GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G B GB This guide has been prepared for the operator of Carrier Transicold GENESIS R90 UNDERMOUNT refrigeration units. It contains basic instructions for the daily operation of the refrigeration unit as well as safety information, trouble shooting tips, and other information that will help you to deliver the load in the best possible condition. Please take the time to read the information contained in this booklet and refer to it when ever you have a question about the operation of your Carrier Transicold GENESIS R90 UNDERMOUNT units. Your refrigeration unit has been engineered to provide long, trouble--free performance when it is properly operated and maintained. The checks outlined in this guide will help minimize problems. Maintenance program will also help to control operating costs, increase the unit’s working life, and improve performance. Carrier Transicold has an on--going product quality upgrade policy. As a result, specifications are liable to change without notice. The nameplate identifies: S serial number, refrigerant charge and quantity, date in service * gives you all the information when calling 24 hour Assistance.

Upload: doanbao

Post on 27-Aug-2018

266 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

GENESIS R90 UNDERMOUNTOPERATOR’S MANUAL

1

GB

GBThis guide has been prepared for the operator of Carrier TransicoldGENESISR90UNDERMOUNT refrigeration units. It contains basic instructions for the dailyoperation of the refrigeration unit as well as safety information, trouble shooting tips,and other information that will help you to deliver the load in the best possible condition.Please take the time to read the informationcontained in this booklet and refer to itwhenever you have a question about the operation of your Carrier TransicoldGENESISR90 UNDERMOUNT units.

Your refrigeration unit has been engineered to provide long, trouble--free performancewhen it is properly operated andmaintained. The checks outlined in this guide will helpminimize problems.

Maintenance program will also help to control operating costs, increase the unit’sworking life, and improve performance.

Carrier Transicold has an on--going product quality upgrade policy. As a result,specifications are liable to change without notice.

The nameplate identifies:S serial number, refrigerant charge and quantity, date in service

* gives you all the information when calling 24 hour Assistance.

Page 2: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

GENESIS R90U OPERATOR’S MANUAL

2

CONTENTSPage

SAFETY 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FEATURES 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PRETRIP INSPECTION 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UNIT OPERATION 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Starting the unit 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Changing the setpoint 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Stop the unit 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operation with auxiliary control panel (option) 17. . . . . . . . . . . . . . . . . . . . . .

PRODUCT LOADING 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECOMMENDED TRANSPORT TEMPERATURES 21. . . . . . . . . . . . . . . . . . . . .

PROBLEMS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UNIT MAINTENANCE 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit maintenance schedules 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Description of maintenance operations 29. . . . . . . . . . . . . . . . . . . . . . . . . . . .Belts 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Filters 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STANDBY OPERATION GUIDELINES 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MANUFACTURER INFORMATION 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

“A.T.P. EUROPE” REGULATION EXTRACT 35. . . . . . . . . . . . . . . . . . . . . . . . . . .

EMERGENCY ROAD SERVICE 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 3: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

SAFETY

3

GB

Your Carrier Transicold refrigeration unit has been designed with the safety of theoperator in mind. During normal operation, all moving parts are fully enclosed to helpprevent injury. During all pre--trip inspections, daily inspections, and problemtroubleshooting, you may be exposed to moving parts; please stay clear of thesemoving parts when the unit is in operation and when the main power switch is in theRun (On) position.The evaporator and condenser are made of finned tubes. The fins can cause injury oncontact with skin. It is recommended to wear protective gloves during all handlingoperations.During operation, certain components such as the exhaust pipe, discharge outlet, andcooling circuit radiator can become extremely hot. During routine service operations,wear protective gloves.

AUTO--START/STOP

Your refrigeration unit is equipped with Auto-Start/Stop, a valuable fuel saving feature.When the unit is set for Auto-Start/Stop operation it may start at any time. Whenperforming any check of the refrigeration unit (e.g., checking the belts, checking theoil), make certain that the main power switch is in the OFF (0) position.

ENGINE COOLANT

The engine, as with all diesel engines, is equipped with a pressurized cooling system.Under normal operating conditions, the coolant in the engine and radiator is under highpressure and is very hot. Contact with hot coolant can cause severe burns. Do notremove the cap from a hot radiator; if the cap must be removed, do so very slowly inorder to release the pressure without spraying.

REFRIGERANTS

The refrigerant contained in the refrigeration system of your unit can cause frostbite,severe burns, or blindness when in direct contact with the skinor eyes.For this reason,andbecauseof legislation regarding thehandlingof refrigerants during systemservice,whenever your unit requires service of the refrigeration system, we recommend thatyou contact your nearest Carrier Transicold authorized repair facility for service.

Page 4: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

SAFETY

4

BATTERY

This unit is equipped with a lead--acid type battery. The battery normally vents smallamounts of flammable hydrogen gas. Keep any flame, any lighted object (cigaretteetc.) or any source of sparks away from the battery elements. A battery explosion cancause serious physical harm and/or blindness.

AUTOMATIC START UP IN DIESELWHEN LOSS OF STANDBY

FROM EPROM 4.05

To activate this function : TIME STRT set up in functionnal parameters.

When the unit is started in standby, the “ROAD” light is flashing and the“STANDBY” light is lit.

After 5 minutes of loss of power, the unit automatically starts in diesel. 5minutes after the power comes back, the unit starts again automatically inelectricmode. The “STANDBY MOTOR” alarm appears, alarm that you would have toclear.

