eu1377-h

Upload: mspd2003

Post on 03-Apr-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/28/2019 EU1377-H

    1/22

    How Does AMetal OxideDistribution

    Arrester Work?

    Reprint of a Series of Articles from Ohio Brass

    POWER SYSTEMS, INC.

  • 7/28/2019 EU1377-H

    2/223

    The comments in this series apply toOhio Brass Type PDV and PVR

    arresters.

    The distribution class surgearrester is the most widely used of all

    arrester classifications. This high volume

    has held the cost to a level where, even

    in areas of relatively low thunderstorm

    activity, distribution surge arresters can

    be used to protect every pole top

    distribution transformer. In some casesof higher isokeraunic levels, distribution

    class surge arresters are also used for line

    protection and are installed periodically

    along the distribution line.

    Arrester design advances and progress

    have allowed for continued improve-

    ments in reliability and safety. The

    polymer-housed MOV distribution class

    Chapter One

    How Does a Metal-OxideDistribution Arrester Work?One in a Series

    MOV arresters depend on the nonlinear resistance characteristics of theirblocks for suitable discharge and continuous operating capabilities.

    Figure 1

    surge arrester is an excellent example ofthis trend toward higher reliability and

    safety. The polymer-housed arrester

    offers a lower failure rate and higher

    safety because of its leakproof design

    and its non-fragmenting characteristics.

    Arrester FunctionThe reason for applying an arrester is

    to provide overvoltage protection for

    electrical insulation, thereby maintaining

    high service reliability levels. It is

    worthwhile to discuss how the distribu-tion class surge arrester performs this

    function.

    The principal of the polymer-housed

    MOV distribution class surge arrester is

    quite simple. It is a device which is

    electrically connected in parallel with

    insulation needing protection. The

    polymer-housed distribution class metal-

    oxide surge arrester is connected line toground in parallel with this equipment.

    Therefore, it has a high resistance at the

    arresters normal 60-cycle operating

    voltage. As shown in Figure 1, the

    resistance of the metal-oxide arrester

    elements is a function of the voltage

    which is applied to them. At normal

    operating voltages, the resistance of the

    metal-oxide blocks is extremely high.

    The MOV arrester essentially behaves as

    an insulator at these voltages.

    Under a surge condition, the resistanceof the metal-oxide varistors drops

    dramatically and the arrester permits the

    surge to be diverted to the ground while

    providing equipment protection.

    The current which flows through the

    arrester is the discharge current, and the

    voltage which is developed across the

    terminals of the metal-oxide arrester is

  • 7/28/2019 EU1377-H

    3/224

    called the discharge voltage. Since thearrester is in parallel with the insulation,

    the discharge voltage of the arrester plus

    the voltage drop in the arrester leads

    equals the stress level to which the

    insulation is subjected. The voltage

    developed in the lead wires will be

    discussed in a later chapter of this series.

    After the discharge current has passed

    through the arrester and the voltage

    returns to normal system operating

    voltage, the arrester again has a higher

    resistance. The arrester then reverts tothe mode where it essentially behaves as

    an insulator.

    Arrester Designand Manufacture

    The metal-oxide arrester components

    are housed in an ESP rubber housing.

    The rubber housing provides an external

    electrical insulation for the internal

    components, and it also protects them

    from the effects of the elements. The

    ESP rubber housing prevents moisture

    from entering the arrester, causing an

    arrester failure. This is accomplished by

    a seal on each end of the arrester plus a

    live silicone interface between the

    internal elements and the rubber housing.

    The amount of internal air space inside a

    polymer-housed MOV distribution

    arrester is quite small compared to a

    porcelain-housed arrester. Therefore, the

    possibilities of moisture ingress are

    reduced or eliminated. Studies have

    indicated that nearly 90% of allporce-

    lain-houseddistribution arrester failures

    have been a result of moisture ingress.

    The metal-oxide varistors in the Ohio

    Brass distribution class arresters are

    manufactured in our high-volume facility

    in Wadsworth, Ohio. This facility is

    dedicated exclusively to the manufacture

    of metal-oxide varistors.

    The metal-oxide varistors consist

  • 7/28/2019 EU1377-H

    4/225

    primarily of zinc-oxide, with approxi-

    mately 5% of the remaining material

    consisting of various metal-oxides

    forming a boundary around zinc-oxide

    grains. These boundary regions give the

    metal-oxide varistor its nonlinear

    characteristics. (For more information on

    this please contact Ohio Brass.)

    The metal-oxide ingredients are

    processed to a powder state and then this

    powder is pressed to the necessary

    diameter to match the application. The

    metal-oxide varistors are fired in

    controlled-atmosphere kilns at tempera-

    tures over 2000F. The sides of the

    finished metal-oxide varistors are

    covered with an insulating electrical

    collar and the ends are given a metalized

    surface for electrical contact. This

    finished arrester component is referred to

    as a metal-oxide varistor.

    Ohio Brass manufactures normal duty

    polymer-housed MOV arresters (PDV-

    65) and heavy duty distribution polymer-

    housed MOV arresters (PDV-100). The

    primary differences between these

    designs are in the energy handling

    capability and the discharge voltage

    levels (protective levels) of these

    designs. The PDV-65 uses a metal-oxide

    disc 32mm in diameter and the PDV-100

    uses a disc 40mm in diameter. These

    differences will be discussed in more

    detail in later chapters.

    In the remaining chapters in this

    series, we will discuss other factors

    which are pertinent to distribution

    arrester application including ANSI

    Standard Terms and Tests, lightning

    phenomenon, testing of metal oxide

    varistors and assembled metal-oxide

    distribution arresters both in the factory

    and in the field, hardware accessories

    which are available for distribution

    arresters, protection of underground

    distribution systems, the effects of lead

    length, and other factors that should be

    considered in the evaluation and applica-

    tion of distribution class surge arresters.

  • 7/28/2019 EU1377-H

    5/226

    Chapter Two

    How Does a Metal-OxideDistribution Arrester Work?One in a Series

    PDV-100 Arrester, 9 kV Unit.

