facilities services · 08 33 26 overhead coiling grilles 08 43 00 storefront systems 08 44 00...
TRANSCRIPT
FACILITIES SERVICES
CAMPUS STANDARDS FOR CONSTRUCTION SPECIFICATIONS
11-21-17
Page 1 Facilities Services
THE EVERGREEN STATE COLLEGE CAMPUS STANDARDS FOR CONSTRUCTION SPECIFICATIONS
TABLE OF CONTENTS
DIVISION 2: Existing Conditions
02 41 16 STRUCTURE DEMOLITION
02 41 19 SELECTIVE DEMOLITION
02 82 13 ASBESTOS ABATEMENT
DIVISION 3: Concrete
03 20 00 CONCRETE REINFORCEMENT
03 30 00 CAST-IN-PLACE CONCRETE
03 30 03 UNDERSLAB VAPOR RETARDER
03 35 00 CONCRETE FINISHING
03 40 00 PRECAST CONCRETE
03 54 00 CAST UNDERLAYMENT
DIVISION 4: Masonry
04 05 00 MORTAR AND MASONRY GROUT
04 05 23 MASONRY ACCESSORIES
04 21 13 BRICK MASONRY
04 21 23 CLAY UNIT MASONRY
04 22 00 CONCRETE UNIT MASONRY
04 23 00 GLASS UNIT MASONRY
DIVISION 5: Metals
05 10 00 STRUCTRURAL STEEL
05 20 00 METAL JOISTS
05 30 00 STEEL DECK
05 40 00 COLD FORMED METAL FRAMING
05 50 00 METAL FABRICATIONS
DIVISION 6: Wood, Plastics & Composites
06 10 00 ROUGH CARPENTRY
06 12 00 STRUCTURAL INSULATED PANELS (SIP’S)
06 16 00 SHEATHING
06 17 53 WOOD TRUSSES
06 18 00 GLUED-LAMINATED TIMBER (BEAMS AND COLUMNS)
06 20 00 FINISHED CARPENTRY
06 42 00 WOOD PANELING
06 64 00 PLASTIC PANELING
DIVISION 7: Wood, Plastics & Composites
07 13 00 SHEET WATERPROOFING
07 19 00 WATER REPELLENTS
Page 2 Facilities Services
07 21 00 THERMAL INSULATION
07 21 29 SPRAYED INSULATION
07 22 00 ROOF AND DECK INSULATION
07 24 00 (EIFS) EXTERIOR INSULATION & FINISH SYSTEMS
07 27 00 AIR BARRIERS
07 31 13 ASPHALT SHINGLES
07 41 13 METAL ROOF PANELS
07 46 00 SIDING
07 53 23 EPDM ROOFING
07 62 00 SHEET METAL FLASHING & TRIM
07 71 23 METAL GUTTERS AND DOWNSPOUTS
07 72 00 ROOF SPECIALTIES
07 81 00 APPLIED FIREPROOFING
07 84 00 FIRESTOPPING
07 90 05 JOINT SEALERS
DIVISION 8: Openings
08 11 00 METAL DOORS AND FRAMES
08 14 00 FLUSH WOOD DOORS
08 16 13 FIBERGLASS DOORS
08 31 13 ACCESS DOORS AND FRAMES
08 33 23 OVERHEAD COILING DOORS
08 33 26 OVERHEAD COILING GRILLES
08 43 00 STOREFRONT SYSTEMS
08 44 00 CURTAIN WALL & GLAZED ASSEMBLIES
08 51 00 METAL WINDOWS
08 51 13 ALUMINUM WINDOWS
08 52 13 METAL CLAD WOOD WINDOWS
08 54 13 FIBERGLASS WINDOWS
08 56 19 PASS-THRU WINDOWS
08 62 00 UNIT SKYLIGHTS
08 71 00 DOOR HARDWARE
08 80 00 GLAZING
08 84 00 PLASTIC GLAZING
DIVISION 9: Finishes
09 29 00 GYPSUM BOARD SYSTEMS
09 30 13 CERAMIC TILE
09 30 16 QUARRY TILE
09 30 19 PAVING TILE
09 51 13 ACOUSTICAL TILE CEILINGS
09 65 13 RESILIENT BASE
09 65 16 RESILIENT FLOORING
09 65 66 RESILIENT ATHLETIC FLOORING
09 68 13 TILE CARPETING
09 70 00 WALL FINISHES
09 84 00 ACOUSTIC ROOM COMPONENTS
09 91 13 EXTERIOR PAINTING
09 91 23 INTERIOR PAINTING
09 96 23 GRAFFITI RESISTANT COATINGS
Page 3 Facilities Services
DIVISION 10: Specialties
10 11 00 VISUAL DISPLAY SURFACES
10 14 00 SIGNAGE
10 21 00 TOILET COMPARTMENTS
10 21 23 CUBICLE CURTAINS AND TRACKS
10 22 26 VERTICAL FOLDING PARTITIONS
10 26 13 CORNER GUARDS
10 28 00 TOILET AND BATH ACCESSORIES
10 44 00 FIRE PROTECTION SPECIALTIES
10 51 00 METAL LOCKERS
10 74 00 MANUFACTURERD EXTERIOR SPECIALTIES
DIVISION 11: Equipment
11 16 00 VAULTS
11 16 16 SAFES
11 31 00 RESIDENTIAL APPLIANCES
11 40 00 FOOD SERVICE EQUIPMENT
11 52 13 PROJECTION SCREENS
11 52 16 PROJECTORS
11 53 13 LABORATORY FUME HOODS
11 61 00 THEATER AND STAGE EQUIPMENT
11 68 00 PLAYFIELD EQUIPMNET AND STRUCTURES
11 82 00 SOLID WASTER HANDLING EQUIPMENT
DIVISION 12: Furnishings
12 21 00 WINDOW BLINDS
12 24 13 ROLLER SHADES
12 30 00 CASEWORK
12 46 19 CLOCKS
12 93 00 SITE FURNISHINGS
DIVISION 14: Conveying Equipment
14 20 00 ELEVATORS
DIVISION 22: Plumbing
22 00 00 PLUMBING
22 42 00 COMMERCIAL PLUMBING FIXTURES
22 4516 EYEWASH EQUIPMENT
22 47 13 DRINKING FOUNTAINS
DIVISION 31 & 32: Earthwork & Exterior Improvements
31 10 00 SITE CLEARING
31 21 00 EARTH MOVING
31 62 00 DRIVEN PILES
31 63 00 BORED / AUGERED PILES
32 13 00 RIGID PAVING
32 14 16 BRICK UNIT PAVING
Page 4 Facilities Services
32 16 00 CONCRETE CURBS
32 31 00 FENCES & GATES
32 80 00 IRRIGATION
32 91 13 SOIL PREPARATION
32 92 00 TURF & GRASSES
32 93 00 PLANTS
DIVISION 33: Utilities
33 12 19 FIRE HYDRANTS
33 73 00 UTILITY TRANSFORMERS
Standard Specifications The Evergreen State College
DIVISION 2 – Existing Conditions
Division 2 Existing Conditions Page 1 Facilities Services11/21/2017
Section No. Title Comments
02 41 16 STRUCTURE DEMOLITION
1. No blasting or burning on-site.2. Protect persons and adjacent improvements to remain.3. Clean site on a daily basis.4. Minimize environmental impacts. Re-purposing of
materials highly encouraged. Dispose of non-repurposed materials properly and at approved College sites as appropriate.
02 41 19 SELECTIVE DEMOLITION
1. Protect persons and adjacent improvements to remain.2. Clean up on a daily basis.3. Minimize environmental impacts.4. Minimize obstructed means of egress from all occupied
areas.5. Coordinate salvage materials with project manager.
Turn over salvaged items to College at designated location.
02 82 13 ASBESTOS ABATEMENT
1. Protect persons and adjacent improvements to remain.2. Minimize environmental impacts.3. Provide asbestos free certificate for new buildings
prior to occupancy.4. Abatement shall be included in Work of General
Contractor.
Standard Specifications The Evergreen State College
DIVISION 3 CONCRETE
Division 3 Concrete Page 1 Facilities Services11/21/2017
Section No. Title Comments
03 20 00 CONCRETEREINFORCEMENT
1. Grade 60 re-bar or as required by E.O.R.2. WWF at all walks and other flat work.3. Areas subject to vehicular traffic to have re-bar
installed.4. Provide dowels at cold joints on all exterior flat work.5. Require a pre-construction meeting regarding rebar
placement and inspection before scheduling any concrete pours.
03 30 00 CAST-IN-PLACECONCRETE
1. 2,500 psi at flat work not subject to potential vehicle use, 6,000 psi at flat work that will be subject to vehicular use, 3,000 psi min. for structural.
2. Slabs-on-grade 4-inch thick minimum at sidewalks designated for pedestrian use, 6 to 8-inch thickness for locations subject to vehicular use.
3. 4-inch deep 5/8” crushed gravel min below all slabs on grade, 6-inch minimum, with #4 rebar at 24” o.c. each way, at vehicular traffic areas. Thicker paving sections should be engineered for fire lanes.
4. 4x4 WWM reinforcing in sidewalks without vehicular traffic.
5. All conduit, piping, raceways and related items to be located below gravel and bedded in sand.
6. Use of Chlorine containing additives is prohibited.7. Slab-on-grade control joints at 16 feet o.c. maximum.;
if joints are saw cut they shall be cut with-in 24-hours of pour (spec shall call for exposed slabs to be poured in afternoon and cut first thing next morning).
8. Use clear membrane forming curing & sealing compound.
9. Form finishes for Architectural Concrete to be steel, glass-fiber reinforced plastic, or other approved non-absorptive panel materials that will provide a continuous, true and smooth concrete finish.
10. SpecStrip or equal form release agent.11. College will hire a testing agency to take samples and
perform tests on concrete cylinders.12. Coordinate with floor covering placement and
Standard Specifications The Evergreen State College
DIVISION 3 CONCRETE
Division 3 Concrete Page 2 Facilities Services11/21/2017
Section No. Title Comments
finishing requirements.13. BASF MasterAir VR 10, Sika Aer, and Euclid Eucon
Air Mix air-entraining admixture for concrete exposed and exterior flatwork.
14. Grace Daracem 19 admixture for water-reduction.15. Euclid SBR Latex –adhesive bonding admixture to be
used with these applications: toppings, repairs and leveling of concrete surfaces.
