Fuse Block SpecificationsBulletin Number 1491
Specifications
Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Topic Page
1491 Specifications this page
Fuse Size 1…30 A — Approximate Dimensions 2
Fuse Size 31…60 A — Approximate Dimensions 3
Fuse Size 61…100 A — Approximate Dimensions 4
Fuse Size 101…200 A — Approximate Dimensions 5
Fuse Size 201…400 A — Approximate Dimensions 6
Fuse Size 401…600 A — Approximate Dimensions 6…7
Electrical
UL Fuse Type Class H Class J Class R Class C Class CC
Maximum Fuse Cartridge Size 30…600 A 30…600 A 30…600 A 30…600 A 30 A
Maximum Voltage AC/DC 600V/250V 600V/250V 600V/250V 600V/250V 600V/250V
Thermal Current Rating 30…600 A 30…600 A 30…600 A 30…600 A 30 A
Maximu Short Circuit Prospective Fault Current 10 kA 200 kA 200 kA 100 kA 200 kA
Construction
Fuse Clips Tin-plated copper
Terminals Tin-plated copper
Fuse Block Base Phenolic or porcelain
Environmental
Ambient Temperature OpenEnclosedStorage
-20…+55 °C (-4…+131 °F)-20…+40 °C (-4…+104 °F)
-40…+65 °C (-40…+149 °F)Altitude (per IEC 947-5) 2000 m
Relative Humidity (per IEC 947-3) 90% @ 20 °C (68 °F) and 50% @ 40 °C (104 °F)
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.
2 Rockwell Automation Publication 1491-TD001A-EN-P
1491 Fuse Blocks Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Fuse Size 1…30 A
2 Holes0.172 (4.37) Dia.
RejectionFeature
4 Terminals Combination of:Double Quick-Connect
(0.250x0.032) 20 A Max.,and Pressure Plate Screw
(10…32 Sems).(Ref.) Wire: #10 AWG Max. Cu Only
Cat. No. 1491-R162
1…30 A, Single Pole, 600V Cat. No. 1491-N161
Shipping Weight — 1 lb (0.45 kg)
Drill & Tap2 Holes for
#10…32 Screws
1…30 A, 2-Pole, 250V Cat. No. 1491-N122
Shipping Weight — 2 lb (0.91 kg)
Drill & Tap 4 Holesfor #10…32 Screws
1…30 A, 3-Pole, 250…600V Cat. No. 1491-N125 (250V) Cat. No. 1491-N126 (600V)
Shipping Weight — 1 lb (0.45 kg)
Drill & Tap2 Holes for
#10…32 Screws
9/32 (7.1) Dia.
Voltage[V]
Class H Class J
A B A B
250 2-1/8 (54.0) 3 (76.2) — —
600 2-3/8 (60.3) 5-3/4 (146.1) 2-3/8 (60.3) 3 (76.2)
�Alternate mounting holes.
Fuse Size[A]
MaximumVolts [V] Cat. No.
A‡±0.020
BRef.
1…30250 1491-R125 2.94 (74.68) 2-1/8 (53.97)
600 1491-R126 5.72 (145.29) 2-3/8 (60.33)
‡ Dimension “A” must be held to insure fuse block rejection function.
Note: When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
Drill & Tap for#10…32 Screws
Rejection Members
1…30 A, 250…600V Cat. No. 1491-R125 (250V) Cat. No. 1491-R126 (600V)
Shipping Weight — 1 lb (0.45 kg)
3Rockwell Automation Publication 1491-TD001A-EN-P
Approximate Dimensions 1491 Fuse Blocks
Fuse Size 31…60 A
Drill & Tap 4 Holesfor #10…32 Screws
31…600 A, 3-Pole, 250…600V Cat. No. 1491-N226 (250V)
Shipping Weight — 1 lb (0.45 kg)
Cat. No. 1491-N266 (600V) Shipping Weight — 2 lb (0.91 kg)
Drill & Tap for#10…32 Screws
Rejection Members
31…60 A, 250…600V Cat. No. 1491-R226 (250V)
Shipping Weight — 1 lb (0.45 kg)Cat. No. 1491-R266 (600V)
Shipping Weight — 2 lb (0.91 kg)
Drill & Tap 4 Holesfor 1/4-20 Screws
Drill & Tap 8 Holesfor 1/4-20 Screws
Single Pole Application Use (1) of Cat. No. 1491-N321
Approximate Shipping Weight — 2 lb (0.91 kg)
3-Pole Application Use (3) of Cat. No. 1491-N321
Approximate Shipping Weight — Approx. 3 times wt. of 1-Pole
Drill & Tap 6 Holesfor 1/4-20 Screws
2-Pole Application Use (2) of Cat. No. 1491-N321
Approximate Shipping Weight — Approx. 2 times wt. of 1-Pole
Voltage[V]
Class H Class J
A B A B
250 2-3/8 (60.3) 3-3/4 (95.3) — —
600 2-11/16 (68.3) 6-1/4 (158.8) 2-11/16 (68.3) 3-1/8 (79.4)
�Alternate mounting holes.
Fuse Size[A]
MaximumVolts [V] Cat. No.
A‡±0.020
BRef.
31…60250 1491-R226 3.72 (94.49) 2-3/8 (60.33)
600 1491-R266 6.22 (157.99) 2-11/16 (68.26)
‡ Dimension “A” must be held to insure fuse block rejection function.
