  • Hudson Products Corp. Page 1 of 35 The Basics of Axial Flow Fans

    The Basics ofAXIAL FLOW FANS

  • Hudson Products Corp. Page 2 of 35 The Basics of Axial Flow Fans

    CONTENTS

    PageFOREWORD ........................................................................................................................ 3FIGURES ............................................................................................................................. 3NOMENCLATURE ............................................................................................................. 4

    1.0 Definition of Axial Fans ........................................................................................... 62.0 Fan Engineering Nomenclature ................................................................................ 6

    2.1 Fan Engineering Units .................................................................................. 82.2 Useful Conversion Factors ........................................................................... 9

    3.0 Fan Selection Criteria ............................................................................................... 104.0 Basic Fan Equations - (I-P Units Only) .................................................................... 115.0 Fan Performance Calculation ................................................................................... 126.0 Some Basic Assumptions ......................................................................................... 14

    Effect of:6.1 Tip Clearance ................................................................................................ 156.2 Inlet Conditions ............................................................................................ 166.3 Velocity Recovery Stacks ............................................................................. 166.4 System Resistance ........................................................................................ 176.5 Horsepower ................................................................................................... 186.6 Density .......................................................................................................... 196.7 Vibration ....................................................................................................... 206.8 Number of Blades ......................................................................................... 216.9 Blade Shape .................................................................................................. 226.10 Seal Disc ....................................................................................................... 23

    7.0 Variable Airflow Fans (Auto-Variable ) .................................................................. 238.0 Variable-Pitch vs. Variable-Speed ............................................................................ 299.0 Noise Considerations ................................................................................................ 29

    9.1 Noise-Related Nomenclature ........................................................................ 309.2 Allowable Fan Noise .................................................................................... 319.2.1 ACHE Noise ................................................................................................. 319.2.2 Cooling Tower Noise .................................................................................... 319.3 Predicting Fan Noise .................................................................................... 319.4 Noise Testing ................................................................................................ 33

    REFERENCES ..................................................................................................................... 34DEDICATION ...................................................................................................................... 34

  • Hudson Products Corp. Page 3 of 35 The Basics of Axial Flow Fans

    FIGURESPage

    1. Typical Air-Cooled Heat Exchanger Fan .................................................................. 62. Typical Fan Curve .................................................................................................... 123. Approximate HP Savings with Velocity Recovery Stack. ........................................ 144. Stall Points on Fan Curve ......................................................................................... 145. Tip Vortex (Leakage) ................................................................................................ 156. Tip Clearance ............................................................................................................ 157. Airflow with No Inlet Bell ....................................................................................... 168. Airflow with Inlet Bell ............................................................................................. 169. Typical Large Cooling Tower Fan with VR Stack.................................................... 1710. Approximate Cost of Power to Operate 8400 hrs/yr. ............................................... 1711. ASP vs. CFM for Air-Cooled Heat Exchanger ......................................................... 1812. Velocity Profiles - Tapered vs. Constant Chord Blade ............................................. 2213. Typical Seal Disc Prior to Installation ...................................................................... 2314. Typical Auto-Variable Fan ...................................................................................... 2315. Inverted Actuator-Variable Pitch Fan ....................................................................... 2316. AV Force Diagram .................................................................................................... 2417. Airflow vs. Signal for Variable-Pitch Hub ............................................................... 2418. Typical Auto-Variable Hub ..................................................................................... 2519. Throttled Flow Through Fan .................................................................................... 2720. Air Delivery vs. Temperature ................................................................................... 2821. Power Study Results ................................................................................................. 2822. Weighted Sound Levels ............................................................................................ 30

    FOREWORD

    This manual is designed to familiarize userswith applications for axial flow fans,velocity recovery stacks, seal discs, andvariable flow fans. Calculations are providedfor estimating fan power consumption andnoise.

    It should be noted that final fan selection shouldbe made by using Hudsons Tuf-Lite FanSelection Program or by contacting HudsonProducts Corporation at 713-914-5700 or1-800-634-9160.

  • Hudson Products Corp. Page 4 of 35 The Basics of Axial Flow Fans

    NOMENCLATURE

    English Letter Symbols

    ACHE = air-cooled heat exchangerACFM = actual cubic feet per minute

    ACT = actual conditionsASP = actual static pressureATP = actual total pressureAVP = actual velocity pressureBHP = brake horsepowerBPF = beam or blade passing frequency

    CS = current sourceCFM = cubic feet per minute

    DR = density ratioEff = efficiency

    D = fan diameterFPM = feet per minute

    HP = horsepowerLP = sound pressure levels (metric units)

    LW = sound power levels (metric units)MSL = mean sea level

    N = number of fansNFA = net free fan areaPWL = sound power level (I-P units)

    r = inlet bell radiusPWM = pulse wide modulation

    R = feet from center of noise sourceRH = relative humidity

    RPM = revolutions per minuteSCFM = standard cubic feet per minute

    SF = speed factorSP = static pressure

    SPL = sound pressure level (I-P units)SR = solidity ratio

    STD = standard conditionsEffTotal = total efficiencyEffStatic = static efficiency

    TP = total pressureV = velocity

    VFD = variable-frequency driverVP = velocity pressureVR = recovered velocity pressure

    VVI = variable-voltage inverter

  • Hudson Products Corp. Page 5 of 35 The Basics of Axial Flow Fans

    Greek Letter Symbols

    = density

    Subscripts

    ACT (act) = actual conditionSTD (std) = standard condition

    exit (ex) = velocity recovery stack exitc = fan curve condition at standard density

    1 = inlet, condition 12 = outlet, condition 2

    in = inletout = outletSL = sea leveldes = designeff = effective

  • Hudson Products Corp. Page 6 of 35 The Basics of Axial Flow Fans

    Typical Air-Cooled Heat Exchanger FanFig. 1

    2.0 Fan Engineering Nomenclature

    ACFM - Actual cubic feet per minute of airmoved by the fan.

    Actual Conditions - Resistances related toactual inlet or outlet temperature and fanelevation above mean sea level compared tostandard conditions.

    Air Density - Air density at the plane of thefan based on standard or actual conditions.

    Beam Passing Frequency - Number of timesper revolution that one fan blade passes overa beam or strut thought of as how thestructure interacts with the fan blade ex-pressed in cycles/sec (Hz).

    Blade Natural Frequency - Frequency atwhich a blade freely vibrates when it is struckin cycles/sec (Hz).

    Blade Passing Frequency - Number of timesper revolution that a fan tip passes a point onthe fan ring expressed in cycles/sec (Hz) thought of as how the fan interacts with thestructure.

    Brake Horsepower - (BHP) - Net powerrequired by the fan at actual conditions toperform the required design work.

    Chord - Straight line distance between theleading and trailing airfoil edges.

    Fan Diameter - Width/distance between op-posite blade tips.

    Fan Laws - Set of laws that predict perfor-mance changes if one or more parameters arechanged from one fan or operating conditionto another. These laws govern airflow, pres-sure capability and power required amongmany other parameters.

    AXIAL FLOW FANS

    1.0 Definition of Axial Fans

    An axial flow fan moves air or gas parallelto the axis of rotation. By comparison, acentrifugal or radial flow fan moves airperpendicular to the axis of rotation. Axialflow fans are better suited for low-resistance,high-flow applications, whereas centrifugalflow fans apply to high-pressure resistance,low-flow conditions. Typically, the types offans discussed in this manual can handleresistances up to approximately 1 in. ofwater. Axial fans can have widely variedoperating characteristics depending on bladewidth and shape, number of blades andtip speed.

    The most common type of fan for air-cooledheat exchanger (ACHE) is less than 14 ft.diameter and has four blades. The mostcommon type for wet cooling towers is 28 ftdiameter and has eight blades. A typicalACHE fan is shown in Fig. 1.

  • Hudson Products Corp. Page 7 of 35 The Basics of Axial Flow Fans

    Fan Ring Diameter - Inside diameter of fanhousing at the plane of fan.

    First Mode Resonant Frequency -Frequency at which a blade freely vibrateswhen struck (natural frequency) in cycles/sec (Hertz).

    Forced Draft ACHE - Fan is located belowthe heat transfer surface forcing ambient airthrough the bundle.

    Harmonic Frequency - Integer multiples offan RPM and expressed as 1x, 2x and 3x fanspeed in cycles/second (Hertz). Harmonicfrequency is checked against resonantfrequencies to prevent vibration and fatigue.

    Induced Draft ACHE - Fan is located abovethe heat transfer surface drawing ambient airthrough the bundle. The fan is exposed tothe heated exhaust air.

    Leading Edge - Thicker portion of the air-foil that is the first part of the blade to meetthe air.

    Net Free Area - Net area at the plane of thefan through which all air must pass.Usually based on the nominal fan diameterminus seal disc area or hub diameter. Notethat blade area is not considered.

