Page 1 THE ELGIN AREA PRIMARY WATER SUPPLY SYSTEM JOINT BOARD OF MANAGEMENT PROJECT NO. EA4023 TENDER NO. 13-78 ELGIN AREA WATER TREATMENT PLANT RESIDUALS MANAGEMENT FACILITY ADDENDUM BULLETIN NO.2 This addendum contains amendments and/or documents and shall form part of the Contract Documents. Include any related costs in the tender prices. PART I: CONTACT INFORMATION The tender closing date and time remains unchanged from the tender document. Bidders should be aware that any extension to the tendering period would result in the award of the contract being delayed to the end of March, for which bidders would be required to hold their price. At this time, there are no technical bases to justify an extension to the tendering period. The addenda are to be acknowledged on pg FT-1 clause 1. No part of the addenda needs to be included as part of the submission. Signed addendum forms will be collected at time of document execution. The Bid deposit amount is One Million Five Hundred Thousand Dollars ($1,500,000.00) to be made out to Elgin Area Primary Water Supply System. Liquidated damages rate is $3,250.00 per day ($1,500/d owner costs plus $1,750/d Administration Cost) Form of Tender a) Item 7d) “Fall Arrest Allowance” is to be $10,000 and includes items to be purchased by the contractor at the direction of the owner as per 01000 1.37 “Cash Allowances” b) The price for items described in Divisions 10 and 12 shall be included with item Division 15(f) “All Other items to Complete Division 15 c) Scope of supply for item 11 q) is attached “Westech Sludge Scraper Control Expansion”. This item is to be provisional. It is to be included in the Total Tender Price, however payment for this item will be at the discretion of the Owner. Notwithstanding the one year warrenty identified in the document, a two year warrenty will apply for the contract. Although not identified in the scope of work this item also includes PLC programming and OIT software configuration for the additional sludge pump controls. Information for Tenders a) Remove Section 6.0 item 5) in its entirety b) Relocate Section 6.0 item 4) in its entirety to Section 6.1 c) Remove Section 6.1 item 3) d) Add the following to Section 6.2 item 3) “The Owner may withhold funds in the amount of any OCIP deductible paid out for claims where the Contractor or other party covered by the Project’ OCIP is found liable, from monies owing to the Contractor/OCIP insured party by the Owner under this Contract or any other contract between the Owner and the Contractor/OCIP Insured Party” e) Section 6.2 item 4) should read “Notwithstanding item 6.2 3) above, the Owner…” f) Add the following item to Section 6.2, “item 5) Contractors’ Equipment Insurance covering all equipment, tools and machinery used by the Successful Proponent, (including spare parts and accessories), equipment that a contractor owns or has in its care, custody or control for the full replacement cost of that property.”

Upload: ngodiep

Post on 21-May-2018

258 views

Category:

Documents


2 download

TRANSCRIPT

  • Page 1

    THE ELGIN AREA PRIMARY WATER SUPPLY SYSTEM JOINT BOARD OF MANAGEMENT PROJECT NO. EA4023

    TENDER NO. 13-78

    ELGIN AREA WATER TREATMENT PLANT RESIDUALS MANAGEMENT FACILITY

    ADDENDUM BULLETIN NO.2

    This addendum contains amendments and/or documents and shall form part of the Contract Documents. Include any related costs in the tender prices.

    PART I: CONTACT INFORMATION The tender closing date and time remains unchanged from the tender document. Bidders should be aware that any extension to the tendering period would result in the award of the contract being delayed to the end of March, for which bidders would be required to hold their price. At this time, there are no technical bases to justify an extension to the tendering period. The addenda are to be acknowledged on pg FT-1 clause 1. No part of the addenda needs to be included as part of the submission. Signed addendum forms will be collected at time of document execution. The Bid deposit amount is One Million Five Hundred Thousand Dollars ($1,500,000.00) to be made out to Elgin Area Primary Water Supply System. Liquidated damages rate is $3,250.00 per day ($1,500/d owner costs plus $1,750/d Administration Cost) Form of Tender

    a) Item 7d) Fall Arrest Allowance is to be $10,000 and includes items to be purchased by the contractor at the direction of the owner as per 01000 1.37 Cash Allowances

    b) The price for items described in Divisions 10 and 12 shall be included with item Division 15(f) All Other items to Complete Division 15

    c) Scope of supply for item 11 q) is attached Westech Sludge Scraper Control Expansion. This item is to be provisional. It is to be included in the Total Tender Price, however payment for this item will be at the discretion of the Owner. Notwithstanding the one year warrenty identified in the document, a two year warrenty will apply for the contract. Although not identified in the scope of work this item also includes PLC programming and OIT software configuration for the additional sludge pump controls.

    Information for Tenders

    a) Remove Section 6.0 item 5) in its entirety b) Relocate Section 6.0 item 4) in its entirety to Section 6.1 c) Remove Section 6.1 item 3) d) Add the following to Section 6.2 item 3) The Owner may withhold funds in the amount of any

    OCIP deductible paid out for claims where the Contractor or other party covered by the Project OCIP is found liable, from monies owing to the Contractor/OCIP insured party by the Owner under this Contract or any other contract between the Owner and the Contractor/OCIP Insured Party

    e) Section 6.2 item 4) should read Notwithstanding item 6.2 3) above, the Owner f) Add the following item to Section 6.2, item 5) Contractors Equipment Insurance covering all

    equipment, tools and machinery used by the Successful Proponent, (including spare parts and accessories), equipment that a contractor owns or has in its care, custody or control for the full replacement cost of that property.

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 2

    PART II: SPECIFICATION AMENDMENTS

    1. ADD SECTION 01515 ATTACHED

    2. ADD SECTION 02930 ATTACHED

    3. SECTION 03200

    Part 1.3B Reinforcement Placing Drawings and Bar Lists, add the following: 5. The Reinforcement Placing Drawings should have a sufficient number of plans, sections and details to accurately illustrate the location and extents of each reinforcing steel bar within each concrete component. The Drawings should be sufficiently detailed to permit placement of reinforcing steel (without the use of design drawings) and allow the designer of the structure to verify the accuracy of the reinforcing steel placement / layout with the intended design (without guess work). Failure to sufficiently illustrate the reinforcing steel as described for these two purposes will automatically result in a rejection of the submission.

    4. SECTION 03300

    a) Part 2.1C(4) Concrete for Benching. Add: (C) This mix may be used for concrete in equipment pads and containment curbs

    b) Part 3.11B Limitations to Pour Lengths

    Add: (5) Limit the extent of each pour to 8 m maximum horizontally from each side of a corner pour.

    5. SECTION 04220

    Delete Part 2.5A Veneer Ties (Concrete Block Walls) and replace with:

    A. Veneer Ties (from Cast in Place Concrete) 1. For tying brick veneer to cast in place concrete, use Fero Heavy Duty RAP Ties (as supplied by

    Stuart & Associates, 519-759-3854) fastened to backup with U-CAN Super Scru-it fasteners, 65 mm x 6 mm diameter fasteners (2 fasteners per tie).

    2. The Fero V-tie (4.76 mm diameter) shall be of length to provide placement of V-tie legs at the centreline of veneer facing.

    3. The Fero Heavy Duty RAP Plate length to suit thickness of insulation. 4. All metal components: Type 304 stainless steel. 5. Fero plastic insulation support

    6. SECTION 08310

    Part 2.5 Manufacturers, add the following: B. Pre-approved manufacturers include Bilco (London ON), Mico Manufacturing (Whitby ON) and Earl Ross (Ailsa Craig ON). Delete Part 2.3A and replace with A. Specified Product: Heavy duty, flush mount, aluminum framing, design live load 14.4 kN/m2 (300 psf), drainage channel, all stainless steel hardware/hinges/latch, odour /weather resistant gaskets.

    7. SECTION 08800

    Delete Part 2.5 Glass and Glazing Types and replace with:

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 3

    2.5 Glass and Glazing Types

    A. Glass Type GL-1 1. Double glazed insulated glass unit, minimum 6.4 mm, outer clear laminated tempered

    safety glass, interpane space, inner lite of clear laminated tempered safety glass with low emissivity coating on No. 5 surface.

    B. Glass Type GL-2 1. Double glazed insulated glass unit, minimum 6.4 mm, tinted glass outerlite, interpane

    space, clear glass inner lite with low emissivity coating on No. 3 surface. C. Glass Type GL-3

    1. 6.4 mm clear tempered glass inner lite, tinted.

    8. SECTION 09760

    Part 2.2C, add the following subsection: 2. Applicators for Cemkote Flex CR shall be on the approved applicators list. Employees undertaking the work shall be provide the Contract Administrator on-site proof, in the form of Approved Installer Card.

    9. SECTION 11116 PIPNG VALVES AND FITTINGS

    a) GA Industries is an acceptable manufacturer of the following products listed in Section 11116: a. 2.12 Air Relase Valves b. 2.13 Air/Vacuum Valves c. 2.16 Mud Valves d. Flanged Butterfly Valves

    10. SECTION 11280

    a) 2.3.A Orbinox is to be added as an acceptable supplier b) Clause 3.4.B Section 11280 shall be replaced with For the maximum seating heads as specified,

    the leakage shall not exceed 0.62 L/min/meter (0.05 gpm per foot) of seating perimeter. For the maximum unseating heads as specified, the leakage shall not exceed 1.24 L/min per meter (0.1 gpm per foot) of the seating perimeter.

    11. SECTION 11300

    2.2A Revise minimum underflow solid concentration (w/w) to 1% for BWW thickeners

    12. SECTION 11420

    Section 1.1A.1 should read Four (4) sludge transfer pumps to convey settled sludge (SS) from the sedimentation basin at the main plant to the SS equalization basin at the residuals management facility (RMF).

    13. SECTION 11850

    a) 11850 Item 2.11B.1 Each LCP to come complete with a Stratix 5700 Ethernet switch (Part No. 1783-BMS06TL)

    b) 2.5.C.3 Section 11850 is not required. c) 2.3.A.1 Acceptable Manufacturer is Metcon Sales and Engineering Ltd.

    14. SECTION 11900

    Acceptable Manufacturers includes SPIRAL Engineering, ATARA, KWS

    15. SECTION 13100

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 4

    a) Contractor to supply and install a new Total Chlorine Residual Analyzer (EAW_CLF00_AT1) as shown on the new Section 13100, Appendix 1-3 data sheet and associated sketches attached.

    b) In addition, 120VAC power for this new analyzer is to be run from SCP20, as well as a twisted, shielded pair cable tied to a spare Analog Input point on PLC20 for chlorine residual indications and a 2C 120VAC signal cable tied to a spare Discrete Input point on PLC20 for analyzer fault signal.

    16. SECTION 13100 APPENDIX 1-3

    a) EAW_UPS20 is identified in the table as 3-phase. This unit is to be single phase b) Pg 17 Ultrasonice Sludge Blanket Level Transmitters model number to be 2020 XT c) See updated appendix 1-3 sheets attached

    17. SECTION 1700

    See Revised Appendix Sections Attached: Appendix 1-2 Appendix 1-3 Appendix 1-4

    PART III: DRAWING AMENDMENTS

    18. D603

    Drawing identifies removal of existing buildings, the contractor is responsible for disposal of all material associated with building removal.

    19. D602

    The new 150mm dia. Service waterline identified to be installed within the centreline of the existing roadway is to be connected to a new watermain constructed by others

    20. S603

    Notes Delete Note 4 and replace with: 4. Coating system for wet to dry area (positive side) shall be Cem Kote Flex CR. See specifications for application requirements.