16. Brighton Professional: “Hard Rock Sealer” sealing and bonding undercoat for interior concrete floors that are to be exposed.
17. Sustainable Earth: “80 Floor Finish and Sealer” for use on slabs to receive resilient floor covering.
18. If desire to match existing paving use “Lamp Black” to match areas of black concrete, and “Pebble” to match areas stem walls at the Longhouse.
See 10 74 00 MANUFACTURED EXTERIOR SPECIALTIES regarding skateboard deterrents in exterior concrete walls.
03 30 03 UNDERSLAB VAPOR RETARDER
1. See division 7.
03 35 00 CONCRETE FINISHING
1. Light broom finish exterior flat work typical; no “picture framing”. Stamped concrete has not been successful for the College on past projects; stay away from it.
03 40 00 PRECASTCONCRETE
1. Low preference in using precast panels, except for indoor stair treads.
03 54 00 CAST UNDERLAYMENT
1. Laticrete “Supercap” should be specified if it is believed there may be a possible problem with slabs properly curing which could then impact floor covering installation schedule.
NOTES:1. Colored concrete to be thoroughly mixed and shall not have surface applied colorant.2. Create tapered threshold with radius edge at all exterior door locations on slabs-on-grade.3. Consult with owner on fire lane design regarding reinforcing and base.4. Appropriate contained washout areas shall be designated before any concrete pours.
Standard Specifications The Evergreen State College
DIVISION 4 MASONRY
Division 4 Masonry Page 3 Facilities Services11/21/2017
Section No. Title Comments
04 05 00 MORTAR AND MASONRY GROUT
1. Mortar shall be 1,800- psi min.2. Grout shall be 2,500 psi min.3. “Dry-Block” additive required.
04 05 23 MASONRYACCESSORIES
1. All accessories shall be galvanized.
04 21 13 BRICK MASONRY 1. Use of brick masonry encourage for building exteriors.
04 21 23 CLAY UNITMASONRY
1. Minimum f ’c 2,500-PSI.
04 22 00 CONCRETE UNITMASONRY
1. Minimum f ’c 1,350-psi. 1,500-psi 2. “Dry-Block” additive req’d.3. No split-face exterior units. Smooth or polished face
finish preferred.
04 23 00 GLASS UNITMASONRY
1. Glass block not allowed.
NOTES:
1. Seal all exposed masonry surfaces.2. See 09 96 23 GRAFFITI RESISTANT COATINGS regarding anti-graffiti coatings for exterior
masonry.3. Provide control joints in masonry walls as required. Review very carefully!
Align with joints in slab-on –grade.4. All masonry caps and sills exposed to weather are to be sloped to drain and flashed with sheet
metal.5. See 32 14 00 for Brick Pavers.
Standard Specification The Evergreen State College
DIVISION 5 METALS
Division 5 Metals Page 4 Facilities Services11/21/2017
Section No. Title Comments
05 10 00 STRUCTURAL STEEL
1. College preference is to avoid use of steel framing on exterior walls and insulated roof structures due to thermal bridging issues. If steel framing cannot be avoided serious thought should go into details in order to avoid thermal bridging.
05 20 00 METAL JOISTS 1. Discourage use due to issues with thermal bridging; see notes above regarding this issue.
2. Shall conform to Steel Joist Institute requirements.3. Provide shop drawings and calculations stamped by a
structural engineer licensed in the state of WA.
05 30 00 STEEL DECK 1. Sound deaden above classrooms and sleeping rooms.
05 40 00 COLD FORMED METALFRAMING
1. Discourage use on exterior walls due to issues with thermal bridging.
2. Install deflection track at head of wall locations subject to live loads.
3. Provide solid blocking at all locations for shelving, grab bars, casework etc.
05 50 00 METAL FABRICATIONS
1. Grind smooth all exposed welds.
Note: Preference is that all metal exposed to the elements shall be either powder coated or galvanized.
Standard Specification The Evergreen State College
DIVISION 6 WOOD, PLASTICS & COMPOSITES
Division 6 Wood and Plastics Page 5 Facilities Services11/21/2017
General: No exposed wood members on exterior of buildings. Any exposed wood (fascias, rake edges, etc…) must be wrapped in metal flashing with proper air space behind metal.
Section No. Title Comments
06 10 00 ROUGH CARPENTRY 1. Kiln dried Douglas Fir lumber species preferred.2. Metal plate connectors shall be ICBO approved.3. Pressure treated lumber at Code required locations.
06 12 00 STRUCTURAL INSULATED PANELS (SIP’S)
1. 5-ply Douglas Fir plywood sheathing preferred. 2. If only available with OSB panels then wood
waterproofing must be applied to exterior face and edges of OSB before delivery to job site.
3. Expanded polystyrene rigid core.4. Use manufacturer’s specified connectors / screws and
sealants.
06 16 00 SHEATHING 5. 5-ply min APA rated plywood for wall and roof sheathing.
6. No OSB use unless approved by Owner.
06 17 53 WOOD TRUSSES 1. Provide shop drawings and calculations stamped by a structural engineer licensed in the state of WA.
06 18 00 GLUED-LAMINATEDTIMBER (BEAMS AND COLUMNS)
1. Douglas Fir lumber species preferred.2. Architectural appearance grade at all interior exposed
locations, except mechanical and storage rooms.3. Protect exposed beams from water and soil during
construction.4. Hidden connections not preferred, owner should be
consulted on this issue.
06 20 00 FINISH CARPENTRY 1. Natural hardwood trims preferred; don’t use soft woods such as cedar.
2. Composites by Owner approval only. Maintenance, durability and longevity are pertinent.
3. Any exposed screws/fasteners used shall have finished washers.
4. Plastic laminate faced plywood at window sills preferred.
06 42 00 WOOD PANELING 1. Hardboard paneling - use by Owner approval only.
06 64 00 PLASTIC PANELING 1. Glasbord as manufactured by Crane Composites, and “Standard” FRP by Marlite.
2. Color matched trims.
Standard Specification The Evergreen State College
DIVISION 6 WOOD, PLASTICS & COMPOSITES
Division 6 Wood and Plastics Page 5 Facilities Services11/21/2017
3. Seal all edges and joints where exposed to water.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 6Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
07 13 00 SHEET WATERPROOFING
1. Carlisle CCW MIRADRI 860/861 or approved equal.a. Application for use: Below grade concrete
walls.b. Self-adhering waterproofing sheet membrane
of rubberized asphalt. 60-mils, dark gray or black.
c. Use with high-tack water-based contact adhesive applied by roller; Carlisle CCW-702 WB or approved equal.
d. Liquid Mastic: Carlisle CCW LM-800XL, or approved equal.
e. Drainage Composites: Carlisle CCW MIRADRIAN 6000, or approved equal.
f. Use manufacturer’s recommended termination bar.
g. Above items shall all be installed by a manufacturer’s authorized applicator.
h. Other approved manufacturer’s: W.R. Meadows, Grace Construction Products.
i. Pre-installation conference required before product installation.
2. Fortifiber Moistop Ultra 15 and Stego Industries Stego Wrap 15-MIL.
a. Application for use: Slab-on-grade.b. Pre-installation conference required before
product installation.
07 19 00 WATER REPELLENTS 1. Silane / Siloxane penetrating water repellent for exposed finished exterior concrete walls.
a. Fabrikem Fabrishield 653 preferred.b. Other manufacturers approved: BASF, Evonic,
Euclid Chemical Co., Vexcon Chemicals, Tnemic Co., and Prosoco.
c. Use low-VOC product.d. Non-yellowing, non-glossy, colorless water-
vapor permeable finish that is invisible once dried.
07 21 00 THERMAL INSULATION
1. Spray foam insulation product with closed-cell polyurethane foam. ATSM C 1029.
a. Preferred for cavity walls if the budget allowsb. Use to fill voids in exterior metal door frames
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 7Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
2. Glass and Mineral fiber blanket, are second choice in preference for cavity walls
a. Certain Teed, Knauf, Johns Manville, Owens-Corning, and Guardian.
b. Friction fit.c. R-value as requiredd. Meets ASTM E 136 for combustibility.e. Fire Hazard Classification: ASTM E 84.f. Foil faced vapor retarder on interior side of
insulated wall or ceiling with transmission rating of 1 perm or less. Install with galvanized or electroplated nails or staples at wood framing. Seal seams with 2” wide mesh reinforced aluminum tape. See 07 90 05 for vapor retarder sealant.
g. No formaldehyde content.h. Flame Spread Index: 10/10i. Smoke Development Index: 10/10j. Non-combustible, except for facingk. Minimum K-value: 0.27l. Minimum density: 1.0 poundm. Support wire to be steel, electroplated or
galvanized3. Extruded Polystyrene Board Insulation at foundation
walls. a. Insulfoam R-Tech IV and Owens Corning
Fomular 250.b. Minimum compressive strength of 25 PSI per
ASTM D1621 test method.4. No cellulose blow-in insulation allowed.5. Acoustical insulation:
a. Wall insulation to be R-11 mineral or fiberglass blankets; manufacturers as listed on number 2 above.
b. Provide acoustical insulation in office walls, restroom walls, corridors and classroom walls. Install from top of floor plate to bottom of structure above.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 8Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
07 21 29 SPRAYED INSULATION
1. Acoustical: K-13 Spray-on acoustical insulation by International Cellulose Corporation.
2. Applicator shall be approved by manufacturer to install product.
3. Must meet ASTM E 1042 testing requirements.4. Minimum fiber recycled content to be 75%.5. NRC of 0.75 per ASTM C 423 with 1” of material.6. Color: Black7. Certification required from manufacturer to ensure
product contains no fiberglass, asbestos or other man-made fibers.
8. Mock-up required before proceeding with installation.9. No urea-formaldehyde resins.
07 22 00 ROOF AND DECKINSULATION
1. Spray foam insulation preferred for rafter cavities if the budget allows. Use closed-cell polyurethane foam. ATSM C 1029
2. Mineral fiber blanket, or rigid insulation board are second choice in preference; friction fit.
3. Polyisocyanurate rigid board insulation per manufacturer’s recommendations as required per EPDM roofing manufacturer.
07 24 00 (EIFS) EXTERIOR INSULATION& FINISH SYSTEMS,OR STUCCO
1. Not allowed.
07 27 00 AIR BARRIERS 1. Interior vapor retarder shall be installed on outside face of wall sheathing.
