flow apparatus

Upload: oshane-thomas

Post on 14-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 flow apparatus

    1/22

    Introduction:

    Throughout the experiment, the three apparatus being studied are the Venturi, Orifice and

    Rotameter. The venturi meter (Diagram 2) through using differential pressure, which is the

    pressure difference between the pressure entering the meter and the pressure at the neck of the

    meter. After the constricted area, the fluid is passes through a pressure recovery exit section,

    where up to 80% of the differential pressure generated at the constricted area, is recovered. The

    Venturi meter is generally preferred because it has less head loss than the other methods due to

    its streamlined design.

    The Orifice meter functions similarly to the Venturi meter. As the fluid approaches the orifice

    the pressure increases slightly and then drops suddenly as the orifice is passed. It continues to

    drop until the vena contracta is reached and then gradually increases until at approximately 5to 8 diameters downstream a maximum pressure point is reached that will be lower than the

    pressure upstream of the orifice. The decrease in pressure as the fluid passes thru the orifice is a

    result of the increased velocity of the gas passing thru the reduced area of the orifice. When the

    velocity decreases as the fluid leaves the orifice the pressure increases and tends to return to its

    original level. All of the pressure loss is not recovered because of friction and turbulence losses

    in the stream. The pressure drop across the orifice (Diagram 1) increases when the rate of flow

    increases. When there is no flow there is no differential. The differential pressure is proportional

    to the square of the velocity.

    The rotameter's (Diagram3) operation is based on the variable area principle: fluid flow raises a

    float in a tapered tube, increasing the area for passage of the fluid. The greater the flow, the

    higher the float is raised. The height of the float is directly proportional to the flowrate. With

    liquids, the float is raised by a combination of the buoyancy of the liquid and the velocity head of

    the fluid. With gases, buoyancy is negligible, and the float responds to the velocity head alone.

    The float moves up or down in the tube in proportion to the fluid flowrate and the annular areabetween the float and the tube wall. The float reaches a stable position in the tube when the

    upward force exerted by the flowing fluid equals the downward gravitational force exerted by the

    weight of the float. A change in flowrate upsets this balance of forces. The float then moves up

    or down, changing the annular area until it again reaches a position where the forces are in

    equilibrium. To satisfy the force equation, the rotameter float assumes a distinct position for

  • 7/27/2019 flow apparatus

    2/22

    every constant flowrate. However, it is important to note that because the float position is gravity

    dependent, rotameters must be vertically oriented and mounted.

    In a nozzle or other constriction, the coefficient of discharge is the ratio of the mass flow rate at

    the discharge end of the nozzle to that of an ideal nozzle which expands an identical working

    fluid from the same initial conditions to the same exit pressure.

    Whenever the fluid speed is sufficiently subsonic (V< mach 0.3),

    the incompressibleBernoulli's equation describes the flow. Applying this equation to a streamline

    travelling down the axis of the horizontal tube gives,

    From continuity, the throat velocity Vb can be substituted out of the above equation to give,

    Solving for the upstream velocity Va and multiplying by the cross-sectional areaAa gives the

    volumetric flow rate Q,

    Ideal, inviscid fluids would obey the above equation. The small amounts of energy converted

    into heat within viscous boundary layers tend to lower the actual velocity of real fluids

    somewhat. A discharge coefficient Cis typically introduced to account for the viscosity of fluids,

    http://www.efunda.com/formulae/fluids/glossary.cfm?ref=incomp#incomphttp://www.efunda.com/formulae/fluids/navier_stokes.cfm#continuityhttp://www.efunda.com/formulae/fluids/glossary.cfm?ref=invis#invishttp://www.efunda.com/formulae/fluids/glossary.cfm?ref=invis#invishttp://www.efunda.com/formulae/fluids/navier_stokes.cfm#continuityhttp://www.efunda.com/formulae/fluids/glossary.cfm?ref=incomp#incomphttp://www.efunda.com/formulae/fluids/glossary.cfm?ref=incomp#incomp
  • 7/27/2019 flow apparatus

    3/22

    Cis found to depend on the Reynolds Numberof the flow, and usually lies between 0.90 and

    0.98 for smoothly tapering venturis.

    The mass flow rate can be found by multiplying Q with the fluid density,

    http://www.efunda.com/formulae/fluids/overview.cfm#reynoldshttp://www.efunda.com/formulae/fluids/overview.cfm#reynolds
  • 7/27/2019 flow apparatus

    4/22

    Objectives:

    a. To compare flow measurements by Venturi meter, Orifice meter and Rotameterb. To determine the coefficients of discharge for the Venturi and Orifice meters, and to

    calibrate the Rota meter.

    c. To compare the pressure drops across each device and also across a gradual enlargementand a sharp bend.