* This function will be active even after a stop (OFF) of the unit. To deactivate it: set up TEMP STRT in functionnal parameters.

DEACTIVATE THIS FUNCTIONWHENUNIT IS RUNNING INA CLOSED AREA !

Page 5: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

5

GB

This refrigeration unit is equipped with a wide range of features that are designed toimprove reliability and temperature control within the body.

The unit can be delivered fitted with a microprocessor controller.

MICROPROCESSOR CONTROLS

1. Display

2. Up and down arrow keys

3. Function change key

4. Run/Stop switch

5. Road key

6. Comp. 1 ON/OFF switch

7. City speed key

8. Comp. 2 ON/OFF switch

9. Manual defrost key

10. Comp. 3 ON/OFF switch

11. Buzzer off key

12. Standby key

13. Pretrip key

14. Auto-start/Stop key

15. Unit data key

16. Fault alarm led

17. Enter key

1.

3.

2.

17.

4.

5.

7. 9.

11.

12.

13.

14.

15.

16.

6. 8. 10.

Page 6: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

6

The microprocessor controls incorporated into this unit are the most reliable controlsystem available. It is also designed to be the easiest to use, offering great flexibilityin control, yetminimal user input for normal operation : a true “set it and forget it” design.

1. Display window : shows set--point, box temperature, operatingmode, alarm displays, as well as data on the unit itself (battery

voltage, water temperature etc.).

Function Change key

The function change key is used to display the operatingparameters. Each time this key is pressed the display will advanceto the next parameter. This key, in conjunction with the up/downarrow and enter keys, will allow the user to change the parameters.

Arrows key

The UP ARROW and DOWN ARROW keys are used to alter theset--point. Press the up or down arrow keys until the desiredsetpoint is displayed on the left--hand side of the display window.When the correct set--point is displayed, press the ENTER key toconfirm the setting.The UP ARROW and DOWN ARROW keys are also used tochange the unit functions and scroll through the FUNCTION andUNIT DATA screens.

Enter key

The ENTER key confirms changes made to unit operation. It mustbe pressed to change the setpoint after using the arrow keys toadjust it. If the ENTER key is not pressed, the setpoint will revert tothe previously entered setting.The ENTER key must also be pressed whenever a FUNCTIONsetting is being altered. If this key is not pressed, the function willrevert to its previous setting.

RUN/STOP switch

Themain unit RUN/STOP switch controls the unit operation.Whenswitched to the Run (I) position, the unit will start in the operatingmode last entered (Road or Standby). The set--point will be at thelast set--point entered on the keypad.

Road key

The ROAD key puts the unit into Road (or engine) operation whenthe unit has been previously operated in the Standby mode.

City Speed key

Page 7: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

7

GB

TheCITYSPEED key toggles the unit between high speed and lowspeed (diesel mode). When City Speed is selected, the unit will runonly in low speed except during defrost cycles. This feature isuseful in areas where noise is restricted.

Manual defrost key

The MANUAL DEFROST key places the unit in a defrost cycle.Under most conditions it is not necessary to defrost the unitmanually as this is done automatically with the air switch or thedefrost timer. Manual defrost may become necessary due to iceaccumulated on the evaporator coil during frequent door openingsin humid environments.

Buzzer Off key

The BUZZER OFF key temporarily turns off the FAULT ALARMbuzzer. The red light “Fault alarm” remains illuminated on thecommand cab.

Standby key

The STANDBY key places the unit in Standby (or electric) modewhen the previous mode of operation has been Road.

Pretrip Check key

The PRETRIP key initiates a check of all normal operating modes.The temperature inside the box must be below 5_C¦ 1_C (35_F¦ 2_F) to start this check. Upon initiation, the unit will cycle throughall operating modes at 30 second intervals. The display will show“PPPP” at the beginning and will show various unit data during thepre--trip cycle. Upon completion of the pre--trip cycle the unit will beplaced into the defrost mode.

Auto Start/Stop Continuous key

The AUTO--START/STOP key toggles the unit operating modebetween Auto--Start/Stop and continuous run. When the unit is setfor Auto--Start/Stop operation, the unit will run until the boxtemperature reaches set--point and then cycle off (after theminimum run time has been met) until further cooling or heating isnecessary. When in the continuous mode, the unit will cyclebetween heat and cool as required to maintain the set temperaturein the body. If the setpoint is below -12_C (10_F) the unit will notheat, it will run continuously in low speed cool.

Page 8: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

8

Unit Data key

iThis key scrolls the display through the various operating conditiondisplays, engine temperature or battery voltage, for example. A morecomplete description of the function is found later in this chapter.

Compartment 1 ON/OFF switch

when switched to (I) the unit and compartment 1 will start in theoperating mode last entered (cooling or heating).

Compartment 2 ON/OFF switch

when switched to (I) the unit and compartment 2 will start in theoperating mode last entered (cooling or heating).

Compartment 3 ON/OFF switch

when switched to (I) the unit and compartment 3 will start in theoperating mode last entered (cooling or heating).

16. Fault Alarm led : illuminates when an alarm is detected.

IMPORTANT

If the cab control displays nothing, check the position of the RUN switch (1), locatedon the microprocessor control box.