    Design distribution arrestersfor protection against surges

    To fully understand how distribution

    and riser pole arresters perform their

    functions, it is important to understand

    something about the nature of surges on

    the power system. The most common

    surges on the distribution system are

    from lightning. Therefore, in this

    installment, we will examine lightning

    and its characteristics.

    Lightning, completely unpredictable

    in most ways, is the most destructive of

    all elements associated with thunder-

    storms. Generated by massive thermal

    instability of the atmosphere, thunder-

    storms represent violent examples of

    convection whereby huge layers of the

    atmosphere are disrupted and overturned.

    Isokeraunic maps published by the

    government indicate the average number

    of thunderstorm days per year for areas

    of the United States. One thunderstorm

    day is defined as "a day on whichthunder is heard." One thunderstorm day

    could be one lightning stroke or it could

    be hundreds of lightning strokes. On the

    average, rural transmission lines in areas

    with an isokeraunic level of 30 thunder-

    storm days per year can expect to

    experience approximately one lightning

    stroke per mile per year.

    There have been recent advances in

    the field of lightning detection and

    measurement. In fact, maps are now

    being made that are useful in determin-ing the ground flash density. The entire

    nation is being monitored by The State

    University of New York Lightning

    Detection Network.

    Electric power lines are particularly

    vulnerable to lightning. Utilities in areas

    of average or high isokeraunic levels

    often report lightning as the primary

    cause of service interruptions and

    damage to equipment. Conductors,

  • 7/28/2019 EU1377-H

    6/227

    Isokeraunic map prepared by the National Weather Service with hatched areas indicating thunderstorm days per year.

    towers and poletop equipment all havethe attributes which make them attractive

    targets for lightning. Lightning invari-

    ably seeks the easiest path between

    positive and negative charged centers of

    the storm area, even if such paths add

    substantial length to the strokes.

    We know when lightning strikes a

    power line, there is a zone extending to

    each side of the actual stroke where the

    lightning voltage may greatly exceed the

    insulation level of the line and flashover

    to ground will occur instantaneously.

    Simultaneously, traveling waves are

    generated in the conductors on either

    side of the stricken point. These traveling

    waves have two components: voltageand current. The voltage magnitude is

    equal to the current magnitude multiplied

    by the surge impedance of the line and is

    less than the flashover voltage of the

    system insulation. These surges travel

    along the overhead line at about 1,000

    feet per microsecond (the speed of light).

    As much as possible must be known

    about the wave characteristics of the

    lightning surge in order to devise

    effective protection. This is a field in

    which scientists have made notable

    progress, and design engineers are able

    to separate lightning surges into a

    distinct category in relation to the broad

    spectrum of overvoltage surges. A typicallightning surge has an extremely steep

    wave front, which means that its voltage

    is rising at the rate of millions of volts

    per microsecond; in fact, 15 percent of

    strokes crest in less than one microsec-

    ond. The steep wave front is followed by

    a short wave tail, which means that after

    crest voltage is reached, surge voltage

    diminishes to half crest value in less than

    200 microseconds and completely

    dissipates in less than 1000 microsec-

    onds.

    The unpredictability of lightning

    reasserts itself in attempts to classify

    stroke dimensions, however, since it is

  • 7/28/2019 EU1377-H

    7/228

    an established fact that many lightning

    strokes are actually multiple discharges,

    one stroke following another along the

    path of the initial stroke. In contrast to

    the explosive short-duration stroke

    described as typical, there are occasional,

    relatively long-duration strokes.

    The development, testing, and

    correlation of insulation with lightning

    protective devices has been facilitated by

    adoption of a standard 1.2/50 voltage

    wave as representative of impulse surges.

    In the 1.2/50 wave, voltage crest is

    reached in 1.2 microseconds and the

    wave decays to half crest in 50 microsec-

    onds. High-voltage testing laboratories,such as at Ohio Brass, have developed

    surge generators which can stimulate

    lightning strokes, producing not only the

    1.2/50 waves, but also the steeper-front

    waves with which arresters are tested for

    equivalent front-of-wave as specified by

    standards.

    While lightning is usually considered

    synonymous with extremely high

    voltage, it is the current component in

    Rural transmission lines in areas with 30thunderstorms days per year can expect toexperience approximately one lightning strokeper mile per year.

    the lightning stroke which is the measure

    of its effect on a stricken object. The

    instant a voltage-sensitive device such as

    a metal oxide arrester goes into a high

    level of conduction, it becomes a

    current-carrying path of relatively low

    impedance for the duration of the surge

    discharge. Major components of the

    arrester's protective characteristics are

    determined by its performance in

    discharging the surge current.

    Extensive and elaborate scientific

    investigations have been made to

    measure and record lightning stroke

    currents. A tremendous range has been

    reported, varying from lows of 1000amperes to highs of more than 200,000

    amperes, again emphasizing the

    unpredictability of lightning. Probability

    patterns of lightning stroke currents have

    been ably discussed in several of the

    technical references of the industry; but

    for the arrester application engineer, the

    pertinent information can be consoli-

    dated into a statistical graph which

    compares stroke currents to transmission

    lines and to towers with discharge

    currents through distribution and station

    arresters. This analysis shows that

    currents through arresters are only about

    one-tenth the total stroke currents, but it

    is significant to note that less than five

    percent of distribution arrester currents

    exceed 10,000 amperes. Discharge

    currents through distribution arresters are

    noticeably greater than those recorded

    through station arresters because of their

    normal installation on unshielded

    overhead lines.

    The destructive power of lightning is

    well documented. The use of distribution

    and riser pole surge arresters provides ahigher power quality level to the utility

    customer.

    The surge arresters are not only used

    to protect equipment such as transform-

    ers and cables, they are also in use to

    protect the air around line insulators on

    unshielded lines reducing lightning

    caused interruptions. This results in

    better power quality and this is the

    primary goal.

  • 7/28/2019 EU1377-H

    8/229

    Insulation flashover

    and traveling waveon a power line.Traveling wavevoltage is equal tothe current magni-tude multiplied bythe surge imped-ance of the line.

