63 g Multilin Generator Protection Complete protection for small to medium sized generators Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P&C life cycle costs Combined generator and transformer protection Advanced automation capabilities for providing customized protection and control solutions Robust network security enabling Critical Infrastructure Protection through user command logging, and dual permission access control Application flexibility with multiple I/O options and programmable logic (FlexLogic™) High-end fault and disturbance recording eliminating the need for redundant recording devices Ambient temperature monitoring with alarming when outside temperature exceeds upper thresholds High-speed peer-to-peer communications allowing reduction of relay to relay wiring and associated installation costs Embedded IEC61850 Protocol Small to medium sized generators typically driven be steam, gas or hydraulic turbines Pumped Storage Generators Combined Generator and Transformer in the zone of protection Distributed Generator (DG) interconnect protection per IEEE 1547 Metering - current, voltage, power, energy, frequency Oscillography – analog and digital parameters at 64 samples/cycle Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs Data Logger - 16 channels with sampling rate up to 1 sample / cycle Setting Security Audit Trail for tracking changes to G30 configuration Monitoring and Metering Protection and Control Overall unit differential including transformer Restricted ground fault Split phase protection Loss of excitation, overexcitation Third harmonic neutral undervoltage Generator unbalance Reverse and low forward power Accidental energization Synchronism check Phase sequence reversal for pumped storage EnerVista TM Software Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures EnerVista TM Integrator providing easy integration of data in the G30 into new or existing monitoring and control systems Communications Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, C37.94 Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) Direct I/O – secure, high-speed exchange of data between URs for transformer tripping applications Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports G30 GENERATOR PROTECTION SYSTEM Small to medium generators & combined generators and transformer protection FEATURES APPLICATIONS KEY BENEFITS Robust communications with up to 8 HardFiber Bricks Seamless integration with existing G30 functions Redundant architecture for dependability and security IEC 61850 Process Bus Interface

Upload: phamque

Post on 28-Feb-2018

220 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

63g Multilin

Gen

erat

or P

rote

ctio

n

• Completeprotectionforsmalltomediumsizedgenerators• CompleteIEC61850ProcessBussolutionprovidingresource

optimizationandminimizingtotalP&Clifecyclecosts• Combinedgeneratorandtransformerprotection• Advancedautomationcapabilitiesforprovidingcustomized

protectionandcontrolsolutions• RobustnetworksecurityenablingCriticalInfrastructure

Protectionthroughusercommandlogging,anddualpermissionaccesscontrol

• ApplicationflexibilitywithmultipleI/Ooptionsandprogrammablelogic(FlexLogic™)

• High-endfaultanddisturbancerecordingeliminatingtheneedforredundantrecordingdevices

• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds

• High-speedpeer-to-peercommunicationsallowingreductionofrelaytorelaywiringandassociatedinstallationcosts

• EmbeddedIEC61850Protocol

• Smalltomediumsizedgeneratorstypicallydrivenbesteam,gasorhydraulicturbines

• PumpedStorageGenerators

• CombinedGeneratorandTransformerinthezoneofprotection

• DistributedGenerator(DG)interconnectprotectionperIEEE1547

• Metering-current,voltage,power,energy,frequency• Oscillography–analoganddigitalparametersat

64samples/cycle• EventRecorder-1024timetaggedeventswith0.5msscanof

digitalinputs• DataLogger-16channelswithsamplingrateupto

1sample/cycle• SettingSecurityAuditTrailfortrackingchangestoG30

configuration

Monitoring and Metering

Protection and Control• Overallunitdifferentialincludingtransformer• Restrictedgroundfault• Splitphaseprotection• Lossofexcitation,overexcitation• Thirdharmonicneutralundervoltage• Generatorunbalance• Reverseandlowforwardpower• Accidentalenergization• Synchronismcheck• Phasesequencereversalforpumpedstorage

EnerVistaTM Software• GraphicalLogicDesignerandLogicMonitortosimplify

designingandtestingprocedures• EnerVistaTMIntegratorprovidingeasyintegrationofdatain

theG30intoneworexistingmonitoringandcontrolsystems

Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,

RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,

ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–secure,high-speedexchangeofdatabetween

URsfortransformertrippingapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber

opticportsand2copperports

G30GEnEraTor

ProTECTion SySTEMSmalltomediumgenerators&combinedgeneratorsandtransformerprotection

