• Energy Efficient • Easy to Install• Extended Service Life
• Energy effi cient compact blower coils• Ideal for educational, hospitality, multi-family, or other commercial environments • Designed for ducted applications • Nominal CFM range of 600 to 3,000 CFM
BUILD YOUR REPUTATION ON OURS
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Horizontal Direct Drive Blower Coils
222222
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
International Environmental Corporation (IEC) works continually to improve its products. As a result, the design and specif ications of each product may be changed without notice and may not be as described herein. Please contact IEC for information regarding current design and product specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely IEC’s opinion or commendation of its products. Manufacturer’s standard limited warranty applies.
2 Table of Contents
3 Portfolio
4-5 Features and Benefi ts
6-7 Unit Nomenclature
8 Nominal Capacity and Listing
9-16 Cooling Capacity Tables
17-20 Heating Capacity Tables
21 Electric Resistance Heating
22 Motor Data
23 Component Static Resistance
24 Sound Power Data
25-28 Fan Curves
29-30 Physical Data
31-32 Piping Stub-Out Location
33 Distributed Weight Calculations
34 Filters
35 Factory-Installed Options
36-37 Options - Mixing Box
Table of content
3
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Horizontal Direct Drive Units
600 to 3000 CFM
Versatile Units
These compact blower coils are ideally suited for a variety of ducted applications that require a range of 600 to 3000 CFM, capacities between 1.5 tons to 10 tons, and generally rated for applications with 1” w.g. or less of external static pressure, but can be operated at higher ESP - contact factory for additional information. These units provide comfort cooling and heating while off ering a broad range of application fl exibility between the traditional fan coil unit and a central station air handling unit. Several confi gurations are available to meet the needs of diff erent climates and applications. The HDY units can be ordered as a:
• 2-pipe system
• 2-pipe system with electric heat
• 4-pipe system
• Direct expansion system cooling
• Direct expansion cooling with electric heat
• Direct expansion cooling with hot water heating
Multitude of Applications
These units are ceiling mounted, and available with a variety of options that can meet the design requirements, and provide a low cost solution for a multitude of applications.
TOOL-FREE REMOVAL OF ACCESS PANELS
PRIMARY AND SECONDARY DRAIN CONNECTION FROM DOUBLE-SLOPED STAINLESS STEEL DRAIN PAN
IMPROVED FILTER RACK DESIGN, ACCEPTS 1”, 2”, OR 4” FILTERS, TOOL-FREE FILTER ACCESS FROM BOTTOM AND TWO SIDES
DOUBLE SLOPED STAINLESS STEEL DRAIN PAN
ISOLATED BLOWER FOR QUIET OPERATION
STANDARD EC MOTOR
OPTIONAL DOUBLE WALL CONSTRUCTION
Horizontal Direct Drive Blower Coils
4444444
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Operating Limitations
Fan curves defi ne the recommended airfl ow and static pressure ranges of operations. Running the HDY units outside this range could lead to drastically reduced bearing life and premature wheel failure. In cooling applications, this could also result in moisture carry over. In addition, running the fan at its maximum fan speed will increase the power requirements and generate higher sound levels.
On units with electric heat, the minimum airfl ow shown on the fan curve must be maintained to prevent excessive discharge temperature and electric heat safety trips.
Standard Horizontal Direct Drive Blower Coil
Applications
Where the application calls for cooling capacities or external static pressures that can not be met with standard or high performance direct drive fan coil units; use an IEC horizontal direct drive blower coil.
Outside Air Applications
With the availability of larger capacities, a variety of optional coils, mixing boxes, and the capability of delivering air through long duct runs, the direct drive units are ideal for handling outside air. When used as outside air units, the heating coil should be in the pre-heat location (consult factory).
Large Public Areas
These units are ideal for applications with a large common area such as restaurants, airports, sports arenas, stadiums, private boxes, gymnasiums, exercise areas, locker rooms, atriums and foyers, auditoriums, shopping malls, equipment or mechanical rooms, and casinos, to name a few.
Installation Considerations
The HDY units are typically suspended above the ceiling. Attention should be paid to having enough clearance around the units for service and maintenance. Horizontal units are generally suspended above the ceiling using hanger rods that go through the corner knock-outs provided in the units. External vibration isolation and fl ex connections for ducts are recommended.
Acoustical Considerations
With sound becoming more of a concern to design engineers, building owners, and occupants, proper consideration should be given to the selection and placement of these units. Whenever possible, avoid placing these units above an occupied space. To further reduce the sound level, additional measures such as: using fl exible duct connectors; lining the main supply and return ducts with acoustical absorption material; locating the return air grilles as far away from the unit as possible; and using 3-phase motors.
5
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Application Fit
• Horizontal confi guration, with 8 diff erent sizes to meet a multitude of room layouts and ventilation needs
• Wide variety of coil options including 100% outside air applications
Design Flexibility
• Optional 1” double wall construction, perforated or solid lined
• Removable double-sloped stainless steel drain pan for ease of cleaning and better IAQ performance; all models include primary and secondary drain connections to provide back-up if the main drain is plugged
• Wide variety of coil sizes (4, 6, 8-rows) for a better match to the heating and cooling loads of the space; coils with diff erent materials (copper fi ns with stainless steel end sheets and bottom coil baffl es)
• Standard EC Motors ranging from 1/2 to 3 HP in a variety of voltages, in both single- and 3-phase
• A standard fi lter rack allows for 1”, 2” or 4” of fi ltration up to MERV 13
• Variety of insulation materials to comply with IAQ concerns
• Heating provided by a hot water coil or electric heat for varying application needs and climates
• Mixing boxes available for outside air applications
• User-friendly Ratings program expedites the project design and equipment selection
Ease of Installation
• Units are pre-assembled with factory installed optional electric heater controls
• 24 V control eliminates the need to run control wiring in conduit
• Corner knock-outs for hanger rods and isolators facilitate quick and easy installation
• Duct collars for supply and return air
• Optional factory installed controls eliminate the need for motor starters
Ease of Service
• Tool-free and easily accessible fi lters from multiple sides
• Large, tool-free access panels on both sides
• Optional lighting available in cabinet and control box; provides a well lit space to perform service or routine maintenance
Quality and Safety
• Every unit tested and inspected at the factory for trouble-free startup
• Optional condensate fl oat switch satisfi es the latest building codes constraints
• Motors have built-in thermal overload protection
• ETL and CETL listed
Horizontal Direct Drive Blower Coils
666666
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
UNIT SIZE
06 600 CFM 08 800 CFM 10 1000 CFM 12 1200 CFM16 1600 CFM
20 2000 CFM 22 2200 CFM 30 3000 CFM
CABINET OPTIONSDrain Pan
AS Double Slope Stainless Steel
Filter OptionsA 1” throwawayC 2 sets of 1” throwaway
F 1” Pleated MERV 8G 2” Pleated MERV 8
M 2” MERV 11 with 2” pleated pre-fi lter U 4” MERV 11 (not available w/mixing box)W 4” MERV 13 (not available w/mixing box)
Insulation C 1” Closed CellW 1” Standard Fiberglass
S 1” Premium IAQ Fiberglass (Edges Sealed)G 1”Foil Face (Edges Sealed)
C, S & G not allowable w/ Double-Wall
Mixing box
N Rear & Top/Bottom Return comes Standard with Single-blade Dampers
Walls Construction
Y Single-Wall (Standard) A Double-Wall Construction (Solid Liner) B DW Constr. (Perforated)
Other Cabinet Options
A Cabinet/Control Box Service Light
COIL
Rows
BY 4 KY 6 LY 8 B6 4/1 B7 4/2 K6 6/1 K 6/2 QY 4 row DX 410A FY 6 Row DX 410A 6Q 1 row heating (pre-heat position) and 4 row DX 410A 6F 1 row heating (pre-heat position) 6 row DX 410A 7Q 2 row heating (pre-heat position) 4 row DX 410A 7F 2 row heating (pre-heat position) 6 row DX 410A. On size 16 and above with 1 row heat coil is 2 circuit, below size 16 coil has 1 circuit
Total rows allowed is 8.
Hand R Right-hand Coil Connections L Left-hand Coil Connections
Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections
Material (Tube/Fin/Coatings) Y Aluminum Fins w/ Galvanized Wrap S Aluminum Fins w/ Stainless Steel Wrap C Copper Fins Stainless Steel Wrap
Accessories - Vents/Drains
Y MAV(Std) A AAV(2-Pipe) B AAV(4-Pipe) C MAV w/ Drain (2-Pipe) D MAV w/ Drain (4-Pipe) E AAV w/ Drain (2-Pipe) F AAV w/ Drain (4-Pipe)
Accessories - TXV T TXV Valve (DX Only) Y None
UNIT NOMENCLATURE
7
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
EC MOTOR
Motor-Voltage/Phase/Hertz
C 115/1/50-60D 208/1/50-60
E 230/1/50-60F 277/1/50-60V 220/1/50
N 208/3/50-60P 230/3/50-60
G 460/3/50-60
Horsepower
C 1/2 HP E 1 HP F 1.5 HP (Three Phase only)H 3 HP (Three Phase only)
Motor Type
M EC Motor, no board (0 -10 VDC) N EC Motor, POT board, 3 discrete speeds
ELECTRIC HEATHeater Voltage
Y None F 277/1/60C 120/1/60 N 208/3/60
D 208/1/60 P 240/3/60 E 240/1/60 G 460/3/60
Heater Kilowatt
Y NoneBY 1.0 HY 5 NH 15CY 1.5 JY 6 NJ 16DY 2 KY 7 NL 18EY 2.5 LY 8 RY 19.9FY 3 NY 9.9 RH 25FA 3.5 PY 12 SY 30GY 4 QY 14 SH 35GA 4.5Note: Voltage rules required , motor & heater voltage must match. Dual power source is not available.
