gb 50009-2001 - 2006 load code for the building design, china

118

Click here to load reader

Upload: xin-liang

Post on 06-Sep-2015

168 views

Category:

Documents


66 download

DESCRIPTION

Load Code for Building Structures, Chinese National Standard.

TRANSCRIPT

  • NATIONAL STANDARD OF

    THE PEOPLES REPUBLIC OF CHINA

    GB 50009-2001

    Load Code for the Design of Building Structures

    (2006 Edition)

    Issued on January 10, 2002 Implemented on March 01, 2002 Jointly Issued by the Ministry of Construction (MOC) and the General

    Administration of Quality Supervision, Inspection and Quarantine (GAQSIQ) of the Peoples Republic of China

    GB

  • Notice of Issuing Load Code for the Design of Building Structures

    JIANBIAO [2002] No.10 In accordance with Notice of Printing and Distributing the Establishment and

    Amendment Plan of Project Construction Standard of 1997 (JIANBIAO [1997] No.108) issued by the Ministry of Construction, the Load Code for the Design of Building Structures jointly developed by the Ministry of Construction and related departments has been authorized by related departments as a national standard, with the number of GB 50009- 2001 and will be implemented from March 1, 2002. Among which, articles 1.0.5, 3.1.2, 3.2.3, 3.2.5, 4.1.1, 4.1.2, 4.3.1, 4.5.1, 4.5.2, 6.1.1, 6.1.2, 7.1.1 and 7.1.2 are compulsory ones and shall be executed strictly. At the same time, the original Load Code for Building Structures (GBJ9-87) shall be terminated on December 31, 2002. The Code is in the charge of the Ministry of Construction that is responsible for the interpretation of compulsory articles. The China Architecture Research Institute will be responsible for the interpretation of technical contents. In addition, the Code shall be published by China Architecture & Building Press (CABP) with the organization of Research institute of Standards & Norms.

    Ministry of Construction P. R. China July 20, 2001

  • Foreword This Code has been overall revised in accordance with Notice of Printing and

    Distributing of the Establishment and Amendment of Building Construction of 1997 (JIANBIAO [1997] No.108) issued by the Ministry of Construction and the Load Code for the Design of Building Structures (GBJ 9-87) jointly approved by China Architecture Scientific Research Institute and related departments.

    During the process of revising, the team has carried out monographic study, summarized design experience in recent years, referred to related contents of foreign norms and international standards, widely asked for opinions from related departments all over the country and finalized after repeated amendment.

    This Code can be divided into seven chapters and seven appendices. Primary contents revised are as follows:

    1. In accordance with the rule of combination stated in Unified Standard for Reliability Design of Building Structures and getting rid of Wind Combination, the combination controlled by permanent load effect was added to the load fundamental combination. In the limit design of regular service, for the short-term effect combination, characteristic and frequent combinations are listed and at the same time, the frequent value coefficient was added to the variable load. For all combination values of variable loads, respective combination value coefficient is listed.

    2. Partial adjustment and amendment of floor live load. 3. Adjustment has been made to roofing rectangular distribution live load that permits no

    person on the roof and provisions on roof gardens and helicopter pad load have been added. 4. Character of service for crane has been changed into work classes of cranes. 5. According to new observation data, statistics of wind pressure and snow pressure from

    national weather stations has been collected. At the same time, the basic value of wind and snow load recurrence interval has been changed from 30 years to 50 years. In the appendix, the 10-year, 50-year and 100-year wind pressure and snow pressure in main stations all over the country have been listed.

    6. One Type has been added to the terrain roughness. 7. For the wind pressure altitude variation coefficient of buildings in a mountainous area,

    compensation factors have been given for the consideration of terrain conditions. 8. Specific provisions have been made to wind load of envelop enclosure members. 9. The interactive influences between buildings in architectural complex have been put

    forward. 10. For flexible structures, the test requirements for crosswind vibration have been added.

    This Code may be revised as required. Information and contents revised will be published on the journal of Standardization of Engineering Constructions. The compulsory articles in this Code shall be executed strictly. In order to improve the quality of this Code, units shall sum up experience and collect background information. For feedback of related opinions and suggestions, please contact: China Architecture Scientific Research Institute (No.30 East Road, North Third Ring).

    Chief Development Organization: China Architecture Technical Research Institute Participating Development Organizations: Construction Department of Tongji University,

  • Building Design Institute, Beijing International Design Institute of China Light Industry, Beijing: China Institute of Architecture Standard Design Press, Beijing Institute of Architectural Design and China Weather Scientific Research Institute

    Chief Drafting Staffs: Chen Jifa, Hu Dexin, Jin Xinyang, Zhang Xiangting, Gu Zicong, Wei Caiang, Cai Yiyang, Guan Guixue, Xue Hang

  • Contents 1. General Principles ................................................................................................................. 1 2. Terms and symbols ................................................................................................................ 1

    2.1 Terms ........................................................................................................................... 1 2.2 Main symbols............................................................................................................... 3

    3. Classification of loads and combination of load effect ......................................................... 4 3.1 Classification of loads and representative values of a load ......................................... 4 3.2 Load combination ........................................................................................................ 5

    4. Live load of floors and roofs ................................................................................................. 7 4.1 Rectangular distribution live load on floors of civilian buildings ............................... 7 4.2 Floor live load of industrial buildings........................................................................ 10 4.3 Roof live load............................................................................................................. 10 4.4 Roofing dust load........................................................................................................11 4.5 Construction and repair load as well as handrail horizontal load .............................. 13 4.6 Dynamic coefficient................................................................................................... 14

    5. Crane load............................................................................................................................ 14 5.1 Vertical and horizontal load of cranes........................................................................ 14 5.2 The combination of several cranes ............................................................................ 15 5.3 Dynamic coefficient of crane loads ........................................................................... 15 5.4 The combination value, frequent value and quasi-permanent value of crane loads .. 15

    6. Snow load ............................................................................................................................ 16 6.1 The characteristic value/nominal value and reference snow pressure of snow loads 16 6.2 Coefficient of snow distribution over the roof........................................................... 17

    7. Wind load ............................................................................................................................ 20 7.1 The characteristic value/nominal value and reference wind pressure of wind loads . 20 7.2 Variation coefficient of wind pressure altitude .......................................................... 21 7.3 Wind load coefficient ................................................................................................. 22 7.4 Downwind vibration and wind vibration coefficient ................................................. 36 7.5 Gustiness factor.......................................................................................................... 38 7.6 Crosswind vibration................................................................................................... 39

    Appendix A Deadweight of Commonly-used Materials and Members................................... 41 Appendix B Method for Deciding the Floor Isoeffect Rectangular Distribution Live Load... 55 Appendix C Floor live load of industrial buildings................................................................. 60 Appendix D Measurement Method of Fundamental Snow Pressure and Wind Pressure........ 66 Appendix E Empirical Formula for the Structure Which is Natural Vibration Period .......... 108 Appendix F Approximation of the Structural Mode Factor....................................................111 Appendix G Wording Explanation .........................................................................................113

  • 1

    1. General Principles

    1.0.1 This Code is designed to meet demands in building structure design and requirements of secure application and economic feasibility. 1.0.2 This Code is applicable to the building structure design. 1.0.3 This Code has been made in accordance with principles stated in Unified Standard for Reliability Design of Building Structures (GB 50068-2001). 1.0.4 Effects involved with the building structure design include direct effect (combination of loads) and indirect effect (including subbase deformation, concrete shrinkage, welding deformations, temperature fluctuation or effects caused by earthquakes). In this Code, only provisions on combination of loads are stated. 1.0.5 The design reference period adopted in this Code is 50 years. 1.0.6 Effects or combination of loads involved with the building structure design shall be in accordance with this Code as well as other current national provisions.

    2. Terms and symbols

    2.1 Terms

    2.1.1 Permanent load During the utilization period of structures, the value of the combination of loads shall

    have no change with the passage of time or the variation is negligible compared with the average, or the variation is monotonous and tends to the limitation. 2.1.2 Variable load

    During the utilization period of structures, the value of combination of loads shall be changed with the passage of time and the variation is negligible compared with the average. 2.1.3 Accidental load

    During the utilization period of the structure, the combination of loads does not necessarily appear, but one it appears, the value is great but the duration is short. 2.1.4 Representative values of a load

    The value of combination of loads adopted during the design for the checking of limiting state, such as characteristic value/nominal value, combination value, frequent value and quasi- permanent value. 2.1.5 Design reference period

    The time parameter selected for deciding the representative value of the variable load. 2.1.6 Characteristic value/nominal value

    The basic representative value of loads refers to the maximum characteristic value (such as typical value, mode, median or some place value) of statistical distribution of loads in the design reference period. 2.1.7 Combination value

  • 2

    The value of combination of loads that makes the load effect exceed probability during the design reference period and make the solitude appearance of the combination of loads has a unified value of combination of loads or make the structure has unified value of combination of loads with reliability index stated in the provision. 2.1.8 Frequent value

    For variable load, during the design reference period, the exceeded total time is the minimum ratio or the exceeded frequency is the value of the combination of loads of the assigned frequency. 2.1.9 Quasi- permanent value

    For variable load, during the design reference period, the exceeded total time is about half of the value of combination of loads in the design reference period. 2.1.10 Design value of a load

    The arithmetic product of the representative values of a load and the partial load factor. 2.1.11 Load effect

    Reaction of structures or structural elements caused by the combination of loads, such as internal force, distortion and crack 2.1.12 Load combination

    In the limit design, to guarantee the built-in reliability, provisions for all kinds of design values of a load have been made. 2.1.13 Fundamental combination

    In the limit of bearing capacity state, the combination of permanent effect and variable effect 2.1.14 Accidental combination