    Apparatus:

    TecQuipment Flow Measuring Apparatus, TecQuipment Hydraulic Bench, stopwatch

    Important dimensions:

    Inlet and outlet diameters of the venture tube = 25.4mm

    Throat diameter of the venturi tube = 15.9mm

    Change of diameters at gradual enlargement = 25.4 to 50.8mm

    Included angle of gradual enlargement = 53

    Diameter of orifice = 22.2mm

    Change of diameter in sharp bend = 50.8 to 38.1mm

  • 7/27/2019 flow apparatus

    5/22

    Diagram 1 showing an Orifice meter

    Diagram 2 showing a Venturi meter

  • 7/27/2019 flow apparatus

    6/22

    Diagram 3 showing a Rotameter

  • 7/27/2019 flow apparatus

    7/22

    Diagram 4 Showing the positioning of each meter in the experiment apparatus

  • 7/27/2019 flow apparatus

    8/22

    Procedure:

    The flow measuring apparatus was mounted on top of the Hydraulics Bench facing the weight

    hanger. The end of the supply hose from the pump was put unto the inlet pipe. The end of the

    discharge hose was positioned so as to lead the discharge to the weight tank.

    It was ensured that the supply valve was closed. The outlet gate valve at the top of the unit was

    fully opened. The brass valve in the vent line tube to the right of the manometer panel was

    closed, before the pump was switched on. The bench supply valve was opened slowly/gradually.

    All air bubbles were allowed to leave the flow passages and manometer tubes to help in this

    process the tubes were gently tapped to allow the bubbles to leave. The bench supply valve was

    adjusted to give a high reading of about 250mm on the Rotameter scale. A pencil was then used

    to gently depress the air valve at the left end of the manifold, at the top of the manometer panel,

    to release air and bring the level of h1 up to about 350mm. Alternatively, the brass valve in the

    vent line at the right of the manometer panel was cracked open to achieve the same effect. All 8

    manometric readings were recorded. A stopwatch was used to time the collection of about

    13.6kg of water. This procedure was repeated, gradually reducing the flow rate down to a low

    reading of about 40mm on the Rotameter to obtain a total of at least 6 sets of readings.

    The pump was switched off, the brass valve in the vent line opened and the water allowed to

    drain off the unit back to the sump. The bench supply valve and the brass valves were then

    closed.

  • 7/27/2019 flow apparatus

    9/22

    RESULTS

    Table 1 showing the results obtained from the Venturi, Orifice and Rota meters in the experiment

    Table Showing Readings for The Venturi Meter

    m Flow Rate (Q) m /s

    0.276 0.525 0.00048

    0.212 0.46 0.000428

    0.136 0.369 0.00038

    0.106 0.326 0.000299

    0.082 0.286 0.000264

    0.048 0.219 0.000196

    0.047 0.217 0.000114

    Table 2 showing some readings obtained from the Venturi meter.

    ROTAMETER

    (mm) MASS kg TIME (s) kg/s h1 h2 h h3 h4 h h5 h6 h h7 h8 h

    250 13.636 28.39 0.48031 35 7.4 27.6 30.5 31 -0.5 32.8 12 20.8 16.2 10 6.2

    220 13.636 31.89 0.427595 31.2 10 21.2 27.8 28 -0.2 29.4 13.4 16 16.6 11.8 4.8170 13.636 40.38 0.337692 26 12.4 13.6 23.6 24 -0.4 25 14.8 10.2 17 14 3

    150 13.636 45.57 0.299232 24.1 13.5 10.6 22.3 22.4 -0.1 23.4 15.4 8 17 14.6 2.4

    130 13.636 51.7 0.263752 22.6 14.4 8.2 21.2 21.6 -0.4 22.1 15.8 6.3 17 15.2 1.8

    90 13.636 69.64 0.195807 20.2 15.4 4.8 19.2 19.2 0 19.6 16.4 3.2 17 16 1

    40 13.636 119.15 0.114444 18.2 13.5 4.7 17.8 17.8 0 18 16.8 1.2 17.1 16.7 0.4

    MEASURED FLOW VENTURIMETER ENLARGEMENT ORFICE METER 90 BEND

  • 7/27/2019 flow apparatus

    10/22

    Readings Obtained from the Orifice meter

    The square root of m Flow Rate (Q) m

    0.000208 0.0144 0.00048

    0.00016 0.0126 0.000428

    0.000102 0.0101 0.00038

    0.000008 0.00283 0.000299

    0.000063 0.00794 0.000264

    0.000032 0.00566 0.000196

    0.000012 0.00346 0.000114

    Table 3 Showing results obtained from the Orifice meter

    Graph 1 showing the Discharge versus h^1/2 of the Venturi meter

    y = 0.0011x - 6E-05

    R = 0.9329

    0

    0.0001

    0.0002

    0.0003

    0.0004

    0.0005

    0.0006

    0 0.1 0.2 0.3 0.4 0.5 0.6

    Discharge(Q)m^1/2m^1/2

    (h)^1/2 m^1/2

    Discharge (Q) m3/s vs (h)^1/2 m^1/2

    Flow Rate (Q) m3/s

    Linear (Flow Rate (Q) m3/s)