    21. S610

    Section 1 (right side) Delete reference for anchor plate detail on Dwg S610. Replace reference for anchor plate detail with Dwg S992.

    22. S612

    Section 3 Replace the reinforcing steel arrangement (left wall / top slab) with the detail illustrated at the right wall / top slab of Section 3.

    23. S613

    Section 5 Provide hooked S35M dowels from the wall to the truck bay slab at Gridline D (similar to those illustrated at Gridline C) Sections 6 and 7

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 5

    Provide hooked S35M dowels from the wall to the truck bay slab at Gridline D (similar to those illustrated at Gridline C)

    24. S616

    Polymer Room Plan Delete the vertical waterstop illustrated at the junction of the containment curb and the exterior wall at Gridline A. Typical Exterior Wall Section W1 Typical Intermediate Roof/Wall Detail Typical Low Roof/Wall Detail Replace references to Galvanized veneer ties with Stainless Steel veneer ties (typical for all locations).

    25. S617

    Section 14 Delete 150x150 Concrete Pedestal for Grating Support. Delete 2-15M dowels (for Concrete Pedestal support) Add 300x150 Concrete Pedestal for Grating Support Add 2-15M dowels into concrete (for Concrete Pedestal support)

    26. S701

    Sections 1 and 2 Delete note Slope as per geotextile Replace note with Slope according to Geotechnical recommendations and OHSA requirements.

    27. S990

    Detail Crack Control Reinforcement at Walls/Slab Intersection The following clarification is provided. The additional reinforcing need only applied to below grade walls that serve as a liquid retention function and on all exterior walls.

    28. S996

    Hatch Detail The following clarification is provided. References related to Bilco hatches are provided on the drawing. Equivalent heavy duty products are accepted from two additional suppliers.

    29. PROCESS DRAWINGS

    Stainless Steel process piping is identified in Dwg DI601 Pipe Material Identification In DWG D705 and other process drawings process piping identified as SS3 is equivalent to SS1 and pipe identified as SS4 is equivalent to SS2

    30. DRAWING REVISIONS

    See attached sketches: a) 60246477-SKE-30-D-SK-06 b) 60246477-SKE-30-D-SK-07 c) 60246477-SKE-30-D-SK-08

    Part IV: Contractor Clarifications Q: When is the Signed Notice of Designated Substances required? A: Notice of Designated Substances is to be provided at document execution as per IT-6 clause 13(g)

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 6

    Q: Is the viscosity of 0.5% polymer solution really 8000cps? Or 800? A: The design of polymer preparation systems shall consider the two base polymers as specified. Ashland A3040L solution (as 0.5% active) has a viscosity value larger than 8,000 cp. Q: Can you confirm if we are to include both the building permit fee and the development fee in our costs? A: The building permit fee is to be included in the contact. The Municipality of Central Elgin has confirmed there is no development fee associated with the site. Q: Can you confirm the scope of work covered by the landscaping allowance? A: Landscaping allowance are for items not identified in the contract. Items associated with this item are to be determined during construction (i.e. additional tree planting at the discretion of the owner). Q: As per Spec Section 15260 Thermal Insulation for Piping Domestic Cold Water, Hot Water and Horizontal Sanitary Drainage Requires Insulation. Can you please indicate if any Process Piping requires Insulation? If so, Please indicate which System, Insulation Type, Thickness and Jacketing. A: No process piping insulation is required Q1 There is no specification for EAW_UPS30 (shown on drawing for chemical area EAW_NCP30) , and have assumed it to be the same as EAW_UPS20 (from drawing for Residual Control Area EAW_NCP20), Both are shown on GENERAL SCADA Network Architecture, sheet DI620. Please advise. A: See Section 17100, Appendix 1-4, Page 5 for the data sheet for EAW_UPS30. Q: Will complete Auto-CAD drawings/revit model be provided to the successful contractor w/o charge? A: Select AUTOCAD drawings may be provided to the selected contractor when deemed necessary. No revit model drawings will be supplied. Q: On Page 9 in Section 13100, bullet item 3 reads: "All related SCADA screens and functionality shall also be duplicated on the EAWTP main SCADA server located in the EAWTP control room." Should this not read "All related SCADA screens and functionality shall also be duplicated on the EAWTP main redundant SCADA servers located in the EAWTP control room." for clarity? A: Correct redundant SCADA servers Q: Still on the same paragraph, it further reads: "System integrator is also responsible for configuration of the quantity two (2) wireless view nodes being supplied under this contract." Are these wireless view node to be configured to provide viewing for the entire plant (meaning linked to the plant main SCADA) or simply to view RMF process only? A: Wireless view nodes are to be configured to show all WTP SCADA screens (including new RMF screens) via FactoryTalk View client/server connection. The wireless view nodes are not to be configured as standalone SCADA nodes, strictly as clients retrieving/polling the SCADA screens from the main plants Redundant SCADA Servers. Q: Will there be any plant VantagePoint Historian reporting integration of the data collected by the standalone SCADA server in the RMF? If so will there be a requirement to also integrate these to the existing Data Center (Museum) VantagePoint application? A: VantagePoint Historian reporting integration of the new RMF standalone SCADA server is required and integration into the existing Data Center (Museum) VantagePoint application is also required. Q: Will there be a requirement to update the existing AssetCenter with the new documentation generated from this project?

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 7

    A:Yes Q: Is there a list identifying which CPU models and firmware versions are going to be supplied by the vendors of packaged systems? A:Not available at this time. Q: On page 11 in Section 13100, bullet item E.2 (For Packaged Systems): It is not made clear that the scope of work listed under the heading is the responsibility of the packed system vendor and not the System Integrator. Please clarify. A: Section 13100, Item 1.6.E.2 is describing the scope of work for the Packaged Systems vendor not the System Integrator. System integrator must coordinate with the Packaged Systems vendors for all required communications between the RMF PLC and vendor PLCs and the System Integrator is also responsible for development of SCADA screens for the Packaged Systems Q: Spec 13100 1.4.A details that contractor is to conform to SCADA Standards. The website shows documents are under revision. What are the revisions and release dates for the specifications to be used? System integrators are to conform to the current version of the SCADA standards, available at the following website: http://www.watersupply.london.ca/Consultant_Resources.html. Should any revisions to these standards occur during the timeframe of the Contract, the System Integrator is to review the revisions and inform the Consultant/Owner of any additional costs that would be incurred to meet the new revisions to the SCADA Standards. The Consultant/Owner will then decide if the System Integrator is to proceed with the changes via issuance of a change order. Current versions of the Standards are as follows:

    a. Section 100 Version 5, January 2011 b. Section 200 Version 7, March 2013 c. Section 300 Version 5, January 2011 d. Section 400 Version 8, May 2013 e. Section 500 Version 6, January 2011

    Q Spec 13100 1.4.a details the contractor is to follow the standards for tagging, documentation, drawings, control system and hardware, PLC programming, control panel installation and OIT/SCADA programming. Are web-services including reports, remote access and historian services also include? A: Yes Q: If yes to question 2 please provide details what is to be included on the reports, how many variables, how many reports are required. All new analog input points and SCADA alarms that are a part of this contract will require reporting. Daily, Monthly, Yearly reports must also be integrated into the plant VantagePoint application as well as at Museum London. Q: If the reports are all new please provide a template to follow. A template will be provided following commencement of the Contract. Q: Specifications 13100 1.5.4.D details the system is Allen Bradley Logix PLCs and FactoryTalk View SE. Please confirm there are no other software programming requirements. All software required to complete Question 2 above shall also be included in the System Integrators scope of work. This shall include Rockwell Software Transaction Manager to pass all analytical data (min, max, avg) to the SQL database at 5 minute intervals. This data is also to be stored in PLC memory in one (1) second intervals averaged over five (5) minutes. Rockwell Automation AssetCenter shall be used to back up all PLC programs, OIT and SCADA software. Rockwell Automation VantagePoint

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 8

    software shall also be used as a Web Server application. SCADA overview screens for all new works in this Contract must be integrated into the VantagePoint application running at Museum London. Q: Specification 13100 1.5.4.D details the communication is by plant Ethernet network. Please detail any network programming requirements. All new Ethernet switches shown on the SCADA network architecture (drawing DI620) are to be configured/programmed by the System Integrator, with assistance from the Consultant, Owner and Vendor Package suppliers as required. Q: Specification 13100 details the system integrator is responsible for design, network configuration, programming, testing and commissioning association with project. Confirm the System integrator's responsibility is limited to supply but not installation of SCPs. Contractor is responsible for installation of SCP panels. Q: Specification 13100 1.5.C.1 details PLC programming for System Integrator is restricted to PLC20. Confirm no other panels require programming by system integrator. A: Yes Q: Specification 13100 1.5.c details a minimum of two weeks time for control software installation. Confirm System Integrator is to carry 80 hours for software installation. Minimum of 2 weeks is the requirement for this activity. System Integrator to determine if additional time is required above this minimum time requirement based on the System Integrators scope of work. Q: Specification 13100 1.5.c.3 details SCADA programming of vendor equipment is by System Integrator. Confirm SCADA programming is intended to mean the Factory Talk View graphics and communication to Vendor Supplied communication map. Confirm all vendor panels are capable of communication with Factory Talk directly. Confirm System Integrator will not be required to complete any PLC programming for vendor units. Confirm vendor units are to be programmed as black boxes showing On/Off status and alarms only. If vendor units require more status provided a detailed list of every point (analog or discrete, read or write) to be communicated such that the Factory Talk View programming can be appropriately estimated for this contract. SCADA programming for vendor equipment entails development of SCADA screens and communication mapping to vendor PLCs. All vendor PLCs in this project are Allen-Bradley CompactLogix PLCs that can communicate directly with SCADA, with the exception of the Centrifuges. For the Centrifuges, the System Integrator will be responsible for mapping vendor PLC registers over to PLC20 to be used for related SCADA screens. It has been confirmed with the Centrifuge Vendor that the vendors PLC can communicate directly with PLC20 over Ethernet. The System Integrator is not responsible for any programming of Vendor supplied PLCs. Vendor units are NOT to be programmed on SCADA as Black Boxes. Utilize the Contract P&IDs and PCN provided to determine level of effort for development of SCADA screens for these vendor systems. For the sludge scraper systems (SCP30, SCP31 - PanelView Plus 1000), the Centrifuges (SCP21, SCP22 - 2Touch HMI), and the Polymer preparation systems (SCP27, SCP28 - PanelView Plus 600), the vendor supplied and programmed OIT screens functionality are to be duplicated on SCADA screens. Work closely with the Vendor Package suppliers to ensure proper functionality and monitoring of the Vendor package systems on SCADA. Shop drawing information for both the Sludge Scraper systems and the Centrifuges was also included in the Tender package and provides further details on all vendor I/O points for these packages. Please note that for the sludge scraper systems, the vendors control panels will also be controlling the sedimentation sludge transfer pumps and associated instrumentation, which is not currently shown on the shop drawings included in the Tender package. The additional I/O points for these pumps are: 31 DI, 12 DO, 8 AI and 3 AO for each control panel (SCP30, SCP31), for a total of 62 DI, 24 DO, 16 AI and 6 AO.

