Safety Series Isolator and Splitter SSX/SST Page 1 The rugged metal DIN housing of the SSX/SST Safety Series Isolator and Splitter snaps securely onto G-type and Top Hat rails. April 2015 Features exida certified IEC 61508:2010. exida has certified the SSX/SST for use in an SIS up to SIL 3 in monitor mode, where only the input circuit is part of the safety function. For single use mode, the SSX/SST is approved for use in an SIS up to SIL 2. Comprehensive FMEDA certified safety data. Upon request, exida-certified FMEDA data is provided to be used by a functional safety practitioner to determine the SST’s and SSX’s applicability in specific safety-related applications. Valuable HART data not lost . Both the SSX and SST pass critical HART data to asset management systems, programming devices or host systems. Split signals between two locations. The 4-Wire SST takes in one signal and gives you two fully isolated outputs that can be taken to two separate receiving devices. This facilitates maintenance on either output loop without losing the signal on the other output loop. • RFI/EMI Protection. Standard 20V/m protection offered to protect against harmful effects of radio frequency and electromagnetic interference. Transmitter excitation. The 4-wire SST is capable of providing loop power to a 2-wire transmitter that is connected to its input. 2015 Moore Industries-International, Inc. Description Part of Moore Industries’ FS Functional Safety Series, the exida ® approved, SIL 3 capable 2-wire (loop powered) SSX and 4-wire (line/mains powered) SST Safety Isolators and Splitters provide isolation and signal conversion for your SIS (Safety Instrumented System) needs. These units protect and enhance loops and also pass valuable HART ® data from the field transmitter to host systems and vice-versa. Isolate your SIS from your Basic Process Control System or monitoring system so disconnections or failures to these secondary systems don’t affect your safety system. FMEDA (Failure Mode Effects and Diagnostic Analysis) reports are available with the required safety data to ensure that risk reduction requirements are met (See Figure 1). Protect your safety system from surges, spikes and transients in the field. With 1500Vrms isolating capability, the SSX/SST protects your safety I/O cards and system from the rigors of plant environments. With built-in HART pass-through technology you can rest assured that when your loops use HART transmitters that critical and valuable HART diagnostic, process, and calibration information can be read on either side of the SSX/SST. Most all other isolators block and “strip off” the HART signal. Figure 1. The 2-wire SSX provides safety system isolation while still allowing valuable HART data to pass. 206-792-04D HART is a registered trademark of the HART Communication Foundation. opto isolation SSX Logic Solver (e.g. Safety System or DCS) Monitor/Control System (e.g. DCS, or Asset Management System) 24V Certifications (See Page 2 for details)

Upload: nguyenkhue

Post on 12-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Safety Series Isolator and SplitterSSX/SST

Page 1

The rugged metal DIN housing of the SSX/SST Safety Series Isolator and Splitter snaps securely onto G-type and Top Hat rails.

April 2015

Features• exida certified IEC 61508:2010. exida has certifiedtheSSX/SSTforuseinanSISuptoSIL3inmonitormode,whereonlytheinputcircuitispartofthesafetyfunction.Forsingleusemode,theSSX/SSTisapprovedforuseinanSISuptoSIL2.

• Comprehensive FMEDA certified safety data.Uponrequest,exida-certifiedFMEDAdataisprovidedtobeusedbyafunctionalsafetypractitionertodeterminetheSST’sandSSX’sapplicabilityinspecificsafety-relatedapplications.

• Valuable HART data not lost . BoththeSSXandSSTpasscriticalHARTdatatoassetmanagementsystems,programmingdevicesorhostsystems.

• Split signals between two locations. The4-WireSSTtakesinonesignalandgivesyoutwofullyisolatedoutputsthatcanbetakentotwoseparatereceivingdevices.Thisfacilitatesmaintenanceoneitheroutputloopwithoutlosingthesignalontheotheroutputloop.

