a measurable difference! ® Gold Series Thermal Dispersion Airflow Measurement Technology Model GTx108 Technical Manual Advantage III Gold Series by Ebtron Installation, Operation and Maintenance Technical Manual GTx108 “Plug & Play” Transmitters Combination RS-485 and Dual Analog output model: GTC108-F Combination Ethernet and Dual Analog output model: GTM108-F LonWorks ® output model: GTL108-F Data Logger output model: GTD108-F Document Name: TM_GTx108_R2B1 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: 800.2EBTRON (232.8766) Fax: 843.756.1838 Internet: EBTRON.com TM_GTx108_R2B Part Number: 930-0006 LISTED European Union Shipments Models GTC108 and GTM108 BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BI.

Upload: others

Post on 27-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

a measurable difference!

®

Gold Series Thermal Dispersion Airflow Measurement Technology

Model GTx108Technical Manual

Advantage IIIGold Series by Ebtron

Installation, Operation and Maintenance Technical Manual

GTx108“Plug & Play” Transmitters

Combination RS-485 and Dual Analog output model: GTC108-F

Combination Ethernet and Dual Analog output model: GTM108-F

LonWorks® output model: GTL108-F

Data Logger output model: GTD108-F

Document Name: TM_GTx108_R2B1

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

TM_G

Tx10

8_R

2B

Part Number: 930-0006

LISTED

European Union

Shipments

Models GTC108 and GTM108

BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or testproducts for compliance with ASHRAE standards. Compliance of listed products to therequirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI).BTL is a registered trademark of BI.

Page 2: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Copyright © 2013, EBTRON ®, Inc.All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to

change without notice. Visit EBTRON.com to view and/or download the most recent versions of this and other documents.

All rights reserved.

LIST OF EFFECTIVE AND CHANGED PAGES

Insert latest changed pages (in bold text); remove and dispose of superseded pages.Total number of pages in this manual is 48.

Page No Revision * . . . . . . .Description of Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Date

1, 2 . . . . . . . . . . . .R2B . . . . . . . . . . . . . . . .Updated revision to R2B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .02/02/201641-47 . . . . . . . . . .R2B . . . . . . . . . . . . . . . .Minor corrections to Advantage 3 Setup Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .02/02/2016

1 through 4 . . . . .R2A . . . . . . . . . . . . . . . .Changed revision to R2A; updated Tables of Contents, List of Figures and Tables . . . . . . . . . . . . . . . . . . . . .12/15/201522, 23 . . . . . . . . .R2A . . . . . . . . . . . . . . . .Updated Velocity and Flow Variables and Temperature Variables and Configuration Properties to . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .include variables for individual Fans 1-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/15/201524-43 . . . . . . . . . .(no change) . . . . . . . . . .Renumbered pages 24-43 to allow for new content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/15/2015

1,2 . . . . . . . . . . . .R1C . . . . . . . . . . . . . . . .Changed revision to R1C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .06/26/201510, 14 . . . . . . . . . .R1C . . . . . . . . . . . . . . . .Clarified SW1/SW2 switch settings and AO1/AO2 SGNL= menu items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .06/26/201513 . . . . . . . . . . . . .R1C . . . . . . . . . . . . . . . .Added Fan n Alarm Output Assignment Types; Added note for FA TYPE-DEV for 2-fan operation. . . . . . . . . .06/26/201517 . . . . . . . . . . . . .R1C . . . . . . . . . . . . . . . .Table 5 units changed from FPM to CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .06/26/201548 . . . . . . . . . . . . .R1C . . . . . . . . . . . . . . . .Added Fan Volume menu item . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .06/26/2015

13 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Updated Table 3 for ability to view individual fan velocities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/201426 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Modified Table 16, item *LCD INT= from 30 to 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/201442 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Added SET SHAPE criteria menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/201443 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Modified SETUP MENU, item *LCD INT= from 30 to 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/201447 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Added “Affects analog outputs only” to OUTPUT TEST item . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/201448 . . . . . . . . . . . . .R1B . . . . . . . . . . . . . . . .Added ARRAY (Array Connector Board) and FAN VELOCITY menu items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .05/29/2014

1-48 . . . . . . . . . . .R1A . . . . . . . . . . . . . . . .Initial Document Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .04/01/2014

2 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

2B

Page 3: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5ADVANCED TECHNOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5GTx108 TRANSMITTER FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . .6ORDERING GUIDE - GTx108 TRANSMITTER . . . . . . . . . . . . . . . . . . .6GTx108 TRANSMITTER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . .7

GTx108 Mechanical Dimensions . . . . . . . . . . . . . . . . . . . . . . .7Power Transformer Selection . . . . . . . . . . . . . . . . . . . . . . . . . .8Connecting Power to the Transmitter . . . . . . . . . . . . . . . . . . . .8Connecting Sensor Probes to the Transmitter . . . . . . . . . . . . .9LCD Display and Menu Item Keys . . . . . . . . . . . . . . . . . . . . . . .9

GTC108, GTM108 - COMBINATION ANALOG + NETWORK TRANSMITTER SETUP . . . . . . . . . . . . . . . . . . . . . . . . . .10

GTC/GTM108 - ANALOG OUTPUT WIRING AND SETUP . . . . .10GTC/GTM108 - ALARM FEATURES . . . . . . . . . . . . . . . . . . . . .12

Average Alarm (AO2 ASGN=ALRM) . . . . . . . . . . . . . . . .12Fan Alarm (AO2 ASGN=FA) . . . . . . . . . . . . . . . . . . . . . . .12Trouble Alarm (AO2 ASGN=TRBL) . . . . . . . . . . . . . . . . .12FA Remove (FA REMOVE=YES) . . . . . . . . . . . . . . . . . . . .12No Fault (NO FAULT=HI) . . . . . . . . . . . . . . . . . . . . . . . . .12Alarm Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Average Low Alarm - “LO ALRM= ON” . . . . . . . . . . . . . .12Average High Alarm - “HI ALRM= ON” . . . . . . . . . . . . . .13Fan Alarm - “FA TYPE= MIN” . . . . . . . . . . . . . . . . . . . . .13Fan Alarm - “FA TYPE= DEV” . . . . . . . . . . . . . . . . . . . . .13Fan Alarm - “FA TYPE= %MAX” . . . . . . . . . . . . . . . . . . . .13Trouble Alarm - “AO2 ASGN=TRBL” . . . . . . . . . . . . . . . .13

GTC/GTM108 - ANALOG OUTPUT TYPE SELECTION AND SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

GTC/GTM108 - Converting Analog Output Signal Values to Airflow and Temperature . . . . . . . . . . . . . . . .14GTC108 - OUTPUT TEST - Sending a Test Output Signal to the Host Control System . . . . . . . . . . . . . . . . .14

GTC108 - TRANSMITTER SETUP FOR RS-485 NETWORK OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

GTC108 - RS-485 Network Options and Communications Menu Settings . . . . . . . . . . . . . . . . . .15GTC108 - Setting Transmitter Termination for RS-485 Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15GTC108 - Setting RS-485 Network Protocol . . . . . . . . .15GTC108 - Setting Transmitter Address . . . . . . . . . . . . .15GTC108 - Setting Baud Rate . . . . . . . . . . . . . . . . . . . . .15GTC108 - Setting Modbus Parity . . . . . . . . . . . . . . . . . .15GTC108 - Setting Device Instance Number . . . . . . . . . .15

GTC108 - Resetting Communications Options to Factory Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15GTC108 - RS-485 NETWORK WIRING CONNECTIONS . . . . .16

RS-485 Network Cable Specifications . . . . . . . . . . . . . .16Connecting to an Isolated RS-485 Network: . . . . . . . . .16Connecting to a Non-Isolated RS-485 Network: . . . . . .16

GTM108 - TRANSMITTER SETUP FOR ETHERNET NETWORKOPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

GTM108 - Ethernet Network Options and Communications Menu Settings . . . . . . . . . . . . . . . . . .18GTM108 - Selecting Static or Dynamic IP Settings . . .18GTM108 - Setting Ethernet Transmitter IP Address . . .18GTM108 - Setting Subnet Mask . . . . . . . . . . . . . . . . . . .18GTM108 - Setting Gateway IP . . . . . . . . . . . . . . . . . . . .18GTM108 - Setting BACnet Protocol Mode . . . . . . . . . . .19GTM108 - Setting Device Instance Number . . . . . . . . .19

GTM108 - Resetting Communications Options to FactoryDefault Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19GTM108 - ETHERNET WIRING CONNECTIONS . . . . . . . . . . .19

GTL108 - LONWORKS TRANSMITTER SETUP . . . . . . . . . . . . . . . .20GTL108 - LONWORKS NETWORK CONNECTIONS . . . . . . . . .20GTL108 - LONWORKS INTERFACE . . . . . . . . . . . . . . . . . . . . .21

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Basic Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21GTL108 - VELOCITY AND FLOW VARIABLES CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Velocity and Flow Variables . . . . . . . . . . . . . . . . . . . . . .22Velocity and Flow Configuration Properties . . . . . . . . .22

Temperature Variables and Configuration Properties . . . . .23Temperature Configuration Properties . . . . . . . . . . . . .23

GTL108 - DEFAULT DELTA VALUES . . . . . . . . . . . . . . . . . . . . .23GTx108-F TRANSMITTER START-UP, INITIALIZATION AND SETUP MENUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Transmitter Initialization and Setup Menus . . . . . . . . . . . . . .24Changing the System of Units - IP (Inch Pound) units or SI(Standard International) Units . . . . . . . . . . . . . . . . . . . . . . . .24

GTx108 TRANSMITTER CALIBRATION . . . . . . . . . . . . . . . . . . . . . .24GTx108 LCD DISPLAY NOTIFICATIONS . . . . . . . . . . . . . . . . . . . . . .24

Factory Default Menu Settings for GF2 (-F) Sensor Probes .24GTx108 CHANGING FACTORY DEFAULT SETUP MENU SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

Setup Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Selecting Actual and Standard Output Measurement Type .26Output Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Changing the LCD Display from Volumetric Flow CFM to Velocity FPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Converting the Analog Output Signal from FPM to CFM . . . .26Locking the Configuration Settings . . . . . . . . . . . . . . . . . . . .26

VIEWING SENSOR DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Viewing Sensor Data on the Local LCD Display . . . . . . . . . . .27Viewing Sensor Data over BACnet or Modbus Networks orthrough the EB-Link Reader . . . . . . . . . . . . . . . . . . . . . . . . . .27Sensor Addressing and Probe Positioning . . . . . . . . . . . . . . .27

Type ‘B’ (4 Connector) Transmitters . . . . . . . . . . . . . . . .27Type ‘C’ (8 Connector) Transmitters . . . . . . . . . . . . . . . .27

EB-Link WIRELESS INFRARED COMMUNICATIONS OPTION . . . . .30EB-Link Card Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Obtaining and Installing EB-Link Software . . . . . . . . . . . . . .31

EB-Link Reader Software . . . . . . . . . . . . . . . . . . . . . . . .31EB-Link Software for PDA Devices . . . . . . . . . . . . . . . . .31

Real Time Duct Traverses Using EB-Link . . . . . . . . . . . . . . . .31FIELD ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

ALTITUDE CORRECTION ADJUSTMENT . . . . . . . . . . . . . . . . . .32FACTORY CALIBRATION ADJUSTMENTS . . . . . . . . . . . . . . . . .32ADJUSTING THE LOW LIMIT CUTOFF . . . . . . . . . . . . . . . . . . .32Field Adjustment Wizard - AUTOMATED FIELD ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Overview of the Field Adjustment Wizard . . . . . . . . . . .32Engaging and Using the Field Adjustment Wizard . . . .32

MANUAL ADJUSTMENT OF FACTORY OFFSET/GAIN CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33Procedure for 1 Point Field Adjustment . . . . . . . . . . . . . . . . .33Procedure for 2 Point Field Adjustment . . . . . . . . . . . . . . . . .33

MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34GENERAL TROUBLESHOOTING (All GTx108 Systems) . . . . .35GTC108 (ANALOG OPERATION) TRANSMITTER TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36GTM108 ETHERNET TRANSMITTER TROUBLESHOOTING . .37GTL108 LonWorks TRANSMITTER TROUBLESHOOTING . . . .37

APPENDIX A - WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . .38GTC108 Combination Analog/RS-485 Output Transmitter Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .38GTM108 Combination Analog/Ethernet Output Transmitter Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .39GTL108 LonWorks Output Transmitter Wiring Diagram . . . .39

APPENDIX B - GTx108-F SETUP MENUS . . . . . . . . . . . . . . . . . . . .40

3EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R2

A

Table of Contents

Page 4: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Figure 1. GTx108 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Figure 2. GTx108 Transmitter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Figure 3. GTx108 Transmitter Ordering Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Figure 4. GTx108 Transmitter Mechanical Detail Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Figure 5. GTx108 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Figure 6. TypeB and Type C Transmitter Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Figure 7. Connector Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Figure 9. GTM108 Combination Analog/Ethernet Transmitter Interior Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Figure 8. GTC108 Combination Analog/RS-485 Transmitter Interior Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Figure 10. GTL108 LonWorks Transmitter Interior Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Figure 11. GTx108 Transmitter Connector Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Figure 12. Suggested Sensor Configurations (for Traverse decoding and EB-Link Data) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28Figure 13. EB-Link Installation Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Figure 14. EB-Link Reader and PDA Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Figure 15. Typical EB-Link Data Acquisition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Figure A-1. Model GTC108 Combination Analog/RS-485 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38Figure A-2. Model GTM108 Combination Analog/Ethernet Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39Figure A-3. Model GTL108 LonWorks Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39Figure B-1. GTx108-F Setup Wizard Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41Figure B-2. TM_GTx108-F System of Units Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42Figure B-3. TM_GTx108-F Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

List of Figures

Table 1. GTx108 Connectivity Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Table 2. GTx108 Power Transformer Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Table 3. GTx108 Alarm Types and Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Table 4. GTC/GTM108 Converting Analog Output Values to Airflow/Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Table 5. GTx108 BACnet Object List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Table 6. GTx108 Modbus Register Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Table 7. GTM108 TCP/IP Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19Table 8. GTL108 LonWorks Node Velocity and Flow Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Table 9. GTL108 LonWorks Node Velocity and Flow Configuration Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Table 10. GTL108 LonWorks Node Temperature Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Table 11. GTL108 LonWorks Node Temperature Configuration Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Table 12. Standard “IP” and “SI” Menu Units Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24Table 13. Factory Default Menu Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Table 14. Fan Arrays Suggested Sensor Configurations (for Traverse decoding and EB-Link Data) . . . . . . . . . . . . . . . . . . . .29Table 15. General Troubleshooting (All GTx108 Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35Table 16. GTC108 and GTM108 - Analog Operation Transmitter Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36Table 17. GTC108 RS-485 Transmitter Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36Table 18. GTM108 Ethernet Transmitter Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37Table 19. GTL108 LonWorks Transmitter Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

List of Tables

4 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

2A

Page 5: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Network Connectivity

Solutions

OVERVIEWEBTRON’s GTx108 (Figure 1) transmitter is designed for measure-ment of fan airflow and temperature on single inlet, dual inlet andfan array applications (up to eight fans) and includes a programma-ble alarm feature to indicate low or high fan flow and sensor prob-lems. The transmitter accepts one to eight of EBTRON's new GF2sensors and provides individual fan flow and temperature readingsas well as array average readings on multiple fan array applications.A programmable alarm can be set to monitor and report fan alarmsfor individual fan Minimum, %Maximum, and %deviation setpoints. Inaddition, concurrent alarms can be set for average flow low limit,high limit and sensor fault alarms. Analog output 2 (OUT2) can beconfigured as active low (0VDC or 4mA) or active high (5/10VDC or20mA) when assigned as an alarm output. The transmitter is fullyindependent of the sensors and does not require field matching tothem. It includes a 16 character LCD display for airflow, temperatureand system configuration and diagnostics. Field configuration isaccomplished through a simple four-button interface on the main cir-cuit board. Individual sensor airflow and temperature measurementscan be displayed from the diagnostic mode and are beneficial as anHVAC system diagnostic tool. The airflow output signal can be fil-tered, and a process low limit can be set to force the output to zerowhen airflow falls below a user defined value. A Field AdjustmentWizard feature can be engaged for one or two point field adjustmentin applications where field adjustment is required. The GTx108 trans-mitter is available in analog output and network output versions.

