esp rectifier transformer
DESCRIPTION
ESP Rectifier Transformer - Basic working principleTRANSCRIPT
ESP Rectifier transformer
M.G.Morshad / ACM Transformer Mtce / TPS II
Principle of operation
• Electrodes at high voltage create a corona effect (ionized atmosphere) surrounding them.
• This charges the passing particles. Once charged, particles are subject to a transverse electrostatic force that pulls them toward the collecting plates.
• Plates are periodically “rapped” (vibrated) to make the collected particles fall down into a receiver hopper.
Back corona
-
+ + + + + + + + + + + + + + + + + + + + +
+ + + + + + + + + + + + + + + + + + + + + +
Positively charged
collecting plates
- - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - -
High resistive dust particles
Negatively charged dust
particles
Negatively charged emitting electrodes
Spark between layers of dust particles
In case of high resistive dust ( dry dust) , dust layer creates an insulation between the positively charged collecting plate and negatively charged dust particles.
In such condition, spark / arc within the layer of dust particle is formed with the decrease of KV (DC). This phenomena is known as BACK CORONA.
As a result of spark / arc formation , field current (mA ) gets increased with substantial decrease in field voltage KV (DC).
To avoid back corona, field voltage KV(DC) has to be reduced sufficiently, but such measures finally reduces the collection efficiency of the field
Field short
In case of low resistive dust ( wet dust), dust layer gets positively charged. In such condition whenever the gap between positively charged dust particles & negatively charged electrodes gets reduced due to accumulation of dust layer , spark ( that extinguishes with the reduction of applied voltage ) or arc (that does not extinguish with the reduction of applied voltage ) gets emitted from emitting electrode to the collecting plates causing shorting of fields.
As a result of field shorting , field voltage KV (DC) gets collapsed with drawing of high field current (mA ) between emitting electrode and the collecting plates. This may cause the failure of HV winding if transformer is not switched off immediately after field short.
-
+ + + + + + + + + + + + + + + + + + + + +
+ + + + + + + + + + + + + + + + + + + + + +
+ + + + + + + + + + + + + + + + + + + +
Negatively charged emitting electrodes
Spark between layers of dust particles
+ + + + + + + + + + + + + + + + + + ++ + + + + + + + + + + + + + + + + + +
+
+ + + + + + + + + + + + + + + + + ++ + + + + + + + + + + + + + + + + + ++ + + + + + + + + + + + + + + + + + +
Voltage - current characteristics
KV ( DC)
mA ( DC)
Back Corona Zone
Operating Zone
Field Short
0
Operating Zone : With the increase of field voltage [KV (DC)], field current (mA) increases linearly and no spark is emitted.
Back Corona zone : Spark starts emitting causing decrease in field voltage KV(DC) with high increase in field current (mA)
Field short : Spark persist continuously causing field voltage KV(DC) to become zero with maximum flow of field current (mA)
Parameters affect the performance of ESP1. Gas Temperature : Normally ESP is designed to operate in the temperature range 180- 200 Deg C. At higher temperature, thequality of insulation deteriorate and flash over voltage limit decreases. In such condition operating voltagehas to be brought down to avoid back corona that results in lower dust collecting efficiency . At
temperaturebelow the acid dew point, deposition of acid in the structure leads to faster corrosion .
2. Moisture content : Moisture content has a large influence on the performance of ESP. Moisture increases the ionization
tendency and decreases the resistivity of the dust particles. As an effect of these factors dust collection efficiency increases with reduced back corona tendency .
3.Dust particle size: The collecting efficiency increases with increase in particle size since the larger particles receive charge
more quickly and attains migration velocity. (Migration velocity is proportional to diameter when d>1pm and is independent when d<1μm). Hence , collection efficiency decreases with the increase of fineness of the dust particles’.
4. Dust resistively: Dust resistivity increases with the increase of dryness of dust and quality of fuel. At higher dust resistivity ,
internal spark over between two layers of dust takes place as a result of potential difference created by the high resistance of dust. This phenomena is called Back Corona. Once the back corona starts , field intensity ( KV DC) start reducing with increase of field current . This reduces the collecting efficiency of the ESP.
