• Energy Efficient • Easy to Install • Extended Service Life Energy efficient compact blower coils Ideal for educational, hospitality, multi-family, or other commercial environments Designed for ducted applications Nominal CFM range of 600 to 3,000 CFM BUILD YOUR REPUTATION ON OURS Horizontal Direct Drive Blower Coils TECHNICAL CATALOG

Upload: buikhuong

Post on 19-May-2018

219 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

• Energy Efficient • Easy to Install• Extended Service Life

• Energy effi cient compact blower coils• Ideal for educational, hospitality, multi-family, or other commercial environments • Designed for ducted applications • Nominal CFM range of 600 to 3,000 CFM

BUILD YOUR REPUTATION ON OURS

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Page 2: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

222222

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

International Environmental Corporation (IEC) works continually to improve its products. As a result, the design and specif ications of each product may be changed without notice and may not be as described herein. Please contact IEC for information regarding current design and product specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely IEC’s opinion or commendation of its products. Manufacturer’s standard limited warranty applies.

2 Table of Contents

3 Portfolio

4-5 Features and Benefi ts

6-7 Unit Nomenclature

8 Nominal Capacity and Listing

9-16 Cooling Capacity Tables

17-20 Heating Capacity Tables

21 Electric Resistance Heating

22 Motor Data

23 Component Static Resistance

24 Sound Power Data

25-28 Fan Curves

29-30 Physical Data

31-32 Piping Stub-Out Location

33 Distributed Weight Calculations

34 Filters

35 Factory-Installed Options

36-37 Options - Mixing Box

Table of content

Page 3: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

3

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Horizontal Direct Drive Units

600 to 3000 CFM

Versatile Units

These compact blower coils are ideally suited for a variety of ducted applications that require a range of 600 to 3000 CFM, capacities between 1.5 tons to 10 tons, and generally rated for applications with 1” w.g. or less of external static pressure, but can be operated at higher ESP - contact factory for additional information. These units provide comfort cooling and heating while off ering a broad range of application fl exibility between the traditional fan coil unit and a central station air handling unit. Several confi gurations are available to meet the needs of diff erent climates and applications. The HDY units can be ordered as a:

• 2-pipe system

• 2-pipe system with electric heat

• 4-pipe system

• Direct expansion system cooling

• Direct expansion cooling with electric heat

• Direct expansion cooling with hot water heating

Multitude of Applications

These units are ceiling mounted, and available with a variety of options that can meet the design requirements, and provide a low cost solution for a multitude of applications.

TOOL-FREE REMOVAL OF ACCESS PANELS

PRIMARY AND SECONDARY DRAIN CONNECTION FROM DOUBLE-SLOPED STAINLESS STEEL DRAIN PAN

IMPROVED FILTER RACK DESIGN, ACCEPTS 1”, 2”, OR 4” FILTERS, TOOL-FREE FILTER ACCESS FROM BOTTOM AND TWO SIDES

DOUBLE SLOPED STAINLESS STEEL DRAIN PAN

ISOLATED BLOWER FOR QUIET OPERATION

STANDARD EC MOTOR

OPTIONAL DOUBLE WALL CONSTRUCTION

Page 4: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

4444444

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Operating Limitations

Fan curves defi ne the recommended airfl ow and static pressure ranges of operations. Running the HDY units outside this range could lead to drastically reduced bearing life and premature wheel failure. In cooling applications, this could also result in moisture carry over. In addition, running the fan at its maximum fan speed will increase the power requirements and generate higher sound levels.

On units with electric heat, the minimum airfl ow shown on the fan curve must be maintained to prevent excessive discharge temperature and electric heat safety trips.

Standard Horizontal Direct Drive Blower Coil

Applications

Where the application calls for cooling capacities or external static pressures that can not be met with standard or high performance direct drive fan coil units; use an IEC horizontal direct drive blower coil.

Outside Air Applications

With the availability of larger capacities, a variety of optional coils, mixing boxes, and the capability of delivering air through long duct runs, the direct drive units are ideal for handling outside air. When used as outside air units, the heating coil should be in the pre-heat location (consult factory).

Large Public Areas

These units are ideal for applications with a large common area such as restaurants, airports, sports arenas, stadiums, private boxes, gymnasiums, exercise areas, locker rooms, atriums and foyers, auditoriums, shopping malls, equipment or mechanical rooms, and casinos, to name a few.

Installation Considerations

The HDY units are typically suspended above the ceiling. Attention should be paid to having enough clearance around the units for service and maintenance. Horizontal units are generally suspended above the ceiling using hanger rods that go through the corner knock-outs provided in the units. External vibration isolation and fl ex connections for ducts are recommended.

Acoustical Considerations

With sound becoming more of a concern to design engineers, building owners, and occupants, proper consideration should be given to the selection and placement of these units. Whenever possible, avoid placing these units above an occupied space. To further reduce the sound level, additional measures such as: using fl exible duct connectors; lining the main supply and return ducts with acoustical absorption material; locating the return air grilles as far away from the unit as possible; and using 3-phase motors.

Page 5: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

5

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Application Fit

• Horizontal confi guration, with 8 diff erent sizes to meet a multitude of room layouts and ventilation needs

• Wide variety of coil options including 100% outside air applications

Design Flexibility

• Optional 1” double wall construction, perforated or solid lined

• Removable double-sloped stainless steel drain pan for ease of cleaning and better IAQ performance; all models include primary and secondary drain connections to provide back-up if the main drain is plugged

• Wide variety of coil sizes (4, 6, 8-rows) for a better match to the heating and cooling loads of the space; coils with diff erent materials (copper fi ns with stainless steel end sheets and bottom coil baffl es)

• Standard EC Motors ranging from 1/2 to 3 HP in a variety of voltages, in both single- and 3-phase

• A standard fi lter rack allows for 1”, 2” or 4” of fi ltration up to MERV 13

• Variety of insulation materials to comply with IAQ concerns

• Heating provided by a hot water coil or electric heat for varying application needs and climates

• Mixing boxes available for outside air applications

• User-friendly Ratings program expedites the project design and equipment selection

Ease of Installation

• Units are pre-assembled with factory installed optional electric heater controls

• 24 V control eliminates the need to run control wiring in conduit

• Corner knock-outs for hanger rods and isolators facilitate quick and easy installation

• Duct collars for supply and return air

• Optional factory installed controls eliminate the need for motor starters

Ease of Service

• Tool-free and easily accessible fi lters from multiple sides

• Large, tool-free access panels on both sides

• Optional lighting available in cabinet and control box; provides a well lit space to perform service or routine maintenance

Quality and Safety

• Every unit tested and inspected at the factory for trouble-free startup

• Optional condensate fl oat switch satisfi es the latest building codes constraints

• Motors have built-in thermal overload protection

• ETL and CETL listed

Page 6: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

666666

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

UNIT SIZE

06 600 CFM 08 800 CFM 10 1000 CFM 12 1200 CFM16 1600 CFM

20 2000 CFM 22 2200 CFM 30 3000 CFM

CABINET OPTIONSDrain Pan

AS Double Slope Stainless Steel

Filter OptionsA 1” throwawayC 2 sets of 1” throwaway

F 1” Pleated MERV 8G 2” Pleated MERV 8

M 2” MERV 11 with 2” pleated pre-fi lter U 4” MERV 11 (not available w/mixing box)W 4” MERV 13 (not available w/mixing box)

Insulation C 1” Closed CellW 1” Standard Fiberglass

S 1” Premium IAQ Fiberglass (Edges Sealed)G 1”Foil Face (Edges Sealed)

C, S & G not allowable w/ Double-Wall

Mixing box

N Rear & Top/Bottom Return comes Standard with Single-blade Dampers

Walls Construction

Y Single-Wall (Standard) A Double-Wall Construction (Solid Liner) B DW Constr. (Perforated)

Other Cabinet Options

A Cabinet/Control Box Service Light

COIL

Rows

BY 4 KY 6 LY 8 B6 4/1 B7 4/2 K6 6/1 K 6/2 QY 4 row DX 410A FY 6 Row DX 410A 6Q 1 row heating (pre-heat position) and 4 row DX 410A 6F 1 row heating (pre-heat position) 6 row DX 410A 7Q 2 row heating (pre-heat position) 4 row DX 410A 7F 2 row heating (pre-heat position) 6 row DX 410A. On size 16 and above with 1 row heat coil is 2 circuit, below size 16 coil has 1 circuit

Total rows allowed is 8.