FEaTurES

aPPliCaTionS

KEy BEnEFiTS

• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingG30functions• Redundantarchitecturefordependabilityandsecurity

iEC 61850 Process Bus interface

Page 2: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com64

G30Generator Protection SystemG

ener

ator

Pro

tect

ion

Protection and ControlThe G30 Generator protection systemprovides comprehensive protection forsmall to medium sized steam, hydraulicand combustion-turbine generatorsas well as applications that have boththe generator and transformer inthe same zone of protection. The G30is ideal for protecting single and multi-polegeneratorswith singleor split phasewindingsconfigurationofgenerators.TheG30 includes advanced automation andcommunication capabilities, extensiveI/O options, and powerful fault recordingfeatures that can simplify fault anddisturbancetroubleshootingandminimizegenerator downtime. As part of the URfamily,theG30providessuperiorprotectionandcontrolthatincludes:

Generator/Transformer Differential

High-speedpercentdifferentialprotectionis provided for detecting and clearingboth generator stator and transformerwinding faults that occur in the zone ofprotection of a single generator. Thedifferential protection element has built-in phase compensation and magnitudecompensationcharacteristicsthatallowfordealingwiththeinherentoffsetthatoccurswith CTs located on different windingsof the transformer. These compensationcharacteristics eliminate the need forinstalling additional interposing CTs to

account for the difference in parametersmeasuredbytherelay.

2nd Harmonic inrush inhibit

The G30 utilizes a 2nd Harmonic InrushInhibit function to block the G30 fromtripping under transformer inrushconditions that can otherwise causethe differential element to maloperate.This element can be configured toinclude energization of different types oftransformersbyusingeitheratraditionaloradaptivemodeof2ndHarmonicrestraint.

The adaptive 2nd harmonic restraintmaintains protection dependability andspeed on internal faults while ensuringsecurityduringinrushconditionsevenwithweaksecondharmonics.

overexcitation inhibit

An increase in transformer voltage ordecrease in system frequencymay resultin overexcitation of the transformer. It isoften desirable to prevent operation ofthe percent differential element in thesecasesthereforeafirthharmonicinhibitis

PTs Located on Transformer HV Side

G30 Generator Protection System

24

34

50G27X 59X

METERING87GT

40 50P 50N 51P 51N 46 67N

51G27TN

67P

64REF

67_250/27

27P 59P 59_2 59N 81O 81U 81R

25CLOSETRIP

Functional Block Diagram

The G30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into HMI or SCADA monitoring and control systems like Viewpoint Monitoring as shown.

G30 - Protection, Metering, Monitoring and Control

DeviceNumber Function24 VoltsPerHertz25 SynchronismCheck27P PhaseUndervoltage27TN ThirdHarmonicNeutralUndervoltage27X AuxiliaryUndervoltage27/50 AccidentalEnergization32 DirectionalPower40 LossofExcitation46 StatorCurrentUnbalance50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50SP SplitPhaseInstantaneousOvercurrent51G GroundTimeOvercurrent51P PhaseTimeOvercurrent59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage67_2 NegativeSequenceDirectionalOvercurrent67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent81O Overfrequency81R RateofChangeofFrequency81U Underfrequency87GT Generator/TransformerDifferential87RGF RestrictedGroundFault

ANSIDeviceNumbers&Functions

Page 3: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com 65

G30Generator Protection System

Gen

erat

or P

rote

ctio

n

No Transformer

G30 Generator Protection System

24

34

87G 50G27X 59X

METERING87

40 50P 50N 51P 51N 46 67N

51G27TN

67P 67_250/27

27P 59P 59_2 59N 81O 81U 81R

25CLOSETRIP

integratedintopercentdifferentialfunctionto protect for overexcitation conditionsresulting from an increased V/Hz ratio.Theoverexcitation inhibitworksonaper-phasebasisandisuserdefinable.

Split Phase Protection

Split phase protection is provided forsensitivedetectionforinter-turnfaultsandcanberuninconjunctionwiththeprimarystatordifferentialprotection. Independentsettingsareprovidedonaper-phasebasisand a single-slope bias characteristic isusedtoallowoperationonmachineswithasectionofwindingbypassed.

restricted Ground Fault (rGF)

Restricted Ground Fault protection (alsoknown as zero sequence differential)extendsprotectioncoveragetotheneutralpoint of the stator winding, where faultcurrentsmay be below the pickup of themain stator differential element. The low-impedanceRGFprotectionprovidedbytheG30 uses an optimized adaptive restraintsignal that provides security for externalfault conditions that may cause CTsaturationwhilestillmaintainingsensitivityforinternalfaults.