• RFI/EMI Protection. Standard20V/mprotectionofferedtoprotectagainstharmfuleffectsofradiofrequencyandelectromagneticinterference.

• Transmitter excitation.The4-wireSSTiscapableofprovidinglooppowertoa2-wiretransmitterthatisconnectedtoitsinput.

2015MooreIndustries-International,Inc.

Description PartofMooreIndustries’FS Functional Safety Series,theexida® approved, SIL3capable2-wire(looppowered)SSXand4-wire(line/mainspowered)SSTSafetyIsolatorsandSplittersprovideisolationandsignalconversionforyourSIS(SafetyInstrumentedSystem)needs.TheseunitsprotectandenhanceloopsandalsopassvaluableHART® datafromthefieldtransmittertohostsystemsandvice-versa. Isolate your SIS fromyourBasicProcessControlSystemormonitoringsystemsodisconnectionsorfailurestothesesecondarysystemsdon’taffectyoursafetysystem.FMEDA(FailureModeEffectsandDiagnosticAnalysis)reportsareavailablewiththerequiredsafetydatatoensurethatriskreductionrequirementsaremet(SeeFigure1).

Protect your safety systemfromsurges,spikesandtransientsinthefield.With1500Vrmsisolatingcapability,theSSX/SSTprotectsyoursafetyI/Ocardsandsystemfromtherigorsofplantenvironments.

With built-in HART pass-through technology youcanrestassuredthatwhenyourloopsuseHARTtransmittersthatcriticalandvaluableHARTdiagnostic,process,andcalibrationinformationcanbereadoneithersideoftheSSX/SST.Mostallotherisolatorsblockand“stripoff”theHART signal.

Figure 1. The 2-wire SSX provides safety system isolation while still allowing valuable HART data to pass.

206-792-04D

HARTisaregisteredtrademarkoftheHARTCommunicationFoundation.

opto isolation

SSX

Logic Solver(e.g. Safety System

or DCS)

Monitor/Control System(e.g. DCS, or

Asset Management System)

24V

Certifications (See Page 2 for details)

Safety Series Isolator and Splitter SSX/SST

Page 2

2-Wire, Loop Powered SSXTheSSXisa2-wireisolator,drawingpowerfromtheoutputsideoftheloop.Typically,thisisfromasecondaryreceivingdevicesuchasaDCSorPLC.

Isolation for Safety Systems UsetheSSXtoisolateyourSISfromyourbasicprocesscontrolsystem.WhilepowerfortheSSXisderivedfromtheoutputsideoftheloop,disconnectionorlossofpowerwillnotaffecttheinputloop’ssignalintegrity.Thisallowsmaintenancetobeperformedonthenon-criticalsideoftheloop(SeeFigure2).

Isolate and Pass Critical HART Data WhenHARTdataisrequiredfordiagnostics,maintenanceorcalibrationtheSSXisabletoisolateandpassHARTdatafromthetransmittertothehostsystem(SeeFigure3).

Stop Ground Loop Noise and Convert Signals Differenceinpotentialbetweenagroundedtransmitterandagroundedreceivingdevicemayresultinunpredictablegroundloopproblemsthatcanleadtosignaldrift.TheSSXbreaksthegalvanicpathbetweenthefieldinstrumentandreceivingdeviceandevenconvertssignalswhenrequired(SeeFigure4).

Solve “Bucking” Power Supplies and Filter HART Whentwodevices(suchasa4-wireHARTtransmitterandaDCS)aretryingtosourcepowertothesameloop,theresultisanon-functioningloop.Whenneitherofthedevicescanbeeliminated,thesolutionisanSSX.Itcanoperatewithpoweredinputsfrombothsides,thusrestoringnormaloperationstotheloopwhilealsopassinganyHARTsignals.SometimesolderDCSandPLCinputcardshavetroublewithHARTsignals.WhenthisproblemarisesyoucanordertheSSXwithoptioncode-0HARTandtheSSXwillfiltertheHARTsignal(SeeFigure5).

