FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf. Migration_Provox_DeltaV_FMS- PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs Non contractual documentation – Firelec can improve the design or the specifications of the product described herein without prior notification FMS-PVXCL-DV-1-DI Page 1/44 FIRELEC FIRELEC Migration Solution EMERSON Provox™ > DeltaV™ CL Series - Using IOPs Discrete Inputs FMS-PVXCL-DV-1 Rev Date Subject 01 12/04/2013 First revision 02 18/07/2013 Update of cable references 03 07/03/2014 Document update 04 07/12/2016 Update of cable references

Upload: ngohuong

Post on 03-May-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 1/44

FIRELEC

FIRELEC Migration Solution

EMERSON Provox™ > DeltaV™

CL Series - Using IOPs

Discrete Inputs

FMS-PVXCL-DV-1

Rev Date Subject

01 12/04/2013 First revision

02 18/07/2013 Update of cable references

03 07/03/2014 Document update

04 07/12/2016 Update of cable references

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 2/44

FIRELEC

Summary

INTRODUCTION ................................................................................................................. 3

1.1. KEY ADVANTAGES OF THE FMS-PVXCL-DV-1 SOLUTION...................................................... 4

1.2. DESCRIPTION OF THE FMS-PVXCL-DV-1 SOLUTION ............................................................ 5

1.2.1. Existing Provox architecture ........................................................................................ 5

1.2.2. Existing Provox Hardware to be removed.................................................................... 5

1.2.3. Process I/Os kept in place ........................................................................................... 6

1.2.4. New DeltaV architecture .............................................................................................. 6

DISCRETE INPUTS ............................................................................................................ 7

2.1. CL6781 / CL6783 / CL6787(CE) (SIMPLEX) CL6784 / CL6788(CE) (REDUNDANT) ............ 8

2.1.1. Description and connection .......................................................................................... 8

2.1.2. Solution : FMS-PVXCL-DV-1-DI1-A ............................................................................. 9

2.1.3. Solution : FMS-PVXCL-DV-1-DI1-B ........................................................................... 12

2.1.4. Solution : FMS-PVXCL-DV-1-DI1-C .......................................................................... 15

2.2. CL6761 / (SIMP.) / CL6762 (RED.) CL6763(CE) (SIMP.) /CL6764(CE) (RED.)................... 17

2.2.1. Description and connection ........................................................................................ 17

2.2.2. Solution : FMS-PVXCL-DV-1-DI2-A ........................................................................... 18

2.2.3. Solution : FMS-PVXCL-DV-1-DI2-B ........................................................................... 20

2.2.4. Solution : FMS-PVXCL-DV-1-DI2-C .......................................................................... 23

2.3. CL6343(CE) (SIMPLEX / REDUNDANT) - IS (EX) .............................................................. 26

2.3.1. Description and connection ........................................................................................ 26

2.3.2. Solution : FMS-PVXCL-DV-1-DI3-A ........................................................................... 27

2.3.3. Solution : FMS-PVXCL-DV-1-DI3-B ........................................................................... 31

2.4. CL6344(CE) (SIMPLEX / REDUNDANT) - IS (EX) .............................................................. 35

2.4.1. Description and connection ........................................................................................ 35

2.4.2. Solution : FMS-PVXCL-DV-1-DI4-A ........................................................................... 36

2.5. CL6301-3(CE) (SIMPLEX / REDUNDANT) - IS (EX) ........................................................... 38

2.5.1. Description and connection ........................................................................................ 38

2.5.2. Solution : FMS-PVXCL-DV-1-DI5-A ........................................................................... 39

2.6. CL6301-4(CE) (SIMPLEX / REDUNDANT) - IS (EX) - PULSE INPUTS ................................... 42

2.6.1. Description and connection ........................................................................................ 42

2.6.2. Solution : FMS-PVXCL-DV-1-DI6-A ........................................................................... 43

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 3/44

FIRELEC

INTRODUCTION

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 4/44

FIRELEC

The purpose of this document is to guide the user of a 20 series I/Os PROVOXTM system with the safe, efficient and easy way to migrate toward a DeltaVTM system. FIRELEC has developed a migration solution (FMS-PVXCL-DV-1) allowing to protect the existing wiring investment as the user convert from an existing PROVOX system toward the DeltaVTM system. The FMS-PVXCL-DV-1 solution is a set of new I/O panels installed in place of the existing 20 series ProvoxTM I/O panels, allowing to migrate easily the existing ProvoxTM I/Os toward a new DeltaVTM system, keeping the I/O wiring in place. The ProvoxTM I/Os connected on the existing I/O panels are kept in place and connected on a new IOPs electrically and mechanically fully compatible with existing I/Os and the new DeltaVTM I/O cards linked using suitable cables provided with each type of new IOP.