    Statistical datacompare towerstroke currentswith station anddistribution ar-rester currents.

  • 7/28/2019 EU1377-H

    9/2210

    Chapter Three

    How Does a DistributionClass Surge Arrester Work?One in a Series

    ANSI/IEEE StandardC62.11 describes therelevant laboratory testsfor distribution classsurge arresters.

    ANSI/IEEE Standard C62.11, developed

    by IEEE, with input from users, produc-

    ers, and those with general interest, is the

    major industry reference document

    pertaining to metal-oxide surge arresters.The major objectives accomplished by

    C62.11 are:

    1. The definition of terms unique to

    the arrester field

    2. Establishment of standard and

    nonstandard service conditions

    3. Requirement of uniformity in

    certain construction aspects, such

    as nameplate data and terminal

    sizes

    4. Description of electrical test by

    which conformance to standardscan be demonstrated

    5. Formulation of a group of design

    tests which can be duplicated by

    properly equipped electrical

    laboratories to serve as a basis for

    arrester ratings and classifications

    6. Assignment of minimum ratings in

    the design test categories where

    such ratings are appropriate and

    reasonable

    The scope of C62.11 IEEE/ANSI

    Standard is defined as applicable to surge

    protective devices, having the capability

    for repeated limiting of voltage surges on

    50/60 Hz power systems by discharging

    surge current and automatically resealing

    against system continuous voltage. This

    standard applies to station, intermediate,

    Insulation Withstand Test

    Requirement

    A surge arrester is known as a "self-

    protecting" device. During the discharge

    of a surge the arrester limits the voltageto a level below external flashover level.

    Therefore, an external flashover of a

    surge arrester during a discharge is

    prevented.

    To ensure that the external insulation

    Table 1Arrester Ratings in (kV) rms

    Duty-Cycle Voltage

    3

    6

    9

    10

    12

    15

    18

    21

    24

    27

    30

    36

    MCOV

    2.55

    5.1

    7.65

    8.4

    10.2

    12.7

    15.3

    17.0

    19.5

    22.0

    24.4

    29.0

    distribution and secondary classes of

    metal-oxide surge arresters. The portions

    of the standard that relate to metal-oxide

    distribution class surge arresters are

    included in this discussion.

    Service conditions as described in the

    standard relate to both physical and

    electrical aspects of the arrester. Condi-

    tions are described as standard where the

    ambient temperature does not exceed

    40C and the altitude is not above 6,000feet and the power system frequency is

    limited to 50/60 Hz. Conditions exceed-

    ing these limits and including unusual

    circumstances of contamination or

    clearances are termed nonstandard and

    require special consideration in the form

    of recommendations from the arrester

    manufacturer.

    The standard defines MCOV (Maxi-

    mum Continuous Operating Voltage)

    ratings of the arresters as well as duty-

    cycle voltage ratings. The standard alsodefines the relationship between the

    duty-cycle voltage rating of the arrester

    and the MCOV assigned to an arrester.

    Table 1 shows the standard duty-cycle

    voltage and MCOV voltage ratings of

    distribution arresters.

    The tests developed to evaluate

    relative performance of distribution class

    surge arresters are:

    (1) Housing withstand test

    (2) Power frequency sparkover test

    (3) Discharge current withstand test

    (4) Impulse sparkover voltage time

    characteristics

    (5) Discharge voltage test

    (6) Duty-cycle test

    (7) Radio influence and internal

    ionization voltage test

    (8) Disconnector test

    (9) Contamination test

    (10) Fault current withstand test

    In this issue we will examine in detail

    the housing withstand and the discharge

    current withstand tests.

  • 7/28/2019 EU1377-H

    10/2211

    of the surge arrester is commensurate

    with the remaining insulation on the

    system, IEEE/ANSI Standard C62.11

    defines housing insulation withstand test

    requirements.

    The test standard specifies require-

    ments for an impulse test and 60 Hz wet

    and dry tests. The 60 Hz wet and dry

    tests are especially important since the

    arrester spends its service life under 60

    Hz conditions.Under the test conditions outlined in

    the standard, the voltage withstand test

    of the arrester insulation demonstrates

    that the assembled insulating

    members of the arrester can withstand

    the values listed in Table 2.

    Discharge CurrentWithstand Tests

    The discharge current withstand tests

    are performed to demonstrate the

    arrester's ability to discharge various

    types of surges and remain physically

    intact, thermally stable and capable of

    performing its protective function. The

    discharge current withstand tests are

    critical to determining the durability of asurge arrester.

    The two tests which make-up the

    discharge current withstand capability

    portion of the test are the low-current

    long-duration test and the high-current

    short-duration test.

    The requirements for the discharge

    current withstand portion of the standard

    test series vary depending upon the

    durability designation of the surge

    arrester.

    There are two types of distribution

    class surge arresters. These are the

    normal duty and the heavy duty surge

    arresters.

    The high current short duration test

    requirements for these types are asfollows:

    The normal duty arrester must

    withstand two discharges of 65 kA

    with a 4-6/10-15 wave.

    The heavy duty distribution class

    surge arrester must withstand two

    discharges of 100 kA with a 4-6/10-

    15 wave.

    The test is performed on completearresters or on thermally prorated

    sections of the arrester without 60 Hz

    voltage applied.

    The two discharges are spaced such

    that the arrester section cools to ambient

    between discharges.

    Within five minutes of the second

    discharge the surge arrester must be

    energized at its maximum continuous

    operating voltage (or higher if required

    by the arrester design) and must demon-

    strate thermal stability.

    Thermal stability is demonstrated by a

    decrease in temperature, resistive current

    or watts loss. The 60 Hz voltage must be

    maintained on the arrester for at least 30

    minutes.

    Table 2Insulation Withstand Test Voltages

    rmsDuty-Cycle

    Voltage Ratingof Arrester

    (kV)

    3

    6

    9

    10

    1215

    18

    21

    24*

    25

    27

    30

    36*

    Impulse Test1.2/50 Full Wave

    (kV) Crest*(BIL)

    45

    60

    75

    75

    8595

    125

    125

    150

    150

    150

    60 Hz rmsTest Voltage

    (kV)

    1 min Dry Test

    15

    21

    27

    27

    3135

    42

    42

    70

    70

    70

    1 min Dry Test

    13

    20

    24

    24

    2730

    36

    36

    60

    60

    60

    * Insulation values are not covered in standards.