    Pitch Angle - Blade tip angle below thehorizontal required to do the design work andmove air upward. Hudson fans all rotateclockwise looking into the airflow.

    Resonant Frequency Safety Margin -Percent difference between the closestresonant frequencies of 1st mode resonantfrequency, blade and beam pass frequencies,and 1x Harmonics.

    SCFM - Airflow rate moved at standardconditions, in standard cubic feet per minute.

    Solidity Ratio - Measure of a fanspressure capability solidity sum of the tipwidths divided by the fan circumference.

    Stall Point - Fan operating condition wherethe boundary layer of air separates fromthe airfoil and causes turbulence. Thiscan be compared to boat propeller orpump cavitation.

    Standard Conditions - Resistancesrelated to the standard density of air at 0.075lbs/ft3, at 70F dry bulb temperature and sealevel (29.92 in. Hg).

    Static Efficiency - Fan efficiency based onstatic pressure and fan brake horsepower atthe same density.

    Static Pressure - Sum of all the system resis-tances against which the fan must work,expressed in inches of H2O. This is theuseful work required from the fan. (Velocitypressure excluded).

    Tip Clearance - Distance between the tipblade and the fan ring or housing, sometimesexpressed as a percent of the fan diameter.

    Tip Speed - Peripheral speed of the fan tipexpressed in feet per minute.

    Total Efficiency - Fan efficiency based on thetotal pressure and fan brake horsepower at thesame density for standard or actual conditions.

    Total Pressure - Sum of the static pressureand velocity pressures.

    Trailing Edge - Thinner portion of the air foil.

    Velocity Pressure - Parasitic loss caused bywork done to collect all the air into the fansinlet, expressed in in. of H2O. It is based onthe fans net free area at the plane of the fan.

  • Hudson Products Corp. Page 8 of 35 The Basics of Axial Flow Fans

    Velocity Recovery Stack - Devicefrequently used in cooling towers but rarelyin ACHEs. It captures the kinetic energy ofthe exit air velocity and converts it to usefulwork. It reduces air velocity and decreasesthe total pressure acting on the fan.

    WR2- Flywheel effect of fan that relates massmoment of inertia about the axis of rotation.in lb - ft2.

    2.1 Fan Engineering Units

    I-P: inch-pound U.S. systemmetric: metric systemSI: international system of units

    LENGTH

    I-P: feet (ft)metric: meter (m)SI: meter (m)

    VOLUME

    I-P: cubic feet per minute (CFM)metric: cubic meters per second (m3/s)

    cubic meters per hour (m3/h)SI: cubic liters per second (l3/s)

    PRESSURE

    I-P: inches of water (in. - H2O)metric: mm of water (mm - H2O)SI: Pascals (N/m2)

    DENSITY

    I-P: lbs per cubic ft (lb/ft3)metric: kilograms per cubic meter (kg/m3)SI: (kg/m3)

    Note standard density

    I-P = 0.075 lb/ft3metric = 1.201 kg/m3SI = 1.201 kg/m3

    ROTATIONAL SPEED

    I-P: revolutions per minute (RPM)metric: turns/minSI: turns/min

    TEMPERATURE

    I-P: degrees Farenheit (oF)metric: degrees Celsius (oC)SI: degrees Celsius (oC)

    AREA

    I-P: ft2metric: m2SI: m2

    POWER

    I-P: HP (horsepower)metric: kW (kilowatt)SI: kW

    (kilowatt)

  • Hudson Products Corp. Page 9 of 35 The Basics of Axial Flow Fans

    TIP SPEED

    I-P: ft/minmetric: m/sSI: m/s

    VIBRATION AMPLITUDE

    I-P: mils (1/1000 inches)metric: microns (1/1000 mm)SI: microns (1/1000 mm)

    VIBRATION FREQUENCY

    I-P cycles per minute (CPM)cycles per second (Hz)

    metric: cycles per second (Hz)SI: cycles per second (Hz)

    SOUND POWER LEVEL

    I-P: PWL dB (decibels)metric: Lw dB (decibels)SI: Lw dB (decibels)

    SOUND PRESSURE LEVEL

    I-P: SPL dB (decibels)metric: Lp dB (decibels)SI: Lp dB (decibels)

    2.2 Useful Conversion Factors

    AIRFLOW

    2118.64 * m3/s = ft3/min0.000 471 947 * ft3/min = m3/s

    PRESSURE

    25.40 * in.-H2O = mm- H2O

    249.08 * in.- H2O = Pa

    9.806 * mm-H2O = Pa

    Pascal (Pa) = N/m2

    VOLUME

    35.314 * m3 = ft30.02832 * ft3 = m3

    DENSITY

    Standard density = 0.075 lb/ft316.018 463 * lb/ft3 = kg/m3Standard density = 1.201 kg/m3

    LENGTH

    25.4 * inch = mm3.281 * m = ft1000 * mm = micron0.3048 * foot = m

    TEMPERATURE

    (oC * 1.8) + 32 = oF (oF - 32) / 1.8 =

    =

    oC

    POWER

    0.746 * HP = kW

  • Hudson Products Corp. Page 10 of 35 The Basics of Axial Flow Fans

    Selection is checked for the following:

    (a) Confirm that the operating point is notclose to a stall condition. (Explainedin detail later).

    Typically, a 2 pitch angle safetymargin is desired before reaching a stallpoint on the curve or overloading themotor. The American PetroleumInstitute has specific limitations thatmust be met for ACHE applications.

    (b) Confirm that the fan brake horsepower(BHP) is low enough that whenenvironmental, drive and motor lossesare added, the installed motor HP isnot exceeded.

    (c) Be sure that the horsepower per blademechanical limit (for Hudson fans) is notexceeded or select a fan with additionalblades.

    (d) Calculate the blade passing frequency,and compare it to the first moderesonance frequency for the selectedblade (for Hudson fans).

    (e) Repeat step (d) for the beam passingfrequency. (Most structures have fourmain beams.)

    (f) Repeat step (d) for 1x harmonic offan RPM, and compare to first moderesonant frequency.

    (g) Check resulting noise level against anynoise limit specifications. Noise levelis most often specified as soundpressure level (SPL) at a given distancefrom the tower or ACHE. Convert theSPL to a sound power level (PWL) toevaluate the selected fan. Some adjust-ments to tip speed and/or the number ofblades may be required.

    3.0 Fan Selection Criteria

    Many parameters are important in selectinga fan to meet the specified operating condi-tions such as:

    Fan diameter - to suit bay or cell size,

    Hudson blade type: H, HW, B,C, D, K,

    ACFM - Airflow required for design heattransfer duty,

    ASP - Actual static pressure from the sumof all resistances to airflow,

    Air temperature at plane of fan,

    Fan elevation above mean sea level orair density at fan, and

    Fan speed in either tip (FPM) or rotationalspeed (RPM).

    Also, a velocity recovery stack installed? Isthere a noise limitation? How much allow-able horsepower can the fan use? Will thefan avoid resonant frequency problems?

    In the most simple case, design airflow, staticpressure, and density are calculated for thefan curve conditions at 12,000 FPM tipspeed and standard density with no noiselimitations. The operating point is thenplotted on a fan curve of the appropriatediameter.

    The fan curve shows the correct pitch angleand horsepower required by the fan at thedesign point.

  • Hudson Products Corp. Page 11 of 35 The Basics of Axial Flow Fans

    ACFM = Actual ft3/min

    BHP =

    Note: 6356 is a constant relating to thepower required to move one CFM of airagainst a static pressure of one in.-H20 atstandard density using one horsepower.

    Brake HP is the net power absorbed bythe fan and does not include motor anddrive losses.

    Conversely:

    EffTOTAL =

    EffSTATIC =

    Note: Pressures and horsepower must be at the same density, either all

    standard or actual.

    Velocity (ft/min) =

    where NFA is the net free area of the fan

    Velocity Pressure = for std air

    AVP =

    where

    = density at the fan

    = std air density (0.075 lb/ft3)2

    1

    (h) Check air temperature at the fan. Doesit exceed maximum fan operating orstartup temperatures?

    If you have any questions, or require acopy of the Hudson Tuf-Lite FanRating Program or specificationcurves please contact the HudsonFan Sales department for assistance at1-800-634-9160.

    4.0 Basic Fan Equations - (I-P Units Only)

    For standard conditions (0.075 lbs/ft3density)

    TP = SP + VP TP = Total Pressure SP = Static Pressure VP = Velocity Pressure

    Normally, pressures are given at actualconditions (density) so the equation becomes:

    ATP = ASP + AVP also:

    TP = ATP * 1 / Density Ratio

    Density Ratio =

    SP = ASP * 1 / DR

    Note: Hudson fan curves are based onstandard conditions and 12,000 FPM tipspeed. If operating conditions are given inactual conditions, they must be convertedto standard conditions before referring to thefan curve to determine performance.