Sensitive Directional Power

Two separate directional power elementsare provided to detect reverse and lowforward power conditions that is oftenneeded for ensuring power only flows inone direction through the breaker. Eachelement responds to either reverse orlow forwardpower flowandcanbeusedto provide independent alarm and tripsettings.

loss of Excitation

Generator loss of excitation protectionis provided via two negative offset mhocharacteristics as per IEEE C37.102.Independentpickuptimedelaysettingsandblocking input provide security for blownVTfusesandpowerswingconditions.

Frequency rate of Change

Thefouravailablefrequencyrateofchange(df/dt) elements can be used to provideprotection against system disturbancesthrough load shedding and to provideanti-islandingprotection. Theseelementsmonitorthespeedbywhichthefrequencychangesinanydirection,throughvoltage,current,andfrequencysupervision.

Pump Storage Generator

The G30 can be used for protectinggenerators that are also run as pumpstorage motors without the need forswitchingtheCTsecondarycircuitry. TheG30 is able to automatically compensatefor the phase reversal that occurs whenthegeneratorisbeingrunasamotor.

Synchronism Check

The G30 provides elements to monitordifferences in voltage magnitudes,phase angles, and frequencies toperform synchronism check across up totwo breakers. The G30 can be used inconjunctionwithanexternalsynchronizeras an independent check of thesynchronizerpriortoclosingthegeneratorbreaker.

iEC 61850 Process BusThe IEC 61850 Process Bus module isdesigned to interfacewith theGEMultilinHardFiber System, allowing bi-directionalIEC61850fiberopticcommunications.TheHardFiberSystemisdesignedtointegrateseamlesslywiththeexistingUniversalRelay

The Adaptive 2nd Harmonic Inhibit function will stop blocking the differential element as soon as the 2nd harmonic level drops below the pickup level if the angle of the 2nd Harmonic to Fundamental ratio is close to 0° or 180° (Point A). If the angle of the 2nd Harmonic to Fundamental ratio is close to 90°or 270°, this is a indication that the transformer is an inrush condition even if the magnitude drops below the pickup level, the Adaptive 2nd Harmonic Inhibit function will continue to block the differential element for an extended period of time (Point B).

2nd Harmonic Blocking Characteristic

Page 4: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com66

G30Generator Protection SystemG

ener

ator

Pro

tect

ion

applications,includingprotectionfunctions,FlexLogic,meteringandcommunications.

TheGEMultilinHardFiberSystemoffersthefollowingbenefits:

• CommunicatesusingopenstandardIEC61850messaging

• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations

• IntegrateswithexistingG30’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule

• DoesnotintroducenewCyberSecurityconcerns

VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.

advanced automationTheG30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmable logic, communication,andSCADA capabilities that far surpass whatis found in the average generator relay.TheG30 integrates seamlesslywith otherURrelaysforcompletesystemprotection,includingtheunitandauxiliarytransformers,andBalanceofPlantprotection.

Flexlogic™

FlexLogic™ is the powerful UR platformprogramming logic engine that providestheabilityofcreatingcustomizedprotectionand control schemes thereby minimizingthe need, and the associated costs, ofauxiliarycomponentsandwiring.Using FlexLogic™, the G30 can beprogrammed to provide required trippinglogic along with custom scheme logicfor generator breaker control (includinginterlocking with external synchronizers),transfer tripping schemes for remotebreakers and dynamic setting groupchanges.

Scalable HardwareTheG30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesign allows for easy configuration andfutureupgrades.

• MultipleCT/VTconfigurationsallowforimplementationofmanydifferentialschemes,includingconcurrentsplit-phaseanddifferentialprotection

• Upto80digitalinputsandupto56digitaloutputsareavailable

• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs

• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure

Monitoring and MeteringTheG30 includeshighaccuracymeteringand recording for all AC signals. Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. Currentand voltage parameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.

Fault and Disturbance recording

The advanced disturbance and eventrecording features within the G30 cansignificantly reduce the time needed forpostmortem analysis of power systemeventsandcreationof regulatoryreports.Recordingfunctionsinclude:

• SequenceofEvent(SOE)-1024timestampedevents

• Oscillography,

-64digital&upto40Analogchannels

• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel

• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues

The very high sampling rates and largeamounts of storage space available fordata recording in the G30 can eliminatethe need for installing costly standalonerecordingequipment.

advanced Device Health Diagnostics

The G30 performs comprehensive devicehealthdiagnostictestsduringstartupandcontinuously at runtime to test its ownmajor functions and critical hardware.These diagnostic tests monitor forconditions thatcould impactsecurityandavailability of protection, and present

FlexlogicTM Designer

Flexlogic allows for customizing the G30 to operate and control the breakers and other auxiliary devices needed to fit most generator protection schemes and applications.