2. Continuous Air Barrier: Vaproshield “WrapShield SA” self-adhering vapor permeable air barrier sheet membrane is the preferred product.
3. Install with manufacturer’s recommended seam tape.4. Primers, cleaners, sealants and flexible flashings as
recommended by manufacturer of air barrier.5. Pre-installation conference and mock-up installation
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 9Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
required before installation of any of these products.
07 31 13 ASPHALT SHINGLES 1. Malarkey Artic Seal 401 or Titanium PSU 30 on entire roof with roof pitches between 3:12 and 4:12.
2. Malarkey Artic Seal 401 or Titanium PSU 30 at all overhangs, valleys, and ridges with roof pitches greater than 4:12.
3. Malarkey The Alaskan 3-Tab shingle shall be based bid asphalt shingle; 15-year workmanship, 35-year material warranty. Malarkey Legacy Laminated Architectural Shingle shall be alternate bid; 20-year workmanship, 50-year material warranty. Both versions shall feature “Scotchgard” protection.
4. Sheet metal valleys per below.5. No asphalt shingles allowed below 3:12 pitch. 6. See valley spec at the end of this Division.
07 41 13 METAL ROOF PANELS
1. Use metal roof panels if considering roof mounted photo voltaic panels on this project.
2. AEP Span: Span-Lok hp 16” wide, 2” standing seam rib.
3. 22 Ga. preferred.4. Dura Tech 5000 finish preferred.5. Use S-5! Colorgard Snow Retention system at all
areas above exterior doorways and pedestrian walkways near building perimeter.
07 46 00 SIDING 1. Pre-finished metal products preferred for low maintenance, high durability products.
2. No exposed wood, use fiber cement products in lieu of wood siding and trim.
3. CMU with anti-graffiti coating – see Div. 4.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 10Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
07 53 23 EPDM ROOFING (FOR LOW SLOPE APPLICATIONS)
1. Carlisle SynTec, 60 mil, or Firestone equivalent. a. Black finish. b. Fully adhered.c. Class 1 and windstorm resistance of 1A-90.d. Use manufacture’s Polyisocyanurate tapered
boards.e. Provided manufacturer’s pressure-sensitive
molded walkway pads as deemed necessary per maintenance staff.
f. Use manufacturer’s 40-mil self-adhering air and vapor barrier as a temporary roof membrane for no more than 30-days.
g. Entire roof assembly shall all be installed by a manufacturer’s authorized applicator.
h. Pre-installation conference required before installation.
i. 15-year standard warranty regarding prevention of water penetration for entire roof system.
j. Defective work shall be corrected within two-years of substantial completion.
2. Clad metal flashing as necessary.3. Consider 90 mil as an additive alternate bid item
07 62 00 SHEET METALFLASHING & TRIM
1. 24-gauge minimum preferred.2. Pre-finished with standing seam coping joints over Ice
& Water-Shield type product or EPDM membrane.3. 26-gauge, No.304 stainless steel for scuppers.4. Solder joints.5. Follow SMACNA standards.6. See below for valley spec.
07 71 23 METAL GUTTERS and DOWNSPOUTS
1. 22 gauge minimum for gutters. See 5 below for gutter guard.
2. Downspouts 12’ above grade to be min 4” diameter ABS pipe.
3. Downspouts below 12’ above grade to be schedule 10 galvanized pipe with welded joints and cleanout. Connect to subsurface piping at / or just above grade. Downspouts should be removable, not set in concrete.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 11Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
Seal around downspout and tightline.4. Exterior through wall scuppers shall be Josam or
Watts bronze “cow tongue” type downspout nozzle.5. Gutter guard: 22 gauge minimum powder coated steel
or aluminum, with ½” perforated holes forming 48% open area.
07 72 00 ROOF SPECIALTIES 1. Curb-mount all accessories.2. Install loop-type safety anchors along ridges for
moderate to steep sloped roofing systems. 3. Roof restraint fall protection systems shall be designed
for low-slope roof systems; Guardian CB anchor system or similar cable based system as approved.
4. Cor-a-vent X-5 ridge vent on asphalt shingle vented roofs.
5. Low slope roof drains & overflow: Zurn RD2120 or approved equal.
6. See below for valley spec.
07 81 00 APPLIED FIREPROOFING
1. Grace Construction Products: Monokote Z-106/G, and Isolotek International; Cafco 400.
2. Product meets the following standards:a. ASTM E84, ASTM E605, ASTM E736,
ASTM E759, ASTM E760, ASTM E761, ASTM E937, ASTM E859, ASTM G21, ASTM E136, ASTM E1354, ASTM C423, ASTM518
3. Warranty shall cover defective work for 2-years after Substantial Completion.
4. Pre-installation Conference: Schedule one week prior to installation begins, include installers. Review preparation and installation procedures and coordination and scheduling necessary for related work.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 12Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
07 84 00 FIRESTOPPING 1. Elastomeric Silicone Firestopping:a. 3M Fire Barrier Water Tight Sealant
3000WTb. Hilti CP 601Sc. STI SIL300 Firestop Sealant
2. Foam Firestopping:a. 3M Fire Barrier Rated Foam FIPb. Hilti CP 620 Firestop Foam
3. Other Firestopping:a. Owens Corning Thermafiberb. Pecora AC-20 FR
07 90 05 JOINT SEALERS 1. Type A -Exterior sealant: Dow Corning 791 and 795, Tremco Spectrem 1, 2, 3 and 4-TS, Pecora 865, 895 and 898.
a. Applications for use: Control, expansion and soft joints for masonry. Joints between concrete and other materials. Joints between metal frames and other materials. Joints at curtain walls, storefronts, aluminum break metal and other substrates.
2. Type B –Exterior Metal Lap Joint sealant: Tremco Butyl Sealant and Pecora BC-158.
a. Applications for use: Concealed sealant bead in sheet metal work and siding overlaps.
3. Type C –Interior sealant: Tremco Tremflex 834 and Pecora AC-20 +Silicone.
a. Applications for use: Interior wall and ceiling control joints including top, bottom and corners of all gypsum acoustical partitions. Joints between door and window frames and wall surfaces. Other interior joints for which no other type of sealant is indicated.
4. Type D –Acoustical sealant: Pecora AIS-919 and Tremco Tremflex 834.
a. Applications for use: Interior acoustical sealant for interior walls, ceilings and floors.
b. For concealed locations only.
Standard Specifications The Evergreen State College
DIVISION 7 THERMAL & MOISTURE PROTECTION
Page 13Division 7 Thermal & Moisture Protection Facilities Services11/21/2017
Section No. Title Comments
5. Type E – Vapor retarder sealant: 1 part polyurethane type such as Tremco Dymonic FC.
NOTES: Valley Specification: This is to be used on all composition roofs with valleys.1. At valley lay continuous ice & water shield from eave to ridge at 36-inches wide minimum
coverage.2. Lay in raised edge “W” valley flashing and install per SMACNA Standards.3. Install Ice & water shield on each side of “W” flashing. Lap 6” min over flashing and run
continuous from eave to ridge.4. Cut shingles in valley. Start narrow at the ridge and widen toward the eave. Trim shingle points
and seal down.
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 1
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
08 11 00 METAL DOORS AND
FRAMES
1. Exterior Doors
a. Doors shall meet the requirements of ANSI A250.4
b. 16-gauge min. face sheets with internal
reinforcement.
c. 1-3/4” thickness.
d. Level 3, physical performance A, Model 1.
e. Factory prime painted
f. Full Flush
g. Polyurethane insulated core.
h. Beveled edge profile.
i. Provide closure strip at head of all exterior doors
exposed to weather.
j. Galvannealed finish if in wet areas.
k. Vision Panels: Non-removable stops on secure side
l. Approved Manufacture’s: Ceco /Assa Abloy, Curries
/ Assa Abloy, Door Components, Inc., Steelcraft,
Stiles, and Republic.
2. Interior Doors
a. Fire-Rated & Non-Fire-Rated
� Doors shall meet the requirements of
ANSI A250.8
� 18-gauge min. face sheets with 16 gauge
stile and rails.
� 1-3/4” thickness
� Level 2, Model 1
� Factory prime painted
� Full Flush
� Beveled edge profile
� If required to be fire-rated: provide units
listed and labeled by UL, attach fire
rating label to each unit
� Polystyrene core, 25 STC for acoustic
doors, Kraft honeycomb core otherwise
� Galvannealed finish if in wet areas
� Vision Panels: Non-removable stops on
secure side
� Approved Manufacture’s per exterior
doors noted above
3. Door Frames
a. Comply with the requirements of grade specified for
corresponding door
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 2
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
b. Factory prime painted
c. Welded corners.
d. Grouted frame as required by Owner, structo-lite is
acceptable alternate to grout.
e. Galvannealed finish if in wet areas.
f. Frames wider than 48-inches shall be reinforced with
steel channel fitted tightly into frame head, flush with
top.
g. Frames installed back-to-back shall be reinforced
with steel channels anchored to floor and overhead
structure.
h. Fire rating to be same as door.
i. Approved Manufactures: Same as Exterior Doors
above.
4. Door and Frame Finish
a. 1st Coat: High Build Epoxy, MPI #108
b. 2nd Coat: Polyurethane, MPI #72
c. 3rd Coat: Polyurethane, MPI #72
d. MPI Gloss Level 5
e. Minimum Pencil Hardness of 4H
08 14 00 FLUSH WOOD DOORS 1. All interior locations unless noted otherwise.
2. Weyerhaeuser, Vancouver, Eggers or VT Industries
products preferred.
3. AWI “Premium Grade” minimum.
4. Solid core: Particleboard.
5. Hardwood lumber stiles and rails and reinforcing where
required for hardware.
6. Veneer maple finish
7. Beveled and stained hardwood vertical edges..
8. Vision Panels: Non-removable stops on secure side.
08 16 13 FIBERGLASS DOORS 1. Super-insulating fiberglass doors shall be considered at
exterior openings.
2. Factory painted finish.
3. Special-Lite Model AF-100, or as approved by Owner.
4. Closed-cell polyurethane insulated core.
5. 1-3/4” thickness.
6. Use with Special-Lite Model AF-150 door frame; painted
to match door.
7. 10-year warranty for door and frame.
08 31 13 ACCESS DOORS &
FRAMES (Walls &
Ceilings)
1. Doors and frames: formed steel.
2. Provide keyed camlock at public places.
3. Provide twist turn handle at emergency shut-off
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 3
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
locations.