  • 7/28/2019 EU1377-H

    11/2212

    The low current long duration portion

    of the discharge current withstand tests

    are also performed on complete arrester

    The oscillogram below shows the 60 Hz voltage and current wave shape at

    the end of the thermal stability test.

    Test Results

    The following oscillogram shows the l00kA discharges. The downward

    deflecting trace represents the current wave form and the upward deflecting

    trace represents the prorated sample discharge voltage.

    or on thermally prorated sections of the

    surge arrester.

    The parameters for the normal duty

    distribution class surge arrester are 20

    discharges of 75 amps with a duration of

    2,000 microseconds and for the heavy

    duty arrester 250 amps with a duration of

    2,000 microseconds.

    As with the high current short duration

    test after the conclusion of the low

    current long duration portion of the test

    series the surge arrester must demon-

    strate thermal stability.

    The discharge current withstand test

    series allows the arrester to demonstrate

    that it has the capability to withstand

    surge currents of both long and short

    duration and remain intact and func-

    tional.

    In addition to the thermal stability

    requirements there is also a requirement

    for stability of protective characteristics.

    To ensure the arrester protective ability

    has not been impaired, the protective

    levels of the arrester at 10 kA may notincrease by more than 10 percent at the

    conclusion of this test.

    Ohio Brass publishes booklets with

    design test reports for PDV-65 normal

    duty and PDV-100 heavy duty distribu-

    tion class arresters.

    These design test report booklets

    include copies of oscillograms which

    detail the results of the test described in

    this section.

    In the next issue we will continue to

    examine the series of design tests whichapply to distribution class surge arresters

    and will take a look at how these relate

    to the arresters ability to perform its

    function.

    End of Thermal Stability (100 kA)

    2.09 kV

    0.25 mA

    5 ms/majordivision

    5.82 kVp

    0.38 kAp(resistive)

    0.49 mAp(total)

    28.3 kV

    104 kA

    6/14

  • 7/28/2019 EU1377-H

    12/2213

    Chapter Four

    How Does a DistributionClass Arrester Work?One in a Series

    ANSI/IEEE StandardC62.11-1987 DescribesRelevant LaboratoryTests For DistributionClass Surge Arresters

    In this segment, we will continue ourlook at the design test requirements for

    distribution class surge arresters as well

    as how these test requirements relate to

    the ability of the arrester to perform its

    primary function. The primary function

    of the surge arrester is protection of

    utility equipment against overvoltages.

    In this issue, we will examine the:

    (a) The duty cycle test,

    (b) The discharge voltage test,

    (c) Impulse sparkover voltage timecharacteristic test.

    Duty Cycle Test

    The duty cycle test is performed to

    ensure the arrester will support its duty

    cycle rated voltage while discharging

    lightning surge currents.

    The duty cycle test voltage is a 60 Hz

    voltage in excess of the MCOV rating of

    the surge arrester.

    The duty cycle test is performed byenergizing the surge arrester at its duty

    cycle rated voltage and subjecting it to a

    series of 20 discharges.

    In the case of the normal duty distribu-

    tion arrester, the magnitude of these

    discharges is 5 kA with an 8/20 wave.

    The discharges are spaced one minute

    apart.

    Discharge voltage test set up with

    prorated sample in impulse generator.

    For the heavy duty arrester, the surges

    are 10 kA with an 8/20 wave followed by

    an oven preheat to 60C. The arrester

    then receives two additional discharges

    of 40 kA, while energized at MCOV.

    These additional discharges at the

    higher current level are to ensure the

    durability which users have come to

    expect from a heavy duty product.

    After completion of the duty cycleseries, the arrester is energized at the

    MCOV rating and is monitored to ensure

    thermal stability.

    After the completion of the duty cycle

    test, the protective characteristics of the

    surge arrester are measured to ensure the

    arrester will perform its function as

    designed.

    Discharge Voltage Test

    A surge arrester protects equipment

    from lightning surges. Therefore, the

    measurement of the voltage developed

    by the arrester when it discharges iscritical.

    This measurement is performed during

    the discharge voltage portion of the test

    sequence.

    The discharge voltage of a prorated

    arrester section using the appropriate

    diameter varistors is measured. A

    prorating factor is then applied to the

  • 7/28/2019 EU1377-H

    13/2214

    measured values to determine the

    discharge voltage of arresters made from

    this same type of varistor. This test helps

    to assure the manufacturers cataloged

    discharge voltages for the arrester will

    not be exceeded.

    The test is performed on the prorated

    section by measuring the 1.5, 3, 5, 10, 20

    and 40 kA discharge voltage using an 8/20 wave. In addition to the 8/20 wave

    discharge voltage, the fast front charac-

    teristic of the arrester is also measured.

    This is done by using a current wave that

    causes the arrester discharge voltage to

    crest in .5 ,sec. For the heavy duty

    distribution class arrester, this current

    wave has a 10 kA magnitude, and for a

    normal duty distribution class surge

    arrester, it has a magnitude of 5 kA.

    The discharge voltage (therefore, the

    protective level) of the arrester solely

    determines its protective characteristics

    if the arrester is a gapless design.

    If the surge arrester includes an

    internal gap, then additional tests must

    be performed. This testing includes

    determining if the protective level is

    defined by the gap sparkover or the

    varistor discharge voltage.

    Impulse Sparkover Test

    The impulse sparkover test is per-

    formed to ensure the gapped distribution

    class arrester's protective level is

    adequately defined for the end user.

    The voltage impressed on the pro-

    tected equipment is the higher of

    the metal-oxide varistor element dis-

    charge voltage or the gap sparkover.

    The impulse sparkover test is per-

    formed by taking a prorated sample of

    arrester elements including the metal-

    oxide varistors and the gap. The test is

    conducted using various voltage wave

    shapes and the sparkover of the gap

    element is measured at these wave

    shapes.

