field processing methods fo transformer dry out

42
Field Processing Field Processing Methods for Methods for Transformer Transformer Dry out Dry out by Derek Baranowski by Derek Baranowski

Upload: lbk50

Post on 25-Jan-2016

22 views

Category:

Documents


2 download

DESCRIPTION

Methods to remove and to dry out transformer oils in field

TRANSCRIPT

Page 1: Field Processing Methods Fo Transformer Dry Out

Field Processing Field Processing Methods for Methods for Transformer Transformer

Dry outDry outby Derek Baranowski by Derek Baranowski

Page 2: Field Processing Methods Fo Transformer Dry Out

1. If water is removed from the oil only:A large percentage of the total water in the systemwill still remain.After the transformer is returned to service, water in the insulation will migrate to the drier oil until equilibrium is met and the transformer will test wet.

2. The rate of aging of the cellulose materials is directly proportional to the water content. That is if water content is doubled from 1 to 2 percent, the life is halved.

3. Low water content of the solid insulation permits greater extremes in temperature cycling without impairing the dielectric integrity of the system.

Importance of Removing Water from the Insulation

Page 3: Field Processing Methods Fo Transformer Dry Out

Factors Affecting Water Content of the Insulation

Water may be adsorbed in the solid insulation from:• Exposure to atmosphere during installation and

inspections.• From aging of the paper.• From leaks.• Ingress through the oil expansion system.• Water remaining from the manufacturing of the

transformer may also vary.

Water may be adsorbed in the solid insulation from:• Exposure to atmosphere during installation and

inspections.• From aging of the paper.• From leaks.• Ingress through the oil expansion system.• Water remaining from the manufacturing of the

transformer may also vary.

Page 4: Field Processing Methods Fo Transformer Dry Out

Importance of Removing Water from the

Insulation• Water in the transformer will

seek equilibrium throughout the entire insulation system including the oil and the insulation.

• Data shows that there is a relationship between the amount of water in the oil and the amount in the paper insulation.

• Although this relationship exists, the paper has a higher tendency to hold water than the oil – so more of the water resides there.

Where is the water?

Page 5: Field Processing Methods Fo Transformer Dry Out

• Factors Affecting the Rate of Insulation Drying –Things We Can’t Change

• In a transformer there are generally different insulation elements, differing in thickness and nature (board, paper tape or sheet).

• Drying out times in the inside layers depend on the nature of the material and on the path along which the water must travel to reach the surface.

• Water is removed from the exterior surfaces first and sucked away by the vacuum pumps.

• Water in the inside layers migrates to the surface (called diffusion).

• In a transformer there are generally different insulation elements, differing in thickness and nature (board, paper tape or sheet).

• Drying out times in the inside layers depend on the nature of the material and on the path along which the water must travel to reach the surface.

• Water is removed from the exterior surfaces first and sucked away by the vacuum pumps.

• Water in the inside layers migrates to the surface (called diffusion).

Page 6: Field Processing Methods Fo Transformer Dry Out

• Factors Affecting the Rate of Insulation Drying –Things We Can Change

• Speed and efficiency at which heat is added to the system.

• Minimizing heat loss to the surroundings.

• The pumping speed of the vacuum pumping system.

• Size of the vacuum hose.• Vapor traps to trap moisture and oil

from entering the vacuum pumps.

• Speed and efficiency at which heat is added to the system.

• Minimizing heat loss to the surroundings.

• The pumping speed of the vacuum pumping system.

• Size of the vacuum hose.• Vapor traps to trap moisture and oil

from entering the vacuum pumps.

Page 7: Field Processing Methods Fo Transformer Dry Out

Methods of Drying Transformer Insulation

• Hot Air.• Oil Circulation . • Vacuum Only (with or without a cold trap).• Heat and Vacuum (with or without a cold

trap).• On Line Systems

• Hot Air.• Oil Circulation . • Vacuum Only (with or without a cold trap).• Heat and Vacuum (with or without a cold

trap).• On Line Systems

Page 8: Field Processing Methods Fo Transformer Dry Out

Why Add Heat?• For the water in

the transformer to turn into vapor (change phase) heat is required just to allow the phase change.

• The moisture leaving the transformer takes this heat with it.

Why Add Heat?• For the water in

the transformer to turn into vapor (change phase) heat is required just to allow the phase change.