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 9

    Q: Specification 13100.15.6 details the hardware and software in vendor subsystems must confirm to Client SCADA standards. Who is responsible for confirming this? What is required to prove reasonably they conform? Vendor conformance to the SCADA standards will be the responsibility of the Contractor with the Owner/Consultant ensuring that the Standards are followed during the Shop Drawing reviews and Software FAT testing. Q Specification 13100.2.8.C makes references to remote capability. Is the system integrator responsible to configure remote monitoring capability. Is this referencing the ability to Go Online with the controller from the SCADA workstation? If not provide clarification as to what the intended function is. This item is detailing that communications between the SCADA system and the PLCs shall be by Ethernet communications. Q: Specification 17100 states the System Integrator is responsible for configuration of Ethernet switches. Confirm the System Integrator is not specifically responsible for Supply of the Ethernet switches or WAP. The Contractor is responsible for the supply and installation of all required Ethernet Switches and WAP panels. Contractor ask (1) 20A 120V breaker for existing panel LPL2. I cannot find panel LPL in the drawings, please let me know where it is on the drawings. Also is the existing panel manufactured by Eaton? If so I need to know what type of panel it is(i.e. PRL1a) and what the kA rating required is? LPL2 is on drawing E301. Panel is EATON PRL1a. Match existing breakers BAB 10kAIC. LPL2 shop drawing attached.

    Existing panel LP-D, shown on E-310, whos panel is it? Eaton? Need to know the type of panel and kA rating. Contractor to confirm exact type. Existing 5kV swgr, in the spec its stated that its Eaton. Can pictures of the rating label be sent to us and also if you can locate the shop order # for it So that we can pull up our shop drawings to make sure the new section is quoted and manufactured correctly. Picture of label attached. Shop drawings of switchgear As builts, attached. Shop order # CMMU0322 / CALW06446 Elgin Area.

    Existing MCC-13, spec states that its Eaton. Can you supply pictures of the rating label and confirm the shop order # for the MCC. Also please confirm that there is enough space for a 400A feeder breaker to be added? It takes up 4X space. Picture attached of MCC-13. Shop order # 37B661503. There is sufficient space for 4X space. MCC spec, section 16225 article 2.01.J, states that the starters are to have C440 OL relays but the schematic drawings show it as a C441. Please clarify which type of OL relay is required, C440 or C441? The O/L relay is intended as the C441 Motor Insight Overload relay as per the drawings.

    Is the OPTIM550 trip unit really required on the main breaker of MCC-31, as stated in the spec? If so is it only because of the devicenet communication capabilities? The specification for the main breaker in Sesction 16225 Motor Control Centre, Part 2 Products, Sub-section 2.01.I.1 shall be deleted and replaced with the following: The main breaker shall be an 800A with RMS sensing solid state trip unit with Long, Short and Instantaneous Time settings and Ground Fault protection settings. Changing the breakers continuous rating shall be accomplished by the use of a

  • ELGIN AREA WATER TREATMENT PLANT RESIDUAL MANAGEMENT FACILITY ADDENDUM BULLETIN NO. 1

    Page 10

    mechanically interlocked rating plug, with no exposure to live parts. The breakers interrupting rating shall be 25kA RMS Symmetrical at 600V. The main breaker section shall come complete with provisions for pad-locking the main breaker and sealing screws on the front cover. Grounding shall be with a removable disconnect link to ground the neutral, service conduit, and system ground. Main breaker shall include diagnostic information for cause and magnitude of trips and DeviceNet connectivity for communications of breaker status, cause of trip and magnitude of trip. MCC spec calls for FDC feeder breakers, section 16225 article 2.01.L, but the kA rating shown on the SLD is 25kA therefor we can use HFD. FDC breakers are 35kA rated while the HFD breakers are 25kA rated. Please confirm if HFD breakers can be used instead of the FDC? 25kA amps interrupting current breakers may be used on the 600VAC systems. Only ABB is specified as an approved manufacturer for the active harmonic filter. Can Eaton be added as an acceptable manufacturer? We can supply Eaton HCU series active harmonic filters. Equivalent Active Harmonic Filters may be substituted.

    If Eaton is acceptable for the active harmonic filters, we can have it integrated inside the MCC so that it does not have to be a lose item outside the MCC. Please confirm if we can proceed with this option? Equivalent Active Harmonic Filters may be substituted and may be integrated in the MCC. The following suppliers have requested to be listed as alternatives to the contract. They will not be approved for tender; however the bidder may apply for approval according to the terms outlined in the contract including section 01630 Equivalents and Alternatives.

    CIF and BedcoLab lab furniture per 12310 Indachem and Acrison Inc for polymer system per 11850 Rotech pumps per 11420 Carlisle Coatings & Waterproofing (CCW) per 07100 Siemens for Magnetic Flow Meters and Temperature Transmitters Hach for UltraSonic Sludge Blanket Level Transmitter

    This addendum is to be signed by the Contractor and provided at the time of execution.

    Issued by:

    AECOM Citi Plaza 250 York Street, Suite 410 London, ON N6A 6K2 Tel: (519) 673-0510 Fax: (519) 673-5975

    Signed by:

    Contractor/Company Date P:\60246477\400-Technical Information & Discipline Work In Progress\450-Tender Documents\450.2-Addenda\Addendum Bulletin No 1.doc

  • DI612

    M

    M

    M

    M

    M

    BACKWASH WASTE

    THICKENER/CLARIFIER

    CLF01

    BACKWASH WASTE

    THICKENER/CLARIFIER

    CLF02

    THICKENER

    VENDOR PACKAGE

    DI603

    DI607

    DI612

    30

    0-B

    TS

    -S

    S1

    300-BTS-SS1

    100-BCS-SS2

    20-POL-PVC80

    20-POL-PVC80

    200-BWW-SS1

    200-BWW-SS1

    DI603

    SS

    CLF01_AT2

    CLF02_AT2

    CLF02_FT1

    CLF01_FT1

    CLF01_MX1

    CLF01_0C1

    CLF02_0C1

    CLF01_AT1_FAULT

    TRANSMITTER FAULT

    CLF01_AT1_STAAI

    TSS INDICATION

    CLF01_FT1_STAAI

    FLOW INDICATION

    CLF01_FT1_FAULT

    TRANSMITTER FAULT

    CLF02_FT1_STAAI

    FLOW INDICATION

    CLF02_FT1_FAULT

    TRANSMITTER FAULT

    CLF02_AT1

    CLF01_AT1

    RMF

    FROM BACKWASH

    WASTE TRANSFER

    PUMP BWP03

    FROM POLYMER

    SYSTEM

    FROM BACKWASH

    WASTE TRANSFER

    PUMP BWP01

    FROM POLYMER

    SYSTEM

    TO

    DISCHARGE

    TO THICKENED

    SLUDGE HOLDING

    TANKS

    M

    M

    200x250

    200x250

    M

    M

    400x300

    SS

    400x300

    200x100

    300x350

    DI606

    FROM SEDIMENTATION

    SLUDGE THICKENERS

    DISCHARGE

    300-CTS-SS1

    350-BTS-SS1

    CLF02_AT1_FAULT

    TRANSMITTER FAULT

    CLF02_AT1_STAAI

    TSS INDICATION

    CLF01_IC1

    CLF02_IC1

    CLF01_IC1_FAULT

    FAULT STATUS

    CLF01_IC1_CLOSD

    CLOSED STATUS

    CLF01_IC1_OPEND

    OPENED STATUS

    CLF01_IC1_REMOT

    LOCAL/REMOTE STATUS

    CLF01_IC1_CLOSE

    CLOSE COMMAND

    CLF01_IC1_OPENN

    OPEN COMMAND

    CLF02_IC1_FAULT

    FAULT STATUS

    CLF02_IC1_CLOSD

    CLOSED STATUS

    CLF02_IC1_OPEND

    OPENED STATUS

    CLF02_IC1_REMOT

    LOCAL/REMOTE STATUS

    CLF02_IC1_CLOSE

    CLOSE COMMAND

    CLF02_IC1_OPENN

    OPEN COMMAND

    M

    M M

    CLF01_MX2

    CLF02_MX1 CLF02_MX2

    CLF02_SLC

    THICKENER

    VENDOR PACKAGE

    SS

    SS

    CS CS CS

    CS CS CS

    VENDOR

    CONTROL PANEL

    SCP23

    VENDOR

    CONTROL PANEL

    SCP24

    CLF01_SLC

    M

    SS

    M

    SS

    CLF02_FT2

    CLF02_AT3

    CLF01_FT2

    CLF01_AT3

    TO BWW

    EQUALIZATION

    BASIN

    N/C

    100-BCS-SS2

    200x100

    TO BWW

    EQUALIZATION

    BASIN

    NOTE 2

    NOTE 2

    CL2

    CLF00_AT1_STAAI

    CL2 RESIDUAL INDICATION

    CLF00_AT1_FAULT

    TRANSMITTER FAULT

    RE

    SID

    UA

    LS

    M

    AN

    AG

    EM

    EN

    T F

    AC

    IL

    IT

    Y

    EL

    GIN

    A

    RE

    A W

    AT

    ER

    T

    RE

    AT

    ME

    NT

    P

    LA

    NT

    Pro

    je

    ct N

    o.: 6

    02

    46

    47

    7

    DA

    TE

    :N

    o.:

    La

    st sa

    ve

    d b

    y: K

    OH

    LE

    RS

    (2

    01

    3-1

    1-0

    7) L

    ast P

    lo

    tte

    d: 2

    01

    3-1

    1-0

    7

    File

    na

    me

    : P

    :\6

    02

    46

    47

    7\0

    00

    -C

    AD

    D\0

    40

    C

    AD

    D-B

    IM

    W

    IP

    \0

    3-S

    KE

    TC

    HE

    S\D

    -P

    RO

    CE

    SS

    \6

    02

    46

    47

    7-S

    KE

    -3

    0-D

    -S

    K0

    6.D

    WG

    P &

    I D

    EF

    FL

    UE

    NT

    W

    AT

    ER

    CH

    LO

    RIN

    E R

    ES

    ID

    UA

    L A

    NA

    LY

    ZE

    R

    60

    24

    64

    77

    -S

    KE

    -3

    0-D

    -S

    K-0

    62

    01

    3-1

    1-0

    7

    REFERENCE DRAWING: DI 605

    ADDITION OF SAMPLE LINE

    ANALYZER, FLUSHING

    CONNECDTION AND

    SAMPLE/DRAIN PORT

  • MAIN FLOOR

    213.25 m

    PUMP ROOM FLOOR

    204.55 m

    T.W.L. BWW

    209.98 m

    RESIDUALS MANAGEMENT FACILITY

    ELGIN AREA WATER TREATMENT PLANT

    Project No.: 60276477

    DATE: No.:

    La

    st sa

    ve

    d b

    y: K

    OH

    LE

    RS

    (2

    01

    3-1

    1-0

    7) L

    ast P

    lo

    tte

    d: 2

    01

    3-1

    1-0

    7

    File

    na

    me

    : P

    :\6

    02

    46

    47

    7\0

    00

    -C

    AD

    D\0

    40

    C

    AD

    D-B

    IM

    W

    IP

    \0

    3-S

    KE

    TC

    HE

    S\D

    -P

    RO

    CE

    SS

    \6

    02

    46

    47

    7-S

    KE

    -3

    0-D

    -S

    K0

    7.D

    WG

    PROCESS

    EFFLUENT WATER

    CHLORINE RESIDUAL MONITORING

    60246477-SKE-30-D-SK-072013-11-07

    350-BTS-SS1

    EFFLUENT WATER

    TO PLANT DISCHARGE

    CHLORINE

    RESIDUALS

    ANALYZER

    15mm PVC

    SAMPLE LINE

    FLUSHING CONNECTION

    PROVIDE 9mm SERVICE

    WATER LINE

    FUNNEL FLOOR

    DRAIN

    REFERENCE DRAWING: D618

    ELEVATION - PUMP ROOM WEST WALL

    Scale 1:50

    DRAIN & SAMPLE PORT

    PVC FUNNEL AND DRAIN

    LINE TO FLOOR DRAIN

  • GRADE EL. 212.95

    75

    07

    50

    50

    01

    00

    0

    A A

    B

    B

    PLAN

    SECTION A-A SECTION B-B

    C/L EL. 210.90

    55

    0

    2400mm X 3000mm PRECAST

    VALVE CHAMBER

    700 1700

    250mm SED SLUDGE BYPASS

    TO PLANT DRAIN

    250mm TO SED. SLUDGE

    EQUALIZTION TANK No. 1

    250mm TO SED. SLUDGE

    EQUALIZTION TANK No. 2

    22

    50

    75mm PVC FROM SUMP

    TO PLANT DRAIN

    NOTES:

    1. 2400 x 3000mm PRECAST VALVE CHAMBER TO BE

    CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH

    OPSD 1101.016, 1101.017, 1101.018, 1101.019

    2. ALL PIPE WITHIN CHAMBER 316L SS SCH 40s

    3. SEE CIVIL DRAWINGS FOR BURIED PIPE DETAILS

    4. PRECAST VALVE CHAMBER TO BE WATERTIGHT

    150mm GRANULAR 'A' OVER

    300mm GRANULAR 'B' BEDDING

    COMPACTED TO 98% MAX DRY DENSITY

    GRANULAR 'B' BACKFILL TO BE

    PLACED IN 300mm LIFTS AND COMPACTED

    THROUGHOUT TO 95% MAX DRY DENSITY

    CAST IRON RECTANGULAR

    FRAME AND GRATE

    OPSD 402.030

    ZSL

    ZSL

    FLOAT SWITCH

    SELF ADHERING WATER PROOFING MEMBRANE

    MEL-ROL OR EQUAL

    50mm STYROFOAM INSULATION

    ADHERE TO INTERIOR OF CHAMBER

    15

    00

    ALUMINUM LADDER

    OPSD 404.010

    250mm FROM SEDIMENTATION

    BASINS

    VC

    VC

    VC

    EL. 210.90

    RE

    SID

    UA

    LS

    M

    AN

    AG

    EM

    EN

    T F

    AC

    IL

    IT

    Y

    EL

    GIN

    A

    RE

    A W

    AT

    ER

    T

    RE

    AT

    ME

    NT

    P

    LA

    NT

    Pro

    je

    ct N

    o.: 6

    02

    46

    47

    7

    DA

    TE

    :N

    o.:

    La

    st sa

    ve

    d b

    y: K

    OH

    LE

    RS

    (2

    01

    3-1

    1-0

    8) L

    ast P

    lo

    tte

    d: 2

    01

    3-1

    1-0

    8

    File

    na

    me

    : P

    :\6

    02

    46

    47

    7\0

    00

    -C

    AD

    D\0

    40

    C

    AD

    D-B

    IM

    W

    IP

    \0

    3-S

    KE

    TC

    HE

    S\D

    -P

    RO

    CE

    SS

    \6

    02

    46

    47

    7-S

    KE

    -3

    0-D

    -S

    K0

    8.D

    WG

    PR

    OC

    ES

    S

    SE

    DIM

    EN

    TA

    TIO

    N S

    LU

    DG

    E

    VA

    LV

    E C

    HA

    MB

    ER

    D

    ET

    AIL

    S

    60

    24

    64

    77

    -S

    KE

    -3

    0-D

    -S

    K-0

    82

    01

    3-1

    1-0

    7

    REFERENCE DRAWING: D706

    SEDIMENTATION SLUDGE VALVE CHAMBER

    Scale 1:50

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    Low Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CLF01_AT1/AE EAW_CLF01_AT2/AE EAW_CLF02_AT1/AELocation: Residuals Management Facility Residuals Management Facility Residuals Management Facility

    Service:Backwash Waste Clarifier CLF01

    Inlet TSS AnalyzerBackwash Waste Clarifier CLF01

    Outlet TSS AnalyzerBackwash Waste Clarifier CLF02 Inlet

    TSS AnalyzerVessel/line No.: 200-BWW-SS 300-BTS-SS 200-BWW-SS

    Process:

    Fluid:Backwash Waste Backwash Waste Thickener Supernatant Backwash Waste

    Temp min/max: 0.5 / 25 deg. C 1 / 25 deg. C 0.5 / 25 deg. CSoild Range 0 - 280 mg/L 0 - 25 mg/L 0 - 280 mg/L

    Sensor: Sensor Type: Inline Inline Inline

    LED Scattered Light LED Scattered Light LED Scattered LightElement Submersible MLSS Probe Submersible MLSS Probe Submersible MLSS Probe

    Cable Length As required As required As requiredCompensation Automatic Automatic Automatic

    Mounting Rail Mounted Rail Mounted Rail MountedOptions c/w 316 SS brackets, accessory kit c/w 316 SS brackets, accessory kit c/w 316 SS brackets, accessory kit

    & all fittings & mounting hardware & all fittings & mounting hardware & all fittings & mounting hardwarec/w Jct Box & Env. Conn. c/w Jct Box & Env. Conn. c/w Jct Box & Env. Conn.

    & Cleaning System & Cleaning System & Cleaning SystemTransmitter:

    Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication Single Channel c/w LCD Indication Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )

    Four Sets of On/Off Control Relays Four Sets of On/Off Control Relays Four Sets of On/Off Control Relays1 fault relay 1 fault relay 1 fault relay

    Power Supply: 120 VAC, 60 Hz 120 VAC, 60 Hz 120 VAC, 60 HzEnclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X Field Mounted NEMA 4X

    Calibr. Range: 0 - 300 mg/L 0 - 30 mg/L 0 - 300 mg/LAccuracy: +/- 5% of reading +/- 5% of reading +/- 5% of reading

    Options

    Electrical:Approval: CSA CSA CSA

    Enclosure: NEMA 4X NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories, tubing, valve and enclosure requried to mount TSS sensor andtransmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: YSI/WTW Hach Engineer Approved Equal

    Supplier:Model Number: ViSolid 700 IQ and 2020XT TSS sc Tri-Clamp and SC200

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 2 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    Low Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CLF02_AT2/AE EAW_CLF03_AT2/AE EAW_CLF04_AT2/AELocation: Residuals Management Facility Residuals Management Facility Residuals Management Facility

    Service:Backwash Waste Clarifier CLF02

    Outlet TSS AnalyzerSedimentation Sludge Thickener

    CLF03 Outlet TSS AnalyzerSedimentation Sludge Thickener

    CLF04 Outlet TSS AnalyzerVessel/line No.: 300-BTS-SS 200-CTS-SS 200-CTS-SS

    Process:

    Fluid:Backwash Waste Thickener

    SupernatantClarifier Sludge Thickener

    SupernatantClarifier Sludge Thickener

    SupernatantTemp min/max: 1 / 25 deg. C 1 / 25 deg. C 1 / 25 deg. C

    Soild Range 0 - 25 mg/L 0 - 50 mg/L 0 - 50 mg/LSensor:

    Sensor Type: Inline Inline InlineLED Scattered Light LED Scattered Light LED Scattered Light

    Element Submersible MLSS Probe Submersible MLSS Probe Submersible MLSS ProbeCable Length As required As required As required

    Compensation Automatic Automatic Automatic Mounting Rail Mounted Rail Mounted Rail Mounted

    Options c/w 316 SS brackets, accessory kit c/w 316 SS brackets, accessory kit c/w 316 SS brackets, accessory kit& all fittings & mounting hardware & all fittings & mounting hardware & all fittings & mounting hardware

    c/w Jct Box & Env. Conn. c/w Jct Box & Env. Conn. c/w Jct Box & Env. Conn.& Cleaning System & Cleaning System & Cleaning System

    Transmitter: Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication Single Channel c/w LCD Indication

    Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )Four Sets of On/Off Control Relays Four Sets of On/Off Control Relays Four Sets of On/Off Control Relays

    1 fault relay 1 fault relay 1 fault relayPower Supply: 120 VAC, 60 Hz 120 VAC, 60 Hz 120 VAC, 60 Hz

    Enclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X Field Mounted NEMA 4XCalibr. Range: 0 - 30 mg/L 0 - 100 mg/L 0 - 100 mg/L

    Accuracy: +/- 5% of reading +/- 5% of reading +/- 5% of readingOptions

    Electrical:Approval: CSA CSA CSA

    Enclosure: NEMA 4X NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories, tubing, valve and enclosure requried to mount TSS sensor andtransmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: YSI/WTW Hach Engineer Approved Equal

    Supplier:Model Number: ViSolid 700 IQ and 2020XT TSS sc Tri-Clamp and SC200

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 3 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    High Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CLF01_AT3/AE EAW_CLF02_AT3/AE EAW_CLF03_AT1/AELocation: Residuals Management Facility Residuals Management Facility Residuals Management Facility

    Service:Backwash Waste Clarifier CLF01

    Outlet TSS AnalyzerBackwash Waste Clarifier CLF02

    Outlet TSS AnalyzerSedimentation Sludge Thickener

    CLF03 Inlet TSS AnalyzerVessel/line No.: 100-BCS-SS 100-BCS-SS 200-CS-SS

    Process:

    Fluid:Backwash Waste Thickener

    Thickened SludgeBackwash Waste Thickener

    Thickened Sludge Clarifier Sludge

    Temp min/max: 1 / 25 deg. C 1 / 25 deg. C 0.5 / 25 deg. CSoild Range 0 - 4% TSS 0 - 4% TSS 0 - 1.5% TSS

    Sensor: Sensor Type: Flow-through Inline Flow-through Inline Flow-through Inline

    Microwave "time of flight" Microwave "time of flight" Microwave "time of flight"Process Connection: 4" ANSI 600 Flange 4" ANSI 600 Flange 8" ANSI 600 Flange

    Sensor Material: 316 SS 316 SS 316 SSCable Length As required As required As required

    Compensation Automatic Automatic Automatic Enclosure Class: NEMA 4X NEMA 4X NEMA 4X

    Options

    Transmitter: Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication Single Channel c/w LCD Indication

    Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )1 fault relay 1 fault relay 1 fault relay

    Power Supply: 120 VAC, 60 Hz 120 VAC, 60 Hz 120 VAC, 60 HzEnclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X Field Mounted NEMA 4X

    Calibr. Range: 0 - 5% TSS 0 - 5% TSS 0 - 2% TSSRepeatability: +/- 0.01 %Cs +/- 0.01 %Cs +/- 0.01 %Cs

    Sensitivity: +/- 0.001 %Cs +/- 0.001 %Cs +/- 0.001 %CsOptions

    Electrical:Approval: CSA CSA CSA

    Enclosure: NEMA 4X NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories requried to mount TSS sensor and transmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Metso

    Supplier:Model Number: Metso TS and TCU

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 4 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    High Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CLF03_AT3/AE EAW_CLF04_AT1/AE EAW_CLF04_AT3/AELocation: Residuals Management Facility Residuals Management Facility Residuals Management Facility

    Service:Sedimentation Sludge Thickener

    CLF03 Outlet TSS AnalyzerSedimentation Sludge Thickener

    CLF04 Inlet TSS AnalyzerSedimentation Sludge Thickener

    CLF04 Outlet TSS AnalyzerVessel/line No.: 200-CCS-SS 200-CS-SS 200-CCS-SS

    Process:

    Fluid:Clarifier Sludge Thickener

    Thickened Sludge Clarifier SludgeClarifier Sludge Thickener Thickened

    SludgeTemp min/max: 1 / 25 deg. C 0.5 / 25 deg. C 1 / 25 deg. C

    Soild Range 0 - 4% TSS 0 - 1.5% TSS 0 - 4% TSSSensor:

    Sensor Type: Flow-through Inline Flow-through Inline Flow-through InlineMicrowave "time of flight" Microwave "time of flight" Microwave "time of flight"

    Process Connection: 8" ANSI 600 Flange 8" ANSI 600 Flange 8" ANSI 600 FlangeSensor Material: 316 SS 316 SS 316 SS

    Cable Length As required As required As requiredCompensation Automatic Automatic Automatic

    Enclosure Class: NEMA 4X NEMA 4X NEMA 4XOptions

    Transmitter: Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication Single Channel c/w LCD Indication

    Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )1 fault relay 1 fault relay 1 fault relay

    Power Supply: 120 VAC, 60 Hz 120 VAC, 60 Hz 120 VAC, 60 HzEnclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X Field Mounted NEMA 4X

    Calibr. Range: 0 - 5% TSS 0 - 2% TSS 0 - 5% TSSRepeatability: +/- 0.01 %Cs +/- 0.01 %Cs +/- 0.01 %Cs

    Sensitivity: +/- 0.001 %Cs +/- 0.001 %Cs +/- 0.001 %CsOptions

    Electrical:Approval: CSA CSA CSA

    Enclosure: NEMA 4X NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories requried to mount TSS sensor and transmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Metso

    Supplier:Model Number: Metso TS and TCU

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 5 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    High Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CEN01_AT1/AE EAW_CEN02_AT1/AELocation: Residuals Management Facility Residuals Management Facility

    Service:Centrifuge CEN01 Inlet TSS

    AnalyzerCentrifuge CEN02 Inlet TSS Analyzer

    Vessel/line No.: 150-SLU-SS 150-SLU-SSProcess:

    Fluid: Blended Sludge Blended SludgeTemp min/max: 1 / 25 deg. C 1 / 25 deg. C

    Soild Range 0 - 5% TSS 0 - 5% TSSSensor:

    Sensor Type: Flow-through Inline Flow-through InlineMicrowave "time of flight" Microwave "time of flight"

    Process Connection: 6" ANSI 600 Flange 6" ANSI 600 FlangeSensor Material: 316 SS 316 SS

    Cable Length As required As requiredCompensation Automatic Automatic

    Enclosure Class: NEMA 4X NEMA 4XOptions

    Transmitter: Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication

    Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )1 fault relay 1 fault relay

    Power Supply: 120 VAC, 60 Hz 120 VAC, 60 HzEnclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X

    Calibr. Range: 0 - 5% TSS 0 - 5% TSSRepeatability: +/- 0.01 %Cs +/- 0.01 %Cs

    Sensitivity: +/- 0.001 %Cs +/- 0.001 %CsOptions

    Electrical:Approval: CSA CSA

    Enclosure: NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories requried to mount TSS sensor and transmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Metso

    Supplier:Model Number: Metso TS and TCU

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 6 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    High Total Suspended Project No. 60246477Solids Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_RSP10_AT1/AE EAW_RSP20_AT1/AELocation: Chemical Area Chemical Area

    Service:

    Sediment Transfer Pumps RSP11 and RSP12 Discharge TSS Analyzer

    Sediment Transfer Pumps RSP21 and RSP22 Discharge TSS Analyzer

    Vessel/line No.: 250-CS-SS 250-CS-SSProcess:

    Fluid: Blended Sludge Blended SludgeTemp min/max: 0.2 / 25 deg. C 0.2 / 25 deg. C

    Soild Range 0 - 2% TSS 0 - 2% TSSSensor:

    Sensor Type: Flow-through Inline Flow-through InlineMicrowave "time of flight" Microwave "time of flight"

    Process Connection: 10" ANSI 600 Flange 10" ANSI 600 FlangeSensor Material: 316 SS 316 SS

    Cable Length As required As requiredCompensation Automatic Automatic

    Enclosure Class: NEMA 4X NEMA 4XOptions

    Transmitter: Type: Single Channel c/w LCD Indication Single Channel c/w LCD Indication

    Output: 4 - 20 mA isol. (600 ) 4 - 20 mA isol. (600 )1 fault relay 1 fault relay

    Power Supply: 120 VAC, 60 Hz 120 VAC, 60 HzEnclosure: Field Mounted NEMA 4X Field Mounted NEMA 4X

    Calibr. Range: 0 - 3% TSS 0 - 3% TSSRepeatability: +/- 0.01 %Cs +/- 0.01 %Cs

    Sensitivity: +/- 0.001 %Cs +/- 0.001 %CsOptions

    Electrical:Approval: CSA CSA

    Enclosure: NEMA 4X NEMA 4XClass/Div/Grp: N/A N/A

    Notes: 1) Follow all manufacturer's recommendations for installation, calibration, and cabling distance limitations. 2) Provide calibration and training program by Manufacturer's Service Technician, and two year warranty.

    3) Provide all mounting hardware.4) Provide all hardware accessories requried to mount TSS sensor and transmitter.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Metso

    Supplier:Model Number: Metso TS and TCU

    Installation:Serial No.:

    Calibration:Zero/Low:

    Span/High:Verification:

    Date:Signature:

    Page 7 of 25

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 13100Appendix 1-3

    Total Chlorine Project No. 60246477Residual Analyzer Rev: 0

    7-Nov-13

    Tag No: EAW_CLF00_AT1 Location: Residuals Management Facility

    Service:

    Backwash Waste Clarifier CLF01 & CLF02 Supernatant Discharge

    (Combined) Analyzer

    Vessel/line No.: 350-BTS-SS1Process:

    Fluid:Backwash Waste Thickener

    SupernatantTemp min/max: 0.5 / 25 deg. C

    Density: ~1Conductivity: Variable

    Sensor: Sensor Type: Colorimetric DPDCable length: Field To DetermineDrain Fitting: Std.

    Process Conn: Std.Mounting: Wall

    Accessories: 1 Year Maintenance KitCAL/Verification Kit

    Transmitter: Output: 4 - 20 mA isolated (600 )

    Power Supply: 120 VAC - 60 HzEnclosure: ABS Plastic, IP62Indication: Local , 3 1/2 digit display

    Calibr. Range: 0 to 0.5 mg/LAccuracy: 5%

    Options:Electrical:

    Approval: CSAEnclosure:

    Class/Div/Grp: N/ANotes: 1.Supply and deliver residual chlorine analyzer, capable of accurate measurement of total residual chlorine.

    2. Supply and install all required process connections, valves, pressure / flow regulators, filters, and misc mounting hardware not provided with analyzer, and mount along with the analyzer on a skid.3. Provide a Junction Box c/w terminal blocks (and 4-20 ma isolators if req'd) and wire all process signals to the J.B.4. Supply one (1) year supply of consumables and spare parts.5. General Contractor to provide all sample piping and associated fittings from the skid to the process line.

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Hach

    Supplier:Model Number: CL17 Total Chlorine Analyzer

    Installation:Serial No.:

    Calibration: Provide ISO CertifiedZero/Low: Calibration Certificate

    Span/High:Verification:

    Date:Signature:

    Page 1 of 1

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 17100Appendix 1-2

    Project No. 60246477Rev: 0

    October-2013

    Fibre Optic Patch CableQty: As required each with a color-coded PVC buffer for easy installation.

    The cable shall not contain metallic elements.

    Manufacture: CorningModel/Part Number: 1) 055002T5120002M: Fiber Optic Jumper, 2 F, LC Duplex to ST Compatible,

    Zipcord Tight-Buffered Cable, Riser, with 2.0 mm legs, 50 m multimode (OM3), 2 m

    * Confirm compatible products with manufacturer.* Adhere to manufacturer's installation instructions* Refer to Specification 17100

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Corning Engineer Approved Equal

    Supplier:Model Number: See Above

    Installation:Serial No.:

    Verification:Date:

    Signature:

    The cable shall be reinforced with Aramid yarn for superior strength.

    Fibre Optic Cable(Patch Cable)

    Quantity Description

    Multimode 50/125 um Fibre Optic Cable

    Page 2 of 3

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 17100Appendix 1-3

    Project No. 60246477Rev: 0

    October-2013

    24 Port Ethernet SwitchQty: 1

    Building.

    Model/Part Number: WS-C3750V2-24PS-S (Cisco Catalyst)Port Attributes: 24 Ethernet 10/100 PoE ports and 2 x 1G SFP

    PoE configurations with up to 15.4W per port (370W Total)1 RU fixed-configurationIP Base software feature set

    Performance: Forwarding Rate 6.5 mppsVLAN: Max 1000 VLANs

    Input Power: 100-240 VACOperating Temperature: -5C to 45C

    Operating Relative Humidity: 10% to 95% non-condensingDimensions: 1.73" H x 17.5" W x 11.6" D (44mm x 443mm x 295mm)

    Follow manufacturers installation instructions

    SFP Module Small Form-Factor Pluggable ModuleQty: 2 Installed in Cisco 3750 Series Switch

    Model/Part Number: GLC-SX-MM Description: 1000 Base-SX multi-mode transceiver

    Wavelength: 850 nmCore Cladding: 62.5/125 & 50/125

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Cisco

    Supplier:Model Number: Cisco Catalyst 3750

    Installation:Serial No.:

    Verification:Date:

    Signature:

    Follow manufacturers installation instructions

    Installed in Wall Mount Rack in NEW Communications Panel (EAW_NCP20) in New RMF

    24 Port IndustrialEthernet Switch

    Quantity Description

    24 Port Managed Ethernet Switch

    Page 4 of 6

  • ELGIN AREA WATER SUPPLY SYSTEMElgin Area Water Treatment Plant - Residuals Management Facility

    Section 17100Appendix 1-4

    Project No. 60246477Rev: 0

    October-2013

    6 Port Ethernet SwitchQty: 1

    Area - Sedimentation Basins Area

    Model/Part Number: Rockwell Stratix 5700 1783-BMS06SGL (Rockwell)Port Attributes: 4 Ethernet 10/100 ports & 2 SFP Ports

    Input Power: 0.5-2.0A max @ 12-48VDCPower Consumption: 9.5 W @ 24V DC

    Outputs: 1 A @ 30V DC Alarm relay

    Operating Temperature: -40 - C60 COperating Relative Humidity: 5% to 95% non-condensing

    Dimensions: 5.1" H x 2.94" W x 4.59" D (129.5mm x 74.8mm x 116.7mm)

    Follow manufacturers installation instructions

    SFP Module Small Form-Factor Pluggable ModuleQty: 2 Installed in Rockwell Stratix 5700 Managed Switch

    Model/Part Number: 1783-SFP100FXDescription: 100Base-SX multi-mode transceiver

    Wavelength: 1310 nmCore Cladding: 62.5/125 & 50/125

    Manufacturer: 1st Named Named Alternate Named AlternateManufacturer: Rockwell

    Supplier:Model Number: Stratix 5700

    Installation:Serial No.:

    Verification:Date:

    Signature:

    Follow manufacturers installation instructions

    Installed in Wall Mount Panel in NEW Communications Panel (EAW_NCP30) in Chemical

    6 Port IndustrialEthernet Switch

    Quantity Description

    6 Port Managed Ethernet Switch

    Page 3 of 6

  • Master Document Index

    Cutler-Hammer Medium Voltage Assemblies

    MVA 5 kV Lineup

    GO-ITEM: CALW06446-003 File/Rev: MM001I49.HTM/4 SO Number: PO Number:

    Designation: GS1 SWGR Customer: CALW06446 Elgin Area

    User: tayloba Date: 3/26/2009 10:06:33 AM

    Approval: Construction: As-Built: X

    Drawing Description Document Name Rev 1 Master Drawing List MM001I49.DOC 4

    2 Certified Production Test Report - MVA M90006O9.DOC 1

    3 NAMEPLATES MK826I1Y0101.DOC 3 4 KEY LOCK SCHEDULE MK826I1K0101.DOC 3 5 BILL OF MATERIAL MK826I1P0101.DOC 3 6 LEGEND LEGEND-GWD.DWG 5 7 POWER FLOW MK826I1L0101.DWG 4 8 END VIEW MK826I1O0101.DWG 3 9 PLAN VIEW MK826I1Q0101.DWG 3 10 FRONT VIEW MK826I1F0101.DWG 3 11 SECTIONAL SIDE VIEW MK826I1V0101.DWG 3 12 SECTIONAL SIDE VIEW MK826I1V0201.DWG 3 13 SECTIONAL SIDE VIEW MK826I1V0301.DWG 3 14 SECTIONAL SIDE VIEW MK826I1V0401.DWG 3

    15 ELECTRICAL MASTER DRAWING MK826I1E0101.DWG 2

    16 ELECTRICAL MASTER DRAWING MK826I1E0102.DWG 2

    17 SCHEMATIC DIAGRAM MK826I1S0101.DWG 2 18 SCHEMATIC DIAGRAM MK826I1S0201.DWG 2 19 SCHEMATIC DIAGRAM MK826I1S0301.DWG 2 20 SCHEMATIC DIAGRAM MK826I1S0401.DWG 3 21 THREE LINE DIAGRAM MK826I1T0101.DWG 3 22 WIRING DIAGRAM MK826I1W0101.DWG 2 23 WIRING DIAGRAM MK826I1W0102.DWG 2 24 WIRING DIAGRAM MK826I1W0201.DWG 2 25 WIRING DIAGRAM MK826I1W0202.DWG 2 26 WIRING DIAGRAM MK826I1W0301.DWG 1 27 WIRING DIAGRAM MK826I1W0302.DWG 2 28 WIRING DIAGRAM MK826I1W0401.DWG 2 29 WIRING DIAGRAM MK826I1W0402.DWG 2

  • M90006O9.DOC

    Certified Test Report Medium Voltage Assemblies

    Cutler-Hammer, 2210 Highway 72/221 East, Greenwood, SC 29648

    GO NO.: CALW06446 ITEM (S): 003 CUSTOMER ORDER NO.: 037966 EQUIPMENT DESIGNATION: GS1 SWGR REFERENCE DRAWINGS: CERTIFICATION: The test below reflect the requirements in ANSI/IEEE C37.20.2 CSA C22.2 No. 31-04 and EEMAC G11-1 for inspections and production testing. TESTING:

    PASSED DOES NOT APPLY

    v Actual operation performed wherever possible, inspection or continuity checks made.

    X

    v Component devices operated as shown on diagrams. X v Control bus energized as 80% rated D-C or 85% A-C control

    voltage. X

    v Control devices operated as shown on diagrams. X v Verification of all remote circuits and spare contacts which

    were not included in operational test. X

    v Unless otherwise reported, protective relays, and other associated equipment functionally tested by energizing current and potential circuits to rated values.

    X

    v Instruments operated, expected readings verified. X v Electro-mech watt hour meters checked for proper direction of

    disc rotation and current circuits for phasing. X

    v Protective relays operated for functional check in accordance with rating and application. Instantaneous trips manually operated to verify correct functioning of operation indicator and associated circuits.

    X

    v Relays set and checked for operation within range of test equipment

    X

    v Control circuits and associated wiring received insulation test of 1500 volts, 60 cycles for one minute, except where equipment manufacturer specifications do not permit.

    X

    v Primary insulation tested at (19K VAC, 60Hz RMS). X v Primary insulation tested at (36K VAC, 60Hz RMS). X v Primary insulation tested at (60K VAC, 60Hz RMS). X v Primary insulation tested at (80K VAC, 60Hz RMS). X v The corona pulse magnitude was less than 100pC when tested

    at a corona-extinction voltage of 3.5 KV. X

  • M90006O9.DOC

    v The corona pulse magnitude was less than 100pC when tested at a corona-extinction voltage of 5.5 KV.

    X

    v The corona pulse magnitude was less than 100pC when tested at a corona-extinction voltage of 10.5 KV.

    X

    v The corona pulse magnitude was less than 100pC when tested at a corona-extinction voltage of 19.5 KV.

    X

    v The corona pulse magnitude was less than 100pC when tested at a corona-extinction voltage of 26.5 KV.

    X

    This certifies that the above is based upon recorded factory tests made at this location. David T Taylor Tester 3/16/2009 Date

  • NAMEPLATES

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1Y0101 GO. : CALW06446-003

    ITEM: 003 SHEET 1

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: NAMEPLATES

    CIRCUIT NAMEPLATES FRONT AND REAR OF SWITCHGEAR

    4.32 x 1.00 [109.7 x 25.4] SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20 [5.1]

    Maximum number of characters per line 18

    ID LINE ONE LINE TWO LINE THREE TOTAL QTY

    C01A F5 ELECTRICAL ROOM BUILDING POWER T2 2 C01D SPARE 2 C02A F8 LOW LIFT BUILDING 2 C02D F7 HIGH LIFT BUILDING 2 C03A G1 LINE VTS 2 C03D G1 5KV GENERATOR 2 C04A L1 LINE AND BUS VTS 2 C04D L1 MAIN INCOMING 2

    EXTERIOR DEVICE NAMEPLATES 2.50 X .75 SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20

    Maximum number of characters per line 18

    ID LINE ONE LINE TWO TOTAL QTY

    D019A TS-1 ION 7550 2 D019B TS-2 G60 2 D022A 11G-1 1 D023A 11F-2 1 D026A 11F-1 1 D044A G-1 METERING 2 D231A TS-1 TEST SWITCH 4

    INTERIOR DEVICE NAMEPLATES

    2.50 X .75 SCREW MOUNTED NAMEPLATES WHITE WITH BLACK LETTERS 0.20 Maximum number of characters per line 18

    ID LINE ONE LINE TWO TOTAL QTY

    D003 BKR CLOSE CKT 20 AMP 6 D007 BUS V.T.S 1 D017 LINE V.T.S 2 D200 BKR TRIP CKT 30 AMP 6

    D600A G60 PWR SUPPLY 3 AMP FUSE 2 D600B ION 7550 PWR SUPPLY 3 AMP FUSE 2 D600C INSULGARD PWR SUPPLY 3 AMP FUSE 1 D600D F35 PWR SUPPLY 3 AMP FUSE 1 D600E IDEC PWR SUPPLY 3 AMP FUSE 1 D600F 125 VDC INPUT/ 24 VDC OUTPUT 1

  • NAMEPLATES

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1Y0101 GO. : CALW06446-003

    ITEM: 003 SHEET 2

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: NAMEPLATES

    ID NP ENGRAVING

    G.O: CALW06446 Manufactured in: GREENWOOD,SC, USA Date of Mfr.: 01/15/2009

    Item: 003 Rated Freq: 60 Phases: 3 Shop Order: 72YK826 Rated Max Voltage: 4.76kV

    Type: VC-W Power Frequency Withstand: 19 kV BIL: 60 kV MAIN BUS CURRENT RATINGS

    Continuous: 1200A Momentary,RMS Asymmetrical: 57.6 KA RMS 2 Second Short Time: 36kA

    Enclosure Type: 1 Enclosure Category: C Instructions: IB 32-255-1 3A38498H01

  • KEY LOCK SCHEDULE

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON.

    FILENAME : MK826I1K0101 GO. : CALW06446-003

    ITEM: 003 SHEET 1

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: KEYLOCK

    ITEM NO.

    CATALOG NO.

    TYPE PROJ. EXTENDED / WITHDRAWN

    INT LOCK NO.

    NOTE WHERE USED VS NO.

    H01 KFL000010S EE 0 EE K2 BREAKER PAN ASSEMBLY 03 H02 KFL000010S EE 0 EE K4 BREAKER PAN ASSEMBLY 04 H03 KDL000020S EE 0 EE K2,K3 UPPER REAR DOOR 03 H04 KDL000020S EE 0 EE K4,K5 UPPER REAR DOOR 04

    1. System works with one key of each stamping.

    2. Customer to secure all spare keys.

    3. Sequence of operation: Keys K2 and K4 are held captive if the breaker is racked into the connected position. Once either breaker G1 or L1 is racked out to the test/disconnected position, then keys K2 or K4 can be released. Keys K2 and K4 can then be taken to rear cable compartment lock. Keys K3 and K5 are held captive at the remote switch. Opening the remote switch(Lock Out) will then release either Key K3 or K5. Inserting keys K2, K3 or K4, K5 into the specific lock will unlock the rear cable compartment door. Keys K2, K3 and K4,K5 are held captive in the lock while the door is unlocked.

    PURCHASE FROM ----- KIRK KEY COMPANY

    ULTIMATE USER ----- ELGIN AREA WTP

    LOCATION ----- PORT STANLEY,ON

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 1

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    VERTICAL SECTION 01 2 3A84048H01 RELAY, CH, PD-SENSOR, RFCT 3/4

    W/50 FT CBL 1WR,1ZR

    2 HWK-100-C-L MISC, HAWK, INFRARED SIGHTGLASS WINDOW, 4 IN

    1WV,1ZV

    2 3A40354G02 50 VCPW 250, 1200A BREAKER, 60HZ, UL, 125VDC C/M/T

    1AB,1DB

    2 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B CONN ONLY

    1AM,1DM

    3 6353C89H01 CT, ABB, SCVD 50/5 HI-ACC C10 1AP 2 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B

    WIRED 1AT,1DT

    D003,D003 2 3A40335G17 PROT/CTRL, CH, PULL FUSE W/2 20 AMP FUSES

    1BA,1CA

    D200,D200 2 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30 AMP FUSES

    1BB,1CB

    3 6353C89H08 CT, ABB, SCVD 400/5 HI-ACC C100 1DP 2 8718C31H05 MISC, GWD, PLEXIGLASS VIEWING

    WINDOW 5 X 6.5 X .25 1HA,1PF

    2 2452D SWITCH, ELS, SER 24, BKR CTRL, PULL-TO-LOCK HNDL 5-ST

    1HB,1PD

    D231A,D231A 2 C129A521G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 2 POTENTIAL

    1HC,1PE

    2 3A40275G36 LIGHT, CH, E22-LED, IND LT ASSY GREEN LED 125V

    1HD,1PA

    2 3A40275G46 LIGHT, CH, E22-LED, IND LT ASSY RED LED 125V

    1HE,1PB

    1 3A84591G03 SWITCH, ELS, 24-SEL, 4-STG, 2-POS W/NP LOCAL-REMOTE

    1PC

    3 8264A16H10 COMPONENT, WES, TERMINAL 250 KCM COMPRESSION

    1WL

    1 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 1WZ 6 1C17370H01 CABLE BOOTS FOR TERMINALS FOR