    The protective level which then must

    be used for insulation coordination is the

    higher of the metal-oxide varistor

    discharge voltage or the gap sparkover.

    The end user is able to compare the

    arrester protective characteristics with

    the insulation to determine if the arrester

    selected is suitable for the application.

    If the protective level of the arrester is

    too high to protect the equipment, then

    the user has the option of selecting a

    different class of arrester. This includes

    Technician monitors discharge voltage test, analyzing oscilloscope results.

    the option of using a riser-pole type

    arrester, intermediate or station class

    arrester.

    In the next installment, we will

    complete our examination of the design

    tests which are appropriate for distribu-

    tion class surge arresters.

  • 7/28/2019 EU1377-H

    14/2215

    Chapter Five

    How Does a DistributionClass Arrester Work?One in a Series

    ANSI/IEEE StandardC62.11-1987 DescribesRelevant LaboratoryTests For DistributionClass Surge Arresters

    In this installment, we will completeour look at design testing of distribution

    class surge arresters.

    The tests that will be covered are:

    1. Radio influence and internal

    ionization voltage test

    2. Disconnector tests

    3. Contamination test

    4. Fault current withstand test.

    RadioInfluence andInternallonizationVoltage TestThe surge arrester

    is continuously

    energized with a

    60 Hz voltage. If asolid electrical

    contact is not

    maintained

    throughout the surge arrester, it will have

    internal ionization which may result in

    degradation of the internal elements.

    Also, this internal ionization can result in

    radio and television interference. Loose

    external hardware connections can also

    result in radio influence voltage (RIV).

    ANSI C62.11 requires testing of the

    arrester design with a circuit in accor-

    dance with NEMA Standard LA- I . The

    arrester must have an RIV/IIV level of

    250 microvolts or less. This voltage is

    measured at 1000k Hz with the arrester

    energized at 1.05 x MCOV.

    All Ohio Brass PDV surge arresters

    are factory tested at 1.176 x MCOV. The

    arrester must exhibit an RIV/IIV of 10

    microvolts or less.

    Disconnector TestsToday's polymer-housed MOV surge

    arresters have a very low failure rate.

    They are still subject to system-gener-

    ated failures. The majority of arrester

    failures occur with the arrester becoming

    a short circuit to ground. If a shorted

    arrester remains connected to the line, it

    is not possible to reenergize the line.

    The disconnector serves to disconnect

    a failed arrester from the line. This

    serves two purposes. It allows the line to

    be put back in service and allows the

    failed arrester to be identified for future

    replacement.

    Figure 1

    Cross-section of a ground lead disconnector

  • 7/28/2019 EU1377-H

    15/2216

    The disconnector must not operate

    under any normal service condition. All

    design tests must be performed with the

    disconnector installed on the sample.

    The disconnector operation character-

    istic must also be verified. This is done

    by subjecting samples to rms currents of

    20 through 800 amps. The time for the

    disconnector to operate is plotted as a

    function of current.

    The detonation time-current curve for

    the Ohio Brass PDV arrester is included

    in this article.

    Contamination TestsGapless MOV arresters are resistant tocontamination failures. ANSI/IEEE

    Standard C62.11 requires an external

    contamination test be performed on the

    arrester to verify contamination resis-

    tance.

    The test program consists of three

    separate tests. The first test is a voltage

    excursion test with a total of 32 test

    cycles at voltages from MCOV to duty

    cycle voltage.

    The second test is a five hour contami-

    nation test. This test is performed by 20

    separate applications of contaminant

    solution. Between contaminant applica-

    tions, the arrester is energized at MCOV.

    At the conclusion of the test, thermal

    stability is verified.

    The final contamination test is the

    partial wetting test. This is performed by

    contaminating the bottom units of amultiple unit arrester. Thermal stability is

    verified at the end of the test series.

    Ohio Brass PDV arresters comply

    with all Contamination Test Require-

    ments.

    Fault Current Withstand TestSince surge arresters fail as line-to-

    ground short circuits, they will conduct

    system fault current after failure.

    The fault current withstand test is

    performed to verify the surge arrester

    will not fail in a manner that will cause

    large internal parts to be violently

    expelled.

    The test sample is preshorted by one

    of the two methods prescribed bystandards. The shorted arrester is then

    energized on a circuit with a given

    available fault current. (The standard

    does not specify currents and durations.)

    Additional test samples are tested at

    higher currents until the maximum value

    claimed by the design is verified. The

    values achieved by Ohio Brass PDV

    arresters are summarized in the table

    below:

    This concludes our discussion of

    design tests required by ANSI/IEEEStandard C62.11-1987.

    In the next issue, we will look at the

    various factory tests used to verify the

    quality of metal oxide varistors and

    assembled polymer arresters.

    Table I

    Fault Allowable Duration

    Current (cycles)

    PDV-65 PDV-100

    500A 120 120

    2500A 60 60

    5000A 30 30

    10,000A 10 10

    20,000A N/A 10

    Figure 2

    Curve of Detonation

  • 7/28/2019 EU1377-H

    16/2217

    Chapter Six

    How Does a DistributionClass Arrester Work?

    In the last several issues we have

    looked at design tests required on

    distribution arresters. Design tests

    provide a measure of the arrester's

    capability, but they cannot verify thequality of the finished arrester as

    manufactured.

    To ensure the quality of the arrester, a

    series of factory tests are performed on

    the metal oxide varistors and the arrester

    itself. These tests are in excess of any

    required by today's industry standards.

    The metal oxide varistor blocks used

    in all Ohio Brass PDV arresters are made

    in a dedicated plant in Wadsworth, Ohio.

    The varistors are used in arresters that

    are subject to direct lightning strokes. It

    is important to verify they will withstand

    the type of duty they will see in the field.

    Each varistor receives an 8120 current

    surge that ~subjects the varistor to its

    rated energy.

    ANSI Standards do not require this

    type of testing. However, the Ohio Brass

    100% energy test recognizes the unique

    environment in which the PDV arrester

    operates.