• The moisture leaving the transformer takes this heat with it.

Temperature Temperature –– the key to success!the key to success!

Page 9: Field Processing Methods Fo Transformer Dry Out

Why We Add Heat• It takes 143.4 btu to turn 1 lb of ice

into water • It takes 970.3 btu to turn 1 lb of

water into steam • It takes 1220 btu to turn 1 lb of ice

directly into steam (sublimation)(All values for atmospheric pressure)

Why We Add Heat• It takes 143.4 btu to turn 1 lb of ice

into water • It takes 970.3 btu to turn 1 lb of

water into steam • It takes 1220 btu to turn 1 lb of ice

directly into steam (sublimation)(All values for atmospheric pressure)

Temperature Temperature –– the key to success!the key to success!

Page 10: Field Processing Methods Fo Transformer Dry Out

Why We Add Heat• The heat required for the phase

change of the water in the transformer comes from the surrounding oil and transformer parts.

• As heat moves from the oil into the water, the temperature of the oil and transformer drops.

• Therefore replacement heat is added by continuously reheating the oil and pumping it into the transformer.

• If the heat is not replaced, eventually freezing can occur.

Why We Add Heat• The heat required for the phase

change of the water in the transformer comes from the surrounding oil and transformer parts.

• As heat moves from the oil into the water, the temperature of the oil and transformer drops.

• Therefore replacement heat is added by continuously reheating the oil and pumping it into the transformer.

• If the heat is not replaced, eventually freezing can occur.

Temperature Temperature –– the key to success!the key to success!

Page 11: Field Processing Methods Fo Transformer Dry Out

Why We Add Heat• Once freezing occurs, water must

go from solid to vapor without becoming liquid (sublimation).

• Sublimation requires more heat than vaporization so temperature continues to drop until the process stalls.

• When this happens the vacuum will get very good since no water vapor is being pumped.

• When the transformer is returned to service, the ice will melt and the insulating system will test ‘wet’.

Why We Add Heat• Once freezing occurs, water must

go from solid to vapor without becoming liquid (sublimation).

• Sublimation requires more heat than vaporization so temperature continues to drop until the process stalls.

• When this happens the vacuum will get very good since no water vapor is being pumped.

• When the transformer is returned to service, the ice will melt and the insulating system will test ‘wet’.

Haley’s CometA ball of frozen ice flying through space for

thousands of years because in the absence of heat, sublimation is a very slow

process.

Temperature Temperature –– the key to success!the key to success!

Page 12: Field Processing Methods Fo Transformer Dry Out

Why We Add Heat• If some heat is necessary . . . then the

more we add the better . . . Right?

Why We Add Heat• If some heat is necessary . . . then the

more we add the better . . . Right?• No, if we try to run too hot, transformer oil will

vaporize with the water and end up in the vacuum pumps. Transformer oil is a blend consisting of lighter and heavier fractions. The ‘light ends’ have a lower boiling temperature and will boil off.

• Higher temperatures increase risk of thermal damage to oil and equipment.

Temperature Temperature –– the key to success!the key to success!

Page 13: Field Processing Methods Fo Transformer Dry Out

The Methods

Page 14: Field Processing Methods Fo Transformer Dry Out

Methods of Drying – Hot Air

The Hot Air Method involves:• Heating the inlet air to 80-100 Deg C and delivering it to the

bottom of the transformer• Using enough heating and insulation to achieve an exit air

temperature of within 20 Deg C of the inletBenefits:• Can be used on transformers that can’t take vacuum.Limitations:• Not highly efficient• Oxygen accelerates aging of the insulation• Does not do a good job of removing water from deep within the

insulation.

The Hot Air Method involves:• Heating the inlet air to 80-100 Deg C and delivering it to the

bottom of the transformer• Using enough heating and insulation to achieve an exit air

temperature of within 20 Deg C of the inletBenefits:• Can be used on transformers that can’t take vacuum.Limitations:• Not highly efficient• Oxygen accelerates aging of the insulation• Does not do a good job of removing water from deep within the

insulation.

Page 15: Field Processing Methods Fo Transformer Dry Out
Page 16: Field Processing Methods Fo Transformer Dry Out

Methods of Drying – Oil Circulation

Oil Circulation involves:• Continuously circulating the entire volume of the

oil in the transformer through the purifier then back into the transformer.