5. Rapping frequency : Whenever the electrode surface is subjected to rapping shock, re-entertainment of particles takes place in
the main flow path and carried away by the gas causing increase in emission level . To reduce the re-entertainment to a minimum level, it must be allowed to form a layer of significant thickness of dust so that when it is dislodged by rapping, the layer breaks into agglomerate masses, sufficiently large to fall into the hopper before, being carried out by the moving gas stream into the outlet duct. Secondly rapping frequency is to be set to optimum level for each field in accordance with the concentration and type of dust entering the field to minimize penetration.
Components of rectifier transformers
Microprocessor based Voltage controller
Control panel – 1. Analog Meters for quick visual indication of operating level.2. Electronic Controller for Controlling power (KV and mA)
delivered to the TR.3. SCR Module with Heat Sinks under control of the Electronic
Controller for Phase Control of the AC Feed to the TR.4. Circuit Breaker, Contactor and Misc. control and interlock
relays Phase control Thyristor,
Transformer unit – 1.Series reactor, 2.Transformer coil, 3.Rectifier bridge, 4.Resistor assembly 5.HF choke.6.Insulating oil7.LV & HV Bushing8.Control feed back terminals
SCR controller
The single phase input voltage of 480 V is applied across the SCR assembly which is made up of two SCRs connected in a reverse polarity parallel configuration .
The primary voltage of transformer is controlled by changing the conduction angle of the SCR with the help of feed back signal ( mA & KV) taken from DC side of the secondary
The SCRs are protected from dv/dt damage by a resistor capacitor snubber network consist of metal oxide varistor and fuse to protect against over current conditions.
Transformer Unit
Rectifier Bridge
+ -DC Volt / Current
AC Input = 415 V,200A
AC Out put = 53570 V, 1.40 A
Voltage Ratio
1:143.42
Output DC Voltage = 53570 x (1.414/1.08) = 70KV Output DC current = 1.40 / 1.414= 0.990 A
Output KWr = V x I = 70 x0.990 = 69.3KW
Input KVA = 373.5 x 200 = 75KVAInput KW = 75KVA x1 = 75KW
Single phase transformer with higher voltage ratio is used to create high voltage at secondary terminal
Transformer is operated with 2 phase supply for achieving natural commutation of rectifier bridge.
Transformer KVA is controlled by controlling the voltage & current with the help of SCR controller
Heat generation during operation is equal to (Input 75 KW – Output 69.3 KW ) 5.7 KW is carried away by the silicon oil to maintain the temperature.
Gas generation due to high temperature is detected by BUCHOLTZ relayVarious capacity of transformer
CLR
Current Limiting Reactor
Rectifier unit
LV
HV
Series Reactor 373.5 V
Supply
Impedance (Z) = V/I (AC Resistance) Z = V/I = L x 2πf Ohms % Z = [(L x 2πf x I) / V ] x 100 Ohms L = (V x %Z) x (I x 2πf ) Henry
CLR reactance (L) = 1.5 mHCLR resistance ( R ) =9 mΏ Impedance of CLR =24.64%TR impedance = 10%System impedance = 34 .64%
A system impedance of 50% limits the maximum AC current to twice the rated current. At 33% the limit is three times the rated current
1. The primary purpose of the CLR is to limit the surge current that is produced due to generation of spark & arc in the ESP field . The typical CLR value is selected in such a way that it can limit the current surge, within a 8.3 msec (Line ½ Cycle) to approximately 2 – 4 limitation is required because the SCR controller cannot respond (turn off) until the end of the line cycle.
2. The secondary purposed of the CLR is provide a means for decreasing mA and KV ripple on the DC Power delivered to the ESP. The reduced Ripple results in increased average KV levels, and increased ESP performance (efficiency)
415 V Supply
Rectifier Diode assembly
•
The diode assembly is used to convert the high voltage AC output of the transformer to a DC signal.
The diode assembly is made up of a series string of many diode junctions. This series string of diodes should be capable of blocking at least twice the peak output voltage of the T/R. i.e. (2 x 70 KVp = 150 KV)
For obtaining high blocking voltage special measures are employed to assure proper voltage sharing.
