cement mortar It has lowest strength at fail ure among these three

materials. So it is used in minor repair works in structural application.

Mechanical anchors Mechanical anchors provide both shear and ten sion

resistance. Such anchors are manu factured to give sufficient strength.

Page 19: Group 2 brick masonry- 0506,1706,3006,5207
Page 20: Group 2 brick masonry- 0506,1706,3006,5207

RETROFIT: Post earthquake improvement of the

seismic resistance of a structure including repair of damage . Upgrading of structural and non-structural systems to provide a higher level of resistance than existed before the earthquake.

SURFACE TREATMENT:

Surface treatment is a common method, which has largely developed through experience.

Surface treatment incorporates different techniques such as ferrocement, reinforced plaster, and shotcrete.

Page 21: Group 2 brick masonry- 0506,1706,3006,5207

FERROCEMENT:

Ferrocement consists of closely spaced multiple layers of hardware mesh of fine rods(Figure 1 (a)) with reinforcement ratio of 3-8% completely embedded in a high strength (15-30 MPa) cement mortar layer (10- 50 mm thickness).The mortar is troweled on through the mesh with covering thickness of 1-5 mm.Typical mortar mix consists of 1 part cement: 1.5-3 parts sand with approximately 0.4 w/c ratio.

Page 22: Group 2 brick masonry- 0506,1706,3006,5207

REINFORCED PLASTER:

A thin layer of cement plaster applied over high strength steel reinforcement can be used for retrofitting.

The steel can be arranged as diagonal bars or as a vertical and horizontal mesh.

In diagonal tension test and static cyclic tests, the technique was able to improve the improvement in strength depends on the strengthening layer thickness, the cement mortar strength, the reinforcement quantity and the means of its bonding with the retrofitted wall, and the degree of masonry damage.

Page 23: Group 2 brick masonry- 0506,1706,3006,5207

SHOTCRETE:Shotcrete overlays are sprayed onto the surface of a

masonry wall over a mesh of reinforcing bars.In shotcrete the size of coarse aggregate is limited to 6mm.With thorough mixing of aggregates and adjustment of

pressure at the nozzle should be controlled otherwise a large proportion of coarse aggregate is lost in rebound.

Due to greater wear of nozzles during shotcrete there is a tendency to reduce the proportion or even eliminate coarse aggregates.

Certain additives are available which can reduce wear and tear of nozzles.

After shotcreting proper curing is essential.In situation where heavy construction machinery can not be

moved or is not economically viable, manual shotcreting can also be resorted too.

In manual method layers of concrete can not exceed 35-40 mm in thickness when laid.

Mason should be trained properly to move the trowel applying vibrations and simultaneously for compacting effect on each layer.

Non destructive testing of shotcrete repair work should be carried out.

Page 24: Group 2 brick masonry- 0506,1706,3006,5207

GROUT AND EPOXY INJECTION: PROCESS :The crack or joint should be widen wherever the injection work

is to be carried out (approximately 15 mm wide x 15 mm depth)Drill holes of about 13 mm dia upto 150 mm deep at 500 mm @

c/c. Use compressed air to clean the hole, as well as crack to

remove dust, dirt, loose materials etc. Use 12 mm dia specially threaded injection nipples and fix

them into the holes provided. Seal the entire surface around the nipple with putty.

Seal the surface of the crack with putty so as to ensure that the injected grout does not leak from the gaps & from cracked surface.

The surface now is ready for injection.Prepare the injection grout and load it into the injection gun.

Page 25: Group 2 brick masonry- 0506,1706,3006,5207

EXTERNAL REINFORCEMENT:

A steel plates or tubes can be used as external reinforcement for existing Unreinforced Masonry(URM) buildings.

Steel system is attached directly to the existing diaphragm or wall.

Two vertical members (via pin connections), which are placed next to the existing wall (i.e. creating in-fill panel) can be used.

Page 26: Group 2 brick masonry- 0506,1706,3006,5207

CONFINING URM USING R.C. COLUMNS:Confined masonry with R.C., weak frame represents one of the most widely used masonry construction system in Asia and Latin America.

In China, they used such confinement in new masonry buildings as well as it is used as retrofitting for existing URM buildings.

The basic feature of confined masonry structures is the vertical R.C. or reinforced masonry tie columns, which confine the walls at all corners and wall intersections as well as the vertical borders of doors and windows openings.