  • 7/27/2019 flow apparatus

    11/22

    Graph 2 showing the Discharge versus h^1/2 of the Orifice meter

    Discussion:

    The results obtained were used to plot graphs of discharge versus h. For the graphs obtained

    from the Venturi and Orifice meters, it was observed that there is a direct correlation between the

    two entities. As a result a straight line graph was obtained for both meters. As the difference in

    h increases thee is also an increase in the values of Q and vice versa. It was found that the

    coefficient of discharge for a venturi meter should be at or around 0.98 and that of the orifice

    meter should be at or around 0.64. From the calculations the experimental values found for the

    respective meters were 0.97 and 0.47. The venturi meter fell in the range it was supposed to nut

    the reading of the orifice meter fell short. The venture meter was off by just 0.01 while the

    orifice meter was off by 0.17.

    The head loss caused by venturi meter is much smaller than that of the orifice meter. This is

    because the diameter of the neck of the venturi meter is smaller than that between the orifice

    meter with the 90obend. The manometer readings for h6 and h7 should not be the same because

    y = 0.0008x + 0.0001

    R = 0.7417

    0

    0.0001

    0.0002

    0.0003

    0.0004

    0.0005

    0.0006

    0 0.1 0.2 0.3 0.4 0.5

    Discharge(Q)m^3/s

    (h)^1/2 m1/2

    Discharge (Q) m3/s vs (h)^1/2 m^1/2

    Flow Rate (Q) m3/s

    Linear (Flow Rate (Q)

    m3/s)

  • 7/27/2019 flow apparatus

    12/22

    there is a difference in diameter between the two. The coefficient of the enlargement was

    calculated to be very small because the head loss is also small and the coefficient of the 90o

    bend

    is 0 because there is no head loss.

    Pressure losses for the orifice and flow nozzles are similar but quite significant,

    However pressure losses were lower for the venturi meter.

    To ensure that the readings were taken correctly, throughout the experiment the tubes should be

    tapped slightly to ensure that there is no air bubbles that develop even though at the beginning it

    was ensured that there were no bubbles in the system.

    Conclusion

    The objectives of this experiment were successful in that the flow measurement of venturi meter,

    orifice meter, and rotameter were all compared with each other and all have shown to have

    different flow rate.

    The coefficients of discharge for the venturi and orifice meters were 0.97 and .046 respectively.

    The pressure drops experienced across each device, the enlargement and the 90 bend were all

    different due to the varying diameters that the fluid passes through.

    References

    American Society of Mechanical Engineers (ASME). 1971. Fluid meters: Their theory and

    application. Edited by H. S. Bean. 6ed. Report of ASME Research Committee on Fluid Meters

    wefunda.com/formulae/fluids/venturi_flowmeter.cfmww.

    http://www.grc.nasa.gov/WWW/K-12/airplane/bern.html

    http://www.grc.nasa.gov/WWW/K-12/airplane/bern.htmlhttp://www.grc.nasa.gov/WWW/K-12/airplane/bern.html
  • 7/27/2019 flow apparatus

    13/22

    Calculations

    Measured Flow =39.28

    636.13

    t

    mass

    = 0.48031 kg/s

    Volumetric Flow rate (Q) = Measured Flow/ (density)

    Density of water is 1000 kg/m3

    1000

    48031.0

    sm /1048031.0 33

    Venturi Meter h = h1- h2

    h = 350-74

    = 276 cm

    Enlargement h = h3 - h4

    h = 305-310

    = -5cm

    Orifice Meter h = h5h6

    h = 328-120

    = 208mm

    Bend h = h7h8

    h = 162-100

    = 62mm

    Converting millimetres to meters

  • 7/27/2019 flow apparatus

    14/22

    1m = 1000mm

    Therefore from venture meter calculations 276 mm = 276/1000

    = 0.276 m

    m

    h

    525.0

    276.02/1

    Venturi Meter

    2122

    1

    2

    AA

    hgACQ d

    The graph plotted yields a straight line thus the equation, y = mx + c where Q = y, x = h and m

