evolution of the fault locator o n mv distribution networks: from … · 2018-09-10 · installed...

4
C I R E D C I R E D C I R E D C I R E D 21 st Internationa Paper No 0507 Evolution of the Fault Locator o o sophisticated strat e e Roberto CALONE Enel Distribuzione – Ital [email protected] ABSTRACT The paper describes the evolution of during the time, their performances and the reasons that lead to this evolution. Describes the various versions that h focusing on the latest generation of fault reasons that led to its definition. INTRODUCTION ENEL started using Fault Passage Indi MV networks in the ‘90s, when in North important requests of higher quality of su medium-small industries in the area, as a the introduction of high technology controlled apparatus and machines. Over the years, with the increasing improvement of quality of service, the becoming increasingly sophisticated. B descriptions of the FPIs first, sec generations, concluding with a more de of the fourth generation currently being te EVOLUTION OF FAULT INIDICATOR The First generation First FPIs where battery supplied, have t poles and were sensitive to the magn consequence, FPI had the capacity overcurrents (poliphase faults) and me residual current (higher than 20 A in firs in the more recent ones). No directiona possible, due to the absence of v Discrimination between fault upstream the FPI installation point was possible du of the network, i.e. the contribution t both polyphase and single phase, has to time, it really was) much higher from network with respect to the one from dow Furthermore, no remote communication download FPI information, only local available. In case of a permanent fault, it w individuate the faulty section “following” along the feeder, using local signals instance proper lamps); to increase preventive maintenance, instead, expec non permanent fault (giving transient i al Conference on Electricity Distribution o on MV distribution networks: from simple st a a e egic component of the SMART GRID control l Alberto CERRETTI Alessandro ly Enel Distribuzione – Italy Enel Distribuz m [email protected] alessandro.fatic f Fault Locator d their limits and ave taken place t locator and the icators (FPIs) on East part of Italy upply came from a consequence of and computer g demands for FPI has evolved Below are brief cond and third etailed discussion ested. PASSAGE to be installed on netic field; as a to detect high edium-low value st versions, 10 A al detection was voltage signals. and downstream ue to the features to fault currents, o be (and, at the m the upstream wnstream part. n was present to connection was was possible to ” the fault “path” s from FPI (for e efficiency of cially concerning interruptions) it was possible to collect inform proper period and, manually distribution on the differe consequently, possible weak permanent fault occurs. Evolutions of these FPI a DISTRIBUZIONE, in some portable version. Pole installed versions had equipped with transmission events and with electric field voltage presence, therefore ab self-extinguish faults and fa intervention). Figure 1: Example of first versions, portable or pole in transmission) The Second generation The first generation devices massive introduction of P DISTRIBUZIONE MV netw reduction of residual currents with 0 fault resistance), it directional detection of phase In addition, a survey perfo voltage and current values re devices in presence of a phas the minimum sensitivity thre low even with insulated neu percentage of phase to earth f possible evolution in a perma Finally, it was decided to ha the recorded information and FPI for local tripping operatio disconnectors. Due to this, a new version o directional detection of phase the SCADA system and in control and automation syste inputs using signals coming Frankfurt, 6-9 June 2011 Paper 0507- 1/4 a and alone device, to a l l system FATICA zione – Italy [email protected] mation from many FPIs in a y, to analyze transient fault ent feeder sections, and, k insulation points before a are still used from ENEL circumstances, but in the d been evolved too, being n systems of the detected d sensor (necessary to detect ble to discriminate between aults cleared through a CB generation FPIs (modern nstalled, with distance data worked quite well until the Petersen coils on ENEL work [1]. Due to the drastic s (maximum 50 A at 20 kV was necessary to introduce to earth faults. ormed on tripping residual ecorded from MV protection se to earth fault showed that eshold of the FPIs was too utral, so that an important faults were not detected with anent fault [2], [3]. ave the remote download of d to use local signals from ons of motor operated switch of FPI was developed, with to earth faults, integrated in n the MV network remote em, obviously with voltage g from capacitive dividers