Heater Stages
Y NoneA 1-Stage, Single-Phase (1-12 kW)
B 2-Stage, Single-Phase (3-12 kW) C 1-Stage, 3-Phase (1-35 kW) D 2-Stage, 3-Phase (4-35 kW) E 3-Stage, 3-Phase (12-35 kW)
Rules apply for stages
CONTROLS
Applications
BA1Y BP1K
BA3Y BP1H
BA1J BP1L
BA3J BP3K
BP1R BP3H
BP3R BP3L
1st Digit is Control Voltage (B=24 volt); 2nd Digit is Type of Control (A=Motor Controls;P=Electric Heat & Motor Controls);Third Digit is Phase (1=Single Phase;3=3 Phase);4th Digit is Fusing and Disconnect (Y=No Fusing or Discon-nect; J=40 amp Disconnect and Appropriate Motor Fusing; R=Appropriate Motor and Heater Fusing; K=R plus 40 amp disconnect; H=R plus 60 amp disconnect; L=R plus 80 amp disconnect (All electric heat includes thermal limit switch)
Special Controls
O Condensate Overfl ow Switch
Low Voltage Package
V 3-Speed Adjustable (Default)W Proportional (requires 0-10 VDC
controller)
Horizontal Direct Drive Blower Coils
888888
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
C-ETL-US Listing IEC’s Direct Drive Series blower coil units are listed by Intertek Testing Services (ITS). ITS’s C-ETL-US listing signifi es that IEC’s blower coil units have been examined by ITS and comply with the minimum requirements of U.S. and Canadian national product safety standard, UL 1995/CSA C22.2 No. 236, and that IEC’s manufacturing site has been audited. ITS’s re-examination service includes periodic visits to IEC’s factory to ensure continued compliance for all listed products.
Nominal Capacity Range
Model Unit Size Coil Rows Nominal CFM
Water Pressure
Drop
(ft.water)
Cooling Capacity1 (BTUH)Power Input
(Watts)Total Sensible
HDY
06 4 600 1.8 19,900 13,800 85
06 6 600 3.8 25,000 16,000 120
06 8 600 4.8 26,000 16,000 120
08 4 800 2.9 24,900 17,800 160
08 6 800 5.5 31,000 20,100 175
08 8 800 8.4 34,800 21,200 205
10 4 1,000 5.7 33,700 23,200 220
10 6 1,000 10.7 40,500 25,900 240
10 8 1,000 15.9 45,100 27,500 260
12 4 1,200 7.2 38,400 26,800 335
12 6 1,200 14.7 47,600 30,700 350
12 8 1,200 20.5 52,000 31,800 380
16 4 1,600 4.7 49,000 35,300 410
16 6 1,600 10.0 61,500 39,700 420
16 8 1,600 14.2 67,100 41,400 520
20 4 2,000 5.5 62,100 45,000 445
20 6 2,000 11.2 78,000 51,300 465
20 8 2,000 17.0 87,400 55,400 510
22 4 2,200 8.0 65,000 47,200 575
22 6 2,200 15.0 83,800 54,900 600
22 8 2,200 23.0 95,500 59,000 660
30 4 3,000 6.1 98,500 71,100 790
30 6 3,000 10.7 123,900 80,400 860
30 8 3,000 18.4 140,000 88,500 890
NOTES: 1. Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, 45°F (7.2°C) EWT , 10°F Δ(5.6°C Δ) water temperature rise , high fan speed , motor voltage 115/1/60, and airfl ow under dry coil conditions.
2. For all application ratings, use IEC’s computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative.
3. For additional information, please consult AHRI’s website at www.ahrinet.org.
AHRI Certifi cationIEC’s Horizontal Direct Drive Blower Coil units are certifi ed in compliance with Air-Conditioning, Heating, and Refrigeration Institute (AHRI) industry standard AHRI-440 for room fan coil units. Approved standard ratings are tabulated below.
3061627HEATING AND COOLING EQUIPMENT
9
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
06(1/2) HP
500
480 / 67 45
10 16.9 12.4 3.4 1.612 14.9 11.5 2.5 1.8
75 / 63 4510 12.5 10.6 2.5 1.012 11.1 10.0 1.8 0.6
680 / 67 45
10 20.9 14.2 4.1 3.312 19.0 13.4 3.2 3.6
75 / 63 4510 15.3 11.9 3.0 2.012 14.0 11.4 2.3 1.3
880 / 67 45
10 22.9 15.1 4.5 5.112 21.1 14.3 3.5 3.3
75 / 63 4510 16.7 12.6 3.3 3.112 15.5 12.0 2.6 2.1
600
480 / 67 45
10 19.5 14.5 3.9 1.912 17.4 13.7 2.9 1.2
75 / 63 4510 14.6 12.5 2.9 1.212 13.1 11.9 2.2 0.8
680 / 67 45
10 24.5 16.8 4.9 4.212 22.4 16.0 3.7 2.8
75 / 63 4510 18.1 14.2 3.6 2.612 16.7 13.6 2.8 1.7
880 / 67 45
10 27.1 18.0 5.4 6.612 25.1 17.2 4.2 4.4
75 / 63 4510 20.0 15.1 4.0 4.112 18.6 14.5 3.1 2.7
700
480 / 67 45
10 21.9 16.5 4.3 2.312 19.7 15.7 3.3 1.5
75 / 63 4510 16.6 14.3 3.3 1.512 15.1 13.7 2.5 1.0
680 / 67 45
10 27.9 19.3 5.5 5.212 25.6 18.4 4.2 3.4
75 / 63 4510 20.8 16.4 4.1 3.312 19.2 15.8 3.2 2.2
880 / 67 45
10 31.2 20.9 6.2 8.312 29.1 20.0 4.8 5.5
75 / 63 4510 23.2 17.6 4.6 5.212 21.7 16.9 3.6 3.5
Cooling Capacity
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
Horizontal Direct Drive Blower Coils
1001010110110111111110
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
08(1 HP)
700
480 / 67 45
10 21.9 16.5 4.3 2.312 19.7 15.7 3.3 1.5
75 / 63 4510 16.6 14.3 3.3 1.512 15.1 13.7 2.5 1.0
680 / 67 45
10 27.9 19.3 5.5 5.212 25.6 18.4 4.2 3.4
75 / 63 4510 20.8 16.4 4.1 3.312 19.2 15.8 3.2 2.2
880 / 67 45
10 31.2 20.9 6.2 8.312 29.1 20.0 4.8 5.5
75 / 63 4510 23.2 17.6 4.6 5.212 21.7 16.9 3.6 3.5
800
480 / 67 45
10 24.2 18.5 4.8 2.712 21.9 17.6 3.6 1.7
75 / 63 4510 18.5 16.2 3.7 1.812 16.9 15.5 2.8 1.2
680 / 67 45
10 31.1 21.8 6.2 6.112 28.8 20.8 4.8 4.1
75 / 63 4510 23.4 18.7 4.6 3.912 21.8 18.0 3.6 2.6
880 / 67 45
10 35.2 23.7 7.0 10.012 33.0 22.7 5.5 6.7
75 / 63 4510 26.3 20.1 5.2 6.312 24.7 19.3 4.1 4.3
900
480 / 67 45
10 26.4 20.4 5.2 3.112 23.9 19.5 4.0 2.0
75 / 63 4510 20.4 17.9 4.0 2.112 18.6 17.2 3.1 1.4
680 / 67 45
10 34.2 24.2 6.8 7.112 31.7 23.2 5.2 4.7
75 / 63 4510 25.9 20.8 5.1 4.612 24.2 20.1 4.0 3.1
880 / 67 45
10 39.2 26.5 7.8 11.812 36.7 25.4 6.1 8.0
75 / 63 4510 29.4 22.5 5.8 7.512 27.6 21.7 4.6 5.1
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
11
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
10(1/2 HP)
900
480 / 67 45
10 33.9 23.6 6.0 4.812 30.3 21.7 5.6 6.6
75 / 63 4510 22.6 18.6 4.5 3.112 20.8 17.9 3.4 2.0
680 / 67 45
10 36.5 24.8 7.2 9.912 33.9 23.6 5.6 6.6