    () STD

    () ACT

    TPACT * ACFM

    6356 * EffTOTAL

    ACFM(ft3/min)NFA (ft2)

    V4005

    2

    V4005

    2

    TPACT * ACFM

    6356 * BHP

    SPACT * ACFM

    6356 * BHP

    2

    1

  • Hudson Products Corp. Page 12 of 35 The Basics of Axial Flow Fans

    5.0 Fan Performance Calculation

    Typical Fan Curve Fig. 2

    Manual fan selection procedure(See Fig. 2, Fan Curve).

    1. Define operating conditions

    Fan diameter

    Blade type: select Tuflite II, designatedby H after fan diameter.

    ACFM (Actual Cubic Feet per Minute)

    ASP (Actual Static Pressure)

    Air temperature at fan

    Elevation above MSL or

    Air Density

    RPM or tip speed

    Velocity recovery stack used? If so,height of the venturi section above thefan or fan exit diameter is required .

    Noise requirements will affect selection,and will be discussed later.

    Note: Velocity pressure (noted onHudsons fan curves) must bedetermined based on the fan used andrequired ACFM.

    Basic fan laws:

    CFM = fn(RPM)1Airflow varies in direct proportion toRPM

    SP or TP = fn(RPM)2Pressure capability varies with thesquare of a change in RPM

    HP = fn(RPM)3Power required varies with the cubeof a change in RPM.

    When velocity recovery stacks areused:

    VR = (VPfan - VPexit) * Recoveryefficiency

    Recovery efficiency is usually 0.6 - 0.8

    Use:VPfan - velocity pressure at plane of fan

    VPexit - velocity pressure at top of stack

    When velocity recovery stack is used,horsepower savings are calculated using:

    TPeff, act = TPact - VR

    Note: All pressures should be basedon the same density.

    Other noise related equations are foundin Section 9 (Fan Noise).

    Airflow (CFM)

    Tota

    l Pre

    ssur

    ein

    .-H2O

    Hor

    sepo

    wer

    PitchAngle Velocity

    Pressure

    TIP SPEED, 12,000 FPM DENSITY: 0.075 lb/ft3

    10

    6

    2

    10

    62

  • Hudson Products Corp. Page 13 of 35 The Basics of Axial Flow Fans

    9. Calculate total efficiency:

    EffTOTAL =

    Note: All values must be at the samedensity conditions. TPc and BHPstd areat standard density.

    Another formula for total efficiency is:

    EffTOTAL=

    10. Calculate static efficiency

    EffSTATIC = EffTOTAL *

    11. If a VR Stack is used:

    1. Calculate stack exit area . If notknown, assume 7 angle of sides andcalculate exit diameter and area. Useheight of venturi section above planeof fan.

    Calculate SF 2 and SF 3

    2. Calculate exit velocity pressure:

    VPex =

    3. Calculate VR assuming 70%recovery efficiencyVR = 0.7 *(VPfan - VPex ) in.-H20

    4. Calculate TPeff = (TPfan - VR)

    5. Recalculate BHP =

    Fig. 3 shows the HP saved by usingVR stacks. See Section 6.3 forexample calculations.

    2. Find density correction factor 1/DR

    3. Find velocity pressure (STD) fromappropriate fan curve or:

    VPstd =

    Velocity ressure line is shown at thebottom of the Hudson curves.

    4. Calculate standard total pressure:

    TPstd = ASP * (1/DR) + VPstd

    5. Calculate speed factor (SF) =

    Calculate SF 2 and SF 3

    Note: If fan is operating at 12,000 FPMtip speed, SF = 1 when using Hudsoncurves.

    6. Prepare to enter curve: c = curve cond.

    ACFMc = ACFMdesign * SFTPc = TPstd * SF 2

    7. Enter curve:

    Read up from ACFMc to TPc. Find pitchangle, and interpolate if necessary. Readup to design pitch angle on HP lines.Read left to design BHP (std).

    Note: To determine the fan operatingpoint, pitch angle and standard BHP mustbe found from curve.

    8. Calculate actual BHP:

    BHPact =

    ASPATP

    Curve RPMActual RPM

    V4005

    2

    BHPstd(1/DR) * SF 3

    TPact * ACFM6356 * BHPact

    TPc * ACFMc6356 * BHPstd

    *

    2 ACFMAreaexit * 4005

    PexitPstd

    TP * ACFM6356 * Eff

    eff

    TOTAL

  • Hudson Products Corp. Page 14 of 35 The Basics of Axial Flow Fans

    13. Calculate blade passing frequency (BPF):

    BPF = in Hz

    Hz = cycles/second

    Compare with 1st mode resonance for theblade being used. There should be a 5%margin of safety on either side of aresonant condition. If not, change thespeed or number of blades.

    14. Check horsepower per blade:

    HP/Blade =

    Refer to Hudsons Tuf-Lite FanSelection Program for maximum recom-mended HP/blade chart.

    6.0 Some Basic Assumptions

    Following are basic assumptions that can besafely used for fan selection if certain data isnot available.

    1. Typically for cooling towers or ACHEs,tip speed will be 14,000 FPM maximum.

    2. Typical blade quantities per fan are:

    up to 14 ft dia. 4 blades16 - 20 ft 6 blades24 - 30 ft 8 blades36 - 40 ft 8 blades

    3. Horsepower ranges:

    6-10 ft dia 7.5 - 15 HP12 ft 20 - 30 HP14 ft 30 - 60 HP16 - 20 ft 50 - 100 HP24 - 30 ft 100 - 250 HP36 - 40 ft 150 - 300 HP

    No. Blades * RPM60

    Approximate HP Savings with VR Fig. 3

    12. Check operating point on curve withproximity to stall. A stall point is wherethe curve changes inflection. (See Fig. 4below).

    Note: The Tuf-Lite program avoids allstall conditions.

    Stall Points on Fan Curve Fig. 4

    Allow a 2 pitch angle margin of safetybefore stall for a conservative fanoperating point.

    BHPact

    Stall Points

    0.4

    20

    16

    12

    8

    4

    00.1 0.2 0.3

    H

    P Sa

    ved

    (perce

    ntage

    )

    Velocity Pressure (in. of H20)

    No. Blades in fan

  • Hudson Products Corp. Page 15 of 35 The Basics of Axial Flow Fans

    Tip Vortex (Leakage) Fig. 5

    Exit air will be at a higher pressure thanincoming air due to the work expendedby the fan. Note that the blade performsmost of the work in the outer portion ofthe airfoil. If a leakage path (or clearance)exists, the air will seek the path of leastresistance and bypass the tip, causing avortex and loss of performance. Tipclearances can be reduced with Hudsonaccessories.

    Fig. 6 shows the API recommended tipclearances for smaller (16ft and less)diameter fans. Also included in thisfigure are the nominal tip clearances forlarger diameter fans.

    4. Temperatures at the fan (Farenheit):

    Forced draft air coolers 80- 100Induced draft air coolers 150 - 200Cooling towers 100, 100% RH

    5. Fan stacks:

    Assume 7 angle per side and 70% (0.7)recovery efficiency.

    6. Noise levels:

    @ 12,000 FPM 102 PWL dB(A)

    7. Typical Hudson fan:

    Total efficiency 75% minimum

    Static efficiency 55% minimum

    6.1 Effect of Tip Clearance

    Tip clearance between the blade andinside of the fan cylinder or fan ring iscritical to proper axial flow fan perfor-mance. Hudson fan curves are derivedfrom tests conducted at Texas A&MUniversitys Engineering Laboratory,based on very close tip clearances withoptimum inlet conditions. If close tipclearances are not maintained, a loss ofperformance will be noted, in pressurecapability and airflow. The primaryreason for close tip clearance is to mini-mize air loss or leakage around the tip,known as a tip vortex. (See Fig. 5).Hudson recommends the use of safetyfactors to correct for the environment inwhich a fan is placed.

    Fan Diameter Minimum Maximum

    3ft through 9ft 1/4 in. 1/2 in.>9ft through 11ft 1/4 in. 5/8 in.>11ft through 16ft 1/4 in. 3/4 in.18ft through 40ft 1/2 in. 1 in.

    Tip ClearanceFig. 6

  • Hudson Products Corp. Page 16 of 35 The Basics of Axial Flow Fans

    Airflow with Inlet Bell Fig. 8

    Note: Hudson Products Fin-FansAir-Cooled Heat Exchangers all haveinlet bells as standard equipment.

    Hudsons Tuf-Lite fan rating programallows several choices of inlet condi-tions: No inlet bell, elliptical inlet bell,rounded outlets with r = 0.05D, 0.1Dor 0.15D and conical inlets withr = 0.05D, 0.1D or 0.15D.

    \\

    6.3 Effect of Velocity Recovery Stacks

    The VR stack recovers wastedvelocity pressure energy at the top ofthe stack and converts it into usefulwork at the plane of the fan. Amountof recovery is based on the venturisection length and exit diameter.Hudsons Tuf-Lite program assumesa 7 included venturi angle and a 70%recovery efficiency. Fig. 9 shows atypical VR stack on a large coolingtower fan.