SPECIFICATIONS

ADVANCED TECHNOLOGY• Microprocessor-based electronics with industrial

grade integrated circuits.

• “Plug and Play” design.

• Accepts from 1 to 8 fan airflow and temperaturesensors for one to eight fans.

• LCD display and Push-button user interface for sim-ple field configuration and diagnostics.

• Programmable Alarm Output (models GTC andGTM108) for average flow low/high limits or fanminimum, deviation from median and deviationfrom maximum flow.

• Independent airflow and temperature output.

• Analog output signals and network protocols avail-able for interface with virtually all modern buildingautomation systems.

Maximum Sensing Points• 8 (8 airflow + 8 temperature, inde-

pendently processed)Sensor System Configuration

(max.)• Type B (probes x sensors): 4x1• Type C (probes x sensors): 8x1

Digital Signal Processing• Microprocessor: Yes• Multiplexing: 8 channels• A/D Converter: 12-Bit"Plug and Play" Sensor Systems• Sensors do not require matching

to transmitterPower Requirements• 24 VAC (22.8 to 26.4 VAC), at 12

to 20 VA (dependent on number ofsensors); isolation not required

• "Brownout" protection: "Watchdog"reset circuit

• Protection: Over voltage, over cur-rent and surge protection

Enclosure• AluminumUser Interface• Pushbutton and LCD displayDisplay • 16 character alpha-numeric dis-

play (auto-ranging)Output to Host ControlsGTC108, GTM108: (Combination Dual

Analog Output + Network models):Analog Output: Isolated dual 0-10VDC / 0-5VDC(resolution 0.010 / 0.020% FS) or4-20mA and:

for GTC108: Dual analog plus RS-485 Output at 76.8 kbps maxBACnet®, Modbus orfor GTM108: Dual Analog plus 10-BaseT Ethernet, BACnet,Modbus, and TCP/IP

GTL108: LonWorks® Free TopologyTransceiver (no analog output)

Airflow Output Adjustments:• Field Adjustment Wizard• Offset/gain • Airflow Output adjustable integra-

tion 1 to 1000 • Airflow Low Limit Cutoff: Forces

output to zero below defined value • Alarm Output programmable for

array average low and high limits,and individual fan low and highlimits

System Diagnostics• Sensor/transmitter diagnostics

mode and alarm output optionEnvironmental Limits• Operating Temperature: -20° F to

120° F (-28.8° C to 48.8° C)• Moisture: 0 to 99% rh, non con-

densing (protect from water)Compatible Sensor Systems • GF2 fan inlet sensorsListings • UL® 873 Airflow & Temperature

Indicating Devices • CE (EU shipments only) • BACnet BTL ListingWarranty • 36 months from shipment

Modbus

LONWORKS®

Figure 1. GTx108 Transmitter

Ethernet

5EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R2

B

Page 6: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Output to Host Controls Output/Protocols Supported Airflow Temperature Status

Analog: Linear 0-5VDC / 0-10VDC or 4-20mA Yes Yes Yes

RS-485: BACnet®-MS/TP, Modbus-RTU Yes Yes Yes

Analog: Linear 0-5VDC / 0-10VDC or 4-20mA Yes Yes Yes

BACnet Ethernet

BACnet-IP

Modbus-TCP

TCP/IP

LonWorks® - Model GTL108 Free Topology Transceiver Yes Yes Yes

Combination Analog / RS-485

Model GTC108

Combination Analog / Ethernet

Model GTM108 Yes Yes Yes

-

4 Fan Sensor Connectors8 Fan Sensor Connectors

LonWorks® Free Topology

Combination - Analog (0-5VDC / 0-10VDC or 4-20mA) andEthernet, BACnet®, Modbus, TCP/IP

L

Type C

G T 1

Transmitter Output

D Data Logger

0 8

M

Combination - Analog (0-5VDC / 0-10VDC or 4-20mA) and RS-485 (BACnet®, Modbus)

Transmitter TypeType B

C

ORDERING GUIDE - GTx108 TRANSMITTER

GTx108 TRANSMITTER FEATURES

Figure 3. GTx108 Transmitter Ordering Guide

Table 1. GTx108 Connectivity Options

Figure 2. GTx108 Transmitter Features

Power switch

Switching power supply

conserves energy and

reduces heat

Pushbutton interface

simplifies field configuration(Note: devices are plug and play and generally do not require configuration.)

Expansion port

Multiplexers independently

measure sensor voltages from

up to 16 sensing points

Gold plated interconnects to

sensor input receptacles

Output signal terminal.

connection to fused and.

protected output cards.(Note: not used when optional.

network cards are installed.)

LCD contrast.

Transmitter status LED.(Green 1 second flash normal;

2 second flash for fault)

High accuracy.

A/D converter.

Gold plated interconnects.

to optional output cards.

Cable receptacles with

gold.interconnects.

6 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

1A

Page 7: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

In locations exposed to direct rain and/or snow, the transmitter must be enclosed in a NEMA4 enclosure.

Leave unobstructed space of at least 9 in. (228.6 mm) above, 2 in. (50.8 mm) to each side and 3.5 in. (88.9 mm) below thetransmitter to allow for cover removal, sensor connections and heat dissipation.

Locate the transmitter in a location that can be reached by all connecting cables from the sensor probes.

Do not drill into the transmitter enclosure since metal shavings could damage the electronics.

GTx108 TRANSMITTER INSTALLATIONThe GTx108 transmitter is designed for use in an environment between -20° F to 120° F (-28.8° C to 48.8° C) whereit will not be exposed to rain or snow.

The transmitter should be mounted upright in a field accessible location. The enclosure (Figure 4) is designed toaccept 1/2 in. (12.7 mm) conduit fittings for signal and power wiring at the top left and right sides of the circuit board.The transmitter should be located such that the connecting cables from all of the sensor probes reach the receptacleson the bottom of the transmitter enclosure.

Figure 4. GTx108 Transmitter Mechanical Detail Drawing

GTx108 Mechanical Dimensions

2) IF UNIT HAS 2 PROBE CONNECTIONS THEN IT IS A TYPE "A" UNIT. IF UNIT HAS 4 PROBE CONNECTIONS THEN IT IS A TYPE "B" UNIT.

NOTES:

1) MEASUREMENTS IN BRACKETS ARE IN MILLIMETERS.

Ø.88 [Ø22.23 mm]

6.69 [169.86 mm]

5.94 [150.81 mm]

1.38 [34.93 mm]

SEE NOTE 21.56 [39.67 mm]

Ø.19 [Ø4.76 mm]

2.50 [63.50 mm]

7.94 [201.55 mm]

.38 [9.53 mm]

7.19[182.55 mm]

8.69 [220.73 mm]

.75 [19.05 mm]

5.19 [131.76 mm]

PROVIDE 3.5 INCH MINIMUM CLEARANCE AT BOTTOM FOR CONNECTOR ACCESS.

PROVIDE 9 INCH MINIMUM CLEARANCE AT TOP FOR COVER ACCESS (SLIDE UP TO REMOVE).

PROVIDE 2 INCH MINIMUM CLEARANCE AT BOTH SIDES OF ENCLOSURE

1.01[25.58 mm]

NOTES:1) MEASUREMENTS IN BRACKETS ARE IN MILLIMETERS.2) IF UNIT HAS 4 PROBE CONNECTIONS THEN IT IS A TYPE ‘B’ UNIT.

IF UNIT HAS 4 PROBE CONNECTIONS THEN IT IS A TYPE ‘C’ UNIT.

1.38[35.05 mm]

[O22.35 mm]O.88

[201.68 mm]

[O4.83 mm]O.19

[182.63 mm]

[9.65 mm]

[131.83 mm]

[150.88 mm]

[169.93 mm]

7EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R1

A

Page 8: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Power Transformer SelectionSelect a 24 VAC transformer based on the maximum power requirements indicated on the transmitter label (20 VA) orfrom the table below. The operating supply voltage (transmitter power “ON” with all sensor probes connected) shouldnot be less than 22.8 VAC or greater than 26.4 VAC.

NOTEIn order to retain the GTx108 device CE marking, GTx108 transmitters must be powered by a transformer that also carries the CE mark.

Connecting Power to the TransmitterSlide the cover plate up and off of the transmitter enclosure, and ensure that the power switch is in the “OFF” positionbefore connecting the 24 VAC power source.

Connect 24 VAC power to the large, two position power input terminal labeled “POWER” on the upper right hand side ofthe main circuit board (Figure 5). Since the output signals are isolated from the power supply, it is not necessary to pro-vide an isolated (secondary not grounded) power source.

Table 2. GTx108 Power Transformer Selection Guide

Figure 5. GTx108 Power Connections

Total

SensorsMinimumVA Req.

Total

SensorsMinimumVA Req.

1 12 5 14

2 13 6 15

3 13 7 15

4 14 8 16

REPLACE WITH

1.5 AMP

FAST ACTING ONLY

OUTPUT1 2 COM

POWER24VAC INL2 L1 ON

OFF

L2

L1

24 VAC 22.8 to 26.4 VAC20 VA max.

PowerSwitch

Power Fuse Replace with UL® listed, 1.5 amp, fast acting onlyP.N. 800-1115 (10 pack)

LISTED

8 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

1A

Multiple GTx108 transmitters wired to a single transformer must be wired “in-phase” (L1 to L1, L2 to L2).

Sensor probes must be connected to the transmitter before turning the power switch to the “on” position to properly “flash” sen-sor calibration data to the transmitter.

Page 9: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Connecting Sensor Probes to the TransmitterAfter mounting the sensor probes and transmitter, connect one or more sensor probe cable plugs to the circular recep-tacles located at the bottom of the GTx108 transmitter enclosure. Probes are “Plug and Play” and do not have to be con-nected to a specific receptacle on the transmitter (unless traverse data is desired - see note below). Transmitters acceptonly GF2 sensors. For fan array applications, sensors must be connected in the specific order shown in Figure 6 to ensurethat proper parameters (area, number of sensors, etc.) are entered during set up.

Provide a “drip loop” at the transmitter if there will be the potential for water runoff or condensation along the sensor probecable(s).

Sensor probe cable plugs are “keyed” as shown in Figure 7. Line up plug with receptacle and push straight on to receptacle. DONOT TWIST. Squeeze cable plug “ribs” towards receptacle when removing. Forcing the cable plug in or out of the receptacle willdamage the connectors and void warranty.If traverse data is desired, probes should be installed and connected to the transmitter using the mounting convention specifiedin the separate GF1/GF2 sensor probe manual. Proper installation simplifies sensor location decoding during data analysis.

Figure 7. Connector Detail

Figure 6. TypeB and Type C Transmitter Detail

LCD Display and Menu Item KeysThe GTx108-F begins a brief initialization at power up. On first power up (or if the Setup Wizard has not been complet-ed) the GTx108 begins a guided Setup Wizard to assist in setting up the transmitter. The Setup Wizard must be complet-ed in order for the transmitter to properly function. After completion, the transmitter LCD display automatically displaysairflow and temperature when fan inlet sensor probes (GF2) have been connected. Refer to the menus and descriptionswhich appear later in this manual for a complete description of programming features.

Align Key and Slot

Transmitter ReceptacleCable End Plug Squeeze and Pull to RemoveDO NOT TWIST!

9EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R1

A

Type A TRANSMITTERType B Transmitter

C1 C2 C3 C4

Type B TRANSMITTERType C Transmitter

C1 C2 C3 C4

C5 C6 C7 C8

Page 10: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1C

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com10

GTC108, GTM108 - COMBINATION ANALOG + NETWORK TRANSMITTERSETUPThe GTC108 Combination card option allows simultaneous analog outputs and RS-485 differential bus/line transceiveroutputs designed to integrate with various network protocols.

The GTM108 Combination Analog/Ethernet card option allows simultaneous analog outputs and full duplex IEEE 802.3ethernet interface with automatic re-transmission on collision and cyclic redundancy checking on network data. An on-board microcontroller performs over 7 million instructions per second to insure minimal network latency. Link status aswell as network activity are available via on-board LED indicators.

The GTC/GTM108 Combination card plugs directly onto the main circuit board as shown in Figures 8 and 9.

GTC/GTM108 - ANALOG OUTPUT WIRING AND SETUPAnalog output connections are made at the top left of the transmitter main circuit board OUTPUT connector as shown inFigures 8 and 9. Independent 12-bit (4096 discrete states) linear analog outputs are provided for airflow at OUTPUT ter-minal 1, and for temperature (or alarm) at OUTPUT terminal 2, each with over voltage and over current protection. Airflowand temperature outputs are field selectable for either 0-5/0-10VDC or 4-20 mA. The GTx108 circuit board switchSW1/SW2 settings determine which of the matching A01/A02 SGNL= menu items are available. The OUTPUT terminal2 can be assigned as an Alarm output to provide an active high, active low, fan alarm or trouble alarm output (as deter-mined by SW2 and AO2 SGNL= menu settings). Outputs are galvanically isolated from the main power supply to permitsimple integration with virtually all building automation systems.

To wire the analog output signals, slide the cover plate up and off of the enclosure. Ensure that the power switch is inthe “OFF” position. Connect signal wires for airflow rate and temperature (or alarm) to the small, three position outputterminal labeled “OUTPUT” on the upper left hand side of the main circuit board as indicated in Figure 8. Airflow outputis at terminal 1, and temperature, alarm, fan alarm or trouble alarm output is at terminal 2.

When configured for a 4-20mA output, the GTC108 is a “4-wire” device. The host controls shall not provide any excitation volt-age to the output of the GTC108.

Page 11: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 11

ESC ENTER

CONTRAST

REPLACE WITH

1.5 AMP

FAST ACTING ONLY

OUTPUT1 2 COM

POWER24VAC INL2 L1 ON

OFF

RS-485

NET COM

NET -

NET +

ON

TERM

F1

F2

VDC mAOUT 1

OUT 2

RS-485

Figure 8. GTC108 Combination Analog/RS-485 Transmitter Interior Detail

Analog Output FusesF1=OUT1F2=OUT2

UL listed 0.125 AmpP.N. 800-1105 (Qty:10)

Transmitter Status LED(Green 1 second flash normal;

2 second flash for fault)

Power Switch

COM*

NET -NET +

ANALOG OUTPUT1: Airflow2: Temperature/AlarmCOM: Common

(RS-485 output below)

*CAUTIONThe common for the ANALOG and the RS-485 outputs must be at the same potential.For ISOLATED RS-485 output, COM connection MUST BE CONNECTED to network common. For NON-ISOLATED output, COM connection MUST BE CONNECTED to the common ground that other network devices are using (typically theground side of the 24VAC supply - L2 of the POWER terminals). Refer to RS-485 Network Wiring Connections paragraph for additional detail.

RS-485 Activity LED.(Green LED indicating RS-485 network activity).

SW1 (for OUT1)Airflow - Output Signal SelectSW2 (for OUT2)Temperature/Alarm, Fan Alarm,Trouble - Output Signal SelectVDC: (0-5/0-10 VDC) or mA: 4-20 mA

LCD Display

RS-485 OUTPUT(For Analog Output, seeseparate output above)

Combination Analog/RS-485 Output Card

P.N. 800-1825

Figure 9. GTM108 Combination Analog/Ethernet Transmitter Interior Detail

ACTIVITY

TRAFFIC

LINKD4D3D2

ETHERNET 10/100

VDC mA

S1

S2

F1

F2

ESC ENTER

CONTRAST

REPLACE WITH

1.5 AMP

FAST ACTING ONLY

OUTPUT1 2 COM

POWER24VAC INL2 L1 ON

OFF

Combination Analog/ EthernetOutput CardP.N. 800-5026

LCD Display

ACTIVITY (green) indicatesEthernet output boardhealth/status (Green 1 second flash normal;2 second flash for fault)

TRAFFIC (green) indicates ethernet traffic

LINK (green) indicates ethernet link status

Power Switch

RJ45 Ethernet Output

ANALOG OUTPUT1: Airflow2: Temperature/AlarmCOM: Common

(RJ45 Ethernet output below)

Analog Output FusesF1=OUT1F2=OUT2

UL listed 0.125 Amp P.N. 800-1105 (Qty:10)

SW1 (for OUT1)Airflow Output Signal Select

SW2 (for OUT2)Temperature/Alarm, Fan

Alarm, Trouble - OutputSignal Select

VDC: (0-5/0-10 VDC) or mA: 4-20 mA

1 2 3 4

off off off off No Termination

off oon on off End of Lineon off off oon Fail-safe Bias

DIP Switch Position

TERMINATION DIP SwitchNetwork

Termination

OFF ONSW3 TERMINATION Switch

Page 12: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

GTC/GTM108 - ALARM FEATURESThe analog temperature output AO2 (OUT2) of the GTC/GTM108 transmitter can be assigned to function instead as analarm output. The OUT2 alarm output can be assigned in the SETUP menu to operate as an average alarm (A02ASGN=ALRM), as a fan alarm (AO2 ASGN=FA) or as a trouble alarm (AO2 ASGN=TRBL) for monitoring the status of thetransmitter and sensors. The AO2 ASGN= setting is located in the ANALOG OUT submenu of the SETUP menu:

Average Alarm (AO2 ASGN=ALRM)AO2 output is assigned as an average airflow alarm output. Useful for applications where a low flow alarm, a high flowalarm or an alarm for operation outside of a defined range (setpoint and tolerance) is required.