Main unit operation switch (RSS)

Turn the switch to “RUN” (1) in order tocontrol the unit from the cab control.

Page 9: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

i

FEATURES

9

GB

TO DISPLAY UNIT DATA

The unit data list can be scrolled through by pressing the UNIT DATA key. The list willadvance by one with each key press; or, press the UNIT DATA key once and use theUP or DOWN ARROW keys to scroll through the list more quickly. Press the ENTERkey to display the data for 30 seconds.

UNIT DATA

CODE ENGLISH DATA

CD1 SUCT Suction pressure

CD2 ENG Engine hours

CD3 WT Engine temperature

CD4 1 RA Compartment 1 -- Return air temperature

CD6 2 DT Compartment 2 -- Defrost thermistor sensor

CD7 3 DT Compartment 3 -- Defrost thermistor sensor

CD8 1 DTS Compartment 1 -- Defrost thermistor sensor

CD9 CDT Compressor discharge temperature

CD10 BATT Battery voltage

CD11 SBY Standby hours

CD12 MOD V Future expansion

CD13 REV Software revision

CD14 SERL Serial number low

CD15 SERU Serial number upper

CD16 2RA Compartment 2 -- Return air temperature

CD17 3RA Compartment 3 -- Return air temperature

CD18 MHR1 Maintenance hour meter 1

CD19 MHR2 Maintenance hour meter 2

CD20 SON Switch on hour meter

Page 10: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

10

TO CHANGE A FUNCTION

1. Press the FUNCTION CHANGE key until the function you want to changeappears on the display.

2. Press ENTER.

3. Press the UP or DOWN ARROW key until the function setting you wantappear on the display.

4. Press ENTER.

FUNCTION PARAMETERS

CODE ENGLISH AVAILABLE SELECTIONS

FN0 DEFR Defrost interval 1.5, 3, 6, or 12 hr

FN1 ON CITY SPEED Low speed only

FN1 OFF HIGH SPEED Low and High speed

FN2 OFF T Minimum off-time 10,20, 30, 45 or 90 mn

FN3 ON T On-time 4 or 7 min.

FN4 Degrees_C or _F

Temperature Unit (_C or _F)

FN5 ON TIME STRT Maximum Off-time 30 min*

Desactivate FN2

FN5 OFF TEMP STRT Minimum time 10, 20, 30, 45, 90 min

Reactivate FN2

FN6 MOP STD Future expansion

FN7 ON AUTO OP Auto start operation

FN7 OFF MAN OP Manual start operation

FN8 T RANGE Out of range (A=2_C / B= 3_C/ C=4_C)

CODES or ENGLISH Code or English display format

NORMAL GLOWOVERRIDE

Normal of add 30 seconds

ALARM CLR No alarm active

ALARM RST Alarm reset required

* From EPROM 4.05 version -- see WARNING here after

Page 11: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

11

GBAUTOMATIC START UP IN DIESEL

WHEN LOSS OF STANDBY

FROM EPROM 4.05

To activate this function : TIME STRT set up in functionnal parameters.

When the unit is started in standby, the “ROAD” light is flashing and the“STANDBY” light is lit.

After 5 minutes of loss of power, the unit automatically starts in diesel. 5minutes after the power comes back, the unit starts again automatically inelectricmode. The “STANDBY MOTOR” alarm appears, alarm that you would have toclear.

* This function will be active even after a stop (OFF) of the unit. To deactivate it: set up TEMP STRT in functionnal parameters.

DEACTIVATE THIS FUNCTIONWHENUNIT IS RUNNING INA CLOSED AREA !

Page 12: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

FEATURES

12

CONTROL PANEL (OPTION)

User-friendly indicator and operator control panels clearly show individualcompartment temperatures with easy-to-read displays.

These compact panels can be mounted to suit the individual operator’s preferences.

(Example : on the front bulkhead, in the cab or in the refrigerated compartment --including mounting in the truck wall itself.)

♦ Control panel

1. Compartment ON/OFF key

2. Control panel power on

3. Unit ON/OFF key

4. Manual defrost key

5. Control panel locking

6. Up and down arrow keys

7. Heating operating mode lightof a compartment

8. Cooling operating mode lightof a compartment

9. Temperature indicated in_C or _F

3. 4.

1.

6.

8.

7.

2.

9.

5.

From this control panel (option) you can :

- switch on the unit

- check compartement 1, 2 or 3 temperatures

- change setpoints

- energize a manual defrost

Page 13: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PRETRIP INSPECTION

13

GB

The pre--trip inspection should be performed before picking up any load. Thisinspection is essential to anticipate and help minimize the possibility of“over--the--road” problems. These checks take only a few minutes.

1. Place the unit’s main switch in the STOP (0) position.

2. Fuel -- drain any water and impurities from the sump of the refrigeration unitfuel tank by opening the drain--cock located on the bottom of the tank (if soequipped). Close the valve when only pure fuel emerges. Check the fuel levelin the tank, ensuring that the fuel supply is adequate for unit operation. Refuelif necessary.

3. POLY-V Belts -- Genesis R90U unit is equipped with poly-V belt. It allowshigher power transmission compared to the conventional V-belt but aligmenttolerances are tighter.

4. Battery -- on unit equipped with serviceable batteries, the level of theelectrolyte in each of the cells should be checked. If the level is low, distilledwater should be added to the correct level. Most units, however, areequipped with low or no--maintenance batteries. Check battery connectionsand battery supports.