    = 212

    21

    2

    AA

    gACd

    The gradient m = 0.0011 from the graph

    Cd =

    gA

    AAm

    2

    /1

    2

    2

    12

    4

    2

    11

    dA

    d1= 25.4 mm or 25.410-3

    m

    24

    1

    23

    1

    10067.5

    4

    104.25

    mA

    A

  • 7/27/2019 flow apparatus

    15/22

    4

    2

    22

    dA

    d2 = 15.9 mm or 15.910-3

    m

    973.0

    10803.8

    779.00011.0

    784.921099.1

    10067.5/1099.110011.0

    4

    4

    44

    d

    d

    d

    C

    C

    C

    Orifice Meter

    hgACQ d 2

    The graph plotted yield a straight line thus the equation y = mx + c, where y = Q and

    x =

    h and m gACm d 2

    gA

    mCd

    20

    The gradient m = 0.0008 from the graph

    4

    2

    10

    dA

    Where d1= 22.210-3

    m

    24

    1

    23

    0

    1087.3

    4

    102.22

    mA

    A

    24

    2

    23

    2

    10986.14

    109.15

    mA

    A

  • 7/27/2019 flow apparatus

    16/22

    467.0

    568.191087.3

    0008.04

    d

    d

    C

    C

    Venturi Meter

    Head loss (hl) = h1h3

    = 350305

    = 45mm

    Inlet velocity

    A

    Qv

    vAQ

    Where Q = 0.4810-3

    m3/s and A = 1.9910

    -4m

    2

    smv

    v

    /41.2

    1099.1

    1048.0

    4

    3

    Velocity head (hv)g

    v

    2

    2

    mh

    h

    v

    v

    297.0

    568.19

    8081.5

    Head loss/inlet velocity head ratio (hl/hv)

    hl/hvm

    m

    297.0

    040.0

    = 0.135

  • 7/27/2019 flow apparatus

    17/22

    Orifice Meter

    Head loss = h5h7

    = 328-162

    = 166mm

    Inlet velocity head for orifice

    A

    Qv

    vAQ

    Where Q = .4810-3

    m3/s and A = 3.8710

    -4m

    2

    smv

    v

    /24.1

    1087.3

    1048.0

    4

    3

    Head Velocity (hv)g

    v

    2

    2

    mh

    h

    v

    v

    21086.7

    568.19

    538.1

    Head loss/inlet velocity head (hl/hv)

    hl/hvm

    m

    0786.0

    166.0

    = 2.11

    Enlargement

  • 7/27/2019 flow apparatus

    18/22

    Bernoullis equationg

    v

    g

    PZ

    g

    v

    g

    PZ

    22

    2

    222

    2

    111

    mmZZ 7021

    g

    v

    g

    v

    g

    P

    g

    PZZ

    2)(

    2

    3

    2

    44321

    d4 = 50.8mm

    d3 = 25.4mm

    4

    2

    44

    dA

    23

    4

    23

    4

    100268.2

    4

    108.50

    mA

    A

    24

    3

    23

    3

    10067.5

    4

    104.25

    mA

    A

    4

    4A

    Qv

    vAQ

    smv

    v

    /237.0

    100268.2

    1048.0

    4

    3

    3

    4

    smv

    v

    /9473.0

    10067.5

    1048.0

    3

    4

    3

    3

    gvvhh 2/232443

  • 7/27/2019 flow apparatus

    19/22

    568.19

    9473.0237.0 22

    43

    hh

    = -0.043m

    he = h1- hm

    Where h1= -0.043m and hm = 0.305-0.310 = -0.005

    he = -0.043-(-0.005) = -0.038m

    gVKh ee 2/2

    1

    1

    1A

    Qv

    vAQ

    Where A1= 5.067 10-4

    m2

    and Q = 0.48 10-3

    m3/s

    smv

    v

    /947.0

    10067.5

    1048.0

    1

    4

    3

    1

    gvhK ee2

    2

    1

    784.92947.0

    038.02

    eK

    Ke = -0.829

    Sharp Bend

    d7 = 50.8mm

    d8 = 38.1mm

    4

    2

    7

    7

    dA

  • 7/27/2019 flow apparatus

    20/22

    4

    )108.50(23

    7

    A

    A7 = 2.0268 10-3

    m2

    4

    )101.38( 23

    8

    A

    A8 = 1.14 10-3

    m2

    7

    7A

    Qv

    vAQ

    smv

    v

    /2368.0

    100268.2

    1048.0

    7

    3

    3

    7

    smv

    v

    /421.01014.1

    1048.0

    7

    3

    3

    8

    gvvhh 2/272887

    568.19

    2368.0421.0 22

    87

    hh

    = 6.19 10-3

    m

    hs = h(7-8)-hm2

    hm2 = 0.162-0.10 = 0.062

    hs = 6.1910-3

    - 0.062

  • 7/27/2019 flow apparatus

    21/22

    = -0.000384 m

    gVKh ss 2/2

    1

    gvhK ss2

    2

    1

    Where v = 0.974m/s

    784.92237.0

    000384.02

    eK

    = -0.134

  • 7/27/2019 flow apparatus

    22/22

    The University of Technology, Jamaica

    Thermal Fluid Science Lab. 1

    Flow Measuring Apparatus

    Name: George Robinson

    I.D. # 0907818

    Lecturer: Mr Kavian Cook