• Oil is dried in the purifier vacuum chamber, then put back into the transformer where it picks up moisture from the insulation.

• Main Limitation: very slow

Oil Circulation involves:• Continuously circulating the entire volume of the

oil in the transformer through the purifier then back into the transformer.

• Oil is dried in the purifier vacuum chamber, then put back into the transformer where it picks up moisture from the insulation.

• Main Limitation: very slow

Page 17: Field Processing Methods Fo Transformer Dry Out
Page 18: Field Processing Methods Fo Transformer Dry Out

Methods of Drying – Vacuum Only

The Vacuum Only Technique:• Is used primarily to remove surface moisture adsorbed after the original

dryout of a unit. This would include water from the atmosphere or from human perspiration and respiration during inspection or assembly.

Precautions:• **It is important not to apply high vacuum suddenly on wet transformers

to prevent damage to the insulation caused by rapidly boiling off of water.

• The lowest temperature recommended for vacuum drying without heat is usually 10 Deg C for less than EHV (<345 kV) units and 20 Deg C for EHV to prevent ice formation

• Very good vacuums must be achieved because water removal is lessefficient at low temperatures because the vapor pressure of the water is so low.

The Vacuum Only Technique:• Is used primarily to remove surface moisture adsorbed after the original

dryout of a unit. This would include water from the atmosphere or from human perspiration and respiration during inspection or assembly.

Precautions:• **It is important not to apply high vacuum suddenly on wet transformers

to prevent damage to the insulation caused by rapidly boiling off of water.

• The lowest temperature recommended for vacuum drying without heat is usually 10 Deg C for less than EHV (<345 kV) units and 20 Deg C for EHV to prevent ice formation

• Very good vacuums must be achieved because water removal is lessefficient at low temperatures because the vapor pressure of the water is so low.

Page 19: Field Processing Methods Fo Transformer Dry Out
Page 20: Field Processing Methods Fo Transformer Dry Out

Vacuum – Leak Test

What is a leak test:– It is a check of the

transformer main tank, radiators, bushings etc. to verify that they will hold vacuum.

What is a leak test:– It is a check of the

transformer main tank, radiators, bushings etc. to verify that they will hold vacuum.

Page 21: Field Processing Methods Fo Transformer Dry Out

Vacuum – Leak Test

When to Perform a Leak Check?:• Prior to vacuum filling a transformer.

The fill process will not proceed until the leak test is acceptable.

Why?• To assure that rain, humidity or other

contamination is not drawn into the tank by vacuum to contaminate the environment.

When to Perform a Leak Check?:• Prior to vacuum filling a transformer.

The fill process will not proceed until the leak test is acceptable.

Why?• To assure that rain, humidity or other

contamination is not drawn into the tank by vacuum to contaminate the environment.

Page 22: Field Processing Methods Fo Transformer Dry Out

Typical Leak Test

Typical Procedure:• Apply vacuum and pull down to 1000 microns (1 Torr).• Valve off vacuum hose at the transformer.• Monitor vacuum level for 30 minutes and log reading

every 5 minutes.• After 30 minutes examine the total vacuum lost during

the test.• Acceptable loss is ≤ 700 microns for a new

transformer.• Acceptable loss is ≤ 1300 microns for a used or rebuilt

transformer.

Typical Procedure:• Apply vacuum and pull down to 1000 microns (1 Torr).• Valve off vacuum hose at the transformer.• Monitor vacuum level for 30 minutes and log reading

every 5 minutes.• After 30 minutes examine the total vacuum lost during

the test.• Acceptable loss is ≤ 700 microns for a new

transformer.• Acceptable loss is ≤ 1300 microns for a used or rebuilt

transformer.

Page 23: Field Processing Methods Fo Transformer Dry Out

Typical Automated Transformer Leak test

Page 24: Field Processing Methods Fo Transformer Dry Out

Methods of Drying – Heat and Vacuum

There are 3 common methods used to heat the transformer insulation:– Running current through the transformer windings while

under vacuum while pulling vacuum– Heating the oil in the transformer and then removing it

quickly to expose the insulation to vacuum– Lowering the oil level in the transformer and spraying a

heated portion of the oil over the insulation while pulling vacuum. This is the most widely used technique.