    Airflow with No Inlet Bell Fig. 7

    D

    r

    Vena Contracta

    6.2 Effect of Inlet Conditions

    Consider the air around the entrance tothe fan. In a re-entrant tube, like a fanring, air must be collected from all di-rections and accelerated to thevelocity at the plane of the fan. Someof this air is moving at 90 to the fanaxis. If a smooth transition is notpresent, the inability of the airflowvectors to make rapid changes indirection will create a VenaContracta at the blade tip, starving theblade of air in this area. (See Fig. 7)

    Since most of the work is done by theouter portion of the fan blade, theresult can be a loss of efficiency as highas 15-20%. An additional adverseeffect can be increased vibration.

    To prevent this loss, consider the useof an inlet bell attached to the bottomof the fan ring. A properly designedinlet bell provides a smooth transitionas the air is gathered from all directionsinto the plane of the fan as shown inFig. 8.

  • Hudson Products Corp. Page 17 of 35 The Basics of Axial Flow Fans

    Most large fans now incorporatevelocity recovery stacks because ofthese significant power savings.Fig. 10 illustrates the approximatepower costs for various motor sizesassuming 96% of the year in constantoperation.

    Approximate Cost of Power to Operate 8400 hrs/yr

    Fig. 10

    6.4 Effect of System Resistance

    Fan system resistance is defined asthe sum of the static pressure resis-tances of each element in the system,as a function of airflow. It is importantto be aware how system resistancechanges when a new fan operatingpoint is considered. The most commonexample is an airflow increase to anACHE to increase the equipments heattransfer capability.

    Restating the basic fan laws:

    1. Airflow is directly proportional to speed.

    2. Static pressure requirements vary in proportion to (airflow)2.

    Typical Large Cooling Tower Fan with VR Stack

    Fig. 9

    Consider the following fan:

    28 ft diameter, 8 blades, Type H14 ft stack, 9 ft venturi height1,180,000 ACFM0.38 in. - H20 ASP136 RPM105 F, at sea levelUse r = 0.10D inlet condition

    With no VR stack, fan performance is:

    137.7 BHP0.835 Total efficiency0.512 Static efficiency0.619 Total pressure actual

    With the VR stack:

    BHP = 123.60.840 Total efficiency0.571 Static efficiency0.559 Total pressure (actual)

    In this example the VR stack reducedrequired power by (137.7 - 123.6) =14.1 HP (10.5 kW). Operating 8400hrs/yr and assuming a power cost of$0.05/kW-hr, yearly savings are $4410per fan with the VR stack.

    0 20 40 60 80 100 120 140 Cost (Thousands of $)

    kW14913111293755637

    19

    HP200175150125100

    7550

    25 0

    .04 .06 .08 .10 $kW-HR

  • Hudson Products Corp. Page 18 of 35 The Basics of Axial Flow Fans

    Factors limiting use of the existing fancould be:

    (a) Fan stall(b) Allowable HP/blade

    If further duty increases were required,consider more blades per fan, adifferent (wider) blade type or higheroperating speed. In some cases wherehigher noise may not be objectionable,speeds up to 13,500 FPM have beenused for small fans . Increased noiseand vibration will always accompanyfan speed increase.

    Fig. 11 shows the typical systemresistance line for this example atincreased airflows.

    ASP vs. CFM for ACHE Fig. 11

    6.5 Effect of Horsepower

    Once the required fan horsepower(BHP) is determined, certain variablesincluding efficiencies and environ-mental factors, will determine the ratedor installed driver horsepower .

    60

    50

    40

    30

    20

    10

    00 5 10 15 20 25 30

    % Increase ACFM

    % In

    crea

    se in

    ASP

    1.8CFMCFM

    2

    1

    3. Horsepower requirements vary in proportion to (airflow)3.

    Therefore, a 10% increase in CFM re-quires a 33% increase in HP (1.33 xHP). Likewise, a 10% increase in CFMresults in a 21% increase in SP (1.21 xASP). (Note: Actual operating expe-riences have determined the relation-ship between SP and ACFM is moreaccurately predicted by an exponent of1.8 rather than 2.0 and is dependentupon the unit design).

    For ACHEs: SP2= SP1

    Consider a 25% increase in airflowrequired for a 14H - 4 fan currentlymoving 200,000 ACFM at 0.33 ASPwith a 20 HP motor. (Assume 0.075lbs/ft3 air density and 273 RPM).Hudsons Tuf-Lite program shows:

    17.1 BHP, 6.1 pitch

    A 25% increase in airflow yields250,000 ACFM. The new ASPincreases to 1.49x0.33 or 0.49 in. - H20.

    Results from the Tuf-Lite programshow a 14H - 4 fan is still a choice, but33.9 HP is now required to produce the250,000 ACFM. A 40 HP motorwould be required instead of theoriginal 20 HP.

    Note: American Petroleum Institute(API) guidelines allow up to 50 HPfor belt-driven ACHEs. It is notuncommon to increase blade count toeight blades and increase motor HPsignificantly to achieve increased air-flow. Larger motors, new drivesystems or structural modificationsmay be required to accommodate therequired airflow.

  • Hudson Products Corp. Page 19 of 35 The Basics of Axial Flow Fans

    The required electrical power for thisexample:

    = 69.6 * 0.746 = 51.9 kW

    6.6 Effect of Density

    Density, or weight of air per unitvolume, is affected by air temperatureand altitude at the plane of the fan.These are the inlet air conditions on aforced draft fan or the exit air condi-tions for an induced draft fan.

    A constant RPM, constant pitch fan isconsidered to be a constant volumemachine. That is, it will movea constant volumetric flow (ACFM) ofair regardless of the density.

    Consider a change in ambient tempera-ture for a forced draft fan. If thetemperature decreases, air density (lb/ft3) increases. Generally, resistance toairflow by the cooling tower fill orexchanger tubes (static pressure)increases, since the fan is moving thesame volume of heavier air therebyincreasing the required horsepower.

    The opposite occurs when ambienttemperature increases: Air densitydecreases, along with the static pres-sure and required horsepower staticpressure decreases, and the requiredhorsepower decreases. As stated,Hudsons fan curves show operation atstandard density of lb/ft3 at 70F andsea level.

    If a density table is not available, adensity ratio can be calculated as:

    Density Ratio = =

    1. Hudsons Tuf-Lite fan selectionprogram shows fan brake horse-power required for the selectedoperating point. Drive systeminefficiencies will result inan increased driver horsepowerrequirement.

    2. Environmental losses are moredifficult to determine but are a func-tion of actual fan tip clearance, faninlet conditions, number and size ofbeams under the fan and structuralgeometry. These losses must beaccounted for when determiningdriver power requirement.

    Example:For a given fan selection:Actual Fan Brake Horsepower = 62BHP (at the fan shaft)

    Example:Electric Motor Efficiency 95%

    Example:Drive System Efficiencies:Gear Boxes 98%V-Belts 95%Cog Belts 98%

    Example:Conservative Estimate ofEnvironmental Losses 97%

    Therefore if:HPin = Total Horsepower Required = Fan Horsepower Required

    Using a gear box drive:HPin = 62

    (0.95) (0.98) (0.97)

    = 69.6 HP

    Accounting for environmental losses.

    (Eff Motor) (Eff Drive) (Eff Environment)

    ACTSTD

    460 + 70F460 + T

    air

  • Hudson Products Corp. Page 20 of 35 The Basics of Axial Flow Fans

    Density ratio is the ratio of thelocal air density to standard density.

    If the fan plane is other than at sea level,then

    DR =

    For example, at 95F air temperatureand Pact = 14.6 psia, then

    DR = = 0.949

    6.7 Effect of Vibration

    All objects have a natural vibrationfrequency when struck sharply. Thisincludes fan blades, fan rings and thestructure. A component will generallyvibrate in a sinusoidal wave motion.Vibration frequency is the number ofcycles per second, also called Hertz.The distance a component moves pervibration cycle is called the amplitudeand is usually measured in mils (1/1000 of an in.) peak-to-peak. Peak-to-peak means the total amplitude onboth sides of the components still po-sition (plus and minus directions). Thismovement can also be characterized bythe components velocity given ininches per second.

    A fans environment continuallyinduces vibration. Each time a bladepasses near an obstruction, such as adrive shaft or structural support, bladeload fluctuates. Vibration level is afunction of the fans speed and number

    of blades. If the vibration is at the fansnatural frequency, amplitude and inter-nal stresses on the blade are greatlyincreased and can be destructive.

    Blades should be tested by themanufacturer to determine vibrationcharacteristics. Hudson checks allmodes of vibration from 0 - 50 Hertz(cycles/sec) for every fan blade type.A mode is the basic shape the bladeassumes during vibration. The 1stmode is the most significant with theblade assuming a flapping shape.The 2nd mode causes the blade tovibration in a lazy S shape with aneutral point in the middle. This neu-tral point is called a node. Therecan be more complex modes that theblade assumes as the frequenciesincrease from 3rd through nth mode.