75 / 63 4510 27.0 20.9 5.4 6.112 25.2 20.1 4.2 4.1
880 / 67 45
10 38.6 25.7 7.7 14.412 35.9 24.6 5.9 9.6
75 / 63 4510 28.3 21.5 5.6 8.812 26.6 20.8 4.4 6.0
1000
480 / 67 45
10 32.7 23.8 6.5 5.512 30.0 22.7 5.0 3.6
75 / 63 4510 24.7 20.4 4.9 3.512 22.8 19.7 3.8 2.3
680 / 67 45
10 39.4 27.2 7.9 11.412 37.1 26.1 6.1 7.6
75 / 63 4510 29.6 23.0 5.9 7.112 27.8 22.2 4.6 4.8
880 / 67 45
10 42.6 28.4 8.4 16.812 39.7 27.2 6.6 11.3
75 / 63 4510 31.4 23.9 6.2 10.412 29.5 23.1 4.9 7.1
1100
480 / 67 45
10 35.2 25.8 7.0 6.212 32.4 24.7 5.4 4.0
75 / 63 4510 26.7 22.3 5.3 4.012 24.7 21.5 4.1 2.6
680 / 67 45
10 43.4 29.7 8.6 12.912 40.3 28.4 6.7 8.6
75 / 63 4510 32.4 25.2 6.4 8.212 30.4 24.4 5.0 5.5
880 / 67 45
10 46.5 31.2 9.2 19.312 43.3 29.8 7.2 12.9
75 / 63 4510 34.4 26.2 6.8 12.012 32.5 25.4 5.4 8.2
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
Horizontal Direct Drive Blower Coils
1221212112112111111112
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
12(1 HP)
1100
480 / 67 45
10 35.2 25.8 7.0 6.212 32.4 24.7 5.4 4.0
75 / 63 4510 26.7 22.3 5.3 4.012 24.7 21.5 4.1 2.6
680 / 67 45
10 43.4 29.7 8.6 12.912 40.3 28.4 6.7 8.6
75 / 63 4510 32.4 25.2 6.4 8.212 30.4 24.4 5.0 5.5
880 / 67 45
10 46.5 31.2 9.2 19.312 43.3 29.8 7.2 12.9
75 / 63 4510 34.4 26.2 6.8 12.012 32.5 25.4 5.4 8.2
1200
480 / 67 45
10 37.7 27.8 7.5 6.812 34.7 26.6 5.7 4.5
75 / 63 4510 28.7 24.1 5.7 4.512 26.7 23.3 4.4 3.0
680 / 67 45
10 46.6 32.1 9.2 14.412 43.4 30.8 7.2 9.7
75 / 63 4510 35.0 27.4 6.9 9.212 32.8 26.5 5.4 6.2
880 / 67 45
10 50.3 33.9 10.0 21.812 47.1 32.5 7.8 14.7
75 / 63 4510 37.5 28.6 7.4 13.812 35.4 27.7 5.8 9.4
1300
480 / 67 45
10 39.9 29.7 7.9 7.512 37.0 28.6 6.1 5.0
75 / 63 4510 30.6 25.9 6.1 4.912 28.5 25.0 4.7 3.3
680 / 67 45
10 49.9 34.5 9.9 16.112 46.6 33.2 7.7 10.8
75 / 63 4510 37.5 29.5 7.4 10.312 35.4 28.6 5.8 7.0
880 / 67 45
10 54.0 36.5 10.7 24.412 50.8 35.1 8.4 16.6
75 / 63 4510 40.4 30.9 8.0 15.512 38.2 30.0 6.3 10.6
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
13
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
16(1 HP)
1400
480 / 67 45
10 42.2 31.9 8.4 3.512 38.4 30.4 6.4 2.3
75 / 63 4510 32.1 27.7 6.4 2.312 29.4 26.6 4.9 1.5
680 / 67 45
10 50.5 35.8 10.0 7.012 46.9 34.3 7.8 4.7
75 / 63 4510 37.9 30.6 7.5 4.512 35.4 29.6 5.9 3.0
880 / 67 45
10 54.3 37.4 10.8 10.512 50.3 35.7 8.3 7.0
75 / 63 4510 40.3 31.7 7.99 6.612 37.8 30.6 6.3 4.5
1600
480 / 67 45
10 46.7 35.8 9.3 4.112 42.9 34.3 7.1 2.7
75 / 63 4510 36.0 31.3 7.1 2.712 33.2 30.2 5.5 1.8
680 / 67 45
10 56.8 40.6 11.3 8.412 52.7 38.9 8.7 5.6
75 / 63 4510 42.9 34.9 8.5 5.412 40.3 33.8 6.7 3.7
880 / 67 45
10 61.6 42.6 12.2 12.912 57.5 40.9 9.5 8.6
75 / 63 4510 46.0 36.3 9.1 8.112 43.3 356.1 7.2 5.5
1800
480 / 67 45
10 51.2 39.7 10.2 4.712 47.4 38.2 7.8 3.1
75 / 63 4510 39.8 34.9 7.9 3.212 36.8 33.7 6.1 2.1
680 / 67 45
10 62.7 45.2 12.4 9.812 58.5 43.5 9.7 6.6
75 / 63 4510 47.6 39.0 9.5 6.412 44.9 37.9 7.4 4.4
880 / 67 45
10 68.5 47.7 13.6 15.212 64.1 45.9 10.6 10.2
75 / 63 4510 51.5 40.8 10.2 9.712 48.8 39.7 8.1 6.7
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
Horizontal Direct Drive Blower Coils
1441414114111111111414
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
20(1 HP)
1800
480 / 67 45
10 57.3 42.6 11.4 4.512 52.6 40.8 8.7 2.9
75 / 63 4510 43.8 37.1 8.7 3.012 40.4 35.7 6.7 1.9
680 / 67 45
10 70.0 48.7 13.9 9.312 65.2 46.7 10.8 6.3
75 / 63 4510 52.7 41.6 10.5 6.012 49.4 40.2 8.2 4.1
880 / 67 45
10 89.6 57.4 17.77 18.4912 84.3 55.0 13.9 12.6
75 / 63 4510 66.3 47.7 13.1 11.512 62.2 45.9 10.3 7.8
2000
480 / 67 45
10 61.9 46.5 12.28 5.0812 57.1 44.6 9.43 3.34
75 / 63 4510 47.6 40.6 9.4 3.412 44.1 39.1 7.3 2.2
680 / 67 45
10 76.4 53.5 15.2 10.712 71.2 51.3 11.8 7.2
75 / 63 4510 57.8 45.9 11.5 6.912 54.2 44.4 9.0 4.7
880 / 67 45
10 93.2 61.0 18.5 19.712 87.7 58.5 14.5 13.4
75 / 63 4510 69.2 51.1 13.7 12.312 65.2 49.3 10.8 8.4
2200
480 / 67 45
10 66.4 50.3 13.2 5.712 61.3 48.3 10.1 3.7
75 / 63 4510 51.2 44.0 10.2 3.812 47.6 42.5 7.9 2.5
680 / 67 45
10 82.6 58.2 16.4 12.112 77.2 56.0 12.8 8.2
75 / 63 4510 62.8 50.1 12.5 7.912 59.1 48.5 9.8 5.4
880 / 67 45
10 95.2 63.9 18.8 20.312 89.4 61.4 14.8 13.8
75 / 63 4510 71.3 54.2 14.1 12.912 67.4 52.4 11.1 8.9
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Cooling Capacity, Cont’d.
15
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
22(1 1/2 HP)
2000
480 / 67 45
10 61.9 46.5 12.28 5.0812 57.1 44.6 9.43 3.34
75 / 63 4510 47.6 40.6 9.4 3.412 44.1 39.1 7.3 2.2
680 / 67 45
10 76.4 53.5 15.2 10.712 71.2 51.3 11.8 7.2
75 / 63 4510 57.8 45.9 11.5 6.912 54.2 44.4 9.0 4.7
880 / 67 45
10 93.2 61.0 18.5 19.712 87.7 58.5 14.5 13.4
75 / 63 4510 69.2 51.1 13.7 12.312 65.2 49.3 10.8 8.4
2200
480 / 67 45
10 66.4 50.3 13.2 5.712 61.3 48.3 10.1 3.7
75 / 63 4510 51.2 44.0 10.2 3.812 47.6 42.5 7.9 2.5
680 / 67 45
10 82.6 58.2 16.4 12.112 77.2 56.0 12.8 8.2
75 / 63 4510 62.8 50.1 12.5 7.912 59.1 48.5 9.8 5.4
880 / 67 45
10 95.2 63.9 18.8 20.312 89.4 61.4 14.8 13.8
75 / 63 4510 71.3 54.2 14.1 12.912 67.4 52.4 11.1 8.9
2400
480 / 67 45
10 70.5 53.9 14.0 6.212 65.4 52.0 10.8 4.1
75 / 63 4510 54.9 47.4 10.9 4.212 51.1 45.9 8.5 2.8
680 / 67 45
10 88.6 62.8 17.6 13.512 82.9 60.5 13.7 9.1
75 / 63 4510 67.5 54.2 13.4 8.812 63.8 52.6 10.5 6.1
880 / 67 45
10 95.4 66.2 18.9 20.412 89.8 63.9 14.9 13.9
75 / 63 4510 72.3 56.8 14.3 13.212 68.8 55.3 11.4 9.1
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
Horizontal Direct Drive Blower Coils
1661616116116111111116
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEAT
(°F) DB/WBEWT(°F)
ΔT(°F)
Total(MBH)
Sensible (MBH)
GPMWPD
(ft. wg.)