    In the limit of bearing capacity state, the combination of permanent effect, variable effect and an accidental combination 2.1.15 Characteristic/nominal combination

    In the regular service limiting state, the characteristic value/nominal value or combination value adopted is the combination of representative values of a load. 2.1.16 Frequent combinations

    In the regular service limiting state, the frequent value or permanent value is adopted in the variable load is the combination of representative values of a load. 2.1.17 Quasi- permanent combinations

    In the regular service limiting state, the quasi- permanent value adopted by the variable load is the combination of the representative values of a load. 2.1.18 Equivalent uniform live load

    During the structure design, the actual load of continuous distribution above or under the floor is always by substituted by the evenly distributed load. The equivalent uniform live load refers to the load effect received by the structure can keep in line with the evenly distributed load of the actual load effect. 2.1.19 Tributary area

    The tributary area is adopted during the calculation of the beam column members. It refers to the floor space of the calculated member load. It shall be divided by the zero line of the floor slab. In the practical situation, it can be simplified. 2.1.20 Dynamic coefficient

  • 3

    Structures and members that receives dynamic load, when designed according to the static force, shall adopt the value that is the ratio of the maximum power effect of structures or members and relevant static force effect. 2.1.21 Reference snow pressure

    The reference pressure of snow load shall be decided by the maximum value of the 50-year period calculated from the probability statistics according to the observation data from the deadweight of snow on the local open and equitable terrain. 2.1.22 Reference wind pressure

    The reference pressure of wind load shall be decided by the maximum wind speed for a 50-year period calculated from the probability statistics according to the observation data of average speed in 10min at 10m on the local open and equitable terrain. Also, relevant air density shall be considered and the wind pressure shall be calculated according to the formula (D.2.2-4). 2.1.23 Terrain roughness

    When the wind passes 2km range before reaching the structure, the class used to describe the distribution pattern of irregular barriers on the ground.

    2.2 Main symbols

    Gkcharacteristic value/nominal value of permanent load; Qkcharacteristic value/nominal value of variable load; GGkcharacteristic value/nominal value of permanent load effect; SQkcharacteristic value/nominal value of the variable load effect; Sload effect combination design value; RThe design value of resisting power of structural members; SADownwind load effect; SCCrosswind load effect; TNatural vibration period of structures; HTop height of structures; BWindward width of structures; ReReynolds number; StStrouhai number; skCharacteristic value/nominal value of snow load; s0reference snow pressure; wkcharacteristic value/nominal value of wind load; w0reference wind pressure; crCritical wind velocity of crosswind sympathetic vibration; Angle of gradient; zGust coefficient at height Z; gzGust coefficient at height Z; 0Structure significance coefficient; GSubentry coefficient of permanent load; QSubentry coefficient of variable load; ccombination value coefficient of the variable load;

  • 4

    ffrequent value coefficient of variable load; qquasi-permanent value coefficient of variable load; rCoefficient of snow distribution over the roof zVariation coefficient of wind pressure altitude; sWind load coefficient; Coefficient of wind load terrain and physiognomy amendment; Aggrandizement coefficient of wind load pulsation; Impact coefficient of wind load pulsation; zStructural vibration mode coefficient; Structural damping ratio.

    3. Classification of loads and combination of load effect

    3.1 Classification of loads and representative values of a load

    3.1.1 The structural combination of loads can be divided into three kinds: 1. Permanent load, such as dead load, earth pressure and prestress. 2. Variable load, such as floor live load, roof live load and dust load, crane load, wind

    load and snow load. 3. Accidental load, such as blasting power and force of percussion. Note: Deadweight refers to the combination of loads (gravitation) caused by the weight of materials.

    3.1.2 During the design of building structures, different combinations of loads shall adopt different representative values. For permanent loads, the representative value shall be the characteristic value/nominal value. While for variable loads, the representative value shall be the characteristic value/nominal value, combination value, frequent value or quasi- permanent value according to different design requirements. For accidental loads, the representative value shall be decided according to the utilization characteristics of building structures. 3.1.3 Permanent load characteristic value/nominal value: for structural deadweight, it shall be decided according to the design size of structural members and the deadweight of unit volume of materials; for commonly-used materials and members, it shall be decided according to appendix 1 of this Code; for materials and members (including field fabricated heat insulators, concrete thin-wall members) with major changes in deadweight, it shall be the upper value or the lower range value according to the advantage or disadvantage state to members.

    Note: For commonly-used materials and members, refer to Appendix A.

    3.1.4 The characteristic value/nominal value of variable loads shall be adopted according to provisions in this Code. 3.1.5 The design of limit of bearing capacity state or the regular service limiting state shall adopt the combination value as the representative value of the variable loads. The combination value of variable loads refers to the variable load characteristic value/nominal value multiplied by the combination value coefficient of combination of loads. 3.1.6 If the regular service limiting state is designed according to the frequent combinations,

  • 5

    the frequent value, quasi-permanent value shall be adopted as the representative value. If it is designed according to the quasi-permanent combinations, the quasi-permanent value shall be adopted as the representative value of variable loads. The frequent value of variable loads shall adopt the variable load characteristic value/nominal value multiplied by the frequent value coefficient of combination of loads. The variable load quasi- permanent value shall adopt the characteristic value/nominal value of variable loads multiplied by the quasi-permanent value coefficient of combination of loads.

    3.2 Load combination

    3.2.1 The design of building structures shall be in accordance with the combination of loads arising in the construction during the utilization process, according to the limit of bearing capacity state and the regular service limiting state. The design shall take the most disadvantaged combination for the combination of loads (effect). 3.2.2 For the limit of bearing capacity state, the combination of loads (effect) shall adopt the fundamental combination or accidental combination of load effect. The following design expression shall be adopted:

    0S R (3.2.2) Where,

    0Structure significance coefficient; SThe design of load effect combination; RThe design value of resisting power of structural members shall be decided by

    related design specifications of building structures. 3.2.3 For the design value (S) of the fundamental combination of loads and load effect, it shall be decided by the most disadvantaged value from the following combination values:

    1) Combination controlled by the variable load effect;

    (3.2.3-1)

    Where, GSubentry coefficient of permanent load shall be adopted according to Article

    3.2.5. QiThe ith subentry coefficient of variable load. Qi is the subentry coefficient of

    variable load Q1, to be adopted according to Article 3.2.5. SGkThe load effect value calculated according to the permanent load

    characteristic value/nominal value Gk; SQikThe load effect value calculated according to variable load characteristic

    value/nominal value Qik. SQ1k is the controller of all variable load effects. ciThe combination value coefficient of the variable load Qi shall be adopted

    according to provisions in chapters. nThe number of variable loads forming the combination. 2) Combination controlled by the permanent load effect:

  • 6

    (3.2.3-2)

    Note: 1 The design value of fundamental combination is applicable to the linear load effect.

    2. If the SQ1k can't be decided distinctively, each variable load effect shall be taken as SQ1k and the most

    disadvantaged load effect combination shall be selected.

    3.2.4 For common bents and frame structures, the reduction rule may be adopted in the fundamental combination and the most disadvantaged value shall be selected according to the following combination values:

    1) Combination controlled by variable load effect;

    (3.2.4)

    2) The combination controlled by the permanent load effect shall be adopted according to formula (3.2.3-2). 3.2.5 The subentry coefficient of combination of loads in the fundamental combination shall be adopted according to the following provisions:

    1. Subentry coefficient of permanent load; 1) If the effect causes disadvantages to the structure,

    for the combination controlled by the variable load effect, select 1.2; for the combination controlled by the permanent load effect, select 1.35.

    2) If the effect causes advantages to the structure, select 1.0. 2. Subentry coefficient of variable load: Generally, select 1.4; For the characteristic value/nominal value of the live load of industrial housing

    floor greater than 4kN/m2, select 1.3. 3. For the overturn, slippage or floating calculation, the load subentry coefficient

    shall be adopted according to provisions in related design codes for structures. 3.2.6 For the design value of accidental combination and load effect combination, it shall be in accordance with the following provisions: the representative value of the accidental loads doesn't multiply subentry coefficient; if it appears together with the accidental loads and other combinations of loads, the representative value shall be adopted according to the observational data and project experience. Under different circumstances, the formula of design value of the load effect shall be decided by contrary provisions. 3.2.7 In the regular service limiting state, according to different design requirement, the characteristic/nominal combination, frequent combinations or quasi-permanent combinations may be adopted and the design shall be carried out according to the following design expression:

    SC (3.2.7) Where,

    CThe limitation of structures or structural members when they are in regular service, such as the limitation of distortion, crack, amplitude, acceleration and stress, shall be adopted

  • 7

    according to related design codes for building structures. 3.2.8 The design value (S) characteristic/nominal combination and load effect combinations shall be adopted according to the following formula:

    (3.2.8)

    Note: The design value of the combination is applicable to the linear combination of loads and load effect.

    3.2.9 The design value (S) of frequent combinations and load effect combinations shall be adopted according to the following formula:

    (3.2.9)

    Where, f1The frequent coefficient of variable load Q1 shall be adopted according to

    provisions in chapters. qiThe quasi value coefficient of the variable load Qi shall be adopted according to

    provisions in chapters. Note: The design value of the combination is applicable to the linear combination of loads and load effect.

    3.2.10 The design value (S) of quasi-permanent combinations and load effect combinations shall be adopted according to the following formula:

    (3.2.10)

    Note: The design value of the combination is applicable to the linear combination of loads and load effect.

    4. Live load of floors and roofs

    4.1 Rectangular distribution live load on floors of civilian buildings

    4.1.1 The characteristic value/nominal value, combination value, frequent value and quasi-permanent value coefficient of the rectangular distribution live load on floors of civilian buildings shall be adopted according to Table 4.1.1.