There are 3 common methods used to heat the transformer insulation:– Running current through the transformer windings while

under vacuum while pulling vacuum– Heating the oil in the transformer and then removing it

quickly to expose the insulation to vacuum– Lowering the oil level in the transformer and spraying a

heated portion of the oil over the insulation while pulling vacuum. This is the most widely used technique.

Page 25: Field Processing Methods Fo Transformer Dry Out
Page 26: Field Processing Methods Fo Transformer Dry Out

• Typical Manhole adapter with spray nozzle

• Typical vacuum connection using sudden pressure relief connection

(Vacuum only)

Page 27: Field Processing Methods Fo Transformer Dry Out

Use of Cold Traps in Drying Processes

Dry Ice and Acetone / Liquid Nitrogen

• Usually mounted on top of transformer• Uses either liquid nitrogen or a slurry or

dry ice and acetone to cool the thimble.• Water freezes to the thimble and

therefore can be collected for measurement.

• Protects vacuum pumps from water contamination and makes them more efficient since water is removed from the air stream before going through the pump.

Page 28: Field Processing Methods Fo Transformer Dry Out

Use of Cold Traps in Drying Processes

Cascade Cold Trap• Usually mounted in the trailer, in a

separate trailer or sits on the ground.

• Uses electric power and refrigeration to chill freeze plates.

• Water freezes to the plates providing the same benefits as the previous trap but without need for liquid N2, dry ice or acetone.

• Heated defrosting allows rapid ice thawing and speedy measurement.

Page 29: Field Processing Methods Fo Transformer Dry Out

Cold Traps - They’re not just for measuring moisture!

• One pound of water becomes 100 cubic feet of water vapor at 100 torr.

• One pound of water becomes 10,000 cubic feet of water vapor at 1 torr

• A cold trap condenses that vapor into a solid so that the vapor no longer has to be removed by the vacuum system.

Page 30: Field Processing Methods Fo Transformer Dry Out

Automated Moisture Monitor

The Automated Moisture Monitor is similar to the cold trap method except that the water is not collected. Instead, the moisture content of the air being pumped from the transformer, as well as the pumping speed and pressure, are used to calculate the number of pounds of water removed per hour plus a running total. If the amount of insulation and its initial moisture content are known, the amount of water removed can provide a sense of the insulation dryness.

Pros and Cons• Sometimes initial dryness and mass of insulation is difficult to

ascertain.• Equipment cost.• Benefit of having electronic monitoring and data gathering.

The Automated Moisture Monitor is similar to the cold trap method except that the water is not collected. Instead, the moisture content of the air being pumped from the transformer, as well as the pumping speed and pressure, are used to calculate the number of pounds of water removed per hour plus a running total. If the amount of insulation and its initial moisture content are known, the amount of water removed can provide a sense of the insulation dryness.

Pros and Cons• Sometimes initial dryness and mass of insulation is difficult to

ascertain.• Equipment cost.• Benefit of having electronic monitoring and data gathering.

Page 31: Field Processing Methods Fo Transformer Dry Out

Automated Moisture Monitor

Page 32: Field Processing Methods Fo Transformer Dry Out

On Line Systems

• Operate unattended while transformer in operation

• Take advantage of heat created by operation

• Can be used on non vacuum rated transformers

• Ideally suited for transformers where time is not of the essence.

Page 33: Field Processing Methods Fo Transformer Dry Out

On Line Systems

Page 34: Field Processing Methods Fo Transformer Dry Out

How wet is it still?

There are several methods of determining the estimated moisture content of a transformer that has undergone a drying process.

The following is a brief discussion of them most commonly used methods.

Page 35: Field Processing Methods Fo Transformer Dry Out

Vapor Pressure

Vapor Pressure measurement consists of isolating the transformer while under vacuum and monitoring vacuum decay over time (often 30 minutes) then using a Piper Chart to estimate water content.

Pros and Cons• Useful because can be made while a transformer is being

processed using vacuum gauges.• The measurement is an average for the entire system which

may not be a good indicator if the system is not in equilibrium.• Not always a good indicator of the dryness of the most

inaccessible locations in the insulation.

Vapor Pressure measurement consists of isolating the transformer while under vacuum and monitoring vacuum decay over time (often 30 minutes) then using a Piper Chart to estimate water content.

Pros and Cons• Useful because can be made while a transformer is being

processed using vacuum gauges.• The measurement is an average for the entire system which

may not be a good indicator if the system is not in equilibrium.• Not always a good indicator of the dryness of the most

inaccessible locations in the insulation.