    1200A 1-2 PHASES 1WB,1ZB

    1 8264A16H09 COMPONENT, WES, TERMINAL 4/0 AWG COMPRESSION

    1ZG

    3 8264A16H14 COMPONENT, WES, TERMINAL 500 KCM COMPRESSION

    1ZL

    VERTICAL SECTION 02 6 PVI30005 ARRESTER, PV, 6KV INTERMEDIATE

    CLASS 2WA,2ZA

    3 3A84048H01 RELAY, CH, PD-SENSOR, RFCT 3/4 W/50 FT CBL

    2WR,2ZR,2DX

    2 HWK-100-C-L MISC, HAWK, INFRARED SIGHTGLASS WINDOW, 4 IN

    2WV,2ZV

    2 3A40354G02 50 VCPW 250, 1200A BREAKER, 60HZ, UL, 125VDC C/M/T

    2AB,2DB

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 2

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    2 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B CONN ONLY

    2AM,2DM

    6 6353C89H08 CT, ABB, SCVD 400/5 HI-ACC C100 2AP,2DP 2 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B

    WIRED 2AT,2DT

    1 810-112-020 COMM, 6M FIBER OPTIC CABLE, MULTIMODE, ST TO ST

    2HI

    D600D 1 3A40335G05 PROT/CTRL, CH, PULL FUSE 2P W/ 2 3 AMP FUSES

    2BB

    D003,D003 2 3A40335G17 PROT/CTRL, CH, PULL FUSE W/2 20 AMP FUSES

    2BC,2CA

    D200,D200 2 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30 AMP FUSES

    2BD,2CB

    2 8718C31H05 MISC, GWD, PLEXIGLASS VIEWING WINDOW 5 X 6.5 X .25

    2HA,2PF

    2 3A84591G03 SWITCH, ELS, 24-SEL, 4-STG, 2-POS W/NP LOCAL-REMOTE

    2HB,2PC

    2 2452D SWITCH, ELS, SER 24, BKR CTRL, PULL-TO-LOCK HNDL 5-ST

    2HC,2PD

    D023A 1 3A84784H01 RELAY , MUL , F35 , F35-S03-HCH-F8F-H6D-M8H-P6C-U6D-W2S

    2HD

    1 3A40615H01 RELAY, MUL, BEZEL FOR UR-SERIES RELAYS, FLUSH MOUNT

    2HE

    D231A,D231A 2 C129A521G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 2 POTENTIAL

    2HF,2PE

    2 3A40275G36 LIGHT, CH, E22-LED, IND LT ASSY GREEN LED 125V

    2HG,2PA

    2 3A40275G46 LIGHT, CH, E22-LED, IND LT ASSY RED LED 125V

    2HH,2PB

    6 1C17370H01 CABLE BOOTS FOR TERMINALS FOR 1200A 1-2 PHASES

    2WB,2ZB

    6 UI006005065BB21 ARRESTER, CPS, 6KV INTERMEDIATE CLASS

    2WA,2ZA

    6 8264A16H14 COMPONENT, WES, TERMINAL 500 KCM COMPRESSION

    2WL,2ZL

    2 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 2WZ,2ZZ

    VERTICAL SECTION 03 1 3A84048H01 RELAY, CH, PD-SENSOR, RFCT 3/4

    W/50 FT CBL 3ZR

    D017 1 923A302G02 VT, ABB, 2VT L-L ASSY, 60KV BIL, 4200:120V, 36W, 4-FUSE

    3AA

    4 7186A29G02 PRI-FUSE, ITI, 5.5KV 1E .81 DIA 3AF 1 K826LKH04 KEY INTERLOCK BKR PAN 3DK

    D600F 1 PS5R-SC24 IDEC POWER SUPPLY MODEL PS5R (30 WATT)

    3CA

    D600E,D600B,D600A

    3 3A40335G05 PROT/CTRL, CH, PULL FUSE 2P W/ 2 3 AMP FUSES

    3CB,3CC,3CD

    D003 1 3A40335G17 PROT/CTRL, CH, PULL FUSE W/2 20 AMP FUSES

    3CF

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 3

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    D200 1 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30 AMP FUSES

    3CG

    1 3A40354G02 50 VCPW 250, 1200A BREAKER, 60HZ, UL, 125VDC C/M/T

    3DB

    1 HWK-100-C-L MISC, HAWK, INFRARED SIGHTGLASS WINDOW, 4 IN

    3ZV

    1 K826LKH03 KEY INTERLOCK REAR DOOR 3AK 1 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B

    CONN ONLY 3DM

    6 6353C89H08 CT, ABB, SCVD 400/5 HI-ACC C100 3DP,3DS 1 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B

    WIRED 3DT

    D022A 1 3A84783H01 RELAY , MUL , G60 , G60-S03-HCH-F8F-H6D-M8F-P6E-U5D-W2S

    3HA

    1 3A40275G36 LIGHT, CH, E22-LED, IND LT ASSY GREEN LED 125V

    3PA

    1 3A40275G46 LIGHT, CH, E22-LED, IND LT ASSY RED LED 125V

    3PB

    1 3A84591G03 SWITCH, ELS, 24-SEL, 4-STG, 2-POS W/NP LOCAL-REMOTE

    3PC

    1 2452D SWITCH, ELS, SER 24, BKR CTRL, PULL-TO-LOCK HNDL 5-ST

    3PD

    D019B,D019A 2 C129A514G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 4 POTENTIAL

    3PE,3PF

    1 3A40615H01 RELAY, MUL, BEZEL FOR UR-SERIES RELAYS, FLUSH MOUNT

    3HB

    D044A 1 7550B0C0B6F0A0A METER, PML, 7550 ION W/ ETHERNET/FIBER OPTIC

    3PH

    1 8718C31H05 MISC, GWD, PLEXIGLASS VIEWING WINDOW 5 X 6.5 X .25

    3PI

    3 1C17370H01 CABLE BOOTS FOR TERMINALS FOR 1200A 1-2 PHASES

    3ZB

    6 8264A16H10 COMPONENT, WES, TERMINAL 250 KCM COMPRESSION

    3ZL

    1 8264A16H09 COMPONENT, WES, TERMINAL 4/0 AWG COMPRESSION

    3ZY

    VERTICAL SECTION 04 1 7797C93G03 COMPONENT, MECH CABLE INTLK

    ,BKR BESIDE BKR VCP-W 4DC

    1 3A84048H01 RELAY, CH, PD-SENSOR, RFCT 3/4 W/50 FT CBL

    4ZR

    1 HWK-100-C-L MISC, HAWK, INFRARED SIGHTGLASS WINDOW, 4 IN

    4ZV

    3 PVI30005 ARRESTER, PV, 6KV INTERMEDIATE CLASS

    4ZA

    D017,D007 2 923A302G02 VT, ABB, 2VT L-L ASSY, 60KV BIL, 4200:120V, 36W, 4-FUSE

    4AA,4BA

    8 7186A29G02 PRI-FUSE, ITI, 5.5KV 1E .81 DIA 4AF,4BF 1 K826LKH02 KEY INTERLOCK BKR PAN 4AK

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 4

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    1 810-112-026 COMM, 8M FIBER OPTIC CABLE, MULTIMODE, ST TO ST

    4HC

    D600B,D600A 2 3A40335G05 PROT/CTRL, CH, PULL FUSE 2P W/ 2 3 AMP FUSES

    4CB,4CC

    D600C 1 3A40335G04 PROT/CTRL, CH, PULL FUSE 2P W/ 3 AMP FUSE

    4CD

    D003 1 3A40335G17 PROT/CTRL, CH, PULL FUSE W/2 20 AMP FUSES

    4CE

    D200 1 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30 AMP FUSES

    4CF

    1 3A40354G02 50 VCPW 250, 1200A BREAKER, 60HZ, UL, 125VDC C/M/T

    4DB

    1 K826LKH01 KEY INTERLOCK REAR DOOR 4DK 1 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B

    CONN ONLY 4DM

    6 6353C89H08 CT, ABB, SCVD 400/5 HI-ACC C100 4DP,4DS 1 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B

    WIRED 4DT

    D026A 1 3A84783H01 RELAY , MUL , G60 , G60-S03-HCH-F8F-H6D-M8F-P6E-U5D-W2S

    4HA

    1 3A40275G36 LIGHT, CH, E22-LED, IND LT ASSY GREEN LED 125V

    4PA

    1 3A40275G46 LIGHT, CH, E22-LED, IND LT ASSY RED LED 125V

    4PB

    1 3A84591G03 SWITCH, ELS, 24-SEL, 4-STG, 2-POS W/NP LOCAL-REMOTE

    4PC

    1 2452D SWITCH, ELS, SER 24, BKR CTRL, PULL-TO-LOCK HNDL 5-ST

    4PD

    D019B,D019A 2 C129A514G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 4 POTENTIAL

    4PE,4PF

    1 3A40615H01 RELAY, MUL, BEZEL FOR UR-SERIES RELAYS, FLUSH MOUNT

    4HB

    D044A 1 7550B0C0B6F0A0A METER, PML, 7550 ION W/ ETHERNET/FIBER OPTIC

    4PH

    1 INSPK82604 RELAY,CH,INSULGARD, CHPD60026 4PI 1 8718C31H05 MISC, GWD, PLEXIGLASS VIEWING

    WINDOW 5 X 6.5 X .25 4PJ

    3 1C17370H01 CABLE BOOTS FOR TERMINALS FOR 1200A 1-2 PHASES

    4ZB

    3 8264A16H10 COMPONENT, WES, TERMINAL 250 KCM COMPRESSION

    4ZL

    2 8264A16H09 COMPONENT, WES, TERMINAL 4/0 AWG COMPRESSION

    4ZY,4ZG

    MISCELLANEOUS 6 73482AJ00D PROT/CTRL, BUS, FUSE 3 AMPERE

    CONTROL SPARE

    6 73482AJ00K PROT/CTRL, BUS, FUSE 20 AMPERE CONTROL

    SPARE

    6 7186A29G02 PRI-FUSE, ITI, 5.5KV 1E .81 DIA SPARE

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 5

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    6 73482AJ00M PROT/CTRL, BUS, FUSE 30 AMPERE CONTROL

    SPARE

    2 7813C41G03 RAIL EXTENSION LH/RH COMP 1 8346A28G22 TEST CABINET, CH, AC/DC CLOSE, DC

    TRIP COMP

    2 6511C83G01 RAIL CLAMP, CH, FOR 5/15/27KV VCPW SWITCHGEAR

    COMP

    1 REF700B214 SWITCHGEAR STORAGE INSTRUCT DWG

    COMP

    2 8064A02G01 HANDLE ASSY COMP 2 701B601G03 BREAKER, CH, LEV-IN CRANK W/

    CLUTCH CLOSED DOOR COMP

    2 701B601G01 BREAKER, CH, LEV-IN CRANK W/ CLUTCH

    COMP

    2 69B1003H01 NAMEPLATE, GWD, ARC FLASH LABEL COMP 2 6526C23G11 TEST JUMPER, CH, VCPW, 5/15/27KV COMP 1 5676B22H01 SEISMIC CERTIFICATE COMP 1 32220WA00K MISC, PAINT, ANSI 61, 9OZ AEROSOL COMP 1 1C19086H01 LIFT DEVICE, CH, BREAKER COMP 2 691C607G01 BREAKER LIFTING YOKE, CH, VCPW