  • 8

    Table 4.1.1 the characteristic value/nominal value, combination value, frequent value and quasi-permanent

    value coefficient of rectangular distribution live load on floors of civilian buildings

    Item Type Characteristic value/nominal value (kN/m2)

    Combination value

    coefficient c

    Frequent value

    coefficient f

    Quasi-permanent value coefficient

    q

    1

    (1) Residential buildings, dormitories, hotels, office buildings, hospital wards, nursery and kindergarten; (2) Schoolrooms, testing labs, reading rooms, boardrooms, policlinic rooms of hospitals.

    2.0 0.7 0.5

    0.6

    0.4

    0.5

    2 Dining rooms, restaurant, archives for general materials;

    2.5 0.7 0.6 0.5

    3 (1) Auditoria, playhouse, cinema and bleachers with fixed seats; (2) Public laundries.

    3.0 3.0

    0.7 0.7

    0.5 0.6

    0.3 0.5

    4 (1) Stores, exhibition halls, stations, ports,airport halls and waiting rooms; (2) Bleachers without fixed seats.

    3.5

    3.5

    0.7

    0.7

    0.6

    0.5

    0.5

    0.3

    5 (1) Gymnasia and stages for performance; (2) Ballrooms.

    4.0 4.0

    0.7 0.7

    0.6 0.6

    0.5 0.3

    6 (1) Stack rooms, archival repository and store rooms; (2) Stack rooms with dense tanks.

    5.0 12.0

    0.9 0.9 0.8

    7 Fan houses and elevator towers 7.0 0.9 0.9 0.8

    8

    Automobile passages and parking rooms: (1) one-way slab building covers (the span no less than 2m) Carriages; Fire-fighting vehicles; (2) Two-way slab building covers (the span no less than 6m*6m) and flat slab floor (the dimension of column grids no less than 6m * 6m) Carriages; Fire-fighting vehicles.

    4.0 35.0

    2.5 20.0

    0.7 0.7

    0.7 0.7

    0.7 0.7

    0.7 0.7

    0.6 0.6

    0.6 0.6

    9 Kitchen (1) Ordinary; (2) Restaurant.

    2.0 4.0

    0.7 0.7

    0.6 0.7

    0.5 0.7

    10 Bathrooms, toilets and wash rooms: (1) Civilian building in item 1; (2) Other civilian buildings.

    2.0 2.5

    0.7 0.7

    0.5 0.6

    0.4 0.5

    11

    Corridors, hallways, staircases: (1) Dormitories, hotels, hospital wards, nursery, kindergarten and residential buildings; (2) Office buildings, schoolrooms, restaurants, policlinic of hospitals; (3) Fire-control fire escapes and other civilian buildings.

    2.0

    2.5 3.5

    0.7

    0.7 0.7

    0.5

    0.6 0.5

    0.4

    0.5 0.3

    12 Balcony: (1) In common situation; (2) People may be gathering.

    2.5 3.5

    0.7 0.6 0.5

  • 9

    Note:

    1. All live loads in this Table are applicable for natural service conditions. If the working load is extremely large,

    the live loads shall be adopted according to practical situations.

    2. for the live load of stack rooms in item 6, if the height of bookshelves is greater than 2 m, the live load for

    stack rooms shall be decided according to a height no less than 2.5kN/m2.

    3. The live load for carriages in item 8 is applicable to carriages holding fewer than 9 persons. The live load of

    fire-fighting vehicles is applicable to oversize vehicles with the full load of 300kN. If requirements in this Table are

    not met, according to the equivalence principle of structural effect, the partial load of wheels shall be converted to

    the equivalent uniform live load.

    4. The live load for staircases in item 11, for the precast stair footfall slabs, shall be calculated according to a

    concentrated load of 1.5kN.

    5. All combinations of loads do not contain the deadweight of partitions and the combination of loads for the second

    fixture and fitting. The fixed partition and deadweight shall be taken as permanent combination of loads. If the

    position of partitions can be moved freely, the weight of non-fixed partitions shall take 1/3 the weight of the wall as

    the additive value (kN/m2) which shall be no less than 1.0 kN/m2 of the live loads on floors.

    4.1.2 For the design of girders, walls, columns and foundations of floors, under the following circumstances, the characteristic value/nominal value of live loads on the floors in Table 4.1.1 shall be multiplied by the discount coefficient:

    1. The discount coefficient during the design of floor girders; 1) In item 1(1), if the tributary area of girders exceeds 25m2, select 0.9; 2) In items 1(2)-7, if the tributary area of girders exceeds 50m2, select 0.9; 3) In item 8, junior beam of one-way slabs and vittae of trough plates, select

    0.9; For girder of one-way slabs, select 0.6; For girders of two-way slabs, select 0.8. 4) For items 9-12, the discount coefficient shall be the same as that of the

    buildings. 2. The discount coefficient of designing walls, columns and foundations:

    1) Item 1(1) shall be adopted according to Table 4.1.2. 2) Items 1(2)-7 shall adopt the discount coefficient the same as that of the

    girders of floors. 3) In item 8, for one-way slabs, select 0.5; For two-way slabs and flat slab floors, select 0.8. 4) In items 9-12, the discount coefficient shall be adopted the same as that of

    the building. Note: The tributary area of floor girders is decided by the real area within the range extending 1/2 case bay

    to both sides of the girder.

    Table 4.1.2 Discount coefficient of live loads according to different floors

    Number of floors above the calculation section of walls, volumes and foundations 1 2-3 4-5 6-8 9-20 20

    The discount coefficient of live loads total on each floor above the calculation section 1.00 (0.90) 0.85 0.70 0.65 0.60 0.55

    Note: If the tributary area of floor girders exceeds 25m2, the coefficient shall adopt the one in the parentheses.

    4.1.3 The partial loads on floor structures shall be converted into isoeffect rectangular distribution live loads according to Appendix B.

  • 10

    4.2 Floor live load of industrial buildings

    4.2.1 During the production utilization or the installation repair of floors of industrial buildings, the partial load produced by the equipment, pipelines, transportation tools or possibly-removed partitions shall be considered according to the practical situation and can be substituted by the isoeffect rectangular distribution live load.

    Note: 1. The floor isoeffect rectangular distribution live load shall be decided by the method stated in Appendix B.

    2. For common smith shops, instrumentation production workshops, semiconductor device workshops, cotton

    spinning and knitting workshops, preparing shops in tire plants and grain processing workshops, if there are not

    enough materials; it shall be adopted according to Appendix C.

    4.2.2 The operation combination of loads, including operating personnel, general purpose tools, small amount of raw materials and the deadweight of finished products on areas without equipment of floors ( including working platforms) of industrial buildings shall be considered as the rectangular distribution live load and adopt 2.0kN/m2. The staircase live load in production workshops shall be adopted according to the practical situation and shall be no less than 3.5kN/m2. 4.2.3 The combination value coefficient, frequent value coefficient and quasi- permanent value coefficient of floor live loads of industrial buildings shall be adopted according to the practical situation besides values given in Appendix C. However, under no circumstance shall the combination value and the frequent value coefficient be less than 0.7 and the quasi-permanent value coefficient no less than 0.6.

    4.3 Roof live load

    4.3.1 The roof rectangular distribution live load on the horizontal projection surface shall be adopted according to Table 4.3.1. The roof rectangular distribution live load can't be considered together with the snow load.

    Table 4.3.1 Roof rectangular distribution live load

    Item Type

    Characteristic

    value/nominal value

    (kN/m2)

    Combination value

    coefficient c

    Frequent value

    coefficient f

    Quasi-permanent value

    coefficient q

    1 Roof without

    holding persons 0.5 0.7 0.5 0

    2 Roof holding

    persons 2.0 0.7 0.5 0.4

    3 Roof garden 3.0 0.7 0.6 0.5

    Note: 1. For roofs without holding persons, if the construction load is comparatively large, it shall be adopted

    according to the practical situation. For different structures, according to related design specifications, the

    characteristic value/nominal value shall be increased or decreased by 0.2kN/m2.

    2. For roofs holding persons, if they are used for other purposes, relevant floor live loads shall be adopted.

    3. For seeper combination of loads caused by the disturbance of roof drainage or blockage, construction

    measures shall be adopted. If necessary, the roof live loads shall be decided according the possible depth of

  • 11

    seepers.

    4. The live load on roof gardens does not include the material deadweight of earth materials.

    4.3.2 The combination of loads of parking apron for helicopters shall be considered as the partial load according to the gross weight of the helicopter. At the same time, its isoeffect shall be no lower than 5.0kN/m2. The partial load shall be decided according to the practical maximum lifting loads of helicopters. If there is no technical information of aircraft types, commonly, the partial load characteristic value/nominal value and active area shall be selected according to various requirements of light, medium and heavy types:

    Light-type: the maximum take-off weight is 2t, partial load characteristic value/nominal value is 20kN and the active area is 0.20m * 0.20m.

    Medium-type: the maximum take-off weight is 4t, partial load characteristic value/nominal value is 40kN and the active area is 0.25m * 0.25m.

    Heavy-type: the maximum take-off weight is 6t, the partial load characteristic value/nominal value is 60kN and the active area is 0.30m * 0.30m. The combination value coefficient of loads shall be 0.7, the frequent value coefficient 0.6 and the quasi-permanent value coefficient shall be 0.

    4.4 Roofing dust load

    4.4.1 During the design of workshops that release mass dust and their neighboring buildings, for roofs of machinery, cement and metallurgy workshops with certain dedusting facilities, the roof dust load on the horizontal projection surface shall be adopted according to Table 4.4.1-1 and 4.4.1-2.