4. Stainless steel in public spaces.
5. Painted finish in maintenance locations.
6. Factory coated white in hard-lid ceilings.
08 33 23 OVERHEAD COILING
DOORS
1. 20-gauge min. steel door slats, aluminum or stainless
steel, guides and housing to match door construction.
Stainless construction in Kitchen areas.
2. Larger openings to be chain operated. Provide pull down
handle elsewhere. No finger holes.
3. Motor operator at vehicle entries with manual override.
Three button control.
4. Overhead Door Co. door and operator preferred.
5. Lock cylinders to accept large format interchangeable
cores by Assa.
08 33 26 OVERHEAD COILING
GRILLES
1. Powder coated expanded aluminum grille.
2. Manual operation.
3. Lock cylinders to accept large format interchangeable
cores by Assa.
08 43 00 STOREFRONT
SYSTEMS
1. Not preferred for exterior walls.
2. Allowed at interior installations.
a. Use Kawneer, EFCO, CRL / US Aluminum, or
Oldcastle Building Envelope. Use Kawneer Trifab
VersaGlaze 450 as standard example.
b. Factory fabricated, factory finished framing
members with infill and related flashings.
c. Glazing position: Centered (front to back)
d. Vertical Mullion: 2-inches wide x 4-1/2” deep.
e. Sections and Stops to accept ¼” glazing units.
f. Internal weep drainage system.
3. Doors:
a. Glazed aluminum frame
b. Match Kawneer Trifab VersaGlaze 450
c. Finish to match fixed Storefront
4. Brake Metal:
a. Match Storefront
b. 8 and 16 gauge material
5. Flashings (aluminum):
a. 20 gauge where exposed, match Storefront finish
b. 25 gauge where concealed
6. Fasteners:
a. Stainless Steel
b. Color and finish to match framing members
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 4
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
08 44 00 CURTAIN WALL &
GLAZED
ASSEMBLIES
1. Maybe allowed depending on type of project. Check
with Owner.
08 51 00 METAL WINDOWS 1. Not allowed at exterior openings.
2. Use as interior relites or sidelights.
08 51 13 ALUMIMNUM.
WINDOWS
1. Not preferred.
08 52 13 METAL CLAD WOOD
WINDOWS
1. Not allowed.
08 53 13 VINYL WINDOWS 1. Not preferred.
2. See Fiberglass windows below.
08 54 13 FIBERGLASS
WINDOWS
1. Preferred over other windows. Milgard or College
approved.
2. Powder coated exterior finish.
3. Must use the most technologically advanced
insulating frame and glazing.
4. Minimize number of different sizes.
08 56 19 PASS-THRU
WINDOWS
1. Tempered glass with stainless rollers and guides.
2. National or Olympus locks – small pin tumbler D4292
keyway.
08 62 00 UNIT SKYLIGHTS 1. Kalwall Standard , or CrystaLite layer plastic dome
skylights.
08 71 00 DOOR HARDWARE 1. College standard products only. Substitutions only as
noted.
2. All items, except as noted below, shall be warranted in
writing by the manufacturer against failure due to
defective materials and workmanship for a minimum of
one (1) year commencing on the date of final completion.
3. Hinges: Hagar, also: McKinney and Bommer. One (1)
hinge for every 30” of door height.
a. Minimum size: 4-1/2” x 4” wide.
b. Use piano hinges on all major exterior doors.
c. Finish: stainless steel
4. Keying:
a. All locks and cylinders shall be provided with
construction cores for use during the construction
phase.
b. All permanent cores shall be keyed to the existing
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 5
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
Assa Twin Exclusive key system (2BA131) per
approved key schedule. Provide College with the
permanent cores in which staff will remove and
replace construction cores with permanent ones.
Construction cores will be returned to the
contractor so they may be returned to the supplier
c. Provide three (3) keys minimum per lock, unless
otherwise noted by owner.
5. Cylinder cores:
a. ASSA Twin Exclusive with large format
interchangeable cores.
b. Substitutions are not allowed.
6. Locksets (mortise):
a. Corbin Russwin ML 2000 series preferred.
b. Sargent 8200 also acceptable
c. Five year warranty required
d. Field-adjustable, beveled armored front, .125”
thickness.
e. 2-3/4” backset with a one-piece ¾” anti-friction
stainless steel latchbolt.
f. Deadbolt: Full 1” throw made of stainless steel
with two hardened steel roller inserts.
g. Strike: Shall be non-handed with a curved lip.
7. Pivott Sets: Dorma or Rixson, models as required to meet
door weights.
8. Exit Devices and Mullions:
a. Sargent 80 Series and Von Duprin 98 Series
b. Devices must fit flat against the door face with no
gap that permits unauthorized dogging of the
push bar.
c. Provide with key cylinder to allow dogging of
device, not to be dogged with hex key; do not
provide at locations electrical hardware is
installed.
d. Push rail mounting rails to be formed from a
solid piece of stainless steel no less than .072”
thick
e. Push rails shall be constructed of .062” thick
stainless steel.
f. Lever trim shall be in finishes and designs to
match that of the specified locksets
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 6
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
g. Removable mullions with malleable-iron top and
bottom retainers. Fit with standard stabilizers and
imbedded weatherstriping
9. Electrified Devices:
a. Manufacturer: Von Duprin. Sargent an approved
substitution
b. Power for devices shall utilize a continuous
electric hinge for a clean design and no visible
means of interrupting power to the device
c. Exit devices, both fire and non-fire doors,
requiring electrical dogging shall be held in the
dogged or retracted position
d. All exit devices with electric latch retraction shall
provide for a remote means of unlocking the
momentary or maintained periods of time
e. Refer to Section 281300 – Access Control for
Electronic Access Control products
10. Door Closures:
a. Manufacturer: Norton 7500. LCN 4041 Series
also approved.
b. Ten year warranty required
11. Heavy-Duty Automatic Door Operators:
a. Manufacturer: Horton 4000/7000 Series. Norton
6900 an approved substitution
b. 4”x4” press to operate face plate with ADA
international symbol
12. Door and wall stops and holders:
a. Basis of design: Rockwood.
b. Also approved: Trimco and Hager
c. Model preferred: 445, 462, 494R and 402
13. Overhead stops / holders:
a. Basis of design: Rixson
b. Also approved: Sargent
c. Model preferred: Concealed Mount 1ADJ Series
14. Protection Plates, Push Plates and Pulls:
a. Basis of design: Rockwood Standard Line
b. Also approved: Sargent, Trimco and Hager
c. Do not specify any hardware trim that could
compromise the security of the locking
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 7
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
mechanism
15. Gaskets, Bottoms and Thresholds:
a. Basis of design: Pemko,
b. Also approved: McKinney Manufacturing and
Reese Enterprises.
c. Use only non-adhesive applied gaskets
d. Do not use threshold mounted gaskets or seals
16. Silencers: Trimco or Rockwood.
17. Door & Hardware submittals are required to be
reviewed by the College.
08 80 00 GLAZING 1. Float Glass Manufacturer’s:
a. Cardinal Glass Industries
b. AGC Flat Glass North America
c. Guardian Industries
d. Pilkington
e. Vitro
f. Schott North America
2. Types of float glass:
a. S-1: Single Vision Glazing:
� ¼” thickness
� Clear
� Annealed float glass
� Use typically at all interior locations
unless required by code
b. S-2: Single Safety Glazing:
� ¼” thickness
� Clear
� Fully tempered float glass
� Use as required by code
c. S-3: Anti-reflective Glazing
� ¼” thickness
� Clear
� Anti-reflective coating on float glass
� Use as directed
3. General:
a. Insulated units – 1” minimum thickness.
b. When feasible minimize use of large units.
4. Glazing Compounds:
a. Bostik Pure Silicone sealant
b. GE RGS7700 RapidStrength
Standard Specification The Evergreen State College
DIVISION 8 OPENINGS
Page 8
Division 8 Openings Facilities Services
Revised 1/3/18
Section No. Title Comments
c. Pecora 860
d. Dow Corning 983 sealant at Curtain Walls
5. Glazing Tape:
a. Saint Gobain V2200
b. Tremco Commercial Sealants ET 675
6. Accessories:
a. Neoprene setting blocks to suit glazing method,
weight and area.
b. Neoprene spacer shims to suit application; self-
adhesive on one face.
c. Glazing gaskets as required at interior
applications.
08 84 00 PLASTIC GLAZING 1. Not allowed unless prior approval from Owner.
NOTES: 1. All permanent door cores and keys will be supplied by the contractor and installed by the College
2. All double doors to have keyed removable mullions keyed to College cylinders.
3. Contractor shall provide and install temporary construction cores and supply College with (5)
construction keys and (2) control keys.
4. A door hardware meeting with the hardware consultant, the College Locksmith, Project Manager, and
Electrical Engineer should take place during the design development stage.
5. Before door hardware is ordered there shall be a keying meeting the includes members of the College
(Campus Locksmith, Project Manager, and user representative) along with the Hardware Supplier and
General Contractor. This should be clearly noted in the Hardware Specification.
6. All closers to be through bolted.
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 11Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
09 29 00 GYPSUM BOARD SYSTEMS
1. Manufacturer’s product for typical wall locations:a. Georgia Pacific:
ToughRock Gypsum Board.b. USG:
Sheetrock Brand Gypsum Panels.2. Manufacturer’s product for high traffic areas (corridors):
a. Georgia Pacific: ToughRock Abuse-Resistant Gypsum Board
b. USG: Sheetrock Brand AR Panels
3. Manufacturer’s product for wall areas subject to moisture:a. Georgia Pacific:
DensArmor Plus High-Performance Interior Panel.
b. USG: Sheetrock Brand Mold Tough Panels
4. Manufacturer’s product for ceiling board:a. Georgia Pacific:
DensGlass Sheathing ½” thicknessb. USG:
Sheetrock Brand Gypsum Panels ½” thickness5. Manufacturer’s product for ceiling board subject to
moisture:a. Georgia Pacific:
DensArmor Plus Interior Panels ½” thicknessb. USG:
Sheetrock Brand Glass-Mat Panels Mold Tough (regular) ½” thickness
6. Manufacturer’s product for exterior substrate:a. Georgia Pacific:
DensGlass (regular) Sheathing or Fireguard Sheathing
b. USG: Securock Glass Mat Sheathing Regular or
Firecode X7. Edge profiles: Square cut on short end, long edges shall be
tapered.8. Accessories:
a. Metal corners and edge trim, screw fastened.9. Finishing of Gypsum Board:
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 12Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
a. Level 1 for utility spaces, plenums, and concealed areasb. Level 4 for most all other areas, except as noted belowc. Level 5 for skylight wells and other areas prone to be
viewed with high levels of sunlight or areas with a gloss finish
Smooth finish for all surfaces exposed to view; no orange peel or other texturing.