    It is commonly thought that the mostcritical frequency is the blade passfrequency which is:

    BPF =

    We think of this as how the fan inter-acts with the structure. The criticalfrequency is the frequency at whichthe blade pass frequency coincides withthe blades 1st mode natural frequency.

    We believe that a more importantfrequency is the beam pass frequency.This is the number of obstructions orbeams one blade passes over perrevolution. For example, if there arefour beams in a fan turning 300 RPM,the beam pass frequency is:

    BPF = = 20Hz4 Beams * 00 RPM60

    3

    No.Blades * RPM60

    (4 )(460 + T )air

    60 70+

    ( )AtmPres(AtmPress)

    s act

    SL

    530555

    14 614 7

    .

    .

  • Hudson Products Corp. Page 21 of 35 The Basics of Axial Flow Fans

    Blade pass frequency problems can beexpensive, especially when due toresonance in a fan stack or structure.In some cases, it is necessary to addanother blade or change motor speedto move away from the problemfrequency.

    Some final comments about vibrationand resonance in fan blades:

    Operating at the resonant frequency ismuch more dangerous for metal bladesthan composite fiberglass blades, likeTuf-Lite or Tuf-Lite II, because of thelower fatigue strength of aluminum.Fiberglass blades also have a highdampening factor that helps to reduceblade vibration.

    Further, Tuf-Lite blade resonantfrequency peaks are typically verynarrow, so a 5% margin on either sideof resonance is adequate.

    API 661 Standard (Air-Cooled HeatExchangers for General RefineryServices) states: 6 mils peak-to-peakis the maximum allowable vibration onthe motor and primary supportingstructure. The Cooling TowerInstitute also publishes recommendedvibration limits.

    6.8 Effect of Number of Blades

    The greatest amount of work a fanperforms is done by the outer portionof the blade. Consequently, the fansolidity is critical. Solidity ratio isdefined as the ratio of the sum of theblade widths to the fans circumference.For example, consider a 14 ft 4-bladedfan with 13in. wide tips. The solidityratio is:

    Think of beam pass as how the struc-ture interacts with the fan blade.

    It is also very important to considerharmonics of the fan RPM.Harmonics are integer multiples of thefan speed. The 1st harmonic = 1 x RPM.

    In Hudsons Tuf-Lite fan ratingprogram, both blade pass and beampass frequencies are calculated andcompared to 1st mode fan resonance, aswell as the 1st harmonic assuming thenumber of beams are input. AFrequency Safety Margin iscalculated as the closest marginbetween any two of these frequencies.We recommend 5% as a minimumsafety margin for trouble-freeoperation.

    Consider not only vibration amplitudebut also frequency. Frequency tells youwhere the problem is most likelylocated. For instance:

    Fan unbalance occurs at fan speed(once per revolution).

    Vibration at blade pass frequencyis usually due to aerodynamicproblems such as air moving overobstructions, beams or blockedinlets. It could mean a resonancein the structure or fan stack trig-gered by the blade pass frequency.

    Vibration at motor speed couldmean a misaligned coupling,sheave, or drive shaft.

    Fan unbalance can be corrected in thefield. Field dynamic balancing takesinto account the mass or rigidity of themount and the sheave balance.

  • Hudson Products Corp. Page 22 of 35 The Basics of Axial Flow Fans

    SR = = 0.10

    If we increased the number of bladesto 6, the solidity ratio would be 6/4 x0.1 or 0.15. Likewise, for 8 blades,SR would be 0.2. So theoretically atleast, 6-blades would do 50% morework than 4 blades, and 8 blades woulddo 100% more work. In reality a 6blade fan only does about 40% morework than a 4-bladed fan; however, theprincipal is that: the work a fan canprovide is proportional to the numberor width of blades. Likewise, 4 wideblades can do more work than 4narrow blades by the ratio of the bladewidths even if the blade shapes arenot similar.

    6.9 Effect of Blade Shape

    Airflow across the plane of the fan isnot uniform varying from positive atthe tip to negative at the center of thefan. Blade shape and twist of the air-foil along the blade affects the shapeof the velocity profile.

    Velocity profile of a well-designedtapered blade with a generous twistcompared to a constant chord bladewith minimal twist is shown in Fig. 12.

    Work preformed by a fan blade is basi-cally a function of three factors at anypoint or radius:

    Chord width

    Airfoil twist

    Tangential velocity squared

    At mid radius (0.25D), tangentialvelocity is only 25% of the velocity atthe tip. To compensate for thisdecrease in velocity, the chord widthand twist must be increased. This isthe reason for the increased efficiencyand more uniform airflow from atapered blade. Note that for a constantchord width blade, exit velocitydecreases rapidly inboard of the tip andtypically becomes negative outboardof the seal disc. A typical aluminumblades chord width and twist do notvary along the blade.

    The advantages of a tapered, well-designed blade with even airflow acrossthe fan result in higher efficiencies andlower horsepower to attain designperformance.

    Velocity Profiles-Tapered vs.Constant Chord Blade

    Fig. 12

    12 pi 144 13 Tapered Chord Fan

    High Efficiency Velocity Profiles

    Seal Disc

    Straight Chord FanPoor Efficiency

    StraightChord Fan

    TaperedChord Fan

    PositiveFlow

    NegativeFlow

  • Hudson Products Corp. Page 23 of 35 The Basics of Axial Flow Fans

    7.0 Variable Airflow Fans (Auto-Variable)

    Variable-pitch or Auto-Variable fans auto-matically adjust the pitch angle to providethe precise amount of airflow for controllingprocess temperature while saving substantialamounts of energy. This section discussesbasic operating characteristics, processtemperature control methods, energy savingsand economic comparisons with other axialfan airflow control systems.

    Variable-pitch applications are typically10 -14 ft (3.04 - 4.3m) in diameter consum-ing up to 40 horsepower (30 kW). Fig. 14shows the typical type actuator system foundin ACHEs. Fig. 15 shows the invertedactuator system popular in Europe for theease of access to the actuator.

    Typical Auto-Variable FanFig. 14

    Inverted Actuator-Variable-Pitch FanFig. 15

    6.10 Effect of Seal Disc

    Note that the airflow direction becomesnegative near the center of the fan. Thisis the result of the torque applied to thefan which creates a swirleffect on the air vectors. Air at the tipsis axial or parallel to the fan axis.Toward the fans center, air velocitydecreases by the square of the radiusand the air vectors lean further towardthe horizontal. At or before the centerof the fan, the air is actually movingopposite to the airflow at the blade tips.A well-designed fan will have a centerseal disc of about 25% of the fansdiameter. Referring to Fig. 12, note thatthe air vectors at the center of the fanactually turn to a negative direction.Tests have shown that the seal disc pre-vents this negative airflow andimproves fan efficiency by about4 - 5%. The seal disc can be as large as14 ft in diameter for 40 ft fans. Fig. 13shows a typical seal disc.

    Typical Seal Disc Prior to Installation

    Fig. 13

  • Hudson Products Corp. Page 24 of 35 The Basics of Axial Flow Fans

    Operating and Control Characteristics:

    Variable-pitch fan actuators used in ACHEscan be described in general terms as verysimilar to diaphragm-operated, spring-returnvalves. Instead of moving a valve stem upand down, the actuator controls fan bladepitch. A force diagram is shown in Fig. 16.

    AV Force DiagramFig. 16

    As the blade moves the air, the aerodynamicmoment acts to turn the blade to a lower pitch.The hub spring creates an opposing momentto hold the blade in position. This is afail-safe mechanism. If air pressure on thediaphragm fails, the fan operates as a fixed-pitch fan providing the maximum designairflow. Variable-pitch hubs can be config-ured to fail to the maximum or minimumpitch setting.

    To reduce airflow, or even reverse airflowdirection, air pressure is exerted on thediaphragm to oppose the hub spring anddecrease the blade pitch.

    When the blade pitch is about minus 10, nowork is done and essentially zero flow isattained. The minimum air velocity obtain-able is approximately 50-100 fpm (0.37 - 0.51m/s). If the hub has the pitch stops adjustedfor reverse flow, air is directed downward andcan be as much as 60% of the positive pitchairflow at the same horsepower.

    A typical variable-pitch hub requires a 3 - 15psi (21-103 kPa) control signal and operatesthe blades from the maximum design pitchback down to zero airflow. Most hubs arecapable of 45 total pitch travel and performas shown in Fig. 17.