    One of the most important characteris-

    tics of a distribution arrester is the

    discharge voltage. To assemble anarrester with the proper total discharge

    voltage, the discharge voltage of each

    varistor must be measured.

    Every PDV-100 (heavy duty arrester)

    varistor has the 10 kA discharge voltage

    measured. The PDV-65 (normal duty

    arrester) varistor has a 5 kA discharge

    measured. The discharge voltage of each

    block is stamped on the metallized face.

    RIV and starting voltage tests

    performed on all PDV arresters.

    An blocks receive an 8/20 classifying current shot.

    The batch and m data is printed on each block.

    Life tests performed at elevated temperatures

    on sample blocks from each batch.

    In addition to the above tests which

    are performed on every varistor block, a

    number of tests are performed on a

    sample of blocks from each batch. These

    are briefly described below:

    1. Square Wave EnergyA sample of

    varistors are tested using a switching

    surge type waves of successively higher

    current. These blocks are taken to thepoint of failure. This test is used to verify

    the energy rating of the varistors.

    2. High Current TestPDV-100

    varistors are tested at 100 kA and PDV-

    65 varistors at 65 kA. This testing

    verifies the high current strength of the

    varistors.

    3. AC TestThe watts loss and

    capacitive currents of a sample are

    measured. These are measured to ensure

    the batch is within the design limits for

    the arrester.

    4. Accelerated Aging TestA sampleof each batch is energized at MCOV at 1

    30C for 250 hours. This test is equiva-

    lent to energizing the arrester in service

    for over 100 years at 40C, per IEEE/

    ANSI C62.11-1987.

    After all testing is completed on the

    blocks, they are shipped to Aiken, South

    Carolina, for assembly into arresters.

    All finished arresters receive two

    electrical tests. Each arrester is tested for

    RIV at a voltage equal to 1.176 x

    MCOV. The arrester must test at ten

    microvolts or less.

    A starting voltage test is performed.

    This is a measure of the voltage at which

    the arrester begins to conduct. This test is

    a final check on the assembly. It assuresthe arrester has been energized at least at

    MCOV before it is shipped.

    For more information on these tests,

    please request OB publication EU1150-

    HR1 for PDV-100 and EU1281-H for

    PDV-65 arresters from your Ohio Brass

    customer service representative.

    In the next issue, we will look at lead

    length effects.

  • 7/28/2019 EU1377-H

    17/2218

    Chapter Seven

    How Does a DistributionArrester Work?

    The selection of the best arrester for a

    given application can be negated by poor

    installation practices. The length and

    configuration of the line and ground

    leads is critical in determining theamount of equipment protection avail-

    able. This chapter will examine the

    effects of voltage drop in the leads on

    protective margins.

    Surge current flowing through the

    leads causes an inductive voltage drop.

    The voltage in the lead is calculated by

    the formula:

    V=LYou really do not have to do calculus

    to calculate this voltage.For a straight lead wire, the inductance

    is .4H/foot. If the lead wire is coiled,

    the inductance can be much higher. This

    can really hurt the protective margins.

    There is always a voltage drop in the

    lead wires. This voltage does not always

    add to the arrester discharge voltage. For

    lead wire voltage to count in protection,

    it must carry surge current and beelectrically in parallel with the equip-

    ment the arrester is protecting. Ohio

    Brass publication EU1202-H covers

    various connection methods in much

    greater detail. Request a copy of it from

    your OB representative.

    We will look at the protective margins

    achieved by an 8.4kV MCOV PDV-100

    arrester protecting a 95kV BIL trans-

    former. Figure 1 shows the insulation

    coordination curve for this application.

    The insulation coordination curve gives a

    graphical method of showing the

    relationship between the transformer

    insulation strength and the arrester

    protective level. Both of these are a

    function of the time it takes for the

    voltage to crest.

    The transformer can withstand a higher

    voltage for waves that have a voltage

    that crests in a short time. You can alsosee that the arrester allows a higher

    voltage to be developed for fast rising

    waves.

    The protection level is the sum of the

    arrester discharge voltage and the

    voltage drop in the lead wire.

    We need to determine the protective

    level of the arrester/lead wire combina-

    tion. The arrester discharge voltage

    comes from the catalog. In this example,

    the coordination current will be 10kA.

    The 10kA-8/20 discharge voltage of the

    arrester is 32kV. Now add the voltage

    drop from the lead wire. The voltage is:

    .4x10-6 H/ft x =500V/ft

    didt

    10x103A8x10-6 Sec

  • 7/28/2019 EU1377-H

    18/2219

    The total protective level at the 8/20

    current level (transformer BIL) is:

    32+(.5kV/ft) (6ft)=35kV

    The margin is:

    95kV -1 x 100 = 171%35kV

    Next we need to consider the fast front

    characteristics. The arrester 10kA .5sec

    IR is 36.5kV. For MOV arresters the

    current crests in about 70% of the time tovoltage crest. Therefore the current crest

    is .35sec. This value is coordinated

    with the transformer chopped wave

    strength. The chopped wave strength is

    approximately 15% higher than the

    transformer BIL.

    The voltage drop in the lead is:

    .4x10-6 H/ft x 10x103A =11.4kV/ft.35x10-6Sec

    The total protective level is:

    36.5kV + 11.4kV/ft) (6ft) = 104.9

    (arrester) (lead wire) (total)The voltage drop in the lead is

    significantly higher than for the 8/20

    wave. This is a result of the much faster

    time for the current to crest.

    The protective margin (Figure 2) is:

    110.00kV -1 x 100 = 4.9%104.9kV

    This is a small margin.

    It is easy to see how important it is to

    keep the leads as short and straight as

    possible!

    Utilities will often look at insulation

    coordination when selecting arresters

    and use the full insulation strength of the

    transformer. As the transformer ages

    however, the BIL and other insulation

    levels will likely reduce. A reduction of

    at least 20% is considered typical.

    The protective levels of MOV

    arresters do not increase with duty. This

    also was not true for silicon carbide

    designs.