09 30 13 CERAMIC TILE 1. Manufacturer: a. Daltile
Walls: “Natural Hues” 6” x 6” sizes Floors: “Natural Hues” 12” x 12” sizes
b. American Olean Walls: “Bright” 6” x 6” sizes Floors: “Theoretical” 24”x24” and
12”x24”x 3/8” or unglazed mosaic tile2. Grout:
a. Bostik: Hydroment Vivid or Ceramic Tile Grout
sandedb. Custom Building Products
Polyblend sandedc. Laticrete
1500 Sandedd. No white or light colored groute. 1/8” grout joint preferred
3. Mortar: a. Bostik
PM and Large Format Floorb. Custom Building Products
MegaLite RS and MegaLite Ultimate CPc. Laticrete
252 Silver for thin-set 226 Thick-bed with 3701 admixture for
mortar bed installation, or 3701 Fortified mortar bed
4. Sheet membrane waterproofing:a. NobleSeal TS at floors of rest rooms and showers;
run 12” minimum up tile backer-board on walls. 5. Sealant:
a. Dow Corning 786 Silicone Sealant – M
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 13Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
b. GE SCS1700 Sanitary and SCS1702c. Tremco Sealants Proglaze
6. Tile backer-board:a. Georgia Pacific Dens-Shield tile backer-board behind
all ceramic tileb. USG Durock Brand Glass-Mat tile backer-board also
acceptable7. All grout to be mixed with Custom Building Products
“Stain Blocker for Grout” or Specialty Construction Brands Grout Boost Advanced Pro in lieu of grout sealer
Provide 10 square feet of extra stock for each type and color of tile.Avoid complicated layouts that will add to installation costs.Floor tile in wet areas shall have a COF .60 or greater.Use thin-set floor installation method above ground floor and mortar bed installation method at ground floors.
09 30 16 QUARRY TILE 1. Use in kitchen areas if budget allows.2. No white or light colored grout.3. All grout to be mixed with Custom Building Products
“Stain Blocker for Grout” or Specialty Construction Brands Grout Boost Advanced Pro in lieu of grout sealer.
09 30 19 PAVING TILE 1. Use at high traffic public stairways.2. 3/8" thick minimum.3. No white or light colored grout.4. Slip resistant finish; COF .60 or greater.5. All grout to be mixed with Custom Building Products
“Stain Blocker for Grout” or Specialty Construction Brands Grout Boost Advanced Pro in lieu of grout sealer.
6. Use of bond breaker membrane for crack isolation.09 51 13 ACOUSTICAL TILE
CEILINGS Suspension type systems:
1. Manufacturer: Armstrong or US Gypsum products preferred. Rockfon also approved
2. Suspension Grid: (ASTM Heavy Duty Class)a. Armstrong: Prelude Plus XL Aluminum
15/16” exposed teeb. USG: AX, DXLA and DX / DXL 15/16”
exposed teec. Rockfon: Seismic 1200 – 15/16” exposed tee
3. Panels:
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 14Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
a. Armstrong: Ultima High NRC, Mesa and Cirrus preferred. Dune also acceptable.
b. USG: Eclipse High NRC, Olympia Micro and Radar.
c. Rockfon: Alaska dB4. Panel sizes: 2’x4’. 2' x 2' grid at architectural features
when approved.5. Panel colors: Standard white. Other colors when
approved.CertainTeed / Saint-Gobain products will also be considered.Transition metal: Use same finished material as finished aluminum grid; 24 Ga. metal profiles for transitions between different ceiling heights.Seismic wall clips as per manufacturers recommendation. Use galvanized steel, size and type to suit application, seismic requirements, and ceiling system.Glue-on ceiling systems:
1. Pinta Acoustic, Inc.a. SONEX Glue on Contour at areas where
acoustic performance is of high importance09 65 13 RESILIENT BASE 1. Mannington Thermoset rubber (TS), preferred
2. Size: 4” x 1/8” roll or straight lengths3. Color: Midnight #938 (Black)4. Finish: Satin5. Use prefinished exterior corners, typical6. Armstrong, Burke, Johnsonite and Roppe products
which specs are equal to this product are approved.
09 65 16 RESILIENT FLOORING
No-wax resilient flooring products should be highly encouraged for use in high traffic areas such as corridors and elevators. See below for a basis of design:
1. Rubber Tile: Mannington Teles, ColorSpec or ColorScape.
2. Size: 18-1/8” tiles. 3. Expanko Reztec, Mohawk TRUE Medi-Flex are also
approved products.4. Subfloor filler: Use water based type recommended by
adhesive manufacturer.5. Primers, adhesives and seaming materials: Water
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 15Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
based, waterproof, solvent free types as recommended by flooring manufacturer.
6. Moldings, transition and edge strips: Metal7. Seams: Heat welded rod as recommended by flooring
manufacturer; color to match floor field color.8. Before installation: Verify that all surfaces are per the
tolerances acceptable to the flooring manufacturer and are free of cracks that could telegraph through. All floor surfaces should also be clean, dry and free of curing compounds, surface hardeners, and other chemicals that might interfere with bonding. Concrete slab test results must indicate requirements for moisture content and alkalinity are below manufacture’s allowable criteria before installation may proceed. Obtain direction from manufacturer if the test results do not meet those requirements.
09 65 66 RESILIENT ATHLETIC FLOORING
1. Basis of design: Robbins Sports Surfaces, Pulastic Classic 110r for use in Main Gymnasiums.
2. Gerflor Taraflex Multi-use 5.0 Maple considered for use in Auxiliary Gymnasiums.
3. No Tuflex Rubber Flooring, the off-gassing fumes from this product are overbearing.
09 68 13 TILE CARPETING For fixed walkoff mats:1. Manufacturer: Interface 2. Product Line: Entry Level 3. Backing: Glasbac Tile4. Fiber: Blended Yarn Nylon5. Dye Method: Solution Dyed6. Pile: .150-inch thickness
General purpose tile carpet:1. Mohawk Group2. Product Line: Artist II, CEO II and Doctor II3. Backing: EcoFlex ICT4. Fiber: Colorstrand Nylon5. Dye Method: Solution / Yarn Dyed6. Pile Weight: 15 oz. per yard7. Extra stock: Provide 15 full size extra tiles for future
use of each type, color and pattern. Subfloor filler: Use water based type recommended by
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 16Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
adhesive manufacturer.Before installation: Verify that all surfaces are per the tolerances acceptable to the flooring manufacturer and are free of cracks that could telegraph through. All floor surfaces should also be clean, dry and free of curing compounds, surface hardeners, and other chemicals that might interfere with bonding. Concrete slab test results must indicate requirements for moisture content and alkalinity are below manufacture’s allowable criteria before installation may proceed. Obtain direction from manufacturer if the test results do not meet those requirements.
09 70 00 WALL FINISHES 1. High traffic corridor walls shall be finished with wainscots and should be painted MDF, stained and / or sealed Bamboo or Plywood panels.
2. Maple or metal trim at horizontal wall finish transitions.
3. FRP at mop sinks and kitchens09 84 00 ACOUSTIC ROOM
COMPONENTSClip or track mounted, fabricated fiberglass acoustical wall panel with stretched fabric covering.
1. Edges: Square2. Thickness: As determined by designer3. Trim: Aluminum angle
09 91 13 EXTERIOR PAINTING 1. Low to Zero VOC paints preferred. Review proposed paints with Owner for selection.
2. Product: 2010 – 100% Acrylic Latex Exterior3. Contractor to provide 2-year performance bond.4. Contractor to set up pre-paint walk through prior to
application. 5. Limit selection to three paint colors.6. Contractor to provide 2-year performance bond.
General:1. Materials, preparation and workmanship shall
conform to all requirements of the current edition of the Architectural Painting Specification Manual by the Master Painters Institute (MPI) hereafter referred to as the MPI Painting Manual.
2. Only materials listed in the current edition of the MPI Painting Manual. All integral systems shall be from a single manufacturer.
3. Unless otherwise specified herein or pre-approved, all paint shall be ready-mixed and pre-tinted. All paint
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 17Division 9 Finishes Facilities ServicesRevised 7/17/17
Section No. Title Comments
shall be re-mixed in containers prior to application.4. All painting work shall be in accordance with MPI
Premium Grade finish requirements.5. Exterior Metal Fixtures: Campus Standard Bronzetone
(see college for sample) with eggshell (G3) finish09 91 23 INTERIOR PAINTING 1. Low to Zero VOC paints preferred. Review proposed
paints with Owner for selection.2. Contractor to provide 2-year performance bond.3. Manufacturer pre-paint walk through prior to application. 4. Discourage the use of “flat” sheen, except as noted.5. Standard Interior Color: White (see college for sample)6. Sheen:
Location FinishPublic walls G3 – EggshellDoors and frames G5 – Semi-glossRest Rooms G5 – Semi-glossShowers G5 – Semi-glossKitchens G5 – Semi-glossExposed ducts G1– FlatExposed pipingconduit and hangers G1– Flat
7. Limit selection to four paint colors8. Don’t paint over labels of manufactured equipment &
doors or fire rating label on plywood.09 96 23 GRAFFITI
RESISTANT COATINGS
1. Non-sacrificial coating anti-graffiti coating on exterior cementitious (not painted) walls and masonry.
2. Integral water repellant.3. Min 10’-0” high treatment on grade level walls.4. Depending upon product used, provide min. (1) gallon of
compatible graffiti remover.5. Preferred products:
Prosoco “Blok-Guard & Graffiti Control II”Degussa “Protectosil”Frabrikem “Fabrishield PR-63”Prof. Products of Kansas “Prof. Water Sealant & Anti-Graffitiant”
6. Pre-application meeting with manufacturer, owner and applicator before installation.
7. Masonry wall applications shall be applied by masonry contractor, not a painter.
Standard Specification The Evergreen State College
DIVISION 9 FINISHES
Page 18Division 9 Finishes Facilities ServicesRevised 7/17/17
NOTES:1. Use Type X Fire-resistant gypsum board panels at fire rated assemblies.2. Check with RAD regarding their floor covering requirements on RAD projects.