Page 36: Field Processing Methods Fo Transformer Dry Out

Vapor Pressure

Typical Piper Chart

Page 37: Field Processing Methods Fo Transformer Dry Out

Rate of Water Collection in a Cold Trap

The Cold Trap method involves measuring the amount of water collected in a trap over a four-to-six hour period and the amount of water collected per hour is calculated. If the amount of insulation and its initial moisture content are known, the amount of water removed can provide a sense of the insulation dryness.

Pros and Cons• Sometimes initial dryness and mass of insulation is difficult to

ascertain.• Must have a cold trap available that efficiently traps the majority

of the water so it can be measured.• Collecting the water in a trap prevents it from collecting in the

vacuum pump.

The Cold Trap method involves measuring the amount of water collected in a trap over a four-to-six hour period and the amount of water collected per hour is calculated. If the amount of insulation and its initial moisture content are known, the amount of water removed can provide a sense of the insulation dryness.

Pros and Cons• Sometimes initial dryness and mass of insulation is difficult to

ascertain.• Must have a cold trap available that efficiently traps the majority

of the water so it can be measured.• Collecting the water in a trap prevents it from collecting in the

vacuum pump.

Page 38: Field Processing Methods Fo Transformer Dry Out

Power Factor

Power Factor has been used for many decades to assess the drying process of transformers using low voltage test or by the use of probes and models to assess the condition of the solid insulation.

Pros and Cons• Can be used for acceptance testing and at completion of field

drying after oil filling to ensure a dry unit.• Can be used to detect pockets of water that may be deeply

imbedded that may be missed by other methods that rely on equilibrium conditions to be accurate.

Power Factor has been used for many decades to assess the drying process of transformers using low voltage test or by the use of probes and models to assess the condition of the solid insulation.

Pros and Cons• Can be used for acceptance testing and at completion of field

drying after oil filling to ensure a dry unit.• Can be used to detect pockets of water that may be deeply

imbedded that may be missed by other methods that rely on equilibrium conditions to be accurate.

Page 39: Field Processing Methods Fo Transformer Dry Out

Vacuum Endpoint and Time

The Use of Vacuum Endpoint and Time consists of pulling vacuum until a decided vacuum endpoint is achieved and then maintaining that vacuum for a certain time period.

Pros and Cons• Low cost.• Must be sure transformer core temperature is

sufficient to prevent freezing otherwise a faulty indication will be given.

• Not very precise, especially from one transformer geometry to another.

The Use of Vacuum Endpoint and Time consists of pulling vacuum until a decided vacuum endpoint is achieved and then maintaining that vacuum for a certain time period.

Pros and Cons• Low cost.• Must be sure transformer core temperature is

sufficient to prevent freezing otherwise a faulty indication will be given.

• Not very precise, especially from one transformer geometry to another.

Page 40: Field Processing Methods Fo Transformer Dry Out

Water Content of the Oil

Water Content of the Oil is typically determined using a Karl Fischer tester or Panametrics hygrometer.

Pros and Cons• Requires equilibrium conditions.• The operating temperature has a tremendous effect

on the water content of the oil and therefore PPM values may be inadequate to determine the overall dryness of the insulation system.

Water Content of the Oil is typically determined using a Karl Fischer tester or Panametrics hygrometer.

Pros and Cons• Requires equilibrium conditions.• The operating temperature has a tremendous effect

on the water content of the oil and therefore PPM values may be inadequate to determine the overall dryness of the insulation system.

Page 41: Field Processing Methods Fo Transformer Dry Out

Dew Point

Dew Point measurement of the gas inside the transformer is used to provide an estimate of the average surface water content of the insulation after reaching steady state (equilibrium) conditions.

Pros and Cons• Requires equilibrium conditions.• Is done without oil in the transformer so must be

done on a new unit or after vacuum drying a unit.

Dew Point measurement of the gas inside the transformer is used to provide an estimate of the average surface water content of the insulation after reaching steady state (equilibrium) conditions.

Pros and Cons• Requires equilibrium conditions.• Is done without oil in the transformer so must be

done on a new unit or after vacuum drying a unit.

Page 42: Field Processing Methods Fo Transformer Dry Out

For additional information please contact Baron USA, Inc.

931 528 8476

[email protected]

www.baronusa.com