Hand R Right-hand Coil Connections L Left-hand Coil Connections

Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections

Material (Tube/Fin/Coatings) Y Aluminum Fins w/ Galvanized Wrap S Aluminum Fins w/ Stainless Steel Wrap C Copper Fins Stainless Steel Wrap

Accessories - Vents/Drains

Y MAV(Std) A AAV(2-Pipe) B AAV(4-Pipe) C MAV w/ Drain (2-Pipe) D MAV w/ Drain (4-Pipe) E AAV w/ Drain (2-Pipe) F AAV w/ Drain (4-Pipe)

Accessories - TXV T TXV Valve (DX Only) Y None

UNIT NOMENCLATURE

Page 7: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

7

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

EC MOTOR

Motor-Voltage/Phase/Hertz

C 115/1/50-60D 208/1/50-60

E 230/1/50-60F 277/1/50-60V 220/1/50

N 208/3/50-60P 230/3/50-60

G 460/3/50-60

Horsepower

C 1/2 HP E 1 HP F 1.5 HP (Three Phase only)H 3 HP (Three Phase only)

Motor Type

M EC Motor, no board (0 -10 VDC) N EC Motor, POT board, 3 discrete speeds

ELECTRIC HEATHeater Voltage

Y None F 277/1/60C 120/1/60 N 208/3/60

D 208/1/60 P 240/3/60 E 240/1/60 G 460/3/60

Heater Kilowatt

Y NoneBY 1.0 HY 5 NH 15CY 1.5 JY 6 NJ 16DY 2 KY 7 NL 18EY 2.5 LY 8 RY 19.9FY 3 NY 9.9 RH 25FA 3.5 PY 12 SY 30GY 4 QY 14 SH 35GA 4.5Note: Voltage rules required , motor & heater voltage must match. Dual power source is not available.

Heater Stages

Y NoneA 1-Stage, Single-Phase (1-12 kW)

B 2-Stage, Single-Phase (3-12 kW) C 1-Stage, 3-Phase (1-35 kW) D 2-Stage, 3-Phase (4-35 kW) E 3-Stage, 3-Phase (12-35 kW)

Rules apply for stages

CONTROLS

Applications

BA1Y BP1K

BA3Y BP1H

BA1J BP1L

BA3J BP3K

BP1R BP3H

BP3R BP3L

1st Digit is Control Voltage (B=24 volt); 2nd Digit is Type of Control (A=Motor Controls;P=Electric Heat & Motor Controls);Third Digit is Phase (1=Single Phase;3=3 Phase);4th Digit is Fusing and Disconnect (Y=No Fusing or Discon-nect; J=40 amp Disconnect and Appropriate Motor Fusing; R=Appropriate Motor and Heater Fusing; K=R plus 40 amp disconnect; H=R plus 60 amp disconnect; L=R plus 80 amp disconnect (All electric heat includes thermal limit switch)

Special Controls

O Condensate Overfl ow Switch

Low Voltage Package

V 3-Speed Adjustable (Default)W Proportional (requires 0-10 VDC

controller)

Page 8: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

888888

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

C-ETL-US Listing IEC’s Direct Drive Series blower coil units are listed by Intertek Testing Services (ITS). ITS’s C-ETL-US listing signifi es that IEC’s blower coil units have been examined by ITS and comply with the minimum requirements of U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236, and that IEC’s manufacturing site has been audited. ITS’s re-examination service includes periodic visits to IEC’s factory to ensure continued compliance for all listed products.

Nominal Capacity Range

Model Unit Size Coil Rows Nominal CFM

Water Pressure

Drop

(ft.water)

Cooling Capacity1 (BTUH)Power Input

(Watts)Total Sensible

HDY

06 4 600 1.8 19,900 13,800 85

06 6 600 3.8 25,000 16,000 120

06 8 600 4.8 26,000 16,000 120

08 4 800 2.9 24,900 17,800 160

08 6 800 5.5 31,000 20,100 175

08 8 800 8.4 34,800 21,200 205

10 4 1,000 5.7 33,700 23,200 220

10 6 1,000 10.7 40,500 25,900 240

10 8 1,000 15.9 45,100 27,500 260

12 4 1,200 7.2 38,400 26,800 335

12 6 1,200 14.7 47,600 30,700 350

12 8 1,200 20.5 52,000 31,800 380

16 4 1,600 4.7 49,000 35,300 410

16 6 1,600 10.0 61,500 39,700 420

16 8 1,600 14.2 67,100 41,400 520

20 4 2,000 5.5 62,100 45,000 445

20 6 2,000 11.2 78,000 51,300 465

20 8 2,000 17.0 87,400 55,400 510

22 4 2,200 8.0 65,000 47,200 575

22 6 2,200 15.0 83,800 54,900 600

22 8 2,200 23.0 95,500 59,000 660

30 4 3,000 6.1 98,500 71,100 790

30 6 3,000 10.7 123,900 80,400 860

30 8 3,000 18.4 140,000 88,500 890

NOTES: 1. Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, 45°F (7.2°C) EWT , 10°F Δ(5.6°C Δ) water temperature rise , high fan speed , motor voltage 115/1/60, and airfl ow under dry coil conditions.

2. For all application ratings, use IEC’s computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative.

3. For additional information, please consult AHRI’s website at www.ahrinet.org.

AHRI Certifi cationIEC’s Horizontal Direct Drive Blower Coil units are certifi ed in compliance with Air-Conditioning, Heating, and Refrigeration Institute (AHRI) industry standard AHRI-440 for room fan coil units. Approved standard ratings are tabulated below.

3061627HEATING AND COOLING EQUIPMENT

Page 9: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

9

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

06(1/2) HP

500

480 / 67 45

10 16.9 12.4 3.4 1.612 14.9 11.5 2.5 1.8

75 / 63 4510 12.5 10.6 2.5 1.012 11.1 10.0 1.8 0.6

680 / 67 45

10 20.9 14.2 4.1 3.312 19.0 13.4 3.2 3.6

75 / 63 4510 15.3 11.9 3.0 2.012 14.0 11.4 2.3 1.3

880 / 67 45

10 22.9 15.1 4.5 5.112 21.1 14.3 3.5 3.3

75 / 63 4510 16.7 12.6 3.3 3.112 15.5 12.0 2.6 2.1

600

480 / 67 45

10 19.5 14.5 3.9 1.912 17.4 13.7 2.9 1.2

75 / 63 4510 14.6 12.5 2.9 1.212 13.1 11.9 2.2 0.8

680 / 67 45

10 24.5 16.8 4.9 4.212 22.4 16.0 3.7 2.8

75 / 63 4510 18.1 14.2 3.6 2.612 16.7 13.6 2.8 1.7

880 / 67 45

10 27.1 18.0 5.4 6.612 25.1 17.2 4.2 4.4

75 / 63 4510 20.0 15.1 4.0 4.112 18.6 14.5 3.1 2.7

700

480 / 67 45

10 21.9 16.5 4.3 2.312 19.7 15.7 3.3 1.5

75 / 63 4510 16.6 14.3 3.3 1.512 15.1 13.7 2.5 1.0

680 / 67 45

10 27.9 19.3 5.5 5.212 25.6 18.4 4.2 3.4

75 / 63 4510 20.8 16.4 4.1 3.312 19.2 15.8 3.2 2.2

880 / 67 45

10 31.2 20.9 6.2 8.312 29.1 20.0 4.8 5.5

75 / 63 4510 23.2 17.6 4.6 5.212 21.7 16.9 3.6 3.5

Cooling Capacity

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 10: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

Horizontal Direct Drive Blower Coils

1001010110110111111110

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

08(1 HP)

700

480 / 67 45

10 21.9 16.5 4.3 2.312 19.7 15.7 3.3 1.5

75 / 63 4510 16.6 14.3 3.3 1.512 15.1 13.7 2.5 1.0

680 / 67 45

10 27.9 19.3 5.5 5.212 25.6 18.4 4.2 3.4

75 / 63 4510 20.8 16.4 4.1 3.312 19.2 15.8 3.2 2.2

880 / 67 45

10 31.2 20.9 6.2 8.312 29.1 20.0 4.8 5.5

75 / 63 4510 23.2 17.6 4.6 5.212 21.7 16.9 3.6 3.5

800

480 / 67 45

10 24.2 18.5 4.8 2.712 21.9 17.6 3.6 1.7

75 / 63 4510 18.5 16.2 3.7 1.812 16.9 15.5 2.8 1.2

680 / 67 45

10 31.1 21.8 6.2 6.112 28.8 20.8 4.8 4.1

75 / 63 4510 23.4 18.7 4.6 3.912 21.8 18.0 3.6 2.6

880 / 67 45

10 35.2 23.7 7.0 10.012 33.0 22.7 5.5 6.7

75 / 63 4510 26.3 20.1 5.2 6.312 24.7 19.3 4.1 4.3

900

480 / 67 45

10 26.4 20.4 5.2 3.112 23.9 19.5 4.0 2.0

75 / 63 4510 20.4 17.9 4.0 2.112 18.6 17.2 3.1 1.4

680 / 67 45

10 34.2 24.2 6.8 7.112 31.7 23.2 5.2 4.7

75 / 63 4510 25.9 20.8 5.1 4.612 24.2 20.1 4.0 3.1

880 / 67 45

10 39.2 26.5 7.8 11.812 36.7 25.4 6.1 8.0

75 / 63 4510 29.4 22.5 5.8 7.512 27.6 21.7 4.6 5.1

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 11: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

11

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

10(1/2 HP)