30(3 HP)
2800
480 / 67 45
10 91.9 68.6 18.2 4.612 84.8 65.9 14.0 3.1
75 / 63 4510 70.6 59.9 14.0 3.112 65.4 57.8 10.8 2.0
680 / 67 45
10 116.4 80.4 23.1 10.212 109.5 77.5 18.1 7.0
75 / 63 4510 88.5 69.1 17.6 6.712 83.3 66.8 13.8 4.5
880 / 67 45
10 131.4 87.4 26.1 16.612 124.7 84.6 20.6 11.5
75 / 63 4510 99.5 74.4 19.7 10.712 94.2 72.1 15.6 7.4
3000
480 / 67 45
10 96.4 72.5 19.1 5.012 89.2 69.7 14.7 3.3
75 / 63 4510 74.4 63.4 14.8 3.312 69.1 61.2 11.4 2.2
680 / 67 45
10 122.5 85.1 24.3 11.112 115.4 82.2 19.1 7.6
75 / 63 4510 93.5 73.3 18.5 7.212 88.1 71.0 14.6 4.9
880 / 67 45
10 139.4 93.0 27.7 18.212 131.9 89.8 21.8 12.5
75 / 63 4510 105.5 79.2 20.9 11.812 100.0 76.8 16.5 8.1
3200
480 / 67 45
10 100.8 76.3 20.0 5.412 93.4 73.4 15.4 3.6
75 / 63 4510 78.1 66.9 15.5 3.612 72.7 64.6 12.0 2.4
680 / 67 45
10 128.6 89.8 25.5 12.012 121.2 86.8 20.0 8.2
75 / 63 4510 98.3 77.5 19.5 7.812 92.9 75.2 15.4 5.4
880 / 67 45
10 146.6 982.3 29.1 19.712 138.6 94.9 22.9 13.5
75 / 63 4510 111.1 83.8 22.0 12.812 105.6 81.4 17.5 8.8
Cooling Capacity, Cont’d.
NOTE: Ratings are based on 80°F (26.7°C) DB and 67°F (19.4°C) WB EAT, or 75°F ( 23.9 °C) DB and 63°F (17.2°C) WB; 45°F (7.2°C) EWT , 10°F Δ (5.6°C Δ) or 12°F Δ ( 6.7°C Δ) water temperature rise.
17
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEWT(°F)
ΔT(°F)
MBHLAT(°F)
GPMWPD
(ft. wg.)
06(1/2 HP)
500
1140
40 7.8 84.2 0.4 0.220 11.3 90.7 1.1 1.4
18040 16.8 100.6 0.8 0.820 19.7 106.0 2.0 4.1
2140
40 13.2 94.1 0.7 0.120 18.9 104.6 1.9 1.0
18040 28.2 121.6 1.4 0.520 32.6 129.6 3.3 2.8
600
1140
40 9.1 83.9 0.5 0.220 13.2 90.2 1.3 2.0
18040 19.6 99.9 1.0 1.020 23.1 105.2 2.3 5.6
2140
40 15.6 93.8 0.8 0.220 22.2 103.9 2.2 1.4
18040 33.1 120.5 1.7 0.720 38.3 128.4 3.8 3.9
700
1140
40 10.2 83.3 0.5 0.320 14.7 89.3 1.5 2.4
18040 21.8 98.5 1.1 1.320 25.7 103.6 2.6 7.0
2140
40 17.6 93.0 0.9 0.220 25.0 102.6 2.5 1.7
18040 37.2 118.6 1.9 0.920 43.1 126.4 4.3 4.9
08(1 HP)
700
1140
40 10.2 83.3 0.5 0.320 14.7 89.3 1.5 2.4
18040 21.8 98.5 1.1 1.320 25.7 103.6 2.6 7.0
2140
40 17.6 93.0 0.9 0.220 25.0 102.6 2.5 1.7
18040 37.2 118.6 1.9 0.920 43.1 126.4 4.3 4.9
800
1140
40 11.0 82.6 0.6 0.320 15.9 88.2 1.6 2.8
18040 23.5 96.9 1.2 1.520 27.8 101.8 2.8 8.2
2140
40 19.2 92.0 1.0 0.320 27.2 101.1 2.7 2.1
18040 40.5 116.3 2.0 1.120 47.1 123.8 4.7 5.8
900
1140
40 11.6 81.8 0.6 0.420 16.8 87.1 1.7 3.1
18040 24.8 95.2 1.2 1.620 29.4 99.9 2.9 9.1
2140
40 20.4 90.8 1.0 0.320 29.0 99.5 2.9 2.3
18040 43.1 113.8 2.2 1.220 50.3 121.1 5.0 6.7
NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.
Heating Capacity
Heating Capacity, Cont’d.
Horizontal Direct Drive Blower Coils
1881818118118111111118
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.
Unit Size CFM RowsEWT(°F)
ΔT(°F)
MBHLAT(°F)
GPMWPD
(ft. wg.)
10(1/2 HP)
900
1140
40 14.9 85.1 0.7 0.820 20.2 90.6 2.0 6.0
18040 30.1 100.6 1.5 3.220 34.8 105.4 3.5 16.8
2140
40 25.6 96.1 1.3 0.620 34.0 104.6 3.4 4.2
18040 50.9 121.7 2.5 2.320 57.9 128.9 5.8 11.6
1000
1140
40 16.0 84.6 0.8 1.020 21.8 89.9 2.2 6.9
18040 32.4 99.6 1.6 3.720 37.5 104.3 3.8 19.4
2140
40 27.7 95.3 1.4 0.720 36.8 103.7 3.7 4.9
18040 55.0 120.3 2.8 2.620 62.8 127.4 6.3 13.6
1100
1140
40 16.9 84.1 0.8 1.120 23.1 89.2 2.3 7.8
18040 34.3 98.5 1.7 4.120 39.8 103.1 4.0 21.8
2140
40 29.5 94.5 1.5 0.820 39.3 102.6 3.9 5.6
18040 58.6 118.8 2.9 3.020 67.0 125.7 6.7 15.5
12(1 HP)
1100
1140
40 16.9 84.1 0.8 1.120 23.1 89.2 2.3 7.8
18040 34.3 98.5 1.7 4.120 39.8 103.1 4.0 21.8
2140
40 29.5 94.5 1.5 0.820 39.3 102.6 3.9 5.6
18040 58.6 118.8 2.9 3.020 67.0 125.7 6.7 15.5
1200
1140
40 17.7 83.5 0.9 1.220 24.2 88.4 2.4 8.5
18040 35.9 97.3 1.8 4.520 41.7 101.7 4.2 24.0
2140
40 31.0 93.6 1.5 0.920 41.4 101.5 4.1 6.2
18040 61.8 117.1 3.1 3.320 70.7 123.9 7.1 17.2
1300
1140
40 18.3 82.9 0.9 1.220 25.0 87.6 2.5 9.1
18040 37.2 96.1 1.9 4.820 - - - -
2140
40 32.3 92.7 1.6 1.020 43.2 100.4 4.3 6.8
18040 64.4 115.3 3.2 3.620 73.8 121.9 7.4 18.8
Heating Capacity, Cont’d.
19
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEWT(°F)
ΔT(°F)
MBHLAT(°F)
GPMWPD
(ft. wg.)
16(1 HP)
1400
1140
40 19.9 83.0 1.0 0.220 29.1 89.0 2.9 1.9
18040 43.1 98.2 2.2 1.020 51.0 103.3 5.1 5.6
2140
40 37.4 94.5 1.9 0.520 50.6 103.0 5.1 3.5
18040 75.5 119.3 3.8 1.820 86.5 126.5 8.7 5.4
1600
1140
40 21.4 82.2 1.1 0.320 31.4 87.9 3.1 2.2
18040 46.4 96.5 2.3 1.220 54.9 101.4 5.5 6.4
2140
40 40.6 93.2 2.0 0.620 55.0 101.4 5.5 4.1
18040 82.0 116.9 4.1 2.220 94.2 123.8 9.4 11.4
1800
1140
40 22.6 81.5 1.1 0.320 33.0 86.8 3.3 2.5
18040 48.8 94.8 2.4 1.320 57.8 99.4 5.8 7.2
2140
40 43.1 91.9 2.2 0.620 58.5 99.7 5.8 4.6
18040 87.1 114.3 4.4 2.520 100.4 121.0 10.0 12.9
20(1 HP)
1800
1140
40 26.2 83.3 1.3 0.520 36.9 88.8 3.7 3.7
18040 54.7 97.8 2.7 1.920 64.1 102.6 6.4 10.5
2140
40 43.7 92.2 2.2 0.320 61.9 101.5 6.2 2.2
18040 92.1 116.8 4.6 1.220 107.3 124.5 10.7 6.3
2000
1140
40 27.6 82.6 1.4 0.520 38.9 87.8 3.9 4.1
18040 57.6 96.3 2.9 2.220 67.6 100.9 6.8 11.7
2140
40 46.4 91.2 2.3 0.320 65.8 100.1 6.6 2.5
18040 97.8 114.7 4.9 1.320 114.2 122.2 11.4 7.1
2200
1140
40 28.7 81.9 1.4 0.620 40.4 86.8 4.0 4.4
18040 59.9 94.9 3.0 2.320 70.3 99.2 7.0 12.7
2140
40 48.5 90.2 2.4 0.420 69.0 98.7 6.9 2.7
18040 102.5 112.6 5.1 1.520 119.8 119.8 12.0 7.9
NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.