In order to be effective, tie columns should connect with a tie beam along the walls at floors levels.

Page 27: Group 2 brick masonry- 0506,1706,3006,5207

POST TENSIONING:

Post-tensioning involves a compressive force applied to masonry wall; this force counteracts the tensile stresses resulting from lateral loads.

There has been little application of this technique; post-tensioning is mainly used to retrofit structures characterized as monuments.

This is due in part to lack of knowledge about the behavior of post-tensioning masonry.

In addition, the codification of post-tensioning masonry has only begun recently.

Page 28: Group 2 brick masonry- 0506,1706,3006,5207

(Contd…..)POST TENSIONING:

Post-tensioning tendons are usually in the form of alloy steel thread bars.

Bars typically show higher relaxation losses (2-3 times strand losses) and much lower strength/weight ratio (VSL 1990); in addition, a major drawback for using of steel bars is corrosion. Fiber reinforced plastic presents a promising solution for this problem

Tendons are placed inside steel tube (duct) either within holes drilled along the midplane of the wall or along groves symmetrically cut on both surfaces of the wall.

Holes are cement grouted and external grooves are filled with shotcrete.

Page 29: Group 2 brick masonry- 0506,1706,3006,5207

GROUT OR EPOXY INJECTION IN CRACKS

1 - Plaster removed

2 - Cracks sealed after cleaning

3 - Grout ports

Strengthening of existing masonry

1 - Brick or block wall

2 - Injection holes

3 - Grout mixture

Page 30: Group 2 brick masonry- 0506,1706,3006,5207

STRENGTHENING WITH WIRE MESH AND MORTAR

CORNER REINFORCEMENT

1 - Welded wire mesh - 50 mm

x 50 mm

2 - Mortar or micro-concrete rendering

3 - Concrete roof band

4 - Cross ties at 500 to 750 mm apart

5 - Corner bar diameter 8 mm

STRENGTHENING WITH WIRE MESH Two steel meshes (welded wire fabric with an elementary mesh of approximately 50 x 50 mm) are placed on the two sides of the wall, they are connected by passing steel each 500 to 750 mm apart, A 20 to 40 mm thick cement mortar or micro concrete layer is then applied on the two networks thus giving rise to two interconnected vertical plates. This system can also be used to improve connection of orthogonal walls.

3

Page 31: Group 2 brick masonry- 0506,1706,3006,5207

Strengthening of existing masonry1 - Wire mesh on front face

2 – Clamps

3 - Wire mesh on back face

4 - Cement plaster

5 - Crack in wall

For Large cracks and crushed concreteFor cracks wider than about 6 mm or for regions in which the concrete or

masonry has crushed, a treatment other than injection is indicated. The following procedure may be adopted.The loose material is removed and replaced with any of the materials mentioned earlier, i.e., expansive cement mortar, quick setting cement or gypsum cement mortar.

Page 32: Group 2 brick masonry- 0506,1706,3006,5207

Splint and bandage strengthening techniqueThe technique of covering the wall with steel mesh and mortar or micro-concrete may be used only on the outside surface of external walls but maintaining continuity of steel at the corners. This would strengthen the walls as well as bind them together. As a variation and for economy in the use of materials, the covering may be in the form of vertical splints between openings and horizontal bandages over spandrel walls at suitable number of points.

Page 33: Group 2 brick masonry- 0506,1706,3006,5207

Splint and bandage strengthening technique

Page 34: Group 2 brick masonry- 0506,1706,3006,5207

NEGLIGENCE AFTER REPAIRS AND RETROFITTING

No. Negligence Reasons

1 Hair cracks are found on the all

ready strengthened brick masonry walls.

lack of curing after 4 hours from the application of cement mortar.

2 Weld mesh are soon on the brick masonry walls after finishing

coat.

improper thickness of the cement mortar

3 Uneven plaster surface are found on

the wall.

works are going on without preparing proper level markers.

4 Different shades are found on plastered

surface.