900

480 / 67 45

10 33.9 23.6 6.0 4.812 30.3 21.7 5.6 6.6

75 / 63 4510 22.6 18.6 4.5 3.112 20.8 17.9 3.4 2.0

680 / 67 45

10 36.5 24.8 7.2 9.912 33.9 23.6 5.6 6.6

75 / 63 4510 27.0 20.9 5.4 6.112 25.2 20.1 4.2 4.1

880 / 67 45

10 38.6 25.7 7.7 14.412 35.9 24.6 5.9 9.6

75 / 63 4510 28.3 21.5 5.6 8.812 26.6 20.8 4.4 6.0

1000

480 / 67 45

10 32.7 23.8 6.5 5.512 30.0 22.7 5.0 3.6

75 / 63 4510 24.7 20.4 4.9 3.512 22.8 19.7 3.8 2.3

680 / 67 45

10 39.4 27.2 7.9 11.412 37.1 26.1 6.1 7.6

75 / 63 4510 29.6 23.0 5.9 7.112 27.8 22.2 4.6 4.8

880 / 67 45

10 42.6 28.4 8.4 16.812 39.7 27.2 6.6 11.3

75 / 63 4510 31.4 23.9 6.2 10.412 29.5 23.1 4.9 7.1

1100

480 / 67 45

10 35.2 25.8 7.0 6.212 32.4 24.7 5.4 4.0

75 / 63 4510 26.7 22.3 5.3 4.012 24.7 21.5 4.1 2.6

680 / 67 45

10 43.4 29.7 8.6 12.912 40.3 28.4 6.7 8.6

75 / 63 4510 32.4 25.2 6.4 8.212 30.4 24.4 5.0 5.5

880 / 67 45

10 46.5 31.2 9.2 19.312 43.3 29.8 7.2 12.9

75 / 63 4510 34.4 26.2 6.8 12.012 32.5 25.4 5.4 8.2

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 12: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

Horizontal Direct Drive Blower Coils

1221212112112111111112

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

12(1 HP)

1100

480 / 67 45

10 35.2 25.8 7.0 6.212 32.4 24.7 5.4 4.0

75 / 63 4510 26.7 22.3 5.3 4.012 24.7 21.5 4.1 2.6

680 / 67 45

10 43.4 29.7 8.6 12.912 40.3 28.4 6.7 8.6

75 / 63 4510 32.4 25.2 6.4 8.212 30.4 24.4 5.0 5.5

880 / 67 45

10 46.5 31.2 9.2 19.312 43.3 29.8 7.2 12.9

75 / 63 4510 34.4 26.2 6.8 12.012 32.5 25.4 5.4 8.2

1200

480 / 67 45

10 37.7 27.8 7.5 6.812 34.7 26.6 5.7 4.5

75 / 63 4510 28.7 24.1 5.7 4.512 26.7 23.3 4.4 3.0

680 / 67 45

10 46.6 32.1 9.2 14.412 43.4 30.8 7.2 9.7

75 / 63 4510 35.0 27.4 6.9 9.212 32.8 26.5 5.4 6.2

880 / 67 45

10 50.3 33.9 10.0 21.812 47.1 32.5 7.8 14.7

75 / 63 4510 37.5 28.6 7.4 13.812 35.4 27.7 5.8 9.4

1300

480 / 67 45

10 39.9 29.7 7.9 7.512 37.0 28.6 6.1 5.0

75 / 63 4510 30.6 25.9 6.1 4.912 28.5 25.0 4.7 3.3

680 / 67 45

10 49.9 34.5 9.9 16.112 46.6 33.2 7.7 10.8

75 / 63 4510 37.5 29.5 7.4 10.312 35.4 28.6 5.8 7.0

880 / 67 45

10 54.0 36.5 10.7 24.412 50.8 35.1 8.4 16.6

75 / 63 4510 40.4 30.9 8.0 15.512 38.2 30.0 6.3 10.6

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 13: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

13

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

16(1 HP)

1400

480 / 67 45

10 42.2 31.9 8.4 3.512 38.4 30.4 6.4 2.3

75 / 63 4510 32.1 27.7 6.4 2.312 29.4 26.6 4.9 1.5

680 / 67 45

10 50.5 35.8 10.0 7.012 46.9 34.3 7.8 4.7

75 / 63 4510 37.9 30.6 7.5 4.512 35.4 29.6 5.9 3.0

880 / 67 45

10 54.3 37.4 10.8 10.512 50.3 35.7 8.3 7.0

75 / 63 4510 40.3 31.7 7.99 6.612 37.8 30.6 6.3 4.5

1600

480 / 67 45

10 46.7 35.8 9.3 4.112 42.9 34.3 7.1 2.7

75 / 63 4510 36.0 31.3 7.1 2.712 33.2 30.2 5.5 1.8

680 / 67 45

10 56.8 40.6 11.3 8.412 52.7 38.9 8.7 5.6

75 / 63 4510 42.9 34.9 8.5 5.412 40.3 33.8 6.7 3.7

880 / 67 45

10 61.6 42.6 12.2 12.912 57.5 40.9 9.5 8.6

75 / 63 4510 46.0 36.3 9.1 8.112 43.3 356.1 7.2 5.5

1800

480 / 67 45

10 51.2 39.7 10.2 4.712 47.4 38.2 7.8 3.1

75 / 63 4510 39.8 34.9 7.9 3.212 36.8 33.7 6.1 2.1

680 / 67 45

10 62.7 45.2 12.4 9.812 58.5 43.5 9.7 6.6

75 / 63 4510 47.6 39.0 9.5 6.412 44.9 37.9 7.4 4.4

880 / 67 45

10 68.5 47.7 13.6 15.212 64.1 45.9 10.6 10.2

75 / 63 4510 51.5 40.8 10.2 9.712 48.8 39.7 8.1 6.7

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 14: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

Horizontal Direct Drive Blower Coils

1441414114111111111414

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

20(1 HP)

1800

480 / 67 45

10 57.3 42.6 11.4 4.512 52.6 40.8 8.7 2.9

75 / 63 4510 43.8 37.1 8.7 3.012 40.4 35.7 6.7 1.9

680 / 67 45

10 70.0 48.7 13.9 9.312 65.2 46.7 10.8 6.3

75 / 63 4510 52.7 41.6 10.5 6.012 49.4 40.2 8.2 4.1

880 / 67 45

10 89.6 57.4 17.77 18.4912 84.3 55.0 13.9 12.6

75 / 63 4510 66.3 47.7 13.1 11.512 62.2 45.9 10.3 7.8

2000

480 / 67 45

10 61.9 46.5 12.28 5.0812 57.1 44.6 9.43 3.34

75 / 63 4510 47.6 40.6 9.4 3.412 44.1 39.1 7.3 2.2

680 / 67 45

10 76.4 53.5 15.2 10.712 71.2 51.3 11.8 7.2

75 / 63 4510 57.8 45.9 11.5 6.912 54.2 44.4 9.0 4.7

880 / 67 45

10 93.2 61.0 18.5 19.712 87.7 58.5 14.5 13.4

75 / 63 4510 69.2 51.1 13.7 12.312 65.2 49.3 10.8 8.4

2200

480 / 67 45

10 66.4 50.3 13.2 5.712 61.3 48.3 10.1 3.7

75 / 63 4510 51.2 44.0 10.2 3.812 47.6 42.5 7.9 2.5

680 / 67 45

10 82.6 58.2 16.4 12.112 77.2 56.0 12.8 8.2

75 / 63 4510 62.8 50.1 12.5 7.912 59.1 48.5 9.8 5.4

880 / 67 45

10 95.2 63.9 18.8 20.312 89.4 61.4 14.8 13.8

75 / 63 4510 71.3 54.2 14.1 12.912 67.4 52.4 11.1 8.9

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 15: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Cooling Capacity, Cont’d.

15

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

22(1 1/2 HP)

2000

480 / 67 45

10 61.9 46.5 12.28 5.0812 57.1 44.6 9.43 3.34

75 / 63 4510 47.6 40.6 9.4 3.412 44.1 39.1 7.3 2.2

680 / 67 45

10 76.4 53.5 15.2 10.712 71.2 51.3 11.8 7.2

75 / 63 4510 57.8 45.9 11.5 6.912 54.2 44.4 9.0 4.7

880 / 67 45

10 93.2 61.0 18.5 19.712 87.7 58.5 14.5 13.4

75 / 63 4510 69.2 51.1 13.7 12.312 65.2 49.3 10.8 8.4

2200

480 / 67 45

10 66.4 50.3 13.2 5.712 61.3 48.3 10.1 3.7

75 / 63 4510 51.2 44.0 10.2 3.812 47.6 42.5 7.9 2.5

680 / 67 45

10 82.6 58.2 16.4 12.112 77.2 56.0 12.8 8.2

75 / 63 4510 62.8 50.1 12.5 7.912 59.1 48.5 9.8 5.4

880 / 67 45

10 95.2 63.9 18.8 20.312 89.4 61.4 14.8 13.8

75 / 63 4510 71.3 54.2 14.1 12.912 67.4 52.4 11.1 8.9

2400

480 / 67 45

10 70.5 53.9 14.0 6.212 65.4 52.0 10.8 4.1

75 / 63 4510 54.9 47.4 10.9 4.212 51.1 45.9 8.5 2.8

680 / 67 45

10 88.6 62.8 17.6 13.512 82.9 60.5 13.7 9.1

75 / 63 4510 67.5 54.2 13.4 8.812 63.8 52.6 10.5 6.1

880 / 67 45

10 95.4 66.2 18.9 20.412 89.8 63.9 14.9 13.9

75 / 63 4510 72.3 56.8 14.3 13.212 68.8 55.3 11.4 9.1

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 16: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

1661616116116111111116

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEAT

(°F) DB/WBEWT(°F)

ΔT(°F)

Total(MBH)

Sensible (MBH)

GPMWPD

(ft. wg.)

