end block design

14
17/05/2015 1 End Block Design End Block Design Introduction How prestressing force transmitted to concrete? - Pretensioned : transmitted by an internal force system through bond between steel and concrete - Post-tensioned : through external anchorage system The zone within which the applied prestressing force on steel is fully dissipated in to concrete and made to act as a distributed force is known as transmission zone in pretensioned element and anchor zone in post-tensioned elements.

Upload: others

Post on 14-May-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: End Block Design

17/05/2015

1

End Block DesignEnd Block Design

Introduction

How prestressing force transmitted to concrete?

- Pretensioned : transmitted by an internal force system through bond between steel and concrete

- Post-tensioned : through external anchorage system

• The zone within which the applied prestressing force on steel is fully dissipated in to concrete and made to act as a distributed force is known as transmission zone in pretensioned element and anchor zone in post-tensioned elements.

Page 2: End Block Design

17/05/2015

2

Introduction

In post-tensioned construction, the prestressing force is transferred to the concrete through relatively small anchorage plates behind the anchorage by bearing. This results in a very high concrete bearing stress behind the anchorage plate.

Failure of anchorage zone is perhaps the most common cause of problems arising during construction

Such failures are difficult and expensive to repair and might require replacement of the entire member.

Introduction

Anchorage zones failure due to uncontrolled cracking or splitting of the concrete from insufficient transverse reinforcement.

Bearing failures immediately behind the anchorage plate are also common and may be caused by inadequate dimensions of bearing plates or poor quality of concrete.

Page 3: End Block Design

17/05/2015

3

End Block

Page 4: End Block Design

17/05/2015

4

End Block

End Block

Page 5: End Block Design

17/05/2015

5

Stress Distribution The prestressing force in a tendon is applied through the

anchorages as a concentrated force. By St Venant’s principle, the stress distribution in a member is

reasonably uniform away from the anchorage, but in the region of the anchorage itself the stress distribution within the concrete is complex.

The most significant effect for design is that the tensile stresses are set up transverse to the axis of the member, tending to split this concrete apart. This tensile force also known as b i fbursting force.

Reinforcement must be provided to resist these tensile stresses.

Stress Distribution

Page 6: End Block Design

17/05/2015

6

Stress distribution

Design for Bursting Force It is sufficiently accurate to consider the resultant of these stresses,

Fbst At SLS, Fbst is assumed to act in a region extending from 0.2yo to

2yo. The value of Fbst as a proportion of Pi may be found from Table 4.7

BS8110.

The values in Table can be defined by the following equation :y g q

With ypo/yo 0.3, Fbst/Pi = 0.23ypo/yo ≥ 0.7, Fbst/Pi = 0.11

Page 7: End Block Design

17/05/2015

7

Design for Bursting Force

For post-tensioned members which are grouted after tensioning, the maximum force applied to the member is the initial jacking force, Pi and the design is based on SLS.

The bursting force is resisted by reinforcement in the form of spirals or closed links, uniformly distributed throughout the end block (from 0.2yo to 2.0yo) and with a stress of 200 N/mm2.

Design for Bursting Force

For post-tensioned members with unbonded tendons, area of reinforcement is design at ULS given by Fb t/0 87f h Fb t i bt i d f T bl 4 7 Fbst/0.87fy, where Fbst is obtained from Table 4.7 BS8110.

Where an end block contains several anchorages, it should be divided into a series of symmetrically loaded prisms and then each prism treated as a separate end block. Additional reinforcement should be provided around the Additional reinforcement should be provided around the whole group of anchorages to maintain overall equilibrium.

Page 8: End Block Design

17/05/2015

8

Example 1End block of a T-beam is made solid rectangular in cross-section and the tendons are grouped in three bundles with a parabolic profile. Three plates are provided for the three bundles of tendon Design and detail stirrups placement in the end block tendon. Design and detail stirrups placement in the end block according to BS8110. Each bundle of tendons has a jacking force 1000 kN.A plate of 150mm x 150mm can be used for each bundle.

500

150

150 400

400

400

Solution

In the vertical direction

Use formula

Page 9: End Block Design

17/05/2015

9

SolutionIn the horizontal direction

< 0.3

From Table 4.7,

Max Fbst = 0.23Pi

0.3

Solutionuse T10 – 2 leg, Asv = 157 mm2

No of links = 1150/157 = 7.3, use 8 bars

Provide 8T10 through a distance of 500mm (2yo)

For checking: Force provided by bar =

= 251.36 kN >230 kN ..ok

Page 10: End Block Design

17/05/2015

10

Example 2

Design the end block reinforcement for the following bonded post-tensioned beam. A prestressing force of 1055 kN is applied by a single tendon using a bearing plate of 200 x 300mm. Take e = 0 t t= 0 at supports.

SolutionIn the vertical direction,

From Table 4.7 or equation

In horizontal direction,

Page 11: End Block Design

17/05/2015

11

SolutionFbst = 0.17 (1055) = 179.35 kN

Use T12 – 2leg, As = 113 mm2

No of links = 896.75/113 = 7.9, use 8

Provide 8T12 through a distance of 600mm (2yo)

Example 3The beam end shown below has six anchorages with 75mm x 75mm bearing plates and a jacking force of 500 kN applied to each anchorages. Determine the reinforcement required to contain the bursting forces if fy = 460 N/mm2.g y

Page 12: End Block Design

17/05/2015

12

SolutionIndividual Prism (150mm x 250mm)

In the vertical direction,

In the horizontal direction,

SolutionMax Fbst = 115 kN

Use T10 – 2 leg, As = 157 mm2

No of links = 575/157 = 3.7, use 4

Provide 4T10 through a distance of 250mm (2yo)

Page 13: End Block Design

17/05/2015

13

SolutionOverall Prism (350mm x 750mm)

Equivalent 2ypo = (6 x 75 x 75)0.5 = 184mm

In the vertical direction

In the horizontal directionIn the horizontal direction

SolutionMax Fbst = 690 kN

Use T16 – 2 leg, As = 402 mm2

No of links = 3450/402 = 8.5, use 9

Provide 9T16 through a distance of 750mm (2yo)

Page 14: End Block Design

17/05/2015

14

Detailing Reinforcement