Fan Alarm (AO2 ASGN=FA)AO2 output is assigned as a fan alarm output for multiple fan (fan array) applications. In fan arrays this is useful for indi-cating which fan is in alarm state by providing an analog output level proportional to the fan number. For example, if fannumber 3 is in alarm, OUT2 will provide an output of 30% of the full scale analog range selected.

For fan arrays, the Fan Alarm can be set for one of 3 modes through the FA TYPE= setting in the FAN ALARM submenu:

FA TYPE=MIN: Alarm actives if a fan flow falls below a minimum defined flow rate setpoint

FA TYPE=DEV: Alarm actives if a fan flow deviates more than a defined percentage setpoint from the median flow of all fans

FA TYPE=%MAX: Alarm actives if a fan flow deviates more than a defined percentage setpoint from its own max-imum flow

In both AO2 ASGN=ALRM and AO2 ASGN=FA alarm modes, a delay feature can be specified to prevent nuisance alarms,and a zero-off feature can be engaged to prevent low flow alarms when the system is reading zero flow (i.e. when fansare off). In addition, a reset feature allows for the alarm to be reset either manually or automatically in the event thatthe alarm condition no longer exists.

Trouble Alarm (AO2 ASGN=TRBL)AO2 output is assigned as a transmitter trouble alarm indicating a fault within the transmitter or a sensor of the airflowmeasurement system. The transmitter LCD will indicate a trouble code and a brief description of the trouble. ContactEBTRON customer service for additional information or assistance with trouble codes.

The transmitter LCD display will indicate the Alarm status for 2 seconds, and will cycle through any other alarms if mul-tiple alarm events are active for 2 seconds each, and then display the current actual flow for 2 seconds. Detailed set upof the Alarm features is shown in the Setup menu.

FA Remove (FA REMOVE=YES)This setting determines whether a fan that is in alarm should be removed from the transmitter calculated average.

No Fault (NO FAULT=HI)When AO2 output is assigned as an alarm, this setting configures the normal output condition to be HI or LO relative tothe full scale analog output level selected when no fault condition exists.

Alarm IndicationsTable 3 details the alarm types, LCD indications and AO2 alarm outputs available from the GTC/GTM108. User canselect either of the two Average Alarms, one of the three Fan Alarms or the Trouble Alarm:

Average Low Alarm - “LO ALRM= ON”The Low Alarm is activated when the average airflow falls to a defined level below the SETPNT= value. The definedlevel is equal to the SETPNT= value minus the calculated value of (TOL= value) x (SETPNT= value). Once active, the alarmcan be cleared when the average airflow rises above the set point minus calculated tolerance value.

12 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

1C

Page 13: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

Average High Alarm - “HI ALRM= ON”The High Alarm is activated when the average airflow rises above a defined level above the SETPNT= value. Thedefined level is equal to the SETPNT= value plus the calculated value of (TOL= value) x (SETPNT= value). Once active,the alarm can be cleared when the average airflow falls below the set point + calculated tolerance value.

Fan Alarm - “FA TYPE= MIN”The Fan Alarm Minimum alarm is activated when the airflow of any of the fans in the fan array falls below the selectedset point (SETPNT=) value. Once active, the alarm can be cleared when the airflow rises above the set point value. Themagnitude of the fault signal is proportional to the (lowest) fan number that is in alarm state.

Fan Alarm - “FA TYPE= DEV”The Fan Alarm Deviation alarm is activated when the airflow of any of the fans in the fan array exceeds the median air-flow by the percentage specified by the (SETPNT=) value. Once active, the alarm can be cleared when the airflow returnswithin the specified percentage of median airflow. The magnitude of the fault signal is proportional to the (lowest) fannumber that is in alarm state. If only 2 fans, the highest flow will be used for median comparison.

Fan Alarm - “FA TYPE= %MAX”The Fan Alarm Maximum alarm is activated when the airflow of the any of the fans deviates from its highest stored valueby the percentage specified by the (SETPNT=) value. Once active, the alarm can be cleared when the airflow returns with-in the range specified by the set point value. The magnitude of the fault signal is proportional to the (lowest) fan numberthat is in alarm state.

Trouble Alarm - “AO2 ASGN=TRBL”The Sensor Trouble alarm is selected in the ANALOG OUT submenu (AO2 ASGN=TRBL) and provides trouble codes use-ful for isolating setup issues or problems within the transmitter or sensors. The transmitter LCD will indicate TROUBLE!The Diagnostic submenu can be engaged for the error code and a brief description of the trouble. Contact EBTRON cus-tomer service for information on troubleshooting using the Trouble error codes.

ALARM OUTPUTASSIGNMENT TYPE

LOCAL LCD DISPLAY OF ALARM TYPEAND NOTIFICATION

ALARM (OUT2) INDICATION

User can select either of the two Average Alarms, one of the Fan Alarms or the Trouble Alarm:

**LOW ALARM**(Average Alarm)

Display alternates between **LOWALARM** (then any other alarms) andactual reading for 2 seconds each.

On alarm, OUT2 is active high (or active low) relative to the fullscale maximum (or minimum) analog value as determined bySETUP Menu “NO FAULT=” selection. Individual sensor velocitiescan be viewed using the Diagnostics submenu. **HIGH ALARM**

(Average Alarm)

Display alternates between **HIGHALARM** (then any other alarms) andactual reading for 2 seconds each.

** FAN n MIN **(Fan Alarm)

Display alternates between ** FAN nMIN ** (then any other alarms) andactual reading for 2 seconds each.

For multiple fan array applications, the alarm output is propor-tional to the (lowest) fan number that is in alarm. For example,if fan number 3 is in alarm, OUT2 will provide an output of 30%of the full scale analog range selected. Individual fan velocitiescan be viewed using the Diagnostics submenu.

n= fan number. If multiple fans are in alarm, n= lowest fannumber in alarm.

** FAN n DEV **(Fan Alarm)

Display alternates between ** FAN nDEV ** (then any other alarms) andactual reading for 2 seconds each.

** FAN n %MAX **(Fan Alarm)

Display alternates between ** FAN n%MAX ** (then any other alarms) andactual reading for 2 seconds each.

TROUBLE !(Trouble Alarm)

Display indicates TROUBLE !(Refer to DIAGNOSTIC menu to obtaina brief description of the error and anyother alarms).

On alarm, OUT2 is active high (or active low) relative to the fullscale maximum (or minimum) analog value as determined bySETUP Menu “NO FAULT=” selection. Individual sensor velocitiesand temperatures can be viewed using the Diagnostics sub-menu.

Table 3. GTx108 Alarm Types and Notifications

13EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R1

C

Page 14: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1C

Table 4. GTC/GTM108 Converting Analog Output Values to Airflow/Temperature

TO CONVERT TO

Airflow (FPM, MPS) Output Voltage/10 x FS1 Output Voltage/5 x FS1 (Output Current-4)/16 x FS1

Airflow (CFM) Area (SQF) x Output/10 x FS1 Area (SQF) x Output/5 x FS1 Area (SQF) x (Output - 4)/16 x FS1

Airflow (LPS) Area (SQM) x Output/10 x FS1 x 1000 Area (SQM) x Output/5 x FS1 x 1000 Area (SQM) x (Output - 4)/16 x FS1 x 1000

TO CONVERT TO

Airflow (CFM, LPS) Output Voltage/10 x FS1 Output Voltage/5 x FS1 (Output Current - 4)/16 x FS1

TO CONVERT TOTemp (°F,°C) Output Voltage/10 x (FS2 - MS2) + MS2 Output Voltage/5 x (FS2 - MS2) + MS2 (Output Current - 4)/16 x (FS2 - MS2) + MS2

NOTES:FS1 is OUTPUT1 full scale analog output value from SETUP MENU.FS2 is OUTPUT2 full scale analog output value from SETUP MENU.MS2 is OUTPUT2 minimum scale analog output value from SETUP MENU.

ANALOG OUTPUT SCALING AND TYPE

0-10 VDC 0-5 VDC 4-20 mA

ANALOG OUTPUT SCALING AND TYPE

When OUTPUT 1 is Configured as Linear Airflow (FPM, MPS):

When OUTPUT 1 is Configured as Volumetric Airflow (CFM, LPS):

0-10 VDC 0-5 VDC 4-20 mA

ANALOG OUTPUT SCALING AND TYPE

0-10 VDC 0-5 VDC 4-20 mA

When OUTPUT 2 is Configured as Temperature (°F,°C):

GTC/GTM108 - ANALOG OUTPUT TYPE SELECTION AND SETUP The analog output signal type at OUT1 (airflow) and OUT2 (temperature/alarm) can be set for mA or VDC output by set-ting switches SW1/SW2 (Figure 8). SW1/SW2 settings enable the appropriate 4-20mA, 0-5 VDC or 0-10VDC menuranges in Setup menu options for *AO1 RNGE= / *AO2 RNGE= settings (Appendix B). The transmitter is shipped fromthe factory with SW1/SW2 and Setup menu options *AO1 SGNL= and *AO2 SGNL= set for 4-20mA.

GTC/GTM108 - Converting Analog Output Signal Values to Airflow and TemperatureSince the accuracy of the GTC/GTM108 is “percent of reading” there should be no need to reconfigure the default out-put scales listed inside of the transmitter cover. However, factory default settings can be easily reconfigured in the field(see: CHANGING FACTORY DEFAULT SETTINGS).The equivalent volumetric flow full scale reading can easily be determined by multiplying the full scale reading by the freearea where the airflow measuring station is located (free area x 1000 for S.I. scaling when the area is calculated insquare meters). For GF1/GF2 sensors, the free area must be determined after the units are installed. Table 4 lists spe-cific conversion factors for analog voltage or current output options.

GTC/GTM108 - OUTPUT TEST - Sending a Test Output Signal to the Host Control SystemA test output signal between 0 and 100% of the full scale output (4-20 mA or 0-5VDC/0-10VDC) can be provided by theGTC/GTM108 transmitter to verify proper conversion of the output signals from the transmitter at the host control sys-tem. To set a fixed output signal for airflow and temperature, navigate to the TOOLS sub menu to access OUTPUT TEST.OUT1 and OUT2 tests are independently accessed, and the output will maintain the % shown until the “ESC” button ispressed and normal operation is resumed.

14 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

Page 15: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 15

GTC108 - RS-485 NETWORK WIRING CONNECTIONSRefer to the Figure 8, and the following paragraph for network wiring considerations.

RS-485 Network Cable SpecificationsThe RS-485 network cable shall be shielded twisted pair with a characteristic impedance of 100 to 130 ohms.Distributed capacitance between conductors shall be less then 100 pF per meter. Distributed capacitance between con-ductors and shield shall be less then 200 pF per meter. The maximum recommended length of a network segment is1200 meters with AWG 18 cable.

Connecting to an Isolated RS-485 Network:Connect the NET+, NET- and COM terminals to the network with shielded twisted pair cable meeting the specificationsdefined in the previous paragraph (typically using two pairs, with one wire not used; one pair for +/- and both wires inother pair for GND when using 2-pair cable). The connection to the network must be made in a "daisy chain” configura-tion. "T" connections and stubs are NOT permitted. The shield should be terminated at one end on the network only. Ifthe GTC108 is not the first or last device, set the on-board termination DIP switches for NO TERMINATION. If the GTC108is the first or last device, set the on-board termination DIP switches to either END OF LINE or FAIL SAFE BIAS termination.

*CAUTIONFor ISOLATED output, the COM connection MUST BE CONNECTED to the network common for proper operation.In addition, when the Analog Output is concurrently used with the RS-485 Output, the Common connection forboth Analog and RS-485 Outputs must be at the same potential.

Connecting to a Non-Isolated RS-485 Network:Connect the NET+ and NET- terminals to the network with a shielded twisted pair cable meeting the specificationsdefined in the previous paragraph. The connection to the network must be made in a "daisy chain” configuration. No "T"connections or stubs are permitted. The shield should be terminated at one end on the network only. If the GTC108 isnot the first or last device, set the on-board termination DIP switches for NO TERMINATION. If the GTC108 is the first orlast device, set the on-board termination DIP switches to either END OF LINE or FAIL SAFE BIAS termination. Becausethe GTC108 output is isolated, the COM terminal must be connected to the "common ground" that the other devices onthe network are using as their ground reference. This is typically the ground side of the 24VAC supply (L2 on the GTC108POWER terminals).

*CAUTIONFor NON-ISOLATED output, the COM connection MUST BE CONNECTED to the common ground that is used bythe other network devices (typically the ground side of the 24VAC supply; the L2 terminal at the POWER connec-tor block as shown in Figure 8). In addition, when the Analog Output is concurrently used with the RS-485Output, the Common connection for both Analog and RS-485 Outputs must be at the same potential.

Tables 5 and 6 list the specific values provided for BACnet and Modbus communication protocols.

TM_G

Tx10

8_R

1A

Page 16: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com16

BACnet MS/TP

ModbusModbus RTU

Table 6. GTx108 Modbus Register Map

Table 5. GTx108 BACnet Object ListAnalog Inputs

Type, IDDefault Units

Device x = C for RS-485 x = M for Ethernet

AI, 1 CFM

AI, 2 °F

AI, 3

0: No alarm, 1: High Alarm, 2: Low Alarm, 3: Both

AI, 4 0: No alarm, 1: Alarm

Name

Fan Alarm Status

GTx 108

Avg. Flow

Avgerage Temperature

Alarm Status

Notes:

Type, IDDefault Units

xx

Analog ValuesAV, 1 Fan 1 Area sq.ft.

AV, 8 Fan 8 Area sq.ft.

AV, 9 Fan 1 Flow CFM

AV, 16 Fan 8 Flow CFM

AV, 17 Fan 1 Temperature °F

AV 24 Fan 8 Temperature °F

Name

x

AV, 24 Fan 8 Temperature °F

NNotes: 1. Number of AV objects is dependent on the fan count.2. User Executed Services Supported: Subscribe COV, Read Property, Write Property, Device Communication Control, Who-Is.

Function Address Type Units Description Range/Value

2 10001 boolean Trouble Status 0:OK, 1:Trbl4 30001-30002 float FPM Average Airflow 0 to 15,0004 30003-30004 float °F Average Temperature -20 to 1604 30005 word Number of Inserts 0 to 84 30006 word Fan Count 1 to 8

4 30007 word Alarm Status0 - 3: Flow alarm4: Fan alarm

4 30008 word Fans in alarm bitwise representation

30009-30024 Fan Flows30009-30010 Fan 1 Flow

0 to 15,000FPMfloat4

30023-30024 Fan 8 Flow

30025-30040 Fan Temperatures30025-30026 Fan 1 Temp

0 to 15,000

-20 to 160°F

FPMfloat4

4 float

30039-30040 Fan 8 Temp

30041-30056 Insert Flow Traverse30041-30042 Insert 1 Flow

30055-30056 Insert 8 Flow

0 to 15,000FPM4 float

30056-30072 Insert Temp Traverse30056-30057 Insert 1 Temp

30071-30072 Insert 8 Temp

30073-30088 Fan Areas

-20 to 160float °F4

30073-30074 Fan 1 Area

30087-30088 Fan 8 Area

4 30202 word Float word order0: high word first;1: low word first

float Sq.Ft 0 to 49.994

TM_G

Tx10

8_R

1C

NOTE: For GTM108 BACnet IP operation, use port 47808.