  • 12

    Table 4.4.1-1 Roof dust load

    Characteristic value/nominal value

    (kN/m2)

    Roofs with breastplate Item Type Roofs

    without

    breastplateWithin

    breastplates

    Out of

    breastplates

    Combination

    value

    coefficient

    c

    Frequent

    value

    coefficient

    f

    Quasi-permanent

    value

    coefficient

    q

    1 Foundry in machinery plants

    ( cupola) 0.5 0.75 0.30

    2 Melting house ( oxygen converter) - 0.75 0.30

    3 Manganese and ferrochrome

    workshops 0.75 1.00 0.30

    4 Silicon and ferrotungsten

    workshops 0.30 0.50 0.30

    5 Sintering chambers of sintering

    plants and primary mixing rooms 0.50 1.00 0.20

    6 Propylaea and other workshops in

    sintering plants 0.30 - -

    7

    Workshops with dust sources in

    cement mills ( kiln rooms, mill

    rooms, combined storehouses,

    drying rooms and fragmentation

    rooms)

    1.00 - -

    8

    Workshops without dust sources in

    cement mills ( compressor plants,

    workshops, material sheds and

    distribution substations)

    0.50 - -

    0.9 0.9 0.8

    Note: 1. In the Table, the evenly distributed load of soot formation shall be only applicable to the roof slope 25. If

    45, the dust load may be neglected. If 25

  • 13

    Table 4.4.1-1 Roof dust load

    Characteristic value/nominal

    value(kN/m2)

    The distance between the roof and

    the blast furnace (m)

    Blast furnace

    volume ( m3)

    50 100 200

    Combination value

    coefficient c

    Frequent value

    coefficient f

    Quasi-permanent value

    coefficient q

    620

    0.50

    0.75

    1.00

    -

    0.30

    0.50

    -

    -

    0.30

    1.0 1.0 1.0

    Note: 1. Note 2 of Table 4.4.1-1 can be applicable to this Table as well.

    2. If the distance between the roofs of neighboring buildings and the blast furnace is the intermediate value in the

    Table, the value can be selected according to the interpolation method.

    4.4.2 For places vulnerable for dust deposition on roofs, during the design of roof boards and summers, the characteristic value/nominal value of dust load shall be multiplied by the aggrandizement coefficient as stated: Within the dispersion of distribution that is twice the roof height difference but no greater than 6.0m in the high-low span, select 2.0; within the dispersion of distribution no greater than 3.0m of cullis, select 1.4. 4.4.3 The dust load shall be considered with the snow load or roof live load but the one with a comparatively large value.

    4.5 Construction and repair load as well as handrail horizontal load

    4.5.1 During the design of roofing boards, summers, reinforced concrete projecting eaves, rain hoods and prefabricated joists, the concentrated load (the deadweight of people and small tools) for construction and repair shall select 1.0kN and shall be calculated in the most disadvantaged place.

    Note: 1. For light members or wide members, if the construction load exceeds the aforesaid combination of loads, it

    shall be calculated according to the practical situation, or temporary facilities like adding backing boards

    and supports shall be adopted.

    2. During the calculation of intensity of the projecting eaves and rain hoods, one concentrated load shall be

    taken into consideration in every 1.0m of the width of boards. During the calculation of overturning of

    projecting eaves and rain hoods, a concentrated load shall be taken into consideration in every 2.5-3.0m of

    the width of boards.

    4.5.2 The handrail top horizontal combination of loads on the staircases, bleachers, balcony and roofs holding persons shall be adopted according to the following:

    1. For residential buildings, dormitories, office buildings, hotels, hospitals, nursery, kindergartens, select 0.5KN/m.

    2. For schools, dining rooms, playhouses, cinema, stations, auditoria, museums or palaestra, select 1.0kN/m. 4.5.3 If the quasi- permanent combinations of loads is adopted, the construction and repair load as well as the handrail horizontal load can be neglected.

  • 14

    4.6 Dynamic coefficient

    4.6.1 The power calculation of building structure design, if there are enough bases, shall be calculated according to the static force after the deadweight of heavy objects or equipment is multiplied by the dynamic coefficient. 4.6.2 The dynamic coefficient for starting and stopping vehicles, porting and handling heavy objects shall adopt 1.3. Its dynamic loads can only be transferred to the floor slabs and girders. 4.6.3 The combination of loads on roofs by helicopters shall be multiplied by the dynamic coefficient. For helicopters with hydraulic pressure tires, the coefficient shall adopt 1.4. The dynamic load can only be transferred to the floor slabs and girders.

    5. Crane load

    5.1 Vertical and horizontal load of cranes

    5.1.1 The characteristic value/nominal value of vertical loads of cranes shall adopt the maximum wheel pressure or the minimum wheel pressure of cranes according to relevant regulations. 5.1.2 The longitudinal and transverse horizontal combination of loads of cranes shall be adopted according to the following provisions:

    1. The characteristic value/nominal value of vertical combination of loads of cranes shall be adopted according to 10% the total of maximum wheel pressures of all skid wheels that work on the same orbit. The point of application of this load shall lie on the point of contact between the skid wheel and the orbit, with the direction same as that of the orbit.

    2. The characteristic value/nominal value of transverse horizontal combination of loads shall adopt the percentage in the following of the sum of the weight of crane carriages and the load-lifting capacity and then the result shall be multiplied by the acceleration of gravity:

    1) Flexible-hook cranes: If the load-lifting capacity is no larger than 10t, select 12% If the load-lifting capacity is between 16-50t, select 10% If the load-lifting capacity is no less than 75t, select 8% 2) For hard-hook crane: select 20%. The transverse horizontal combination of loads

    shall be allocated evenly on both ends and transferred to the rail head by means of wheels on the orbit, with the direction vertical with the orbit. The skid with two opposite directions shall be taken into consideration. Note: 1. The horizontal load of suspending cranes can be neglected and received by related supports.

    2. The horizontal load of hand cranes and electric blocks can be taken no account of.

  • 15

    5.2 The combination of several cranes

    5.2.1 When the vertical load of several cranes are considered during the counting of bent frames, the number of cranes for the single-span workshops shall be no more than 2, while for multi-span ones, the number shall be no more than 4. For the horizontal load of several cranes, for the bent frames for single-span or multi-span workshops, the number of the cranes shall be no more than 2.

    Note: Particular instances shall be considered according to the practical situation.

    5.2.2 During the calculation of bent frames, the characteristic value/nominal value of the vertical load and horizontal load of several cranes shall be multiplied by the discount coefficient stated in Table 5.2.2.

    Table 5.2.2 the discount coefficient of combination of loads of several cranes Work class of the crane

    The number of cranes for the combination A1-A5 A6-A8

    2 3 4

    0.9 0.85 0.8

    0.95 0.90 0.85

    Note: For the single-span or multi-span workshops of multi-layer cranes, during the calculation of bent frames, the number

    of cranes for the combination and the discount coefficient of loads shall be considered according to the practical situation.

    5.3 Dynamic coefficient of crane loads

    5.3.1 During the calculation of intensity of crane beams and their connections, the vertical load of cranes shall be multiplied by the dynamic coefficient. Concerning the suspending cranes (including electric hoists), for the work class A1-A5 flexible-hook cranes, the dynamic coefficient shall be 1.05; for the work class A6- A8 flexible-hook cranes, hard-hook cranes and other special-type cranes, the dynamic coefficient shall be 1.1.

    5.4 The combination value, frequent value and quasi-permanent value of crane loads

    5.4.1 The combination value, frequent value and quasi-permanent value coefficient of crane loads shall be adopted according to Table 5.4.1.

  • 16

    Table 5.4.1 the combination value, frequent value and quasi-permanent value of crane loads

    Work class of the crane Combination value

    coefficient c

    Frequent value

    coefficient f

    Quasi-permanent value

    coefficient q

    Flexible-hook crane

    Work class A1-A3

    Work class A4- A5

    Work class A6-A7

    Hard-hook cranes and flexible-hook cranes with

    the work class of A8

    0.7

    0.7

    0.7

    0.95

    0.6

    0.7

    0.7

    0.95

    0.5

    0.6

    0.7

    0.95

    5.4.2 During the design of bent frames in workshops, in the quasi- permanent combinations of combinations of loads, the load of cranes shall be taken no account of. However, in the regular service limit design of crane beams, the quasi- permanent value of crane loads shall be adopted.

    6. Snow load

    6.1 The characteristic value/nominal value and reference snow pressure of snow loads

    6.1.1 The characteristic value/nominal value of snow load on the horizontal projection surface of the roof shall be calculated according to the following formula:

    Sk = rS0 (6.1.1) Where,

    Skcharacteristic value/nominal value of the snow load (kN/m2); rCoefficient of snow distribution over the roof S0reference snow pressure (kN/m2).

    6.1.2 The reference snow pressure shall be adopted according to the 50-year value listed in Appendix D.4. For structures sensitive to snow loads, the reference snow pressure shall be elevated and decided by related codes for structural design. 6.1.3 If the reference snow pressure value of cities or construction sites is not listed in Appendix D, the reference snow pressure value can be decided according to the maximum snow pressure or snow depth materials, based on the definition of the reference snow pressure and making analysis over statistics. During the analysis, the influence of sample quantity shall be taken into consideration (please refer to Appendix D). If there is also no snow pressure or snow depth material, the value can be decided according to the reference snow pressure in the neighboring places or long-term materials and by means of contrastive analysis over meteorological and terrain conditions. Also, it can be approximately decided by the natioanl reference snow pressure distribution graph (appendix D.5.1). 6.1.4 The snow load of mountains shall be decided after the practical survey. If there is no survey material, it can be adopted as the snow load multiplied by the coefficient 1.2 in the local neighboring and open level surfaces. 6.1.5 The combination value coefficient of snow loads shall select 0.7, the frequent value coefficient 0.6 and the quasi-permanent value coefficient shall be 0.5, 0.2 and 0 respectively

  • 17

    according to snow load zoning I, II and III. The snow load zonings shall be decided according to Appendix D.4 or Attached figure D.5.2.

