fire resistance of walls made of soil-cement and ...cristina/rrest/aulas_apresentacoes/07... ·...

16
Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks Márcio Buson 1 , Nuno Lopes 2, * ,, Humberto Varum 2 , Rosa Maria Sposto 1 and Paulo Vila Real 2 1 Faculdade de Arquitetura e Urbanismo, Universidade de Brasília, Brasília CEP 70910-900, Brazil 2 Departamento de Engenharia Civil, Universidade de Aveiro, 3810-193 Aveiro, Portugal SUMMARY This study presents the results of re resistance tests on walls made of soil-cement and Kraftterra compressed earth blocks (CEBs). The purpose of this work was to evaluate and compare the re resistance of CEB walls with and without cellulose pulp derived from the recycling of cement sacks. This article describes the Kraftterra mixture and its production processes as well as the re resistance test campaign. The re resistance performance of CEB walls produced with Kraftterra and soil-cement blocks is analysed. Copyright © 2012 John Wiley & Sons, Ltd. Received 25 July 2011; Revised 18 April 2012; Accepted 11 June 2012 KEY WORDS: compressed earth blocks; Kraftterra; soil-cement; re resistance 1. INTRODUCTION At present, the construction sector is moving towards the development and optimisation of more sustainable solutions, from the materials used to the energy consumed in the construction process. Additionally, the energy consumption involved in the heating/cooling of dwellings is a topic of a great concern. Thus, the number of earth-based construction solutions is increasing. The compressed earth block (CEB) is the modern descendent of the moulded earth block [1], more commonly known as the adobe block [2]. Presses are used in CEB production to compact the soil particles, thus increasing density. According to Rigassi [2], adding bres to reinforce the soil is very common in traditional adobes but is incompatible with the CEB compression process because it complicates production. Plant and vegetable bres have been used extensively in traditional earth construction to improve the mechanical properties of soil-based constructive components. To improve the durability of adobes, strength should be increased, and water absorption should be decreased. The most effective method to modify the adobe is to compact the earth and stabilise it with additives [3]. Fibre, cement, bitumen, lime or cow dung can be used to stabilise the adobe [4]. Natural bres from bamboo, coconut husk and sisal [5] or articial bres such as plastic or polystyrene fabrics [6] are examples of efcient stabilisers. Analyses of a new composite material, Kraftterra, have has encouraging results. Kraftterra proved to be an excellent material for the production of CEBs, as demonstrated by the compressive strength, diagonal compression strength, shrinkage and re resistance of walls made with Kraftterra CEBs. *Correspondence to: Nuno Lopes, Departamento de Engenharia Civil, Universidade de Aveiro, 3810193 Aveiro, Portugal. E-mail: [email protected] Copyright © 2012 John Wiley & Sons, Ltd. FIRE AND MATERIALS Fire Mater. (2012) Published online in Wiley Online Library (wileyonlinelibrary.com). DOI: 10.1002/fam.2148

Upload: phungduong

Post on 31-Jan-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

FIRE AND MATERIALSFire Mater. (2012)Published online in Wiley Online Library (wileyonlinelibrary.com). DOI: 10.1002/fam.2148

Fire resistance of walls made of soil-cement and Kraftterracompressed earth blocks

Márcio Buson1, Nuno Lopes2,*,†, Humberto Varum2, Rosa Maria Sposto1 andPaulo Vila Real2

1Faculdade de Arquitetura e Urbanismo, Universidade de Brasília, Brasília CEP 70910-900, Brazil2Departamento de Engenharia Civil, Universidade de Aveiro, 3810-193 Aveiro, Portugal

SUMMARY

This study presents the results of fire resistance tests on walls made of soil-cement and Kraftterracompressed earth blocks (CEBs). The purpose of this work was to evaluate and compare the fire resistanceof CEB walls with and without cellulose pulp derived from the recycling of cement sacks. This articledescribes the Kraftterra mixture and its production processes as well as the fire resistance test campaign.The fire resistance performance of CEB walls produced with Kraftterra and soil-cement blocks is analysed.Copyright © 2012 John Wiley & Sons, Ltd.

Received 25 July 2011; Revised 18 April 2012; Accepted 11 June 2012

KEY WORDS: compressed earth blocks; Kraftterra; soil-cement; fire resistance

1. INTRODUCTION

At present, the construction sector is moving towards the development and optimisation of moresustainable solutions, from the materials used to the energy consumed in the construction process.Additionally, the energy consumption involved in the heating/cooling of dwellings is a topic ofa great concern. Thus, the number of earth-based construction solutions is increasing. Thecompressed earth block (CEB) is the modern descendent of the moulded earth block [1], morecommonly known as the adobe block [2]. Presses are used in CEB production to compact the soilparticles, thus increasing density. According to Rigassi [2], adding fibres to reinforce the soil isvery common in traditional adobes but is incompatible with the CEB compression process becauseit complicates production.

Plant and vegetable fibres have been used extensively in traditional earth construction to improvethe mechanical properties of soil-based constructive components. To improve the durability ofadobes, strength should be increased, and water absorption should be decreased. The most effectivemethod to modify the adobe is to compact the earth and stabilise it with additives [3]. Fibre, cement,bitumen, lime or cow dung can be used to stabilise the adobe [4]. Natural fibres from bamboo,coconut husk and sisal [5] or artificial fibres such as plastic or polystyrene fabrics [6] are examplesof efficient stabilisers.

Analyses of a new composite material, Kraftterra, have has encouraging results. Kraftterra proved tobe an excellent material for the production of CEBs, as demonstrated by the compressive strength,diagonal compression strength, shrinkage and fire resistance of walls made with Kraftterra CEBs.

*Correspondence to: Nuno Lopes, Departamento de Engenharia Civil, Universidade de Aveiro, 3810–193 Aveiro, Portugal.†E-mail: [email protected]

Copyright © 2012 John Wiley & Sons, Ltd.

Page 2: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

M. BUSON ET AL.

Tonnes of cement are used every year in civil construction. Most of the cement sacks are thrown outwithout any environmental treatment, causing an enormous negative environmental impact. In 2008,cement production in Brazil reached 51.9 million tonnes. Of this, 73%, or 37.3 million tonnes ofcement, was packed in sacks [7]. Cement in Brazil is typically packed in 50-kg sacks. It is estimatedthat in 2008, 747.3 million cement sacks were used in Brazil, which corresponds to a consumptionof 112.0 tonnes of Kraft paper.

The fibres of these sacks have excellent mechanical and physical properties. The fabrication ofthese sacks is guided by strong specifications demanded by the cement industry. Sack fabricators usehigh-resistance long-fibre sulphate cellulose, mainly in its pure form. After the cement is used, thesack, which has desirable characteristics, ends up not being accepted by the recycling industry becauseit has been ‘contaminated’ by the cement. However, there is great potential for reusing the sacks inthe production of new construction materials or for improvements in the technical, economical andsustainable properties of some traditional components utilised in dwelling construction.

The fire risk in a dwelling may be high, as there may be several ignition sources (chemical, mechanical,thermal or even electrical). Additionally, catastrophic events, such as impacts, explosions and earthquakes,are commonly associated with the occurrence of fires. These building fires may have very severeconsequences (loss of human life [8]), which justify society’s increasing attention.

Kraftterra blocks have raised doubts regarding their fire resistance, limiting their application inpractice. This study presents the results of fire resistance tests on walls made with soil-cement andKraftterra CEBs. The walls were tested without additional loads apart from their deadweight. Thisrepresents the typical loading conditions of these walls when inserted in single dwellings. Thepurpose of this work was to assess and compare the fire resistance of CEB walls with and withoutcellulose pulp derived from the recycling of cement sacks. Moreover, the eventual decay of the CEBmasonry during its lifecycle may affect the fire performance of the walls. This aspect was notanalysed in this research.

2. MATERIALS DESCRIPTION

One possibility for the use of earth in construction is the CEB. The idea of compressing earth toimprove the performance of adobe blocks is not new. The first CEBs were produced with a heavywood rammer, a process that is still used today in some regions of the world [9–11].

The first machine used to compress the earth probably dates to the 18th century. In France, FrancoisCointeraux, inventor and supporter of the new pisè, designed the crecise, a device derived from a grapepress for wine production. However, only in the early 20th century did the first designs appear formechanical presses with heavy caps for moulding earth. The decisive moment for the adoption ofpresses in the production and consequent use of CEBs for construction and execution of specificarchitectural demands arrived only in 1952, with the invention of the famous CINVA-RAM press,designed by the Engineer Raul Ramirez [2].

Since the 1970s, different models of manual presses have been developed. Mechanical andmotorised presses enabled the extension of the market for the production and use of CEBs inconstruction. The decision regarding the type of press to use for CEB production is of extremeimportance because the greater the compaction imposed on the soil or composite, the better the CEBperformance will be.

The presses compact the soil or composites in moulds that define the dimensions and shape of theCEB. Today, in addition to the varied equipment available for the production of CEBs, there areseveral types, forms, styles and designs for CEB blocks (see examples in Figure 1): solid, cast,smooth, with and without inserts, curved, half-block, corner, and so on.

Among the types of CEBs available, solid and smooth blocks were chosen for analysis in this study.The choice of these types of blocks simplifies the laboratory procedures by reducing the occurrence ofany deviation in the test results associated with the consistency in the form and location of the holes.These blocks also allow the study of wall elements constructed with mortar bed-joints.

Barbosa [12] comments that, in general, CEB quality depends on the type of soil, amount of moistureduring moulding, type of CEB machine, choice of curing process and type and quantity of binder.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 3: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

Figure 1. Examples of different geometries of CEBs [8].

SOIL-CEMENT AND KRAFTTERRA CEBS

Currently, the most commonly used composite for the production of CEBs is the soil-cement mixture.As the name implies, these blocks consist of soil stabilised with cement, normally Portland cement.

The main binder in the new composite Kraftterra, which is studied in this work, is dispersed Kraftfibres obtained from the recycling of cement bags. Other materials such as cement and lime may alsobe used as supplementary stabilising agents in Kraftterra. However, depending on the characteristics ofthe soil used in the mixture, these additional agents may be omitted.

3. FIRE RESISTANCE TESTS

Fire safety regulations and codes are prescriptive in nature. Most of these regulations are bothextensive and complex, making their interpretation difficult. In reality, Brazil has a national firecode, which consists of a general document and does not contain detailed fire safety requirements.Therefore, detailed regional fire safety regulations are applied on a daily basis and vary from city tocity. Despite these regional regulations, some required systems for buildings are analysed andcertified on the basis of national standards [13].

These regulations are based on international standards such as ASTM E119, ISO 834 and BS 476,among others [13]. The typical fire resistance required for the structural frame is defined by regulationsNBR 5628 [14] and NBR 14432 [15]. The fire resistance of load-bearing and non-load-bearing walls isregulated by NBR 10636 [16]. Regarding the European standards, Eurocode 6 [17] gives the designprocedures for obtaining fire resistance in masonry walls.

The Laboratory for Structures and Fire Resistance at the Department of Civil Engineering of theUniversity of Aveiro, Portugal, uses the European Standards for testing fire resistance (e.g. EN1363-1 [18] and EN 1364-1 [19]).

In comparing the Brazilian standard NBR 10636 [16] with the European Standard EN 1363-1 [18],many similarities in their descriptions, recommendations and procedures are observed. Both are aimedat evaluating the fire resistance of vertical non-load-bearing partition elements. These properties arecharacterised by the ability of the construction element to maintain its load-bearing capacity,integrity and thermal insulation.

Load-bearing capacity refers to the ability of the wall or partition to maintain its mechanicalstrength (load-bearing capacity) without collapsing. Integrity refers to the ability of the separatingelement to prevent the passage of flames or hot gases from the compartment with the fire toanother compartment. In addition, thermal insulation refers to the ability of the partition elementto resist heat transmission, keeping the temperature increase on the face not exposed to fire withinallowable limits.

A test specimen is considered to maintain its load-bearing capacity when, during tests involvingthe application of loads, it does not deform at a rate higher than the limits prescribed in theaforementioned standards.

A test specimen is considered to guarantee fire integrity when, during a test, it does not present openingsthat permit the passage of hot gases or flames lasting for more than 10 s from the fire-exposed face to theopposite face (not exposed).

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 4: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

M. BUSON ET AL.

A test specimen is considered to be thermally insulated when the average temperature increase doesnot exceed 140 �C on the unexposed face and when the temperature increase is always lower than180 �C at any thermocouple of the same face [16,18].

A difference between these standards can be observed regarding the heating conditions used todefine the temperature–time curve imposed during the test. NBR 10636 [16] uses in its formula(expression 1) T0, which refers to the furnace initial temperature in �C, with 10 �C≤ T0≤ 40 �C. EN1363-1 [18] adopts the ISO 834 fire curve (expression 2), which considers a constant value equal to20 �C and allows variations of 20 �C� 10 �C in the initial temperature.

T � T0 ¼ 345 log10 8t þ 1ð Þ (1)

T ¼ 345 log10 8t þ 1ð Þ þ 20 (2)

The other procedures and recommendations provided by the two standards are similar, particularlywith regard to temperature tolerance, pressure conditions, temperature measurements of the furnaceand of the unexposed face of the test specimen, average and maximum allowable temperature, andthe installation and dimensions of the test specimen.

In Brazil, it is recognised that the city of São Paulo has the most advanced standards regarding theprevention and control of fire in buildings; these standards are often used as a model for thedevelopment of standards in other Brazilian cities [13].

Technical Instruction 8/2004 of the São Paulo Fire Department [20] includes a table of masonry fireresistances, which provides the minimum performance requirements for some types of masonry andstructural sealing. As a reference, the performance values for ceramic brick walls, concrete hollowblocks (14 and 19 cm thick), clay bricks with eight holes and uncoated reinforced concrete walls arepresented in Table I.

In this technical reference [20], a table with fire resistance time requirements (TRRF, from the originalPortuguese name) that depend on the type of occupation and use of the building is also presented. Thisregulation proposes that the required fire resistance is determined as a function of several parameters,including the type of occupation: residential, service hosting, retail trade, professional services,personal and technical, educational and physical culture, public meeting, automotive services, healthservices and institutional industrial and deposits. The TRRF required for buildings with a height of upto 80m is 120min.

This study was not conducted under ideal temperature and pressure conditions, under which sixdifferent specimens of 3.1� 3.1m2 would be tested for each of the three configurations (withoutplaster, with plaster on the face exposed to the fire and with plaster on both sides) for the two materials.

The concurrent construction of six different specimens, with dimensions 3.1� 3.1m2, was notpossible because of limitations of the number of frames available in the laboratory. Otherwise, theconstruction of the six specimens on different dates would influence their behaviour because of thedifferences in the curing conditions of each specimen.

Table I. Masonry fire resistance [20].

Tested wall

Time to fulfil each of the criteria (h)Fire

resistance (h)Load-bearing Integrity Thermal insulation

Ceramic brick 5� 10� 20 cm ≥2 ≥2 1½ 1½Concrete hollow blocks 14� 19� 39 cm ≥1½ ≥1½ 1½ 1½Concrete hollow blocks 19� 19� 39 cm ≥2 ≥2 1½ 1½Clay bricks with eight holes 10� 20� 20 cmwith cement-mortar coating of 1.5 cm

≥2 ≥2 2 2

Uncoated reinforced concrete, thickness 11.5 cm 2 2 1 1½

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 5: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

SOIL-CEMENT AND KRAFTTERRA CEBS

4. TEST CAMPAIGN AND PROTOTYPES DESCRIPTION

A TERSTARAM Appro-Techno press was used for the CEB production (Figure 2). This machineproduces two CEBs at each pressing and has a system to adjust the height and volume of the mouldwith steel plates (Figure 2c).

This press produces CEBs with dimensions of 22� 11� 5.5 cm. For the construction of the wall,vertical and horizontal joints with a thickness of approximately 1.5 cm were adopted. To conduct thefire resistance test, a CEB wall was constructed in a surrounding reinforced concrete frame, withdimensions 3.10� 3.10m, which constituted the oven cover.

A test to characterise the fire resistance of Kraftterra masonry was carried out. Comparative analyseswere performed on the wall panels constructed with soil-cement blocks and on those constructedwith Kraftterra blocks. Different plastering conditions were also studied. To that end, the wall wasconstructed in two different phases corresponding to two distinct horizontal bands: the bottomhalf-height wall with traditional soil-cement CEBs and soil-cement mortar in the joints and the tophalf-height wall with Kraftterra in the CEBs and mortar.

To experimentally assess different plastering conditions commonly adopted in buildingconstruction using CEBs, the wall was divided into three vertical strips, each 1m wide, to producethree different plastering configurations for each type of wall (soil-cement and Kraftterra).Figure 3 shows views of the finished wall, particularly the external face not exposed to fire(Figure 3a) and the inner surface before exposing it to fire (Figure 3b). The nomenclature adoptedfor each wall panel is presented in Figure 4. The central strip was not plastered on both sides(P2 and P5 for the panels with Kraftterra and soil-cement blocks, respectively). One lateral stripwas plastered only on the face exposed to the fire (P1 and P4 for the panels with Kraftterraand soil-cement blocks, respectively). The other lateral strip was plastered on both sides of the

Figure 2. (a) Machine TERSTARAM; (b) CEBs production; (c) detail of the system to adjust the height ofthe mould; (d) general aspect of the CEBs produced for this research.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 6: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

Figure 3. (a) External face and (b) inner surface of the constructed wall infilled in a reinforced concreteframe mounted to test for fire resistance at the Laboratory for Structures and Fire Resistance.

A B C

7 8

6

9 10

D E F

11

Thermocouples for the increase of average unexposed face temperatureThermocouples for the increase of maximum unexposed face temperature

Points for the deflection measurement

G I K

H J L

1 2

3 4

5

22

23

24

30

31

32

26

25

14 15

1312

19 20 21 27

1816 28

2917

Thermocouples at 3 cm deep within the wallThermocouples at 6 cm deep within the wall

M O

N P

1

2

3

4

1

2

3

4

A B C

P1 P2 P3

P4 P5 P6

x

Krafterra

Soil-cement

Figure 4. Test instrumentation set-up, thermocouples and points where displacements were measured.

M. BUSON ET AL.

wall (P3 and P6 for the panels with Kraftterra and soil-cement blocks, respectively). Thus, six differentpanels were studied. The plaster, a soil-cement mortar, had the same composition in all of thepanels, and the same soil was used in the production of the CEBs and 12% cement (in mass). Theaverage thickness of the plaster was 2.0 cm, which resulted in a wall with a total thickness of 15 cm(for the panels plastered on both faces). Before plastering, the wall was wet to prevent rapid waterabsorption from the mortars and to reduce shrinkage.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 7: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

SOIL-CEMENT AND KRAFTTERRA CEBS

5. TEST MEASUREMENTS

The test was conducted at the Laboratory for Structures and Fire Resistance in two distinct stages(heating and cooling) with a total duration of 6 h 54min. Figure 4 presents the external thermocoupleposition on the test specimen in each panel and the points used for measuring displacements. Theposition of the internal thermocouples used to measure the temperature evolution within the wallbehind panels P2 and P5 can also be observed in Figure 4.

A neutral pressure plane (a pressure of zero) was imposed 500mm above the floor level.During the first 2 h of the test, the average temperature values for all of the furnace thermocouples

followed the ISO 834 fire temperature evolution curve, defined by expression (2), where t is time inminutes and T is the average temperature of all furnace thermocouples.

After the first 2 h of the test, the furnace was turned off, but all of the connected externalthermocouples continued to measure the temperature evolution during the cooling phase.

Some additional observations were noted: thermocouple 28 did not provide temperature valuesthroughout the test; humidity, caused by water evaporation inside of the blocks and subsequentcondensation on the plastered surface not directly exposed to fire, was observed during heating indifferent cracks (Figure 5b); and 1 h 53min after the beginning of the test, a vertical fissuredeveloped on the face that was not exposed to the fire, initially in the middle of the panel P2, asshown in Figure 5. It is noteworthy that the wall integrity was not at risk, and no hot gases orflames passed through the test specimen.

The crack ran vertically along the centre of the wall (panels P2 and P5) and was more visible on theface directly exposed to the fire (see Figure 6). On the exposed face, detachment of the plaster wasobserved in some locations.

6. TEST RESULTS AND COMPARISON

The room temperature recorded in the laboratory at the beginning of the test was 22.8 �C. After120min, the temperature increased to 23.0 �C. At the end of the test (after 414min, including thewall cooling), the recorded room temperature was 31.2 �C (see Table II), which is in the range ofthe ambient temperature condition limits prescribed by EN 1363-1 [18].

The graph in Figure 7 illustrates the furnace temperature evolution corresponding to the ISO 834curve up to 120min. After 120min, the furnace was turned off to reproduce the cooling phase of anatural fire. It was decided not to account for the ignition phase of real fires [21] to make it possibleto determine the fire resistance time as prescribed in fire resistance tests standards [16,18].

According to the behaviour criteria proposed in EN 1363-1 [18], insulation is defined by the time inminutes during which the wall maintains its separation function without developing high temperatures

Figure 5. Vertical crack at the centre of the non-exposed to fire face. Appearance of humidity in crackscaused by water evaporation inside the wall (b).

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 8: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

Figure 6. Vertical crack in the centre of the wall face directly exposed to fire. Detail of detachments of the plaster.

Table II. Room temperature recorded during the fire resistance test.

t (min) Room temperature (�C) t (min) Room temperature (�C)

0 22.8 80 22.310 22.0 90 22.620 22.0 100 22.830 21.8 110 22.740 21.8 120 23.050 22.1 220 28.760 22.1 310 30.070 22.5 414 31.2

Figure 7. Furnace temperature evolution.

M. BUSON ET AL.

on the unexposed surface. This property is evaluated by limiting the increase in the averagetemperature to 140 �C or by limiting the increase of temperature at any point to 180 �C.

The mean initial temperature value recorded was 22.8 �C. Thus, the materials studied will beconsidered insulators until the instant when the average temperatures on the surface not exposed tofire reach 162.8 �C or until a temperature above 202.8 �C is recorded.

In Technical Instruction No. 08/2004 of the São Paulo Fire Department [20], the structural safety ofa building is evaluated according to the fire resistance of its elements. In that document, values areproposed for the TRRF.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 9: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

SOIL-CEMENT AND KRAFTTERRA CEBS

According to the values proposed in the document, it is possible to verify that the maximum fireresistance required for all buildings is 120min, with the exception of Group M (labelled ‘special’),where 150min is required.

The global behaviour of the wall was excellent. The temperature on the external surface did notincrease more than 80 �C at any point until the furnace was turned off (120min after the test began).This demonstrates that CEB walls perform adequately against fire, considering the performance criteriaoutlined previously. After 120min, wall behaviour during the cooling phase was also characterised.

It is noteworthy that the different analysed walls showed adequate performance for consideration asfirewalls to be eventually used in stairs or in partitions.

As presented in Figure 4, thermocouples t25 and t26 measured the temperature evolution at differentdepths of Kraftterra panel 2, and thermocouple t29 (thermocouple t28 was damaged during the test)measured the temperature evolution for the soil-cement panel 5. Figure 8 presents the temperatureevolution at these thermocouples and for the corresponding unexposed surface thermocouples (t4for panel 2 and t16 for panel 5). The maximum temperature recorded in the interior of panel 2(from thermocouple t26), which is inferior to the corresponding thermocouple from panel 5 (t29),was approximately 75 �C.

Although the maximum furnace temperature was achieved at 120min, the wall temperaturecontinued to increase afterwards because of the heat transfer process.

From the graph in Figure 8, it is also possible to observe along the wall the differences in theoccurrence of total water vaporisation. This vaporisation process decelerates the temperature evolutionon the unexposed to fire surface. Figure 9 presents the temperature profile evolution in panels 2 and 5.It can be observed that in both panels, the heating on the unexposed surface is faster and the coolingis slower when compared with the corresponding temperature changes inside the blocks. For theKraftterra blocks, the vaporisation occurs at 120min on the surface that was not exposed to the fire.

From the temperature evolution curves in Figures 8 and 9, a rough estimation of the materials’thermal properties can be made mainly on the basis of comparisons between Kraftterra and soil-cement.It can be observed that Kraftterra may have a slightly lower thermal conductivity and specific heat.Future works will focus on the analysis of these parameters.

To evaluate the insulation performance of the different materials, the average temperature and themaximum temperature increases were calculated.

The average temperature increases for the six panels were compared within the limit of 140 �C. Foreach panel, only the thermocouple located in the panel centre was considered. Figure 10 presents theaverage temperature evolutions for the six panels. The temperature increase limit (140 �C) is notreached in any panel during the first 120min of the test with the ISO fire curve.

Temperatures increase in the wall cross-section

0

50

100

150

200

250

300

350

400

0 60 120 180 240 300 360 420 480Time (min)

Tem

pera

ture

(°C

)

t4-P2

t25-P2

t26-P2

t16-P5

t29-P5t16 and t29

t4, t25 and t26

Figure 8. Temperature evolution throughout the wall cross section.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 10: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

0

50

100

150

200

250

300

0 1 2 3 4 5 6 7 8 9 10 11

Tem

per

atu

re (

°C)

Thickness (cm)

Temperature increase profiles in panel 2

120 min

240 min

420 min

0

50

100

150

200

250

300

350

400

0 1 2 3 4 5 6 7 8 9 10 11

Tem

per

atu

re (

°C)

Thickness (cm)

Temperature increase profiles in panel 5

120 min

240 min

420 min

Figure 9. Temperature profile evolution in the cross section of the panel: (a) Kraftterra, (b) soil cement.

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures average increase t3-P1

t4-P2

t11-P3

t18-P4

t16-P5

t17-P6

140°C

Figure 10. Averages temperature increase in the unexposed surface of the six panels during the fireresistance test.

M. BUSON ET AL.

Graphs in Figures 11–16 show the temperature evolution recorded in each thermocouple for eachpanel tested.

By individually analysing the results for each panel, it is concluded that Kraftterra CEBs presentslightly better performance than soil-cement BTCs, especially in the conditions without plaster and

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 11: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 1t1-P1

t3-P1

t5-P1

t22-P1

t23-P1

180°C

t1t22

t3

t23 t5

Figure 11. Temperature increase evolutions in the thermocouples of panel P1, Kraftterra blocks with plasteronly in the surface exposed to fire.

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 4t7-P4

t18-P4

t19-P4

t24-P4

180°C

t7

t19

t18

t23

Figure 12. Temperature increase evolutions in the thermocouples of panel P4, soil-cement blocks with plasteronly in the surface exposed to fire.

SOIL-CEMENT AND KRAFTTERRA CEBS

with plaster on both sides. However, it is also clear that, in general terms, both types of blocks showedsimilar performances, with the major difference being the lower heat transfer showed by the walls withKraftterra blocks. In fact, as can be observed in the graphs of the previous figures, after switching offthe furnace, lower temperatures were recorded for the panels with Kraftterra blocks. This difference ismore pronounced when comparing the two panels without plaster (P2 and P5).

The recorded plateau temperature on all of the thermocouples, which varied by 60 �C to 80 �C, wasinduced by material moisture. All of the moisture evaporation occurred in the cooling phase, when itwas possible to observe rising temperatures, mainly in the panels without plaster.

It can also be concluded that the plaster had a positive effect on fire resistance. Separation betweenthe plaster and the wall was observed in both the surfaces exposed to fire and the surfaces not exposedto fire. The separation of the plaster induced the emergence of air flow zones, which does not favour atemperature increase.

The cooling phases in fire scenarios are gaining increasing importance in fire safety design. In fact,the test results showed that the cooling phase is strongly related to delays in temperature increases

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 12: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 2t2-P2

t4-P2

t6-P2

t9-P2

t12-P2

180ºC

t9 t2

t4

t6 t12

Figure 13. Temperature increase evolutions in the thermocouples of panel P2, Kraftterra blocks withoutplaster.

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 5t8-P5

t14-P5

t16-P5

t20-P5

t21-P5

180ºC

t14t8

t16

t20 t21

Figure 14. Temperature increase evolutions in the thermocouples of panel P5, soil-cement blocks withoutplaster.

M. BUSON ET AL.

(in Figure 8, see the temperature recorded in thermocouples t29 and t26). It can be observed that themaximum temperatures were achieved in the cooling phase, after approximately 240min in thepanels with no plaster and approximately 340min in the panels with plaster on one side. The resultsshow that these temperature increases never reached 180 �C, which is the prescribed limit for theISO curve and is not directly applicable to this phase.

The lateral displacement evolution was also measured during the test. During the ISO fire, the wall,which was subjected to its own weight, was able to maintain stability, and the maximum lateraldisplacement recorded was 20mm.

The horizontal displacements recorded in all positions have small values and do not affect thestability of the wall. The low values for these displacements do not invalidate the fire resistancecharacterisation test.

Illustrations of the displacement evolution at different levels are presented in Figures 17 to 19.It is observed that the centre points of the soil-cement panels (D, E and F) showed a more

pronounced horizontal displacement than the corresponding points of the Kraftterra panels. The

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 13: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 3t10-P3

t11-P3

t13-P3

t30-P3

t31-P3

180°Ct30t10

t11

t13 t31

Figure 15. Temperature increase evolutions in the thermocouples of panel P3, Kraftterra blocks with plasteron both surfaces.

0

20

40

60

80

100

120

140

160

180

200

0 60 120 180 240 300 360 420 480

Tem

pera

ture

(°C

)

Time (min)

Temperatures increase in panel 6t15-P6

t17-P6

t27-P6

t32-P6

180°C

t15

t17

t27 t32

Figure 16. Temperature increase evolutions in the thermocouples of panel P6, soil-cement blocks with plasteron both surfaces.

-20

-15

-10

-5

0

5

10

0 500 1000 1500 2000 2500 3000

Dis

pla

cem

ents

(m

m)

X (mm)

Displacements at level 1 0 min

20 min

40 min

60 min

80 min

100 min

120 min

220 min

414 min

Level 1

Outside the furnace

Inside the furnace

Figure 17. Evolution of the measured horizontal displacements profiles for the Kraftterra panels.

SOIL-CEMENT AND KRAFTTERRA CEBS

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 14: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

-20

-15

-10

-5

00 500 1000 1500 2000 2500 3000

Dis

pla

cem

ents

(m

m)

X (mm)Displacements at level 4 0 min

20 min

40 min

60 min

80 min

100 min

120 min

220 min

414 min

Level 4 Inside the furnace

Figure 18. Evolution of the measured horizontal displacements profiles for the soil-cement panels.

500

700

900

1100

1300

1500

1700

1900

2100

2300

2500

-30 -20 -10 0 10 20

Dis

plac

emen

ts (

mm

)

X (mm)

Displacements at line B

0 min

20 min

40 min

60 min

80 min

100 min

120 min

220 min

414 min

Line B

Inside the furnace Outside the furnace

Figure 19. Evolution of the measured horizontal displacements profiles for the non-plastered walls withKraftterra and soil-cement blocks.

M. BUSON ET AL.

points closest to the interfaces between different materials, namely points H, J and L on the soil-cementpanels, showed larger displacements than those for the Kraftterra panels.

The concave shape of the deformed wall, which deviated towards the inner part of the furnacebecause of the thermal gradients across the wall thickness in the early stages of the heatingprocess, is consistent with the observations that have been made in other similar tests. At thelater stages, the deformed shape evolved in the opposite direction because of a reversal of thethermal gradients within the wall, which occurs because of the thermal inertia of the wall (seeFigures 17 and 18).

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 15: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

SOIL-CEMENT AND KRAFTTERRA CEBS

7. FINAL COMMENTS

The application of this constructive technique is increasing in many countries, both in developingregions and in developed regions where sustainable solutions are enforced and optimised.The mechanical characteristics of CEBs may guarantee its use in certain applications, such asdwellings, in which structural safety and comfort are required. Walls made of Kraftterra blocks,which incorporate cement sacks, has raised doubts regarding their fire resistance, limiting theirapplication in practice.

With the fire resistance test performed, it is concluded that the inclusion of Kraft paper fibresfrom the recycling of cement bags in the production of CEBs resulted in panel elements withadequate performance and fire resistance. The test results confirm that the walls with KraftterraCEBs, with or without plaster, can be used as partition walls.

As discussed, all of the walls built with CEBs composed of soil-cement and Kraftterra showedadequate performance and fire resistance. For all of the panels, the stability was guaranteed, andthe different compositions guaranteed wall integrity until the conclusion of the ISO fire test(120min duration). The walls also prevented the passage of flames, smoke and hot gases. Inregard to thermal insulation, the wall with Kraftterra CEBs showed a better performance.

It is noteworthy that for all of the walls (made with soil-cement and Kraftterra CEB blocks),the temperature rise on the external face was far below the values recommended in thestandards. The performance of the studied walls made with CEBs was comparatively betterthan required for other types of partition masonry walls.

REFERENCES

1. Silveira D, Varum H, Costa A, Martins T, Pereira H, Almeida J. Mechanical properties of adobe bricks in ancientconstructions. Construct Build Mater 2012; 28(1):36–44.

2. Rigassi V. Compressed earth blocks—manual of production. CRATerre-EAG, vol.1, GATE/GTZ/BASIN,German, 1985.

3. Yetgin S, Çavdar O, Çavdar A. The effects of the fiber contents on the mechanic properties of the adobes. ConstructBuild Mater 2008; 22:222–227.

4. Ngowi AB. Improving the traditional earth construction: a case study of Botswana. Construct Build Mater1997; 11:1–7.

5. Ghavami K, Toledo Filho RD, Barbosa NP. Behaviour of composite soil reinforced with natural fibres. Cement andConcrete Composites 1999; 21:39–48.

6. Binici H, Aksogan H, Shah T. Investigation of fibre reinforced mud brick as a building material. Construct BuildMater 2005; 19:313–318.

7. SNIC. Sindicato Nacional da Indústria do Cimento. Relatório Anual 2008–9. http://www.snic.org.br/pdf/relat2008-9web.pdf (webpage visited in Nov/2009).

8. Richardson L. Fire losses in selected property classifications of non-residential, commercial and residentialwood buildings. Part 1: hotels/motels and care homes for aged. Fire and Materials 2007; 31(2):97–123.

9. Buson MA. Autoconstrução com tijolos prensados de solo estabilizado (1st edn). Faculdade de Arquitetura e Urbanismoda Universidade de Brasília: Brasília, Brazil, 2007.

10. Buson M, Varum H, Sposto RM. Viability analysis of using cellulose pulp recycled from cement sacks inthe production of compressed earth blocks. 37th IAHS World Congress on Housing Science: Design, technol-ogy, refurbishment and management of buildings—Santander, Cantabria, Espanha, 26–29 October 2010.

11. Buson M, Varum H, Sposto RM. Performance improvement of adobe blocks with addition of cellulose pulpderived from cement sacks recycling—KRAFTTERRA. 15th International Conference on Composite Structures,ICCS15, FEUP, University of Porto, Porto, Portugal, 15–17 June 2009.

12. Barbosa NP, Matonne R, Mesbah A. Blocos de Concreto de Terra: Uma Opção Interessante Para aSustentabilidade da Construção. Proceedings of the 44º Congresso Brasileiro de Concreto, Belo Horizonte,Brazil, 2002.

13. Tavares RM. An analysis of the fire safety codes in Brazil: is the performance-based approach the best practice? FireSafety Journal 2009; 44:749–755.

14. Associação Brasileira deNormas Técnicas—ABNT.NBR 5628—Componentes construtivos estruturais—Determinaçãoda resistência ao fogo. 2001, Rio de Janeiro, Brazil.

15. Associação Brasileira de Normas Técnicas—ABNT. NBR 14432—Exigências de resistência ao fogo de elementosconstrutivos de edificações—Procedimento. 2001, Rio de Janeiro, Brazil.

16. Associação Brasileira de Normas Técnicas—ABNT. NBR 10636—Paredes divisórias sem função estrutural—Determinação da resistência ao fogo. 2001, Rio de Janeiro, Brazil.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam

Page 16: Fire resistance of walls made of soil-cement and ...cristina/RREst/Aulas_Apresentacoes/07... · Fire resistance of walls made of soil-cement and Kraftterra compressed earth blocks

M. BUSON ET AL.

17. CEN, European committee for standardization. EN1996-1-2, Eurocode 6—design of masonry structures—Part1–2: general rules—structural fire design. Brussels, 2005.

18. CEN, European committee for standardization. EN 1363-1, Fire resistance tests—Part 1: general requirements. 1999.Brussels, Belgium.

19. CEN, European committee for standardization. EN 1364-1, Fire resistance tests for non-load-bearing elements—Part1: walls. 1999. Brussels, Belgium.

20. CBESP, Corpo de Bombeiros do Estado de São Paulo: Instrução Técnica n. 08—Segurança estrutural nasedificações / Resistência ao fogo dos elementos de construção. Secretaria de Estado dos Negócios daSegurança Pública. São Paulo, Brazil, 2004.

21. Manzello S, Gann R, Kukuck S, Prasad K, Jones W. Real fire performance of partition assemblies. Fire andMaterials 2005; 29(6):351–366.

Copyright © 2012 John Wiley & Sons, Ltd. Fire Mater. (2012)DOI: 10.1002/fam