5. Engine Oil -- the engine oil should be checked last since it is necessary for oilto drain out of the block and into the oil pan to obtain a correct reading.Remove the plug/dip--stick (1), wipe it off and re--insert it fully into the engineblock. Once again, remove the dip--stick and observe the oil level; it shouldbe somewhere between the full and add marks. If it is below the add mark,add oil until the level is correct.

Page 14: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PRETRIP INSPECTION

14

1

6. Over--all Unit inspection -- visually inspect the entire unit for leaks, loosebolts, frayed, loose, or broken wires, etc. The radiator and condenser coils ofthe unit should be free of dirt, bugs, cardboard, or any other debris that mayobstruct airflow across the coils. The evaporator (located inside the body)should be free of debris also, especially stretch--wrap, which is often usedduring transport to prevent cargo shifting.

7. Truck body -- The body should be inspected prior to loading. Check the doorand vent seals for damage and wear. Inspect the entire interior and exteriorof the body to detect any damage including in the inner and outer skins of thebody. Damage to the insulation may compromise the unit’s ability to maintainthe product temperature by increasing the amount of heat gain across thetruck body.

Page 15: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT OPERATION

15

GB

STARTING THE UNIT

Complete the pre-trip inspection described in the previous section.

S Road operation

1.

2.

3.

1. Place the RUN/STOP switch (O/I) tothe RUN position (I)2. Press the ROAD operation key (only

if the unit has been previously used instandby mode).3. Place either one, two or three com-

partments OFF/ON switches to ON (I).

4. Then, the unit will :

- perform a complete diagnostic check on the microprocessor controller- pre-heat for the required amount of time based on the engine temperature- starts automatically

S On Standby

2.1.

3.

1. Place the RUN/STOP switch (O/I)to the RUN position (I)2. Press the STANDBY operation

key3. Place either one, two or three

compartments OFF/ON switches to ON(I).4. Then, the unit will begin to run on

electric power.

Be certain that the unit is connected to an appropriatepower source.

Page 16: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT OPERATION

16

CHANGING THE SETPOINT

The sequence is the same for each compartment.

2.

1. Start the unit

2. When the setpoint box temperatureis displayed, press the UP or DOWNARROW key to change the temperaturesetpoint.

STOP THE UNIT

1.

2.

1. Place C1, C2 and C3 switches tothe OFF position (O).

2. Place the RUN/STOP switch (O/I)to the OFF (O) position.

To shut down the unit, ALWAYS use the cab command or thegeneral switch (RS) located on the control box.

Page 17: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT OPERATION

17

GB

OPERATION WITH AUXILIARY CONTROL PANEL (OPTION)

1. Start the unit as mentioned before.

2.

3.

2. Press the SYSTEM ON/OFF key.Power light will go ON.3. Press the ON/OFF key to energize

selected compartment.4. DISPLAY

waiting for communication with unit

compartment temperature display

setpoint temperature display

evaporator status (heat or cool or null)

compartment shut-down via remote control

defrost compartment

temperature sensor malfunction

CHANGE SETPOINT

Setpoint change can be made from control panel or cab control.

1.

1. Press the UP or DOWNARROW key to increase or decreasesetpoint. This is the same operation foreach compartment.

Page 18: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT OPERATION

18

LOCK THE CONTROL PANEL

1.

2.

1. Press the CARRIER logo 10 s.

2. The indicator comes on.

UNLOCK THE CONTROL PANEL

1.

2.

1. Press the CARRIER logo forabout 10 s.

2. The indicator goes off.

REMARK

It is not necessary for the compartment to be running in order to modify or seethe setpoint value and the temperature of the compartment.

The unit can be shut down both with the cab command and the general switch.

Page 19: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PRODUCT LOADING

19

GB

Proper air circulation in the truck body, air that canmove around and through the load,is a critical element in maintaining product quality during transport. If air cannotcirculate completely around the load, hot spots or top--freeze can occur.

The use of pallets is highly recommended. Pallets, when loaded so air can flow freelythrough the pallets to return to the evaporator, help protect the product from heatpassing through the floor of the truck. When using pallets, it is important to refrain fromstacking extra boxes on the floor at the rear of the truck, because this will cut off theairflow.

Product stacking is another important factor in protecting the product. Products thatgenerate heat, fruits and vegetables for example, should be stacked so the air can flowthrough the product to remove the heat; this is called “air stacking” the product.Products that do not create heat, meats and frozen products, should be stacked tightlyin the center of the truck. All products should be kept away from the sidewalls of thebody, allowing air to flow between the body and the load; this prevents heat filteringthrough the walls from affecting the product.

It is important to check the temperature of the product being loaded to ensure that it isat the correct temperature for transport. The refrigeration unit is designed to maintainthe temperature of the product at the temperature at which it was loaded; it was notdesigned to cool a warm product.

OPTIONS FOR INSULATED BODIES

D Mobile partition

The mobile partition must be placed at a minimum distance from the evaporator of 1m for : MTS700 / MTS1100 / MTS1450 / MTS2200

D Ducting of evaporator air outlet

Ventilation ducts must never be covered.

SOME ADVICE

Before loading

D Pre--cool the inside of the insulated body by lowering the temperature for about 15minutes.