    We will look at the protection if the

    insulation levels have reduced by 20%.

    Figure 2 shows the resulting protective

    margins. At the BIL the margin is:

    76kV -1 x 100 = 117%35kV

    and the fast wave margin is:

    88kV -1 x 100 = 16.1%104.9kV

    Therefore, for the fast front the

    insulation strength is well below the

    protective level. The leads must be

    shortened or eliminated.

    The effect of the line and ground leads

    can be reduced if the connections are

    made properly. The lead wire from the

    phase conductor should go to the arrester

    before going to the high voltage bushing

    of the transformer. The voltage in the

    lead coming to the arrester does not

    contribute to the voltage stress on the

    insulation. The ground connection

    should be made to the tank of the

    transformer to minimize the lead effect.

    This article shows dramatically how

    much the improper lead wire connection

    can affect performance of a complete

    system.

    In the next issue we will look at theeffects of the continuous power loss of

    the surge arrester.

    [ ]

    [ ] [ ]

    [ ]

  • 7/28/2019 EU1377-H

    19/2220

    Chapter Eight

    How Does a DistributionArrester Work?Watts Loss and You

    In this series we have studied how a

    distribution arrester works. We have

    reviewed the important tests and product

    characteristics.

    Another important trait of all MOV

    surge arresters is the continuous power

    loss resulting from leakage currents. All

    MOV arresters, even todays gapped

    units, conduct a leakage current. In fact

    gapped units can be expected to conduct

    higher leakage currents and generate

    higher power losses than gapless

    arresters.

    The power loss in MOV arresters

    results from continuous leakage current

    at MCOV. This power loss has several

    implications for utility engineers. Powerlosses affect:

    1. The operating and total ownership

    cost of the arrester.

    2. The thermal recovery of the arrester

    after experiencing high energy duty.

    The power loss of the arrester can be

    affected by the processing methods and

    the ingredients in the MOV and by the

    amount of the MOV material used. The

    MOV block can be developed to have a

    low power loss which will affect the

    shape of the MOV volt-amp curve. Also

    the amount of MOV used in the arrestercan be reduced to improve the discharge

    voltage but this may result in higher

    power losses.

    Operating and TotalOwnership Costs

    The power loss of the MOV surge

    arrester results in a cost to the utility. The

    utility industry has evaluated the power

    loss of distribution transformers for

    many years. The same type of economic

    analysis can be applied to arresters.

    There are two types of losses that areevaluated for transformers. These are the

    no-load (or core) losses and the

    load losses. The no-load losses are

    always present and are independent of

    the system loading conditions. The load

    losses vary as the system load fluctuates.

    The continuous surge arrester losses are

    comparable to the no-load loss of the

    transformer.

    A utility that evaluates losses of

    transformers will determine two cost

    factors associated with these types of

    losses. These include such factors as fuel

    costs, time value of money, operating

    life, etcetera. The usual method of

    determining these factors is based on the

    EEI method. These factors are expressed

    in $/Watt of power loss. The no-load

    factor is commonly known as the A

    factor and the load losses are the B

    factor.

    The distribution arrester engineer will

    not need to calculate these factors if the

    utility already evaluates transformer

    losses since these factors are already

    available from the transformer standards

    group. The A factor is applied to the

    losses of the surge arrester.

    To evaluate the long term operating

    costs of the surge arrester, the engineerwill need to determine the average watts

    loss of the designs under consideration.

    This information should be supplied

    readily by the manufacturer of the

    arrester.

    For reference, the average watts loss

    of the Ohio Brass PDV-100 arrester is

    .018 watts/kV-MCOV. Therefore, for an

    8.4kV MCOV PDV-100 heavy duty

    arrester the average loss is .151 watts

    [(.018 watts/kV-MCOV)*(8.4kV-

    MCOV)].

    The manufacturer of the arrestershould be contacted for information on

    the average power losses. We have

    performed tests on some other designs

    and the results of the random samples

    tested are summarized in Table 1.

    TABLE 1

    Arrester Type Average

    (Watts/kV-MCOV)

    Ohio Brass PDV-100 .018

    Type Y (gapless) .058Type X (gapless) .061

    Type Z (gapped) .200

    This table shows that not all power

    losses are the same. It also shows the

    extremely high power losses of the

    gapped type arrester. This high loss may

    come as a surprise to some so an

    explanation may be in order.

    The high losses of the gapped arrester

    result from replacing some of the high

    resistance MOV elements in the gapless

    arrester with lower impedance silicon

    carbide grading elements in parallel with

    the gap assembly. The silicon carbide

    grading circuit in this hybrid arrester

    allows for a higher continuous current

    flow than is found in similarly rated

    gapless designs.

    The power losses combined with the

    A factor allow the utility to calculate

    the effect of the losses on the ownership

    cost of the arrester.

    Power loss A factors at most

    utilities are below $10.00/Watt. If we use

    a conservative value of $2.50/Watt

    applied to an 8.4kV MCOV arrester the

    above losses translate to the operating

    costs over the life of the arrester shown

    in Table 2.

    TABLE 2

    Arrester Type Operating Cost

    ($)

    Ohio Brass PDV-100 .38

    Type Y (gapless) 1.22

    Type X (gapless) 1.28

    Type Z (gapped) 4.20

    Depending on the first cost of the

    surge arrester, these additional operating

    costs can have a significant impact onthe total ownership cost of the arrester.

    Thermal Recovery andLong Term Aging

    When a surge arrester experiences

    high energy duty such as a high current

    lightning stroke, the MOV blocks absorb

    energy. The temperature of the blocks

    can rise significantly as a result of the

    discharge duty.

    MOV blocks exhibit a negative

    temperature coefficient in the operating

    voltage region of the volt-amp curve.Figure 1 is a typical volt-amp curve for a

    gapless MOV arrester. The negative

    temperature coefficient is apparent from

    the fact that at higher block temperatures

    the MOV elements conduct more

    current. Since the blocks conduct more

    current they become hotter and then will

    conduct even more current. If this

    condition continues without the excess

    heat being removed the arrester will

    experience thermal runaway.