Improper mixing of cement with other materials and improper curing

Page 35: Group 2 brick masonry- 0506,1706,3006,5207

•PHOTOGRAPHS OF DAMAGE DUE TO EARTHQUAKE

•STRENGTHNING OF EXISTING CONSTRUCTION

•STRENGTHNING OF NEW CONSTRUCTION

•PHOTOGRAPHS OF NEW CONSTRUCTION AFTER EARTHQUAKE

CASE STUDY : JABALPUR EARTHQUAKECASE STUDY : JABALPUR EARTHQUAKE

Page 36: Group 2 brick masonry- 0506,1706,3006,5207

JABALPUR EARTHQUAKE DAMAGED NUILDINGS

Partial Building Collapse in the 1997 Jabalpur Earthquake

Faillure of Brick Masonry Walls in the 1997 Jabalpur Earthquake

Page 37: Group 2 brick masonry- 0506,1706,3006,5207

Seismic DeficiencyDescription of Seismic Strengthening

provisions used

Lack of integrity (box-type action)  Installation of seismic belt (bandage) at the lintel level; it consists of welded wire mesh installed above the lintel level and anchored to the wall. The mesh is covered with a thin cement plaster overlay (see Figure a) 

Cracks in the walls  In case of small cracks, pressure injection of epoxy grout; in case of large cracks, filling the gaps with cement grout and jacketing with reinforced cement overlay.

Inadequate wall resistance (shear and tensile) 

Reinforced concrete jacketing. Difficult to find skilled labor and materials for welded wire mesh in rural areas 

Flexible floor/roof diaphragm (Corrugated metal sheets/timber) 

Installation of RC roof band (bond beam). Provision of roof band is expected to enhance the overall intergrity and improve torsional resistance of building 

Cracking/damage of wall corners (due to improper interlocking of cross walls) 

Corner strengthening of wall corners - installation of welded wire mesh anchored to the walls with steel dowels and covered with a thin cement plaster overlay , see Figure b. 

STRENGTHENING OF EXISTING CONSTRUCTION

Page 38: Group 2 brick masonry- 0506,1706,3006,5207

FIGURE A FIGURE B

Page 39: Group 2 brick masonry- 0506,1706,3006,5207

Seismic DeficiencyDescription of Seismic

Strengthening provisions used

Roof  Reinforced concrete roof band; provision of roof band results in an improved overall integrity and torsional resistance of the

building. 

Wall  RCC lintel band; very effective, however skilled labour and materials may not be

available, see Figures 7D, 7E and 7F 

Wall  Improved quality of masonry (bricks and mortar) use of better quality bricks will drastically improve the wall seismic resistance; use or richer cement/sand

mortar will improve wall shear resistance. 

Wall  Provision of vertical reinforcement at wall corners and intersections, see Figure 7G

(Source: IAEE 1986) 

STRENGTHENING OF NEW CONSTRUCTION

Page 40: Group 2 brick masonry- 0506,1706,3006,5207

7D-An Example of New Construction with Seismic Features (note RC lintel

band)

7E-Construction of RC lintel band

7F-Construction of RC Lintel Band - Pouring of Concrete Completed

Page 41: Group 2 brick masonry- 0506,1706,3006,5207

7G-Provision of Vertical Reinforcement at Wall Corners and Intersections

Page 42: Group 2 brick masonry- 0506,1706,3006,5207

CONCLUSIONCONCLUSION

Cost effective and safer approach will be to carry out

appropriate repair and retrofitting of the building.

It will offer the advantage of carrying out the work part by part

or room by room so that the occupants may continue to live in

the building during the repair and retrofitting work .

By doing so the cost of repair and retrofitting came to only 8 %

of the estimated cost of reconstruction.

Page 43: Group 2 brick masonry- 0506,1706,3006,5207

REFERENCES:REFERENCES:

Civil Engineering & Construction Review (Vol.14 Dec.2001)

Structural Consolidation & Strengthening of masonry (Department of Civil Engineering, Belgium)

13th International Brick & Block masonry Conference Deterioration & Damages in Buildings, Department

of Civil Engineering, IIT, Kharagpur Jabalpur & Killari earthquake Damage reports &

Retrofitting Method, Department of Civil engineering, IIT, Kanpur

Page 44: Group 2 brick masonry- 0506,1706,3006,5207

QUESTION FROM OUR PRESENTATION

Why cracks or deteriorations occurs in brick masonry structures? State any 6 techniques by which it can be repaired? Explain any one in detail with neat sketches.

Page 45: Group 2 brick masonry- 0506,1706,3006,5207