electromagnetic sensing techniques for multi- phase flow

129
Electromagnetic Sensing Techniques For Multi- Phase Flow Monitoring In Industrial Processes A thesis submitted to the University of Manchester for the degree of Doctor of Philosophy in the Faculty of Science and Engineering 2018 By Shupei Wang School of Electrical and Electronic Engineering

Upload: others

Post on 10-Jun-2022

23 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Electromagnetic Sensing Techniques For Multi- Phase Flow

Electromagnetic Sensing Techniques For Multi-

Phase Flow Monitoring In Industrial Processes

A thesis submitted to the University of Manchester for the degree of

Doctor of Philosophy

in the Faculty of Science and Engineering

2018

By

Shupei Wang

School of Electrical and Electronic Engineering

Page 2: Electromagnetic Sensing Techniques For Multi- Phase Flow

2

TABLE OF CONTENTS

TABLE OF CONTENTS .............................................................................................. 2

LIST OF FIGURES ...................................................................................................... 7

LIST OF TABLES ...................................................................................................... 12

NOMENCLATURE .................................................................................................... 13

ABSTRACT ................................................................................................................ 18

DECLARATION ........................................................................................................ 19

COPYRIGHT STATEMENT .................................................................................... 20

ACKNOWLEDGEMENTS ........................................................................................ 21

LIST OF PUBLICATIONS ........................................................................................ 22

Chapter 1 Introduction ........................................................................................... 23

1.1 Motivation ...................................................................................................... 23

1.1.1 Clean-In-Place (CIP)................................................................................ 23

1.1.2 Industrial oil/water separation .................................................................. 24

1.2 Aims and objectives ........................................................................................ 25

1.3 Contributions .................................................................................................. 26

1.4 Organization of thesis ..................................................................................... 28

Chapter 2 Background of Sensing Techniques in the Monitoring of Industrial

Process with Multi-Phase Flow .................................................................................. 31

2.1 Existing sensing techniques in multi-phase flow measurement ........................ 31

2.1.1 Mechanical and hydraulic sensing ............................................................ 31

Page 3: Electromagnetic Sensing Techniques For Multi- Phase Flow

3

2.1.2 Electrical sensing ..................................................................................... 32

2.1.3 Acoustic, radiative and microwave sensing .............................................. 34

2.2 Monitoring CIP with Electrical Resistance Tomography (ERT) ...................... 38

2.2.1 State-of-the-art in monitoring CIP ............................................................ 38

2.2.2 Advantages of ERT in monitoring CIP ..................................................... 39

2.3 Measuring industrial oil-water batch separation process with Differential

Electromagnetic Inductive Sensor (DEMIS) .............................................................. 40

2.3.1 State-of-the-art in measuring industrial oil-water batch separation process40

2.3.2 Advantages of DEMIS in monitoring oil separation process ..................... 46

Chapter 3 Monitoring CIP Using Electrical Resistance Tomography (ERT) with

Dynamic Reference ..................................................................................................... 47

3.1 Fundamentals of ERT ..................................................................................... 47

3.1.1 Sensitivity and forward problem .............................................................. 47

3.1.2 Inverse problem and conventional algorithms .......................................... 52

3.2 Experimental setup and principles ................................................................... 55

3.2.1 Experimental setup .................................................................................. 55

3.2.2 Experimental procedures.......................................................................... 57

3.2.3 Measurement protocol ............................................................................. 58

3.2.4 Analytical principles ................................................................................ 59

3.3 Inverse calculation results with LBP and Tikhonov regularization .................. 59

3.3.1 Linear Back Projection (LBP) .................................................................. 59

3.3.2 Tikhonov regularization ........................................................................... 61

Page 4: Electromagnetic Sensing Techniques For Multi- Phase Flow

4

3.4 Algorithm optimization with dynamic reference ............................................. 65

3.4.1 Methodology ........................................................................................... 65

3.4.2 Optimization procedure ........................................................................... 66

3.5 Image reconstruction results calculated from Tikhonov regularization with

dynamic reference ..................................................................................................... 68

3.5.1 Average conductivity values .................................................................... 68

3.5.2 Maximum conductivity values ................................................................. 69

3.5.3 Image reconstruction comparison ............................................................. 70

3.6 Adopting Tikhonov regularization with dynamic reference in different cleaning

conditions ................................................................................................................. 72

3.6.1 Results under higher flow rate with T pipe ............................................... 72

3.6.2 Results with different pipe geometries ..................................................... 73

3.7 Summary ........................................................................................................ 76

Chapter 4 Electromagnetic Simulations: Modelling Three-Coil DEMIS and Oil-

Saline Batch Separation .............................................................................................. 78