1.1. KEY ADVANTAGES OF THE FMS-PVXCL-DV-1 SOLUTION

FMS-PVXCL-DV-1 solution protects the wiring investment as the user converts from the PROVOXTM 20series system toward the DeltaVTM system of Emerson Process Management with following advantages :

1. FMS-PVXCL-DV-1 is a pre-engineered solution, ready to work without any technical rework or limitation regarding the existing capabilities of the Provox system to be migrated.

2. As the instrument wiring is not disturbed, the instrument checkout during startup is reduced to the

minimum

3. The DeltaVTM system's configuration allows for the engineering conversion to be done efficiently. The speed at which FMS-PVXCL-DV-1 solution can be implemented ensures to reduce the process downtime to the minimum.

4. All existing documentations (electrical and loop drawings, maintenance procedures, .....) remain

unchanged as the I/O labelling is strictly the same on new IOPs than on previous ProvoxTM I/O panels removed

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 5/44

FIRELEC

1.2. DESCRIPTION OF THE FMS-PVXCL-DV-1 SOLUTION

1.2.1. Existing Provox architecture

1.2.2. Existing Provox Hardware to be removed

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 6/44

FIRELEC

1.2.3. Process I/Os kept in place

1.2.4. New DeltaV architecture

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 7/44

FIRELEC

DISCRETE INPUTS

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 8/44

FIRELEC

2.1. CL6781 / CL6783 / CL6787(CE) (SIMPLEX) CL6784 / CL6788(CE) (REDUNDANT)

2.1.1. Description and connection 16 channel - Discrete input

Existing Provox architecture Panel Cable Provox card

CL6781 / CL6783 / CL6787(CE) CBL-SUBD37/SUBD37 CL6721

Existing Provox architecture

Panel Cable Provox card CL6784 / CL6788(CE) 2 x CBL-SUBD37/SUBD37 2 x CL6721

CL6784 : 4U

CL6788 : 3U

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 9/44

FIRELEC

2.1.2. Solution : FMS-PVXCL-DV-1-DI1-A

Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)

Module Description

CL6751X1-A7 Discrete input module - Dry contact connected to the signal common

CL6751X1-A8 Discrete input module - Dry contact with current limiter

Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)

Module Description

CL6753X1-A12 Discrete input module - Dry contact with current limiter (CE version)

CL6753X1-A13 Discrete input module - Dry contact connected to the signal common (CE version)

New FIRELEC IOP : IOP-DI-01-1 (16 channels)

Description

16 channels - Discrete input termination panel with fuse for dry contact

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 10/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A1 Interface unit Cable DeltaV card

IOP-DI-01-1

CBL-1097 (Shielded Round Cable)

SUB25F > HE1020 CH 1 to 16 : Cable option A

CH 17 to 32 : Cable option B

½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32

channels, 24 Vdc, Dry contact,

40 pin Mass Termination block

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A2 Interface unit Cable DeltaV card

IOP-DI-01-1 CBL-PVXCL-DV-DI1-A2

CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B

½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32

channels, 24 Vdc, Dry contact,

Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 11/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A3 Interface unit Cable DeltaV card

IOP-DI-01-1 2 x CBL-PVXCL-DV-DI1-A3

2 x VE4031S2T2B1 / 2 x SE4031S2T2B1

Discrete Input card, 8 channels,

24 Vdc, Dry contact, Redundant, Terminal block

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-A4

Interface unit Cable DeltaV card

IOP-DI-01-1 2 x CBL-1281

(Shielded Round Cable) SUB25F > HE1016

2 x VE4001S2T2B3 / 2 x SE4001S2T2B3

Discrete Input card, 8 channels,

24 Vdc, Dry contact, 16 pin Mass Termination

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 12/44

FIRELEC

2.1.3. Solution : FMS-PVXCL-DV-1-DI1-B

Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)

Module Description

CL6751X1-A1 Discrete isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)

CL6751X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)

2H10882-Y012 Discrete isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)

CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)

CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)

Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)

Module Description

CL6753X1-A10 Discrete isolated input module - 3-32Vdc debounce (25Hz max) ) with external power (not powered by the panel)

CL6753X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) ) with external power (not powered by the panel)

CL6753X1-A14 Discrete isolated input module - 20-65Vdc Fast (10KHz) ) with external power (not powered by the panel)

CL6751X1-A13 Discrete input module - Dry contact with current limiter.

CL6751X1-A12 Discrete input module - Dry contact with current limiter.

New FIRELEC IOP : IOP-DI-02-1 (16 channels)

Description

16 channels - isolated discrete input termination panel powered by 15 to 60Vdc voltage

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 13/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B1 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation

Interface unit Cable DeltaV card IOP-DI-02-1

(15Vdc to 60Vdc)

Input frequency limited to 75Hz due to the DeltaV card frequency limitation.

For frequency greater than 75Hz see FMS-PVXCL-

DV-1-DI-C1

CBL-1097 (Shielded Round Cable)

SUB25F > HE1020 CH 1 to 16 : Cable option A

CH 17 to 32 : Cable option B

½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32

channels, 24 Vdc, Dry contact,

40 pin Mass Termination block

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B2 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation

Interface unit Cable DeltaV card IOP-DI-02-1

(15Vdc to 60Vdc)

Input frequency limited to 75Hz due to the DeltaV card frequency limitation.

For frequency greater than 75Hz see FMS-PVXCL-

DV-1-DI-C1

CBL-PVXCL-DV-DI1-B2 CH 1 to 16 : Cable option A

CH 17 to 32 : Cable option B

½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32

channels, 24 Vdc, Dry contact, Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 14/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B3 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation

Interface unit Cable DeltaV card IOP-DI-02-1

(15Vdc to 60Vdc) Input frequency limited to 75Hz due to the DeltaV

card frequency limitation. For frequency greater than 75Hz see FMS-PVXCL-

DV-1-DI-C1

2 x CBL-PVXCL-DV-DI1-B3

2 x VE4031S2T2B1 / 2 x SE4031S2T2B1

Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,

Terminal block

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-B4 Input frequency limited at 75Hz due to the DeltaV c ard frequency limitation

Interface unit Cable DeltaV card

IOP-DI-02-1 (15Vdc to 60Vdc)

Input frequency limited to 75Hz due to the DeltaV card frequency limitation.

For frequency greater than 75Hz see FMS-PVXCL-DV-1-DI-C1

2 x CBL-1281 (Shielded Round Cable)

SUB25F > HE1016

2 x VE4001S2T2B3 / 2 x SE4001S2T2B3

Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin

Mass Termination

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 15/44

FIRELEC

2.1.4. Solution : FMS-PVXCL-DV-1-DI1-C

Existing Provox Panel : CL6781(Simplex) / CL6783 (S implex) / CL6784 (Redundant)

Module Description

CL6751X1-A1 Discrete isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)

CL6751X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)

2H10882-Y012 Discrete isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)

CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)

CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)

Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)

Module Description

CL6753X1-A10 Discrete isolated input module - 3-32Vdc debounce (25Hz max) ) with external power (not powered by the panel)

CL6753X1-A2 Discrete isolated input module - 3-32Vdc Fast (10KHz) ) with external power (not powered by the panel)

CL6753X1-A14 Discrete isolated input module - 20-65Vdc Fast (10KHz) ) with external power (not powered by the panel)

CL6751X1-A13 Discrete input module - Dry contact with current limiter.

CL6751X1-A12 Discrete input module - Dry contact with current limiter.

New FIRELEC IOP : IOP-DIP-01-1 (16 channels)

Description

16 channels - pulse input termination panel

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 16/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI1-C1 Input frequency up to 10KHz for pulse inputs

Interface unit Cable DeltaV card

IOP-DIP-01-1 (15Vdc to 60Vdc)

Input frequency up to 10KHz.

4 x CBL-PVXCL-DV-DI1-C1 CH 1 to 4 : Cable option A CH 5 to 8 : Cable option B

CH 9 to 12 : Cable option C CH 13 to 16 : Cable option D

4 X VE4015 / 4 X SE4015

Pulse Input card, 4 channels,

Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 17/44

FIRELEC

2.2. CL6761 / (SIMP.) / CL6762 (RED.) CL6763(CE) (S IMP.) /CL6764(CE) (RED.)

2.2.1. Description and connection 8 channels - Pulse inputs

Existing Provox architecture Panel Cable Provox card

CL6761 / CL6763(CE) CBL-SUBD37/SUBD37 CL6721

Existing Provox architecture

Panel Cable Provox card CL6762 / CL6764(CE) 2 x CBL-SUBD37/SUBD37 2 x CL6721

CL6762 : 4U

CL6764 : 3U

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 18/44

FIRELEC

2.2.2. Solution : FMS-PVXCL-DV-1-DI2-A

Existing Provox Panel : CL6761 / (Simplex) / CL6762 (Redundant)

Module Description

CL6751X1-A1 Pulse isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)

CL6751X1-A2 Pulse isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)

CL6751X1-A3 Pulse isolated input module - Vortex Powered in 24Vdc by the panel

2H10882-Y012 Pulse isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)

CL6751X1-A7 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)

CL6751X1-A8 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)

Existing Provox Panel : CL6763 (CE) (Simplex) / CL6 764 (CE) (Redundant)

Module Description

CL6753X1-A2 Pulse isolated input module - 3-32Vdc debounce (25Hz max) with external power (not powered by the panel)

CL6753X1-A10 Pulse isolated input module - 3-32Vdc Fast (10KHz) with external power (not powered by the panel)

CL6753X1-A11 Pulse isolated input module - Vortex Powered in 24Vdc by the panel

CL6753X1-A14 Pulse isolated input module - 20-65Vdc Fast (10KHz) with external power (not powered by the panel)

CL6753X1-A12 Discrete input module - Dry contact with current limiter (when mixed with some other pulse input modules on same panel)

CL6753X1-A13 Discrete input module - Dry contact (when mixed with some other pulse input modules on same panel)

New FIRELEC IOP : IOP-DIP-02-1 (8 channels)

Description

8 channels - pulse input termination panel

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 19/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-A1 Interface unit Cable DeltaV card

IOP-DIP-02-1 (For existing I/O modules

CL6751X1-A1 (1) - CL6753X1-A10 (1) CL6751X1-A2 - CL6753X1-A2 CL6751X1-A3 - CL6753X1-A11

CL6751X1-A7 (1) - CL6753X1-A13 (1) CL6751X1-A8 (1) - CL6753X1-A12 (1)

2H10882-Y012 CL6753X1-A14

(1) : With RC filter to be selected if input is dry contact

2 x CBL-PVXCL-DV-DI2-A1

2 X VE4015 / 2 X SE4015

Pulse Input card, 4 channels,

Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 20/44

FIRELEC

2.2.3. Solution : FMS-PVXCL-DV-1-DI2-B

Existing Provox Panel : CL6781 / CL6783 (Simplex) / CL6784 (Redundant)

Module Description

CL6751X1-A5 Discrete isolated input module - 90-140Vac

Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)

Module Description

CL6753X1-A5 Discrete isolated input module - 90-140Vac

New FIRELEC IOP : IOP-DI-03-1 (16 channels)

Description

16 channels - isolated discrete input termination panel powered by AC voltage

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 21/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B1 Interface unit Cable DeltaV card

IOP-DI-03-1

CBL-1097 (Shielded Round Cable)

SUB25F > HE1020 CH 1 to 16 : Cable option A

CH 17 to 32 : Cable option B

½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32

channels, 24 Vdc, Dry contact,

40 pin Mass Termination block

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B2 Interface unit Cable DeltaV card

IOP-DI-03-1 CBL-PVXCL-DV-DI2-B2

CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B

½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32

channels, 24 Vdc, Dry contact,

Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 22/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B3

Interface unit Cable DeltaV card

IOP-DI-03-1 2 x CBL-PVXCL-DV-DI2-B3

2 x VE4031S2T2B1 / 2 x SE4031S2T2B1

Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,

Terminal block

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-B4

Interface unit Cable DeltaV card

IOP-DI-03-1 2 x CBL-1281

(Shielded Round Cable) SUB25F > HE1016

2 x VE4001S2T2B3 / 2 x SE4001S2T2B3

Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin

Mass Termination

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 23/44

FIRELEC

2.2.4. Solution : FMS-PVXCL-DV-1-DI2-C

Existing Provox Panel : CL6781 / CL6783 (Simplex) / CL6784 (Redundant)

Module Description

CL6751X1-A6 Discrete isolated input module - 180-280Vac

Existing Provox Panel : CL6787(CE) (Simplex) / CL67 88(CE) (Redundant)

Module Description

CL6753X1-A6 Discrete isolated input module - 180-280Vac

New FIRELEC IOP : IOP-DI-03-2 (16 channels)

Description

16 channels - isolated discrete input termination panel powered by AC voltage

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 24/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C1 Interface unit Cable DeltaV card

IOP-DI-03-2

CBL-1097 (Shielded Round Cable)

SUB25F > HE1020 CH 1 to 16 : Cable option A

CH 17 to 32 : Cable option B

½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32

channels, 24 Vdc, Dry contact, 40 pin Mass Termination block

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C2

Interface unit Cable DeltaV card

IOP-DI-03-2 CBL-PVXCL-DV-DI2-C2

CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B

½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32

channels, 24 Vdc, Dry contact, Terminal block

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 25/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C3

Interface unit Cable DeltaV card

IOP-DI-03-2 2 x CBL-PVXCL-DV-DI2-C3

2 x VE4031S2T2B1 / 2 x SE4031S2T2B1

Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,

Terminal block

New DeltaV architecture - FMS-PVXCL-DV-1-DI2-C4

Interface unit Cable DeltaV card

IOP-DI-03-2 2 x CBL-1281

(Shielded Round Cable) SUB25F > HE1016

2 x VE4001S2T2B3 / 2 x SE4001S2T2B3

Discrete Input card, 8 channels,

24 Vdc, Dry contact, 16 pin Mass Termination

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 26/44

FIRELEC

2.3. CL6343(CE) (SIMPLEX / REDUNDANT) - IS (EX)

2.3.1. Description and connection 32 channels - IS (Ex) Discrete inputs

Existing Provox architecture

Panel Cable Provox card IS (Ex) CL6343(CE) (SIMPLEX) 2 x CBL-SUBD37/SUBD37 2 x CL6721

Redundancy 1:1 or 1:N

Existing Provox architecture

Panel Cable Provox card IS (Ex) CL6343(CE) (REDUNDANT) 4 x CBL-SUBD37/SUBD37 4 x CL6721

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 27/44

FIRELEC

2.3.2. Solution : FMS-PVXCL-DV-1-DI3-A

Existing Provox Panel : CL6343 / (Simplex) and (Red undant)

Module Description

CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)

New FIRELEC IOP : FC5301-1 or FC5301-4 / (Simplex) and (Redundant) (16 slots)

Module Description

CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)

Keeping the existing CL6356 modules installed on the new panel FC5301-1 or -4 FC5301-1 + 16 x CL6356 or FC5301-4 + 16 x CL6356 Loop agreement remains unchanged and still in use

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 28/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A1 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37)+ 16 modules CL6356 CBL-PVXCL-DV-DI3-A1

VE4001S2T2B5 / SE4001S2T2B5

Discrete Input card, 32 channels, 24 Vdc, Dry contact,

40 pin Mass Termination block

Equiped with 16 conversion modules CL6356

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A2 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37)+ 16 modules CL6356 CBL-PVXCL-DV-DI3-A2

VE4001S2T2B4 SE4001S2T2B4

Discrete Input card, 32 channels, 24 Vdc, Dry contact,

Terminal block

Equiped with 16 conversion modules CL6356

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 29/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A3 Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 16 modules CL6356 CBL-PVXCL-DV-DI3-A3