Upload: others

Post on 15-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Evolution of the Fault Locator o n MV distribution networks: from … · 2018-09-10 · installed and in operation both in Italy and in Rumenia, on ENEL distribution networks, on

C I R E DC I R E DC I R E DC I R E D 21st International Conference on Electricity Distribution

Paper No 0507

EEvvoolluuttiioonn ooff tthhee FFaauull tt LLooccaattoorr oossoopphhiissttiiccaatteedd ssttrraattee

Roberto CALONE Enel Distribuzione – Italy

[email protected]

ABSTRACT

The paper describes the evolution of Fduring the time, their performances and their limits and the reasons that lead to this evolution. Describes the various versions that have taken place focusing on the latest generation of fault locator and the reasons that led to its definition.

INTRODUCTION

ENEL started using Fault Passage IndicatorsMV networks in the ‘90s, when in North East part of Italy important requests of higher quality of supply came from medium-small industries in the area, as a consequence of the introduction of high technology and computer controlled apparatus and machines. Over the years, with the increasingimprovement of quality of service, the becoming increasingly sophisticated. Belowdescriptions of the FPIs first, secondgenerations, concluding with a more detailed discussionof the fourth generation currently being tested

EVOLUTION OF FAULT INIDICATOR

The First generation First FPIs where battery supplied, have to be installed on poles and were sensitive to the magnetic fieconsequence, FPI had the capacity to detect high overcurrents (poliphase faults) and mediumresidual current (higher than 20 A in first versions, 10 A in the more recent ones). No directional detection was possible, due to the absence of voltage signals. Discrimination between fault upstream and downstream the FPI installation point was possible due to the features of the network, i.e. the contribution to fault currents, both polyphase and single phase, has to be (and, at the time, it really was) much higher from the upstream network with respect to the one from downstream part.Furthermore, no remote communication was present to download FPI information, only local connecavailable. In case of a permanent fault, it was possible to individuate the faulty section “following” the fault “path” along the feeder, using local signals from instance proper lamps); to increase efficiency of preventive maintenance, instead, expecially concerning non permanent fault (giving transient interruptions)

International Conference on Electricity Distribution

oonn MMVV ddiissttrriibbuuttiioonn nneettwwoorrkkss:: ff rroomm ssiimmppllee ssttaaeeggiicc ccoommppoonneenntt ooff tthhee SSMMAARRTT GGRRIIDD ccoonnttrrooll

Alberto CERRETTI Alessandro FATICAItaly Enel Distribuzione – Italy Enel Distribuzione

[email protected] [email protected] [email protected]

er describes the evolution of Fault Locator during the time, their performances and their limits and

Describes the various versions that have taken place focusing on the latest generation of fault locator and the

Passage Indicators (FPIs) on MV networks in the ‘90s, when in North East part of Italy important requests of higher quality of supply came from

small industries in the area, as a consequence of high technology and computer

the increasing demands for , the FPI has evolved

Below are brief second and third

a more detailed discussion being tested.

EVOLUTION OF FAULT PASSAGE

where battery supplied, have to be installed on magnetic field; as a

had the capacity to detect high overcurrents (poliphase faults) and medium-low value

in first versions, 10 A ). No directional detection was

possible, due to the absence of voltage signals. Discrimination between fault upstream and downstream

installation point was possible due to the features of the network, i.e. the contribution to fault currents,

h polyphase and single phase, has to be (and, at the time, it really was) much higher from the upstream network with respect to the one from downstream part. Furthermore, no remote communication was present to

, only local connection was

In case of a permanent fault, it was possible to individuate the faulty section “following” the fault “path”

local signals from FPI (for ; to increase efficiency of

expecially concerning non permanent fault (giving transient interruptions) it

was possible to collect information from many proper period and, manually, to distribution on the different feeder sections, and, consequently, possible weak insulation pointspermanent fault occurs. Evolutions of these FPI are still used from ENEL DISTRIBUZIONE, in some circumstances, but in the portable version. Pole installed versions had been evolved tooequipped with transmission systems of the detected events and with electric field sensor (voltage presence, therefore able to discriminate between self-extinguish faults and faults cleared through a CB intervention).

Figure 1: Example of first generation FPIs (modern versions, portable or pole installed, with distance data transmission)

The Second generation The first generation devices worked quite well until the massive introduction of Petersen coilsDISTRIBUZIONE MV network [1reduction of residual currentswith 0 Ω fault resistance), it was necessary to introduce directional detection of phase to earth faults.In addition, a survey performed on tripping residual voltage and current values recorded from MV protection devices in presence of a phase to earth fault showed that the minimum sensitivity threshold of the low even with insulated neutralpercentage of phase to earth faults were not detected wipossible evolution in a permanent faultFinally, it was decided to have the remote download of the recorded information and to use local signals from FPI for local tripping operations of motor operated switch disconnectors. Due to this, a new version of directional detection of phase to earth faults, integrated in the SCADA system and in the MV network remote control and automation system, obviously with voltage inputs using signals coming from capacitive dividers

Frankfurt, 6-9 June 2011

Paper 0507-

1/4

aanndd aalloonnee ddeevviiccee,, ttoo aa ll ssyysstteemm

Alessandro FATICA Enel Distribuzione – Italy

[email protected]

was possible to collect information from many FPIs in a proper period and, manually, to analyze transient fault distribution on the different feeder sections, and,

sequently, possible weak insulation points before a

are still used from ENEL DISTRIBUZIONE, in some circumstances, but in the

Pole installed versions had been evolved too, being with transmission systems of the detected

and with electric field sensor (necessary to detect , therefore able to discriminate between

extinguish faults and faults cleared through a CB

first generation FPIs (modern

versions, portable or pole installed, with distance data

devices worked quite well until the introduction of Petersen coils on ENEL

DISTRIBUZIONE MV network [1]. Due to the drastic reduction of residual currents (maximum 50 A at 20 kV

, it was necessary to introduce directional detection of phase to earth faults.

performed on tripping residual alues recorded from MV protection

devices in presence of a phase to earth fault showed that the minimum sensitivity threshold of the FPIs was too

even with insulated neutral, so that an important percentage of phase to earth faults were not detected with

in a permanent fault [2], [3]. Finally, it was decided to have the remote download of the recorded information and to use local signals from

for local tripping operations of motor operated switch

a new version of FPI was developed, with directional detection of phase to earth faults, integrated in the SCADA system and in the MV network remote control and automation system, obviously with voltage inputs using signals coming from capacitive dividers

Page 2: Evolution of the Fault Locator o n MV distribution networks: from … · 2018-09-10 · installed and in operation both in Italy and in Rumenia, on ENEL distribution networks, on

C I R E DC I R E DC I R E DC I R E D 21st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

Paper 0507-

Paper No 0507 2/4

installed on MV switchboards, previously used for voltage presence lamps.

Figure 2: Example of installation with Petersen Coil Concerning phase to earth faults, detection principles and sensitivity was exactly the same of MV feeder protection panels in HV/MV substation (faults in the range 6,5 kΩ ÷ 4 kΩ can be detected with compensated neutral, this confirmed both in laboratories and with real field tests). About 100.000 of these devices are installed at the moment, with excellent results. In, fact, this FPI is the strategic component of MV automation system [4], [5], active on almost all the MV distribution network of ENEL DISTRIBUZIONE.

Figure 3: Example of second generation of FL

The third generation As no installation was possible on overhead networks, a third generation of FPIFPI was developed, with innovative integrated voltage and current sensors.