NOTE: For GTM108 Modbusoperation, use port 502.Modbus IP is always enabledregardless of *BAC MODEsetting.

Page 17: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 17

TM_G

Tx10

8_R

1A

GTC108 - TRANSMITTER SETUP FOR RS-485 NETWORK OPERATIONFor RS-485 operation, network connections are made on the GTC108 Combination board as shown in Figure 8, and setup is as follows. Network protocol, MS/TP address, device instance number and baud rate options are all selected with-in the NETWORK menu shown in Appendix B.

GTC108 - RS-485 Network Options and Communications Menu SettingsThe transmitter is shipped from the factory with the protocol set for BACnet MS/TP Master, address 2, MS/TP Device ID2, Baud rate of 76,800 and no termination. Initial RS-485 communications settings are accomplished within theGTC108 Communications Setup menu shown in Appendix B. Termination is set up by the TERM DIP switch SW3 locat-ed on the Combination card shown in Figure 8.

GTC108 - Setting Transmitter Termination for RS-485 NetworkThe GTC108 is shipped with the Termination switch set for No termination, which is the recommended setting for devicesinstalled on the network bus anywhere EXCEPT at the ends of the bus/segment. EBTRON recommends the followingtermination strategy for devices connected at the ends of the network bus/segment:

The device at one end of the network should be terminated with “End of Line” (or 120 ohm standard) termination,and the device at the other end should be terminated with “Fail Safe Bias” termination. This method will provideproper network termination and will ensure that the bus is in a known state during idle-line conditions (when nodevices are driving the bus). EBTRON GTC108 transmitters include all three termination options for “NoTermination”, “End of Line” (standard 120 ohm) or “Fail-safe Bias” (recommended at one end of the bus).Termination is selected by setting the TERMINATION DIP switch SW3” (Figure 8) on the Combination board.

GTC108 - Setting RS-485 Network ProtocolTransmitter protocol can be set for MS/TP or MODBUS as shown in the NETWORK submenu (Appendix B). Tables 5 and6 list the specific features of each protocol.

GTC108 - Setting Transmitter AddressThe GTC108 is factory set to an address of 2. Each transmitter must be assigned a unique address between 1 and 255(127 BACnet) prior to connecting it to the network by setting the address in the NETWORK submenu (Appendix B).

GTC108 - Setting Baud RateThe GTC108 transmitter is set at the factory for an MS/TP baud rate of 76,800 baud and can be changed if necessaryusing the GTC108 Communications menu (Appendix B). For MODBUS operation, baud rate is factory set at 19,200 butis adjustable as shown in the GTC108 Communications setup menu (Appendix B).

GTC108 - Setting Modbus ParityWhen using Modbus communications protocol, Parity can be changed in the NETWORK submenu. Parity can be set forEven (default), Odd, None 1 (with 1 stop bit), or None 2 (with 2 stop bits).

GTC108 - Setting Device Instance NumberThe GTC108 is factory set with a Device Instance Number of 2. The Device Instance Number can be set as shown in theNETWORK submenu (Appendix B). The Device Instance Number can also be changed to any number between 0 and4,194,302 by writing to the Device Object's Object Identifier Property over the network.

GTC108 - Resetting Communications Options to Factory Default ValuesCommunications options can be reset to factory default values (asterisk) * values using the GTC108 RESET NET menuoption as shown in Appendix B.

Check the network/network segment to ensure that only one device is terminated with either of these methods. If multiple devices are terminated as described above, network segment operation will be adversely affected.

TM_G

Tx10

8_R

1A

Page 18: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

GTM108 - TRANSMITTER SETUP FOR ETHERNET NETWORK OPERATION An RJ45 network connector is provided on the GTM108 Ethernet/Analog combination board as shown in Figure 9. Theuser can manually select network protocol (BACnet/IP or BACnet Ethernet - MODBUS TCP is always enabled), IP addressand device instance number, or can set the GTM108 to automatically configure itself when used on a network/segmentwith a DHCP server. By default, the DHCP setting is OFF (*DHCP=OFF) for manual device configuration, with BACnet IPprotocol (BAC MODE=IP), a static IP address of 10.0.0.100, a subnet mask of 255.255.255.0, and with gateway set for10.0.0.10. These values can be changed within the COMM menu (Appendix B) as described below.

When IP configuration is complete, confirm IP communications locally by “pinging" the assigned GTM108 IP address andobserving 5 rapid blinks of the ACTIVITY LED (Figure 9).

GTM108 - Ethernet Network Options and Communications Menu SettingsTo access the NETWORK submenu, simultaneously depress and release the UP and DOWN arrow buttons on the GTM108so that it displays SETUP, and then press the ENTER button to navigate to the NETWORK submenu as shown in AppendixB. Depress the ENTER button and navigate to the desired menu item using the UP/DOWN arrow keys as shown, and asdescribed below.

NOTE FOR MANUAL IP SETTINGS (*DHCP=OFF):In order to change GTM108 IP settings, DHCP must first be disabled. While in the NETWORK menu, navi-gate to the DHCP menu item, and ensure that *DHCP= OFF is set.

GTM108 - Selecting Static or Dynamic IP SettingsFor automated device configuration on a network/segment with a properly operating DHCP server, set *DHCP=ON asshown in Appendix B. Then, set *BAC MODE= for BACnet/IP (factory default) or BACnet Ethernet operation, and set *DI=device instance number (factory default=2) as described below. No additional device configuration is required.

For manual device configuration of the GTM108, set menu item *DHCP=OFF (factory default) as shown in Appendix B.When manually changing IP settings (*DHCP=OFF), the display will blink the 3-digit address segment that is underchange. Change the blinking segment by pressing the UP or DOWN buttons to arrive at the desired segment setting.Depress the ENTER key to set this segment and to move the blinking cursor to the next (right) segment. Repeat this untilthe last segment has been selected, and then depress ENTER to store the new address setting.

GTM108 - Setting Ethernet Transmitter IP AddressThe GTM108 is factory set with an IP address of 10.0.0.100. Each transmitter must be assigned a unique address onthe network/segment it is connected to. To change the IP address, navigate to the *IP=10.0.0 menu item as shown inAppendix B and set segments as previously described. (See note above regarding *DHCP=OFF).

GTM108 - Setting Subnet MaskTo change this value, navigate to the *MASK=255.2... menu item as shown in Appendix B, and set new segment valuesas previously described. (See note above regarding *DHCP=OFF).

GTM108 - Setting Gateway IPTo change this value, navigate to the *GATE=10.0.0... menu item as shown in Appendix B, and set new segment valuesas previously described. (See note above regarding *DHCP=OFF).

18 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

1A

Page 19: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 19

GTM108 - Setting BACnet Protocol ModeThe GTM108 is factory set with *BAC MODE=IP for BACnet IP protocol operation. This menu item can be changed to*BAC MODE=ETH for BACnet Ethernet protocol as shown in Appendix B. Tables 5, 6 and 7 provide detail of BACnetObjects, Modbus Register Maps and TCP/IP examples respectively. Note that Modbus IP is always enabled regardless of*BAC MODE setting.

NOTE:For BACnet IP operation, use port 47808. For Modbus TCP operation, use port 502. Modbus IP is always enabled regard-less of the *BAC MODE setting.

GTM108 - Setting Device Instance NumberThe GTM108 is factory set with a Device Instance Number of 2 (*DI=2). The Device Instance Number can be set to anyvalue between 0 and 4194302 as shown in Appendix B. The Device Instance Number can also be changed by writing tothe Device Object's Object Identifier Property over the network.

GTM108 - Resetting Communications Options to Factory Default ValuesCommunications options can be reset to factory default values (asterisk) * values using the GTM108 RESET NET menuoption as shown in Appendix B.

GTM108 - ETHERNET WIRING CONNECTIONSEnsure that the transmitter network settings have been properly set up as previously described. Ensure that the powerswitch is in the “OFF” position. Connect the 10/100 base-T ethernet connection (RJ45) to the female connector on theoutput card as shown in Figure 9.

Tables 5 and 6 list the specific values provided for BACnet and Modbus communication protocols.

TCP/IPhttp://10.0.0.100

(or your custom IP address)

Table 7. GTM108 TCP/IP Example

GTM Data

Page 20: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GTL108 - LONWORKS TRANSMITTER SETUPThe GTL108 includes a full featured LonWorks compatible interface. The EBTRON LonWorks output card (part number800-5030) plugs directly onto the GTL108 main circuit board as shown in Figure 10. It includes a high speed FTT-10A,78k baud Free Topology transceiver interface that is relatively insensitive to network wiring topology. The GTL108 maybe pre-configured using the EBTRON_108.XIF file available for download at:http://www.ebtron.com/downloads/EBTRON_108.XIFor configured at installation via direct LonWorks parameter upload from the GTL108 transmitter. A service push-buttonand LED are provided for standard installation. A “Wink” LED is provided for easy device identification. An “Activity” LEDand separate transmit and receive “TX” and “RX” provide visual indication of transmitter and communication status. The“Activity” LED normally flashes on for 1 second, off for 1 second when the card is commissioned and online, and remainsilluminated constantly if there is an error.

To wire the output signal, slide the cover plate up and off of the enclosure. Ensure that the power switch is in the “OFF”position. Connect network cables to the small, three position output terminal labeled “OUTPUT” on the upper left handside of the main circuit board (shown below) at terminals 1 and 2 only.

GTL108 - LONWORKS NETWORK CONNECTIONSConnect the transmitter output to the LonWorks bus in a "daisy-chain" configuration using a LonWorks approved cable.The transmitter provides an output that is isolated from the main power input. Connect the LonWorks cable at the “OUT-PUT” terminal block as follows:

OUTPUT TERMINAL SIGNAL DESCRIPTION

1 NET+2 NET-

COM COMMON (NOT USED)

Figure 10. GTL108 LonWorks Transmitter Interior Detail

CAUTION HOT

GTx116 Main

ON

OFF

ESC ENTERPGM

CONTRAST

24VAC INL2 L1

OUTPUTCOM

POWER

REPLACE WITH

1.5 AMP

FAST ACTING ONLY

EBTRON INC.400-1810 REV. J

U11U10U9

J6

U4

D4

U1

C1

VR1

J4L1

Z1

D2

D1

C5

HS2HS1

VR2

C6

C4C3

C2

R5R4

R3

LCD1

R2

J1

F1 J2

J3

SW1

R1

EG1

R26R25

R24R23R22R21

R20

R19R18

R17R16R15

R14

R13

R12

R10

R11

U8U7

U3

U6

U24U23U22U21

U20U19U18U17

U16U15U14U13

U12

R6

R59R58R57

R56R55R54R53R52R51R50R49

R48R47R46R45R44R43R42R41

R40R39R38R37R36R35R34R33

R32R31R30R29R28R27

U5

U2

C9C8

C12C11

C7

C22C21

C20

C19

C18

C17

C16C15C13

C10

C14

R9R8

R72R71R70

R7

R69R68R67R66R65

R64R63R62R61R60

+

+

MH1

D3

C23

J7

J8

XTAL1

TP1

TP9TP8TP7TP6TP5TP4TP3TP2 TP17TP16TP14TP13TP12TP11TP10 TP15

SW5SW4SW2 SW3

D1

D4D3

C4

C3

C6

U2

MH1

U1

U3

R1

C5

C2

MH3

C1

EBTRON, INC.400-1850 REV. E

GTL116 LOut

SERVICE

WINK

YEL

GRN

MH2

C15

C16

U6

C8

R7 R8

D6SW1

R4

R10R9

R6

D7

D5

C7

J1

XFMR1

SG1 SG2

D21

10

1

+

+1

U4

C11C10

C9

C14

C12

C13

XTAL1U5

J2

R3R2

R5

1

64

33

32

1

1

10

1 - (connect to network)

2 - (connect to network)

COM - Not used

LonWorks Output CardP.N. 800-5030

LCD Display

Power Switch

TX LED Green

RX LED Green

Service LED Yellow

Service Button

Wink LED Green

Transmitter Status LED.(Green 1 second flash normal;

2 second flash for fault)

Activity LED Red

20 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

1A

Page 21: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GTL108 - LONWORKS INTERFACE

IntroductionThe Ebtron LonWorks interface adapter is designed to provide an output capability for connection to an EchelonLonWorks based network. Two basic function blocks are provided. These include a node object and a gtx108 functionblock.

The node object is used for overhead activities on the LonWorks bus. This object is of little interest to the end user.

The gtx108 function block contains a set of network variables and configuration properties that allow the end user tomonitor various parameters related to airflow, pressure, and temperature that are generated by the transmitter.

Basic DescriptionThe LonWorks protocol is based on "network variable objects"("nvo"). Each device on the network communicates withother devices by "connecting" to the variables of the device it wishes to monitor. These variables consist primarily of pre-defined types that are part of the network specification.

Additionally, a special class of network properties is defined to allow the configuration of various parameters within adevice. These are intended to control the basic operation of a device.

All network variables are defined in terms of "SNVT_xxx". SNVT is an acronym for Standard Network Variable Type. "xxx"is a descriptive phrase that relates to the units used by the parameter represented by the variable. All of the variablesdescribed below are always visible on the network; however, some variables are meaningful only with certain types ofsensors attached to the transmitter. Tables 8 through 11 describe each of the variables used and the configuration prop-erties for each.

All configuration properties are defined in terms of "SCPTxxx". SCPT is an acronym for Standard Configuration PropertyType. There are configuration properties that apply to multiple objects, but may not be listed directly under them whenviewed on the network. Check the "applies to" tag in the description for the configuration property in the following sec-tions.

21EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTERTM

_GTx

108

_R1

A

Units are shown as default values and, depending on software used, may be set automatically by location.NOTE

Page 22: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

GTL108 - VELOCITY AND FLOW VARIABLES CONFIGURATIONThis section details the air flow and air velocity variables and how the configuration properties relate to them.

Velocity and Flow Variables

nvoAirVel (SNVT_speed_mil - Air Velocity)This variable provides simple linear airflow in meters/second.

nvoAirFlow (SNVT_flow - Airflow)This variable provides volumetric airflow in liters/sec.

nvoAirFlowFl (SNVT_flow_f - Airflow Float)This variable provides volumetric airflow in liters/sec.

nvoAirFlow1-8 (SNVT_flow - Airflow)These variables provide volumetric airflow for fans 1-8.

Velocity and Flow Configuration Properties

nvoAirVel (SCPTmaxSendTime - Maximum Time Between Updates)This configuration property sets the maximum time to elapse between updates to the network for velocity and flow to occur.

nvoAirVel (SCPTminSendTime - Minimum Time Before Updates)This configuration property sets the minimum time to elapse before an update to the network for velocity and flow maybe sent. This configuration property takes priority over maxSendTime and sndDelta.

nvoAirVel (SCPTsndDelta - Minimum Change for Update)This configuration property sets the minimum change in velocity that will cause an update of flow and velocity to the net-work. The change is only checked for in velocity, and when the minimum is reached updates will occur for nvoVel,nvoFlow, and nvoFlowFl.

Variable Name SNVT Measurement Type Category TypeResolution Units

nvoAirVel SNVT_speed_mil Linear Velocity Unsigned Long 0.001 m/snvoAirFlow SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlowFl SNVT_flow_f Flow Volume Floating Point n/a l/snvoAirFlow1 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow2 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow3 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow4 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow5 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow6 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow7 SNVT_flow Flow Volume Unsigned Long 1 l/snvoAirFlow8 SNVT_flow Flow Volume Unsigned Long 1 l/s

Air Flow Sensor Objects

nvoAirVel SCPTmaxSendTime Time Signed Long 0.1 SecondsnvoAirVel SCPTminSendTime Time Signed Long 0.1 SecondsnvoAirVel SCPTminDelta Linear Velocity Unsigned Long 0.001 m/s

Air Flow Sensor Configuration Properties

Table 9. GTL108 LonWorks Node Velocity and Flow Configuration Properties

Table 8. GTL108 LonWorks Node Velocity and Flow Variables

22 EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GOLD SERIES GTX108 TRANSMITTER

TM_G

Tx10

8_R

2A

Page 23: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 23

Temperature Variables and Configuration PropertiesThis section details the temperature variable and how the configuration properties that relate to it.

nvoTemp (SNVT_temp_p - Temperature Variable)This network variable provides temperature in degrees Celsius.

nvoTemp1-8 (SNVT_temp_p)These variables provide temperature for fans 1-8.