Page 5: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com 67

G30Generator Protection System

Gen

erat

or P

rote

ctio

n

device status via SCADA communicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issues helps improve systemuptime.

• Comprehensivedevicehealthdiagnosticperformedduringstartup

• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals

• Input,outputs,tripcircuitsandanalogchannelsarecontinuouslymonitoredforaccuracyandperformance

CommunicationsThe G30 provides advanced commun-icationstechnologiesforremotedataandengineering access,making it the easiestandmostflexiblegeneratorprotectionrelaytouseandintegrateintonewandexistinginfrastructures. Direct support for fiberoptic Ethernet provides high-bandwidthcommunications allowing for low-latencycontrols and high-speed file transfers ofrelay fault and event record information.The available redundant Ethernet optionand the embedded managed Ethernetswitchprovidethemeansofcreatingfaulttolerant communication architectures inan easy, cost-effective manner without

theneedfor intermediarycommunicationhardware.The G30 supports the most popularindustrystandardprotocolsenablingeasy,direct integration into DCS and SCADAsystems.

• IEC61850

• DNP3.0

• EthernetGlobalData(EGD)

• IEC60870-5-104

• ModbusRTU,ModbusTCP/IP

interoperability with Embedded iEC61850

Use the G30with integrated IEC61850 tolower costs associated with substationprotection, control and automation. GEMultilin’s leadership in IEC61850 comesfrom thousands of installed devices andfollows on seven years of developmentexperiencewithUCA2.0.

• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging

• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVistaViewpointEngineer

• IntegrateGEMultilinIEDsandgenericIEC61850compliantdevicesseamlesslyinEnerVistaViewpointMonitoring

Direct i/o Messaging

DirectI/Oallowsforsharingofhigh-speeddigital information between multiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexer channel bank. Regardless oftheconnectionmethod,DirectI/Oprovidescontinuous real-time channel monitoringthat supplies diagnostics information onchannelhealth.Direct I/Oprovides superior relay-to-relaycommunications that can be used inadvancedinterlocking,generationrejectionandotherspecialprotectionschemes.

• Communicationwithupto16URrelaysinsingleorredundantringsratherthansimplisticpoint-to-pointconfigurations

• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections

• Built-incontinuousloopandchannelmonitoringprovidesreal-timediagnosticsofyourcommunicationchannels–noexternalorhandheldtesterrequired

Power System Troubleshooting

The G30 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Page 6: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com68

G30Generator Protection SystemG

ener

ator

Pro

tect

ion

Multi-language

TheG30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista setup software, and productmanual. Easily switch between Englishand an additional language on the localdisplayswithoutuploadingnewfirmware.

EnerVistaTM SoftwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifiesevery aspect of using the G30 relay. TheEnerVista suite provides all the tools tomonitor the status of your generator,maintain your relay, and integrateinformation measured by the G30 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software included withevery UR relay, to carry out postmortemeventanalysistoensureproperprotectionsystemoperation.

EnerVista™ launchpad

EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallof thesetupandsupport toolsneeded

forconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpad allows configuring devices inreal-timeby communicating using serial,Ethernet,ormodemconnections,orofflineby creating setting files to be sent todevicesatalatertime.

Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:

• Manuals

• ApplicationNotes

• GuideformSpecifications

• Brochures

• WiringDiagrams

• FAQs

• ServiceBulletins

Viewpoint Monitoring

Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems. ViewpointMonitoring provides a

completeHMI packagewith the followingfunctionality:

• Plug&PlayDeviceMonitoring

• SystemSingle-LineMonitoring&Control

• AnnunciatorAlarmScreens

• TrendingReports

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

Viewpoint Engineer

ViewpointEngineerisasetofpowerfultoolsthatwillallowyoutoconfigureandtestURrelays at a system level in an easy-to-usegraphicaldrag-and-dropenvironment.ViewpointEngineerprovides the followingconfigurationandcommissioningutilities:

• GraphicalLogicDesigner

• GraphicalSystemDesigner

• GraphicalLogicMonitor

• GraphicalSystemMonitor

Viewpoint Maintenance

ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:

• SettingsSecurityAuditReport

• DeviceHealthReport

• SingleClickFaultDataRetrieval

EnerVista™ integrator

EnerVistaTMIntegratorisatoolkitthatallowsseamlessintegrationofGEMultilindevicesinto new or existing automation systems.IncludedinEnerVistaTMIntegratoris:

• OPC/DDEServer

• GEMultilinDrivers

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

The G30 tracks and records information about configuration changes that have been made to the relay thereby providing a method of auditing system security and engineering processes

Providing Traceability and regulatory audit Tracking

Page 7: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

www.GEMultilin.com 69

G30Generator Protection System

Gen

erat

or P

rote

ctio

n

Typical Wiring

user interfaceThe G30 front panel provides extensivelocal HMI capabilities. The local displayis used formonitoring, statusmessaging,fault diagnosis, and device configuration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.