    Airflow vs. Signal for Variable-Pitch Hub Fig. 17

    Typical Components:

    A typical variable-pitch fan hub mechanismis shown in Fig. 18. The basic componentsare:

    Hub spring

    Diaphragm

    Piston

    Blade shafts with eccentric actuator

    Rotary air joint

    Valve positioner

    Airflow Aero Moment

    Rotation

    ForceDiaphragm

    ForceSpring

    Air

    flow

    & H

    orse

    pow

    er (p

    erce

    nt) 140

    120

    100

    80

    60

    40

    20

    0

    -20

    -40

    -60

    Airflow

    Horsepower

    Rated hp

    Signal-(psi)

    Neg

    ativ

    e

  • Hudson Products Corp. Page 25 of 35 The Basics of Axial Flow Fans

    The advantage of the valve positioner is itprovides precise airflow control due to bladepitch position feedback and the ability tooutput high pressure on the diaphragm toquickly change pitch angle.

    If airflow control is not critical, an open-loop system can be used operating on the3-15 psi (21-103 kPa) signal alone. Thissystem excludes blade position feedback tothe controller and is useful in non-critical installations where the fan system willoperate on 15 psi (103 kPa) diaphragmpressure. Operation with only 3-15 psi isgenerally limited to small fans.

    Process Control:

    There are several methods used to controlprocess temperature in an air-cooled heatexchanger:

    Fluid bypass On-off fan operation Two-speed fans Louvers Variable speed fans Variable pitch fans

    The oldest control method bypasses aportion of the process stream around theair cooler.

    On-off fan control is simple and often usedif there are a large number of fans in anidentical service. However, this non-modulating control method can causeproblems in air-cooled condensers such aswater hammer, freezing tube-to-headerleakage, or tube buckling due to differentialthermal expansion of bundles in parallel.Differential tube expansion can cause tubebuckling. Cooling tower fans are a good ex-ample of incremental on-off fan control.

    Typical Auto-Variable Hub Fig. 18

    The blade shafts or axles hold the fan bladeand have an eccentric bearing on the inboardend. These eccentric bearings engage agroove in the piston. As the piston moves upor down, a twisting motion is imparted to theblades, changing the pitch. The rotary airjoint is the static/dynamic interface betweenthe rotating fan and the control air system.

    Control Methods:

    The valve positioner is a closed-loopfeedback device that receives the control sig-nal, (usually 3 - 15 psi) and supplypressure up to 100 psi (689 kPa). Valvepositioners are used when airflow is critical,such as in ACHE condensing application.

    Rotary Air Joint

    Valve Positioner

    Hub SpringLow Pitch LimitStop NutsHigh PitchLimit Stops

    Upper Piston

    Lower Piston Blade Shaft

    Blade Attachment

    Diaphragm

  • Hudson Products Corp. Page 26 of 35 The Basics of Axial Flow Fans

    Two-speed fans are a further refinementgiving 0, 67, or 100% of design airflow ratewith 1800/1200 rpm motors. Naturally,additional motors increase the degrees of air-flow control.

    Louvers are the first step to modulatedairflow; however, fan horsepower is wastedas airflow is throttled by the louver. Atcomplete shut off, the fan stalls and horse-power actually increases.

    Variable-speed fans for fully modulatedairflow are available in two types: hydrau-lic and electric drive. Either type conservesenergy and offers good airflow control. Thelatest development in electrical variable-speed control for fans is the variable-frequency drive (VFD). There are three ba-sic types: VVI (Variable Voltage Inverter),PWM (Pulse Width Modulation) and CS(Current Source). These drives utilize astandard induction motor and automaticcontrol is obtained by a process controldevice to interface the 4 - 20 milliamperetemperature controller output with the VFD.

    The older less common hydraulic drivesystem consists of a motor/variable volumepump/reservoir unit connected to a slow-speed, high-torque, direct-drive motor.Advantages are variable fan speed andeliminating a reduction belt or gear drive.The main disadvantage is inferior systemdrive efficiency. Efficiencies are approxi-mately: motor 0.97, pump 0.92 andhydraulic motor 0.92. Therefore, theoptimum drive system efficiency is(0.97)*(0.92)*(0.92) = 0.82, not countinghydraulic line loses. This must be comparedto a typical motor/belt drive efficiency of0.95 or 0.97 with a gear or timing belts.

    Advantages of VFDs are reduced noise andvibration during slow-speed operation.Disadvantages are high cost per horsepowerfor control of a small number of fans in the

    same service and total loss of service if amultiple fan VFD controller fails. Both hy-draulic and VFD systems can be designed tooperate in reverse airflow to negate the ef-fects of natural draft.

    The variable pitch fan can also provide from0 - 100% positive or from 0 - 60% negativeairflow at the same horsepower. Negativeairflow is useful, along with louvers, inwinterized ACHEs to seal off freezing out-side air and recirculate warm air inside theplenum chambers. Internal recirculationsystems utilize a positive and negativeairflow pair of fans to recirculate warm air.

    Power Consumption and Cost Comparison:

    When evaluating power consumed by anyaxial fan operating at a fixed pitch, considernot only the fan performance curve but thesystem resistance characteristics as well.

    Fan performance curves are obtained in awind tunnel with a means of varying theresistance or static pressure head againstwhich the fan must work, and measuringresulting airflow and horsepower.

    System losses are more difficult to determine,and judgement is necessary in many casesto evaluate the losses due to poor inletconditions, excessive tip clearance andunusual structural conditions. If a coolingservice is critical, it may be wise to modelthe unit and establish the system losses in awind tunnel. What must be determined isthe sum of the static pressure resistancesversus system airflow. Since the fans air de-livery characteristics have been accurately es-tablished, the operating point for anyairflow requirement can be predicted. Thisoperating point is where the fan output interms of pressure and flow, exactly meetsystem requirements and is referred to as theequilibrium point of operation.

  • Hudson Products Corp. Page 27 of 35 The Basics of Axial Flow Fans

    Lets examine a typical case of an ACHE with afixed-pitch fan and a louver for throttling theairflow at the design point and several otherreduced airflow operating points.

    For example, consider a 14 ft diameter fan op-erating at a 14 design pitch at point 1 (Fig.19). The system resistance line, shown as thedashed line, is the locus of pointsobtained by summing the static and velocitypressure losses vs. flow through the bundle. Thepitch angle line for 14 represents the fansdelivery characteristics. Assume densityremains constant and the decreased airflow is aresult of a reduction in required airflow.

    If the louver throttles airflow to control theoutlet temperature, the points shown as 1, 21,31 and 41 in Fig. 19 are total pressure outputand horsepower consumed by the fixed-pitchfan. If we were controlling airflow with avariable-pitch fan instead of a throttlingdevice, total pressure output would exactlymatch the system resistance line as shown atpoints 2, 3 and 4, and the horsepower require-ments are significantly reduced. In this case,the variable-pitch fan used 26, 51, and 73%of the horsepower required by the fixed-pitchfan at points, 21, 31 and 41 respectively.

    Throttled Flow Through FanFig. 19

    Energy Comparison:

    A typical case study to evaluate costdifferentials between fixed-pitch (single-ordual-speed) or variable-pitch fans forair-cooled heat exchangers is conductedas follows:

    Step 1. Thermal studies are neededto determine total airflow requiredas a function of ambient tempera-ture for the particular application.Plot flow versus temperature.

    Step 2. Obtain climatological data for thearea where the air cooler will belocated, and derive a table ofdegree-hours for incrementaltemperature ranges. This tabulatesthe number of hours per year thateach temperature range occurs.

    Step 3. For a fixed-pitch fan, flow is adirect function of speed. Create aplot of fan output versus ambienttemperature for each case to bestudied. This yields HP-hours pertemperature range.

    Once the airflow is defined for each range,fan horsepower for any point can be approxi-mated by the following relation:

    Where: = 2.8

    = Horsepower at cfm1

    = Density at point 1 lb/ ft 3

    = ft 3/min flow at point 1

    = Design horsepower

    = Design density

    Tota

    l Pre

    ssu

    re, IN

    .-H2O

    Hor

    sepo

    wer

    Fixed-Pitch HP

    Variable-Pitch HP

    SystemResistanceLine

    60

    40

    20

    1.2

    1.0

    .8

    .6

    .4

    .2

    41 31 21 1

    3

    4

    41 31 21

    1

    4

    3

    2

    2

    2 610

    14

    150 175 200 225 250 275 300 325

    Flow (Thousands of CFM)

    HP11

    HPdes

    cfmcfm

    1

    des

    1

    des

    HP1 HPdes

    des

    cfm1

  • Hudson Products Corp. Page 28 of 35 The Basics of Axial Flow Fans

    See Fig. 20 for a plot of air delivery vs. am-bient temperature.

    Air Delivery vs. TemperatureFig. 20

    Fig. 21 gives the power study results whichshow that the variable-pitch fan would payfor itself within two years. In this particularapplication, the two-speed motor in Case 2made only a small difference in energy cost.

    Power Study ResultsFig. 21

    Step 4. Using HP-hours for each tempera-ture range, tabulate the total for theyear. The power required is kW =HP (0.746). Arrive at an energycost per year for each scheme.