30(3 HP)

2800

480 / 67 45

10 91.9 68.6 18.2 4.612 84.8 65.9 14.0 3.1

75 / 63 4510 70.6 59.9 14.0 3.112 65.4 57.8 10.8 2.0

680 / 67 45

10 116.4 80.4 23.1 10.212 109.5 77.5 18.1 7.0

75 / 63 4510 88.5 69.1 17.6 6.712 83.3 66.8 13.8 4.5

880 / 67 45

10 131.4 87.4 26.1 16.612 124.7 84.6 20.6 11.5

75 / 63 4510 99.5 74.4 19.7 10.712 94.2 72.1 15.6 7.4

3000

480 / 67 45

10 96.4 72.5 19.1 5.012 89.2 69.7 14.7 3.3

75 / 63 4510 74.4 63.4 14.8 3.312 69.1 61.2 11.4 2.2

680 / 67 45

10 122.5 85.1 24.3 11.112 115.4 82.2 19.1 7.6

75 / 63 4510 93.5 73.3 18.5 7.212 88.1 71.0 14.6 4.9

880 / 67 45

10 139.4 93.0 27.7 18.212 131.9 89.8 21.8 12.5

75 / 63 4510 105.5 79.2 20.9 11.812 100.0 76.8 16.5 8.1

3200

480 / 67 45

10 100.8 76.3 20.0 5.412 93.4 73.4 15.4 3.6

75 / 63 4510 78.1 66.9 15.5 3.612 72.7 64.6 12.0 2.4

680 / 67 45

10 128.6 89.8 25.5 12.012 121.2 86.8 20.0 8.2

75 / 63 4510 98.3 77.5 19.5 7.812 92.9 75.2 15.4 5.4

880 / 67 45

10 146.6 982.3 29.1 19.712 138.6 94.9 22.9 13.5

75 / 63 4510 111.1 83.8 22.0 12.812 105.6 81.4 17.5 8.8

Cooling Capacity, Cont’d.

NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.

Page 17: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

17

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEWT(°F)

ΔT(°F)

MBHLAT(°F)

GPMWPD

(ft. wg.)

06(1/2 HP)

500

1140

40 7.8 84.2 0.4 0.220 11.3 90.7 1.1 1.4

18040 16.8 100.6 0.8 0.820 19.7 106.0 2.0 4.1

2140

40 13.2 94.1 0.7 0.120 18.9 104.6 1.9 1.0

18040 28.2 121.6 1.4 0.520 32.6 129.6 3.3 2.8

600

1140

40 9.1 83.9 0.5 0.220 13.2 90.2 1.3 2.0

18040 19.6 99.9 1.0 1.020 23.1 105.2 2.3 5.6

2140

40 15.6 93.8 0.8 0.220 22.2 103.9 2.2 1.4

18040 33.1 120.5 1.7 0.720 38.3 128.4 3.8 3.9

700

1140

40 10.2 83.3 0.5 0.320 14.7 89.3 1.5 2.4

18040 21.8 98.5 1.1 1.320 25.7 103.6 2.6 7.0

2140

40 17.6 93.0 0.9 0.220 25.0 102.6 2.5 1.7

18040 37.2 118.6 1.9 0.920 43.1 126.4 4.3 4.9

08(1 HP)

700

1140

40 10.2 83.3 0.5 0.320 14.7 89.3 1.5 2.4

18040 21.8 98.5 1.1 1.320 25.7 103.6 2.6 7.0

2140

40 17.6 93.0 0.9 0.220 25.0 102.6 2.5 1.7

18040 37.2 118.6 1.9 0.920 43.1 126.4 4.3 4.9

800

1140

40 11.0 82.6 0.6 0.320 15.9 88.2 1.6 2.8

18040 23.5 96.9 1.2 1.520 27.8 101.8 2.8 8.2

2140

40 19.2 92.0 1.0 0.320 27.2 101.1 2.7 2.1

18040 40.5 116.3 2.0 1.120 47.1 123.8 4.7 5.8

900

1140

40 11.6 81.8 0.6 0.420 16.8 87.1 1.7 3.1

18040 24.8 95.2 1.2 1.620 29.4 99.9 2.9 9.1

2140

40 20.4 90.8 1.0 0.320 29.0 99.5 2.9 2.3

18040 43.1 113.8 2.2 1.220 50.3 121.1 5.0 6.7

NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.

Heating Capacity

Page 18: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Heating Capacity, Cont’d.

Horizontal Direct Drive Blower Coils

1881818118118111111118

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.

Unit Size CFM RowsEWT(°F)

ΔT(°F)

MBHLAT(°F)

GPMWPD

(ft. wg.)

10(1/2 HP)

900

1140

40 14.9 85.1 0.7 0.820 20.2 90.6 2.0 6.0

18040 30.1 100.6 1.5 3.220 34.8 105.4 3.5 16.8

2140

40 25.6 96.1 1.3 0.620 34.0 104.6 3.4 4.2

18040 50.9 121.7 2.5 2.320 57.9 128.9 5.8 11.6

1000

1140

40 16.0 84.6 0.8 1.020 21.8 89.9 2.2 6.9

18040 32.4 99.6 1.6 3.720 37.5 104.3 3.8 19.4

2140

40 27.7 95.3 1.4 0.720 36.8 103.7 3.7 4.9

18040 55.0 120.3 2.8 2.620 62.8 127.4 6.3 13.6

1100

1140

40 16.9 84.1 0.8 1.120 23.1 89.2 2.3 7.8

18040 34.3 98.5 1.7 4.120 39.8 103.1 4.0 21.8

2140

40 29.5 94.5 1.5 0.820 39.3 102.6 3.9 5.6

18040 58.6 118.8 2.9 3.020 67.0 125.7 6.7 15.5

12(1 HP)

1100

1140

40 16.9 84.1 0.8 1.120 23.1 89.2 2.3 7.8

18040 34.3 98.5 1.7 4.120 39.8 103.1 4.0 21.8

2140

40 29.5 94.5 1.5 0.820 39.3 102.6 3.9 5.6

18040 58.6 118.8 2.9 3.020 67.0 125.7 6.7 15.5

1200

1140

40 17.7 83.5 0.9 1.220 24.2 88.4 2.4 8.5

18040 35.9 97.3 1.8 4.520 41.7 101.7 4.2 24.0

2140

40 31.0 93.6 1.5 0.920 41.4 101.5 4.1 6.2

18040 61.8 117.1 3.1 3.320 70.7 123.9 7.1 17.2

1300

1140

40 18.3 82.9 0.9 1.220 25.0 87.6 2.5 9.1

18040 37.2 96.1 1.9 4.820 - - - -

2140

40 32.3 92.7 1.6 1.020 43.2 100.4 4.3 6.8

18040 64.4 115.3 3.2 3.620 73.8 121.9 7.4 18.8

Page 19: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Heating Capacity, Cont’d.

19

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEWT(°F)

ΔT(°F)

MBHLAT(°F)

GPMWPD

(ft. wg.)

16(1 HP)

1400

1140

40 19.9 83.0 1.0 0.220 29.1 89.0 2.9 1.9

18040 43.1 98.2 2.2 1.020 51.0 103.3 5.1 5.6

2140

40 37.4 94.5 1.9 0.520 50.6 103.0 5.1 3.5

18040 75.5 119.3 3.8 1.820 86.5 126.5 8.7 5.4

1600

1140

40 21.4 82.2 1.1 0.320 31.4 87.9 3.1 2.2

18040 46.4 96.5 2.3 1.220 54.9 101.4 5.5 6.4

2140

40 40.6 93.2 2.0 0.620 55.0 101.4 5.5 4.1

18040 82.0 116.9 4.1 2.220 94.2 123.8 9.4 11.4

1800

1140

40 22.6 81.5 1.1 0.320 33.0 86.8 3.3 2.5

18040 48.8 94.8 2.4 1.320 57.8 99.4 5.8 7.2

2140

40 43.1 91.9 2.2 0.620 58.5 99.7 5.8 4.6

18040 87.1 114.3 4.4 2.520 100.4 121.0 10.0 12.9

20(1 HP)

1800

1140

40 26.2 83.3 1.3 0.520 36.9 88.8 3.7 3.7

18040 54.7 97.8 2.7 1.920 64.1 102.6 6.4 10.5

2140

40 43.7 92.2 2.2 0.320 61.9 101.5 6.2 2.2

18040 92.1 116.8 4.6 1.220 107.3 124.5 10.7 6.3

2000

1140

40 27.6 82.6 1.4 0.520 38.9 87.8 3.9 4.1

18040 57.6 96.3 2.9 2.220 67.6 100.9 6.8 11.7

2140

40 46.4 91.2 2.3 0.320 65.8 100.1 6.6 2.5

18040 97.8 114.7 4.9 1.320 114.2 122.2 11.4 7.1

2200

1140

40 28.7 81.9 1.4 0.620 40.4 86.8 4.0 4.4

18040 59.9 94.9 3.0 2.320 70.3 99.2 7.0 12.7

2140

40 48.5 90.2 2.4 0.420 69.0 98.7 6.9 2.7

18040 102.5 112.6 5.1 1.520 119.8 119.8 12.0 7.9

NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.