4.1 Introduction of differential electromagnetic inductive sensor .......................... 78

4.1.1 Sensor structure ....................................................................................... 78

4.1.2 Sensitivity distribution ............................................................................. 79

4.1.3 Sensitivity distribution with different vessel radii..................................... 83

4.2 Electrical model of liquid-liquid separation ..................................................... 86

4.2.1 Liquid-liquid separation model ................................................................ 86

4.2.2 Effective conductivity model ................................................................... 89

Page 5: Electromagnetic Sensing Techniques For Multi- Phase Flow

5

4.3 Simulation of the electrical liquid-liquid separation model .............................. 91

4.4 Simulation results and discussions .................................................................. 93

4.5 Summary ........................................................................................................ 96

Chapter 5 Experimental System and Results In Monitoring Oil-Water

Separation With DEMIS ............................................................................................ 99

5.1 Experimental setup and testing strategy .......................................................... 99

5.1.1 Sensor system ........................................................................................ 100

5.1.2 Mixing and separation system ................................................................ 100

5.1.3 FPGA-based impedance analyser ........................................................... 101

5.1.4 Testing strategy ..................................................................................... 103

5.1.5 Choice of parameters ............................................................................. 104

5.2 Experiment and discussion ............................................................................ 105

5.2.1 Instrument performance inspections ....................................................... 106

5.2.2 Validation of sensitivity distribution ...................................................... 106

5.2.3 Experimental result example .................................................................. 107

5.2.4 Validation of sensor output .................................................................... 109

5.2.5 Experiment results under different mixing conditions ............................ 111

5.3 Summary ...................................................................................................... 115

Chapter 6 Conclusions and Future Works ........................................................... 118

6.1 Conclusions .................................................................................................. 118

6.1.1 Monitoring CIP using ERT with dynamic reference ............................... 118

6.1.2 Measuring oil-water separation process using DEMIS ........................... 120

Page 6: Electromagnetic Sensing Techniques For Multi- Phase Flow

6

6.2 Future work .................................................................................................. 122

REFERENCES ......................................................................................................... 124

Page 7: Electromagnetic Sensing Techniques For Multi- Phase Flow

7

LIST OF FIGURES

Figure 1-1 Schematic diagram of API pilot-scale separator ......................................... 25

Figure 2-1 Venturi meter ............................................................................................. 32

Figure 2-2 Ultrasound velocity profiler ....................................................................... 34

Figure 2-3 Common approach to implement radiative sensing on MPFs...................... 36

Figure 2-4 Schematic of radiography system with multiple radiative sources and 2D

detectors ..................................................................................................................... 36

Figure 2-5 Schematics of ultrasonic techniques in fouling detection. (a) Pulse echo

technique; (b) Transmission technique. ....................................................................... 38

Figure 2-6 Monitoring oil-water separation process with sight glass ............................ 40

Figure 2-7 Monitoring oil-water separation process with motive pressure sensor......... 41

Figure 2-8. Monitoring oil-water separation process with ultrasonic sensor ................. 42

Figure 2-9 Monitoring oil-water separation process with segmented sensor array ........ 44

Figure 3-1 Electromagnetic simulation model for sensitivity matrix calculation .......... 48

Figure 3-2 Sensitivity distributions in part of the projections ....................................... 49

Figure 3-3 Simulated CIP circuit ................................................................................. 55

Figure 3-4 'T-shape' pipe with the 4 ERT planes installed ........................................... 56

Figure 3-5 Schematic diagram of a straight pipe with a butterfly valve installed inside 56

Figure 3-6 Straight pipe with a butterfly valve installed inside .................................... 57

Page 8: Electromagnetic Sensing Techniques For Multi- Phase Flow

8

Figure 3-7 Contents to be measured in the test region under each step of the simulation

test. ............................................................................................................................. 58

Figure 3-8 Maximum conductivity values in all ERT planes during the cleaning process

calculated with LBP .................................................................................................... 60

Figure 3-9 Maximum conductivity values in all ERT planes during the cleaning process

calculated with LBP .................................................................................................... 61

Figure 3-10 Maximum conductivity values in all ERT planes during the cleaning

process calculated with Tikhonov regularization ......................................................... 64

Figure 3-11 Average conductivity values in all ERT planes during the cleaning process

calculated with Tikhonov regularization ...................................................................... 64

Figure 3-12 Relationship between measured boundary voltage and material conductivity

under same projection ................................................................................................. 65

Figure 3-13 Measured boundary voltages (U curves) comparison between pure water

and pure soil. .............................................................................................................. 65

Figure 3-14 Average conductivity values calculated from Tikhonov regularization with

dynamic reference ....................................................................................................... 69

Figure 3-15 Maximum conductivity values calculated from Tikhonov regularization

with dynamic reference ............................................................................................... 70