Heating Capacity, Cont’d.
Horizontal Direct Drive Blower Coils
20020202220222022222222222220
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Unit Size CFM RowsEWT(°F)
ΔT(°F)
MBHLAT(°F)
GPMWPD
(ft. wg.)
22(1 1/2 HP)
2000
1140
40 27.6 82.6 1.4 0.520 38.9 87.8 3.9 4.1
18040 57.6 96.3 2.9 2.220 67.6 100.9 6.89 11.7
2140
40 46.4 91.2 2.3 0.320 65.8 100.1 6.6 2.5
18040 97.8 114.7 4.9 1.320 114.2 122.2 11.4 7.1
2200
1140
40 28.7 81.9 1.4 0.620 40.4 86.8 4 4.4
18040 59.9 94.9 3 2.320 70.3 99.2 7 12.7
2140
40 48.5 90.2 2.4 0.420 69 98.7 6.9 2.7
18040 102.5 112.6 5.1 1.520 119.8 119.8 12 7.9
2400
1140
40 29 81.8 1.5 0.720 40.8 86 4.1 4.8
18040 60 94.8 3.2 2.420 70.8 99 7.1 13
2140
40 49 90 2.6 0.520 70 98.8 7 2.9
18040 103 112.5 5.3 1.720 120.1 119.7 12.1 8.3
30(3 HP)
2800
1140
40 30.0 79.8 1.5 0.120 54.3 87.7 5.4 0.7
18040 79.8 96.1 4.0 0.420 97.1 101.7 9.7 2.2
2140
40 67.9 92.2 3.4 0.220 96.9 101.6 9.7 1.8
18040 144.2 117.1 7.2 0.920 167.7 124.8 16.8 5.0
3000
1140
40 31.5 79.6 1.6 0.120 56.3 87.1 5.6 0.8
18040 82.7 95.2 4.1 0.420 100.7 100.7 10.1 2.3
2140
40 70.8 91.6 3.5 0.220 101.0 100.8 10.1 1.9
18040 150.2 115.8 7.5 1.020 174.9 123.3 17.5 5.5
3200
1140
40 32.7 79.4 1.6 0.120 57.9 86.6 5.8 0.8
18040 85.1 94.3 4.3 0.420 103.7 99.6 10.4 2.5
2140
40 73.3 91.0 3.7 0.320 104.6 99.9 10.5 2.1
18040 155.5 114.4 7.8 1.120 181.4 121.8 18.1 5.9
NOTES: 1. Based on 70°F (21.1°C) entering air temperature. 2. For leaving air temperature above 130°F (54.4°C) consult the factory.
21
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Electric heaters are available on IEC Direct Drive blower coils for total electric heat.
Total Electric HeatTotal electric heat eliminates the requirement for a boiler and provides heating and/or cooling on an individual basis throughout the year. Electric heat is available only for single source power (motor and heater voltage the same).
Heater ConstructionThe heater coils of high-grade resistance wire are supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the outlet after the blower and the coil. An auto and a manual thermal limit switch protect the heater in the event of airfl ow failure. For electric heat control options refer to page 35.
Electric Heater Selection
kWHeater Availability Full Load Amps
Single Phase Three Phase6 8 10 12 16 20/22 30 115 V 208 V 230 V 277 V 208 V 230 V 460 V
1 • • - - - - - 8.3 4.8 4.2 3.6 2.8 2.4 1.21.5 • • • • - - - 12.5 7.2 6.3 5.4 4.2 3.6 1.82 • • • • - - - 16.7 9.6 8.3 7.2 5.6 4.8 2.4
2.5 • • • • • - - 20.8 12.0 10.4 9.0 6.9 6.0 3.03 • • • • • - - 25.0 14.4 12.5 10.8 8.3 7.2 3.6
3.5 • • • • • • - 29.2 16.8 14.6 12.6 9.7 8.4 4.24 • • • • • • - 33.3 19.2 16.7 14.4 11.1 9.6 4.8
4.5 • • • • • • - 37.5 21.6 18.8 16.2 12.5 10.8 5.45 • • • • • • - - 24.0 20.8 18.1 13.9 12.0 6.06 • • • • • • • - 28.8 25.0 21.7 16.7 14.4 7.27 - • • • • • • - 33.7 29.2 25.3 19.4 16.8 8.48 - • • • • • • - 38.5 33.3 28.9 22.2 19.2 9.6
9.9 - - • • • • • - - - 35.7 27.5 23.8 11.912 - - - • • • • - - - 43.3 33.3 28.9 14.414 - - - - • • • - - - - 38.9 33.7 16.815 - - - - • • • - - - - 41.6 36.1 18.016 - - - - • • • - - - - - 38.5 19.218 - - - - - • • - - - - - - 21.7
19.9 - - - - - • • - - - - - - 23.925 - - - - - - • - - - - - - 30.130 - - - - - - • - - - - - - 36.135 - - - - - - • - - - - - - 42.1
NOTES: 1. Electric heaters are available for 1-stage, 2-stage or 3-stage applications depending on power phase and heater kW. SINGLE-PHASE POWER:
1-12 kW: 1-stage available 3-12 kW: 2-stage available
3-PHASE POWER: 1-35 kW: 1-stage available 4-35 kW: 2-stage available 12-35 kW: 3-stage available
2. Electric Heating Capacities (BTUH) = Heater kW x 3413 3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage Electric Heater Amperage for 3-phase Power = (Heater kW x 1000)/(Applied Voltage x 1.73)
Horizontal Direct Drive Blower Coils
22222222222222222222222222222
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Motor Full Load Amps Data – HDY
Voltage
UNIT SIZE
06, 10 08,12,16,20 22 30
Motor HP
1/2 1 1-1/2 3
115 V50/60 Hz1-Phase
6.4 10.7 NA NA
208 V50/60 Hz1-Phase
3.8 6.3 NA NA
230 V50/60 Hz1-Phase
3.6 5.8 NA NA
277 V50/60 Hz1-Phase
3.2 5.1 NA NA
208 V50/60 Hz3-Phase
2.0 7.0 4.4 8.9
230 V50/60 Hz3-Phase
1.85 6.5 4.4 8.9
460 V50/60 Hz3-Phase
1.0 1.75 2.2 4.4
NOTES: 1. Motor full load Amps refer to National Electric Code (NEC) Amps; actual motor nameplate amps may vary. 2. Motors are UL recognized constant speed brushless DC, open drip proof, ball bearing, multi-input voltage options, 0-10 VDC
control, PWM control and 12 VDC supply direct from motor. 1/2 and 1 HP motors have integrated control module with overload and short circuit protection. 1-1/2 and 3 HP motors have remote mounted control with overload and short circuit protection. Control module is mounted internal of cabinet.
Thermal Overload Protection All standard motors on Horizontal Direct Drive units furnished by IEC contain internal thermal overload protection. The overload automatically resets when the temperature returns to a safe limit. These thermal overloads replace the need for motor starters.
23
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Component Static Resistance Table (in w.c.)