    6.2 Coefficient of snow distribution over the roof

    6.2.1 The coefficient of snow distribution over the roof shall be adopted according to Table 6.2.1 for different roofs.

  • 18

    Table 6.2.1 Distribution Coefficient of Snow Pressure

    Item Type Roof Table and distribution coefficient r of snow pressure

    1 Single-span, shed roof

    2 Single-span, gable roof

    Even distribution

    Uneven distribution

    0.75r

    r is adopted by Item 1

    3 Arched roof

    4 The roof with skylight

    Even distribution

    Uneven distribution

  • 19

    Table 6.2.1 (Continued)

    Item Type Roof Table and distribution coefficient r of snow pressure

    5 The roof with skylight and breastplate

    Even distribution

    Uneven distribution

    6 Multi-span, single slope roof (serrated

    roof)

    Even distribution

    Uneven distribution

    7 Double-span, gable or arched roof

    Even distribution

    Uneven distribution

    r is adopted by the requirements of Item 1 and Item 3

    8 High and low roof

    a=2h and 8ma4m

  • 20

    Note: 1. In item 2, only when 2030 of the single-span gable roofs, the even distribution shall be adopted.

    2. Item 4 and item 5 shall be applicable to the general industrial workshop roofs with the gradient 25.

    3. For the double-span or gable or arched roof, if 25 or f/l0.1, the rectangular distribution shall be adopted.

    4. For snow distribution coefficient of multi-span roof, please refer to provisions in item 7.

    6.2.2 During the design of supporting members of buildings structures and roofs, the snow distribution conditions shall be adopted according to the following provisions:

    1. For roofing boards and purline, it shall adopt the most disadvantaged condition of the snow inhomogeneous distribution.

    2. For roof trusses and arch shells, it shall be adopted according to the snow full-span rectangular distribution instances, inhomogeneous distribution instances and half-span evenly-distributed instances.

    3. For frames and columns, it shall be adopted as the snow full-span rectangular distribution instance.

    7. Wind load

    7.1 The characteristic value/nominal value and reference wind pressure of wind loads

    7.1.1 The characteristic value/nominal value of wind loads vertical to the surface of buildings shall be calculated according to the following formula:

    1. During the calculation of main bearing structures, wk=zszw0 (7.1.1-1)

    Where, wkthe characteristic value/nominal value (kN/m2) of the wind load; zWind vibration coefficient at height Z; sWind load coefficient; zVariation coefficient of wind pressure altitude w0Reference wind pressure (kN/m2). 2. During the calculation of envelop enclosures,

    wk=gzs1zw0 (7.1.1-2) Where,

    gzGust coefficient at height Z; s1Partial wind pressure coefficient.

    7.1.2 The reference wind pressure shall be adopted according to the 50-year value listed in Appendix D.4 but shall be no less than 0.3kN/m2. For high-rise buildings, towering structures and other structures sensitive to wind loads, the reference wind pressure shall be elevated and decided according to related codes for structural design. 7.1.3 If the reference wind pressure value of cities and construction sites is not listed in Appendix D, the reference wind pressure value can be decided according to the maximum wind speed materials, based on the definition of the reference wind pressure and making analysis over statistics. During the analysis, the influence of sample quantity shall be taken into consideration (please refer to Appendix D). If there is also no wind speed material, the

  • 21

    value can be decided according to the reference wind pressure in the neighboring places or long-term materials and by means of contrastive analysis over meteorological phenomena and terrain conditions. Also, it can be approximately decided by the national reference wind pressure distribution graph (appendix D.5.3). 7.1.4 The combination value, frequent value and quasi-permanent value coefficient of wind loads shall be 0.6, 0.4 and 0 respectively.

    7.2 Variation coefficient of wind pressure altitude

    7.2.1 For level or small-undulant terrain, the variation coefficient of wind pressure altitude shall be decided according to Table 7.2.1 based on different terrain roughness.

    The terrain roughness can be divided into A, B, C and D classes: A-Class: offing sea surfaces, islands, coasts, lakeshores and deserts; B-Class: open countries, countries, jungles, hills, and villages and suburbia with

    sparse buildings; C-Class: cities with dense buildings; D-Class: cities with dense high-rise buildings.

    Table 7.2.1 Variation Coefficient z of the Wind Pressure Height

    Height away from the ground or sea surface Types of ground roughness

    (m) A B C D

    5

    10

    15

    20

    30

    40

    50

    60

    1.17

    1.38

    1.52

    1.63

    1.80

    1.92

    2.03

    2.12

    1.00

    1.00

    1.14

    1.25

    1.42

    1.56

    1.67

    1.77

    0.74

    0.74

    0.74

    0.84

    1.00

    1.13

    1.25

    1.35

    0.62

    0.62

    0.62

    0.62

    0.62

    0.73

    0.84

    0.93

    70

    80

    90

    100

    150

    200

    250

    300

    350

    400

    450

    2.20

    2.27

    2.34

    2.40

    2.64

    2.83

    2.99

    3.12

    3.12

    3.12

    3.12

    1.86

    1.95

    2.02

    2.09

    2.38

    2.61

    2.80

    2.97

    3.12

    3.12

    3.12

    1.45

    1.54

    1.62

    1.70

    2.03

    2.30

    2.54

    2.75

    2.94

    3.12

    3.12

    1.02

    1.11

    1.19

    1.27

    1.61

    1.92

    2.19

    2.45

    2.68

    2.91

    3.12

    7.2.2 For mountainous buildings, the variation coefficient of the wind pressure height may not be determined by roughness types of the equitable terrain on the basis of Table 7.2.1, but also shall be adopted by considering the orographic conditions compensation and compensation factor 11 respectively on the basis of the following requirements:

  • 22

    1 For the mountain peak and hillside, the compensation factors on the top may be adopted according to the following formula:

    2)]5.2

    1(1[HzktgaB += (7.2.2)

    Where tgThe slope of mountain peak or hillside on the windward side; when tg>0.3, tg

    takes 0.3; kCoefficient, it takes 3.2 for mountain peak, and takes 1.4 for hillside; HOverall height of the peak or hillside (m); zHeight from the calculated position of the building to the building ground, m;

    when z>2.5H, z takes 2.5H;

    Figure 7.2.2 Mountain Peak and Sidehill Schematic

    For other positions of the mountain peak and sidehill, they may comply with figure 7.2.2, compensation factor at Part A, Part C (A and C) is 1, while the compensation factors between A and B or between B and C are determined by linear interpolation of .

    2 For the blocking terrains like intermontaine basin and valley, =0.75~0.85; For the valley mouth and mountain pass concurrent with the wind direction,

    =1.20~1.50. 7.2.3 For high seas offing and insular buildings or structures, the variation coefficient of the

    wind pressure height may not only be determined by roughness type of A-type on the basis of Table 7.2.1, but shall also consider the compensation factor shown in Table 7.2.3.

    Table 7.2.3 Compensation Factor of High Seas Offing and Island

    Distance away from the coast (km)

  • 23

    3 When the building and structures have shapes different to those specified in Table 7.3.1 and no reference available, it should be determined by tunnel test;

    4 For important building and structures with complicated shapes, they shall be determined by tunnel test.

    Table 7.3.1 the Shape Coefficient of Wind Loads

    Items Type Shapes and shape coefficient s

    1 Close-type grounding

    gable roof The median is calculated by interpolation method

    2 Close-type gable roof

    The median is calculated by interpolation method

  • 24

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    3 Close-type grounding arched roof

    The median is calculated by interpolation method

    4 Close-type arched roof

    The median is calculated by interpolation method

    5 Close-type shed roof

    s of the windward slope, it is adopted by Item 2.

    6 Close-type high and low gable roof

    s of the windward slope, it is adopted by Item 2.

    7 Close-type gable roof with scuttle

    Arched roof with scuttle may be adopted by this Figure.

    8 Close-type double-span gable roof

    s of the windward slope, it is adopted by Item 2.

  • 25

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficients

    9

    Close type

    unequal height

    and unequal

    double spans

    gable roof

    Windward slope s is adopted by Item 2.

    10

    Close-type

    unequal height

    and unequal

    three spans gable

    roof

    Windward slopes is adopted by Item 2

    s1 for the windward wall surface on the upper part of the midspan is adopted by the following

    provisions:

    s1=0.6(1-2h1/h)

    when h1=h, s1=-0.6

    11

    Close-type gable

    roof with scuttle

    and cover

    12

    Close-type gable

    roof with scuttle

    and double cover

    13

    Close-type

    unequal height

    and unequal

    three midspans

    gable roof with

    scuttle

    Windward slope s is adopted bt Item 2

    s1=0.6(1-2h1/h)

    when h1=h, s1=-0.6

  • 26

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    14

    Close-type double

    span gable roof with

    scuttle

    s for the second scuttle surface of the windward is adopted by the following requirements:

    When a4h, s=0.2

    When a>4h, s=0.6

    15 Close-type gable roof

    with parapet

    When the parapet height is limited, the shape coefficient of the roof may be adopted as roof

    without parapet

    16 Close-type gable roof

    with canopy

    s of the windward slope is adopted by Item 2.

    17

    Two opposite

    close-type gable roof

    with canopy

    This Fig. is applicable to that with s of 8~20mm, and s of windward slope is adopted by Item

    2.

    18

    Close-type pitched

    roof or arched roof

    with subsiding

    scuttle

  • 27

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    19

    Close-type gable roof

    or arched roof with

    subsiding scuttle

    s of the second scuttle surface of the windward is adopted by the following requirements:

    When a4h, s=0.2

    When a>4h, s=0.6

    20 Close-type roof with

    scuttle wind shield

    21

    Close-type double

    span roof with scuttle

    wind shield

    22 Close type saw-tooth

    roof

    s of windward slope is adopted by Item 2.

    When the tooth surface increases or reduces, it may be regulated evenly in (1), (2) and (3)

    three sections.

    23

    Close-type

    complicated

    multi-span roof s of the scuttle surface is adopted by the following requirements:

    When a4h, s=0.2

    When a>4h, s=0.6

  • 28

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    24

    Backing

    close-type gable

    roof

    This Fig. is applicable to conditions that shape coefficient s in Hm/H2 and s/H = 0.2~0.4

    Shape coefficient s

  • 29

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    25

    Backing

    close-type

    gable roof

    with scuttle

    This Fig. is applicable to conditions that shape coefficient s in Hm/H2and s/H =0.2~0.4;

    26

    Single-sided

    open type

    gable roof

    s of the windward slope is adopted by Item 2.

  • 30

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    27

    Double-side open

    type and four-side

    open type gable roof

    Shape coefficient s

    The median is calculated by interpolation method

    Note: 1 Roof of this Fig. is allergic to wind, so to shall consider the sign reversal condition of s

    when designing;

    2 Overall horizontal force to the roof caused by longitudinal wind loads;

    When a30, a is 0.05Ah

    When a

  • 31

    The median is calculated by interpolation method

    Note: (b) and (c) shall consider Note 1 and Note 2 of Item 27.

    3 When the interior stockpiled articles or the building is on the hillside, the roof suction shall be

    increased, and it may be adopted by Item 26 (a).

    30 Close-type building

    and structures

    (a) Regular polygon (including rectangular) plane

    (b) Y-shape plane

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    31 Members of

    sections

    32 Truss

    The shape coefficient of single truss is st=s

    s is the shape coefficient of the truss components; it is taken by Item 31 for shape steel and it is taken

    by Items 36 (b) for round pipeline members.

    =An/A is the breakwind coefficient of truss

    An is the net projected area of the truss member and node point breakwind

    L-shape plane II-shape plane

    +-shape plane Sectional triangle plane

  • 32

    A=hl is the bounded area of the truss.

    n is the integral shape coefficient parallel to the truss

    =11 n

    ststw

    st is the shape coefficient of the single truss, and is adopted by the following Table.

  • 33

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    33 Independent wall and

    fence

    34 Tower pier

    (a) The profile coefficient s when the angle tower pier is calculated integrally

    Rectangle

    Wind direction Breakwind

    coefficient Wind direction

    Single angle Angle combination

    Triangle wind

    direction

    0.1

    0.2

    0.3

    0.4

    0.5

    2.6

    2.4

    2.2

    2.0

    1.9

    2.9

    2.7

    2.4

    2.2

    1.9

    3.1

    2.9

    2.7

    2.4

    2.0

    2.4

    2.2

    2.0

    1.8

    1.6

    (b) The shape coefficient s when the pipe and round steel tower pier is calculated integrally

    When sw0d20.002, s is adopted by the s of angle tower pier by multiplied by 0.8;

    When sw0d20.015, s is adopted by the s of angle tower pier by multiplied by 0.6.

    The median is calculated by interpolation method

  • 34

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    35 Rotating

    umbo

    (a) The shape coefficient s of surface distribution when it is calculated locally

    36

    Structures

    of circular

    section

    (including

    chimney

    and tower)

    Values in the table are applicable to surface smooth conditions in sw0d20.015, therein, w0 is in unit

    of kN/m2, and d is in unit of m.

    (b) The shape coefficient s when it is calculated integrally

    The median is calculated by interpolation method; is the prominent height of the surface

  • 35

    Table 7.3.1 (Continued)

    Items Type Shapes and shape coefficient s

    37 Rotating

    umbo

    This Fig. is applicable to condition in sw0d20.015

    (a) up and down dual-pipe

    (b) back and forth dual-pipe

    s listed in the table is the same of back and forth dual-pipes, therein, the forth pipe is 0.6

    (c) close packing multi-pipe

    s is the sum of all pipes

    38 Dragline

    The shape coefficient sx of the horizontal component wx and the shape coefficient sy of the vertical

    component wy of the wind loads:

    7.3.2 If the space between multi-buildings, especially dense high-rise buildings is small, the interactive group effect of wind shall be considered. Commonly, the single building coefficient s shall be multiplied by the mutual interference aggrandizement coefficient which can be decided according to test data of similar cases. If necessary, it can be got from the tunnel test. 7.3.3 During the calculation of the enclosure members and their connections, the partial wind pressure coefficient s1 shall be decided according to the following provisions: I. External surface

    1. For zones with positive pressure, it shall be adopted according to Table 7.3.1.

  • 36

    2. Zone of negative pressure For wall face, select -1.0; For wall corners, select -1.8; For roofing partial place (fastigium with periphery and roof slope greater than 10),

    select -2.2; For overhung members, such as cornice, canopy and sun shield, select -2.0. Note: If the action width of wall corners and roof partial regions is 0.1 of the building width or 0.4 of the mean altitude of

    buildings, select the smaller one but no less than 1.5m.

    II. Internal surface For enclosed buildings, the external surface wind pressure shall be -0.2 or 0.2.

    Note: The aforesaid partial wind pressure coefficient s (1) is applicable for enclosed members with the tributary area (A)

    less than or equal to 1m2. If the tributary area of the enclosed member is greater than or equal to 10m2, the partial wind pressure

    system coefficient s (10) shall be multiplied by the discount coefficient 0.8. If the tributary area of members is less than 10m2

    but greater than 1m2, the partial wind pressure system coefficient s (A) shall be decided according to the logarithm linear

    interpolation of the area.

    s(A)=s(1)+[s(10)-s(1)]logA

    7.4 Downwind vibration and wind vibration coefficient

    7.4.1 For building with height of more than 30m, high-rise structures with basic natural vibration period T1 of more than 0.25s and wide span roofing structures, they shall consider the impact of downwind vibration to the to the structure caused by the wind pressure pulse. The wind vibration calculation shall be made according to random vibration theory, and the structural natural vibration period shall be calculated by structural dynamics.

    Note: The basic approximate natural vibration period T1 may be calculated by Appendix E.

    7.4.2 For general cantilever-type structure, if such high-rise structures as truss, tower and chimney, or torsion-neglectable high-rise buildings with height of greater than 30m and depth-width ratio of greater than 1.5, they may only consider the impact of the first vibration mode, while the wind loads of the structure may be calculated by wind vibration coefficient on the basis of formula (7.1.1-1), and the wind vibration coefficientz of the structure at height z may be worked out according to the following formula:

    z=1+z

    zv

    (7.4.2)

    Where Augmenting factor of the ripple; vInfluence coefficient of the ripple; zMode factor; zVariation coefficient of the wind pressure height

    7.4.3 The augmenting factor of the ripple; may be determined by Table 7.4.3.

  • 37

    Table 7.4.3 Augmenting Factor of the Ripple

    0T21(kNs2/m2) 0.01 0.02 0.04 0.06 0.08 0.10 0.20 0.40 0.60

    Steel structure 1.47 1.57 1.69 1.77 1.83 1.88 2.04 2.24 2.36

    Steel structure of building with filler wall 1.26 1.32 1.39 1.44 1.47 1.50 1.61 1.73 1.81

    Concrete and masonry structure 1.11 1.14 1.17 1.19 1.21 1.23 1.28 1.34 1.38

    0T21(kNs2/m2) 0.80 1.00 2.00 4.00 6.00 8.00 10.00 20.00 30.00

    Steel structure 2.46 2.53 2.80 3.09 3.28 3.42 3.54 3.91 4.14

    Steel structure of building with filler wall 1.88 1.93 2.10 2.30 2.43 2.52 2.60 2.85 3.01

    Concrete and masonry structure 1.42 1.44 1.54 1.65 1.72 1.7 1.82 1.96 2.06

    Note: when calculating 0T21, basic wind pressure may be replaced directly for regions with ground roughness of B-type,

    while for regions of A-type, C-type and D-type, it shall be replaced by local basic wind pressure being multiplied by 1.38, 0.62

    and 0.32 respectively.

    7.4.4 Influence coefficient of the ripple may be determined by the following conditions respectively.

    1 The condition when the windward width of the structure is far less than its height such as high-rise structure;

    1) If the contour and mass are even along the aspect ratio, ripple ratio may be determined according to Table 7.4.4-1.

    Table 7.4.4-1 Influence Coefficient of the Ripple

    Total height

    H(m) 10 20 30 40 50 60 70 80 90 100 150 200 250 300 350 400 450

    Types of ground roughness

    A

    B

    C

    D

    0.78

    0.72

    0.64

    0.53

    0.83

    0.9

    0.73

    0.65

    0.86

    0.83

    0.78

    0.72

    0.87

    0.85

    0.82

    0.77

    0.88

    0.87

    0.85

    0.81

    0.89

    0.88

    0.87

    0.84

    0.89

    0.89

    0.88

    0.87

    0.89

    0.89

    0.90

    0.89

    0.89

    0.90

    0.91

    0.91

    0.89

    0.90

    0.91

    0.92

    0.87

    0.89

    0.93

    097

    0.84

    0.88

    0.93

    1.00

    0.82

    0.86

    0.92

    1.01

    0.79

    0.84

    0.91

    1.01

    0.79

    0.83

    0.90

    1.01

    0.79

    0.83

    0.89

    1.00

    0.79

    0.83

    0.91

    1.00

    2) When the width of the windward and crosswind side of the structure varies along the height in beeline or approach beeline, while the mass varies along the height continuous and regularly, influence coefficient of the ripple shown in Table 7.4.4-1 shall be multiplied by compensation factor B and v again. B shall be the ratio between the width Bz at height z and the bottom width Bo of the structures windward; may be determined by Table 7.4.4-2.

    Table 7.4.4-2 Compensation Factor

    BH/Bo 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1

    1.00 L 10 1.20 1.32 1.50 1.5 2.08 2.53 3.30 5.60

    Note: BH and B0 are widths of the structures windward on the top and at the bottom.

    2 When the width of the structure windward is larger, condition for spatial correlation of wind pressure along the width direction shall be considered (such as high-rise building); if the contour and mass are even along the aspect ratio, the influence coefficient of the ripple may be the ratio between the total height H and its windward width B, it may be determined by Table 7.4.4-3.

  • 38

    Table 7.4.4-3 Influence Coefficient of the Ripple

    Total height H(m)

    H/B

    Types of

    ground

    roughness 30 50 100 150 200 250 300 350

    0.5

    A

    B

    C

    D

    0.44

    0.42

    0.40

    0.36

    0.42

    0.41

    0.40

    0.37

    0.33

    0.33

    0.34

    0.34

    0.27

    0.28

    0.29

    0.30

    0.24

    0.25

    0.27

    0.27

    0.21

    0.22

    0.23

    0.25

    0.19

    0.20

    0.22

    0.24

    0.17

    0.18

    0.20

    0.22

    1.0

    A

    B

    C

    D

    0.48

    0.46

    0.43

    0.39

    0.47

    0.46

    0.44

    0.42

    0.41

    0.42

    0.42

    0.42

    0.35

    0.36

    0.37

    0.38

    0.31

    0.36

    0.34

    0.36

    0.27

    0.29

    0.31

    0.33

    0.26

    0.27

    0.29

    0.32

    0.24

    0.26

    0.28

    031

    2.0

    A

    B

    C

    D

    0.50

    0.48

    0.45

    0.41

    0.51

    0.50

    0.49

    0.46

    0.46

    0.47

    0.48

    0.48

    0.42

    0.42

    0.44

    0.46

    0.38

    0.40

    0.42

    0.46

    0.35

    0.36

    0.38

    0.44

    0.33

    0.35

    0.38

    0.42

    0.31

    0.33

    0.36

    0.39

    3.0

    A

    B

    C

    D

    0.53

    0.51

    0.48

    0.43

    0.51

    0.50

    0.49

    0.46

    0.49

    0.49

    0.49

    0.49

    0.42

    0.46

    0.48

    0.49

    0.41

    0.43

    0.46

    0.48

    0.38

    0.40

    0.43

    0.47

    0.38

    0.40

    0.43

    0.46

    0.36

    0.38

    0.41

    0.45

    5.0

    A

    B

    C

    D

    0.52

    0.50

    0.47

    0.43

    0.53

    0.53

    0.50

    0.48

    0.51

    0.52

    0.52

    0.52

    0.49

    0.50

    0.52

    0.53

    0.46

    0.48

    0.50

    0.53

    0.44

    0.45

    0.48

    0.52

    0.42

    0.44

    0.47

    0.51

    0.39

    0.42

    0.45

    0.50

    8.0

    A

    B

    C

    D

    0.53

    0.51

    0.48

    0.43

    0.54

    0.53

    0.51

    0.48

    0.53

    0.54

    0.54

    0.54

    0.51

    0.52

    0.53

    0.53

    0.48

    0.50

    0.52

    0.55

    0.46

    0.49

    0.52

    0.55

    0.43

    0.6

    0.50

    0.54

    0.42

    0.44

    0.48

    0.53

    7.4.5 The mode factor shall be determined by power calculation of the structure. For cantilever-type high-rise structure with contour, mass and rigidity vary continuously and regularly along the height, or the high-rise building even in aspect ratio, the mode factor may also be determined by relative height z/H on the basis of Appendix F.

    7.5 Gustiness factor

    7.5.1 When calculating wind loads of curtain wall component (including door window) of the blind bearing the wind pressure, gustiness factor shall be determined by Table 7.5.1.

    For other roof and wall face components, gustiness factor takes 1.0.

  • 39

    Table 7.5.1 Gustiness Factor gz

    Types of ground roughness Ground level (m)

    A B C D

    5 1.69 1.88 2.30 3.21

    10 1.63 1.78 2.10 2.76

    15 1.60 1.72 1.99 2.54

    20 1.58 1.69 1.92 2.39

    30 1.54 1.64 1.83 2.21

    40 1.52 1.60 1.77 2.09

    50 1.51 1.58 1.3 2.01

    60 1.49 1.56 1.69 1.94

    70 1.48 1.54 1.66 1.89

    80 1.47 1.53 1.64 1.85

    90 1.47 1.52 1.62 1.81

    100 1.46 1.51 1.60 1.8

    150 1.43 1.47 1.54 1.67

    200 1.42 1.44 1.50 1.60

    250 1.40 1.42 1.46 1.55

    300 1.39 1.41 1.44 1.51

    7.6 Crosswind vibration

    7.6.1 For round section structure, crosswind vibration (swirl desquamation) for different Reynolds number Re shall be checked according to the following provisions.

    1 When Re

  • 40

    vH= 02000 wH (7.6.1-3)

    Where TiNatural vibration period of the structural vibration mode i; when checking

    the subcritical breeze sympathetic vibration, it takes basic natural vibration period T1; StStrouhal number, it takes 0.2 for circular sectional structure; HVariation coefficient of the wind pressure height on top of the structure; w0Basic wind pressure (kN/m2); Air density (kg/m3) 6 When the structure is reduced along the height section (inclination pitch is no greater

    than 0.02), diameter at 2/3 structural height may be approximately adopted. 7.6.2 The equivalent wind loads of vibration mode j caused by over-critical fresh gale sympathetic vibration at the height z may be determined by the following formula:

    Wczj=|j|vcr2zj/12800jKN/m2 (7.6.2-1) Initial point height H1 of the critical wind velocity shown in Table 7.6.2 may be

    determined by the following formula:

    H1=H aH

    cr

    vv /1)2.1

    ( (7.6.2-2)

    Where: Ground roughness index, they are 0.12, 0.16, 0.22 and 0.30 for A-type, B-type,

    C-type and D-type respectively; HWind speed on top of the structure (m/s) Note: when checking the crosswind vibration, high vibration mode No. considered is no greater than 4, and it may take the

    first or second vibration mode for general cantilever-type structure.

    Table 7.6.2 Table for j Calculation

    H1/H Structure

    type

    Vibration

    mode No. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

    High-rise

    structure

    1

    2

    3

    4

    1.56

    0.83

    0.52

    0.30

    1.55

    0.82

    0.48

    0.33

    1.54

    0.76

    0.32

    0.02

    1.49

    0.60

    0.06

    -0.20

    1.42

    0.37

    -0.19

    -0.23

    1.31

    0.09

    -0.30

    0.03

    1.15

    -0.16

    -0.21

    0.16

    0.94

    -0.33

    0.00

    0.15

    0.68

    -0.38

    0.20

    -0.05

    0.37

    -0.27

    0.23

    -0.18

    0

    0

    0

    0

    High-rise

    building

    1

    2

    1.56

    0.73

    1.56

    0.72

    1.54

    0.63

    1.49

    0.45

    1.41

    0.19

    1.28

    -0.11

    1.12

    -0.36

    0.91

    -0.52

    0.65

    -0.53

    0.35

    -0.36

    0

    0

    7.6.3 When checking crosswind vibration, the gross effect of wind loads may determine the crosswind load effect Sc and downwind load effect SA by the following formula:

    S= 22 AC SS + (7.6.3) 7.6.4 For the structure of non-circular section, equivalent wind loads of the crosswind vibration should be determined by the tunnel test of the air elastic model; or it may be determined by reference to the relevant information.

  • 41

    Appendix A Deadweight of Commonly-used Materials and Members

    Table A.1 Deadweight of Commonly-used Materials and Members

    Item Deadweight Remarks

    1. Timber (kN/m3)

    Cedar wood 4 Varying according to water ratios

    Fir, spruce, Korean pine, China Armand pine, hemlock, Mongolian

    Scotch Pine, alder, toon, poplar, Chinese ash 4-5 Varying according to water ratios

    Chinese red pine, Burma pine, Chinese pine, red pine, Guangdong

    pine, alder, sweetgum, wear the willow, common sassafras, Qinling

    Mountain larch and Xinjiang larch

    5-6 Varying according to water ratios

    Northeast larch, Dacrydium cupressinum, elm, birch, Manchurian

    ash, chinaberry, ailanthus 6-7 Varying according to water ratios

    Holm oak, Chinese locust 7-8 Varying according to water ratios

    Oak, eucalyptus, beefwood 8-9 Varying according to water ratios

    Common wooden batten, sandal wood 5 Varying according to water ratios

    Sawdust 2-2.5 With preservatives, 3kN/m3

    Fiber board 4-5

    Cork board 2.5

    Chipboard 6

    2. Peeler ( kN/m2)

    Veneer three-ply ( poplar) 0.019

    Veneer three-ply ( basswood) 0.028

    Veneer three-ply ( Manchurian ash) 0.028

    Veneer five-layer plywood ( poplar) 0.03

    Veneer five-layer plywood ( basswood) 0.034

    Veneer five-layer plywood ( Manchurian ash) 0.04

    Cane fiber board (counted based on 10mm) 0.03 Commonly-used thicknesses are

    13mm, 15mm, 19mm and 25mm

    Sound screen (counted based on 10mm) 0.03 Commonly-used thicknesses are

    13mm and 20mm

    Xylolite slab (counted based on 10mm) 0.12 Commonly-used thicknesses are

    6mm and 20mm

    3. metal mineral products (kN/m3)