Page 20: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Heating Capacity, Cont’d.

Horizontal Direct Drive Blower Coils

20020202220222022222222222220

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Unit Size CFM RowsEWT(°F)

ΔT(°F)

MBHLAT(°F)

GPMWPD

(ft. wg.)

22(1 1/2 HP)

2000

1140

40 27.6 82.6 1.4 0.520 38.9 87.8 3.9 4.1

18040 57.6 96.3 2.9 2.220 67.6 100.9 6.89 11.7

2140

40 46.4 91.2 2.3 0.320 65.8 100.1 6.6 2.5

18040 97.8 114.7 4.9 1.320 114.2 122.2 11.4 7.1

2200

1140

40 28.7 81.9 1.4 0.620 40.4 86.8 4 4.4

18040 59.9 94.9 3 2.320 70.3 99.2 7 12.7

2140

40 48.5 90.2 2.4 0.420 69 98.7 6.9 2.7

18040 102.5 112.6 5.1 1.520 119.8 119.8 12 7.9

2400

1140

40 29 81.8 1.5 0.720 40.8 86 4.1 4.8

18040 60 94.8 3.2 2.420 70.8 99 7.1 13

2140

40 49 90 2.6 0.520 70 98.8 7 2.9

18040 103 112.5 5.3 1.720 120.1 119.7 12.1 8.3

30(3 HP)

2800

1140

40 30.0 79.8 1.5 0.120 54.3 87.7 5.4 0.7

18040 79.8 96.1 4.0 0.420 97.1 101.7 9.7 2.2

2140

40 67.9 92.2 3.4 0.220 96.9 101.6 9.7 1.8

18040 144.2 117.1 7.2 0.920 167.7 124.8 16.8 5.0

3000

1140

40 31.5 79.6 1.6 0.120 56.3 87.1 5.6 0.8

18040 82.7 95.2 4.1 0.420 100.7 100.7 10.1 2.3

2140

40 70.8 91.6 3.5 0.220 101.0 100.8 10.1 1.9

18040 150.2 115.8 7.5 1.020 174.9 123.3 17.5 5.5

3200

1140

40 32.7 79.4 1.6 0.120 57.9 86.6 5.8 0.8

18040 85.1 94.3 4.3 0.420 103.7 99.6 10.4 2.5

2140

40 73.3 91.0 3.7 0.320 104.6 99.9 10.5 2.1

18040 155.5 114.4 7.8 1.120 181.4 121.8 18.1 5.9

NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.

Page 21: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

21

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Electric heaters are available on IEC Direct Drive blower coils for total electric heat.

Total Electric HeatTotal electric heat eliminates the requirement for a boiler and provides heating and/or cooling on an individual basis throughout the year. Electric heat is available only for single source power (motor and heater voltage the same).

Heater ConstructionThe heater coils of high-grade resistance wire are supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the outlet after the blower and the coil. An auto and a manual thermal limit switch protect the heater in the event of airfl ow failure. For electric heat control options refer to page 35.

Electric Heater Selection

kWHeater Availability Full Load Amps

Single Phase Three Phase6 8 10 12 16 20/22 30 115 V 208 V 230 V 277 V 208 V 230 V 460 V

1 • • - - - - - 8.3 4.8 4.2 3.6 2.8 2.4 1.21.5 • • • • - - - 12.5 7.2 6.3 5.4 4.2 3.6 1.82 • • • • - - - 16.7 9.6 8.3 7.2 5.6 4.8 2.4

2.5 • • • • • - - 20.8 12.0 10.4 9.0 6.9 6.0 3.03 • • • • • - - 25.0 14.4 12.5 10.8 8.3 7.2 3.6

3.5 • • • • • • - 29.2 16.8 14.6 12.6 9.7 8.4 4.24 • • • • • • - 33.3 19.2 16.7 14.4 11.1 9.6 4.8

4.5 • • • • • • - 37.5 21.6 18.8 16.2 12.5 10.8 5.45 • • • • • • - - 24.0 20.8 18.1 13.9 12.0 6.06 • • • • • • • - 28.8 25.0 21.7 16.7 14.4 7.27 - • • • • • • - 33.7 29.2 25.3 19.4 16.8 8.48 - • • • • • • - 38.5 33.3 28.9 22.2 19.2 9.6

9.9 - - • • • • • - - - 35.7 27.5 23.8 11.912 - - - • • • • - - - 43.3 33.3 28.9 14.414 - - - - • • • - - - - 38.9 33.7 16.815 - - - - • • • - - - - 41.6 36.1 18.016 - - - - • • • - - - - - 38.5 19.218 - - - - - • • - - - - - - 21.7

19.9 - - - - - • • - - - - - - 23.925 - - - - - - • - - - - - - 30.130 - - - - - - • - - - - - - 36.135 - - - - - - • - - - - - - 42.1

NOTES: 1. Electric heaters are available for 1-stage, 2-stage or 3-stage applications depending on power phase and heater kW. SINGLE-PHASE POWER:

1-12 kW: 1-stage available 3-12 kW: 2-stage available

3-PHASE POWER: 1-35 kW: 1-stage available 4-35 kW: 2-stage available 12-35 kW: 3-stage available

2. Electric Heating Capacities (BTUH) = Heater kW x 3413 3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage Electric Heater Amperage for 3-phase Power = (Heater kW x 1000)/(Applied Voltage x 1.73)

Page 22: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

22222222222222222222222222222

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Motor Full Load Amps Data – HDY

Voltage

UNIT SIZE

06, 10 08,12,16,20 22 30

Motor HP

1/2 1 1-1/2 3

115 V50/60 Hz1-Phase

6.4 10.7 NA NA

208 V50/60 Hz1-Phase

3.8 6.3 NA NA

230 V50/60 Hz1-Phase

3.6 5.8 NA NA

277 V50/60 Hz1-Phase

3.2 5.1 NA NA

208 V50/60 Hz3-Phase

2.0 7.0 4.4 8.9

230 V50/60 Hz3-Phase

1.85 6.5 4.4 8.9

460 V50/60 Hz3-Phase

1.0 1.75 2.2 4.4

NOTES: 1. Motor full load Amps refer to National Electric Code (NEC) Amps; actual motor nameplate amps may vary. 2. Motors are UL recognized constant speed brushless DC, open drip proof, ball bearing, multi-input voltage options, 0-10 VDC

control, PWM control and 12 VDC supply direct from motor. 1/2 and 1 HP motors have integrated control module with overload and short circuit protection. 1-1/2 and 3 HP motors have remote mounted control with overload and short circuit protection. Control module is mounted internal of cabinet.

Thermal Overload Protection All standard motors on Horizontal Direct Drive units furnished by IEC contain internal thermal overload protection. The overload automatically resets when the temperature returns to a safe limit. These thermal overloads replace the need for motor starters.

Page 23: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

23

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Component Static Resistance Table (in w.c.)

Unit Size

Nominal CFM

Coil(includes cabinet) Filters

MixingBox

Dry1”

Throw-away

1"MERV 8 Pleated

(Qty. 2)1" Throw-

away

2"MERV 8 Pleated

2" MERV 11

w/Prefi lter

4”MERV 11 Pleated

4”MERV 13 Pleated

4Row

5Row

6Row

7Row

8Row

06

400 0.07 0.08 0.10 0.11 0.12 0.04 0.07 0.05 0.04 0.04 0.03 0.04 0.02500 0.11 0.13 0.16 0.18 0.19 0.06 0.11 0.07 0.05 0.06 0.05 0.06 0.03600 0.15 0.19 0.22 0.24 0.27 0.08 0.14 0.09 0.06 0.07 0.06 0.08 0.04700 0.20 0.24 0.28 0.31 0.34 0.10 0.17 0.11 0.08 0.09 0.08 0.10 0.06800 0.24 0.29 0.34 0.38 0.42 0.12 0.21 0.14 0.09 0.11 0.09 0.12 0.08

08

600 0.15 0.19 0.22 0.24 0.27 0.08 0.14 0.09 0.06 0.07 0.06 0.08 0.04700 0.20 0.24 0.28 0.31 0.34 0.10 0.17 0.11 0.08 0.09 0.08 0.10 0.06800 0.24 0.29 0.34 0.38 0.42 0.12 0.21 0.14 0.09 0.11 0.09 0.12 0.08900 0.28 0.34 0.40 0.45 0.49 0.14 0.24 0.16 0.10 0.12 0.10 0.14 0.10