Temperature Configuration Properties

nvoTemp (SCPTmaxSendTime - Maximum Time Between Updates)This configuration property sets the maximum time to elapse between updates to the network for temperature to occur.

nvoTemp (SCPTminDeltaTemp - Minimum Change for Update)This configuration property sets the minimum change in temperature that will cause an update of nvoTemp to the net-work.

nvoTemp (SCPTminSendTime - Minimum Time Before Updates)This configuration property sets the minimum time to elapse before an update to the network for temperature may besent. This configuration property takes priority over maxSendTime and minDeltaTemp.

GTL108 - DEFAULT DELTA VALUESThe default Delta values determine when updates are sent from the transmitter to the network. The factory default Deltavalues are set to a large enough value to prevent any undesired messages from being sent to the network. Refer to thepreceding paragraphs for description and configuration of the Delta values.

nvoTemp SCPTmaxSendTime Time Signed Long 0.1 SecondsnvoTemp SCPTminDeltaTemp Temperature Signed Long 0.001 Degrees CnvoTemp SCPTminSendTime Time Signed Long 0.01 Seconds

Temperature Sensor Configuration Properties

Table 11. GTL108 LonWorks Node Temperature Configuration Properties

Variable Name SNVT Measurement Type Category TypeResolution Units

nvoTemp SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp1 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp2 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp3 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp4 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp5 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp6 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp7 SNVT_temp_p Temperature Signed Long 0.01 Degrees CnvoTemp8 SNVT_temp_p Temperature Signed Long 0.01 Degrees C

Temperature Sensor Object

Table 10. GTL108 LonWorks Node Temperature Variable

Page 24: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com24

GTx108-F TRANSMITTER START-UP, INITIALIZATION AND SETUP MENUSTo ensure a successful start-up, verify that the airflow measuring station and transmitter are installed in accordance withEBTRON guidelines.

Move the power switch to the “ON” position. The transmitter executes a complete self-check each time the power isturned on that takes 10 seconds to complete.

The GTC108 and GTM108 default analog output signals are set to 4-20mA. The output signal can be changed to 0-5VDC/0-10VDC using board by setting switches SW1, SW2 and then entering the desired setting in the Setup menu. TheGTC108, GTM108 and GTL108 must be properly configured based on the system network protocol. Review the sectionfor the corresponding transmitter output card or contact EBTRON Customer Service, toll free, at 800-232-8766.

Transmitter Initialization and Setup MenusThe GTx108-F Transmitter automatically initializes at power-up and conducts full system diagnostics. At the first start-up, the system will initiate the Setup Wizard that guides the user through the setup of the transmitter. When completed,the Setup Wizard will store all values entered. If not completed, the Setup Wizard will again restart at the next power-upof the transmitter. Navigate through the menus as shown in Appendix B.

Changing the System of Units - IP units or SI UnitsThe GTx108 transmitter is provided with the system of units set to I-P. To change to S.I., simultaneously press and releasethe “ENT” and “ESC” buttons during normal operation. “IP/SI UNITS” will be indicated on the LCD display. Refer toAppendix B SYSTEM OF UNITS MENU for details on the System of Units menu. Note that Setup Menu items are shownin IP System Of Units. When SI System of Units is selected, the units of measure abbreviations used in the menus isshown in Table 12.

GTx108 TRANSMITTER CALIBRATIONThe GTx108 uses high quality industrial grade components and is designed for years of trouble-free operation. Periodicrecalibration of the transmitter is neither required or recommended. Transmitter field calibration verifiers are availablefor purchase from EBTRON for installations requiring periodic validation of instrumentation. Contact EBTRON for moreinformation.

GTx108 LCD DISPLAY NOTIFICATIONSFollowing a brief initialization at power up and following completion of the Setup Wizard, the LCD display automaticallydisplays airflow and temperature with units of measurement in all upper case (caps) characters. The display providesadditional information on system status and alarm conditions. Refer to the ALARM FEATURES section of this manual foradditional detail on Alarm and Trouble Error code indications.

Factory Default Menu Settings for GF2 (-F) Sensor ProbesThe GTx108 transmitter is “plug and play” and does not require setup unless a network option is selected that requiresconfiguration. Table 13 shows the factory default settings for all compatible sensor probes.

To change the Factory Default Settings, see: CHANGING FACTORY DEFAULT SETUP MENU SETTINGS.

TM_G

Tx10

8_R

1A

Check the physical installation, power connections and model specific signal wiring prior to turning the power switch to the “on”position.

“IP” System of Units Description “SI” System of Units DescriptionFPM Feet per minute MPS Meters per secondCFM Cubic feet per minute LPS Liters per secondSQF Square feet SQM Square meters

F Fahrenheit C Celsius

Table 12. Standard “IP” and “SI” Menu Units Abbreviations

Page 25: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 25

TM_G

Tx10

8_R

1A

Display Description I-P S.I.AIRFLOW= Airflow measurement method, Actual or Standard. ACT ACT*LCDU/M= Airflow units of measure ACFM LPS

*AREA= Free area where station is located (required for volumetric measurement)0.00 sq.ft.(see note)

0.000 sq.meters(see note)

*AO1 SGNL= GTC/GTM108 output 1 signal type voltage or mA (airflow) mA mA*AO1 UM= Output 1 units of measure AFPM MPS*AO1 FS= GTC/GTM108 output 1 signal full scale 10,000 FPM 50 MPS*LLIMIT= GTC/GTM108 low limit cutoff 0 AFPM 0 MPS*FLOW ADJ= Output 1 Offset-Gain On/Off Off Off*GAIN= Output 1 Gain factor 1.000 1.000*OFF= Output 1 Offset factor 0.000 0.000*TEMP METH= Temperature Averaging Weighted Avg. Weighted Avg.*AO2 SGNL= GTC/GTM108 output 2 signal voltage or mA (temperature or alarm) mA (see alarms) mA (see alarms)*AO2 MS= GTC/GTM108 output 2 signal minimum scale -20º F -30º C*AO2 FS= GTC/GTM108 output 2 signal full scale 160º F 70º C*LCD INTG= Number of flow calculations to be averaged for LCD display. 100 100*AO1 INTG= Number of flow calculations to be averaged for AO1 output. 30 30*EB-LK INT= Number of flow calculations to be averaged for EB-Link readings. 300 300*ALT= Altitude for flow correction relative to mean sea level (0 ft). 0 ft 0 m*AO2 ASGN = TEMP AO2 Output indicates temperature. TEMP TEMP

*SETPNT=Alarm setpoint value. When AO2 ASGN=ALARM , or AAO2 ASGN=FA only, operates in conjuction with TTOL= value.

0 0

*TOL=Alarm range tolerance value. When AO2 ASGN=ALARM , or AO2 ASGN=FA only, this setting establishes the alarm range relative to the SSETPNT= value.

10% 10%

*NO FAULT=

Sets the AO2 normal (not alarm) output state relative to the full scale analog output selected. HHI provides maximum full scale under normal conditions and minimum scale during alarm. LLO provides minimum full scale under normal conditions and maximum scale during alarm.

HI HI

*DELAY= Time that the alarm condition must exist before alarm output is activated. 2 minutes 2 minutes

*ZERO OFF =Set to YYES to inhibit LO alarm condition when flow reading is zero (dependent on LLIMIT= setting). Set to NNO to disable this feature.

NO NO

*RESET =Set to AAUTO to have alarm self-clear when alarm condition no longer exists. Set to MMANUAL to require manual reset of alarm.

AUTO AUTO

Note: For volumetric measurements (CFM/LPS) using Fan Inlet GGF1, GF2 sensors, the probe free area MMUST be manually calculated and eentered in the transmitter .

Table 13. Factory Default Menu Settings

Page 26: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com26

GTx108 CHANGING FACTORY DEFAULT SETUP MENU SETTINGSSetup Menu OptionsThe GTx108 Transmitter is setup and tested at the factory to be fully operational when sensor probes are connected andpower is applied (set the power switch to the “ON” position). Factory settings can easily be changed using the SETUPMENU by simultaneously pressing and releasing the “UP” and “DOWN” buttons while the transmitter is in its normal oper-ating mode. Navigate through the menu using Appendix B to make changes to the transmitter configuration. The settingstake effect immediately. The following are common field modifications to the factory default settings.

Selecting Actual and Standard Output Measurement TypeThe transmitter is set from the factory to provide actual airflow measurement units (displayed as “ACFM” and “AFPM”).In this mode, airflow measurements are calculated for actual inlet conditions. If using Actual conditions, corrections foraltitude are entered through the ALT= setting in the Setup menu. If desired, the output can be set to provide standardairflow measurement units (displayed as “SCFM” and “SFPM) which provides measurements that are corrected to stan-dard conditions.

Output ScalingEBTRON’s Gold Series sensors are individually calibrated between 0 and the factory default full scale to standards inwind tunnels traceable to the National Institute of Standards and Technology (NIST). Sensors are independent and pro-duce “percent of reading” accuracy. Changing the full scale does not change the accuracy of the device). Factory defaultoutput scaling for analog GTC108 and GTM108 transmitters can be changed using setup menus of Appendix B.

Changing the LCD Display from Volumetric Flow CFM to Velocity FPMThe GTx108 transmitter is shipped from the factory to indicate volumetric flow. For -F probes, the free area for the instal-lation is entered in the SETUP WIZARD. To display velocity in FPM, enter the Setup Menu and in the DISPLAY submenu,change the “*LCD UM=ACFM” to “*LCD UM=AFPM”. Changing the LCD display units will not affect the analog output sig-nal. The analog output signal can be scaled if required as described below.

Converting the Analog Output Signal from FPM to CFMThe GTx108 transmitter is shipped from the factory with analog output“OUTPUT 1” set to indicate velocity in AFPM. Toautomatically convert this analog velocity output to volumetric flow (ACFM), simply set the *AO1 UM from AFPM (default)to ACFM in the Setup Menu (Appendix B). If you wish to manually convert the velocity output to volumetric flow (ACFM),simply multiply the indicated output velocity (in FPM) by the free area of the air flow probe installation location. For -Fsensor probes, determine the free area following installation in accordance with the installation guidelines. Refer alsoto Table 4 for a complete listing of conversions for each of the analog outputs of the GTx108. The AO1 full scale analogoutput (OUTPUT1 ) value is determined by the AO1 FS setting within the SETUP MENU.

Locking the Configuration SettingsThe GTx108 transmitter configuration settings can be locked at one of three security levels within the SECURITY sub-menu using the LOCK SEC= item.

When LOW security level is selected (LOCK SEC=LOW) the last 4 digits of the board serial number are automaticallyassigned as the lock code. To see the board serial number, navigate to DIAGNOSTICS menu in SERIAL NUMBERS item.

When the MED security level is selected (LOCK SEC=MED) the user enters a security code. In the event that this codeis lost/misplaced, EBTRON can provide a key that is unique to the transmitter to unlock it. Contact EBTRON customerservice for this code.

When the HIGH security level is selected (LOCK SEC=HIGH) the user enters a security code. In the event that this codeis lost/misplaced, the transmitter must be returned to the factory in order to unlock it.

TM_G

Tx10

8_R

1A

When LOCK SEC=HIGH is selected, the user defined setting can only be changed after entering the user defined code. STORE THELOCK CODE IN A SAFE LOCATION! For security reasons, the HIGH level lock code can only be reset by returning the transmitter tothe factory.

Page 27: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

1A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 27

VIEWING SENSOR DATAViewing Sensor Data on the Local LCD DisplayAirflow and temperature of individual fan sensors can be displayed on the local LCD display by entering the DiagnosticMenu. Simultaneously depress the up � and down � arrows to enter the GTx108 Setup Menu, and then navigate to theDiagnostic Menu as shown (Appendix B).

Viewing Sensor Data over BACnet or Modbus Networks or through the EB-Link Reader Airflow and temperature of individual sensors can be read across BACnet or Modbus networks, or downloaded directlyto an EB‐Link Reader if the infra‐red EB‐Link option has been installed. Refer to the following Sensor Addressing andProbe Positioning paragraph for the suggested probe installation configuration. Tables 5 and 6 provide BACnet objectsand register addressing information for individual sensor data.

Sensor Addressing and Probe Positioning

Sensors are automatically addressed after power is applied to the transmitter as follows: Type ‘B’ (4 Connector) TransmittersThe probe that is connected to the left-most used receptacle (labeled C1-C4) on the transmitter is addressed as probe1. Up to 4 sensors can be individually viewed. To standardize installation and decoding of the data, EBTRON suggeststhe sensor probe mounting convention as shown in Figure 12 and Table 14 as viewed from fan inlet.

Type ‘C’ (8 Connector) TransmittersProbes are statically numbered. The probe that is connected to the upper row and left-most receptacle (labeled C1) onthe transmitter is addressed as probe 1. Up to 8 sensors can be individually viewed. To standardize installation anddecoding of the data, EBTRON recommends the sensor probe mounting convention as shown in Figure 12 and Table 14as viewed from fan inlet.

When a probe is disconnected and then plugged in to a different port, the transmitter will re-discover it within 15 sec-onds and make any necessary addressing adjustments.

For fan arrays, the fan information provided is specific to the numbered connector.

TYPE B TRANSMITTER TYPE C TRANSMITTER

C1 C2 C3 C4 C5 C6 C7 C8

C1 C2 C3 C4

Figure 11. GTx108 Transmitter Connector Diagram

Page 28: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com28

TM_G

Tx10

8_R

1A

Figure 12. Suggested Sensor Configurations (for Traverse decoding and EB-Link Data)

SINGLE WIDTH SINGLE INLET (SWSI) ANDDOUBLE WIDTH DOUBLE INLET (DWDI) - SUGGESTED SENSOR CONFIGURATIONS

SWSI FANS DWDI FANS

FAN ARRAYS - SUGGESTED SENSOR CONFIGURATIONS

Refer to Fan ArraysSuggested SensorConfigurations on fac-ing page.

Page 29: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 29

TM_G

Tx10

8_R

1A

Table 14. Fan Arrays Suggested Sensor Configurations (for Traverse decoding and EB-Link Data)

FAN ARRAYS - SUGGESTED SENSOR MOUNTING CONFIGURATIONS

Page 30: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com30

TM_G

Tx10

8_R

1A

EB-Link WIRELESS INFRARED COMMUNICATIONS OPTIONThe EB-Link wireless infrared communications option is ideal for air balance contractors, engineers, building ownersand/or contractors who desire fast and accurate measurement without additional interfacing. Individual and averagesensor airflow(s) and temperature(s) from GTx108 transmitters equipped with the EB-Link option can be instantly trans-ferred to the new EB-Link Reader model ELR-1 or to a Palm® or Microsoft® Windows Mobile® operating system PDA. Thismethod reduces the data acquisition time and sampling error inherent with hand held measurements. The data can thenbe transferred to your PC for review, update or analysis.

In addition, a Setup-Upload feature (available only with the PDA software version) permits rapid transfer of preset trans-mitter setup configuration to another EB-Link equipped GTx108 transmitter. This is especially useful when multiple trans-mitters are to be set up or modified.

Real-time duct flow/temperature traverses can be accomplished quickly and easily using the GTx108 transmitterequipped with the EB-Link option. Individual airflow and temperature data can be returned directly to your EB-LinkReader or PDA (using Palm® or Microsoft® Windows Mobile® operating system). The data can also be returned overBACnet or Modbus when probes are connected to a type GTC108 RS-485 networked transmitter.

This innovative feature is ideal for balancers and commissioning agents that desire “on-the-fly” airflow and temperaturetraverses. The advantages of using permanently installed GF2 sensors include nearly instantaneous traverse data (nosampling error over time), accurate and repeatable measurement and simple report generation using the Microsoft®

Excel® spreadsheet provided by EBTRON. Performing duct traverses with permanently mounted EBTRON airflow probesor sensors eliminates the requirement to make additional sampling holes in the duct, and reduces the need to carryaround the job site cumbersome equipment and ladders to accomplish them.

EB-Link Card Installation

The EB-Link card must be installed on the GTx108 main board in order to access sensor data with your PDA. If the EB-Link card is ordered separately from the transmitter, it should be installed after the transmitter is mounted.