D Evacuate the humidity existing inside the box by carrying out amanual defrost. Thiscan only take placewhen enabled by the defrost thermostat (box temperature lowerthan 3_C during pulldown and 8_C during heating).

D Evaporator fans are protected by safety grills. In the event of heavy duty use of theunit, ice can accumulate on the grills. It is therefore recommended to clean themregularly bymeans of a small brush. The operationMUST bedonewhen the unit hasbeen SHUT DOWN.

Page 20: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PRODUCT LOADING

20

When loading

D To be carried out with the unit stopped.

D It is recommended to open doors as little as possible to avoid the intake of hot airand humidity.

D Select the temperature by means of the thermostat, according to the transportedgoods.

D Check the internal temperature of the goods being loaded (using a probethermometer).

D Take care not to obstruct the air intakes on the evaporator section and theventilationducts.

Load spacers

Load on pallets

D Leave a free space of about :- 6 to 8 cm between load and frontwall,

- 20 cm between the top of the load andthe roof,

- between the floor and the load(gratings, pallets).

D Do not forget to close the doors.

D Before closing the doors, check your load once more and see that nobody is shutinside the box.

NOTE :

For stationnary utilization, we recommend to place the body in the shade.

IMPORTANTNever leave your unit more than amonth without running.

Page 21: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

RECOMMENDED TRANSPORTTEMPERATURES

21

GB

Below are some general recommendations on product transport temperatures andoperating modes for the unit. These are included for reference only and should not beconsidered pre--emptive of the set--point required by the shipper or receiver.

More detailed information can be obtained from your Carrier Transicold dealer.

Product Set--point Range Operating mode*

Bananas 15_C 60_F Continuous

Fresh fruits andvegetables

+4_C to +6_C +39_F to+43_F

Continuous

Fresh meats andseefood

+2_C +36_F Auto--Start/Stop orcontinuous

Dairy Products +2_C to +6_C +36_F to+43_F

Auto--Start/Stop orcontinuous

Ice --20_C 15_F to 20_F Auto--Start/Stop

Frozen fruits andvegetables

--18_C 0_F Auto--Start/Stop

Frozen meats andseafood

--20_C --10_F to 0_F Auto--Start/Stop

Ice cream --25_C --20_F Auto--Start/Stop

* During delivery cycles that include frequent stops and door openings, it isrecommended that the unit always be operated in the continuous run mode to helpinsure product quality.

It is essential to shut down the compartment during the periods when the doors areopen, in order to maintain the temperature of the cargo in the other compartments andkeep the unit operating correctly. To do so, the main O/I switch (O: stop/I: start) shouldbe switched to O).

Page 22: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PROBLEMS

22

Everything possible has been done to ensure that your unit is the most reliable,trouble--free equipment available on the market today. If, however, you run intoproblems, the following section may be of assistance.

If you do not find the trouble that you have experienced listed below, please call yourCarrier Transicold dealer for assistance.

General Problems

UNIT WON’T CRANK, BY THE STARTER CHECK BATTERY CONDITION.

CHECK BATTERY CONNECTIONS.

CHECK ALL FUSES.

UNIT WON’T START CHECK FUEL LEVEL.

CHECK ALL FUSES.

UNIT WON’T RUN CHECK FUEL LEVEL.

CHECK ENGINE OIL LEVEL.

CHECK ALL FUSES.

UNIT DIES CHECK BELTS.

CHECK ENGINE OIL LEVEL.

CHECK COOLANT LEVEL.

CHECK FUEL LEVEL.

CHECK ALL FUSES.

UNIT NOT COOLING PROPERLY DEFROST UNIT.

CHECK EVAPORATOR FOR AIRFLOWRESTRICTION.

CHECK CONDENSER FOR AIRFLOWRESTRICTION.

CHECK BODY FOR DAMAGE OR AIRLEAKS.

Page 23: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PROBLEMS

23

GB

FAULT ALARM DISPLAY AND SAFETY FEATURES

Displaywill alternatebetweenan alarmmessage and the normaldisplay whenever anyof the failures listed below occur.

NOTE :Whenever the fault light is on, check display for fault message.

-- Reset the micro to start the unit.

-- Press FUNCTION CHANGE key.

-- Press the UP/DOWN ARROW keys until ALARM RST is displayed.

-- Press enter to clear alarm. Alarm CLR will now be displayed and unit will restart.

Other method to reset : move RUN/STOP switch to STOP. Unit resets and will startwhen RUN/STOP switch is moved to run position.