Figure 3-16 Maximum conductivity values in smaller scale ........................................ 70

Figure 3-17 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under higher flow rate. . a) Average conductivity

Page 9: Electromagnetic Sensing Techniques For Multi- Phase Flow

9

values; b) maximum conductivity values; c) maximum conductivity values in smaller

scale. ........................................................................................................................... 72

Figure 3-18 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under 4100 L/h and butterfly valve. a) Average

conductivity values; b) maximum conductivity values; c) maximum conductivity values

in smaller scale. .......................................................................................................... 74

Figure 3-19 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under 6200 L/h and butterfly valve. a) Average

conductivity values; b) maximum conductivity values; c) maximum conductivity values

in smaller scale. .......................................................................................................... 75

Figure 4-1 Schematic of differential electromagnetic inductive sensor ........................ 78

Figure 4-2 Sensitivity distribution in the axial cross-sectional testing area of a simulated

two-coil sensor system ................................................................................................ 82

Figure 4-3 Simplified and normalized planar sensitivity distribution ........................... 84

Figure 4-4 Planar sensitivity distribution under different testing vessel radii ............... 84

Figure 4-5 Average planar sensitivity values and standard deviation under different

testing area radii .......................................................................................................... 86

Figure 4-6 (a) 4 sections defined in oil/water separation system. (b) Height change of

the boundaries of 4 sections with time ......................................................................... 87

Figure 4-7 Interface heights in a theoretical oil/saline separation model under 350RPM

and oil fraction at 50% ............................................................................................... 92

Figure 4-8 Geometry of the simulation model. (a) 3D model; (b) 2D model. ............... 92

Page 10: Electromagnetic Sensing Techniques For Multi- Phase Flow

10

Figure 4-9 Induced voltage in both receiving coils and the differential output when oil

fraction is 50% and agitation speed is 350RPM ........................................................... 93

Figure 4-10 Simulated sensor outputs of two separation process from the same liquid

system agitated with same time length and different speeds ........................................ 95

Figure 4-11 Simulated sensor outputs of two separation process from the two liquid

system with different oil fractions agitated with same time length and speed ............... 95

Figure 5-1 Experimental system setup ......................................................................... 99

Figure 5-2 (a)Hardwood rod coated with black thermal plastic tube; (b) 3D-printed

plastic impeller ......................................................................................................... 100

Figure 5-3 System block diagram .............................................................................. 101

Figure 5-4 The instrument performance for measuring a voltage signal ..................... 106

Figure 5-5 Experimental test result for vertical sensitivity distribution with saline..... 107

Figure 5-6 Single test result under 1700RPM, 30 seconds mixing and 500 seconds

separation, oil fraction 50%....................................................................................... 108

Figure 5-7 Sensor output signal during separation process ........................................ 108

Figure 5-8 Part of the screenshots from the recorded video during the separation process

................................................................................................................................. 110

Figure 5-9 Comparison between sensor output and saline interface height change during

the separation process ............................................................................................... 110

Page 11: Electromagnetic Sensing Techniques For Multi- Phase Flow

11

Figure 5-10 Sensor outputs of repeated experiments under agitation speed of 1700 RPM,

oil fraction 50%. (a) mixing duration 30 seconds; (b) mixing duration 5 minutes; (c)

mixing duration 15 minutes. ...................................................................................... 112

Figure 5-11 Average sensor outputs of the repeated test under 1700 RPM during

separation process ..................................................................................................... 113

Figure 5-12 Average sensor outputs of the repeated test under 900RPM during

separation process with error bars ............................................................................. 113

Figure 5-13 Average sensor outputs of the repeated test at oil fraction of 33% under

900RPM during separation process with error bars ................................................... 114

Page 12: Electromagnetic Sensing Techniques For Multi- Phase Flow

12

LIST OF TABLES

Table 2-1 General comparison of Electrical Tomography methods .............................. 34

Table 3-1 Adjacent strategy on 16-electrode ERT system ............................................ 58

Table 3-2 Image reconstruction results under different regularization parameters during

cleaning process for Plane 4 ........................................................................................ 62

Table 3-3 The ratio of measured voltage for each projection between the soil and water

background ................................................................................................................. 66

Table 3-4 Reconstructed image in Plane 4 comparisons between conventional and

optimized Tihonov regularization................................................................................ 71

Table 4-1 The average and standard deviation of the sensitivity values under different

test region radii ........................................................................................................... 85

Table 4-2 Experimental profiles and model parameters adopted from [96] for H0=300

mm, D=154 mm, εp=0.65, and one hour agitation time ................................................ 91