Drill & Tap 10 Holesfor 1/4-20 Screws
4-Pole Application Use (4) of Cat. No. 1491-N321
Approximate Shipping Weight — Approx. 3 times wt. of 1-Pole
Voltage[V]
Class H Class J
A B A B
250 82.6 (3-1/4) 174.6 (6-7/8) — —
600 85.7 (3-3/8) 225.4 (8-7/8) 82.6 (3-1/4) 142.9 (5-5/8)
Notes:1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.2. When using Cat. No. 1491-N321, install fiber washers between fuse blocks and mounting plates. Discard extra screws, washers, and clamps on multiple pole
applications.
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
4 Rockwell Automation Publication 1491-TD001A-EN-P
1491 Fuse Blocks Approximate Dimensions
Fuse Size 61…100 ADrill & Tap 4 Holesfor 1/4-20 Screws
3-Pole Cat. No. 1491-N333
Approximate Shipping Weight — 3 lb (1.36 kg)
Voltage[V]
Class H Class J
A B A B
250 2-15/16 (74.6) 5-7/8 (149.2) — —
600 3-1/8 (79.4) 7-7/8 (200.0) 3 (76.2) 4-5/8 (117.5)
Drill & Tap for1/4-20 Screws
Rejection Members
13/32 max.(10.32 max.)
61…100 A, 250…600VCat. No. 1491-R333
Shipping Weight — 3 lb (1.36 kg)
Notes1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.2. Fuse blocks with wedge type clamps (61 A and above) can be oriented to mount all fuses either to the left or to the right of fuse clamp centers.
Fuse Size[A] Maximum Volts [V] Cat. No.
A�±0.020
BRef.
61…100250
1491-R3335.88 (149.35) 2-15/16 (74.61)
600 7.88 (200.15) 3-1/8 (79.38)
�Dimension “A” must be held to insure fuse block rejection function.
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
5Rockwell Automation Publication 1491-TD001A-EN-P
Approximate Dimensions 1491 Fuse Blocks
Drill for 5/16-18 Screw
3-Pole Application Use Three of Cat. No. 1491-N521 Shipping Weight — 19 lb (8.6 kg)
Drill for 5/16-18 Screw
4-Pole Application Use Four of Cat. No. 1491-N521
Shipping Weight — 25 lb (11.4 kg)
Voltage [V]
Class H or R Class J
A B A B
250 4-3/4 (120.7) 9 (228.6) — —
600 4-61/64 (125.8) 12 (304.80) 4-5/8 (117.5) 7-1/2 (190.5)
Fuse Size 101…200 A
Drill & Tap for5/16-18 Screw
Rejection Members
19/32 max.(15.1 max.)
101…200 A, 250…600V Cat. No. 1491-R433
Shipping Weight — 7 lb (3.2 kg)
Drill for 5/16-18 Screw
Single Pole Cat. No. 1491-N521
Shipping Weight — 7 lb (3.2 kg)
Drill for 5/16-18 Screw
2-Pole Application Use Two of Cat. No. 1491-N521 Shipping Weight — 6kg (13 lb)
Fuse Size[A]
MaximumVolts [V] Cat. No.
A�±0.020
BRef.
101…200250
1491-R4337.25 (184.15) 4-3/16 (106.36)
600 9.75 (247.60) 4-5/16 (109.54)
�Dimension “A” must be held to insure fuse block rejection function.
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Note: When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
6 Rockwell Automation Publication 1491-TD001A-EN-P
1491 Fuse Blocks Approximate Dimensions
Fuse Size 201…400 A
Drill & Tapfor 5/16-18
Screws
Rejection Members
1/4 max.(6.35 max.)
201…400 A, 250…600V Cat. No. 1491-R523
Shipping Weight — 19 lb (8.6 kg)
Fuse Size [A]MaximumVolts [V] Cat. No.
A�±0.020
BRef.
201…400250
1491-R5239 (228.60) 4-3/4 (120.70)
600 12 (304.80) 4-61/64 (125.81)
�Dimension “A” must be held to insure fuse block rejection function.
Fuse Size 401…600 A
Single Pole 600 A Terminations Only
Cat. No. 1491-N621 Shipping Weight — 6 lb (2.7 kg)
Notes1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.2. Fuse blocks with wedge type clamps (61 A and above) can be oriented to mount all fuses either to the left or to the right of fuse clamp centers.
Voltage [V]
Class H or R Class J
A B A B
250 8-1/8 (206.38) 4-5/8 (117.47) — —
600 11-1/8 (282.57) 7-5/8 (193.68) 6 (127.00) 2-1/2 (63.50)
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
7Rockwell Automation Publication 1491-TD001A-EN-P
Approximate Dimensions 1491 Fuse Blocks
Drill for 5/16-18 Screw
401…600 A250V
401…600 A600V
401…600 A250V
401…600 A600V
4-Pole 400 A Terminations Only
Cat. No. 1491-N621 (Amt. 4) Shipping Weight — 21 lb (9.5 kg)
Fuse Size 401…600 A, Continued
401…600 A250V
401…600 A600V
401…600 A250V
401…600 A600V
Drill for 5/16-18 Screw
2-Pole 400 A Terminations Only
Cat. No. 1491-N621 (Amt. 2) Shipping Weight — 11 lb (5 kg)
401…600 A250V
401…600 A600V
Drill for 5/16-18 Screw
401…600 A250V
401…600 A600V
3-Pole 400 A Terminations Only
Cat. No. 1491-N621 (Amt. 3) Shipping Weight — 16 lb (7.3 kg)
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1491-TD001A-EN-P - August 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400