To install the EB-Link option card, slide the cover up and off of the transmitter enclosure. Turn the power switch to the“OFF” position on the transmitter main circuit board. Observe ESD precautions when handling and installing the EB-Linkcard. Touch a grounded object, such as a metal duct, before removing the EB-Link card from the anti-static package.Remove the EB-Link card from the anti-static package, being careful not to touch exposed components or circuit boardtraces (hold the card by the edges as indicated on left frame of Figure 13). With the components facing in towards thecenter of the main circuit board, carefully plug the EB-Link card into the header connector labeled J5 on the right handside of the transmitter just below the LCD display (center frame, Figure 13). Do not press on any components. The cardshould stand on its own when properly installed (right frame of Figure 13).

Figure 13. EB-Link Installation Detail

CAUTION: Observe all electrostatic Discharge (ESD) handling precautions. Do not touch internal components.Failure to observe ESD precautions can cause damage to components.

CAUTION: Turn the transmitter “POWER” switch to the “OFF” position before installing the EB-Link card. Failureto do so can cause damage to the EB-Link card and/or the transmitter.

Page 31: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 31

TM_G

Tx10

8_R

1A

Obtaining and Installing EB-Link SoftwareEB-Link software can be downloaded free of charge at:http://www.ebtron.com/support_GOLD.htm. Versions are available for the EB-LinkReader, or for PDAs (for either the Palm® or Microsoft® Windows Mobile® operating sys-tems) as shown in Figure 14. Figure 15 shows the EB-Link in use.

The software includes all of the files required for operation of the EB-Link Reader or forPDAs as well as a Microsoft® Excel® spreadsheet for converting the PDA files to a Testand Balance report.

EB-Link Reader SoftwareThe EB-Link Reader software is designed for operation on Windows XP (or later) oper-ating systems and permits file management and time synchronization for the EB-LinkReader.

The latest version of the EB-Link Reader software, as well as installation, operationand descriptions of all EB-Link Reader functions are contained in the EB-Link ReaderTechnical Documentation under separate cover (available at:http://www.ebtron.com/Ebtron_Home_OnlineLiterature.html.

EB-Link Software for PDA DevicesThe EB-Link Software for PDA Devices is designed for operation with PDA devices usingthe Palm® or Microsoft® Windows Mobile® operating systems. The software includes aMicrosoft® Excel® spreadsheet that allows for the pre-configuration, review or modifica-tion of GTx108 transmitter setup parameters.

The latest version of the software, as well as installation, operation and descriptions ofall EB-Link functions are contained in the readme.txt file that is provided with thedownload.

Real-time traverses can be accomplished quickly and easily using the GTx108 trans-mitter equipped with the EB-Link option. Individual airflow and temperature data canbe returned directly to your PDA (Palm® or Microsoft® Windows Mobile® operating sys-tem). Data can also be returned over BACnet or Modbus when probes are connectedto a GTC108, RS-485 transmitter.

Real Time Traverses Using EB-LinkSimply slide the GTx108 cover up and off of the GTx108 transmitter enclosure andpoint your EB-Link Reader or PDA to the EB-Link sensor located just to the right andbelow the transmitter LCD display as shown in Figure 15 (note: the EB-Link card optionmust be installed). The acquisition of data takes less than 10 seconds to complete.After acquiring data, you can display individual or average airflow and/or temperaturedata on your EB-Link Reader or PDA. Saved data (stored as a comma separated valueCSV file) can also be downloaded to your PC for creation of individual test and balancereports using the software of your choice, or with the Microsoft® Excel® spreadsheetthat EBTRON has included with the PDA software. Note that the traverse sensor datais averaged to provide more stable readings.

Note also that on rectangular ducts, the EBTRON Excel® balance report will alwaysshow the traverse data starting at the top left position of the duct when viewing fromupstream of the flow station, regardless of the orientation of the probes, when theprobes are installed as indicated in the configuration diagrams of Figure 12. Onround/oval ducts, the balance report will always show traverse data in columns, start-ing with probe number one.

If traverse data is desired, ensure that probes/sensors are installed using the mounting convention specified inFigure 12. Proper installation simplifies sensor location decoding during data analysis.

NOTE

Figure 15. Typical EB-LinkData Acquisition

Figure 14. EB-Link Readerand PDA Devices

EB-Link PDACommunication Detail

EB-Link ReaderCommunication Detail

EB-Link and PDA

EB-Link Reader

Page 32: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com32

TM_G

Tx10

8_R

1A

FIELD ADJUSTMENTSALTITUDE CORRECTION ADJUSTMENTThe Altitude Correction Adjustment allows for correction of airflow readings at the installed site altitude and more pre-cise readings regardless on installed altitude. Refer to the SETUP MENU of Appendix B for the *ALT= menu item, andset this value to the installation altitude.

FACTORY CALIBRATION ADJUSTMENTSThe factory calibration should not require adjustment if the sensor probes are installed in accordance with publishedinstallation guidelines. However, some installations may not meet placement guidelines or commissioning requirementsmay dictate field adjustment. Field adjustment may improve the “installed accuracy” of GTx108-F systems when deter-mining volumetric flow rates. Only the Output 1 signal, airflow rate, can be adjusted. Ensure that the reference deviceand technique used to determine the airflow rate in the field are suitable for such measurement. Select a location thatis acceptable for the device being used as the reference, recognizing that this may not be the same location where theEBTRON airflow station is installed. The inherent accuracy of field measurement will not be better than ±5% of readingand can often exceed ±10%. Do not adjust the output of the GTx108 if the difference between the transmitter and thefield measurement is less than 10%.

ADJUSTING THE LOW LIMIT CUTOFFThe low limit cutoff forces the output signal for the airflow rate to zero whenever the airflow rate calculated falls belowthe specified Low Limit value. This feature is useful on outside air intakes that often indicate false airflow rates, inducedby transient wind gusts or when the intake damper is closed and there is no net flow across the damper. Readings of100 FPM or more are not uncommon on many outside air intake applications when the intake damper is closed and area result of air movement in the intake plenum (not a malfunction in the airflow measuring device). Setting the low limitto a value significantly below the control setpoint and higher than the threshold flow for false wind readings simplifiescontrol and interpretation of the airflow rate signal on many applications.

To set the low limit cutoff, enter the Setup menu and set “*LLIMIT={desired value in FPM (MPS in SI units)}” as shownin Appendix B.

Field Adjustment Wizard - AUTOMATED FIELD ADJUSTMENT

Overview of the Field Adjustment WizardThe simple to use Field Adjustment Wizard provides a one or two point automated menu driven field adjustment to fac-tory calibration of the OUTPUT 1 airflow rate signal. (Only OUTPUT 1 is adjustable in this manner). The Field AdjustmentWizard allows engineers, contractors and owners to use EBTRON stable and linear flow meters at a more affordable cost,when field adjustment is necessary or acceptable in close-coupled installations where placement and/or sensor densi-ty may be inadequate to achieve specified "out of the box" accuracy.

Make sure that the reference measurement device and the technique used to determine the airflow rate in the field aresuitable for such measurement. Select a location that is acceptable for the reference measurement device, recognizingthat this may not be the location where the EBTRON airflow station is installed. The inherent accuracy of the field refer-ence measurement will not be better than ±5% of reading and can often exceed ±10%. Do not adjust the transmitteroutput of the if the difference between the transmitter and the field reference measurement is under 10%. In certain applications, manual adjustment of factory gain and offset calibration values can be performed as outlined inthe MANUAL ADJUSTMENT OF FACTORY OFFSET/GAIN CALIBRATION section of this manual.

Engaging and Using the Field Adjustment WizardUse Appendix B to navigate to the FIELD ADJUST submenu. Appendix B provides details of the FIELD ADJ WIZARD menuand how to use it in applications for one or two point automated field adjustment. If you wish to disable the FIELD ADJUSTsetting, navigate to the ADJUSTMENTS submenu and set FLOW ADJ=OFF.

Fluctuations in the airflow output signal are normal. EBTRON’s laboratory research indicates that dampening true fluctuationswill result in poor control and a larger dead-band of operation.

Page 33: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 33

TM_G

Tx10

8_R

1A

MANUAL ADJUSTMENT OF FACTORY OFFSET/GAIN CALIBRATIONIf you prefer, you can instead perform a manual adjustment at one or two points. The GTx108 firmware can be adjust-ed for Output 1 signal “gain” and “offset”. To adjust the output signal “gain”, the “FLOW ADJ” override must be set to“*FLOW ADJ=ON” from the Setup Menu. The adjustments affect both the LCD display and output signal. When “*FLOWADJ=OFF” is set, adjusting the output signal “offset” and/or “gain” does not affect the transmitter output.

Procedure for 1 Point Field AdjustmentSelect an airflow rate that represents a valid operating condition for the system. Set fan speed, dampers and VAV boxesto a fixed speed or position when measurements are taken. Complete the following worksheet to determine the gain set-ting to be set on the transmitter.

1. Enter the setup menu and set “*FLOW ADJ=OFF”. This is the factory default setting and disables any adjust-ments, returning the unit to its original factory calibration.2. __________Record the transmitter output by taking the visual reading from the transmitter LCD. Readings can betaken by the host controls if the output signal conversion has been confirmed. Time averaging the data will improvefield recalibration.3. __________Record the reference reading. Make sure that the unit of measure (FPM, CFM) is identical for boththe transmitter and the reference. If the unit of measure is velocity (FPM), make sure that the reference airflowmeasurement was corrected for the area where the measurement was taken.4. __________Calculate the gain factor (m): m=line 3/line 2.5. Enter the setup menu and set “*FLOW ADJ=ON”. 6. Set “*GAIN={value calculated in line 4}”.7. Confirm that “*OFF=0.00”. 8. Press the “ESC” button until you return to the normal operating mode. Field adjustment is complete.

Procedure for 2 Point Field AdjustmentSelect the minimum and maximum airflow rate that the airflow station will encounter as a valid operating condi-tion for the system. Set fan speed, dampers and VAV boxes to a fixed speed or position when measurements aretaken. Complete the following worksheet to determine the gain and offset settings to be set on the transmitter.

1. Enter the setup menu and set “*FLOW ADJ=OFF”. This is the factory default setting and disables any adjust-ments, returning the unit to its original factory calibration.2. Set the minimum airflow rate.

3. __________ Record the transmitter airflow rate by taking the visual reading from the transmitter LCD. Readingscan be taken by the host controls if the output signal conversion has been confirmed. Time averaging the data willimprove field recalibration.4. __________ Record the reference airflow rate. Make sure that the reference airflow measurement was correct-ed for the area where the measurement was taken.5. Set the maximum airflow rate.

6. __________ Record the transmitter airflow rate.

7. __________ Record the reference airflow rate.

8. __________ Calculate the gain factor (m): m=(line 7 - line 4)/(line 6 - line 3).

9. __________ Calculate the offset factor (b): b=(line 4 - (line 8 x line 3).If more than 2 points are available, perform a linear regression on the data to determine gain and offset.10. Enter the setup menu and set “*FLOW ADJ=ON”.11. Set “*GAIN={value calculated in line 8}”.12. Set “*OFF={value calculated in line 9}”. OFFSET must be entered in FPM. If calculated in CFM divide by areacalculated for station. If fan array, divide the calculated FPM value by total number of fans before entering intotransmitter.13. Press the “ESC” button until you return to the normal operating mode. Field adjustment is complete.

Page 34: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com34

MAINTENANCEWhen transmitter and probes are installed in accordance with EBTRON guidelines, instrument difficulties are rare. Issuesmay easily be resolved by viewing Diagnostic data from the Diagnostic Menu (Appendix B) and by proceeding through thefollowing troubleshooting guides (Tables 15 through 19). Customer support is available Monday - Thursday from 8 AMto 5:00 PM ET, and Friday from 8 AM to 2:20 PM ET at 800-2EBTRON (232.8766). EBTRON Diagnostic Customer Serviceforms are available on-line at www.ebtron.com to assist us in accurately diagnosing issues and will greatly expedite theirresolution. A sketch of the installation, along with the control sequence of operations is recommended to help us diag-nose problems. Fax the information to 843.756.1838 before you call, and have it available when speaking with theCustomer Service team. Address all correspondence to the EBTRON Customer Service Department. Additional informa-tion is also available from your local EBTRON representative.

STANDARD LIMITED PARTS WARRANTYIf any EBTRON product fails within 36 months from shipment, EBTRON will repair/replace the device free of charge asdescribed in the company’s warranty contained in EBTRON’s TERMS AND CONDITIONS OF SALE. Defective equipmentshall be shipped back to EBTRON, freight pre-paid, for analysis.

Page 35: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 35

TM_G

Tx10

8_R

1A

Problem Possible Cause RemedyNo LCD display indication and the green TransmitterStatus LED (D3) on the main circuit board is not illumi-nated.

Power switch not in the "ON" position. Move the power switch to the "ON" position.

Improper supply voltage to the power input terminalblock.

Ensure that 24VAC power is connected to L1 and L2 ofthe POWER terminal block and that the voltage with thepower switch in the "ON" position is between 22.8 and26.4 VAC.

Blown fuse. Check power wiring. Ensure that multiple devices wiredon a single transformer are wired "in-phase". Replacefuse only with a 1.5 amp, fast-acting fuse after the prob-lem has been identified and corrected.

No LCD display indication and the green TransmitterStatus LED (D3) on the main circuit board is flashing.

LCD contrast too low. Turn “Contrast” potentiometer on the main circuit board"clockwise".

The LCD display is scrambled or there is no LCD displayindication after touching the switches, LCD display or cir-cuit board.

Static electricity. Touch an earth-grounded object, such as a duct, to dis-charge static electricity then reset the power. Avoiddirect contact with the LCD display or circuit board.

The green Transmitter Status LED (D3) on the main cir-cuit board is "ON" but not flashing.

The microprocessor is not running. Reset 24VAC power by moving the power switch from the"ON" to "OFF" position and then back to the "ON" posi-tion.

The green Transmitter Status LED (D3) on the main cir-cuit board is flashing at 1-second intervals.

No problem, normal operation. No remedy required.

The green Transmitter Status LED (D3) on the main cir-cuit board is flashing at 2-second intervals.

The sensor detection system has detected trouble. Check sensor probe cable connections. If sensor probeconnections look OK and match the number of sensorprobes indicated on each probe's hang tag, please callEBTRON's customer service department or visit us atwww.ebtron.com.

Wrong type of sensor probes attached to transmitter.. GTx108 transmitter will only operate with GF2 sensorsconnected.

The transmitter indicates airflow when the HVAC systemis not operating.

Sensors are sensitive and can measure very low airvelocities. If a reading is indicated, there is airflow pres-ent where the airflow measuring station is located.

Do not attempt to adjust zero ("offset"). Doing so willresult in an error in airflow measurement. The Low Limitairflow cutoff value can be set to force the output signalto zero.

Table 15. General Troubleshooting (All GTx108 Systems)

Page 36: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com36

TM_G

Tx10

8_R

1A

Table 17. GTC108 RS-485 Transmitter Troubleshooting

Problem Possible Cause RemedyNo output signal can be measured at the OUTPUT termi-nal block of the GTC108/GTM108 transmitter.

Output card is not securely mounted on main circuitboard.

Turn the transmitter power "OFF", and then press theoutput card firmly onto main circuit board. Turn thetransmitter power back "ON".

Blown output fuse (output 1 and output 2 are fused andprotected independently on GTC108/GTM108 transmit-ters).

Make sure that power has not been connected to theoutput terminal block. Correct the problem and replacewith 0.125 amp, fast acting fuse only.

Make sure that the host control system is not configuredfor a 2-wire device (no excitation voltage should be pres-ent on the signals from the host controls). Correct theproblem and replace with 0.125 amp, fast acting fuseonly.

The Low Limit airflow cutoff value is above the actual air-flow reading.

Decrease the Low Limit airflow cutoff value in the Setupmenu until it is below the actual airflow reading.

The output signal on the GTC108/GTM108 transmitterfluctuates while the flow and/or temperature readingson the LCD are steady.

Electrical interference from other devices is creatingnoise in the signal wires to the host control system.

The output signal wiring must be shielded. Individuallyground one or more of the following points: the signalwire shield at host controls; signal wire shield at thetransmitter, or L2 of the power terminal block of theGTC108/GTM108.

The LCD INTG= value may be greater than the AO1 INTG= value.

Review and verify LCD INTG= and AO1 INTG= settings.

The LCD display does not match the readings indicatedby the host control system.