    5/15/27KV 36IN-WIDE COMP

    2 RP02201001E INSTRUCT , CH , RENEWAL-PARTS LEAFLET, 5/15KV

    SP

    VERTICAL SECTION SUMMARY 6 3A40354G02 50 VCPW 250, 1200A BREAKER, 60HZ,

    UL, 125VDC C/M/T 1AB,1DB,2AB,2DB,3DB,4DB

    3 6353C89H01 CT, ABB, SCVD 50/5 HI-ACC C10 1AP 21 6353C89H08 CT, ABB, SCVD 400/5 HI-ACC C100 1DP,2AP,2DP,3DP,3DS,4DP,4DS 12 7186A29G02 PRI-FUSE, ITI, 5.5KV 1E .81 DIA 3AF,4AF,4BF

    D007D017, 3 923A302G02 VT, ABB, 2VT L-L ASSY, 60KV BIL, 4200:120V, 36W, 4-FUSE

    3AA,4AA,4BA

    6 2452D SWITCH, ELS, SER 24, BKR CTRL, PULL-TO-LOCK HNDL 5-ST

    1HB,1PD,2HC,2PD,3PD,4PD

    6 3A40275G36 LIGHT, CH, E22-LED, IND LT ASSY GREEN LED 125V

    1HD,1PA,2HG,2PA,3PA,4PA

    6 3A40275G46 LIGHT, CH, E22-LED, IND LT ASSY RED LED 125V

    1HE,1PB,2HH,2PB,3PB,4PB

    3 3A40615H01 RELAY, MUL, BEZEL FOR UR-SERIES RELAYS, FLUSH MOUNT

    2HE,3PG,4PG

    5 3A84591G03 SWITCH, ELS, 24-SEL, 4-STG, 2-POS W/NP LOCAL-REMOTE

    1PC,2HB,2PC,3PC,4PC

    D022A 1 3A84783H01 RELAY , MUL , G60 , G60-S03-HCH-F8F-H6D-M8F-P6E-U5D-W2S

    3HA

    D026A 1 3A84783H01 RELAY , MUL , G60 , G60-S03-HCH-F8F-H6D-M8F-P6E-U5D-W2S

    4HA

    D023A 1 3A84784H01 RELAY , MUL , F35 , F35-S03-HCH-F8F-H6D-M8H-P6C-U6D-W2S

    2HD

    D044A 2 7550B0C0B6F0A0A METER, PML, 7550 ION W/ ETHERNET/FIBER OPTIC

    3PH,4PH

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 6

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    1 810-112-020 COMM, 6M FIBER OPTIC CABLE, MULTIMODE, ST TO ST

    2BA

    1 810-112-026 COMM, 8M FIBER OPTIC CABLE, MULTIMODE, ST TO ST

    4CA

    6 8718C31H05 MISC, GWD, PLEXIGLASS VIEWING WINDOW 5 X 6.5 X .25

    1HA,1PF,2HA,2PF,3PI,4PJ

    D019AD019B, 4 C129A514G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 4 POTENTIAL

    3PE,3PF,4PE,4PF

    D231A 4 C129A521G01 TEST SWITCH, ABB, FT-1, 3 CURRENT-PAIR, 2 POTENTIAL

    1HC,1PE,2HF,2PE

    1 INSPK82604 RELAY,CH,INSULGARD, CHPD60026 4PI D600C 1 3A40335G04 PROT/CTRL, CH, PULL FUSE 2P W/ 3

    AMP FUSE 4CD

    D600AD600B,D600D,D600E,

    6 3A40335G05 PROT/CTRL, CH, PULL FUSE 2P W/ 2 3 AMP FUSES

    2BB,3CB,3CC,3CD,4CB,4CC

    D003 6 3A40335G17 PROT/CTRL, CH, PULL FUSE W/2 20 AMP FUSES

    1BA,1CA,2BC,2CA,3CF,4CE

    D200 6 3A40335G20 PROT/CTRL, CH, PULL FUSE 2P W/2 30 AMP FUSES

    1BB,1CB,2BD,2CB,3CG,4CF

    D600F 1 PS5R-SC24 IDEC POWER SUPPLY MODEL PS5R (30 WATT)

    3CA

    1 1C19086H01 LIFT DEVICE, CH, BREAKER COMP 1 32220WA00K MISC, PAINT, ANSI 61, 9OZ AEROSOL COMP 6 3A84048H01 RELAY, CH, PD-SENSOR, RFCT 3/4

    W/50 FT CBL 1WR,2ZR,2WR,2ZR,2DX,3ZR,4ZR

    1 5676B22H01 SEISMIC CERTIFICATE COMP 2 6511C83G01 RAIL CLAMP, CH, FOR 5/15/27KV VCPW

    SWITCHGEAR COMP

    2 6526C23G11 TEST JUMPER, CH, VCPW, 5/15/27KV COMP 2 691C607G01 BREAKER LIFTING YOKE, CH, VCPW

    5/15/27KV 36IN-WIDE COMP

    2 69B1003H01 NAMEPLATE, GWD, ARC FLASH LABEL COMP 2 701B601G01 BREAKER, CH, LEV-IN CRANK W/

    CLUTCH COMP

    2 701B601G03 BREAKER, CH, LEV-IN CRANK W/ CLUTCH CLOSED DOOR

    COMP

    6 7186A29G02 PRI-FUSE, ITI, 5.5KV 1E .81 DIA SPARE 6 73482AJ00D PROT/CTRL, BUS, FUSE 3 AMPERE

    CONTROL SPARE

    6 73482AJ00K PROT/CTRL, BUS, FUSE 20 AMPERE CONTROL

    SPARE

    6 73482AJ00M PROT/CTRL, BUS, FUSE 30 AMPERE CONTROL

    SPARE

    2 7813C41G03 RAIL EXTENSION LH/RH COMP 2 8064A02G01 HANDLE ASSY COMP 1 8346A28G22 TEST CABINET, CH, AC/DC CLOSE, DC

    TRIP COMP

    1 K826LKH01 KEY INTERLOCK REAR DOOR 4DK 1 K826LKH02 KEY INTERLOCK BKR PAN 4BK

  • BILL OF MATERIAL

    HUTCHENS

    GREENWOOD

    ELGIN AREA WTP PORT STANLEY,ON. 2365-544961

    FILENAME : MK826I1P0101 GO. : CALW06446-003

    ITEM: 003 SHEET 7

    THE INFORMATION ON THIS DOCUMENT WAS CREATED BY CUTLER-HAMMER. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE IN WHICH IT WAS SUPPLIED.

    REV: 3 DESIGNATION: BILL OF MATERIAL

    DEVICE NAMEPLATE QTY

    PART NUMBER DESCRIPTION * DEVICE IDs

    1 K826LKH03 KEY INTERLOCK REAR DOOR 3DK 1 K826LKH04 KEY INTERLOCK BKR PAN 3AK 9 PVI30005 ARRESTER, PV, 6KV INTERMEDIATE

    CLASS 2WA, 2ZA, 4ZA

    1 REF700B214 SWITCHGEAR STORAGE INSTRUCT DWG

    COMP

    2 RP02201001E INSTRUCT , CH , RENEWAL-PARTS LEAFLET, 5/15KV

    SP

    6 6510C49G03 SWITCH, GWD, TOC, 9-POLE 4A-5B WIRED

    1AT,1DT,2AT,2DT,3DT,4DT

    6 6510C50G03 SWITCH, GWD, MOC, 9 POLE 5A-4B CONN ONLY

    1AM,1DM,2AM,2DM,3DM,4DM

    3 6353C97H01 ZERO SEQ CT, ABB, 50:5A C10 1WZ,2WZ,2ZZ 4 8264A16H09 COMPONENT, WES, TERMINAL 4/0

    AWG COMPRESSION 3ZY,4ZY,1ZG ,4ZG

    12 8264A16H10 COMPONENT, WES, TERMINAL 250 KCM COMPRESSION

    1WL,3ZL,4ZL

    9 8264A16H14 COMPONENT, WES, TERMINAL 500 KCM COMPRESSION

    1ZL,2WL,2ZL

    18 1C17370H01 CABLE BOOTS FOR TERMINALS FOR 1200A 1-2 PHASES

    1WB,1ZB,2WB,2ZB,3ZB,4ZB7799

    9 UI006005065BB21 ARRESTER, CPS, 6KV INTERMEDIATE CLASS

    2WA,2ZA,4ZA

    1 7797C93G03 COMPONENT, MECH CABLE INTLK ,BKR BESIDE BKR VCP-W

    4DC

    * NOTES

  • 2 3 4

  • 2 3

  • 2 3

  • 2 3

  • 2 3

  • 2 3

  • 2 3

  • 2 3

  • Elgin Area Primary Water Supply System PN 60246477 Elgin Water Treatment Plant Residuals Management Facility

    SECTION 01515 TEMPORARY UTILITIES Page 1 of 2

    SECTION 01515 TEMPORARY UTILITIES

    PART 1. GENERAL 1.1 SECTION DESCRIPTION

    .1 Includes temporary utilities to be used during construction.

    .2 Other temporary systems, such as temporary fencing, barricades, hoarding, etc. are described in other specifications throughout the contract document.

    1.2 INSTALLATION AND REMOVAL

    .1 Provide temporary utilities and controls in order to execute work expeditiously.

    .2 Remove all temporary works from site after use.

    .3 Make all necessary applications, obtain permits and pay for all fees, charges for service and use.

    1.3 WATER SUPPLY

    .1 The Contractor shall provide a continuous supply of potable water for construction use. Provide metering at tie-in location to allow Owner to assess costs to Contractor.

    1.4 TEMPORARY HEATING AND VENTILATION

    .1 Any construction heaters used inside building must be vented to the outside or be flameless type. Solid fuel salamanders are not permitted.

    .2 Provide temporary heat and ventilation in enclosed areas as required to:

    .1 Facilitate progress of the Works.

    .2 Protect the Works and products against dampness and cold.

    .3 Prevent moisture condensation on surfaces.

    .4 Provide ambient temperatures and humidity levels for storage, installation and curing of materials.

    .5 Provide adequate ventilation to meet health regulations for safe working environment.

    .3 Maintain inside temperatures above a minimum of 10C in areas where construction is in progress.

    .4 Ventilating:

    .1 Prevent accumulations of dust, fumes, mists, vapours or gases in areas occupied during construction.

  • Elgin Area Primary Water Supply System PN 60246477 Elgin Water Treatment Plant Residuals Management Facility

    SECTION 01515 TEMPORARY UTILITIES Page 2 of 2

    .2 Provide local exhaust ventilation to prevent harmful accumulation of hazardous substances into atmosphere of occupied areas.

    .3 Dispose of exhaust materials in a manner that will not result in harmful exposure to persons.

    .4 Ventilate storage spaces containing hazardous or volatile materials.

    .5 Ventilate temporary sanitary facilities.

    .6 Continue operation of ventilation and exhaust system for time after cessation of work process to assure removal of harmful contaminants.

    .5 The permanent heating system of the building may be used when available. Be responsible for damage to heating system if use is permitted.

    .6 Date of Substantial Performance and Warranties for heating system will not commence until the entire system is in as near original condition as possible and is certified by the Engineer.

    .7 Maintain strict supervision of operation of temporary heating and ventilating equipment to:

    .1 Conform with applicable codes and standards.

    .2 Enforce safe practices.

    .3 Prevent abuse of services.

    .4 Prevent damage to finishes.

    .5 Vent direct-fired combustion units to outside.

    .8 Be responsible for damage to the Works due to failure in providing adequate heat and protection during construction.

    1.5 TEMPORARY POWER AND LIGHT

    .1 The Contractor will provide and pay for temporary power during construction and temporary lighting and operating of power tools. Provide metering from tie-in location to allow Owner to assess costs to Contractor.

    1.6 TEMPORARY COMMUNICATION FACILITIES

    .1 The Contractor will prov