Unit Size
Nominal CFM
Coil(includes cabinet) Filters
MixingBox
Dry1”
Throw-away
1"MERV 8 Pleated
(Qty. 2)1" Throw-
away
2"MERV 8 Pleated
2" MERV 11
w/Prefi lter
4”MERV 11 Pleated
4”MERV 13 Pleated
4Row
5Row
6Row
7Row
8Row
06
400 0.07 0.08 0.10 0.11 0.12 0.04 0.07 0.05 0.04 0.04 0.03 0.04 0.02500 0.11 0.13 0.16 0.18 0.19 0.06 0.11 0.07 0.05 0.06 0.05 0.06 0.03600 0.15 0.19 0.22 0.24 0.27 0.08 0.14 0.09 0.06 0.07 0.06 0.08 0.04700 0.20 0.24 0.28 0.31 0.34 0.10 0.17 0.11 0.08 0.09 0.08 0.10 0.06800 0.24 0.29 0.34 0.38 0.42 0.12 0.21 0.14 0.09 0.11 0.09 0.12 0.08
08
600 0.15 0.19 0.22 0.24 0.27 0.08 0.14 0.09 0.06 0.07 0.06 0.08 0.04700 0.20 0.24 0.28 0.31 0.34 0.10 0.17 0.11 0.08 0.09 0.08 0.10 0.06800 0.24 0.29 0.34 0.38 0.42 0.12 0.21 0.14 0.09 0.11 0.09 0.12 0.08900 0.28 0.34 0.40 0.45 0.49 0.14 0.24 0.16 0.10 0.12 0.10 0.14 0.10
1000 0.33 0.40 0.46 0.52 0.57 0.16 0.27 0.18 0.12 0.14 0.12 0.16 0.12
10
800 0.12 0.14 0.16 0.18 0.21 0.06 0.10 0.08 0.06 0.13 0.05 0.05 0.04900 0.15 0.18 0.21 0.24 0.26 0.07 0.12 0.09 0.07 0.16 0.06 0.06 0.05
1000 0.19 0.22 0.26 0.29 0.32 0.09 0.14 0.11 0.08 0.18 0.07 0.07 0.061100 0.22 0.26 0.30 0.34 0.37 0.10 0.16 0.13 0.09 0.21 0.08 0.08 0.081200 0.25 0.30 0.35 0.39 0.43 0.11 0.18 0.14 0.10 0.23 0.09 0.09 0.09
12
1000 0.19 0.22 0.26 0.29 0.32 0.09 0.14 0.11 0.08 0.18 0.07 0.07 0.061100 0.22 0.26 0.30 0.34 0.37 0.10 0.16 0.13 0.09 0.21 0.08 0.08 0.081200 0.25 0.30 0.35 0.39 0.43 0.11 0.18 0.14 0.10 0.23 0.09 0.09 0.091300 0.29 0.34 0.40 0.44 0.48 0.13 0.19 0.16 0.11 0.25 0.10 0.10 0.111400 0.32 0.38 0.44 0.49 0.54 0.14 0.21 0.18 0.12 0.28 0.11 0.11 0.13
16
1400 0.19 0.23 0.28 0.31 0.34 0.11 0.14 0.17 0.10 0.21 0.09 0.09 0.071500 0.22 0.26 0.31 0.35 0.38 0.12 0.16 0.19 0.10 0.24 0.10 0.10 0.091600 0.24 0.29 0.35 0.38 0.42 0.13 0.17 0.21 0.11 0.26 0.11 0.11 0.101700 0.27 0.32 0.38 0.42 0.47 0.14 0.19 0.22 0.12 0.28 0.12 0.12 0.111800 0.29 0.35 0.42 0.46 0.51 0.15 0.20 0.24 0.13 0.30 0.12 0.13 0.12
20
1800 0.22 0.27 0.32 0.37 0.42 0.11 0.18 0.17 0.11 0.24 0.10 0.13 0.071900 0.24 0.30 0.36 0.41 0.46 0.12 0.19 0.18 0.12 0.26 0.11 0.14 0.082000 0.27 0.33 0.39 0.45 0.50 0.13 0.21 0.20 0.13 0.28 0.12 0.15 0.092100 0.29 0.36 0.42 0.49 0.55 0.14 0.22 0.21 0.13 0.30 0.13 0.16 0.102200 0.31 0.39 0.46 0.53 0.59 0.15 0.24 0.23 0.14 0.32 0.14 0.17 0.112300 0.34 0.42 0.49 0.57 0.64 0.16 0.25 0.25 0.15 0.34 0.15 0.18 0.122400 0.36 0.44 0.53 0.60 0.68 0.17 0.27 0.26 0.16 0.36 0.16 0.20 0.13
22
1800 0.22 0.27 0.32 0.37 0.42 0.11 0.18 0.17 0.11 0.24 0.10 0.13 0.071900 0.24 0.30 0.36 0.41 0.46 0.12 0.19 0.18 0.12 0.26 0.11 0.14 0.082000 0.27 0.33 0.39 0.45 0.50 0.13 0.21 0.20 0.13 0.28 0.12 0.15 0.092100 0.29 0.36 0.42 0.49 0.55 0.14 0.22 0.21 0.13 0.30 0.13 0.16 0.102200 0.31 0.39 0.46 0.53 0.59 0.15 0.24 0.23 0.14 0.32 0.14 0.17 0.112300 0.34 0.42 0.49 0.57 0.64 0.16 0.25 0.25 0.15 0.34 0.15 0.18 0.122400 0.36 0.44 0.53 0.60 0.68 0.17 0.27 0.26 0.16 0.36 0.16 0.20 0.13
30
2400 0.17 0.21 0.24 0.28 0.33 0.09 0.15 0.14 0.10 0.19 0.07 0.11 0.072600 0.20 0.24 0.28 0.33 0.38 0.10 0.16 0.16 0.11 0.22 0.08 0.13 0.092800 0.23 0.27 0.32 0.38 0.43 0.11 0.18 0.17 0.12 0.24 0.09 0.14 0.103000 0.26 0.31 0.36 0.42 0.49 0.13 0.20 0.19 0.14 0.26 0.10 0.16 0.113200 0.29 0.34 0.40 0.47 0.54 0.14 0.22 0.21 0.15 0.28 0.12 0.18 0.133400 0.32 0.38 0.44 0.52 0.59 0.15 0.24 0.23 0.16 0.31 0.13 0.19 0.15
Horizontal Direct Drive Blower Coils
24424242224222422222222222224
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Sound Power DataUNIT SIZE
RATINGFAN
SPEEDCFM
SOUND POWER LEVEL, Lw (dB reference one picowatt) A-wgt (dBA)
MotorHP125 Hz 250 Hz 500 Hz 1K Hz 2K Hz 4K Hz 8K Hz
6
CASING RADIATED
NOTE 2975
600 @
.50” ESP
64 59 55 51 46 40 35 57
1/2DUCTED
DISCHARGE NOTE 3
63 53 53 51 50 45 37 57
8
CASING RADIATED
NOTE 21,075
800 @
.50” ESP
64 60 60 58 56 54 45 64
1DUCTED
DISCHARGENOTE 3
64 61 58 56 50 43 36 60
10
CASING RADIATED
NOTE 21,140
1,000 @
.50” ESP
70 65 59 59 55 49 41 64
1/2DUCTED
DISCHARGENOTE 3
68 63 65 64 61 60 53 68
12
CASING RADIATED
NOTE 21,235
1,200@
.50” ESP
73 69 61 62 57 51 44 67
1DUCTED
DISCHARGENOTE 3
72 67 67 67 64 63 57 72
16
CASING RADIATED
NOTE 21,066
1,600@
.50” ESP
73 69 62 64 60 55 48 68
1DUCTED
DISCHARGE NOTE 3
72 68 69 70 68 68 63 75
20
CASING RADIATED
NOTE 2910
2,000@
.50” ESP
74 69 60 59 56 51 42 66
1DUCTED
DISCHARGE NOTE 3
71 67 66 66 64 63 57 71
22 NOTE 4
CASING RADIATED
NOTE 2950
2,200@
.50” ESP
73 69 60 60 58 53 45 66
1-1/2DUCTED
DISCHARGE NOTE 3
73 68 65 67 64 63 57 72
30NOTE 4
CASING RADIATED NOTE 2
8603,000@
.50” ESP
74 70 65 63 61 57 49 69
3DUCTED
DISCHARGE NOTE 3
71 73 75 72 70 70 64 78
NOTES:1. Unit Test Configuration: Rear Return/Front Supply, 4 Row, 10 FPI Coil, 115/1 PH/ 60HZ VAC Motor, 2” Fiberglass Filter, 1/2” dual density fiberglass insulation.2. Testing per AHRI 260-2001: 4.2.2.3 Casing radiated with free inlet, Sound Rating of Ducted Air Moving and Conditioning Equipment.3. Testing per AHRI 260-2001: 4.2.2.1 Ducted discharge, Sound Rating of Ducted Air Moving and Conditioning Equipment. 4. Size 22 & 30 Unit Test Configuration: Rear Return/Front Supply, 4 Row, 10 FPI Coil, 460/3 PH/ 60HZ VAC Motor, 2” Fiberglass Filter, 1/2” dual density fiberglass insulation.5. Sound power data is expressed in decibels, dB RE: 1 x 10-12 w (picowatts).
25
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Fan Curves
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
0 200 400 600 800 1000 1200
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY06, 1/2 hp Motor
400 600 800 1000 1200 1400RPM
RECOMMENDEDOPERATING RANGE
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
0 200 400 600 800 1000 1200 1400 1600
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY08, 1 hp Motor
400 600 800 1000 1200
1400 1600 1800
RECOMMENDED OPERATING RANGE
RPM
Horizontal Direct Drive Blower Coils
26626262226222622222222222226
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Fan Curves, Cont’d.
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
200 400 600 800 1000 1200 1400 1600 1800 2000
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY10, 1/2 hp Motor
600 800 1000 1200
1400 1600 1800
RPM
RECOMMENDED OPERATING RANGE
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
200 400 600 800 1000 1200 1400 1600 1800 2000
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY12, 1 hp Motor
600 800 1000 1200
1400 1600 1800
RECOMMENDED OPERATING RANGE
RPM
27
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Fan Curves, Cont’d.
