FIRE FIGHING SYSTEM
STAGE-II
BY- SUDAMA RAM
CONTENTS 1. FIRE PUMP HOUSE
2. FIRE BOOSTER PUMP HOUSE
3. FIRE FOAM PUMP HOUSE
4. FIRE ALARM CONTROL PANELS
5. PANEL MAIN CARDS/EQUIPMENTS
6. INSTRUMENTS USED IN FIELD
7. SIMPLE WIRING DIAGRAM OF INPUT DEVICES
8. LOGIC FOR WATER SPRAY IN CABLE GALLARY
9. WATER SPRAY SYSTEM IN COVEYOR
10. INERGEN GAS YSTM
FIRE PUMP HOUSE STAGE-II
MAIN PUMPS HYDRANTS PUMPS
ELECTRICAL HYDRANT PUMP-1 HM-1START 8.5 KG/CM2 F
ELECTRICAL HYDRANT PUMP-2 HM-2 START 8.0 KG/CM2 F
ELECTRICAL HYDRANT PUMP-3 HM-3START 7.5 KG/CM2 F
DIESEL HYDRANT PUMP-4 HD-1 START 7.0 KG/CM2 F
SPRAY PUMPS
ELECTRICAL WATER SPRAY PUMP-1 WS-M-1
START 9.50 KG/CM2 F
DIESEL WATER SPRAY PUMP-1 WS-D-1
START 9.0 KG/CM2 F
FIRE PUMP HOUSE STAGE-II
MAIN PUMPS
JOCKY PUMPS
JOCKY PUMP MOTOR –1 JPM-1
JOCKY PUMP MOTOR –2 JPM-2
FIRE PUMP HOUSE STAGE-II
MAIN PUMPS
HI-HI
LO
LO-LO
HPT
JOCKY PUMPS TAKE START ON THE LVL OF TANK
COMPRESSORS
AIR COMPRESSOR MOTOR-1 AC-1
START 10.2 KG/CM2 F OF HPT PRESSURE
AIR COMPRESSOR MOTOR-2 AC-2
START 10.0 KG/CM2 F OF HPT PRESSURE
FIRE BOOSTER PUMP HOUSE
• ELECTRICAL BOOSTER PUMP
START: 11.5 KG/CM2 F
• DIESEL BOOSTER PUMPSTART: 11 KG/CM2 F
THESE PUMPS MAINTAIN PR. AT BUNKER LEVEL AND 72.0 METER LEVEL.
FOAM PUMP HOUSE
• FOAM PUMPS ARE FOR SAFETY OF LDO TANK
• ELECTRICAL FOAM PUMP
• DIESEL FOAM PUMP
BOTH PUMPS OPERATED THROUGH GE FANUC MICRO PLC.
WATER AND FOAM RATIO IS 97:3
INSTRUMENTS USED IN FIRE FIGHTING SYSTEM
• PRESSURE SWITCHES (INDFOS)• PRSSURE GAUGES• SOLENOID VALVES (ROTEX)• IAM (INDIVIDUAL ADRESSBLE MODULE)• RELAY IAM• RIAM T• MULTI SENSOR SMOKE DETECTOR(MS)• OPTICAL SMOKE DETECTOR(OSD)
•RESPONSE INDICATOR
•HEAT DETECTOR(HD)
•LINE ISOLATOR
•INFRA RED DETECTOR(IRD)
•LINEAR HEAT SENSING CABLE (LHS)
•SIREN& HOOTER
•EVACUATION HOOTER
•MANUAL CALL POINT(MCP)
•ABORT SWITCH
•MANUAL RELEASE SWITCH
INSTRUMENTS USED IN INERGEN SYSTEM
• SUPRESSION RELEASE POWER(SRP)
• COIL SUPPRESSION MODULE (CSM)
• DIRECTIONAL VALVES (DRV)
• ACTUATORS (USED ON DRV AND ON CYLINDERS)
FIRE ALARM CONTROL PANELS
• FACP-1 U #3 MASTER PANEL,HAVING GRAPHIC COMMAND CENTRE07 LOOPS (1 LOOP 250 POINT CAPACITY)
• FACP-2 U#4 - 05 LOOPS• FACP-3 CHP- HAVING GRAPHIC COMMAND
CENTRE-03 LOOPS• FACP-4 SWITCH YARD COTROL ROOM-01
LOOP• FACP-5 FIRE REAPEATER PANEL (FIRE
STATION)
FACP PANEL CARDSXPS POWER SUPPLY
• SPS SPECIAL POWER SUPPLY WITH LOOP CARD • CPU CARD• INTER FACE CARD• MEDIA CARD• LOOP CARD• RELAY CARD• HOA MODULE• DISPLAY CARD• SMALL PRINTER • BAC PAC CARD(FOR COMMUNCATION WITH MAX DNA)
PANEL HAVING ONE SET OF BATTERY BANK AND TWO BATTERY CHARGER
230V AC POWER FROM 27.0 M BOILER MCC
WORKING PRINCIPLE OF SPRAY SYSTEM IN CABLE GALARY
• IN SPRAY AREA
ONE MS
ONE OSFACP
RIAMSOLENOIDDV
OPEN
F/B OF SPRAY ON
PS/IAM
• IN SPRAY AREA WHERE QBD IS USED
DV
PS/IAMFACP
QBD BROKEN
FIRE ALARM
SPRAY ON
EQUIPMENT
SPRAY
DV OPEN
PS/IAM
WORKING OF SPRAY IN TRANSFORMER AREA
SPRAY THROUGH LHS IN CABLE GALLARY
• IN SPRAY AREAFACP
RIAMSOLENOIDDV
OPEN
F/B OF SPRAY ON
PS/IAM
LHS CABLE IAM
ELR
FIRE ALARM THROUGH FACP
MS
FACP
FIRE ALARM LED GLOW & MASSEGE WILL
APPEAR ON SCREEN & GLOBAL HOOTER WILL
START
OS
FACP
INERGEN GAS SYSTEMFIVE AREAS ARE PROTECTED BY INERGEN GAS SYSTEM
• EER U#3 (97 CYLINDERS ARE USED) 03 DISCHARGE LINE WITH 6/6 NOZZLE)
• EER U#4 (97 CYLINDERS ARE USED) 03 DISCHARGE LINE WITH 6/6 NOZZLE)
• UCR & PADO ROOM 105 CYLINDER ARE USED
8/8 NOZZLE,03 LINE• UPS & BATTERY CHARGERU#3(44 CYLINDERS)
02 LINE ,4/4 NOZZLES• UPS & BATTERY CHARGERU#4(44 CYLINDERS)
02 LINE ,4/4 NOZZLES
INERGEN GAS SYSTEMTOTAL NO. OF CYLINDERS 210
• MAIN BANK 105 CYLINDER• STAND BY BANK 105 CYLINDER• NO. OF ACTUATOR ON CYLIDER EA1-EA12• NO. OF ACTUATOR ON DRV 13• NO. OF PR. SWITCHES 05• NO. OF PILOT CYLINDER 12• CYLINDER PR. WRITTEN 3000PSI• ONE PILOT CYLIDER CAN OPERATE 40
CYLINDER• EACH CYLINDER IS EQUIPPD WITH GOOD CAP FITTING & ASH CRAFT PR. GAUGE.
INERGEN SWITCH POSITION IN FACP-1
M.BANK STD. BANK
SW-1
A M A M
A M A M
A M
EERU#3 EER U#4
UPS & BATTERY
CHARGER ROOM
U#3 U#4
UCR & PADO ROOM
WORKING OF INERGEN SYSTEM
ONE MS
ONE OS
FACP-1
•FIRE ALARM APPEAR IN FACP-1.•GLOBAL HOOTER ON.•ELECTRIC SIREN ON.•EVACUATION HOOTER ON.•TRIP COMMAND TO UNIT& CLOSE COMMMAND TO AC DAMPERS.•AFTER ONE MINUTE COUNT DOWN INERGEN WILL RELEASE.INERGEN RELEASE INDICATION TO FACP-1.
FIRE SYSTEM OF CHP AREA
• CHP CONVEYORS 20A/B, 21A/B, 22A/B, 23A/B , 24A/B, 25A/B, 26A/B , 27A/B, 28A/B, 30, CRUSHER HOUSE AND ALL TP ARE PROTECTED WITH SPRAY SYSTEM.
• MCC1, MCC2, MCC3 HAVE FIRE DETECTION SYSTEM ONLY.
• IR DETECTORS ARE INSTALLED IN 21A/B, 24A/B, 25A/B, 27A/B CONVEYORS.
• FIRE IS SENSED BY LHS AND QBD IN CONVEYOR AREA.
• IN MCC AREA MULTI SENSORS ARE USED ONLY.
• IRD ARE USED TO SENSE FLAME AND SPARK ON THE BELT.
SPRAY IN CONVEYOR AREA
IAMIAN
IAM OF Z-1
IIAM
IAM OF Z-2
TP-1 TP-2
CONV. A
CONV.-B
IAM Z-3
QBD QBD
IN TP ONLY QBD IS USED
•WHEN LHS SHORTED OR QBD BROKEN DUE TO FIRE –IAM WILL OPERATED – SIGNAL GOES TO
FACP3– RIAM OPERATED– SOLENOID OPERATED SPRAY TAKE PLACE– SPRAY INDICATION IN FACP3
WIRING DIAGRAM OF IAM & LI
IAM MODULE
TO OTHER DEVICES
PS
FROM FACP 24VDC
ELR
LINE ISOLATOR
IDNET IN FROM PREVIOUS DEVICE
IDNET OUT TO NEXT DEVICE
+_
+_
_
+
DPSW
DPSW
DPSW
NCCOM
NO
NOT USED
++ _TO NEXT DEVICE
FROM PREVIOUS DEVICE
1
2
3
4
RIAM- T
DPSW
NCCOM
NO
NOT USED
++ _TO NEXT DEVICE
1
2
3
4
NOT USED
RIAM
WIRING DIAGRAM OF RIAM
FIRE WATER PUMP HOUSE SCHEMATIC DIAGRAM
AC1START 10. 2 KGF STOP 10.7 KGR
AC2 9.8 KGF STOP 10.7 KGR
FROM CW P/H
TANK 1 TANK 2
HM1 STAR
T 8.5KGF
JP1
WSM1
START9.5K
GF
HD1 STAR
T 7.0KGF
HM3 STAR
T 7.5KGF
HM2 START 8.0 KGF
WSD1 START 9.0KGF
JP1
HPT TO PLANT
HYDRANT BOOSTER PUMP HOUSE
PS START
11. 0 KGF
PS START 11. 50 KGF
DIESEL HYD. BOOS. PUMP-1
ELETRIC HYD. BOOS. PUMP-1
COMMON HEADER OF PLANT
TO 72 METER LEVEL AT MIN. 3.5 KG PR.
*HYDRANT BOOSTER IS CONTROLLED BY GE FANUC MICRO PLC
FOAM PUMP HOUSE
PROPORTIONAL MIXER 97:3(3 NO.)
DV
LDO TANK
FP M1
FP D1
FOAM TANK 1
FOAM TANK 2
HD
FOAM
WATER
*FIRE SENSED BY HEAT DETECTORS AND SENT TO FACP1 COMMAND SENT THROUGH RIAM TO PLC
PLC GENERATE COMMAND TO START FOAM P/Ps
WORKING PRINCIPLE OF HEAT DETECTOR
* HEAT DETECTOR SENSES HEAT OR RATE OF RISE IN THE AIR TEMPARATURE , BASICALLY IT CONSIST THERMISTER WHICH WORK ON NEGATIVE TEMP.
COFFICIENT OF RESISTENCE. WHEN TEMP. INCREASES, RESISTENCE DECREASES IN
THE DETECTER SO IT DRAW MORE CURRENT , WHEN INCREASE IN THE
CURRENT REACH THE PREDETERMINED VALUE THE DETECTOR GIVES THE
ALARM. .
WORKING PRINCIPLE OF OPTICAL SENSOR
* IT CONSIST INFRARED SOURCE WITH PEAK SPECTRAL EMISSION 880 NM. THE LED SOURCE AND THE DETECTOR ARE PLACED AT AN SPECTRALLY MATCHED ANGLE . WHEN NO SMOKE THE LIGHT
REFLECTED FROM CHAMBER WHICH SHOW SMALL CURRENT. IN CASE OF SMOKE DUE
TO SCATTERING OF LIGHT CURRENT GENERATION IS MORE, DUE TO THIS
VOLTAGE LEVEL REACH THE PRESET VOLTAGE VALUE CAUSES FIRE ALARM.
• FDA AND SPRAY IN TRANSFORMER AREA BY QBD
EQUIPMENT
TRANSFORMERQBD
PS/IAM
PS/IAM
DV
FIRE DETECTION
SPRAY ON
PG
• CABLE GALLERY SPRAY SYSTEM BY MS/OS
CABLE GALLERY
PS/IAM
DV
SPRAY ON
PG
FACP
RIAM/SV
• CABLE GALLERY SPRAY SYSTEM BY LHS
CABLE GALLERY
PS/IAM
DV
SPRAY ON
PG
FACP
RIAM/SV
LHS/IAM