Figure 3. The SSX passes HART data to asset management systems or other host control and monitoring systems.

Figure 2. The SSX provides isolation for your safety system and still allows maintenance on the output side of the loop.

Figure 5. The SSX solves bucking power supplies. Also, when used with the -0HART option, the SSX acts as a current isolator that stops a HART signal from reaching a PLC, DCS or other receiving device.

Figure 4. The SSX can also serve as a signal converter.

opto isolation

SSX

Logic Solver(e.g. Safety System

or DCS)

Monitor/Control System(e.g. DCS or Asset

Management System)

24V

24V

IN

IN

NON-ISOLATED TRANSMITTERRECEIVER

NON-ISOLATED4-WIRE

TRANSMITTERRECEIVERRECEIVER

+ +

– –

+24V+

– +IN

1-5VIsolated4-20mA

opto isolation

SSX

LOOPPOWERED

NON-ISOLATED TRANSMITTERRECEIVER

4-WIREHART

TRANSMITTERRECEIVERSIS or PLC

+

– –

+24V+

– +IN

Isolated4-20mA

opto isolation

SSX

4-20mA + HART

+24V

NON-ISOLATED TRANSMITTERRECEIVER

4-WIREHART

TRANSMITTERRECEIVERDCS orAsset

ManagementSystem

+ +

– –

+24V+

– +IN

4-20mA + HART 4-20mA + HART

opto isolation

LOOPPOWERED

SSX

Certifications

CE Conformant -EMCDirective2004/108/ECEN61326;LowVoltageDirective-2006/95/ECEN61010

exida Certified - IEC615082010FunctionalSafetyofElectrical/Electronic/ProgrammableElectronicSafety-RelatedSystems

FM Approvals (FM Global): Non-Incendive ClassI,Division2,GroupsA,B,CandDTemperatureClassT4,Tamb=-40°Cto+85°C

Page3

4-Wire Line/Mains Powered SST and SST SplitterTheSSTisa4-wireunitpoweredby24DC,117ACor230AC.Itisdesignedforapplicationswhereline/mainspowerisreadilyavailable,suchasthebackofapanelorinsideofacontrolroom.

HART Splitter: “Sharing” or “Splitting” Process Signals TheSSTSplittertakestheinputfromoneofyourprocesssignalsandcreatestwoidentical,completelyisolatedoutputstotwoseparatemonitoringorcontroldevices.Additionally,theSSTfunctionsasaHARTsplitterthatpassesvaluableHARTdatatooneorbothoftheSST’sindependentoutputs.ThisisespeciallyimportantwhenassetmanagementsystemsneedtomaintainadigitalHARTconnectionwithcriticalvalvesorinstrumentsfordiagnosticmonitoringorcalibrationrecordkeeping.ThisalsomakesitveryconvenientwhenusingHARThandhelds,modemsorprogrammingdevicestoconfigureremotefieldtransmittersfromcontrolrooms(SeeFigure6).

Power a 2-Wire Transmitter Withtheincluded-TXoption,theSSTprovides24Vpowertoa2-wire,output-looppoweredinstrument.Thiseliminatestheneedforanadditionalpowersupply(SeeFigure7).

Single- and Multiple-Unit Instrument Enclosures DesignedtomeetNEMA4XandIP66ratings,theR-BOXistheperfectsolutionforprotectingtheSST/SSXinfieldandcontrolroomapplications.Ruggedandversatile,itdeliversahighimpactstructureandresistancetoultravioletraysandchemicals.TheR-BOXmountsonapipe,panelorsurface,andcomesinavarietyofwidthstoeconomicallyaccommodateseveralSSTsorSSXs.Itfeaturesapre-installedmountingrail;customizableconduitentryoptions;aclearcoverandasecurelockingmechanism.Formoreinformation,seetheR-BOXField-MountEnclosuredatasheet(SeeFigure8).