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
400 800 1200 1600 2000 2400 2800
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY20, 1 hp Motor
600 800 1000 1200 1400RPM
RECOMMENDED OPERATING RANGE
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY16, 1 hp Motor
600 800 1000 1200
1400 1600
RPM
RECOMMENDED OPERATING RANGE
Horizontal Direct Drive Blower Coils
28828282228222822222222222228
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Fan Curves, Cont’d.
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY30, 3 hp Motor
600 800 1000 1200 1400RPM
RECOMMENDED OPERATING RANGE
0
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
400 800 1200 1600 2000 2400 2800
TOTA
L ST
ATI
C PR
ESSU
RE
SCFM
HDY22, 1.5 hp Motor
600 800 1000 1200 1400RPM
RECOMMENDED OPERATING RANGE
29
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
HDY Unit– Horizontal Direct Drive
SizeFan Size
Depth Width HeightSupply Duct Return Duct (Note 7) Mounting Holes
Aux.Ctrl.
Box
A B C D E F G J K L
06 9 x 6 36(914)
28(711)
19-3/4 (502)
8-7/8(225)
10-7/8(276)
13-3/4(349)
2-1/4(57)
24-1/4(616)
14(356)
2-3/4(70)
27-1/4(686)
35-1/4(895)
5-3/4(146)
08 9 x 6 36(914)
28(711)
19-3/4 (502)
8-7/8(225)
10-7/8(276)
13-3/4(349)
2-1/4(57)
24-1/4(616)
14(356)
2-3/4(70)
27-1/4(686)
35-1/4(895)
5-3/4(146)
10 9 x 6 37-1/2(953)
37(940)
21-1/2(546)
8-7/8(225)
10-7/8(276)
14-1/2(368)
2-1/4(57)
33-1/4(845)
15-3/4(401)
2-7/8(73)
36-1/4(921)
37(940)
5(124)
12 9 x 6 37-1/2(953)
37(940)
21-1/2(546)
8-7/8(225)
10-7/8(276)
14-1/2(368)
2-1/4(57)
33-1/4(845)
15-3/4(401)
2-7/8(73)
36-1/4(921)
37(940)
5(124)
16 10 x 7 37-3/4(959)
47(1194)
21-1/2(546)
10-3/8(264)
12(305)
18-3/8(467)
2-1/4(57)
43-7/8(1115)
15-3/4(401)
2-7/8(73)
46-1/4(1175)
37(940)
1-1/4(32)
20/22 11 x 10 40-1/4(1022)
48(1219)
24 (610)
13-7/8(352)
13(330)
17-1/4(438)
2-1/4(57)
44-1/4(1124)
18(457)
2-7/8(73)
47-1/4(1200)
39-1/2(1033)
2-3/8(60)
30 12 x 12 40-1/4(1022)
48(1219)
32-1/4(819)
16-1/4(413)
14(356)
16(406)
7-1/8 (181)
44-1/4(1124)
26-1/2(673)
1-1/4(32)
47-1/4(1200)
39-1/2(1033)
3-3/4(95)
NOTES:1. RH shown, LH opposite. 2. All dimensions are +/- 1/4" (6 mm). 3. Product specifi cations are subject to changes without notice. 4. Dimensions in parenthesis are shown in (millimeters). 5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area. 6. “C” dimension is measured from coil side of unit. 7. Mixing Box option will vary return duct dimensions, refer to mixing box submittal.
Drawing is not to scale and is provided for reference only.Dimensions may vary with options ordered.
Consult IEC website for up-to-date drawings.
Horizontal Direct Drive Blower Coils
30030303330333033333333333330
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
HDY Unit with Optional Mixing Box
Drawing is not to scale and is provided for reference only.Dimensions may vary with options ordered.
Consult IEC website for up-to-date drawings.
SizeFan Size
DepthUnit
DepthWidth Height
Supply Duct Return Duct (Note 7) Mix BoxMounting
HolesAux.Box
A B C D E F G H J K L
06 9 x 6 51-5/8(1311)
36(914)
28(711)
22-3/4 (578)
8-7/8(225)
10-7/8(276)
13-3/4(349)
2-1/4(57)
24(610)
6(152)
12-1/2(318)
11(279)
27-1/4(686)
35-1/4(895)
5-3/4(146)
08 9 x 6 51-5/8(1311)
36(914)
28(711)
22-3/4 (578)
8-7/8(225)
10-7/8(276)
13-3/4(349)
2-1/4(57)
24(610)
6(152)
12-1/2(318)
11(279)
27-1/4(686)
35-1/4(895)
5-3/4(146)
10 9 x 6 55-1/8(1400)
37-1/2(953)
37(940)
24-1/2(622)
8-7/8(225)
10-7/8(276)
14-1/2(368)
2-1/4(57)
33(838)
8(203)
14-1/4(362)
13(330)
36-1/4(921)
37(940)
5(124)
12 9 x 6 55-1/8(1400)
37-1/2(953)
37(940)
24-1/2(622)
8-7/8(225)
10-7/8(276)
14-1/2(368)
2-1/4(57)
33(838)
8(203)
14-1/4(362)
13(330)
36-1/4(921)
37(940)
5(124)
16 10 x 7 55-3/8(1407)
37-3/4(959)
47(1194)
24-1/2(622)
10-3/8(264)
12(305)
18-3/8(467)
2-1/4(57)
43(1092)
8(203)
14-1/4(362)
13(330)
46-1/4(1175)
37(940)
1-1/4(32)
20/22 11 x 10 57-3/4(1467)
40-1/4(1022)
48(1219)
27(686)
13-7/8(352)
13(330)
17-1/4(438)
2-1/4(57)
44(1118)
8(203)
16-3/4(425)
13(330)
47-1/4(1200)
39-1/2(1033)
2-3/8(60)
30 12 x 12 59-3/4(1518)
40-1/4(1022)
48(1219)
35-1/4(895)
16-1/4(413)
14(356)
16(406)
7-1/8 (181)
44(1118)
10(254)
15(381)
15(381)
47-1/4(1200)
39-1/2(1033)
3-3/4(95)
NOTES:1.RH shown, LH opposite. 10. Add 2”(51) if using a Prefi lter, or 4”(102) fi lter. 2. All dimensions are +/- 1/4” (6 mm). 3. Product specifi cations are subject to changes without notice. 4. Dimensions in parenthesis are shown in (millimeters). 5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area. 6. “C” dimension is measured from coil side of unit. 7. Mixing Box option will vary return duct dimensions, refer to mixing box submittal. 8. Mixing Box options include: a) Knockdown base rails for fi eld assembly; b) Pre-assembled Mixing Box. 9. Linkage kit supplied with Mixing Box is provided for fi eld installation of actuator.
31
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Piping Connection Location (Centerline to Centerline) – Hydronic Cooling and Heating Coils
Coil Header Connection Size
Unit
Size
8 Row 6 Row 4 Row 2 Row HW 1 Row HW
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
06-12 1 1.125 3/4 0.875 3/4 0.875 1/2 0.625 1/2 0.62516-22 1 1.125 1 1.125 1 1.125 1 1.125 1/2 0.625
30 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625
Horizontal, left hand unit with re-heat coil shown.
Unit SizeCoil Rows
A B C D E F GCool Heat
06/08
4– –
6-1/8 12-3/4
– – –5-15/161 3-1/2 15-1/2 7 7
2 3-13/16 15-13/16 7-9/16 7-9/16
6– – – – –
8-1/81 3-1/2 15-1/2 9-3/16 9-3/162 3-13/16 15-13/16 9-3/4 9-3/4
8 – – – – – 10-1/4
10/12
4– –
7-3/4 14-3/8
– – –5-15/161 5-1/8 17-1/8 7 7
2 5-7/16 17-7/16 7-9/16 7-9/16
6– – – – –
8-1/81 5-1/8 17-1/8 9-3/16 9-3/162 5-27/61 17-7/16 9-3/4 9-3/4
8 – – – – – 10-1/4
16
4
– – 7-3/415-5/8
– – –
5-15/161LH 10-5/8
7-3/4 129-5/8 7
RH 13-3/8 9-5/8 72 12 7 16-3/8 13-5/8 10-3/8 7-9/16
6
– – 7-3/415-5/8
– – –
8-1/81LH 10-5/8
7-3/4 1211-13/16 9-3/16
RH 13-3/8 11-13/16 9-3/162 12 7 16-3/8 13-5/8 12-1/2 9-3/4
8 – – 9-1/2 15-5/8 – – – 10-1/4
20/22
4
– – 7-13/16
18-3/16
– – –5-15/16
1LH 11-15/16
7-13/16 13-5/16 9-5/87RH 14-11/16
2 11-9/16 7-7/8 15-13/16 9-1/16 5
6
– – 7-13/16 – – –8-1/8
1LH 11-15/16
7-13/16 13-5/16 11-13/169-3/16RH 14-11/16
2 11-9/16 7-7/8 15-13/16 11-1/4 7-1/88 – – 7-13/16 – – – 10-1/4
30
4– –
5-15/16 26-5/16
– – – 5-15/161 7-1/16 25-13/16 9
7 4-7/82 10-5/16 23-13/16 9-1/8
6– – – – – 8-1/81 7-1/16 25-13/16 11-1/8
9-1/8 7-1/162 10-5/16 23-13/16 11-5/16
8 – – – – – 10-1/4
CR - Cold Water ReturnHR - Hot Water ReturnCS - Cold Water SupplyHS - Hot Water SupplyRH - Right HandLH - Left Hand
0
0
2(51)
B
C6-7/8(17
5)
8-5/8(21
9) E
D
1-5/8(41)
A
2-11
/16(68
) G F10
-3/8(264
)
Horizontal Direct Drive Blower Coils
32232323332333233333333333332
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Piping Connection Location (Centerline to Centerline) – R-410A Cooling with Hot Water Heating
Horizontal, left hand unit with pre-heat coil shown.