Figure 4: Detail of the voltage current sensor Global performances are the same as the cable version,

with a sensitivity up to 6,5 kΩ concerning phase to earth faults on compensated networks [6]. In addition to laboratory tests, real field tests were performed in 2008 on the global MV network automation system, including cable and overhead FPIs, both with compensated and insulated neutral, at the presence of many distribution Companies. At present moment some thousands of these FPI are installed and in operation both in Italy and in Rumenia, on ENEL distribution networks, on MV/LV substations connected directly to overhead feeders or on pole installed switch disconnectors.

Figure 5: Example of third generation of FPI

Figure 5: installation of an outdoor FPI on a substation

Figure 6: installation of an outdoor FPI on a pole installed switch disconnector

Page 3: Evolution of the Fault Locator o n MV distribution networks: from … · 2018-09-10 · installed and in operation both in Italy and in Rumenia, on ENEL distribution networks, on

C I R E DC I R E DC I R E DC I R E D 21st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

Paper 0507-

Paper No 0507 3/4

The fourth generation Starting from these new sensors, a fourth generation of FPI was defined, able for switchboard installation, and with a huge performance improvement. In fact, this new device will be a strategic component of the SMART GRID control system defined by ENEL. The new device, named RGDM (directional fault detection and measurement) is a advanced device with the following functions: • Protection functionality; • Automation functionality; • Measurement and monitoring functionality; • Distributed generation management functionality. The device consists in a central processing unit and three electronic integrated phase voltage and current sensors.. The estimation of the zero-sequence is obtained vector sum by insertion Holmgreen of the three current and voltage sensors. Voltage signals are obtained, on existing prototypes, through a capacitive divider, while current is derived by means of a Rogowsky coil.

Figure 7: two different prototypes of integrated voltage and current sensors Sensors are, at least, in 0,2 accuracy class, but, through the signal conditioning performed from the electronic card, the effective overall accuracy is much higher, allowing negligible phase and module error on residual current and voltage, compatible with the very low threshold settings required from ENEL protection system (2%÷6% residual voltage setting, 1,5 A÷ 2 A residual current setting, ∼ 10° maximum overall phase error, sensors and electronics, for 67N function from 1 A to 500 A phase current). RGDM will be equipped with a optical communication port with protocol IEC 61850.

Fault detection (protection) functionality - Directional overcurrent; - Directional phase to earth fault; - Cross country fault detection; - Re-striking faults detection; - Directional maximum active power; - Second harmonic retention for inrush currents.

Automation functionality - Logic selectivity (locking signal transmission and

reception) for single and multi-phase faults.

Measurement and monitoring functionality - Measurement of electrical values V, I, P, Q, power

factor; - Monitoring of the voltage harmonics in the node.

Distributed generation management functionality - Voltage value control along the MV line by

controlling static converters (for instance PV inverters);;

- Control and remote-trip of interface protection; - Power balance in the generation node. The integrated sensors will be directly factory installed in the switchboard housing new vacuum CBs (DY 800), which, in ENEL DISTRIBUZIONE plans, will be widely adopted at replacement of actual switch disconnectors.

Figure 8: installation of an outdoor FPI on a pole installed switch disconnector These CB will be installed, not only for MV network automation, but also for connection of MV Customers, both traditional (passive loads), and with internal generation (GD).

Figure 8: typical future solution for the connection of a PV plant to ENEL DISTRIBUZIONE MV network with DY 800 and RGDM

Producer premises

ProducerProtectionInterface

GeneralProtection

Production

supervision

System

SwitchEthernet

...