Figure 6. The SST Splitter takes one process signal and delivers two completely isolated signal outputs. HART data can be passed to one or both outputs.

Figure 7. The standard -TX Transmitter Excitation of the SST allows it to supply loop power to a 2-wire transmitter.

Figure 8. Available in a variety of widths, our R-BOX field-mount instrument enclosure is designed to protect DIN-rail instruments in even the most rugged environments

SSTSplitter

+A +OUT

+

–A – OUT

opto isolation

+IN

–IN

AC OR DCPOWER

ISOLATED4-20mA w/ HART

+

B +OUT

B –OUT

4-20mA w/ HART

ISOLATED4-20mA w/ HART

4-WIREHART

TRANSMITTER

SIS

PLC

NON-ISOLATED

2-WIRE XMITTER

RECEIVERSST

ISOLATED4-20mA

+ +TX +

+IN

+OUT

–OUT –

opto isolation

NON-ISOLATED4-20mA

AC or DCPower

SafetySeriesIsolatorandSplitterSSX/SST

Page4

Accuracy:±0.1%ofspanStability:+/-0.2%ofreadingperyear Isolation: SSX:500VrmsbetweenInput,OutputandCase;SST:500VrmsBetweenInput,Output,CaseandPowerTested To: SSX:1500VrmsbetweenInput,OutputandCasefor1minute;SST:1500VrmsbetweenInput,Output,CaseandDCPowerfor1minute(2300VrmsfromACPowertoInput,OutputandCasefor1minute)Response Time (analog output):100msecmax.to99%ofoutput Input Resistance: 100 ohmsstandard;250ohmswith-IZ250optionInput Overrange Protection: 250%offullscaleRipple: <10mVmeasuredacrossa250ohmresistor

Performance

Adjustments

Weight

Burden:1Vmaximumforcurrent;1MohmminimumforvoltageLoad Effect:0.01%ofspanfrom0-100%ofratedoutput(currentonly)Power Supply: SST:24DC±10%;117AC50/60HZ,±10%;230AC50/60HZ,±10%;SSX:12-42DCPower Consumption:SST:Singlechannel:3wattsmax.;Dualoutputchannel:5wattsmax.Power Supply Rejection:Exceeds90dbforcurrentinputunits Load Capability: SSX: Vs–12Vdc

SST: 1000ohms SST-Splitter:600ohmsperchannel Output Current Limiting: 25mAtypical;30mAmax.Voltage Limit (for -EP only): 30Vdcmax.

Temperature Range: Operating:-40°Cto+85°C(-40°Fto+185°F);Storage:-40°Cto+85°C(-40°Fto+185°F)Temperature Effect: ±0.007%ofspan/°Ctypical;±0.015%ofspan/°Cmax Relative Humidity:5-95%non-condensing RFI/EMI Protection: Lessthan+/-0.1%ofspanerrorwhentestedat20V/m@20-1000MHzCommon Mode Rejection: Exceeds95dBat60Hzwithalimitof1500Vrms

Type:Frontpanelpots Span:±2% Zero:±2% SST:DC:12oz(340g),AC:17oz(482g) SST-Splitter: DC:15oz(425g),AC:20oz(567g) SSX: 8oz(227g)

Performance (continued)

Ambient Conditions

Specifications

Accessories: PartNumber700-702-36

FMEDA Report consistentwithIEC61508-2:2010providingtheinformationnecessarytodesignaSafetyInstrumentedSystem(OnecopyprovidedfreewitheachorderUponRequest)

Ordering Information

SST 4-wire, Line-(Mains)Powered, SafetyIsolatorandSplitter

Unit Input Output Power Options Housing

4-20MA4-20mAinto100ohmswithHARTdigitaldatasuperimposed1-5V* into1Mohm

4-20MA Isolated,4-20mAinto1000ohms(with24Vdc,117Vac, or230Vacpower); withHARTdigitaldatasuperimposed2X4-20MA into600ohmsperchannel(availablewith4-20mAinputonly);HARTdigitaldatasuperimposedonChannelAonly