The scaling in the host control system is incorrect, or theAO1/AO2 RNGE= settings are incorrect.

Compare the current configuration of the transmitterwith that of the host control system. Compare the mini-mum and full scale settings for each output by navigat-ing through the Setup menu. Verify AO1/AO2 RNGE=settings

Problem Possible Cause RemedyThe host control system is unable to communicate withthe GTC108 transmitter.

Output card is not securely mounted on main circuitboard.

Turn the transmitter power "OFF" and press the outputcard firmly onto main circuit board. Turn the transmitterpower back "ON".

Network signal wiring is not properly connected to theGTC108 transmitter or the host controls.

Verify that the network signal wires from the host con-trols are connected to the proper terminals of the termi-nal block. On the GTC108 transmitter NETWORK termi-nal block, NET+ is for A, NET- is for B and COM is for com-mon.

Network protocol is not properly set on the GTC108. Set network protocol based on the network require-ments and reset transmitter power.

Network address is not properly set on the GTC108. Set address based on network requirements and resettransmitter power. The address must be unique for thenetwork.

Network termination is not properly set on the GTC108. Set transmitter termination based on network require-ments and reset the transmitter power. Refer to Figure8 of this technical manual for TERMINATION DIP switchsettings.

The LCD display does not match the readings indicatedby the host control system.

The Area of the GTC108 transmitter does not match thatof the host controls.

Compare the value of the Area of the transmitter withthat of the host control system and make adjustments toensure a match.

The returned value for airflow is zero when airflow isindicated on the LCD display of the GTC108 transmitter.

The Low Limit airflow cutoff value is above the actual air-flow reading.

Decrease the Low Limit airflow cutoff value in the Setupmenu until it is below the actual airflow reading.

The status point from the GTC108 transmitter has aTrouble value.

The sensor detection system has detected one or moremalfunctioning or missing sensors.

Check sensor probe cable connections. If sensor probeconnections look OK and match the number of sensorprobes indicated on each probe's hang tag, please callEBTRON's customer service department or visit us atwww.ebtron.com.

Wrong type of sensor probes attached to transmitter. GTx108 transmitter will only operate with GF2 sensorsconnected.

There is no value for the differential pressure point. Differential pressure is only available from transmittersthat have EBTRON's Bi-directional Bleed Airflow Sensorsconnected.

If a differential pressure measurement is required, con-tact your local EBTRON Representative about EBTRON'sBi-directional Bleed Airflow Sensor.

Table 16. GTC108 and GTM108 - Analog Operation Transmitter Troubleshooting

Page 37: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 37

TM_G

Tx10

8_R

1A

Table 19. GTL108 LonWorks Transmitter Troubleshooting

Problem Possible Cause RemedyThe host control system or web browser is unable to com-municate with the GTM108 transmitter.

Verify that power is available to board (ACTIVITY LED isilluminated). If not verify that Output card is securelymounted on main circuit board.

Set transmitter power to "OFF" and press the output cardfirmly onto main circuit board. Turn the transmitterpower back "ON".

There is no link to the network indicated by the LINKLED on the output card.

The LINK LED indicates a valid connection to the net-work when it is illuminated. If the LINK LED is not on,verify network cabling and connections between theGTM108 and the network switch or hub. If LINK LED ison, verify that traffic is flowing by observing the TRAFFICLED. If LINK LED is on, but TRAFFIC LED is not, check fordefective network cabling.

The network protocol has not been properly set on theGTM108.

Set network protocol based on network requirementsand reset transmitter power.

The transmitter address has not been properly set onthe GTM108.

Set the address based on your network requirements.Note that each address must be unique for the network.

The LCD display does not match the readings indicated bythe host control system.

The area factor in the GTM108 transmitter does notmatch that of the host controls.

Compare the value of the Area factor of the GTM108transmitter with that of the host control system andmake adjustments to ensure a match.

The returned value for airflow is zero when there is airflowindicated on the LCD display of the GTM108 transmitter.

The Low Limit airflow cutoff value is above the actualairflow reading.

Decrease the Low Limit airflow cutoff value in the Setupmenu until it is below the actual airflow reading.

The status register from the GTM108 transmitter has aTrouble value.

The sensor detection system has detected one or moremalfunctioning or missing sensors.

Check sensor probe cable connections. If sensor probeconnections look OK and match the number of sensorprobes indicated on each probe's hang tag, please callEBTRON's customer service department or visit us atwww.ebtron.com.

Wrong type of sensor probes attached to transmitter. GTx108 transmitter will only operate with GF2 sensorsconnected.

There is no value for the differential pressure point. Differential pressure is only available from transmit-ters that have EBTRON's Bi-directional Bleed AirflowSensors connected.

If a differential pressure measurement is required, con-tact your local EBTRON Representative about EBTRON'sBi-directional Bleed Airflow Sensor.

Problem Possible Cause RemedyThe host control system is unable to communicate with theGTL108 transmitter.

Output card is not securely mounted on main circuitboard.

Turn the transmitter power "OFF" and press the outputcard firmly onto main circuit board. Turn the transmitterpower back "ON".

The network signal wiring is not properly connectedto the GTL108 transmitter or the host controls.

Verify that network cabling from the host controls is con-nected to the proper terminals of the OUTPUT terminalblock on the GTL108 transmitter. Wires should only beconnected to positions 1 and 2 on the terminal block.

The LonWorks network database has not been con-figured for the GTL108 transmitter.

The LonWorks network database may be pre-configuredusing the EBTRON_108.XIF file available for download atwww.ebtron.com or configured at installation time bydirect LonWorks parameter upload from the GTL108 trans-mitter.

The GTL108 transmitter is not providing values for any ofthe variables.

The required network configuration variables havenot been set.

Certain network configuration variables must be set toenable the LonWorks output card to request data from theGTL108 transmitter. Refer to the GTL108 - LonWorksINTERFACE section of this technical manual for specificGTL108 variables and settings.

There is no value for the differential pressure variables. Differential pressure is only available from trans-mitters that have EBTRON's Bi-directional BleedAirflow Sensors connected.

If a differential pressure measurement is required, contactyour local EBTRON Representative about EBTRON's Bi-directional Bleed Airflow Sensor.

The LCD display does not match the readings indicated bythe host control system.

The area factor in the GTL108 transmitter does notmatch that of the host controls.

Compare the value of the Area of the GTL108 transmitterwith that of the host control system and make adjustmentsto ensure a match.

The returned value for airflow is zero when airflow is indi-cated on the LCD display of the GTL108 transmitter.

The Low Limit airflow cutoff value is above the actu-al airflow reading.

Decrease the Low Limit airflow cutoff value in the Setupmenu until it is below the actual airflow reading.

The status variable from the GTL108 transmitter has aTrouble value.

The sensor detection system has detected one ormore malfunctioning or missing sensors.

Check sensor probe cable connections. If sensor probeconnections look OK and match the number of sensorprobes indicated on each probe's hang tag, please callEBTRON's customer service or visit us at www.ebtron.com.

Wrong type of sensor probes attached to transmit-ter.

GTx108 transmitter will only operate with GF2 sensorsconnected.

Table 18. GTM108 Ethernet Transmitter Troubleshooting

Page 38: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com38

TM_G

Tx10

8_R

1A

GTC108 Combination Analog/RS-485 Output Transmitter Wiring DiagramFigure A-1 is a typical wiring diagram for the GTC108 transmitter.

APPENDIX A - WIRING DIAGRAMS

Figure A-1. Model GTC108 Combination Analog/RS-485 Wiring Diagram

TRANSFORMER24 VAC / 50-60 HZ

(SEE NOTE 4)

LINE IN

24 VAC

SHIELDED TWISTED PAIR (STP) WIRING

(SUPPLIED BY OTHERS)

(SEE NOTES 2, 3)

RS-485CONTROL

GTC108 TRANSMITTER

L2 L1

POWER24VAC IN

SENSOR PROBE CONNECTORS

RS-485 OUTPUT

COMNET -NET +

NET NET+ COM

OUT 1AIRFLOW OUTPUTSIGNAL

1 2 COM

ANALOGOUTPUT

OUT 2*TEMP OR

ALARM OUTPUTSIGNAL

ANALOG BAS CONTROL INTERFACE

* OUT 2 can be set/assigned as Temperature, Alarm, Fan Alarm or Trouble Output. Alarm output can be set as active high or active low.

NOTES:1. OUTPUT 2 CAN BE SET AS TEMPERATURE, ALARM, FAN ALARM OR

TROUBLE ALARM. ALARM CAN BE SET AS ACTIVE HIGH OR ACTIVE LOW.2. CONNECT OUTPUT SIGNAL CABLE DRAINS TO EARTH GROUND AT

ONE END OF EACH CABLE ONLY.3. RS-485 COM CONNECTION MAY USE A SINGLE CONDUCTOR.4. ON MULTIPLE TRANSMITTER INSTALLATIONS WITH A COMMON

24VAC SOURCE, WIRE 24 VAC POWER IN-PHASE TO THE SAMETERMINALS ON ALL TRANSMITTERS (e.g.: L1 to L1, L2 to L2).

Page 39: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 39

TM_G

Tx10

8_R

1A

GTM108 Combination Analog/Ethernet Output Transmitter Wiring Diagram

Figure A-2 is a typical wiring diagram for the GTM108 trans-mitter.

GTL108 LonWorks Output Transmitter Wiring Diagram

Figure A-3 is a typical wiring diagram for the GTL108 trans-mitter.

CAT 5 OR EQUIVALENT

WIRING

(SUPPLIED BY OTHERS)

ETHERNETBAS

INTERFACE

GTM108 TRANSMITTER

SENSOR PROBE CONNECTORS

RJ45 OUTPUT

BAS ETHERNET

TRANSFORMER24 VAC / 50-60 HZ

(See Note 3)

LINE IN

24 VAC

SHIELDED TWISTED PAIR (STP) WIRING

(SUPPLIED BY OTHERS)

See Note 2

L2 L1

POWER24VAC IN

OUT 1AIRFLOW OUTPUTSIGNAL

1 2 COM

ANALOGOUTPUT

OUT 2*TEMP

ORALARM

OUTPUTSIGNAL

ANALOG BAS INTERFACE

* OUT 2 can be set/assigned as Temperature, Alarm, Fan Alarm or Trouble Output. Alarm output can be set as active high or active low.

NOTES:1. OUTPUT 2 CAN BE SET AS TEMPERATURE, ALARM, FAN ALARM OR

TROUBLE ALARM. ALARM CAN BE SET AS ACTIVE HIGH OR ACTIVE LOW.

2. CONNECT OUTPUT SIGNAL CABLE DRAINS TO EARTH GROUND ATONE END OF EACH CABLE ONLY.

3. ON MULTIPLE TRANSMITTER INSTALLATIONS WITH A COMMON 24VAC SOURCE, WIRE 24 VAC POWER IN-PHASE TO THE SAMETERMINALS ON ALL TRANSMITTERS (e.g.: L1 to L1, L2 to L2).

TRANSFORMER24 VAC / 50-60 HZ

(SEE NOTE 3)

LINE IN

24 VAC

USE LONWORKS®

COMPATIBLE SHIELDED TWISTED PAIR (STP)

CABLE(SUPPLIED BY OTHERS)

(SEE NOTES 1, 2)

LONWORKS®

BAS CONTROL INTERFACE

GTL108 TRANSMITTER

L2 L1

POWER24VAC IN

SENSOR PROBE CONNECTORS

NET NET+

1 2 COM

OUTPUT

NOTES:1: REFER TO LONWORKS® FTT-10A Free Topology Transceiver User’s

Guide AVAILABLE AT www.echelon.com FOR LONWORKS® NETWORKWIRING SPECIFICATIONS AND TERMINATION REQUIREMENTS.

2. GTL108 CONNECTIONS AT TERMINALS 1 AND 2 (NET + and NET -) ARE NOT POLARITY SENSITIVE, AND THE COM CONNECTION IS NOT USED

3. ON MULTIPLE GTL108 TRANSMITTER INSTALLATIONS WITH ACOMMON 24VAC SOURCE, WIRE 24 VAC CONNECTIONS IN-PHASE TOTHE SAME TERMINALS ON ALL TRANSMITTERS (e.g.: L1 to L1, L2 to L2)

APPENDIX A - WIRING DIAGRAMS (cont’d)

Figure A-3. Model GTL108

LonWorks Wiring Diagram

Figure A-2. Model GTM108

Combination Analog/Ethernet Wiring Diagram

Page 40: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2A

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com40

TM_G

Tx10

8_R

1A

APPENDIX B -GTx108-F

SETUP MENUS

Page 41: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 41

TM_G

Tx10

8_R

1B

SETUP WIZARD

Launched at initial power-up, and if Setup Wizard was not completed.

Enter (move ) Enter (action, move )Esc (normal oper.) Esc (move ) ACTION

For Array only, verify that sensor count is correct; indicate Error if not.

if AREA METH=AREA

Note: input in ft2, m2

SWSI, DWDI OR ARRAY, if AREAS=EQUAL

SET FAN AREA

DIAMn =1.00(SIDEn = 0.00 )

SETUP COMPLETE!

SETUP COMPLETE!

Note:input in in. and mm

SHAPE= selection will determine menu text. (Items in parentheses are associated when SHAPE=SQUARE is selected.)

if AREA METH=CALC

DIAM =1.00(SIDE = 0.00 )

DIAM =1.00(SIDE = 0.00 )

SET FAN TYPE FAN TYPE=SWSI

FAN TYPE=DWDI

FAN n=2

FAN TYPE=ARRAY

FANS=1

DISTR=EQUAL

SET FANS

SET SHAPESHAPE=ROUND

(SHAPE=SQUARE )

AREA METH=AREA

AREA METH=CALC

AREA=1.00

FAN 2=2

DISTR=VAR

SENS/FAN=2

FAN 1=1

SET AREA METH

SET FAN AREA- SWSI, DWDI OR ARRAY, if AREAS=EQUAL- Note: for DWDI, area is of BOTH inlets combined

- Enter diameter where probes are located

SET SENS/FAN

SETUP COMPLETE!

AREAS=EQUAL

AREAS=VAR

SENS/FAN=1

- Enter area

SETUP COMPLETE!

- ARRAY only, if AREAS=VAR

AREAn=1.00

VISIBLE FOR ARRAY ONLY, FANS=1 to 8 (SWSI=1; DWDI=1)

- VISIBLE FOR ARRAY ONLY if DISTR=EQUAL

- ARRAY only

- VISIBLE FOR ARRAY ONLY

AREA1=1.00

- VISIBLE FOR ARRAY ONLY if DISTR=VAR

- ARRAY only, if AREAS=VAR

Enter (move )Esc (move or prev setting)

- To SET AREA METH

SET AREA DISTR

FAN n=1

SET SENS DISTR

Figure B-1. GTx108-F Setup Wizard Menu

Page 42: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com42

TM_G

Tx10

8_R

1B

SYSTEM OF UNITS MENUSimultaneously depress/release ENTER + ESC keys during normal operation to select

* Factory Default/Current Setting

Enter (move ) Enter (move ) Enter (action, move )

Esc (normal oper.) Esc (move ) Esc (move ) ACTION

Set system of units to I-P (FPM, CFM, sq.ft., ºF)or Set system of units to S.I. (MPS, LPS, sq.M., ºC).NOTE: Changing IP/SI SYS resets alarm settings and scaling values.

SET IP/SI ?*IP/SI=IP SYS IP/SI=IP SYS

IP/SI=SI SYS

TM_GTx108-F Setup Menu (PART 1 OF 6)

SETUP MENUSimultaneously depress/release + keys during normal operation to select

* Factory Default/Current Setting

Enter (move ) Enter (move ) Enter (move ) Enter (move ) Enter (action, move )

Esc (normal oper.) Esc (move or prev setting) Esc (move or prev setting) Esc (move ) Esc (move ) ACTION

Only when AIRFLOW=ACT

TO PART 5 'A' TO PART 2

Set whether or not TROUBLE will display on LCD during a trouble condition.

LCD TRBL=ON

*ON FAIL=LO

O

*ALT=0 SET ALT? ALT=0

LCD UM=ACFM

Displays AREA value. For Fan Arrays when AREA=VAR, displays each value for AREA1= ______, AREA2= ______, AREA3= ______etc.

USE SETUP WIZ

USE SETUP WIZ

SET TEMP METH?*TEMP METH=WGT TEMP METH=WGT Set temperature output for velocity weighted average of temperature sensors.