  • 42

    Cast iron 72.5

    Wrought iron 77.5

    Iron ore scrap 27.6

    Hematite 25-30

    Steel 78.5

    Tough pitch, red copper 89

    Brass, gunmetal 89

    Sulphide copper ore 42

    Aluminium 27

    Aluminium alloy 28

    Zinc 70.5

    Sub-zinc mine 40.5

    Lead 114

    Galena 74.5

    Gold 193

    Platinum 213

    Silver 105

    Tin 73.5

    Nickel 89

    Mercury 136

    Tungsten 189

    Magnesium 18.5

    Antimony 66.6

    Crystal 29.5

    Borax 17.5

    Sulphur ore 20.5

    Asbestos mine 24.6

    Asbestos 10 Compaction

    Asbestos 4 Incoherence, dampness no bigger

    than 15%

    Kaolin 22

    Gypsum mine 25.5

    Gypsum 13-14.5 Hunch stockpile =30

  • 43

    Thin stockpile =40

    Gypsum powder 9

    4. Earth, Sand, Grit, Rock ( kN/m3)

    Humus soil 15-16 Dry, =40; wet, =35, extremely wet, =25

    Clay 13.5 Dry, soft, void ratio is 1.0

    Clay 16 Dry, =40, compaction

    Clay 18 Wet, =35, compaction

    Clay 20 Extremely wet, =25, compaction

    Grit 12.2 Dry, soft

    Sandy soil 16 Dry, =35, compaction

    Sandy soil 18 Wet, =35, compaction

    Sandy soil 20 Extremely wet, =25, compaction

    Sandy soil 14 Dry, fine sand

    Sandy soil 17 Dry, fine sand

    Pebble 16-18 Dry

    Clay with pebble 17-18 Dry, soft

    Sand with pebble 15-17 Dry, soft

    Sand with pebble 16-19.2 Dry, compaction

    Sand with pebble 18.9-19.2 Wet

    Pumice 6-8 Dry

    Pumice filling materials 4-6

    Sandstone 23.6

    Shale 28

    Shale 14.8 Slabstone stow

    Marlstone 14 =40

    Granite, marble 28

    Granite 15.4 Slabstone stow

    Limestone 26.4

    Limestone 15.2 Slabstone stow

    Mussel bed 14

    Dolomite 16 Slabstone stow, =48

    Talcum 27.1

    Flint 35.2

  • 44

    Toniciidae 27.6

    Basalt 29.5

    Feldspar 25.5

    Hornblende, verdantique 30

    Hornblende, verdantique 17.1 Slabstone stow

    Blinding 14-15 Stow

    Rock meal 16 Clay nature or limy

    Bubbly clay 5-8 Filling material, =35

    Kieselguhr filling material 4-6

    Diabase board 29.5

    5. Brick and Brickbat (kN/m3)

    Common brick 18 240mm115mm53mm(684 pieces/m3)

    Common brick 19 Made by machine

    Clinker 21-21.5 230mm110mm65mm (609 pieces/m3)

    Red clinker 20.4

    Firebrick 19-22 230mm110mm65mm(609 pieces/m3)

    Acidproof ceramic tile 23-25 230mm113mm65mm(590 pieces/m3)

    Sand-lime brick 18 Sand: ash= 92:8

    Cinder block 17-18.5

    Slag brick 18.5 Hard slag: soot: lime = 75:15:10

    Breeze brick 12-14

    Soot brick 14-15 Slag: carbide slag: soot=30:40:30

    Clay butt 12-15

    Sawdust brick 9

    Cinder hollow block 10 290mm290mm140mm(85 pieces/m3)

    Cement hollow tile 9.8 290mm290mm140mm(85 pieces/m3)

    Cement hollow block 10.3 300mm250mm110mm(121 pieces/m3)

    Cement hollow block 9.6 300mm250mm160mm(83 pieces/m3)

    Press-powder coal-dust brick 14.0-16.0 Dry and weight degree

    Haydite building block 5.0

    6.0

    Length 600, 400m, width 150, 250mm, height 250,

    200mm

    390mm290mm190mm

    Pulverized fuel ash light hollow brick 7.0-8.0 390mm190mm190mm, 390mm240mm190mm

  • 45

    Press-powder coal ash aerocrete block 5.5

    Concrete hollow small block 11.8 390mm190mm190mm

    Rubble 12 Stow

    Cement tile 19.8 200mm200mm24mm(1042 pieces/m3)

    Porcelain facing brick 19.8 150mm150mm8mm(5556 pieces/m3)

    Ceramic mosaic 0.12kN/m2 Thickness 5mm

    6. Lime, Cement, Mortar and Concrete ( kN/m3)

    Quicklime block 11 Stow, =30

    Quicklime powder 12 Stow, =35

    White lime cream 13.5

    Lime mortar, cement lime mortar 17

    Cement, lime, cinder, mortar 14

    Calcareous slag 10-12

    Cement slag 12-14

    Cement, cinder, mortar 13

    Lime soil 17.5 Lime: earth =3:7, tamping

    Straw lime slurry 16

    Paper lime slurry 16

    Lime sawdust 3.4 Lime: sawdust=1:3

    Lime concrete 17.5 Lime, grit, pebble

    Cement 12.5 Lightweight incoherence, =20

    Cement 14.5 Bulkload, =30

    Cement 16 In bags, compaction, =40

    Slag cement 14.5

    Cement mortar 20

    Cement, grout 5-8

    Asbestos cement mortar 19

    Expanded perlite mortar 7-15

    Gypsum mortar 12

    Rubble concrete 18.5

    Plain concrete 22-24 Bumping down or not bumping down

    Cinder concrete 20

    Breeze concrete 16-17 For bearing

  • 46

    Breeze concrete 10-14 For filling

    Iron-aggregate concrete 28-65

    Pumice concrete 9-14

    Bituminous concrete 20

    Macroporosity concrete without sand 16-19

    Foamed concret 4-6

    Aerocrete 5.5-7.5 Monolith

    Reinforcement concrete 24-25

    Rubble reinforced concrete 20

    Steel-web cement 25 For load-carrying members

    Water glass acid proof concrete 20-23.5

    Pulverized fuel ash pottery pebble

    concrete 19.5

    7. pitch, coal ash, butter grain (kN/m3)

    Petroleum asphalt 10-11 According to relative density

    Tar 12

    Coal pitch 13.4

    Coal tar 10

    Anthracite 15.5 Whole

    Anthracite 9.5 Massive stockpile, =30

    Anthracite 8 Shiver stockpile, =35

    Tobacco smalls 7 Stockpile, =15

    Coal briquette 10 Stockpile

    Lignite 12.5

    Lignite 7-8 Stockpile

    Turf 7.5

    Turf 3.2-3.4 Stockpile

    Xylanthrax 3-5

    Coal coke 12

    Coal coke 7 Stockpile, =45

    Cinder 10

    Coal ash 6.5

    Coal ash 8 Compaction

  • 47

    Plumbago 20.8

    Coal wax 9

    Oil wax 9.6

    Crude oil 8.8

    Kerosene 8

    Kerosene 7.2 In bulk, relative density 0.82-0.89

    Lubricating oil 7.4

    Gasoline 6.7

    Gasoline 6.4 In bulk, relative density 0.72-0.76

    Animal oil, vegetable oil 9.3

    Bean oil 8 Large barrel, per barrel 360kg

    8. Misc ( kN/m3)

    Simple glass 25.6

    Steel glass 26

    Cellular glass 3-5

    Glass wool 0.5-1 For insulating layer filling material

    Rock wool 0.5-2.5

    Pitch glass wool 0.8-1 coefficient of heat conductivity 0.035- 0.047 [ W/( mK)]

    Glass wool board ( pipe socket) 1-1.5 coefficient of heat conductivity 0.035- 0.047 [ W/( mK)]

    Fiberglass reinforced plastics 14-22

    Slag wool 1.2-1.5 Incoherence, coefficient of heat conductivity 0.031-

    0.044 [ W/( mK)]

    Slag wool manufactured product (board,

    brick and tube) 3.5-4 coefficient of heat conductivity 0.041- 0.052 [ W/( mK)]

    Asphalt slag wool 1.2-1.6 coefficient of heat conductivity 0.041- 0.052 [ W/( mK)]

    Asphalt slag wool 1.2-1.6 coefficient of heat conductivity 0.041- 0.052 [ W/( mK)]

    Expanded perlite powder lot 0.8-2.5 Dry, soft, coefficient of heat conductivity 0.052- 0.076

    [ W/( mK)]

    Cement perlite products 3.5-4 Intensity 1N/mm2, soft, coefficient of heat conductivity

    0.058- 0.081 [ W/( mK)]

    Expanded vermiculite 0.8-2 coefficient of heat conductivity 0.052- 0.07 [ W/( mK)]

    Pitch vermiculite manufactured product 3.5-4.5 coefficient of heat conductivity 0.81- 0.105 [ W/( mK)]

    Cement vermiculite manufactured

    product 4-6 coefficient of heat conductivity 0.093- 0.14 [ W/( mK)]

  • 48

    Polyvinyl choride board (tube) 13.6-16

    Polystyrene foam 0.5 coefficient of heat conductivity no greater than 0.035

    [ W/( mK)]

    Asbestos board 13 Water ratio no greater than 3%

    Emulsified asphalt 9.8-10.5

    Flexible rubber 9.3

    White phosphorus 18.3

    Rosin 10.7

    Magnetism 24

    Alcohol 7.85 100% (net)

    Alcohol 6.6 In bulk, relative density 0.79-0.82

    Hydrochloric acid 12 Concentration 40%

    Nitric acid 15.1 Concentration 91%

    Vitriol 17.9 Concentration 87%

    Alkali 17 Concentration 60%