Inverters

Fiber To/From Distributorsupplying substation

ENEL DISTRIBUZIONE MV CB (for Customer

supplying, DY 800)

230 Vca

Router

MV power cables (20 kV)

Ethernet

Optical fiber (IP + 61850)

CENTRAL SCADA SYSTEM (STM)

HV/MV substation RTU

Batteries +Charger

24Vcc

Optical fiber (IP + 61850)CP

Interface

RGDM

Page 4: Evolution of the Fault Locator o n MV distribution networks: from … · 2018-09-10 · installed and in operation both in Italy and in Rumenia, on ENEL distribution networks, on

C I R E DC I R E DC I R E DC I R E D 21st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

Paper 0507-

Paper No 0507 4/4

BENEFITS AND POSSIBLE DEVELOPMENTS

With the new defined solutions many benefits are available: - the installation of combined sensors directly in the CB

switchboard will allow a high accuracy of RGDM, avoiding possible problems due to a non correct installation in field;

- RGDM will be tested in factory, with possible calibration/compensation of the sensors performed from electronic card: this will eliminate, both errors consequent to adjacent phases or adjacent MV cables which can affect ROGOWSKY coils ( dependent from switchboard design and realization), and/or errors of voltage sensors. This is possible thanks to the possibility to have, in factory, reference voltages and currents (in module and phase), hardly available in field;

- global cost of the CB equipped with RGDM will be lower with respect to traditional installation (FPI installed in the switchboard and only partially tested in field);

- in case of pure passive customers, it will be possible to extend the logic selectivity also to the internal plant, thanks to the customer switch connected to the MV/LV substation router through the optical fiber;

- in case of PV inverters it will be possible to control easily active and reactive power production. Settings will be transmitted to an Ethernet port on the inverters, in IEC 61850;

- in case of traditional generators a proper interface will be realized, able to communicate with voltage and frequency regulators;

- the measurements of all the electric parameters mandatory and necessary for the correct management of the distributed generation will be available, in particular active and reactive power generated/absorbed, with excellent accuracy;

- also the possibility to transmit a selective tripping signal, both to generators and to loads, will be available, therefore improving network safety and stability.

Concerning the future developments we point out that, recently, IEC TC 38 decided to create WG 46: “ Current and Voltage sensors or detectors to be used for fault passage indication purposes”. It’s expected to have a first draft to start discussions in the second half of 2011. Finally, it’s easy to imagine an evolution of the FPI in a protection device. This would be possible both developing the concept of an “integrated device” (a sort of “black box” assuring the whole system performances with adequate accuracy and reliability, without referring to single components, each one with its specific standards), and, with a more traditional approach, eliminating traditional CTs and VTs

(and their switchboards), installing integrated phase voltage-current sensors on each CB switchboard and using protections panels able to use directly low level signals. In both cases an appreciable cost reduction would be obtained, in addition to a reduction of space. REFERENCES For a Conference citation: [1] A. Cerretti, G. Di Lembo, G. Valtorta, CIRED 2005,

Turin, June, 6-9, 2005, “Improvement in the continuity of supply due to a large introduction of Petersen coils in HV/MV substations”,

[2] V. Biscaglia, D. Cappellieri, G. Gambelli, G. Guizzo, F. Panin, G. Rocchi, Proceedings of the Meeting "La qualita' del prodotto elettricita'. Interfacciamento Distributore-Utente", Verona, November 25-26, 1993 “Campagne di misura sulla rete elettrica: metodologia e risultati”

[3] A. Cerretti, G. Valtorta: “Rilevatore di guasto direzionale per l’automazione della rete di media tensione ”, L’Energia Elettrica, Volume 78 (2001)

[4] A. Cerretti, G. Di Lembo, G. Di Primio, A. Gallerani, G. Valtorta, CIRED 2003, Barcellona, May, 12-15, 2003, “Automatic fault clearing on MV networks with neutral point connected to ground through impedance”;

[5] A. Bargigia, A. Cerretti, G. Di Lembo, S. Rogai, G. Veglio, CIRED 2003, Barcellona, May, 12-15, 2003, “Telecontrol and automation on Enel Distribuzione’s network: strategy and results”;

[6] A. Cerretti, R. Calone, G. Di Lembo, L. Giansante, CIRED 2009, Praga, June, 8-11, 2009: “An innovative integrated current/voltage sensor for outdoor fault detectors”