ALARM DISPLAY √= FAULT LIGHT ON

CODE ENGLISH DESCRIPTION

AL0 ENG OIL √ Low Oil Pressure

AL1 ENG HOT √ High coolant Temperature

AL2 HI PRESS √ High Discharge Pressure

AL3 START FAIL √ Start failure

AL4 LOW BATT √ Low battery voltage

AL5 HI BATT √ High battery voltage

AL6 DEFRFAIL Defrost Override

AL7 ALT AUX (√) No Alternator Auxiliary Output

AL8 STARTER √ Starter Motor Fault

AL9 1RA SENSOR √ Return Air Sensor Compartment 1Fault

AL10 2RA SENSOR √ Return Air Sensor Compartment 2Fault

AL11 WT SENSOR Coolant temperature sensor

Page 24: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PROBLEMS

24

ALARM DISPLAY √= FAULT LIGHT ON

CODE ENGLISH DESCRIPTION

AL12 HIGH CDT √ High discharge temperature

AL13 CD SENSOR Discharge temperature sensor

AL14 SBY MOTOR √ Standby motor overload

AL15 FUSE BAD √ Fuse open

AL16 3RA SENSOR √ Return Air Sensor Compartment 3Fault

AL17 DISPLAY Display

AL18 SERVICE 1 Maintenance Hour meter 1

AL19 SERVICE 2 Maintenance Hour meter 2

AL20 1RA OUT √ Compartment 1 Out-of-Range

AL21 2RA OUT √ Compartment 2 Out-of-Range

AL22 3RA OUT √ Compartment 3 Out-of-Range

AL23 NO POWER No power supply

√ = fault light ON

WARNING : AL0 (ENG OIL) could come up if alternator is badly connected.

Page 25: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

PROBLEMS

25

GB

FUSES

The fuses which protect the circuits of the control system are located in the box on theleft-hand side of the unit.

The fuses are accessed by loosening the screws that hold the control panel closed.

FUSE IDENTIFICATION

Rep. Item Amps

F1 General fuse 60 A

F2 Controller microprocessor fuse 5 A

F3 Run fuse 15 A

F4 Main heat valve fuse 5 A

F5 Speed control solenoid fuse 10 A

F6 Unloader fuse 3 A

F7 Liquid solenoid valve fuse (comp. 1) 3 A

F8 Liquid solenoid valve fuse (comp. 2) 3 A

F9 Liquid solenoid valve fuse (comp. 3) 3 A

F10 Fuel pump fuse 5 A

F11 Hot gas valve fuse (comp. 1) 10 A

F12 Hot gas valve fuse (comp. 1) 10 A

F13 Hot gas valve fuse (comp. 1) 10 A

Page 26: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT MAINTENANCE

26

Engine oil -- the oils recommended for use in your refrigeration unit must comply withtheAmericanPetroleum Institute’s (API) SG/CD rating. The use of any oil that does notmeet this rating may affect the warranty on the engine in the unit. The use of oil of theproper weight (viscosity) is also essential. The following chart indicates the SAEWeight Rating of the oil to be used in various climates :

10 W or 10W30

20 W or 15W40

30 W or15W40

_F

_C

Page 27: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT MAINTENANCE

27

GB

The following oils are accepted for use in Europe with the unit.

RECOMMENDED OILS

CARRIERAGIPANTARBP

ELF

FIATFINA

HAFA

IGOL

IMPERATORLABOMOBIL

OPALORLYPOLAROILRENAULT

TEXACOTOTALSHELL

UNIL

YACCO

CARRIER TD+15W--40

SIGMA TURBO SHPD 15W--40

GRAPHITE R 15W--40

VANELLUS C3 EXTRA 15W--40

VANELLUS FE 15W30

MULTIPERFORMANCE4D 15W--40

PERFORMANCE TROPHY 15W--40

URANIA TURBO 15W--40

KAPPA LDO 15W--40

KAPPA TD PLUS 15W--40

KAPPA EXTRA 15W--40

DETERGENTE 4DM 15W--40

STRADEX 900 ECO 15W--40

SYNTHIDEX ECO 15W--40

RALLYE TURBO 4E 15W--40

RALLYE TURBO 4E LD 15W--40

RAFF SUPER HPDO 15W--40

MEGAMAXI 15W--40

DELVAC SHC 15W--40

DELVAC 1400 SUPEROPALGET D 500 15W--40

TURBO 2002 15W--40

POLATRUCK 15W--40

KMX 2 PLUS 15W--30

KMX 2 PLUS 15W--40

MV5 “EUROPE”URSA SUPER TD 15W--40

RUBIA TIR MAX 15W40

MYRINA TX 15W--40

MYRINA T 15W--30

SUPER ROC 3D 15W--40

TURBO DX 15W--40

SM 4D + 15W--40

The above oil equivalents are based on the recommendations contained in thesuppliers’s technical literature.

Page 28: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT MAINTENANCE

28

UNIT MAINTENANCE SCHEDULES

All maintenance services must be done by a technician trained on Carrierproducts respecting all safety and quality standards of Carrier.

For the most reliable operation and for maximum life, your unit requires regularmaintenance. This includes oil and filter changes, fuel and air filter replacement,coolant replacement, belts etc

R90UNDER-MOUNT

Required Service

Withstandar-dized

A A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

Bdizedfilter C D C C

D

HOURS 250 1250 2250 3250 4250 5250 6250 7250 8250 9250 10250

In addition to the above service requirements, please adhere to the following :

The engine oil should be changed at least once per year, even if the engine has not runthe necessary number of hours.The coolant (anti-freeze) should be replaced after amaximum of two years.