LEDIndicators

Multi-LanguageDisplay• English• Russian• French• Chinese

UserProgrammablePushbuttons

G60-H00-HCH-F8F-H6G-M8H-PXX-uXX-WXX

830744A2.CDR

1

PowerSupply

9

CPU

JU MX LW KV BHT DN G FPS Rminimum

GROUNDBUS

DCG30 GENERATOR MANAGEMENT RELAY

RS-232

DB-9

(front)

UR COMPUTER

1

TXD RXD

RXD TXD

SGND SGND

1 832

207645

22

CONNECTORCONNECTOR

2 23 34 45 56 67 78 89 9

6

Inputs/outputs

8

VT/CT

8

CT

TC

TC

2

1

SURGE

H6a

H8a

H5b

H7b

H8b

H5a

H7a

H6c

H8c

H5c

H7c

6G H1a

H2b

H1cH1b

H2c

H2a

H4a

H4c

H3bH3a

H4b

H3c

H1

H2

H3

H4

I

V

I

V

I

V

I

V

CRITICALFAILURE

OUTPUT

CONTROLPOWER

HILO

1

FILTERSURGE

B3a

B1b

B8a

B6b

B8b

B6a

B3b

B1aB2b

B5b

PROVIDED

F1a

F1b

F1c

F2a

F2b

F2c

F3a

F4a

F5a

F6a

F7a

F8a

F3b

F4b

F5c

F6c

F7c

F8c

F3c

F4c

VA VB

VC VXVA VB

VC VXIA ICIB IG

IA5

IC5

IB5

IG5

IA1

IC1

IB1

IG1

F5a

F6a

F7a

F5c

F6c

F7c

VA VB

VCVA VB

VC

M1a

M1b

M1c

M2a

M2b

M2c

M3a

M4a

M3b

M4b

M3c

M4c

IA ICIB IGIA5

IC5

IB5

IG5

IA1

IC1

IB1

IG1

Multilin

B

A

C

R

52

ALTERNATE

B

A

C

NOTE:

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

Page 8: GEnEraTor ProTECTion SySTEM - · PDF filecharacteristics as per IEEE C37.102. Independent pickup time delay settings and blocking input provide security for blown VT fuses and power

G30 - * 00 - H * * - F ** - H ** - M ** - P ** - u ** - W/X ** For Full Sized Horizontal MountBaseUnit G30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+Multi-modeST10BaseF H RS485+Multi-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 01 EthernetGlobalData(EGD) 03 IEC61850 04 EthernetGlobalData(EGD)+IEC61850Mount/Coating H Horizontal(19"rack)-Standard A Horizontal(19"rack)-HarshEnvironmentCoating V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshEnvironmentCoatingUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DC L 24-48V(DConly)CT/VTDSP 8L 8L Standard4CT/4VTw/enhanceddiagnostics 8M 8M SensitiveGround4CT/4VTw/enhanceddiagnostics 8N 8N Standard8CTw/enhanceddiagnostics 8R 8R SensitiveGround2CT/6VTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX XX NoModule 4A 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5C 5C 5C 5C 5C 5C 8RTDInputs 5E 5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs 5F 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7R G.703,1Channels 7S G.703,2Channels 7T RS422,1Channels 7W RS422,2Channels 76 IEEEC37.94,820nm,multimode,LED,1Channel 77 IEEEC37.94,820nm,multimode,LED,2Channel 2A C37.94SM,1300nmSinglemode,ELED,1ChannelSinglemode 2B C37.94SM,1300nmSinglemode,ELED,2ChannelSingle 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)ttt

www.GEMultilin.com70

G30Generator Protection SystemG

ener

ator

Pro

tect

ion

ordering

ordering note: ToviewthelatestoptionsavailablefortheG30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.

• URApplicationsILearningCD TRCD-URA1-C-S-1

• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1

• ViewpointEngineer VPE-1

• ViewpointMaintenance VPM-1

• ViewpointMonitoringIEC61850 VP-1-61850

accessories for the G30 • ViewGuideformspecifications