Improper voltage sharing is caused by variation of the reverse leakage of individual diode junctions. This variation results in an uneven distribution of the PIV among the diodes. In such case the diodes will fail in a “domino” fashion
HF Choke
High Frequency Choke / Air Core Reactor (ACR) is an electric coil that is connected between the rectifier bridge and HV bushing for protecting the TR Rectifier Bridge from high frequency, high voltage spikes and disturbances that occur within the sparking ESP.
ACRs used in modern T/Rs are rated from 20 to 50 (mH) and must be capable of withstanding up to 2 times peak rated voltage.
As the ESP sparks and arcs, the full ESP voltage will be impressed across the ACR.
ACR design must provide sufficient layer insulation and clearance to accommodate such voltage.
Typical failure mode for ACRs is a spark over of the layer insulation. Since the ACR is physically much smaller than the transformer secondary coil, it is subject to extreme voltage stress.
In the event of any contamination of the dielectric fluid, the ACR is often the first component to fail.
Resistance board assembly - feed back signal for control & monitoring
1. mA feed backThis signal is used for Control and monitoring. The mA Feed back is implemented by a power resistance of approximately 10 Ohms. It is used to provide a 10 Volt DC signal that will correspond to a 1000 ma TR output. Other resistor values may be used for other ratios. The ma feed back is electrically connected between the Positive (+) leg of the HV Bridge and Earth Ground.The Resistor must be of High Reliability Rating and also backed up by a protective HV Device.If this component fails the rated High Voltage is imposed upon this feed back wire.
2. KV Feed back signal The KV signal is implemented through use of a high voltage divider with a typical ratio 8,000 to 1. The ratio uses an 80 Meg Ohm resistor on the high end and a 10K Ohm resistor on the low end, thus producing a feedback of 8 KV per volt. 120 Meg dividers are sometimes used for higher voltage TR’s. Typical KV Feed Back systems are not frequency compensated, yet provide a reasonable representation of the ESP signal.One of the most important feedback signals is secondary voltage or kV. Although this is one of the most commonly inaccurate signals found in many installations, inaccuracies in KV feed back can be calculated by the following formula : KV ( DC ) = (Primary current x Primary Voltage X 700) / Secondary mA Like the ma Feed Back.. This signal must be protected since the full output voltage of the TR can be imposed on this wire
Insulating oil The Dielectric Fluid is used to provide cooling for the TR internal components as well as to provide high voltage insulation.
Mineral Oil, Silicone Oil and R-Temp Oil are fluids used.
PCB fluid - Askeral (Prior to 1970) ,Silicon Fluid , R-Temp type fluids are having higher fire point and therefore they are used where fire is of greater concern.
Silicon fluid is more viscous than mineral oil at temperatures above 10 Deg c and therefore requires additional radiator or bigger tank for proper cooling.
Silicone fluid has a greater affinity for water absorption compared to Mineral oil (Water saturation point for Mineral oil is approx 70 ppm while silicone can be as high as 200 ppm) . Silicone fluid can maintain a higher dielectric properties at high water concentrations.
The solid insulation of silicon oil filled transformer gets contaminated with water easily since the Silicone fluid has a greater affinity for water absorption and about 90% of the water present in oil is absorbed by the insulation due to natural migration of moisture. Hence HOC is required frequently in silicon fluid for keeping the solid insulation dry.
Decomposition of Silicon fluid due to internal arcing generates gases and carbon particles. When Bucholtz relay is actuated by gases, carbon particles contaminated the oil as well as gets attracted to the transformer windings which finally causes the failure of the transformer due to insulation failure. Hence to remove the contamination from the oil , proper oil filtration or total oil replacement is required before installing the transformer after repair and rectification.
Characteristics of silicon oil
Principle of operation
Depending upon gas temperature, dust resistivity and gas velocity following parameters are set- 1.uni pulse mode/ Semi pulse mode , 2.peak mode ,3.charge ratio, 4.spark control rate ( S & T) 5.secondary DC current limit
mA
Time
Current limit
Max Current at which spark occur
20ms Blocking time
S
T
With switching on primary , SCR controller increase the conduction angle depending upon the DC feed back signal (mA & KV) till it reaches the set current.
During the current rise whenever the secondary encounters with sparks which is detected by low voltage and high current DC feed back signal , SCR controller immediately stops conduction.