Coil Header Connection Size (Nominal OD in Inches)
Unit
Size
LL SL 2 Row HW 1 Row HW
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
Nom.
Size
Actual
OD
06-12 1/4 0.375 3/4 0.875 1/2 0.625 1/2 0.62516-22 1/4 0.375 1 1.125 1 1.125 1/2 0.625
30 1/2 0.625 1-1/2 1.625 1-1/2 1.625 1-1/2 1.625
SIZE
COIL ROWS
A B C D E F G HDX ONLY
WATER
PRE-HEAT
06/08
4 –
4-3/4 5-1/2
– –
12-1/2
2-3/4 – – 6 4
1 6 18
3-3/4 2-5/8 2-5/8 6 4
2 4-7/8 3-1/4 3-1/4 6
10/12
4 –
6-1/2 7-1/8
– –
12-1/2
2-3/4 – – 6 4
1 5-1/8 17-1/8
3-3/4 2-5/8 2-5/8 6 4
2 4-7/8 3-1/4 3-1/4 6
16
4 –
6-1/2 7-1/8
– –
12-1/2
2-3/4 – – 6 4
1 5-1/8 17-1/8 3-3/4 2-5/8 2-5/8 6 4
2 6-3/8 10 13-5/8 6-6/8 4-1/8 2-5/8 6
20/22
4 –
6-1/2 7-1/8 – –
12-1/2
2-3/4 – – 6 4
1 5-1/4 19-3/4 3-3/4 2-5/8 2-5/8 6 4
2 6-3/4 7-1/4 11-5/8 15-7/8 6-3/4 4-1/4 2-5/8 6
30
4 – 4-5/8 5-3/8 – –
12-1/2
2-3/4 – – 6 4
1 4-7/8
6 12-1/8 25-7/8 6-1/8 4-1/2 2-5/8
6 4
2 5-3/8 10-3/8 23-7/8 6-3/8 6
HR - Hot Water ReturnHS - Hot Water SupplyLL - Liquid LineSL - Suction Line
0
0
2(51)
B
D
7/8(17
5)
5/8(21
9)
A
GH E
1-5/8(41)
FC
33
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Distributed Weight CalculationsThe following operating weight information is based on 8-row water-fi lled coils and double wall cabinet construction. For a diff erent coil and cabinet options, use the weight correction factor table.
Horizontal Units (Top View)
HDY UnitNo Electric Heat (lb.) With Electric Heat (lb.)
A B C D Total A B C D Total
06 42 46 36 47 171 42 58 36 66 20208 41 47 38 45 171 41 58 36 67 20210 51 53 49 63 217 51 60 56 83 25012 50 52 51 64 217 50 58 57 85 25016 65 70 64 75 274 70 69 66 104 30920 78 90 77 95 340 81 96 77 107 37822 83 105 80 99 367 86 111 81 111 38930 103 113 97 117 430 104 120 96 149 469
Total Weight Unit Correction Factor (lb.) – HDY
These weights are for 8-row water-fi lled coils and double wall construction. For a diff erent number of rows, total unit weight can be determined by:
Total unit weight can be adjusted by :
a. Identify the size of unit and number of rows b. From the previous table, identify the total weight of the unit c. From the table below, identify the correction factor and deduct this factor from the total weight.
Options 6 8 10 12 16 20 22 30
4-Row Coil -21 -21 -28 -28 -39 -46 -46 -98
5-Row Coil -16 -16 -21 -21 -29 -35 -35 -74
6-Row Coil -11 -11 -14 -14 -20 -23 -23 -49
7-Row Coil -5 -5 -7 -7 -10 -12 -12 -25
Single Wall Construction -31 -31 -40 -40 -47 -58 -58 -67
NOTE: 1. Unit weights (shown in pounds), +/- 10 percent, are based on the largest water-fi lled coil.
Horizontal Direct Drive Blower Coils
34434343334333433333333333334
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
The standard Direct Drive Blower Coils are furnished with a set of 2” pleated MERV 8 fi lters.
Unit SizeFilter
Quantity
Nominal Filter Sizes –Inches (Millimeters)
HDY
06 1 16-1/2" x 24" (419 x 610)
08 1 16-1/2" x 24" (419 x 610)
10 1 18-1/4" x 33" (464 x 838)
12 1 18-1/4" x 33" (464 x 838)
16 2 18-1/4" x 21-1/2" (464 x 546)
20/22 2 20-1/2 x 22" (521 x 559)
30 2 29" x 22" (737 x 559)
• Side and bottom fi lter removal• No tools needed for easy fi lter change, usage of
strong magnets in place of hardware• Choice of 1”, 2” or 4” fi lters• Easy to modify in the fi eld for either 1”, 2” or 4” fi lters• Robust design eliminates unit’s sagging
1” Filter
2” Filter
4” Filter
Magnet
See Detail X
Detail X
Filters
35
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Controls:
Motor Controls – Units without electric heat:
Two controls schemes are available:
• 3 - Speed adjustable.
• Proportional (0 - 10 VDC).
Electric Heat Controls
Electric heaters come standard with a transformer, heater contactors, motor and electric heat fusing, and a terminal strip.
An optional interlocking disconnect switch is available.
Control Box
Condensate Float Switch
A water-level sensing device designed to prevent drain pan overfl ow. The standard switch is wired normally closed. Switches are available only in 24 V.
Cabinet/Control Box Maintenance Light
Optional LED Service Light provides a source of illumination in the main unit cabinet and the control box during routine maintenance and troubleshooting in the dark ceiling spaces.
Above picture is the example of Control box with electric heat, disconnect switch and service light.
Factory Installed Options
Horizontal Direct Drive Blower Coils
36636363336333633333333333336
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Mixing BoxesMixing boxes can be used when outside air is required. Mixing boxes come with base rails. Refer to the drawings on pages 36
and 37 for additional information.
Mixing Box with Base RailsMixing box option includes : 1.) knockdown base rails for fi eld assembly, and 2.) pre-assembled mixing box. Base rails are letter coded for ease of assembly and all hardware required for assembly is included. Linkage kit consists of 2 crank arms, 2 swivels, and either a 25" (sizes 06-16) or a 34" (sizes 20-30) length of 5/16" rod provided for fi eld installation of actuator. Consult factory for the 24 V damper actuator option. Mixing box option adds 3" to the unit height due to the base rails.
Horizontal Units – Dimensions - Inches (Millimeters)
Unit Type and Size W D A
HDY06 28 (711) 51.6 (1311) 16.1 (409)HDY08 28 (711) 51.6 (1311) 16.1 (409)HDY10 37 (940) 55.2 (1402) 18.1 (460)HDY12 37 (940) 55.2 (1402) 18.1 (460)HDY16 47 (1194) 55.4 (1407) 18.1 (460)
HDY20/22 48 (1219) 57.8 (1468) 18.1 (460)HDY30 48 (1219) 59.8 (1519) 20.1 (511)
1(25)W
FRONT VIEW
D
3(76)
A1(25)
SIDE VIEW
Base Rail Details
37
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Mixing Box Details
3(76)
A
C
2.4(61)
4(102)
H
2.4(61)
3(76)
1(25)
2(51)2(51)
WB
TOP VIEWS
BTM/REAR INLET - HDY TOP/REAR INLET - HDY
RIGHT HAND SIDE VIEWS
W
4(102)
2.4(61)
C
1(25)
H
A
A
B
A
2.4(61)
Note: Add 2” (51) to total unit length if using 2” prefilter or 4” filter with mixing box option.
Dimensions - Inches (Millimeters)
Unit Size H W A B C
06 18.5 (470) 28 (711) 6 (152) 24 (610) 11 (279)08 18.5 (470) 28 (711) 6 (152) 24 (610) 11 (279)10 20.25 (514) 37 (940) 8 (203) 33 (838) 13 (330)12 20.25 (514) 37 (940) 8 (203) 33 (838) 13 (330)16 20.25 (514) 47 (1194) 8 (203) 43 (1092) 13 (330)
20/22 22.75 (578) 48 (1219) 8 (203) 44 (1118) 13 (330)30 31 (787) 48 (1219) 10 (254) 44 (1118) 15 (381)
Horizontal Direct Drive Blower Coils
38838383338333833333333333338
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
39
Horizontal Direct Drive Blower CoilsTECHNICAL CATALOG
Contact your local IEC Sales Representative for further details and pricing applicable to this product. Visit our website (iec-okc.com) to fi nd your local IEC Sales Rep.