Standard Specifications The Evergreen State College
DIVISION 10 SPECIALTIES
Page 14Division 10 Specialties Facilities ServicesRevised 11/21/17
Section No. Title Comments
10 11 00 VISUAL DISPLAY SURFACES
1. Markerboards and Chalkboards:a. Porcelain enamel on 24 ga. steelb. Greenguard Certified particleboard laminated to face
sheet. Manufacturer’s standard thickness c. Provide with aluminum backing sheetd. Secure to walls with concealed clips not adhesivese. Clear anodized aluminum edge trim on all sidesf. Horizontal sliding and units made of more than one
panel shall be factory assembled in a sliding panel frame. Manually operated, top supported with extruded aluminum guide and track. Clear anodized finish
g. Combination units: Join panels of multiple units with different construction with H-shaped extruded aluminum molding; finish to match frame. Multiple panels of same construction shall have butt joints
h. Display panels are program dependent2. Accessories:
a. Map rail: extruded aluminum, run full width of frame, with cork insert, finish to match frame
b. Map supports: Formed aluminum sliding hooks to fit in map rail
c. Fit with pen / chalk tray, finish to match frame3. Tackboards:
a. ¼” thick Forbo “bulletin board”b. Clear aluminum trim framec. Glue applied as per manufacturer
10 14 00 SIGNAGE Interior:1. Standard signs for interiors shall have fasteners that are
tamperproof.2. Building Plaque: If project entails a building dedication
plaque it shall be cast bronze with contrasting typeface, locate near entry. Coordinate with Owner regarding wording and design.Exterior:1. Review building indicator signage ideas with owner.2. Standard signs (stop signs, no parking, etc…) shall be
mounted on minimum 2-inch diameter aluminum
Standard Specifications The Evergreen State College
DIVISION 10 SPECIALTIES
Page 15Division 10 Specialties Facilities ServicesRevised 11/21/17
Section No. Title Comments
posts that are solid grouted. No wood posts shall be used.
3. Standard signs located near / adjacent to public roads and could be struck by out of control vehicles shall meet WA DOT standards.
10 21 00 TOILET COMPARTMENTS
1. Manufacturer: Bobrick a. Sierra Seriesb. Ceiling mounted, architect to coordinate with
structural.c. Hinges: Full height heavy-gauge type 304 stainless
steel, self-closing, d. Continuous angle at walle. Non-removable fasteners when exposedf. All stainless hardware, including fastenersg. Stile base leveling device for floor variations, with
one-piece 3” high stainless steel shoe with concealed fasteners
h. Coat hooks with rubber bumperi. Aluminum slide latchj. Rubber door bumper with aluminum mountingk. Aluminum strike and keeper with rubber bumper
10 21 23 CUBICLE CURTAINS AND TRACK
1. Barjan or Inpro preferred.2. Ceiling mount track.
10 22 26 VERTICAL FOLDING ACOUSTIC PARTITIONS
1. Skyfold Classic 55 preferred if budget allows.2. Plastic laminate finish up to 8-feet above finished floor.
Cloth or vinyl finish allowed above 8-feet.3. Demountable Partitions and Accordion Partitions are not
allowed.
10 26 13 CORNER GUARDS 1. Basis of design: InPro 16-ga, 3-1/2” wings, 48” length, stainless steel type 430.
2. Provide at all GWB outside corners in corridors and common areas.4. Preference to start on top of wall base, not at floor level.
Standard Specifications The Evergreen State College
DIVISION 10 SPECIALTIES
Page 16Division 10 Specialties Facilities ServicesRevised 11/21/17
Section No. Title Comments
10 28 00 TOILET AND BATH ACCESSORIES
1. Basis of design: Bobrick mirrors, B-290 with stainless steel welded frame with shelf. Minimum .03-inch galvanized steel sheet backing with non-absorptive and shock absorbing filler. Concealed tamper-proof fasteners. Bradley also approved manufacturer
2. Hand dryers to be “Xlerator” Model XL-W or Dyson Airblade V
3. TP dispensers - F.O.I.C.4. Paper towel dispensers - F.O.I.C.5. Soap dispensers - F.O.I.C.6. Seat cover dispensers – Bobrick model B-42217. Grab bars, shelves, clothes hooks, toilet seat cover
dispensers: Basis of design: Bobrick or approved equal, with stainless steel with brushed finish
8. Sanitary Napkin Disposal: Bobrick model B-4354. Sanisac also approved manufacturer
9. Custodial accessories: Bobrick stainless steel shelf and mop holder with hooks.
10. Baby changing station: Koala KB110-SSWM
10 44 00 FIRE PROTECTION SPECIALTIES
Fire extinguishers and cabinets:1. All extinguishers shall be in locking cabinets except in mechanical areas.2. Full glazing with lock in 1-1/4” frame3. Clear tempered glass4. Semi recessed with rolled edge.5. Steel with white enamel exterior and interior.6. Painted steel door and trim with clear acrylic with black
vertical letters “FIRE EXTENGUISHER”.7. Size cabinet accordingly to extinguisher size which is
dictated by the local jurisdiction. 8. Triangular acrylic 8” x 12” fire extinguisher signs at 8’
a.f.f. Install at each cabinet location in corridors or as required. Accuform Signs or approved, red with white graphics. Screw mounted.
Standard Specifications The Evergreen State College
DIVISION 10 SPECIALTIES
Page 17Division 10 Specialties Facilities ServicesRevised 11/21/17
Section No. Title Comments
10 51 00 METAL LOCKERS 1. Manufacturers:a. Art Metal Products, List Industries, DeBourgh
Manufacturing, Inc., Penco Products, Inc., Republic Storage Systems Company, Inc., Others as approved.
b. 10-year manufacturer warranty.
c. Basis of Design: List Industries-Marquis Booksafe II2. Components:
a. Frame: 16-gauge steel channels or 13-gauge steel angles, minimum.
b. Tops: Steel sheet, 24 gauge, minimum.c. Sloping tops with Flat Ends: 20-gauge, minimum; if
not built in to wall. d. Bottoms: Steel sheet; 24 gauge, minimum.e. Horizontal Dividers: 24-gauge steel sheet,
minimum.f. Sides and Vertical Dividers: 24-gauge steel sheet,
minimum.g. Exposed Ends: 16-gauge steel sheet, minimum,
without exposed holes.h. Backs: 24-gauge steel sheet, minimum.i. Doors: 16-gauge steel sheet, minimum. Provide
with extra stiffeners. j. Louvers: Manufacturers standard size and quantity
security vent.k. Door Handles: Recessed with single point latch, no
moving parts.l. Latching Mechanism: Concealed in door, designed
so that door can be closed while locked, single point spring-loaded latch engaging beveled strike on frame. Securely attach rubber bumpers to each door strike.
m. Hinges: Minimum 14-gauge steel, minimum five knuckle, welded or rivet to frame and door.
n. Miscellaneous Components and Trim: 18-gauge steel sheet, minimum.
3. Fabrication:a. Weld frame in multiple column units to meet job
conditions.
Standard Specifications The Evergreen State College
DIVISION 10 SPECIALTIES
Page 18Division 10 Specialties Facilities ServicesRevised 11/21/17
Section No. Title Comments
b. Weld or rivet hinges to frame and secure to door with not less than two fasteners, which are concealed, and tamperproof when door is closed.
10 74 00 MANUFACTURED EXTERIOR SPECIALTIES
Skateboard Deterrents:1. For concrete benches or low walls along walkways:
a. Skatestoppers “G” Series or approved equal stainless steel device for surface mounted applications. Epoxy in place.
b. Skatestopper “F2” or approved equal stainless steel for recessed poured in place applications.
College preference is to construct recesses into such walls, benches and planters so they deter skateboard grinding of the concrete. Placement at every 4-feet or so. See below for an example.
Standard Specifications The Evergreen State College
DIVISION 11 EQUIPMENT
Division 11 Equipment Page 1 Facilities ServicesRevised 11/21/17
Section No. Title Comments
11 16 00 VAULTS High Security Government Key Box:a. Manufacturer: Knox-Boxb. Model: 3274, hinged, dark bronze, recessed
mountc. Order from
https://www.knoxbox.com/store/Knox-Box-3200-Series.cfm Or obtain order form from McLane / Blacklake Fire Department, Thurston Fire Department District 9, 125 Delphi Road NW, Olympia
d. For first responder use as required by code11 16 16 SAFES 1. B Rated front loading depository safe.
2. ½” thick solid steel door protected with a drill resistant hard plate
3. ¼” thick solid steel body4. (5) 7/8” diameter solid steel active locking bolts5. Check program requirements regarding size.
11 31 00 RESIDENTIAL APPLIANCES
1. Furnished by Owner installed by Contractor
11 40 00 FOOD SERVICE EQUIPMENT
1. Review in detail with Food Service staff.
11 52 13 PROJECTION SCREENS
1. If required refer to C&C Capital Projects Design Checklist.
11 52 16 PROJECTORS 1. If required refer to C&C Capital Projects Design Checklist.
11 53 13 LABORATORY FUME HOODS
1. Program dependent.
11 61 00 THEATER AND STAGE EQUIPMENT
1. Program dependent.
11 68 00 PLAYFIELD EQUIPMENT AND STRUCTURES
1. No wood products.2. Porter exterior volleyball equipment shall be basis of
specification.3. Coordinate selections and layout with Maintenance staff.
11 82 00 SOLID WASTE HANDLING EQUIPMENT
1. Consider use if space for waste is limited in size.
Standard Specifications The Evergreen State College
DIVISION 12 Furnishings
Division 12 Furnishings Page 1 Facilities Services11/21/2017
Section No. Title Comments
12 21 00 WINDOW BLINDS 1. 1-inch aluminum blinds, no valance.2. Basis of design: Bali 1” LightBlocker. Hunter Douglas
and Levelor also allowed.
12 24 13 ROLLER SHADES 1. MechoSystems: Classic Mecho/52. Manual operating, chain drive, room darkening3. Cloth: EcoVeil 1350 Series, 5% open, 100% TPO4. Continuous removable aluminum fascia, mount direct
to bracket without adhesives, magnetic strips, or exposed fasteners.