    This is a very simple approach but a useful tool.As an example, consider the following:

    A 20 ft x 36 ft (6 m x 11 m), four-row, forceddraft, air-cooled heat exchanger with two 14ft (4.3 m) fans each having 40 HP (30 kW)motors.

    The unit is a propane condenser, Item 126Cto be located in West Virginia, close toCharleston. Power cost is $0.035/kW-hr.

    Study power and initial investment costs forone year for three schemes:

    1. Two fixed-pitch fans.

    2. Same, but with one 1800/900 RPM motor.

    3. One fixed-, one variable-pitch fan (single- speed).

    Design Conditions (per fan):

    Flow 224,613 ACFM (106 m3/s)

    Power 29.0 HP (21.6 kW)

    Temperature 45F (7C)

    Elevation 350 ft (107 m)

    Ambient Temperature F

    Propane Desuperheater and Condenser

    Tota

    l Airf

    low

    Req

    d.(T

    hous

    ands

    of ft3

    / m

    in)

    500

    400

    300

    200

    100

    0100 90 80 70 60 50 40 30 20

    Des. Point 2 Fixed-Pitch On

    2 Fixed-Pitch On(1-1/2 Speed)

    1 Fixed-Pitch OnFixed-Pitch 1/2 Speed

    Both Fixed-Pitched Off

    Variable-Pitchat Zero Flow

    Variable-PitchAirflow

    Design AirflowRequired

    Estimated TotalkW-hr/yr

    EnergyCost/yr

    $.035/kW-hr

    Case 1 162,6702 Fixed-Pitch

    Case 2 142,0802 Fixed-Pitch1-1/2 SP (Manual)

    Case 3 70,8871 Fixed-Pitch1 Variable-Pitch

    $5,693

    $4,973

    $2,481

    FirstCosts

    Base

    +$1,000

    +$3,715(a)

    (a) Includes temperature controller, variable-pitch costadder plus estimated $1,500 installation.

  • Hudson Products Corp. Page 29 of 35 The Basics of Axial Flow Fans

    There is a slight advantage in controlling flowby varying speed rather than adjusting bladepitch angle, since efficiency of a variable-pitchfan declines with decreasing pitch angle.

    In both cases, power consumption dropsdramatically. Power savings of 50%/yr or morecan be realized by replacing a fixed-pitch,continuously operating fan with one whereblade pitch or speed is varied automatically.

    9.0 Noise Considerations

    Fan noise can be elusive requiring sophisti-cated equipment to measure accurately. Fannoise control must begin at the air-cooled heatexchanger or cooling tower design stage.Noise control as an after thought, can resultin a very costly fan and drive componentretrofit , and possible addition of heattransfer surface or acoustic barriers.

    Noise is a function of fan tip speed. In aclassic paper (ASME 72-WA/FE-42)Hopper and Seebold suggest that the broadband noise varies approximately with the 5.6power of tip speed, and directly with bladeloading. The minimum operating speed thatprovides effective airflow is a function of thefans pressure capability.

    Since noise (Sound Pressure Level) is afunction of the 5.6 power of tip speed,slowing fan rotation can reduce noise.

    Unfortunately, a fans pressure capabilitydecreases with the square of the speed.Therefore, the fans speed pressurecapability must increase to maintain therequired airflow.

    To increase the pressure capability of a fan,the fans solidity ratio must be increased,by adding more blades, or using blades witha wider chord, such as Hudsons low-noiseblade design. Unfortunately, increasing thenumber of blades can reduce fan efficiency.

    8.0 Variable-pitch vs. Variable-Speed

    The choice between a variable-pitch andvariable-speed fan depends on factors suchas: (1) Initial costs and payback period,(2) availability of suitable fans, and (3) thenumber of fans performing the same duty.

    Payback period is calculated from powersavings that depend on the degree days atthe site, power cost, required airflow vs. am-bient temperature and installation cost. The$/HP cost of a variable-speed drive drops sig-nificantly for larger units.

    For heat transfer purposes, an even airflowacross a bundle is desirable, so the maximumnumber of fans should be operated by a singlelarge controller. Variable-speed drives canexceed 1,000 HP.

    A study by the U.S. Department of Energyof a typical cooling tower in Houston, Texas,operating with 100 million Btu/hr heat loadand a 110-95F cooling water range, revealedthe following relative power consumptions:

    No control, full speed 100% of base

    Single-speed, automatic on/off 65% of base

    Two-speed, automatic on/off 59% of base

    Automatic variable-pitch fan 50% of base

    The tower was equipped with four fans, eachrun by a 25 HP motor. The results typify thepower savings possible in Houston, whereannual dry-bulb temperatures vary from 30Fto more 100F.

    If airflow were controlled with a fixed-pitchfan and a variable-speed drive, rather thanby a variable-pitch fan, results would besimilar. Speed changing saves power becausehorsepower consumption is a cubic functionof airflow, i.e., HP2 = HP1 (CFM2CFM1)3.

  • Hudson Products Corp. Page 30 of 35 The Basics of Axial Flow Fans

    Noise requirements are often more restric-tive at night. If this is a consideration,slowing the fan as ambient temperature dropsusing a variable-speed drive can be onesolution to reducing noise. As the nighttimeambient temperature drops, required airflowis reduced, therefore fan speed may be slowedto lower noise levels.

    9.1 Noise-Related Nomenclature

    Decibel: A number representing relativesound intensity expressed with respect toa reference pressure or power level. Theusual reference for sound pressure levelis of 20 micro newtons per square meter(20 N/m2). A decibel is a logarithm(base 10) of a ratio of the power valuesabbreviated dB.

    Frequency: Sound vibration rate persecond in Hertz (cycles per second).

    Low-Noise Fans: A fan able to operateat low speed due to its high-pressurecapability. Fan pressure capability is afunction of its solidity ratio. Therefore,a low-noise fan will generally have moreor wider blades than would be requiredif the fan operated at normal tip speeds.

    Octave Bands: Noise is categorized bydividing it into separate frequency bandsof octaves or 1/3 octaves. Generally, weuse 63, 125, 250, 500, 1K, 2K, 4K and8K center frequencies to define thesebands in Hertz (cycles/sec).

    Sound Power Level: Acoustical power(energy) can be expressed logarithmicallyin decibels with respect to a referencepower, usually 10-12 watts. The relation-ship is given as: Sound Power LevelPWL = 10 log .

    Sound power level cannot be measureddirectly but must be calculated fromsound pressure levels (SPL) dB. In met-ric terms, this is known as Lw.

    Sound Pressure Level: Known as SPL,or Lp in metric terminology, is theaudible noise given in decibels thatrelates to intensity at a point somedistance from the noise source. It can berelated to octave bands or as an overallweighted level dB(A).

    Weighted Sound Levels: This relatesthe decibel (loudness) to a frequency.Ears can easily pick up high-frequencynoises (both intensity and direction) butare relatively insensitive to low-frequency noise. For a stereo systemhigh-frequency speakers must be verycarefully located in a room for bestresults but low-frequency bass speakerscan be placed anywhere, even out of sight.

    There are three basic weighting systems:A, B and C. The A system, dB(A),most closely relates to our ear, the Bsystem, dB(B), has some specific usesand the C system, dB(C), is consideredunweighted.

    Weighted Sound Levels Fig. 22

    C

    A

    B and C

    B

    A

    Frequency Responses forWeighting Characteristics

    Frequency (Cycles Per Second)

    Rel

    ativ

    e Re

    spon

    se (D

    ecibe

    ls)

    +5 0-5-10-15-20-25-30-35-40-45-50

    20,00

    0

    10,00

    0

    5000

    2000

    1000500

    200

    1005020

    Wwatts10 12

  • Hudson Products Corp. Page 31 of 35 The Basics of Axial Flow Fans

    The dB(A) is the most common weight-ing system. It expresses sound levels witha single number instead of having tospecify the noise of each octave band.

    Note that the sound range of ACHEs (atclose range) is typically between 80 and105 dB(A).

    9.2 Allowable Fan Noise

    To establish noise limitations, decide onthe maximum allowable noise from theACHE or cooling tower.

    9.2.1 ACHE Noise

    If the concern is for overall plant noise orthe noise exposure of plant workers in thevicinity of the fans, a different type ofspecification must be used.

    Overall, noise limitations from an ACHEare typically a sound power level (PWL)specification for each bay. This limits thecontribution of each bay (typically twofans) to the plant noise as a whole. Thisis usually needed where noise at the plantboundary is considered. Contributions ofeach part of the plant must be carefullycontrolled if overall plant noise is limited.PWLs can be expressed as weighted leveldB(A) or sometimes even by limitationson each octave band.

    If worker protection is the main concern,a limitation of sound pressure level at 3ftor 1m below the bundle will probably beimposed as SPL dB(A) at 3 ft. TheOSHA limitation is 90 dB(A) for eight-hour exposure, but 85 dB(A) down to 80dB(A) is becoming more common.