1000 0.33 0.40 0.46 0.52 0.57 0.16 0.27 0.18 0.12 0.14 0.12 0.16 0.12

10

800 0.12 0.14 0.16 0.18 0.21 0.06 0.10 0.08 0.06 0.13 0.05 0.05 0.04900 0.15 0.18 0.21 0.24 0.26 0.07 0.12 0.09 0.07 0.16 0.06 0.06 0.05

1000 0.19 0.22 0.26 0.29 0.32 0.09 0.14 0.11 0.08 0.18 0.07 0.07 0.061100 0.22 0.26 0.30 0.34 0.37 0.10 0.16 0.13 0.09 0.21 0.08 0.08 0.081200 0.25 0.30 0.35 0.39 0.43 0.11 0.18 0.14 0.10 0.23 0.09 0.09 0.09

12

1000 0.19 0.22 0.26 0.29 0.32 0.09 0.14 0.11 0.08 0.18 0.07 0.07 0.061100 0.22 0.26 0.30 0.34 0.37 0.10 0.16 0.13 0.09 0.21 0.08 0.08 0.081200 0.25 0.30 0.35 0.39 0.43 0.11 0.18 0.14 0.10 0.23 0.09 0.09 0.091300 0.29 0.34 0.40 0.44 0.48 0.13 0.19 0.16 0.11 0.25 0.10 0.10 0.111400 0.32 0.38 0.44 0.49 0.54 0.14 0.21 0.18 0.12 0.28 0.11 0.11 0.13

16

1400 0.19 0.23 0.28 0.31 0.34 0.11 0.14 0.17 0.10 0.21 0.09 0.09 0.071500 0.22 0.26 0.31 0.35 0.38 0.12 0.16 0.19 0.10 0.24 0.10 0.10 0.091600 0.24 0.29 0.35 0.38 0.42 0.13 0.17 0.21 0.11 0.26 0.11 0.11 0.101700 0.27 0.32 0.38 0.42 0.47 0.14 0.19 0.22 0.12 0.28 0.12 0.12 0.111800 0.29 0.35 0.42 0.46 0.51 0.15 0.20 0.24 0.13 0.30 0.12 0.13 0.12

20

1800 0.22 0.27 0.32 0.37 0.42 0.11 0.18 0.17 0.11 0.24 0.10 0.13 0.071900 0.24 0.30 0.36 0.41 0.46 0.12 0.19 0.18 0.12 0.26 0.11 0.14 0.082000 0.27 0.33 0.39 0.45 0.50 0.13 0.21 0.20 0.13 0.28 0.12 0.15 0.092100 0.29 0.36 0.42 0.49 0.55 0.14 0.22 0.21 0.13 0.30 0.13 0.16 0.102200 0.31 0.39 0.46 0.53 0.59 0.15 0.24 0.23 0.14 0.32 0.14 0.17 0.112300 0.34 0.42 0.49 0.57 0.64 0.16 0.25 0.25 0.15 0.34 0.15 0.18 0.122400 0.36 0.44 0.53 0.60 0.68 0.17 0.27 0.26 0.16 0.36 0.16 0.20 0.13

22

1800 0.22 0.27 0.32 0.37 0.42 0.11 0.18 0.17 0.11 0.24 0.10 0.13 0.071900 0.24 0.30 0.36 0.41 0.46 0.12 0.19 0.18 0.12 0.26 0.11 0.14 0.082000 0.27 0.33 0.39 0.45 0.50 0.13 0.21 0.20 0.13 0.28 0.12 0.15 0.092100 0.29 0.36 0.42 0.49 0.55 0.14 0.22 0.21 0.13 0.30 0.13 0.16 0.102200 0.31 0.39 0.46 0.53 0.59 0.15 0.24 0.23 0.14 0.32 0.14 0.17 0.112300 0.34 0.42 0.49 0.57 0.64 0.16 0.25 0.25 0.15 0.34 0.15 0.18 0.122400 0.36 0.44 0.53 0.60 0.68 0.17 0.27 0.26 0.16 0.36 0.16 0.20 0.13

30

2400 0.17 0.21 0.24 0.28 0.33 0.09 0.15 0.14 0.10 0.19 0.07 0.11 0.072600 0.20 0.24 0.28 0.33 0.38 0.10 0.16 0.16 0.11 0.22 0.08 0.13 0.092800 0.23 0.27 0.32 0.38 0.43 0.11 0.18 0.17 0.12 0.24 0.09 0.14 0.103000 0.26 0.31 0.36 0.42 0.49 0.13 0.20 0.19 0.14 0.26 0.10 0.16 0.113200 0.29 0.34 0.40 0.47 0.54 0.14 0.22 0.21 0.15 0.28 0.12 0.18 0.133400 0.32 0.38 0.44 0.52 0.59 0.15 0.24 0.23 0.16 0.31 0.13 0.19 0.15

Page 24: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

24424242224222422222222222224

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Sound Power DataUNIT SIZE

RATINGFAN

SPEEDCFM

SOUND POWER LEVEL, Lw (dB reference one picowatt) A-wgt (dBA)

MotorHP125 Hz 250 Hz 500 Hz 1K Hz 2K Hz 4K Hz 8K Hz

6

CASING RADIATED

NOTE 2975

600 @

.50” ESP

64 59 55 51 46 40 35 57

1/2DUCTED

DISCHARGE NOTE 3

63 53 53 51 50 45 37 57

8

CASING RADIATED

NOTE 21,075

800 @

.50” ESP

64 60 60 58 56 54 45 64

1DUCTED

DISCHARGENOTE 3

64 61 58 56 50 43 36 60

10

CASING RADIATED

NOTE 21,140

1,000 @

.50” ESP

70 65 59 59 55 49 41 64

1/2DUCTED

DISCHARGENOTE 3

68 63 65 64 61 60 53 68

12

CASING RADIATED

NOTE 21,235

1,200@

.50” ESP

73 69 61 62 57 51 44 67

1DUCTED

DISCHARGENOTE 3

72 67 67 67 64 63 57 72

16

CASING RADIATED

NOTE 21,066

1,600@

.50” ESP

73 69 62 64 60 55 48 68

1DUCTED

DISCHARGE NOTE 3

72 68 69 70 68 68 63 75

20

CASING RADIATED

NOTE 2910

2,000@

.50” ESP

74 69 60 59 56 51 42 66

1DUCTED

DISCHARGE NOTE 3

71 67 66 66 64 63 57 71

22 NOTE 4

CASING RADIATED

NOTE 2950

2,200@

.50” ESP

73 69 60 60 58 53 45 66

1-1/2DUCTED

DISCHARGE NOTE 3

73 68 65 67 64 63 57 72

30NOTE 4

CASING RADIATED NOTE 2

8603,000@

.50” ESP

74 70 65 63 61 57 49 69

3DUCTED

DISCHARGE NOTE 3

71 73 75 72 70 70 64 78

NOTES:1. Unit Test Configuration: Rear Return/Front Supply, 4 Row, 10 FPI Coil, 115/1 PH/ 60HZ VAC Motor, 2” Fiberglass Filter, 1/2” dual density fiberglass insulation.2. Testing per AHRI 260-2001: 4.2.2.3 Casing radiated with free inlet, Sound Rating of Ducted Air Moving and Conditioning Equipment.3. Testing per AHRI 260-2001: 4.2.2.1 Ducted discharge, Sound Rating of Ducted Air Moving and Conditioning Equipment. 4. Size 22 & 30 Unit Test Configuration: Rear Return/Front Supply, 4 Row, 10 FPI Coil, 460/3 PH/ 60HZ VAC Motor, 2” Fiberglass Filter, 1/2” dual density fiberglass insulation.5. Sound power data is expressed in decibels, dB RE: 1 x 10-12 w (picowatts).

Page 25: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

25

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Fan Curves

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

0 200 400 600 800 1000 1200

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY06, 1/2 hp Motor

400 600 800 1000 1200 1400RPM

RECOMMENDEDOPERATING RANGE

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

0 200 400 600 800 1000 1200 1400 1600

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY08, 1 hp Motor

400 600 800 1000 1200

1400 1600 1800

RECOMMENDED OPERATING RANGE

RPM

Page 26: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

26626262226222622222222222226

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Fan Curves, Cont’d.

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

200 400 600 800 1000 1200 1400 1600 1800 2000

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY10, 1/2 hp Motor

600 800 1000 1200

1400 1600 1800

RPM

RECOMMENDED OPERATING RANGE

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

200 400 600 800 1000 1200 1400 1600 1800 2000

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY12, 1 hp Motor

600 800 1000 1200

1400 1600 1800

RECOMMENDED OPERATING RANGE

RPM

Page 27: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

27

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Fan Curves, Cont’d.

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

3

400 800 1200 1600 2000 2400 2800

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY20, 1 hp Motor

600 800 1000 1200 1400RPM

RECOMMENDED OPERATING RANGE

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

3

400 600 800 1000 1200 1400 1600 1800 2000 2200 2400

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY16, 1 hp Motor

600 800 1000 1200

1400 1600

RPM

RECOMMENDED OPERATING RANGE

Page 28: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

28828282228222822222222222228

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Fan Curves, Cont’d.