Page 29: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT MAINTENANCE

29

GB

DESCRIPTION OF MAINTENANCE OPERATIONS

Service Operations

SERVICE A

S Drain the engine oil, replace oil filter

S Check engine cooling system

S Clean the cartridge of the dry air filter

S Check all bolts, screws and unit mounting bolts for tight-ness. Tighten as required (1st service only)S Check all belts

SERVICE B

S Replace fuel filter

S Check fuel pump filter

S Replace the cartridge of the dry air filter

S Check the battery terminals and fluid level

S Check compressor oil level

S Check alternator brushes

S Check engine thermostat for proper operation

S Check defrost:

- Check timer setting and function- Check refrigerant control valves for proper operation- Fans stop- Defrost ends automatically- Water drains from evaporator

S Check and adjust rocker arms

S Replace belts as necessary

SERVICE C

S Clean radiator and condenser

S Check refrigerant level

S Check and rebuild the alternator

S Clean and adjust fuel injectors (140 kg/cm2)

SERVICE DS Check all belt tension pulleys

S Change anti--freeze in diesel engine

S Check bearings in clutch(es) and electric motors.

Page 30: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

UNIT MAINTENANCE

30

BELTS

Dieselengine

Alternator

Compressor

Standbymotor

2

31

Quantity

1. Standby motor to compressor v-belt 1

2. Generator / standby motor / 12V alternator v-belt 1

3. Compressor / Diesel engine v-belt 1

GENESIS R90 UNDERMOUNT

Too little belt tension cause slippage and excessive belt wear. Too much tensionshortens belt and bearing life.

Properly adjusted belts give long lasting and efficient service (refer to maintenanceschedule).

FILTERS

1. Air filter

2. Fuel filter

3. Oil filter

1.

2.

3.

For code numbers consult the corresponding spare parts manual.

Page 31: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

STANDBY OPERATION GUIDELINES

31

GB

For safe, reliable operation in Standby mode, it is important to consider the followingguidelines :

D Never plug the unit in to the power source with the main switch in the RUN position.The main switch should always be in the STOP position when connecting the unitto the power source.

D The fusing and extension cable used for Standby operation should conform to thefollowing:

UnitFuse

200/240/3/50 Hz220/256/3/60 Hz

Fuse350/415/3/50 Hz380/460/3/60 Hz

Standardized extensioncable

H.07.RNF220/256/3/60 Hz 380/460/3/60 Hz

220 volts 380 volts

GenesisR90 U 40 A 29 A 4 x 10 mm2 4 x 6 mm2

D The unit connection cable must be fitted with a ground connection. The cable mustbe connected to earth.

D On the 380V supply, it is recommended to use a differential protection on each plug.

D When performing service and/or maintenance procedures on a refrigeration unit,make certain that the unit is disconnected from the power source and that the mainunit switch is turned OFF.

D Operations on the 380 V supply for the unit must only be carried out by authorizedpersonnel.

D Warning : changing the operation of a unit from 380 V to 220 V implies a change inthe electrical coupling, adjustment of the overload relay and for certain unit models,the replacement of some components. Please consult our technical service.

Page 32: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

MANUFACTURER INFORMATION

32

WARRANTY

As soon as you receive your warranty card, please keep it in a safe place.

The card will be requested for any intervention under warranty which needs to beperformed on your equipment. Always update the service chart which is to be foundinside the front cover.

This manual refers to the standard model.

Some optionsmay not appear in it, and in such cases you are requested to consult ourTechnical Services.

Carrier Transicold constantly seeks to improve the quality of its products and thereforereserve the right to modify them without prior notice.

INSTALLATION

During assembly and routine service operations, access to the unit may involvecertain risks.

TAKE EVERY SAFETY MEASURE TO ACCESS THE UNIT (e.g.: standard ladders,running board with railing, safety belt etc.)

Installation of this unit requires no special knowledge of refrigeration. To fit thenosemount unit to the vehicle body, it is necessary only to slide the evaporator sectioninto the opening in the front panel and secure using the bolts provided.

Advice

When handling, use suitable lifting gear attached to the lifting points provided for thispurpose on the unit.

Note : The unit should not protude out of the body.

BATTERY

Maintenance :

Never leave a unit more than amonthwithout running. In case of long standstill, chargethe battery independently.

Before performing any welding on the chassis, take care to disconnect the battery ofthe vehicle and the 12VDC and 3 phase alternator, and any other electronic system.

Never try to start the vehicle with a booster because this could damage the electroniccomponents in the unit or on the vehicle.

1. Check that all mounting bolts are well tightened and suitable for use.

2. When you drill holes in the unit or in the body of the vehicle, be careful not topierce the refrigeration tubes or the electrical wiring.

3. When you are working next to the unit (condenser and evaporator) be carefulnot to cut yourself on the sharp edges.

Page 33: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

MANUFACTURER INFORMATION

33

GB

4. When the unit is running, keep your hands away from belts and fan motors.

5. Never close the discharge valves of the compressor when the unit isrunning.

6. In case of repair, only use manometer by--pass hoses which are in a goodcondition and avoid their contact with belts, pulley and fan motor.

7. The refrigerant liquid must be handled with great care.

8. Next to a flame the refrigerant liquid gives off a phosgene gas which has anunpleasant smell and irritates the lungs.

9. Never heat up a closed cooling circuit with a flame, the cooling system must behandled with great care.

10. When liquid refrigerant is in contact with the atmosphere, it evaporates andfreezes everything it makes contact with.

First aid in case of frost--bite :

a) Cover up the frost--bitten part.

b) Warm up quickly the frost--bitten part by dipping it into lukewarm water (not hot).

c) In case you do not have water wrap the wounded place in a clean cloth.

d) If refrigerant fluid has been splashed into your eyes, rinse them immediately withcleanwater; as a precaution, you are recommended to have amedical examination aswell.

11. Cooling oil

Synthetic or derived from fuel

D Avoid contact with skin.

D Wash carefully after handling.

REMARKS ABOUT SAFETY :

Diesel engine

NEVER START THE ENGINE IN A CLOSED ROOM, THE EXHAUST GAS ISPOISONOUS.

It is colourless and adourless and created by incomplete combustion of hydrocarbons.

Exhaust gas is poisonous; breathing it in induces drowsiness and may lead to loss ofconsciousness.

Page 34: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

MANUFACTURER INFORMATION

34

The following symptons indicate an exhaust gas inhalation:

D Blackout

D Intense headache

D Sudden weakness and sleepiness

D Vomiting

D Muscular contractions

D Beating temples

If you feel one of the above mentioned symptoms, go out and breathe fresh air.

The maintenance operation should be done at the recommended intervals on yourequipment. Check the exhaust gas system to avoid gas inhalation.

If you notice a noise ormodification of the exhaust system stop immediately the engineand call sales service center for checking and repair.

Standby and start/stop :

The unit will start automatically, keep away from belts, pulleys and fans.

Page 35: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

“A.T.P. EUROPE” REGULATION EXTRACT

35

GB

(Date: March 1974)

Approval of vehicles intended for the carriage of perishable goods.

Before putting a refrigerated vehicle into service, it is necessary to have it approvedby the Regional Health Department.

CHARACTERISTICS OF VEHICLES USED FOR CARRYING PERISHABLEGOODS; REFRIGERATION UNIT.

The refrigeration unit is an insulatedunit witha coolingsystemwhichmakes it possible,with a mean outside temperature of +30_C, to lower the temperature inside the emptybody and to maintain this low temperature in the following way:

CLASS A

Refrigeration unit furnished with a cooling system whereby a temperature between+12_C and 0_C inclusive can be chosen.

CLASS B

Refrigeration unit furnished with a cooling system whereby a temperature between+12_C and --10_C inclusive can be chosen.

CLASS C

Refrigeration unit furnished with a cooling system whereby a temperature between+12_C and --20_C inclusive can be chosen.

The cooling capacity of a unit is determined by a test carried out in one of the approvedtesting stations and ratified by an official report.

Note: The “K“ factor of bodies intended to be classified as C must be equal to or lowerthan 0.4 W/m2 _C.

Page 36: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

“A.T.P. EUROPE” REGULATION EXTRACT

36

SIGNS, IDENTIFICATION MARKS AND PLATES TO BE ATTACHED TOREFRIGERATION UNITS

Refrigeration Plate

This reference must be followed by identification marks according to the following list:

Standard refrigeration unit Class A FNA

Reinforced refrigeration unit Class A FRA

Reinforced refrigeration unit Class B FRB

Reinforced refrigeration unit Class C FRC

In addition to the above identification marks, the date (month and year) of expiry of theapproval certificate must be indicated.

Example:

FRC

6--2000

(6 = month (June) 2000 = year)

Very important

Regularly check the expiry date of the approval certificate. During transport, theapproval certificate or provisional certificate should be shown on request of qualifiedagents. To have an insulated unit approved as a refrigeration unit, an application tomodify the approval certificate should be sent to the regional health office.

Page 37: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

EMERGENCY ROAD SERVICE

37

GB

AtCarrier Transicoldwe’reworking hard to give you complete servicewhen andwhereyou need it. That implies a worldwide network of dealers and available an emergencyservice. These service centers are manned by factory--trained service personnel andbacked by extensive parts inventories that will assure you of prompt repair.

Should you encounter a unit problem with your refrigeration unit during transit, followyour company’s emergency procedure or contact the nearest Carrier Transicoldservice center. Consult the directory to locate the service center nearest you. Thisdirectory may be obtained from your Carrier Transicold dealer.

If you are unable to reach a service center, call Carrier Transicold’s 24 Hour Assistance:

In Europe, please use the following free phone numbers from :

A AUSTRIA 0800 291039B BELGIUM 0800 99310CH SWITZERLAND 0800 838839D GERMANY 0800 1808180DK DENMARK 808 81832E SPAIN 900 993213F FRANCE 0800 913148FIN FINLAND 0800 113221GB GREAT BRITAIN 0800 9179067GR GREECE 00800 3222523H HUNGARY 00800 13526I ITALY 800 791033

IRL IRELAND 1800 553286L LUXEMBURG 0800 3581

RUS RUSSIA 810 800 200 31032N NORWAY 800 11435NL THE NETHERLANDS 0800 0224894P PORTUGAL 8008 32283PL POLAND 00800 3211238S SWEDEN 020 790470

Page 38: GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL … R90U en… · GENESIS R90 UNDERMOUNT OPERATOR’S MANUAL 1 G ... Maintenance program will also help to control operating costs,

EMERGENCY ROAD SERVICE

38

From other countries : +32 9 255 67 89

Direct : +32 9 255 67 89

In Canada or United States, call 1 -- 800 -- 448 -- 1661.

When calling, please have the following information ready for fastest service :

D Your name, the name of your company, and your location.

D A telephone number where you can be called back.

D Refrigeration unit model number and serial number.

D Box temperature, set--point and product.

D Brief description of the problem you are having, and what you have already done tocorrect the problem.

We will do everything we can to get your problem taken care of and get you back onthe road.