24DC ±10%117AC 50/60HZ,±10%230AC 50/60HZ,±10%3wattsmaximumforsinglechannelmodels;5wattsmaximumfordualoutputchannelmodels

-IZ250**Increasestheinputresistanceto250ohms -EP***Externalpower,outputspoweredbyexternalsource(onlyavailableon2X4-20mAoutputmodels)-0HARTNoHARTsignalpass-through-2HART***HARTsignalpass-throughonbothchannels-RO***ReverseOutput(bothchannels)

DINUniversalDIN-stylehousingmountson32mmG-typerail(EN50035)oron35mmTopHatrail(EN50022FLBFlangebracketwithtop/bottommountingholes

*HART pass-through not available for 1-5V Input models**-IZ250 only available for 4-20mA Input models***-EP, -RO and -2HART only available for 2X4-20mA Output models

4-20MA4-20mAinto100ohmswithHARTdigitaldatasuperimposed1-5V*into1Mohm

4-20MA Isolated,4-20mAinto600ohms(with24Vdcpower);withHARTdigitaldatasuperimposed

12-42DC -IZ250**Increasestheinputresistanceto250ohms -0HARTNoHARTsignalpass-through

SSX 2-wire, Loop-Powered, SafetyIsolator

Unit Input Output Power Options Housing

When ordering, specify:Unit/Input/Output/Power/-Option[Housing]Model number examples:SST/4-20MA/2X4-20MA/24DC/-EP[DIN]SSX/4-20MA/4-20MA/12-42DC/-IZ250[DIN]

20mA

SafetySeriesIsolatorandSplitter SSX/SST

Page 5

Figure 10. Dimensions of the SST Isolator in its aluminum DIN-style housing

100mm(4.0 in)

119mm(4.7 in)

124mm(4.8 in)

131mm(5.1 in)

136mm(5.3 in)

CL

47mmREF.

53mm(2.1 in)REF.

(1.8 in)

REF.

REF.

35mm(1.4 in)

Figure 9. Dimensions of the SSX Isolator in its aluminum DIN-style housing

25mm(1.0 in)

100mm(3.9 in)

119mm(4.7 in)

124mm(4.8 in)

131mm(5.1 in)

136mm(5.3 in)

CL

47mmREF.

53mm(2.1 in)REF.

(1.8 in)

REF.

REF.

Safety Series Isolator and Splitter SSX/SST

Page 6

United States • [email protected]: (818) 894-7111 • FAX: (818) 891-2816

Australia • [email protected]: (02) 8536-7200 • FAX: (02) 9525-7296

Belgium • [email protected]: 03/448.10.18 • FAX: 03/440.17.97The Netherlands • [email protected]

Tel: (0)344-617971 • FAX: (0)344-615920

China • [email protected]: 86-21-62491499 • FAX: 86-21-62490635

United Kingdom • [email protected]: 01293 514488 • FAX: 01293 536852

Specificationsandinformationsubjecttochangewithoutnotice.

Figure 11. Dimensions of the SST Splitter in its aluminum DIN-style housing

100mm(3.9 in)

119mm(4.7 in)

124mm(4.8 in)

131mm(5.1 in)

136mm(5.3 in)

CL

47mmREF.

53mm(2.1 in)REF.

(1.8 in)

REF.

REF.

45mm(1.8in)

Figure 12. The SST Splitter and the SST and SSX Isolators mounted with the FLB flange bracket and the bracket’s dimensions.

23mm(0.9 in)

18mm(0.7 in)

9mm(0.4 in)

2 mm(0.1 in)

11mm(0.4 in)

143mm(5.6 in)

121mm(4.8in)

Ø6mm(Ø0.3 in)