SCR controller restarts conduction after 20 ms with slop less than 5%
This process goes on continuously to keep the field in energized condition with negative polarity without any spark.
Uni pulse / Semi pulse mode
In uni pulse mode of operation fields are in continuous charging state with all half cycle of sinusoidal input ( Charge ratio = 1). This results in imposing of high peak voltage and high average current on the field which causes higher power consumption, lower dust collecting efficiency due to frequent occurrence of Back Corona Effect in the field.
In semi pulse mode of operation fields are in intermittent charging state with only preset half cycle of sinusoidal input ( Charge ratio >1). This results in imposing of high peak voltage and lower average current on the field which causes Lower power consumption, Higher dust collecting efficiency due to complete avoiding of Back Corona Effect in the field.
V
I
V
I
SCR controller Rectifier Uni pulse
Semi pulse
Sinusoidal input
Charge Ratio
To avoid back corona , optimization of field voltage KV (DC) is needed and It is achieved by increasing the time gap between the consecutive voltage pulse which is denoted as charge ratio.For higher dust resistivity, higher charge ratio is required so that field voltage is imposed after a sufficient interval to avoid back corona To maintain the sufficient average field current for increasing collection efficiency , field current is to be set at 200% for charge ratio more than 1 Power consumption reduces with the increase of charge ratio For setting field current at 200% , HV coil is frequently exposed to high current that may lead to failure of coil.Since lignite ash is low resistive dust ( Wet dust), system can be set for charge ratio between 1 & 3 .
Uni pulse mode
Semi pulse mode
Charge Ratio 1
Charge Ratio 3
Charge Ratio 5
Semi pulse mode
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
spark control rate ( S & T control)
The spark rate is determined by the settings of S-control and T-control.
Suppose T-Control is set at 20% , the time required by the rectifier to reach the rated current after a spark, from zero current will be 2 minutes.
Suppose S-Control is set 5% of the rated current, the time from S-Control break point to next spark will then be 5% of the T-Control time (5% of 2 minutes), that is 6 seconds.
If we do not account for the thyristor block time (20mS) then 6 seconds is the statistical interval between sparks in the ESP.
S-Control & T-Control are affected neither by the absolute value of current nor of the voltage at which a spark occurs, the spark rate is constant.
5%
95%
S
T= 6 sec
Field current setting
Formula Field I Field II Field III Field IV Field V Field VI Secondary DC Current mA 100.00 200.00 500.00 500.00 700.00 700.00
Secondary AC Current I2 = (mA x 1.4141)/1000 0.14 0.28 0.71 0.71 0.99 0.99 Secondary DC Voltage KVp = (70 x mA)/1000 7.00 14.00 35.00 35.00 49.00 49.00
Secondary AC Voltage KV2 = (KVp x 1.08)/1.414 5.35 10.69 26.73 26.73 37.42 37.42 Out Put KW Kwo = (mAxKVp)/1000 0.70 2.80 17.50 17.50 34.30 34.30 Trfo voltage ratio R 143.42 143.42 143.42 143.42 143.42 143.42
Primary AC Voltage V1 = (KV2/R)*1000 37.28 74.55 186.38 186.38 260.93 260.93
Primary AC Current I1 = I2 x K 20.28 40.56 101.41 101.41 141.97 141.97 In Put KW Kwi = (V1 x I1)/100 0.76 3.02 18.90 18.90 37.04 37.04 Trfo Loss KW loss = (Kwi - KWo) 0.06 0.22 1.40 1.40 2.74 2.74
LV
HV
CLR
HFC
mA
KVp
+ Positive
- Negative
KV2
I2I1
V1415 V supply
Specification - Stage II transformers
Name Rectifier Transformer
Supply Voltage 415 V AC two phase
Make BHEL
Location Stage II ESP roof top
Capacity 75 KVA
Rated primary Voltage ( LV) 373.5 V
Rated primary current () 200.8 A
Rated secondary voltage (HV) 53570 V
Rated secondary current (HV) 1.4 A
Voltage ratio 143.42
Oil Capacity 400 Liters ( 2 Barrels)
Type of oil Silicon oil