    9.2.2 Cooling Tower Noise

    The primary difference between coolingtower and ACHE noise is falling waternoise in a cooling tower at grade eleva-tion, which also affects noise levels at theplant boundary. Motor and gear noisemust also be considered.

    Fan designers normally do not includethese factors when establishing fan noise.Cooling tower manufacturers will com-bine the contribution from all noisesources when determining theoverall rating of a tower design.

    9.3 Predicting Fan Noise

    Each manufacturer has proprietary equa-tions for predicting fan noise. API Guide-lines use the general formula:

    PWL = 56 + 30 log + log HP

    This calculates PWL as dB(A)

    Hudsons proprietary noise equations(used in the Tuf-Lite program) are basedon actual tests at various speeds andoperating conditions considering thefollowing effects:

    Fan diameter Fan tip speed Blade Type Blade pitch angle Inlet conditions Horsepower

    TipSpeed1000

  • Hudson Products Corp. Page 32 of 35 The Basics of Axial Flow Fans

    Note: Logs are common logs (base 10).

    For example:

    14 ft fan237 RPM (10, 424 FPM tip speed)25.1 HP

    Find sound power level

    PWL = 56 + 30 log 10.4 + 10 log 25.1 = 100.5 dB(A)

    Fan Noise Profile

    It is valuable to consider the noise pro-file of typical Hudson fans. Consider thefan from the previous example with aPWL of 100.5 dB(A). The profile indecibels would be constructed as:

    From testing the noise of numerous fanconfigurations, Hudson knows that fannoise is predominant in the 63-250 Hzbands and mechanical noise dominatesfrom 500 to approximately 2K Hz.Mechanical noise is generated by thedrive systems, motors, bearings andinduced vibrations.

    Some Important Concepts

    When considering multiple noise sources (fans) use the relation:

    PWLN = PWL + 10 log N

    The sound power level for 2 adjacentfans is the PWL of one fan plus 10 log2 or PWL2 = PWL + 3.

    A doubling of the noise source adds 3 dB.

    Noise attenuates with distance bythe equation:

    SPL (at distance R) = PWL - 20 log R

    Where R is in feet from the center ofthe source. Measure R as a line ofsight distance.

    Consider the noise an observer at gradehears at 50 ft from an operating ACHEwith the fan on where the line-of-sightdistance from grade to the center of thefan is actually 62 ft. Remember what theear hears is SPL, the noise energy isPWL. Assume PWL = 100.5 dB(A).

    SPL = 100.5 - 20 log 62 = 64.7 dB(A)

    This also assumes background noise isat least 10 dB quieter.

    Note: If both fans were running, the SPLwould have been 67.7 dB(A).

    Noise at 3 ft Beneath the Unit

    When considering the noise at 3 ftbeneath the unit, the drive system andmotor noise become dominant at lowertip speeds.

    Factors that influence this noise are:

    Motor noise Belt or gear noise Bearing noise Reflected noise from supports Background noise

    Gear noise is especially significant in aforced draft unit.

  • Hudson Products Corp. Page 33 of 35 The Basics of Axial Flow Fans

    point (described in API 631 M) with thefan on and off so that background noisecan be determined. After all data is taken,a standard procedure calculates basic fannoise energy, which is the PWL (SoundPower Level). dB(A) and each octaveband noise are measured.

    This type of test is performed when thenoise contribution from the entire bankof ACHEs is required for plant noisecalculation.

    For cooling towers, noise specificationsare generally concerned with the SPL inthe vicinity of the fan stack or at somepoint distant from the tower itself. Thesetests can be done if background noise isless than 3 dB of the specified level. ForSPLs near the stack, water noise isgenerally not a concern. For distant tests,falling water noise is a major concernbeyond the scope of the fan manufacturer.For cooling tower noise tests, gear andwater noise is not included in the fanmanufacturers fan noise estimate.

    9.4 Noise Testing

    Frequently, the ACHE must be tested forconfirmation that its noise does notexceed specifications imposed by thepurchaser. There are two basic typesof tests normally performed beforeshipment:

    a) Measure SPL dB(A) (Sound PressureLevel) at 3 ft. below the bundle orfan guard - depending on whetherthe unit is induced or forced draft.

    b) Measure PWL (Sound Power Level)using hemispherical power leveltest. PWL is specified as either adB(A) weighted value or by octavebands.

    The SPL at 3 ft test is by far the mostcommon and least expensive. Usually,only one or two measurements arerequired. The answer is immediate andread directly from the noise meter.

    The hemispherical test is far morecomplicated and expensive. Severalhours, many technicians and a large craneare required to perform this test. Fulldetails of the test are given in APIRecommended Practice 631 M, issued inJune, 1981. The test consists of measur-ing SPL at 9 points on the surface of animaginary 10 m radius hemisphere and 4points on an imaginary 10 m radiuscylinder. The cylinder height is fromground level to the geometrical center ofthe ACHE. Since the unit is typicallymounted on beams 8-10 ft. off the ground,the geometrical center falls 12-15 ft offgrade. The crane is required to transportthe technicians and noise meter to reachthe top points of the hemisphere. Thetest consists of measuring noise at each

  • Hudson Products Corp. Page 34 of 35 The Basics of Axial Flow Fans

    REFERENCES:

    Monroe, Robert, CTI Paper TP74-03, Cooling Tower Fans - Today and Tomorrow, Jan. 1974

    Monroe, Robert, CTI Paper TP97-12, Maximizing Fan Performance,Feb. 1997

    API Standard 661, Fourth Edition, Air-Cooled Heat Exchangers for General RefineryServices, Nov. 1997

    API Standard 631M, First Edition, Measurement of Noise from Air-Cooled HeatExchangers, June 1981

    DEDICATION

    The Basics of Axial Flow Fans is a compilation of work performed by many HudsonProducts engineers and employees. However, one individual deserves special recognition.

    Mr. Robert C. Monroe, who worked tirelessly for Hudson from January 28, 1967 to hisretirement on August 1, 1997, was not only a major contributor to the contents of this book butalso to the success of Hudson Products Corporation in manufacturing quality fiberglass-reinforced, plastic fan blades. Bobs expertise, vision and hard work wereinstrumental in Hudsons development of the Tuf-Liteand Tuf-Lite II families of superiorfan blades.

    The Basics of Axial Flow Fans is dedicated to the memory of Mr. Monroe who passed away onMay 31, 1998.

  • Hudson Products Corp. Page 35 of 35 The Basics of Axial Flow Fans

    a McDermott company

    Hudson Products Corporation manufactures

    Auto-Variable fan hubsCombin-Airewater- and air-cooled heat exchangersExact-A-Pitch digital protractor for setting fan pitch anglesFin-Fan air-cooled heat exchangersHeatflo heat pipe air heatersHy-Fin finned tubesSolo Aire air-cooled heat exchangersSplit-Flo compact gas and liquid separatorStac-Flo and Steamflo air-cooled steam condensersThermflo process heatersTuf-Edge erosion resistant leading edge protectionTuf-Lite and Tuf-Lite II fan blades

    6464 Savoy Drive, Suite 800Houston, Texas 77036-3321Post Office Box 36100Houston, Texas 77236-6100Phone: (713) 914-5700Fax: (713) 914-59921-800-634-9160 (24 Hours)Email: [email protected] Home Page Address:http://www.hudsonproducts.com

    Hudson, Auto-Variable, Combin-Aire, Exact-A-Pitch, Fin-Fan, Heatflo, Hy-Fin, Solo Aire, Split-Flo, Stac-Flo, Steamflo, Thermflo, Tuf-Edge, Tuf-Liteand Tuf-Lite II are registered trademarks of Hudson Products Corporation.

    2000 McDermott Incorporated. All Rights Reserved. M0100-186 5M W1/00

    FOREWORDNOMENCLATURE1.0 Definition of Axial Fans2.0 Fan Engineering Nomenclature2.1 Fan Engineering Units2.2 Useful Conversion Factors

    3.0 Fan Selection Criteria4.0 Basic Fan Equations - (I-P Units Only)5.0 Fan Performance Calculation6.0 Some Basic Assumptions6.1 Effect of Tip Clearance6.2 Effect of Inlet Conditions6.3 Effect of Velocity Recovery Stacks6.4 Effect of System Resistance6.5 Effect of Horsepower6.6 Effect of Density6.7 Effect of Vibration6.8 Effect of Number of Blades6.9 Effect of Blade Shape6.10 Effect of Seal Disc

    7.0 Variable Airflow Fans (Auto-Variable)8.0 Variable-pitch vs. Variable-Speed9.0 Noise Considerations9.1 Noise-Related Nomenclature9.2 Allowable Fan Noise9.2.1 ACHE Noise9.2.2 Cooling Tower Noise

    9.3 Predicting Fan Noise9.4 Noise Testing

    REFERENCES: