FIRE FIGHING SYSTEM

STAGE-II

BY- SUDAMA RAM

Page 2: FIRE Fighting System in Power Plant_PPT

CONTENTS 1. FIRE PUMP HOUSE

    2.   FIRE BOOSTER PUMP HOUSE

3. FIRE FOAM PUMP HOUSE

4. FIRE ALARM CONTROL PANELS

5.   PANEL MAIN CARDS/EQUIPMENTS

6.   INSTRUMENTS USED IN FIELD

7.  SIMPLE WIRING DIAGRAM OF INPUT DEVICES

8.   LOGIC FOR WATER SPRAY IN CABLE GALLARY

9.   WATER SPRAY SYSTEM IN COVEYOR

10.   INERGEN GAS YSTM

 

Page 3: FIRE Fighting System in Power Plant_PPT

FIRE PUMP HOUSE STAGE-II

MAIN PUMPS HYDRANTS PUMPS

ELECTRICAL HYDRANT PUMP-1 HM-1START 8.5 KG/CM2 F

ELECTRICAL HYDRANT PUMP-2 HM-2 START 8.0 KG/CM2 F

ELECTRICAL HYDRANT PUMP-3 HM-3START 7.5 KG/CM2 F

DIESEL HYDRANT PUMP-4 HD-1 START 7.0 KG/CM2 F

Page 4: FIRE Fighting System in Power Plant_PPT

SPRAY PUMPS

ELECTRICAL WATER SPRAY PUMP-1 WS-M-1

START 9.50 KG/CM2 F

DIESEL WATER SPRAY PUMP-1 WS-D-1

START 9.0 KG/CM2 F

FIRE PUMP HOUSE STAGE-II

MAIN PUMPS

Page 5: FIRE Fighting System in Power Plant_PPT

JOCKY PUMPS

JOCKY PUMP MOTOR –1 JPM-1

JOCKY PUMP MOTOR –2 JPM-2

FIRE PUMP HOUSE STAGE-II

MAIN PUMPS

HI-HI

LO

LO-LO

HPT

JOCKY PUMPS TAKE START ON THE LVL OF TANK

Page 6: FIRE Fighting System in Power Plant_PPT

COMPRESSORS

AIR COMPRESSOR MOTOR-1 AC-1

START 10.2 KG/CM2 F OF HPT PRESSURE

AIR COMPRESSOR MOTOR-2 AC-2

START 10.0 KG/CM2 F OF HPT PRESSURE

Page 7: FIRE Fighting System in Power Plant_PPT

FIRE BOOSTER PUMP HOUSE

• ELECTRICAL BOOSTER PUMP

START: 11.5 KG/CM2 F

• DIESEL BOOSTER PUMPSTART: 11 KG/CM2 F

THESE PUMPS MAINTAIN PR. AT BUNKER LEVEL AND 72.0 METER LEVEL.

Page 8: FIRE Fighting System in Power Plant_PPT

FOAM PUMP HOUSE

• FOAM PUMPS ARE FOR SAFETY OF LDO TANK

• ELECTRICAL FOAM PUMP

• DIESEL FOAM PUMP

BOTH PUMPS OPERATED THROUGH GE FANUC MICRO PLC.

WATER AND FOAM RATIO IS 97:3

Page 9: FIRE Fighting System in Power Plant_PPT

INSTRUMENTS USED IN FIRE FIGHTING SYSTEM

• PRESSURE SWITCHES (INDFOS)• PRSSURE GAUGES• SOLENOID VALVES (ROTEX)• IAM (INDIVIDUAL ADRESSBLE MODULE)• RELAY IAM• RIAM T• MULTI SENSOR SMOKE DETECTOR(MS)• OPTICAL SMOKE DETECTOR(OSD)

Page 10: FIRE Fighting System in Power Plant_PPT

•RESPONSE INDICATOR

•HEAT DETECTOR(HD)

•LINE ISOLATOR

•INFRA RED DETECTOR(IRD)

•LINEAR HEAT SENSING CABLE (LHS)

•SIREN& HOOTER

•EVACUATION HOOTER

•MANUAL CALL POINT(MCP)

•ABORT SWITCH

•MANUAL RELEASE SWITCH

Page 11: FIRE Fighting System in Power Plant_PPT

INSTRUMENTS USED IN INERGEN SYSTEM

• SUPRESSION RELEASE POWER(SRP)

• COIL SUPPRESSION MODULE (CSM)

• DIRECTIONAL VALVES (DRV)

• ACTUATORS (USED ON DRV AND ON CYLINDERS)

Page 12: FIRE Fighting System in Power Plant_PPT

FIRE ALARM CONTROL PANELS

• FACP-1 U #3 MASTER PANEL,HAVING GRAPHIC COMMAND CENTRE07 LOOPS (1 LOOP 250 POINT CAPACITY)

• FACP-2 U#4 - 05 LOOPS• FACP-3 CHP- HAVING GRAPHIC COMMAND

CENTRE-03 LOOPS• FACP-4 SWITCH YARD COTROL ROOM-01

LOOP• FACP-5 FIRE REAPEATER PANEL (FIRE

STATION)

Page 13: FIRE Fighting System in Power Plant_PPT

FACP PANEL CARDSXPS POWER SUPPLY

• SPS SPECIAL POWER SUPPLY WITH LOOP CARD • CPU CARD• INTER FACE CARD• MEDIA CARD• LOOP CARD• RELAY CARD• HOA MODULE• DISPLAY CARD• SMALL PRINTER • BAC PAC CARD(FOR COMMUNCATION WITH MAX DNA)

PANEL HAVING ONE SET OF BATTERY BANK AND TWO BATTERY CHARGER

230V AC POWER FROM 27.0 M BOILER MCC

Page 14: FIRE Fighting System in Power Plant_PPT

WORKING PRINCIPLE OF SPRAY SYSTEM IN CABLE GALARY

• IN SPRAY AREA

ONE MS

ONE OSFACP

RIAMSOLENOIDDV

OPEN

F/B OF SPRAY ON

PS/IAM

Page 15: FIRE Fighting System in Power Plant_PPT

• IN SPRAY AREA WHERE QBD IS USED

DV

PS/IAMFACP

QBD BROKEN

FIRE ALARM

SPRAY ON

EQUIPMENT

SPRAY

DV OPEN

PS/IAM

WORKING OF SPRAY IN TRANSFORMER AREA

Page 16: FIRE Fighting System in Power Plant_PPT

SPRAY THROUGH LHS IN CABLE GALLARY

• IN SPRAY AREAFACP

RIAMSOLENOIDDV

OPEN

F/B OF SPRAY ON

PS/IAM

LHS CABLE IAM

ELR

Page 17: FIRE Fighting System in Power Plant_PPT

FIRE ALARM THROUGH FACP

MS

FACP

FIRE ALARM LED GLOW & MASSEGE WILL

APPEAR ON SCREEN & GLOBAL HOOTER WILL

START

OS

FACP

Page 18: FIRE Fighting System in Power Plant_PPT

INERGEN GAS SYSTEMFIVE AREAS ARE PROTECTED BY INERGEN GAS SYSTEM

• EER U#3 (97 CYLINDERS ARE USED) 03 DISCHARGE LINE WITH 6/6 NOZZLE)

• EER U#4 (97 CYLINDERS ARE USED) 03 DISCHARGE LINE WITH 6/6 NOZZLE)

• UCR & PADO ROOM 105 CYLINDER ARE USED

8/8 NOZZLE,03 LINE• UPS & BATTERY CHARGERU#3(44 CYLINDERS)

02 LINE ,4/4 NOZZLES• UPS & BATTERY CHARGERU#4(44 CYLINDERS)

02 LINE ,4/4 NOZZLES

Page 19: FIRE Fighting System in Power Plant_PPT

INERGEN GAS SYSTEMTOTAL NO. OF CYLINDERS 210

• MAIN BANK 105 CYLINDER• STAND BY BANK 105 CYLINDER• NO. OF ACTUATOR ON CYLIDER EA1-EA12• NO. OF ACTUATOR ON DRV 13• NO. OF PR. SWITCHES 05• NO. OF PILOT CYLINDER 12• CYLINDER PR. WRITTEN 3000PSI• ONE PILOT CYLIDER CAN OPERATE 40

CYLINDER• EACH CYLINDER IS EQUIPPD WITH GOOD CAP FITTING & ASH CRAFT PR. GAUGE.

Page 20: FIRE Fighting System in Power Plant_PPT

INERGEN SWITCH POSITION IN FACP-1

M.BANK STD. BANK

SW-1

A M A M

A M A M

A M

EERU#3 EER U#4

UPS & BATTERY

CHARGER ROOM

U#3 U#4

UCR & PADO ROOM

Page 21: FIRE Fighting System in Power Plant_PPT

WORKING OF INERGEN SYSTEM

ONE MS

ONE OS

FACP-1

•FIRE ALARM APPEAR IN FACP-1.•GLOBAL HOOTER ON.•ELECTRIC SIREN ON.•EVACUATION HOOTER ON.•TRIP COMMAND TO UNIT& CLOSE COMMMAND TO AC DAMPERS.•AFTER ONE MINUTE COUNT DOWN INERGEN WILL RELEASE.INERGEN RELEASE INDICATION TO FACP-1.

Page 22: FIRE Fighting System in Power Plant_PPT

FIRE SYSTEM OF CHP AREA

• CHP CONVEYORS 20A/B, 21A/B, 22A/B, 23A/B , 24A/B, 25A/B, 26A/B , 27A/B, 28A/B, 30, CRUSHER HOUSE AND ALL TP ARE PROTECTED WITH SPRAY SYSTEM.

• MCC1, MCC2, MCC3 HAVE FIRE DETECTION SYSTEM ONLY.

• IR DETECTORS ARE INSTALLED IN 21A/B, 24A/B, 25A/B, 27A/B CONVEYORS.

• FIRE IS SENSED BY LHS AND QBD IN CONVEYOR AREA.

• IN MCC AREA MULTI SENSORS ARE USED ONLY.

• IRD ARE USED TO SENSE FLAME AND SPARK ON THE BELT.

Page 23: FIRE Fighting System in Power Plant_PPT

SPRAY IN CONVEYOR AREA

IAMIAN

IAM OF Z-1

IIAM

IAM OF Z-2

TP-1 TP-2

CONV. A

CONV.-B

IAM Z-3

QBD QBD

IN TP ONLY QBD IS USED

•WHEN LHS SHORTED OR QBD BROKEN DUE TO FIRE –IAM WILL OPERATED – SIGNAL GOES TO

FACP3– RIAM OPERATED– SOLENOID OPERATED SPRAY TAKE PLACE– SPRAY INDICATION IN FACP3

Page 24: FIRE Fighting System in Power Plant_PPT

WIRING DIAGRAM OF IAM & LI

IAM MODULE

TO OTHER DEVICES

PS

FROM FACP 24VDC

ELR

LINE ISOLATOR

IDNET IN FROM PREVIOUS DEVICE

IDNET OUT TO NEXT DEVICE

+_

+_

_

+

DPSW

DPSW

Page 25: FIRE Fighting System in Power Plant_PPT

DPSW

NCCOM

NO

NOT USED

++ _TO NEXT DEVICE

FROM PREVIOUS DEVICE

1

2

3

4

RIAM- T

DPSW

NCCOM

NO

NOT USED

++ _TO NEXT DEVICE

1

2

3

4

NOT USED

RIAM

WIRING DIAGRAM OF RIAM

Page 26: FIRE Fighting System in Power Plant_PPT

FIRE WATER PUMP HOUSE SCHEMATIC DIAGRAM

AC1START 10. 2 KGF STOP 10.7 KGR

AC2 9.8 KGF STOP 10.7 KGR

FROM CW P/H

TANK 1 TANK 2

HM1 STAR

T 8.5KGF

JP1

WSM1

START9.5K

GF

HD1 STAR

T 7.0KGF

HM3 STAR

T 7.5KGF

HM2 START 8.0 KGF

WSD1 START 9.0KGF

JP1

HPT TO PLANT

Page 27: FIRE Fighting System in Power Plant_PPT

HYDRANT BOOSTER PUMP HOUSE

PS START

11. 0 KGF

PS START 11. 50 KGF

DIESEL HYD. BOOS. PUMP-1

ELETRIC HYD. BOOS. PUMP-1

COMMON HEADER OF PLANT

TO 72 METER LEVEL AT MIN. 3.5 KG PR.

*HYDRANT BOOSTER IS CONTROLLED BY GE FANUC MICRO PLC

Page 28: FIRE Fighting System in Power Plant_PPT

FOAM PUMP HOUSE

PROPORTIONAL MIXER 97:3(3 NO.)

DV

LDO TANK

FP M1

FP D1

FOAM TANK 1

FOAM TANK 2

HD

FOAM

WATER

*FIRE SENSED BY HEAT DETECTORS AND SENT TO FACP1 COMMAND SENT THROUGH RIAM TO PLC

PLC GENERATE COMMAND TO START FOAM P/Ps

Page 29: FIRE Fighting System in Power Plant_PPT

WORKING PRINCIPLE OF HEAT DETECTOR

* HEAT DETECTOR SENSES HEAT OR RATE OF RISE IN THE AIR TEMPARATURE , BASICALLY IT CONSIST THERMISTER WHICH WORK ON NEGATIVE TEMP.

COFFICIENT OF RESISTENCE. WHEN TEMP. INCREASES, RESISTENCE DECREASES IN

THE DETECTER SO IT DRAW MORE CURRENT , WHEN INCREASE IN THE

CURRENT REACH THE PREDETERMINED VALUE THE DETECTOR GIVES THE

ALARM. .

Page 30: FIRE Fighting System in Power Plant_PPT

WORKING PRINCIPLE OF OPTICAL SENSOR

* IT CONSIST INFRARED SOURCE WITH PEAK SPECTRAL EMISSION 880 NM. THE LED SOURCE AND THE DETECTOR ARE PLACED AT AN SPECTRALLY MATCHED ANGLE . WHEN NO SMOKE THE LIGHT

REFLECTED FROM CHAMBER WHICH SHOW SMALL CURRENT. IN CASE OF SMOKE DUE

TO SCATTERING OF LIGHT CURRENT GENERATION IS MORE, DUE TO THIS

VOLTAGE LEVEL REACH THE PRESET VOLTAGE VALUE CAUSES FIRE ALARM.

Page 31: FIRE Fighting System in Power Plant_PPT

• FDA AND SPRAY IN TRANSFORMER AREA BY QBD

EQUIPMENT

TRANSFORMERQBD

PS/IAM

PS/IAM

DV

FIRE DETECTION

SPRAY ON

PG

Page 32: FIRE Fighting System in Power Plant_PPT

• CABLE GALLERY SPRAY SYSTEM BY MS/OS

CABLE GALLERY

PS/IAM

DV

SPRAY ON

PG

FACP

RIAM/SV

Page 33: FIRE Fighting System in Power Plant_PPT

• CABLE GALLERY SPRAY SYSTEM BY LHS

CABLE GALLERY

PS/IAM

DV

SPRAY ON

PG

FACP

RIAM/SV

LHS/IAM