4 x VE4001S2T2B3 / 4 x SE4001S2T2B3

Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin

Mass Termination Block

Equiped with 16 conversion modules CL6356

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 30/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-A4 Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 16 modules CL6356 CBL-PVXCL-DV-DI3-A4

4 x VE4031S2T2B1 / 4 x SE4031S2T2B1

Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,

Terminal block

Equiped with 16 conversion modules CL6356

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 31/44

FIRELEC

2.3.3. Solution : FMS-PVXCL-DV-1-DI3-B

Existing Provox Panel : CL6343 / (Simplex) and (Red undant)

Module Description

CL6356 2 channels - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (7,7 - 9,0 Vdc)

New FIRELEC IOP : FC5301-1 or -4 / (Simplex) and (R edundant) (16 slots)

Module Description

FC302 2 channels – I.S. discrete input for switch or proximity detector. Solid state output

New modules type FC302 installed on the new panel FC5301-1 or -4 FC5301-1 + 16 x FC302 or FC5301-4 + 16 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 32/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B1 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37) + 16 modules FC302 CBL-PVXCL-DV-DI3-B1

VE4001S2T2B5 / SE4001S2T2B5

Discrete Input card, 32 channels, 24 Vdc, Dry contact,

40 pin Mass Termination block

Equiped with 16 conversion modules FC302

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B2 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37) + 16 modules FC302 CBL-PVXCL-DV-DI3-B2

VE4001S2T2B4 / SE4001S2T2B4

Discrete Input card, 32 channels, 24 Vdc, Dry contact,

Terminal block

Equiped with 16 conversion modules FC302

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 33/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B3 Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 16 modules FC302 CBL-PVXCL-DV-DI3-A3

4 x VE4001S2T2B3 / 4 x SE4001S2T2B3

Discrete Input card, 8 channels, 24 Vdc, Dry contact, 16 pin

Mass Termination Block

Equiped with 16 conversion modules FC302

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 34/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI3-B4 Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 16 modules FC302 CBL-PVXCL-DV-DI3-B4

4 x VE4031S2T2B1 / 4 x SE4031S2T2B1

Discrete Input card, 8 channels, 24 Vdc, Dry contact, Redundant,

Terminal block

Equiped with 16 conversion modules FC302

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 35/44

FIRELEC

2.4. CL6344(CE) (SIMPLEX / REDUNDANT) - IS (EX)

2.4.1. Description and connection 16 channels - IS (Ex) Pulse inputs

Existing Provox architecture

Panel Cable Provox card IS (Ex) CL6344(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721

Existing Provox architecture Panel Cable Provox card

IS (Ex) CL6344(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 36/44

FIRELEC

2.4.2. Solution : FMS-PVXCL-DV-1-DI4-A

Existing Provox Panel : CL6343 / (Simplex) and (Red undant)

Module Description

CL6358 1 channel - IS (Ex) Pulse input isolated barrier - (3,6 - 12,0 Vdc) (50KHz max)

New FIRELEC IOP : FC5301-4 / (Simplex) (16 slots)

Module Description

CL6358 1 channel - IS (Ex) Pulse input isolated barrier - (3,6 - 12,0 Vdc) (50KHz max)

Keeping the existing CL6358 installed on the new panel FC5301-4 FC5301-4 + 16 x CL6358 Loop agreement remains unchanged and still in use

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 37/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI4-A1 Input frequency up to 10KHz for pulse inputs

Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 16 modules CL6358

Input frequency up to 10KHz. CBL-PVXCL-DV-DI4-A1

4 X VE4015 / 4 X SE4015

Pulse Input card, 4 channels, Terminal block

Equiped with 16 conversion modules CL6358

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 38/44

FIRELEC

2.5. CL6301-3(CE) (SIMPLEX / REDUNDANT) - IS (EX)

2.5.1. Description and connection 16 channels - IS (Ex) Discrete inputs – Dry contact and proximity switch NAMUR)

Existing Provox architecture

Panel Cable Provox card

IS (Ex) CL6301-3(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721

Existing Provox architecture

Panel Cable Provox card

IS (Ex) CL6301-3(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 39/44

FIRELEC

2.5.2. Solution : FMS-PVXCL-DV-1-DI5-A

Existing Provox Panel : CL6301-3 / (Simplex) and (R edundant)

Module Description

CL6302-1 1 channel - IS (Ex) Discrete input isolated barrier - Dry contact or proximity detector (NAMUR) (Power supply : 8vdc – 4mA)

CL6302-2 1 channel - IS (Ex) Discrete input isolated barrier - Proximity switch input PP 3 wires (Power supply : 18vdc – 25mA)

New FIRELEC IOP : FC5301-1 / (Simplex) and (Redunda nt) (16 slots)

Module Description

FC302 2 channels – I.S. discrete input for switch or proximity detector. Solid state output

New modules type FC302 installed on the new panel FC5301-1 FC5301-1 + 8 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 40/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A1 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37) + 8 modules FC302 CBL-PVXCL-DV-DI5-A1

CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B

½ VE4001S2T2B5 / ½ SE4001S2T2B5 Discrete Input card, 32

channels, 24 Vdc, Dry contact, 40 pin Mass Termination block

Equiped with 8 conversion modules FC302

New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A2 Interface unit Cable DeltaV card

FC5301-1 (1 x SUBD37) + 8 modules FC302 CBL-PVXCL-DV-DI5-A2

CH 1 to 16 : Cable option A CH 17 to 32 : Cable option B

½ VE4001S2T2B4 / ½ SE4001S2T2B4 Discrete Input card, 32

channels, 24 Vdc, Dry contact, Terminal block

Equiped with 8 conversion modules FC302

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 41/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI5-A3 Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD15) + 8 modules FC302 CBL-PVXCL-DV-DI5-A3

2 x VE4031S2T2B1 / 2 x SE4031S2T2B1

Discrete Input card, 8 channels,

24 Vdc, Dry contact, Redundant, Terminal block

Equiped with 8 conversion modules FC302

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 42/44

FIRELEC

2.6. CL6301-4(CE) (SIMPLEX / REDUNDANT) - IS (EX) - PULSE INPUTS

2.6.1. Description and connection 16 channels - IS (Ex) Pulse inputs (Fast 10KHz)

Existing Provox architecture Panel Cable Provox card

IS (Ex) CL6301-4(CE) (SIMPLEX) CBL-SUBD37/SUBD37 CL6721

Existing Provox architecture Panel Cable Provox card

IS (Ex) CL6301-4(CE) (REDUNDANT) 2 x CBL-SUBD37/SUBD37 2 x CL6721

Redundancy 1:1 or 1:N

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 43/44

FIRELEC

2.6.2. Solution : FMS-PVXCL-DV-1-DI6-A

Existing Provox Panel : CL6301-4 / (Simplex) and (R edundant)

Module Description

CL6302-3 1 channel - IS (Ex) Discrete input isolated barrier – Pulse input 10KHz (Power supply : 5 – 32Vdc ; 3 – 15mA)

New FIRELEC IOP : FC5301-4 / (Simplex) (16 slots)

Module Description

FC302 2 channels – I.S. discrete input for switch or proximity detector only . Solid state output

New modules type FC302 installed on the new panel FC5301-4 FC5301-4 + 16 x FC302 Input IS parameters have to be checked for compatibility with new FC302 barriers.

FIRELEC Migration Solution FMS-PVXCL-DV-1 Réf.

Migration_Provox_DeltaV_FMS-

PVXCL-DV-1-DI_v2016_12.docx EMERSON Provox™ > DeltaV™ CL Series - Using IOPs – Discrete Inputs

Non contractual documentation – Firelec can improve the design or the specifications of the product described herein

without prior notification

FMS-PVXCL-DV-1-DI

Page 44/44

FIRELEC

New DeltaV architecture - FMS-PVXCL-DV-1-DI6-A1 Input frequency up to 3KHz for pulse inputs

Interface unit Cable DeltaV card

FC5301-4 (4 x SUBD9) + 16 modules FC302

Max Frequency up to 3KHz 4 x CBL-PVXCL-DV-DI6-A1

4 X VE4015 / 4 X SE4015

Pulse Input card, 4 channels, Terminal block

Equiped with 16 conversion modules FC302