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

3

3.25

3.5

0 500 1000 1500 2000 2500 3000 3500 4000 4500

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY30, 3 hp Motor

600 800 1000 1200 1400RPM

RECOMMENDED OPERATING RANGE

0

0.25

0.5

0.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

3

400 800 1200 1600 2000 2400 2800

TOTA

L ST

ATI

C PR

ESSU

RE

SCFM

HDY22, 1.5 hp Motor

600 800 1000 1200 1400RPM

RECOMMENDED OPERATING RANGE

Page 29: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

29

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

HDY Unit– Horizontal Direct Drive

SizeFan Size

Depth Width HeightSupply Duct Return Duct (Note 7) Mounting Holes

Aux.Ctrl.

Box

A B C D E F G J K L

06 9 x 6 36(914)

28(711)

19-3/4 (502)

8-7/8(225)

10-7/8(276)

13-3/4(349)

2-1/4(57)

24-1/4(616)

14(356)

2-3/4(70)

27-1/4(686)

35-1/4(895)

5-3/4(146)

08 9 x 6 36(914)

28(711)

19-3/4 (502)

8-7/8(225)

10-7/8(276)

13-3/4(349)

2-1/4(57)

24-1/4(616)

14(356)

2-3/4(70)

27-1/4(686)

35-1/4(895)

5-3/4(146)

10 9 x 6 37-1/2(953)

37(940)

21-1/2(546)

8-7/8(225)

10-7/8(276)

14-1/2(368)

2-1/4(57)

33-1/4(845)

15-3/4(401)

2-7/8(73)

36-1/4(921)

37(940)

5(124)

12 9 x 6 37-1/2(953)

37(940)

21-1/2(546)

8-7/8(225)

10-7/8(276)

14-1/2(368)

2-1/4(57)

33-1/4(845)

15-3/4(401)

2-7/8(73)

36-1/4(921)

37(940)

5(124)

16 10 x 7 37-3/4(959)

47(1194)

21-1/2(546)

10-3/8(264)

12(305)

18-3/8(467)

2-1/4(57)

43-7/8(1115)

15-3/4(401)

2-7/8(73)

46-1/4(1175)

37(940)

1-1/4(32)

20/22 11 x 10 40-1/4(1022)

48(1219)

24 (610)

13-7/8(352)

13(330)

17-1/4(438)

2-1/4(57)

44-1/4(1124)

18(457)

2-7/8(73)

47-1/4(1200)

39-1/2(1033)

2-3/8(60)

30 12 x 12 40-1/4(1022)

48(1219)

32-1/4(819)

16-1/4(413)

14(356)

16(406)

7-1/8 (181)

44-1/4(1124)

26-1/2(673)

1-1/4(32)

47-1/4(1200)

39-1/2(1033)

3-3/4(95)

NOTES:1. RH shown, LH opposite. 2. All dimensions are +/- 1/4" (6 mm). 3. Product specifi cations are subject to changes without notice. 4. Dimensions in parenthesis are shown in (millimeters). 5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area. 6. “C” dimension is measured from coil side of unit. 7. Mixing Box option will vary return duct dimensions, refer to mixing box submittal.

Drawing is not to scale and is provided for reference only.Dimensions may vary with options ordered.

Consult IEC website for up-to-date drawings.

Page 30: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

30030303330333033333333333330

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

HDY Unit with Optional Mixing Box

Drawing is not to scale and is provided for reference only.Dimensions may vary with options ordered.

Consult IEC website for up-to-date drawings.

SizeFan Size

DepthUnit

DepthWidth Height

Supply Duct Return Duct (Note 7) Mix BoxMounting

HolesAux.Box

A B C D E F G H J K L

06 9 x 6 51-5/8(1311)

36(914)

28(711)

22-3/4 (578)

8-7/8(225)

10-7/8(276)

13-3/4(349)

2-1/4(57)

24(610)

6(152)

12-1/2(318)

11(279)

27-1/4(686)

35-1/4(895)

5-3/4(146)

08 9 x 6 51-5/8(1311)

36(914)

28(711)

22-3/4 (578)

8-7/8(225)

10-7/8(276)

13-3/4(349)

2-1/4(57)

24(610)

6(152)

12-1/2(318)

11(279)

27-1/4(686)

35-1/4(895)

5-3/4(146)

10 9 x 6 55-1/8(1400)

37-1/2(953)

37(940)

24-1/2(622)

8-7/8(225)

10-7/8(276)

14-1/2(368)

2-1/4(57)

33(838)

8(203)

14-1/4(362)

13(330)

36-1/4(921)

37(940)

5(124)

12 9 x 6 55-1/8(1400)

37-1/2(953)

37(940)

24-1/2(622)

8-7/8(225)

10-7/8(276)

14-1/2(368)

2-1/4(57)

33(838)

8(203)

14-1/4(362)

13(330)

36-1/4(921)

37(940)

5(124)

16 10 x 7 55-3/8(1407)

37-3/4(959)

47(1194)

24-1/2(622)

10-3/8(264)

12(305)

18-3/8(467)

2-1/4(57)

43(1092)

8(203)

14-1/4(362)

13(330)

46-1/4(1175)

37(940)

1-1/4(32)

20/22 11 x 10 57-3/4(1467)

40-1/4(1022)

48(1219)

27(686)

13-7/8(352)

13(330)

17-1/4(438)

2-1/4(57)

44(1118)

8(203)

16-3/4(425)

13(330)

47-1/4(1200)

39-1/2(1033)

2-3/8(60)

30 12 x 12 59-3/4(1518)

40-1/4(1022)

48(1219)

35-1/4(895)

16-1/4(413)

14(356)

16(406)

7-1/8 (181)

44(1118)

10(254)

15(381)

15(381)

47-1/4(1200)

39-1/2(1033)

3-3/4(95)

NOTES:1.RH shown, LH opposite. 10. Add 2”(51) if using a Prefi lter, or 4”(102) fi lter. 2. All dimensions are +/- 1/4” (6 mm). 3. Product specifi cations are subject to changes without notice. 4. Dimensions in parenthesis are shown in (millimeters). 5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area. 6. “C” dimension is measured from coil side of unit. 7. Mixing Box option will vary return duct dimensions, refer to mixing box submittal. 8. Mixing Box options include: a) Knockdown base rails for fi eld assembly; b) Pre-assembled Mixing Box. 9. Linkage kit supplied with Mixing Box is provided for fi eld installation of actuator.

Page 31: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

31

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Piping Connection Location (Centerline to Centerline) – Hydronic Cooling and Heating Coils

Coil Header Connection Size

Unit

Size

8 Row 6 Row 4 Row 2 Row HW 1 Row HW

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

06-12 1 1.125 3/4 0.875 3/4 0.875 1/2 0.625 1/2 0.62516-22 1 1.125 1 1.125 1 1.125 1 1.125 1/2 0.625

30 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625

Horizontal, left hand unit with re-heat coil shown.

Unit SizeCoil Rows

A B C D E F GCool Heat

06/08

4– –

6-1/8 12-3/4

– – –5-15/161 3-1/2 15-1/2 7 7

2 3-13/16 15-13/16 7-9/16 7-9/16

6– – – – –

8-1/81 3-1/2 15-1/2 9-3/16 9-3/162 3-13/16 15-13/16 9-3/4 9-3/4

8 – – – – – 10-1/4

10/12

4– –

7-3/4 14-3/8

– – –5-15/161 5-1/8 17-1/8 7 7

2 5-7/16 17-7/16 7-9/16 7-9/16

6– – – – –

8-1/81 5-1/8 17-1/8 9-3/16 9-3/162 5-27/61 17-7/16 9-3/4 9-3/4

8 – – – – – 10-1/4

16

4

– – 7-3/415-5/8

– – –

5-15/161LH 10-5/8

7-3/4 129-5/8 7

RH 13-3/8 9-5/8 72 12 7 16-3/8 13-5/8 10-3/8 7-9/16

6

– – 7-3/415-5/8

– – –

8-1/81LH 10-5/8

7-3/4 1211-13/16 9-3/16

RH 13-3/8 11-13/16 9-3/162 12 7 16-3/8 13-5/8 12-1/2 9-3/4

8 – – 9-1/2 15-5/8 – – – 10-1/4

20/22

4

– – 7-13/16

18-3/16

– – –5-15/16

1LH 11-15/16

7-13/16 13-5/16 9-5/87RH 14-11/16

2 11-9/16 7-7/8 15-13/16 9-1/16 5

6

– – 7-13/16 – – –8-1/8

1LH 11-15/16

7-13/16 13-5/16 11-13/169-3/16RH 14-11/16

2 11-9/16 7-7/8 15-13/16 11-1/4 7-1/88 – – 7-13/16 – – – 10-1/4

30

4– –

5-15/16 26-5/16

– – – 5-15/161 7-1/16 25-13/16 9

7 4-7/82 10-5/16 23-13/16 9-1/8

6– – – – – 8-1/81 7-1/16 25-13/16 11-1/8

9-1/8 7-1/162 10-5/16 23-13/16 11-5/16

8 – – – – – 10-1/4

CR - Cold Water ReturnHR - Hot Water ReturnCS - Cold Water SupplyHS - Hot Water SupplyRH - Right HandLH - Left Hand

0

0

2(51)

B

C6-7/8(17

5)

8-5/8(21

9) E

D

1-5/8(41)

A

2-11

/16(68

) G F10

-3/8(264

)

Page 32: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

32232323332333233333333333332

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Piping Connection Location (Centerline to Centerline) – R-410A Cooling with Hot Water Heating

Horizontal, left hand unit with pre-heat coil shown.