12 30 00 CASEWORK Plastic Laminate Clad Manufactured Casework:1. Manufactured by: Pacific Cabinets Inc.; Genothen, and
ISEC, Inc. products preferred.2. Quality certification in accordance with AWI/AWS
Quality Certification Program.Finish Materials:
1. Interiors of cabinets and drawers: White melamine 2. Faces of doors and drawers: Plastic laminate by
Wilsonart, Formica, Nevamar or Pionite preferred. GP50 grade with .020-inch backing bonded to substrate at countertops. GP50 grade laminate applied to face before top surface is applied.
Edge-banding: 1. Cabinet ends, doors and drawer fronts: 3 mm PVC,
color to match cabinet end2. Edges of cabinet shelves, sub-tops, bottoms and
partitions and exposed edges at underside of cabinets and drawer parts: .024-inch thick PVC. Color to match cabinet interior.
Cores and substrates: 1. Dry solid stock, plywood preferred. Consult with
Owner regarding use of particleboard and medium density fiberboard. Laminate core material shall be premium grade 45-pound density particleboard with the following exceptions:
a. At countertops with sinks, including backsplashes: use ¾” thick exterior grade plywood substrate
b. Overall thickness at countertops to be 1-1/2”All wood cores and substrates shall be formaldehyde free
Standard Specifications The Evergreen State College
DIVISION 12 Furnishings
Division 12 Furnishings Page 2 Facilities Services11/21/2017
1. Shelves:a. Under 36” – ¾” minimum thickness. b. Shelves 36” and wider – 1” plywood corec. Open shelf units shall be 1” thick plywood core
with plastic laminate finish on all exposed surfaces.d. Plastic laminate shelving shall be GP50 grade
laminate with .020-inch backing sheet bonded to plywood substrate. All exposed edges; self-edged, edges applied after top surface is applied.
Backsplash: 1. 6” high typical, ¾” thick, factory attached with
screws at 6” o.c. Install with waterproof sealant, substrate to be same as countertop.
Drawers:1. Manufactured of standard wood construction type
with the following exceptions:a. Heavy duty drawers at Labs shall be ½” thick
plywood overlaid to match cabinet interiors for drawer bottoms, drawer sides and sub-fronts.
Doors:1. All doors, including sliding units, shall be of
manufacturer’s standard construction.Cabinet backs:
1. Manufacture’s standard construction, with the following exception:a. Provide removable backs as needed to access
mechanical and electrical components.Full height storage units:
1. End panels: ¾” thick2. Shelving: ¾” thick plywood3. Provide with 7 shelf units, 4 to be adjustable and 3
fixed. Fit with metal book / shelf dividers.Hardware:
1. Commercial grade five knuckle hinges US26D.2. Stainless steel bent wire metal pulls, 3.5-inches long
x 5/16” diameter.3. Steel shelf clips – nickel plated.4. Olympus locks – with rekeyable 5-pin tumbler.
a. Drawer: Model 100DWb. Door: Model 100DR
5. Slide bolt at interactive pairs of doors: Epco 9106. Sliding glass door locks: Ratchet type, National
C8140
Standard Specifications The Evergreen State College
DIVISION 12 Furnishings
Division 12 Furnishings Page 3 Facilities Services11/21/2017
7. Keying: Key per program requirements. Furnish six (6) master keys. Refer to door hardware section for requirements on keying meeting.
Accuride slides: 1. Box drawer slides to be full extension No. 3832
with 100 lb. load rating.2. Thin drawers to be full extension No. 3832 with
100 lb. load rating.3. File drawers to be full extension No. 4032 with 150
lb. load rating.Accessories:
1. Adjustable shelf supports: L-shaped with peg fitting; Liberty Hardware No. A11520G-PB-U
2. Clothes Rods: Knape & Vogt KV 750, 1-5/16” diameter rod, chrome finish with .075” thick steel wall.
3. Wire grommets: Hafele No. 631.26.301 – black, 60 mm diameter, two-piece
4. Catches: Commercial grade with maximum 5 lb. pull rating – Epco No. 1000, color to match cabinet interior.
5. Coat hooks to be Ives 580, 581, 582 preferred.6. Vibration isolation pads: Mason Industries Mini
Super W Pads, use under casework where indicated.7. Shelf support brackets:
a. At countertops: 16 ga. 1-1/2” tube steel with welded construction, designed to support countertops off wall, color: black, 18” x 21” for 26” deep, 21” x 27” for up to 32” deep.
b. At shelves: 1-1/4” steel flat bar with ¼” wire rod gusset, all welded and designed to support up to 15-inch deep shelf, black powder coated finish.
8. Wall standards and brackets: extra-duty by Knape & Vogt 85/185 Series
12 46 19 CLOCKS See Section 27 53 13 for GPS wireless clock system12 93 00 SITE FURNISHINGS 1. Bicycle racks:
a. Ground mounted bolt down.b. Powder coated black.
2. Benches:a. Bolt downb. Powder coated, black, no wood.
3. Tables:a. Bolt down.
Standard Specifications The Evergreen State College
DIVISION 12 Furnishings
Division 12 Furnishings Page 4 Facilities Services11/21/2017
b. Powder coated or Anodized Aluminum, no wood.
Standard Specifications The Evergreen State College
DIVISION 14 Conveying Equipment
Division 14 Conveying Equipment Page 1 Facilities Services
1/3/2018
Section No. Title Comments
14 20 00 ELEVATORS
1. Types:
Preference of college to use jackless hydraulic
elevators whenever possible.
2. Manufactueres:
a. Kone
b. Otis
c. Thyssen-Krupp
d. Fujitec
e. Mitsubishi
3. Controllers:
Non-proprietary elevator controls only allowed.
Do not allow elevator manufacturers to use their
own controllers if they are considered
proprietary. Controllers shall be accessible for
service without use of proprietary code, device
or electronic key. This applies to routine service
and all programming functions that can be done
by any maintenance personnel in the field under
applicable ASME codes. Specify products by
Elevator Controls and Motion Control
Engineering (MCE), G.A.L. Manufacturing,
JRT, Inc. controls, or an equal if approved by
the college engineer prior to publication of
specifications.
4. Speed:
Preference is 150 fpm
5. Cab Height:
9-feet, typical
6. Car Operating Panel:
Shall include vandal resistant buttons, digital
position indicator / lantern combination,
lockable panel with window for permit, recessed
telephone and intercom, vandal resistant
fasteners.
7. Hall Station:
a. LED digital floor position indicator lantern,
typical
8. Door Operators:
By G.A.L. Manufacturing
Standard Specifications The Evergreen State College
DIVISION 14 Conveying Equipment
Division 14 Conveying Equipment Page 2 Facilities Services
1/3/2018
9. Renovation of Elevator Machine:
Include new gaskets (no split style shaft seals)
for machines and reassembly with new gear oil.
10. Edge Control:
a. Pana 40
b. Traction elevator cable terminations shall be
shackled, with ends secured.
11. Car Finishes:
a. Utility elevators: Use durable, vandal resistant
elements for cars that have been "tagged" or
otherwise abused as with impact damage from
pallet jacks and cargo loading. Design elements
may include vandal resistant lighting, no
decorative ceiling but a painted and repaired
cartop, rubber tiled floor, stainless steel or
aluminum diamond plate interior panels, and
low level bumpers to limit cargo damage.
b. Passenger elevators:
i. Wall finish: Raised laminate faced
panels selected from manufacturer’s
standard laminates.
ii. Handrails: ½” x 2” flat rail of satin
finished stainless steel on three walls.
iii. Ceiling: Drop ceiling stainless steel or
mirror finished with LED lights
iv. Door: Interior shall be of satin / polished
stainless steel finish. Exterior / corridor
or lobby side: Painted door and frame
with color selected from manufacturer’s
standard colors.
v. Flooring: Finish shall match that of the
adjoining first floor lobby.
vi. Threshold: Nickle finish.
12. Hoistway:
Size of the hoistway should be calculated to be
large enough to work with multiple elevator
vendors.
13. Keying:
a. FEO –K1 for fire recall service
b. EPCO 27 for hatch access control
c. EPCO 1 for attendant service, out-of-service,
fan and lighting controls, and other common
owner controlled items.
Standard Specifications The Evergreen State College
DIVISION 14 Conveying Equipment
Division 14 Conveying Equipment Page 3 Facilities Services
1/3/2018
NOTES: The specification shall call for installation of the elevator(s) to be completed, inspected and
approved by L&I for the owner’s use at least 24-hours before the date of Substantial Completion.
Substantial Completion will not be achieved if this is not accomplished. If this is not achieved by
the noted Substantial Completion date the General Contractor will be responsible for all fees
associated with the operation of the elevator until L&I approval for general use is granted.
d. Switches accessible only through a locked
access door (EPCO 1) shall not be keyed unless
required by code.
14. Optional / Accessories:
a. Use of energy recovery system / regeneration
unit or drives preferred
b. Fit car walls with wall studs for hanging
protective blankets / pads. Fully supply each car
with moving blankets / pads made of 100%
cotton with canvas facing. Blankets / pads shall
be fitted with metal grommets that align with
wall stud locations.
Standard Specifications The Evergreen State College
DIVISION 22 PLUMBING
Division 33 Utilities Page 1 Facilities Services11/21/2017
Section No. Title Comments
22 00 00 PLUMBING
General:1. Waterless traps seals are preferred over trap
primers. Call out IPS Corp. “Green Drain”, or approved equal waterless trap seal for floor drain locations.
22 42 00 COMMERCIALPLUMBING FIXTURES
1. Urinalsa. Basis of design: Sloan HEU, SU-1009 fixtureb. Other approved manufacturers:
i. Kohlerii. American Standard
iii. Acorniv. Zurn
2. Water Closetsa. Basis of design: Kohler K-4325-0, whiteb. Other approved manufacturers:
i. Sloanii. American Standard
iii. Acorniv. Zurn
3. Flush Valves at Urinalsa. Basis of design: Sloan 186 SMO 0.125 gallonb. Other approved manufactuers:
i. Kohlerii. American Standard
iii. Acorniv. Zurn
4. Flush Valves at Water Closetsa. Basis of design: Sloan Royal 143-1.6 ESSb. Other approved manufactuers:
i. Kohlerii. American Standard
iii. Acorniv. Zurn
5. Undercounter Sinksa. Basis of design: American Standard Ovalyn,
Vitreous china, white, unglazed rim, 19-1/4” x 16-1/4”
b. Other approved manufactuers:i. Kohler
Standard Specifications The Evergreen State College
DIVISION 22 PLUMBING
Division 33 Utilities Page 2 Facilities Services11/21/2017
Section No. Title Comments
ii. American Standardiii. Acorniv. Zurn
6. Wall Hung Sinksa. Basis of design: Kohler Greenwich K-2031-0,
Vitreous china, white, use with in-wall concealed arm support brackets.
b. Other approved manufactuers:i. Kohler
ii. American Standardiii. Acorniv. Zurn
7. Wall Hung ADA compliant sinksa. Basis of design: Kohler Morningside K-12638-
0, Vitreous china, white, use with in-wall concealed arm support brackets
b. Other approved manufactuers:i. Kohler
ii. American Standardiii. Acorniv. Zurn
8. Sink Faucetsa. Basis of design: Chicago Faucets Model
116.221.AB.1, 0.5 GPM chrome plated vandal proof pressure compensating econo-flo non-aerating spray, dual beam infrared sensor, 5-year mechanical warranty.
9. Custodial Sinka. Basis of design: American Standard Florwell
Service Sink, white, cast iron enamel coated, floor mounted.
b. Other approved manufacturers:i. Zurn
ii. Acorn10. Custodial Faucet
a. Basis of design: Chicago Faucets Model 897-CP, 8” body, vacuum breaker spout, vandal proof lever handle, chrome plated finish, 5-year
Standard Specifications The Evergreen State College
DIVISION 22 PLUMBING
Division 33 Utilities Page 3 Facilities Services11/21/2017
Section No. Title Comments
cartridge warranty.11. Utility / Service Sink
a. Basis of design: American Standard Lakewell Service Sink, white, cast iron enamel coated, with drilled back 2 holes at 8” o.c.
b. Other approved manufacturers:i. Zurn
ii. AcornUse same faucet as noted for Custodial Faucet.
22 45 16 EYEWASH EQUIPMENT
1. Eye Wash Stationa. Basis of design: Haws Model 7656WWC ADA
compliant eye / face washb. Also approved:
i. Haws Model 7360BTWC ADA compliant eye / face wash
iii. Acorn Model S0440-BFiv. Acorn Model S3160-RA
22 47 13 DRINKING FOUNTAINS
1. Basis of design:a. Elkay Model LVRCGRN8WSKP, Stainless
Steel, Single ADA wall mounted cooler with bottle filler.
b. Other approved manufacturer:i. Haws Model 1109 with 1920 bottle
filler
Standard Specifications The Evergreen State College
DIVISION 31 EARTHWORK and 32 EXTERIOR IMPROVEMENT
Division 31 Earthwork & 32 Exterior Improvement Page 1 Facilities Services11/21/2017
Section No. Title Comments
31 10 00 SITE CLEARING 1. Upon tree removal, remove entire stump. Fill and compact depression.
2. Export all woody debris and dispose of properly off site.
31 21 00 EARTH MOVING 1. Minimize grading to the maximum extent possible.2. Prevent run-off from leaving site with the use of
swales.3. Discourage use of retaining walls. If required the use
of Rockery Retention walls is preferred.4. Note if soils are moisture sensitive.5. Use non-moisture sensitive soil for structural backfill –
see Geotech report for specific site.6. Pipe bedding material shall be sand or peagravel for
water, waste, storm and all conduit.7. All utilities must have tracer tape 12” below finished
grade.8. Use sand bedding for irrigation lines.9. Exterior grade shall be minimum 6-inches below
subfloor and shall slope away from the building.10. A 2-percent slope for all exterior surfaces is preferred.
31 62 00 DRIVEN PILES 1. Discourage use.
31 63 00 BORED / AUGEREDPILES
1. Preferred over driven piles.
32 13 00 RIGID PAVING 1. Class B asphaltic concrete per WSDOT Standard Specifications. See cement concrete paving below.
2. Sidewalks with light broom finish. No picture framing, no exposed aggregate finish.
3. Control/expansion joint spacing applicable to minimize cracking.
4. Cement concrete paving a. Minimum 6-inch thickness with 2-inch CSTC at
standard sidewalks not designed for vehicle use.b. Minimum 6-inch thickness with 6-inch CSTC at
standard sidewalks and areas intended for vehicle use.
c. Use minimum 8-inch thickness with 6-inch CSTC at all designated fire lanes. Install metal dowels between cold joint panels.
Standard Specifications The Evergreen State College
DIVISION 31 EARTHWORK and 32 EXTERIOR IMPROVEMENT
Division 31 Earthwork & 32 Exterior Improvement Page 2 Facilities Services11/21/2017
Section No. Title Comments
32 14 16 BRICK UNIT PAVING
1. Manufacturer: Mutual Materials2. Type: Light-traffic paving brick meeting ASTM C902,
Class SX, Type I3. Size: 4”x8”x1-1/2”4. Color: Chestnut5. Mortar Bed: Laticrete MVIS Premium Mortar Bed6. Bond Coat Mortar: Laticrete Hi-Bond Masonry Veneer
Mortar, or accepted equal7. Grout: High-performance sanded cement grout meeting
ANSI A118.7(Note: The College will continue to use brick paving at Red Square but is tending to get away from continuing its use on other areas of campus)
32 16 00 CONCRETECURBS
1. All concrete curbs shall be cast-in-place, no extruded concrete curbs.
2. Mechanically fastened precast curb stops are preferred.
32 31 00 FENCES & GATES 1. Chain link in compliance with DOT standards.2. Galvanized – No vinyl coated unless program requires
differently.3. Height and fabric gauge at athletic fields appropriate to
activities.4. Provide concrete mow strips, extended 12” out from
face of fence.5. Vinyl vision slats are allowable, but must be screwed
into top metal bar to prevent from being pulled out.6. Ensure that all double gate latch mechanisms align
properly and operate correctly.32 80 00 IRRIGATION 1. Toro Sentinel irrigation controller. Pedestal mount in a
stainless steel enclosure set on a 4” thick concrete slab. 2. Toro TFS 2” flow sensor. Install with data connection
to controller unit.3. Toro 220 Master Valve.4. Heads: Hunter Nozzles (MP rotator series, or other
Hunter Nozzles as required to meet variations in irrigation conditions / needs) on Hunter Pros-Spray PRS40 bodies.
5. Wilkins 950XL (with union ball valves) backflow preventer.
6. Valve boxes for pedestrian areas shall be Carson HDPE 14”x19” below grade enclosures with cover set flush with adjacent grade.
7. Valve boxes for areas that might be driven over by
Standard Specifications The Evergreen State College
DIVISION 31 EARTHWORK and 32 EXTERIOR IMPROVEMENT
Division 31 Earthwork & 32 Exterior Improvement Page 3 Facilities Services11/21/2017
Section No. Title Comments
maintenance equipment (not vehicular) Fibrelyte Composite. Size as needed, below grade enclosure with cover set flush with adjacent grade.
8. Piping shall be PVC Sched 40 with equivalent fittings.9. Tracer wire: 14-gauge with blue plastic coating.10. Controller wire: Solid copper, UL listed for direct
burial use, size as needed for length of wire run.11. Do not install controller wires to zone valves under
main line.32 91 13 SOIL
PREPARATION1. Subgrade material – Remove all concrete, riprap,
asphalt materials prior to adding soil mix. Compacted subgrade shall be broken up to allow for proper drainage. Obtain owner’s approval prior to installation of topsoil.
2. 8” minimum depth topsoil at all planting beds and lawn areas.
3. Soil mix: 60 % clean loamy sand, 40% soil amendment as specified by Landscape Architect.
32 92 00 TURF & GRASSES 1. Ornamental lawn (full sun) – 100% 3 way rye grass mix.
2. Ornamental lawn (partial shade) – 70% 3-way rye grass mix, 15% Chewing fescue, 15% Creeping red fescue.
3. Sports fields – 60% Perennial rye, 20% Fine fescue, 20% Kentucky bluegrass.
4. Provide 3 way rye sod at building perimeter if budget allows. Sod to be provided by Country Green Turf Farms.
5. All seed mixes to have less than 0.1% weed seed.6. No turf areas less than 8’-0” wide.7. Consider slope of 3:1 as maximum mowable slope.
32 93 00 PLANTS 1. Landscaping shall be low maintenance.2. Encourage use of indigenous drought resistant plants.3. Use low growth shrubs next to buildings or ground
cover with bark nuggets over weed blocking fabric.4. Minimize use of lawns.5. Minimize use of deciduous trees.6. Encourage use of conifers.7. Do not locate trees under parking light poles 8. Use high canopy trees at street approach and planting
islands.9. All planting locations shall avoid creating hiding spots.10. Hold trees away from buildings, minimum. 20’-0”
separation
Standard Specifications The Evergreen State College
DIVISION 31 EARTHWORK and 32 EXTERIOR IMPROVEMENT
Division 31 Earthwork & 32 Exterior Improvement Page 4 Facilities Services11/21/2017
Section No. Title Comments
11. Meet minimum Thurston County requirements. 12. Remove wire baskets from all trees prior to planting.13. All plant material shall meet AAN standards and
grades. #1 Grade to be used at all times.14. Topsoil: loam with 20-percent composted organics.15. Fertilizer: appropriate for season and region.
NOTES: PAVEMENT MARKINGS
1. Use WSDOT Standard Specifications.2. Thermoplastic bars at crosswalks.
Standard Specifications The Evergreen State College
DIVISION 33 UTILITIES
Division 33 Utilities Page 1 Facilities Services11/21/2017
Section No. Title Comments
33 12 19 FIRE HYDRANTS 1. Basis of design: Mueller Super Centrurion, or M&H equivalent.
2. 5-1/4” main valve opening three way (two hose and one pumper nozzle)
3. 10-year warranty on material and workmanship4. Post type dry-barrel design5. Dry top design with O-ring sealed oil reservoir.6. Fit with 5” Storz adapter.7. Paint with Sun Yellow high-grade enamel #13312.8. Gate valve by fire hydrant manufacturer and shall be
located between 6 to 8-feet from the hydrant. Access cover to be flush with grade and set in concrete.
9. Bag hydrants until system is functional and approved for service.
33 73 00 UTILITY TRANSFORMERS
1. Utilize Liquid-Filled Utility Transformers.2. Exterior installation is preferred.