  • 7/28/2019 EU1377-H

    20/2221

    A well designed surge arrester will

    never experience thermal runaway for

    any reasonable set of circumstances.

    The excess heat being generated by

    the blocks is dissipated by conduction

    and convection through the housing andend hardware. Figure 2 is a typical curve

    showing the rate of power generation (of

    the MOV blocks) versus the rate of heat

    dissipation (of the housing). A polymer

    arrester with blocks in contact with the

    housing will provide better heat transfer

    than a design relying on convection.

    In service the arrester will reach

    equilibrium at a temperature slightly

    above ambient. When it discharges high

    energy duty the block temperature rises.

    As long as the temperature remains

    below the upper equilibrium point thearrester will slowly cool back to equilib-

    rium. The Ohio Brass PDV arresters are

    designed to remain thermally stable after

    being subjected to two rated energy

    discharges within one minute. The

    energy rating of the PDV-100 is 2.2 kJ/

    kV-MCOV and 1.4 kJ/kV-MCOV for thePDV-65.

    The curve in Figure 2 is based on the

    assumption that the arrester has the

    highest watts loss blocks that would ever

    be used in that design. The lower the

    initial watts loss, the more likely the

    arrester will be thermally stable. Designs

    that have higher losses can still be

    thermally stable, but depending on the

    magnitude of the losses special heat

    transfer methods may be required.

    Also as the MOV blocks age, there is

    long term effect. This is why the designtests call for an accelerated aging test.

    (However, the standard does not require

    one for production. Ohio Brass does such

    a test on each batch of MOV blocks.)

    If the watts loss of the arrester

    increases with time, the arrester watts

    generated curve can shift up as shown in

    Figure 3. This will result in a reduced

    upper thermal equilibrium temperature.

    (The Ohio Brass surge arrester actually

    has decreasing watts over time which

    helps to make it more stable.) Thearrester design test requires that any

    thermal recovery tests after high energy

    duty simulate any increase in watts loss

    resulting from aging effects.

    An increasing watt loss will also affect

    the economic analysis of the cost of the

    losses. The economic calculations are

    based on the assumption that the losses

    are constant. In the specific case of the

    Ohio Brass arresters this is very conser-

    vative since the losses of these arresters

    decrease. This means that the loss costs

    will be even lower than calculated.

    Summary

    The power losses of MOV arresters

    have economic and performance effects

    that need to be considered by the utility

    engineer. To do an effective job of

    evaluating the losses, data must be

    gathered on the average watts loss and

    the long term aging performance of the

    arrester. This information should be

    available from the supplier of the surge

    arrester.

  • 7/28/2019 EU1377-H

    21/2222

    Chapter Nine

    How Does a DistributionArrester Work?

    Hardware Attachments

    For PDV Surge Arresters

    To optimize surge protection, it isimportant to properly position the surge

    arrester near the protected equipment.

    System reliability may also be compro-

    mised by animal contact to the energized

    terminal of the arrester, so proper

    selection of hardware options is critical.

    This article explains the mounting and

    hardware accessories that are available

    for Ohio Brass arresters to obtain

    maximum benefit.

    The table below describes the standard

    hardware items which are available on

    Ohio Brass Type PDV arresters. The

    hardware described in this table is

    suitable for the PDV-100 (heavy duty)

    and PDV-65 (normal duty) surge

    arresters.

    Ohio Brass PDV arresters are speci-

    fied by the six digit catalog numberwhich describes the MCOV (maximum

    continuous operating voltage) rating of

    the arrester. For example the PDV-65

    arrester 8.4 kV MCOV is Catalog

    Number 217259. However, this six digit

    catalog number is not sufficient to

    completely specify the surge arrester. In

    addition to the basic arrester the optional

    hardware attachments which are required

    must also be specified. The optional

    hardware attachments are specified by

    the use of a four digit suffix code

    beginning with the Number 7.

    The three digits following 7 specify

    the top end hardware, the mounting

    hardware, and the bottom end hardware.

    For example, if you need an 8.4 kV

    MCOV PDV 65 arrester with a nut, wire

    clamp and protective cover on the topend, the insulating base bracket and

    NEMA crossarm bracket as the mounting

    attachment and the isolator, washer,

    terminal nut and nut as the lower end

    hardware, then this arrester would be

    specified by code 217259-7324.

    In response to market requests, Ohio

    Brass is now offering a flipper fuse

    holder accessory kit. This is available

    by specifying 76XX code series. A

    drawing of the components is shown in

    Figure 1.

    This concludes our series on how

    MOV distribution arresters work. The

    entire series is being reprinted and bound

    into Ohio Brass publication number

    EU1377-H. If you would like a copy,

    please contact your Ohio Brass represen-

    tative.

    *Must be ordered in conjunction with codes 7060 and 7070.

    **Transformer Bracket 11 " for 8.4 kV MCOV and below and 7-1/2" for 10.2 kV MCOV and above.

  • 7/28/2019 EU1377-H

    22/22

    EU1377 H

    Web: http://www.hubbellpowersystems.comE-mail: [email protected]

    UNITED STATES

    HUBBELL POWER SYSTEMS, INC.

    210 N. Allen

    Centralia, Mo 65240-1395

    Phone: 573-682-5521Fax: 573-682-8714

    e-mail: [email protected]

    CANADA

    HUBBELL CANADA, INC.

    870 Brock Road South

    Pickering, Ontario L1W 1Z8

    Phone: 905-839-1138Fax: 905-831-6353

    e-mail: [email protected]

    MEXICO

    HUBBELL DE MEXICO, S.A. DE. CV

    Av. Coyoacan No. 1051

    Col. Del Valle

    03100 Mexico, D.F.Phone: 52-55-9151-9999

    Fax: 52-55-9151-9988

    e-mail: [email protected]

    ASIA

    HUBBELL S.E. ASIA PTE. LTD.

    23 Tagore Lane #03-16

    Tagore 23 Warehouse

    Singapore 787601Phone: 65-6454-4772

    Fax: 65-6454-4775

    e-mail: [email protected]

    NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.