Total weight including oil 1300 Kg
Location - stage II transformers
5A
1A
2A
3A
4A
6A
11A
7A
8 A
9 A
10A
12 A
5B
1B
2B
3B
4B
6B
11B
7B
8 B
9 B
10B
12 B
Clean gases to chimney
Dusty gases from RAPH
Transformer connection / Stage II
HF Choke
H.VResistance
a1
av
a3
LV
ACR
HV
AR
AS2
AS1A2
A1
Protection diode
DiodeStack
Terminal / Parts Purpose a3 - av AC series Reactor to restrict primary current incase of shorted secondary ( Resistance 9.32 m Ohms)av- a1 winding terminal ( Resistance 14.6 m Ohms)Internal Terminal HV winging terminal (Resistance 454 Ohms)a3 – a1 Two phase AC input terminal (Resistance 24.84 m Ohms)A1 Negative terminal to create negative potential in the fields A2 Positive terminal earthling point to create positive potential in the structure AS2 – AR DC feed back voltage measuring terminalHF Choke To reduce sparking rate at HV terminal ( Inductance 50mH, 6.74 Ohms)Diode Stack Full wave bridge rectifier for converting AC to DCH.V resistance Voltage divider Protection diode To protect the bridge from reverse biasing
Open circuit test – BHEL Transformer
Voltage Applied on LV terminals Using Variac (Volt)
Magnetizing current measured on LV terminals (Amps)
DC feed Back voltage measured between AS2&AR (V)
50 0.116 20.20100 0.176 41.00150 0.190 58.20200 0.280 77.20250 0.490 96.50300 2.460 116.00350 3.110 133.00374 4.240 140.50
Short circuit test – BHEL Transformer Voltage Applied on LV terminals Using Variac
(Volt)
Current measured on LV terminals
(Amps)
DC feed Back Current measured between
AS2 & AS1 (mA)DC Current measured on HV terminals (A)
20 36.00 0.220 0.101
40 67.00 0.400 0.183
60 98.00 0.580 0.230
80 131.00 0.770 0.320
100 171.00 1000.000 0.420
120 199.00 1140.000 0.500
130 206.00 1160.000 0.510
Acceptance test / Stage II Parameters Value
IR Value
Minimum 200 M Ohm
HV – E , ( 2.5 KV Megger),
HV – ( 2.5 KV Megger),
LV – E ( 0.5 KV Megger) LV Winding resistance
14- 15 m Ohms
AC Reactor resistance
9 – 9.5 m Ohms
Combined resistance
24 – 25 m Ohms
Magnetizing current test
Voltage
current As2 – AR
50 Volt 108 mA 19 V DC100 volt 170 mA 39 V DC150 volt 200 mA 59 V DC200 Volt 0.26 A 79 V DC250 Volt 0.46 A 99 V DC 300 Volt 1.25 A 118 V DC
350 Volt 2.81 A 136 V DC400 Volt 4.0 A 145 V DC
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
4.000
4.500
0.00 200.00 400.00 600.00Am
psVolts
Amps
Amps
Fault detection / Stage II
Parameters ValueTwo phase Input AC voltage 110 to 120 VoltPrimary current 0.2 to 0.3 AmpsSecondary Voltage 33 KVSecondary current Zero
OCC test at local – Keeping A1 open
Parameters ValueTwo phase Input AC voltage 110 to 120 VoltPrimary current 14 – 15 AmpsSecondary Voltage 33 KVSecondary current 100 mA
Load test at local – Keeping A1 close
Fault detection
Actuations of Buchholtz relay BOTTOM FLOAT
Actuations of Buchholtz relay
TOP FLOAT
Causes•Internal short circuit between turns •Short Circuit between phase & earth Phase to phase short circuitInsulation break down
CausesLow oil level Air accumulation Fault in core lamination Break down in core blot Insulation Local over heating in the winding Wrong connection
Specifications – Stage I transformers
Make MERLIN GERIN ( France)
Location ESP I,II,II
Population / Unit 24 Nos
Total Population 3 x 24 = 72 Nos
Capacity 75 KVA
% impedance 8%
Primary rated current 181 amps (AC)
Voltage Ratio 415 V / 54000V
Output voltage 75Kv(DC)
Output current 0.13 Amps (DC)
DC out put 59 KW
Primary fuse rating 250 amps / 500 Volt
Protection DGPT 2000 ( Gas emission, internal pressure &
Temperature)
Total weight of one transformer 900 Kg
Oil weight per transformer 290 Kg
Type of oil used HUILE OIL ( Askarel)
Location – stage I transformers
A5
A1
A2
A3
A4
A6
B5
B1
B2
B3
B4
B6
C5
C1
C2
C3
C4
C6
D5
D1
D2
D3
D4
D6
Dusty gases from RAPH
Clean gases to chimney
Transformer connection / Stage I
HF Choke
b
c
a
LV
ACR
HV
m
+
HV Bushing
DiodeStack