Coil Header Connection Size (Nominal OD in Inches)

Unit

Size

LL SL 2 Row HW 1 Row HW

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

Nom.

Size

Actual

OD

06-12 1/4 0.375 3/4 0.875 1/2 0.625 1/2 0.62516-22 1/4 0.375 1 1.125 1 1.125 1/2 0.625

30 1/2 0.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625

SIZE

COIL ROWS

A B C D E F G HDX ONLY

WATER

PRE-HEAT

06/08

4 –

4-3/4 5-1/2

– –

12-1/2

2-3/4 – – 6 4

1 6 18

3-3/4 2-5/8 2-5/8 6 4

2 4-7/8 3-1/4 3-1/4 6

10/12

4 –

6-1/2 7-1/8

– –

12-1/2

2-3/4 – – 6 4

1 5-1/8 17-1/8

3-3/4 2-5/8 2-5/8 6 4

2 4-7/8 3-1/4 3-1/4 6

16

4 –

6-1/2 7-1/8

– –

12-1/2

2-3/4 – – 6 4

1 5-1/8 17-1/8 3-3/4 2-5/8 2-5/8 6 4

2 6-3/8 10 13-5/8 6-6/8 4-1/8 2-5/8 6

20/22

4 –

6-1/2 7-1/8 – –

12-1/2

2-3/4 – – 6 4

1 5-1/4 19-3/4 3-3/4 2-5/8 2-5/8 6 4

2 6-3/4 7-1/4 11-5/8 15-7/8 6-3/4 4-1/4 2-5/8 6

30

4 – 4-5/8 5-3/8 – –

12-1/2

2-3/4 – – 6 4

1 4-7/8

6 12-1/8 25-7/8 6-1/8 4-1/2 2-5/8

6 4

2 5-3/8 10-3/8 23-7/8 6-3/8 6

HR - Hot Water ReturnHS - Hot Water SupplyLL - Liquid LineSL - Suction Line

0

0

2(51)

B

D

7/8(17

5)

5/8(21

9)

A

GH E

1-5/8(41)

FC

Page 33: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

33

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Distributed Weight CalculationsThe following operating weight information is based on 8-row water-fi lled coils and double wall cabinet construction. For a diff erent coil and cabinet options, use the weight correction factor table.

Horizontal Units (Top View)

HDY UnitNo Electric Heat (lb.) With Electric Heat (lb.)

A B C D Total A B C D Total

06 42 46 36 47 171 42 58 36 66 20208 41 47 38 45 171 41 58 36 67 20210 51 53 49 63 217 51 60 56 83 25012 50 52 51 64 217 50 58 57 85 25016 65 70 64 75 274 70 69 66 104 30920 78 90 77 95 340 81 96 77 107 37822 83 105 80 99 367 86 111 81 111 38930 103 113 97 117 430 104 120 96 149 469

Total Weight Unit Correction Factor (lb.) – HDY

These weights are for 8-row water-fi lled coils and double wall construction. For a diff erent number of rows, total unit weight can be determined by:

Total unit weight can be adjusted by :

a. Identify the size of unit and number of rows b. From the previous table, identify the total weight of the unit c. From the table below, identify the correction factor and deduct this factor from the total weight.

Options 6 8 10 12 16 20 22 30

4-Row Coil -21 -21 -28 -28 -39 -46 -46 -98

5-Row Coil -16 -16 -21 -21 -29 -35 -35 -74

6-Row Coil -11 -11 -14 -14 -20 -23 -23 -49

7-Row Coil -5 -5 -7 -7 -10 -12 -12 -25

Single Wall Construction -31 -31 -40 -40 -47 -58 -58 -67

NOTE: 1. Unit weights (shown in pounds), +/- 10 percent, are based on the largest water-fi lled coil.

Page 34: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

34434343334333433333333333334

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

The standard Direct Drive Blower Coils are furnished with a set of 2” pleated MERV 8 fi lters.

Unit SizeFilter

Quantity

Nominal Filter Sizes –Inches (Millimeters)

HDY

06 1 16-1/2" x 24" (419 x 610)

08 1 16-1/2" x 24" (419 x 610)

10 1 18-1/4" x 33" (464 x 838)

12 1 18-1/4" x 33" (464 x 838)

16 2 18-1/4" x 21-1/2" (464 x 546)

20/22 2 20-1/2 x 22" (521 x 559)

30 2 29" x 22" (737 x 559)

• Side and bottom fi lter removal• No tools needed for easy fi lter change, usage of

strong magnets in place of hardware• Choice of 1”, 2” or 4” fi lters• Easy to modify in the fi eld for either 1”, 2” or 4” fi lters• Robust design eliminates unit’s sagging

1” Filter

2” Filter

4” Filter

Magnet

See Detail X

Detail X

Filters

Page 35: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

35

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Controls:

Motor Controls – Units without electric heat:

Two controls schemes are available:

• 3 - Speed adjustable.

• Proportional (0 - 10 VDC).

Electric Heat Controls

Electric heaters come standard with a transformer, heater contactors, motor and electric heat fusing, and a terminal strip.

An optional interlocking disconnect switch is available.

Control Box

Condensate Float Switch

A water-level sensing device designed to prevent drain pan overfl ow. The standard switch is wired normally closed. Switches are available only in 24 V.

Cabinet/Control Box Maintenance Light

Optional LED Service Light provides a source of illumination in the main unit cabinet and the control box during routine maintenance and troubleshooting in the dark ceiling spaces.

Above picture is the example of Control box with electric heat, disconnect switch and service light.

Factory Installed Options

Page 36: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

36636363336333633333333333336

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Mixing BoxesMixing boxes can be used when outside air is required. Mixing boxes come with base rails. Refer to the drawings on pages 36

and 37 for additional information.

Mixing Box with Base RailsMixing box option includes : 1.) knockdown base rails for fi eld assembly, and 2.) pre-assembled mixing box. Base rails are letter coded for ease of assembly and all hardware required for assembly is included. Linkage kit consists of 2 crank arms, 2 swivels, and either a 25" (sizes 06-16) or a 34" (sizes 20-30) length of 5/16" rod provided for fi eld installation of actuator. Consult factory for the 24 V damper actuator option. Mixing box option adds 3" to the unit height due to the base rails.

Horizontal Units – Dimensions - Inches (Millimeters)

Unit Type and Size W D A

HDY06 28 (711) 51.6 (1311) 16.1 (409)HDY08 28 (711) 51.6 (1311) 16.1 (409)HDY10 37 (940) 55.2 (1402) 18.1 (460)HDY12 37 (940) 55.2 (1402) 18.1 (460)HDY16 47 (1194) 55.4 (1407) 18.1 (460)

HDY20/22 48 (1219) 57.8 (1468) 18.1 (460)HDY30 48 (1219) 59.8 (1519) 20.1 (511)

1(25)W

FRONT VIEW

D

3(76)

A1(25)

SIDE VIEW

Base Rail Details

Page 37: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

37

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Mixing Box Details

3(76)

A

C

2.4(61)

4(102)

H

2.4(61)

3(76)

1(25)

2(51)2(51)

WB

TOP VIEWS

BTM/REAR INLET - HDY TOP/REAR INLET - HDY

RIGHT HAND SIDE VIEWS

W

4(102)

2.4(61)

C

1(25)

H

A

A

B

A

2.4(61)

Note: Add 2” (51) to total unit length if using 2” prefilter or 4” filter with mixing box option.

Dimensions - Inches (Millimeters)

Unit Size H W A B C

06 18.5 (470) 28 (711) 6 (152) 24 (610) 11 (279)08 18.5 (470) 28 (711) 6 (152) 24 (610) 11 (279)10 20.25 (514) 37 (940) 8 (203) 33 (838) 13 (330)12 20.25 (514) 37 (940) 8 (203) 33 (838) 13 (330)16 20.25 (514) 47 (1194) 8 (203) 43 (1092) 13 (330)

20/22 22.75 (578) 48 (1219) 8 (203) 44 (1118) 13 (330)30 31 (787) 48 (1219) 10 (254) 44 (1118) 15 (381)

Page 38: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Horizontal Direct Drive Blower Coils

38838383338333833333333333338

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Page 39: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

39

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG

Page 40: Energy Efficient • Easy to Install • Extended Service Life ·  · 2018-01-19Efficient • Easy to Install • Extended ... form the basis of any bargain between the parties but

Contact your local IEC Sales Representative for further details and pricing applicable to this product. Visit our website (iec-okc.com) to fi nd your local IEC Sales Rep.

IEC Catalog Part #: I100-900030973

CA-090(1/2018)

©2018 International Environmental Corporation (IEC)

PO Box 2598Oklahoma City, OK 73101-2598P: 405.605.5000F: 405.605.5001www.iec-okc.com

Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG