flat cable balance_brief29

2
1 TECHNICAL BRIEF CABLE GROUP 29brief ,5 May, 1998 CENTRILIFT, A Baker Hughes company ! 2210 E. L. Anderson Boulevard, Claremore, OK 74017 ! Phone (918) 341-9600, ! FAX (918) 342-0176 FLAT CABLE BAL ANCE Most electrical p ower i s delivered over a balanced, three- phase AC system. This means that each of the three phases is connected to (mostly) equivalent electrical ci rcui ts. In some cases, one circuit w ill n ot match exactly the other two circu its and draw a current different fr om t he ave rage and this leads t o a voltage imbalance. NEMA defines imbalance as: % Voltag e Imbal anc e = Max deviat i o n f rom the average x 100 average voltage Voltage imbalance may result fr om mismatches anywhere in the supply circuit. This includes the supply itself, the power cable and the motor windings. Studies have shown that for norm al depths (below 8000 fee t) a flat cable imbalance has less effect than is likely found in normal variations in power supplies and the motor  wind ings. Only in very dee p wells, where the cable losses are a sign ific ant portio n of  the total los ses, do cable imbalance effects need to be considered. CONCLUSIONS Fa ctor s that affect th e system imb alance a re:  Pre-existing l ine (power suppl y) voltage imbalance  Load (motor) impedance  Cable impedance imbalance (that varies wi th l ength and cu rrent) RECOMMENDATIONS Se veral methods exist to r educe imbalance condition s:  Rotating the three phases until balanced current condi tions exis t   Adj us t t ran sf or mer tap s to achieve balance, this can be used in co nj un ct ion with rotation of phases  Use round cable where clearance is available, consider us ing c able protectors if  tight condition exists  Use a mixed str ing w here approp riate ( i.e., top round and bot tom f lat)

Upload: gustavomilla

Post on 10-Oct-2015

1 views

Category:

Documents


0 download

TRANSCRIPT

  • 5/20/2018 Flat Cable Balance_brief29

    1/3

    1

    TECHNICAL BRIEF

    CABLE GROUP 29brief,5 May, 1998CENTRILIFT, A Baker Hughes company !2210 E. L. Anderson Boulevard, Claremore, OK 74017 !Phone (918) 341-9600, ! FAX (918) 342-0176

    FLAT CABLE BALANCE

    Most electrical power is delivered over a balanced, three-phase AC system. This means

    that each of the three phases is connected to (mostly) equivalent electrical ci rcui ts. Insome cases, one circuit will not match exactly the other two circuits and draw a currentdifferent from the average and th is leads to a voltage imbalance.

    NEMA defines imbalance as:

    % Voltage Imbalance = Max deviation from the average x 100average voltage

    Voltage imbalance may result from mismatches anywhere in the supply circuit . Thisincludes the supply itself, the power cable and the motor windings.

    Studies have shown that for normal depths (below 8000 feet) a flat cable imbalance hasless effect than is likely found in normal variations in power supplies and the motorwind ings. Only in very deep wells, where the cable losses are a significant portion of

    the total losses, do cable imbalance effects need to be considered.

    CONCLUSIONS

    Factors that affect the system imbalance are:

    Pre-exist ing l ine (power supply) voltage imbalance

    Load (motor) impedance

    Cable impedance imbalance (that varies wi th length and current)

    RECOMMENDATIONS

    Several methods exist to reduce imbalance condi tions:

    Rotating the three phases until balanced current condi tions exist Adjust transformer taps to achieve balance, this can be used in conjunct ion with

    rotation of phases

    Use round cable where clearance is available, consider using cable protectors if

    tight condition exists

    Use a mixed str ing where appropriate (i.e., top round and bot tom f lat)

  • 5/20/2018 Flat Cable Balance_brief29

    2/3

    2

    Use a higher voltage motor (for a given HP load) thus reducing the current loading

    on the cable

    Do a phase transpos ition splice at 1/3 intervals of the total cable length. Phase

    transposition allows each of the three conductors to spend an equal amount of timein the center posit ion where the imbalance is created.

    TRANSPOSITION SPLICE

    A B C

    B C A

    C A B

    The transposi tion splice is equally spaced at 1/3 intervals of the total length of thecable. This option may reduce overall cable reliability by having two extra splices in thestring of cable. The cable is also larger at the transposit ion, which causes a size

    problem and the possibili ty of damage. This area requires cable protectors over the twosplices.

    No single criterion exists for recommendation maximum lengths for flat cables. Anyrecommendation needs to account for the effect on specific motor sizes, normal

    variation of conductor resistance (1%), conductor size and kV rating.

    With known or estimated voltage imbalance values, the AutographPCprogram can

    quickly estimate the operating motor temperature for proper size of motor and cablesystems.

    Thomson H. WallaceThomson H. WallaceThomson H. WallaceThomson H. Wallace Walter DinkinsWalter DinkinsWalter DinkinsWalter Dinkins

    Product Development Manager Senior Staff Applications& Product Engineer

  • 5/20/2018 Flat Cable Balance_brief29

    3/3