17 nos resistors,
each 4MΩ
182 KΩ, ¼ W
resistors
Spark detector
Terminal / Parts Purpose a - c AC series Reactor to restrict primary current incase of shorted secondary ( Resistance 11.2 m Ohms)c- b LV winding terminal ( Resistance 18.8 m Ohms)a-b Two phase AC input terminal (Resistance 29.5 m Ohms)+ Grounding point of HV DC terminal earthling point to create positive potential in the structure m Spark detector terminals
Open circuit test – Stage I transformer
Voltage applied between (a-b)
Current through primary winding
50 Volt 89.2 m A100 Volt 148.2 m A150 Volt 0.19A200 Volt 0.27 A225 Volt 0.34 A250 Volt 0.42 A275 Volt 0.57 A300 Volt 0.77 A325 Volt 1.04 A
Fault detection through meter readings (1)
Primary side Secondary side 1. Check if controller is responding to sparking. If it is, use a scope to verify that sparks/arcs are occurring. Run T/R with precipitator disconnected to verify that T/R is not sparking internally.2. Check for open SCR fuses.3. Verify that SCRs are firing.4. Check for open CLR.5. Check for proper operation of controller power components - circuit breaker, contactor
No power to T/R set
Primary side Secondary side
Short Circuit—DC Side
1. Run T/R set with HV bushing disconnected from the precipitator.a. If no current flows the short is in the precipitator.b. If current still flows the short is in the T/R set.2. If precipitator is shorted, check electrodes and insulators for shorts.3. If T/R is shorted, check HV bushing and external switch (if applicable) for shorts
Fault detection through meter readings (2)
1. Megger diodes for shorts.2. Run T/R without diodes. If AAC still high, transformer is bad.
Primary side Secondary side
Short Circuit T/R set
Primary side Secondary side
1. Run T/R set with HV bushing grounded externally.a. If current flows, precipitator field is open.b. If no current flows, T/R is open.2. If precipitator is open, check all HV connections to electrodes.3. If T/R is open, megger unit. Check for open diodes or connections in T/R tank
Open circuit
Failure sequence
In cases of severe arcs or shorted field, the current may instantly rise to twice rating but quickly reduced by the controller to safe level and this instant over current is permitted to continue with every
automatic switching on , excessive heat is generated in the HV winding & diodes stack .
As a result of heat the solder that fastens the diodes to the PC board to melt away
and causes arcing between the diode lead and the PC board.
Actuation of B’ Relay
Instant arching causes generation of gas
Arcing results in the breakdown of the dielectric fluid.
Continuous arching causes generation of carbon particles
Carbon particle gets accumulated in HV windings
HV winding gets shorted
As a result of heat the HV winging joints gets melted.
inter winding arcing HV winding gets opened
Measures to be taken for avoiding frequent failure of transformer
1. Transformer must be switched off whenever it encounter with field short.
2. Whenever transformer gets failed due to internal arc , Transformer shall be filled with new oil after rectification.
3. Since silicon oil is highly hygroscopic, periodical oil circulation is required to avoid moisture absorption in solid insulation which may lead to failure of transformer due to weakness in solid insulation.
4. Availability of feed back signal ( mA & KV) must be ensured before putting the transformer in service since wrong feed back may lead to spurious power input ( Voltage & current ) to the Transformer due to malfunction of thyristor controller.
5. Ensure cleanliness of field and ash level in hopper before switching on the transformer for avoiding switching on of transformer with field short.
6. Set charge ratio 1 for repaired transformer and 3 for non repaired transformer for achieving current setting according to the physical condition of the transformer.