TEMP METH=AVG Set temperature output for mathematical average of temperature sensors.

*TYPE={from setup}

*AREA={from setup}

*LLIMIT=0 SET LLIMIT?

Set the altitude above sea level for flow correction: 0 to 18,000 ft.

USE SETUP WIZ

LLIMIT=0

*FANS={from setup}

For arrays this is always a velocity value.

DISPLAY

*LCD DSPL=BOTH

*LCD UM=ACFM

*NAME={unit serial#} SET NAME ?SETUP

*AIRFLOW=ACT SET AIRFLOW?

AIRFLOW=STD

Set the airflow measurement to ACTUAL units (AFPM/ACFM)

Set the airflow measurement to Standard units (SFPM/SCFM)

AIRFLOW=ACT

Custom LCD Flow Text: Blinking prompt at position of the selected character. Character is selected using the up and down arrows and then ENTER to accept and move cursor forward (right); ESC moves the cursor back (left). Use space charactersfor blank or unwanted text.

Instruction text: "USE AND ENT"

then:NAME= _

GENERAL

SET ON FAIL? ON FAIL=LOSets transmitter analog output state in the event of a major fault (all sensor failure) expressed as LO for minimum scale analog output or HI for full scale analog output.

LCD DSPL=TEMP

*LCD TRBL=ON SET LCD TRBL? LCD TRBL=OFF

ON FAIL=HI

*EXT CABLE=0 SET EXT CABLE? EXT CABLE=0 Enter length of extension cable.

LCD DSPL=BOTH

Set LCD airflow display units to CFM or FPM. (Note: A-ACT or S-STD measurement prefix is set by AIRFLOW= setting above).

SET LCD UM? LCD UM=AFPM

Set what is displayed on LCD.

*LCD INTG=100 SET LCD INTG? LCD INTG=100 Integration samples for LCD.

SET LCD DSPL? LCD DSPL=OFF

LCD DSPL=FLOW

O

Figure B-2. TM_GTx108-F System of Units Menu

Page 43: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 43

TM_G

Tx10

8_R

1A

FROM PART 1

Analog cards only

if AO1 SGNL=mA

if AO1 SGNL=VDC

AO2 output is assigned as temperature output.

if AO2 SGNL=mA

if AO2 SGNL=VDC

if AO2 CFG=TEMP

if AO2 CFG=ALRM, FA or TRBL

TO PART 3

Set AO2 minimum scale.

Set AO2 full scale.

Sets AO2 alarm/trouble output state when no fault condition is present, expressed as HI (full scale analog output) or LO (minimum scale analog output).

AO2 output is assigned as fan alarm to indicate which fan is in alarm by outputting a percentage of the maximum analog output corresponding to the fan number. For example if fan 3 is in alarm and the output is set to 0-10V, the value on OUT2 will be 3V. Lowest fan number is indicated during multiple fan failure conditions.

AO1 UM=ACFM

O

AO1 UM=AFPM

O

*AO1 RNGE=0-10

*AO2 RNGE=4-20

AO2 output is assigned as a transmitter trouble alarm indicating that a sensor or transmitter fault has occurred.

Set full scale for AO1.

Integration samples. Also same as network integration.

Display initially shows the current SW2 PCB switch setting (VDC or mA) for AO2. Pressing enter displays "SET SW2 ON PCB" prompt to confirm SW2 PCB setting.

AO2 output is assigned as an airflow alarm output. Refer to ALARM settings (part 4).

ANALOG OUT *AO1 ASGN=FLOW AO1 ASGN FIXEDThe text "AO1 ASGN FIXED" flashes to indicate that this setting is fixed and cannot be modified.

*A01 SGNL=mA SET SW1 ON PCBDisplay initially shows the current SW1 PCB switch setting (VDC or mA) for AO1. Pressing enter displays "SET SW1 ON PCB" prompt to confirm SW1 PCB setting.

*AO1 RNGE=4-20 AO1 RNGE=FIXEDThe text "AO1 RNGE=FIXED" flashes to indicate that this setting is fixed and cannot be modified.

SET AO1 RNGE? Set analog output range (VDC) for AO1.AO1 RNGE=0-10

AO1 RNGE=0-5

*AO1 UM=AFPM SET AO1 UM?

AO2 FS=160

*AO1 FS=10000 SET AO1 FS? AO1 FS=10000

AO2 ASGN=FA

AO2 ASGN=TRBL

*AO1 INTG=30 SET AO1 INTG? AO1 INTG=30

*AO2 ASGN=TEMP SET AO2 ASGN? AO2 ASGN=TEMP

AO2 ASGN=ALRM

*A02 SGNL=mA SET SW2 ON PCB

*NO FAULT = HI SET NO FAULT? NO FAULT LO

AO2 RNGE=FIXEDThe text "AO2 RNGE=FIXED" flashes to indicate that this setting is fixed and cannot be modified.

*AO2 RNGE=0-10 SET AO2 RNGE? AO2 RNGE=0-10 Set analog output range (VDC) for AO2.

SET AO2 FS?

NO FAULT = HI

Set AO1 output units to FPM or CFM. (Note: A-ACT or S-STD measurement is set by AIRFLOW= setting above).

*AO2 MS=-20 SET AO2 MS? AO2 MS=-20

*AO2 FS=160

AO2 RNGE=0-5

*AO2 UM=F AO2 UNITS FIXEDThe text "AO2 UNITS FIXED" flashes to indicate that this setting is fixed and cannot be modified.

TM_GTx108-F Setup Menu (PART 2 OF 6)

Page 44: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com44

TM_G

Tx10

8_R

1A

TM_GTx108-F Setup Menu (PART 3 OF 6)

FROM PART 2

GTC only GTC configuration

Enter network address.

Set network baud rate.

Option for MODBUS onlySet MODBUS parity type.

Option for BACNET only

GTM only GTM configuration

TO PART 4

Set network device instance number.

Enter IP address, use (up/down arrow) buttons to select value and press ENT to move to right and ESC to move to left.

Enter subnet mask, use (up/down arrow) buttons to select value and press ENT to move to right and ESC to move to left.

Enter gateway IP address, use (up/down arrow) buttons to select value and press ENT to move to right and ESC to move to left.

Set BACnet IP or Ethernet protocol.

Set DHCP to ON or OFF.

SET IP?

SET NETADDRESS?

NETWORK

*IP=10.0.0.1

EB-LINK

O

O

NETWORK

*NETOUT=BACNET SET NETOUT? NETOUT=BACNET Set network protocol type.

NETBAUD=38400

*NETDI=2 SET NETDI?

010.000.000.001

*NETBAUD=76800 SET NETBAUD? NETBAUD=76800

*PARITY=EVEN SET PARITY? PARITY=EVEN

NETBAUD=19200

NETBAUD=9600

BACNET=ETH

*GATE=10.0.0.1 SET GATEWAY?

PARITY=ODD

BACNET=IP

PARITY=NONE2

*BACNET=IP SET BACNET?

*MASK=255.255. SET MASK? 255.255.255.000

010.000.000.001

NETDI=2

*DHCP=OFF

PARITY=NONE1

NETOUT=MODBUS

*NETADDRESS= 2 NETADDRESS=2

SET DHCP? DHCP=OFF

DHCP=ON

*EB-LK INTG=300 SET EB-LK INTG? EB-LK INTG=300 EB-Link integration samples.

*NETDI=2 SET NETDI? NETDI=2 Set network device instance number.

Page 45: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 45

TM_G

Tx10

8_R

1A

TM_GTx108-F Setup Menu (PART 4 OF 6)

FROM PART 3

if FA TYPE=MIN

if FA TYPE=DEV or %MAX

TO PART 5 'B'

When ZERO OFF=YES, this setting is used to inhibit the LO ALRM condition when the unit is reading 0. This is dependent on the low limit setting.

Set alarm RESET. AUTO will clear once the alarm is not active. MANUAL requires user to clear alarm by depressing the ESC key, or for RS485 (GTC108) output, write 0 to corresponding alarm BACnet object or Modbus register. Alarm will only clear when alarm is not active.

When ZERO OFF=YES, this setting is used to inhibit the LO ALRM condition when the unit is reading 0. This is dependent on the low limit setting.

Set alarm RESET. AUTO will clear once the alarm is not active. MANUAL requires user to clear alarm by depressing the ESC key, or for RS485 (GTC116) output, write 0 to corresponding alarm BACnet object or Modbus register. Alarm will only clear when alarm is not active.

Set Fan Alarm type.

When FA TYPE=MIN, sets Alarm units of measure.

When FA TYPE=MIN, sets Alarm setpoint value.

When FA TYPE=DEV or %MAX, sets Alarm setpoint value.

This setting determines whether a fan that is in an alarm condition should be removed from the average.

O

O

*HI ALRM=OFF SET HI ALRM? HI ALRM=OFF

*LO ALRM=OFF

Enable/disable HI alarm.

LO ALRM=OFF Enable/disable LO alarm.ALARM

HI ALRM=ON

*ALRM UM=AFPM SET ALRM UM? ALRM UM=AFPMSet alarm units of measure to FPM or CFM (Note: A if ACT or S if STD measurement prefix set by AIRFLOW= setting above).

LO ALRM=ON

SET LO ALRM?

ALRM UM=ACFM

*SETPNT=0 SET SETPNT? SETPNT=0 Enter setpoint for alarm.

FA TYPE=MIN

*TOL=10% SET TOL? TOL=10% Enter tolerance as value above or below alarm setpoint. Units based on ALARM UM.

*DELAY=2 min SET DELAY? DELAY=2 min Set alarm DELAY.

*ZERO OFF=NO SET ZERO OFF? ZERO OFF=NO

ZERO OFF=YES

*RESET=AUTO SET RESET? RESET=AUTO

RESET=MANUAL

FAN ALARM *FA TYPE=NONE SET FA TYPE? FA TYPE=NONE

Set alarm DELAY.

FA TYPE=DEV

*FA REMOVE=YES

*SETPNT=0 SET SETPNT?

SET FA REMOVE? FA REMOVE=YES

FA REMOVE=NO

*ALRM UM=AFPM SET ALRM UM? ALRM UM=AFPM

DELAY=2 minSET DELAY?*DELAY=2 min

*SETPNT=0% SET SETPNT? SETPNT=0%

*ZERO OFF=NO SET ZERO OFF? ZERO OFF=NO

Alarm on an absolute minimum Fan velocity value.

Alarm on % deviation from median of all fans.

Alarm on % deviation from maximum velocity of individual fan.FA TYPE=%MAX

SETPNT=0

ALRM UM=ACFM

ZERO OFF=YES

*RESET=AUTO SET RESET? RESET=AUTO

RESET=MANUAL

Page 46: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com46

TM_G

Tx10

8_R

1B

TM_GTx108-F Setup Menu (PART 5 OF 6)FROM PART 1 FROM PART 4

Dashed lines indicate Menus when # OF FLOWS=2

TO PART 6

Resets network settings to factory default.

Set OUT1 to % of full scale analog output.

Set OUT2 to % of full scale analog output.

Start field adjust wizard and enter number of integration samples to use.

Enable/disable security lock.

Enter code and confirm code (NOTE: if LOCK SEC= HIGH, DO NOT lose code!)

Reset ALL changes back to factory defaults. Transmitter resets after completion.

Enable/disable flow adjustments.

Enter gain applied to airflow reading.

Enter offset applied to airflow reading.

Initiate SETUP WIZARD. See SETUP WIZARD at beginning of SETUP menus.

Sets security level to HIGH. In this mode, a user defined code is specified. In the event of loss of code, transmitter must be returned to EBTRON for unlock / reset.

Wait. . .%ADJUSTMENT

COMPLETE

SET FLOW1ENSURE THAT FAN IS

ON AND SET TO DESIRED SPEED!

5B

Sets security level to MED. In this mode, a user defined code is specified. In the event of loss of code, contact EBTRON for a unique code for this transmitter to unlock and reset code.

The Field Adjust Wizard will now be engaged as outlined in the following steps. The GAIN and OFF values will be updated, and FLOW ADJ=ON will be set if the wizard is successfully completed.

*FLOW ADJ=OFF FLOW ADJ=OFF

FLOW ADJ=ON

*GAIN=1.000 SET GAIN? GAIN=1.000

SET FLOW ADJ?

OFF=0

# OF FLOWS=2

ADJUSTMENTS

*OFF=0 SET OFF?

OUT1 TEST% SET OUT1 TEST? OUT1 TEST%=0

OUT2 TEST% SET OUT2TEST?

TOOLS SETUP WIZ RUN SETUP WIZ ARE YOU SURE? RUN SET WIZ=NO

RUN SET WIZ=YES

OUT2 TEST%=0

OUTPUT TEST

FIELD ADJUST RUN FA WIZARD? SET FAW INT FAW INT=300

SET # OF FLOWS # OF FLOWS=1

SECURITY *LOCK SEC=LOW SET LOCK SEC? LOCK SEC=LOW

FLOW2= 0(Set 0 to 999999 using

the keys)

Wait. . .%ADJUSTMENT

COMPLETE

SET FLOW2ENSURE THAT FAN IS

ON AND SET TO DESIRED SPEED!

FLOW1= 0(Set 0 to 999999 using

the keys)

LOCK SET=HIGH

RESET ADJ=YES

RESET RESET ALL ARE YOU SURE? RESET ALL=YES

RESET SENS ARE YOU SURE? RESET SENS=YES

RESET SENS=NO

*LOCK=OFF SET LOCK? LOCK=OFF

LOCK=ON

ENTR CODE:0 CONF CODE:0

Sets security level to LOW. In this mode, there is no prompt for a lock code. The last 4 digits of the board serial are used to unlock.

Reset FLOW adjustments to GAIN = 1, OFF = 0, FLOW ADJ = OFF

RESET NET=YES

LOCK SEC=MED

RESET ADJ=NO

RESET ALL=NO

Resets sensor data. Transmitter resets after completion.

ARE YOU SURE?

RESET NET=NO

RESET NET ARE YOU SURE?

RESET ADJ

5A

"Wait. . . %" indicates progress while the Field Adjustment Wizard acquires a large number of samples of airflow rate and averages all of the readings. Display indicates "ADJUSTMENT COMPLETE" when adjustment is complete. If you wish to review the adjustment made, simply navigate back to the SETUP menu and view the ADJUSTMENTS section.

O

Page 47: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,

TM_G

Tx10

8_R

2B

GOLD SERIES GTX108 TRANSMITTER

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 47

TM_G

Tx10

8_R

1C

TM_GTx108-F Setup Menu (PART 6 OF 6)

FROM PART 5

1: NO PROBES

(example shown)

Displays unit serial number.

1=#####CFM

For fan arrays only; Fans 1 to 8.

For sensors =1 to 8

Type C board only

ARRAY ######

ARRAY FW 1.00

TRBL HISTORY

SERIAL NUMBERS UNIT #######

TRBL CODES DSBL TRBL CODE? DSBL TRBL=NO

Displays historical list of last 5 trouble codes encountered and their descriptions. Note that spurious trouble codes may self-clear during normal operation, and this feature permits viewing them even after they have resolved.

C4 ###### F

Displays probe serial numbers followed by a T if connected and functioning properly, and then followed by an F if not connected or not functioning properly.

DSBL TRBL=YES

Displays active trouble codes and their descriptions. Contact EBTRON customer service for recommended service information.

Set DSBL TRBL= YES to ignore currently displayed TRBL alarm. To disable all trouble codes, see SETUP -> DISPLAY -> LCD TRBL.

Displays main PCB serial number.

FAN VELOCITY 1=######FPM

Array connector board serial number

Array connector board firmware revision

1=##.#F

C5 ###### T

SENS TEMP For sensors =1 to 8

C6 ###### F

C7 NC

BRD #####

DIAGNOSTICS

Note: On 8 connector board only

SENS VELOCITY 1=#####FPM For sensors =1 to 8

C1 ###### T

C2 ###### F

1: NO PROBES(example shown)

C3 ###### T

FAN VOLUME For fan arrays only; Fans 1 to 8.

O

C8 NC

SENS VOLTS 1=H##.## T##.##

Page 48: Gold Series by Ebtron · Network Connectivity Solutions OVERVIEW EBTRON’s GTx108 (Figure 1) transmitter is designed for measure- ment of fan airflow and temperature on single inlet,