Page 13: Electromagnetic Sensing Techniques For Multi- Phase Flow

13

NOMENCLATURE

Abbreviations and Acronyms

2D 2-dimentional

3D 3-dimentional

ADC analogue-to-digital converter

API American Petroleum Institute

C4D contactless capacitively coupled conductivity detector

CCD charge-coupled device

CIP Clean-In-Place

CMR Christian Michelsen Research

DAC digital-to-analogue converter

DEMIS differential electromagnetic inductive sensor

ECT Electrical Capacitance Tomography

EIS electrolyte-insulator-semiconductors

EIT Electrical Impedance Tomography

EMT Electromagnetic Tomography

ERT Electrical Resistance Tomography

FEM finite element method

FPGA field-programmable gate array

ILMS Inductive Level Monitoring System

LBP Linear Back Projection

MFMs multi-phase flow meters

MPFs multi-phase flows

NDT non-destructive testing

RPM Revolutions per minute

SNR signal-to-noise ratio

SoC system on a chip

Page 14: Electromagnetic Sensing Techniques For Multi- Phase Flow

14

Symbols

A1 upper sensing region of the DEMIS

A2 lower sensing region of the DEMIS

A magnetic vector potential

AR magnetic vector potential at the target point when the

receiving coil is excited by unit current

AT magnetic vector potential at the target point when the

transmitting coil is excited by unit current

B magnetic flux density

dl position vector of the corresponding segment of the

coil

D separation vessel diameter

E electrical field vector

ER local electric field vectors when the other coil is

excited by unit current and the testing area is empty

ET local electric field vectors when one of the two coils is

excited by unit current and the testing area is empty

E φ electric field vector in the corresponding pixel when

electrode pair one is injecting current and electrode

pair two is measuring the voltage

E ψ electric field vector in the corresponding pixel when

electrode pair two is injecting current and electrode

pair one is measuring the voltage

g gravitational acceleration

Δh1 thickness of the dense-packed zone

hc height of the interface between clear oil zone and

dense-packed zone

hp height of the interface between dense-packed zone and

sedimentation zone

hp1 height of the interface between the dense-packed zone

and sedimentation zone prior to the inflection point

hp2 height of the interface between the dense-packed zone

and sedimentation zone anterior to the inflection point

Page 15: Electromagnetic Sensing Techniques For Multi- Phase Flow

15

hs height of the interface between sedimentation zone

and clear water zone

hsi height of the interface between sedimentation zone

and clear water zone at inflection point

H magnetic field strength

H0 initial height of dispersion

H0il thickness of the clear oil layer

I identity matrix

I amplitude of the excitation current

j voltage projection number

J current vector in the coil

Jj,k normalized sensitivity of pixel k under voltage

projection j

Jp∗w

normalized sensitivity matrix

k pixel number

k1, k2, k3, k4 fitting constants without clear physical meanings

p total number of projections

r distance between the coil elements and the target point

in sensing region

R radius of the oil droplet

R1 upper receiving coil of the DEMIS

R2 lower receiving coil of the DEMIS

Sk planar sensitivity value on the kth cross-section plane

Sk,j the sensitivity value on the kth pixel under voltage

projective j

Sr relative sensitivity in a two-coil system

Sσ local conductivity sensitivity at a spatial point in the

testing area of a two-coil sensor system

Sck sensitivity value of the cth pixel on the kth cross-section

plane

t time

ti inflection point

T transmitting coil of the DEMIS

Page 16: Electromagnetic Sensing Techniques For Multi- Phase Flow

16

v buoyance velocity of an independent sphere oil droplet

in the continuous water phase

v0 initial sedimentation velocity of oil drops

vi sedimentation velocity of oil drops at the inflection

point

Vo output voltage of the DEMIS

V1 real part of the induced complex voltages of one of the

receiving coils

V2 real part of the induced complex voltages of the other

receiving coil

Ve detected signal of the empty space

Vmm median value of the 16 chosen voltages from measured

boundary voltages

VRm median value of the 16 chosen voltages from the

reference voltages

VR,j reference voltage in projection j

V∗ voltage change vector with dynamic reference

VR∗ dynamic reference voltages corresponding to each

frame

Vp∗1 voltage change vector

α Tikhonov regularization parameter

γ ratio between the average level of the measured

voltages and the reference

ΔV perturbation of the induced voltage

∆Vj voltage change in projection j

Δσ perturbation of conductivity

∆σk conductivity change of pixel k

ε0 initial oil hold-up fraction

εp oil holdup fraction in the dense-packed zone

εs oil fraction in the sedimentation zone

μ permeability of medium

μ0 vacuum permeability

μo dynamic viscosity of oil

Page 17: Electromagnetic Sensing Techniques For Multi- Phase Flow

17

ρ0 mass density of oil

ρw mass density of water

σ1 conductivity of the first liquid

σ2 conductivity of the second liquid

σmp effective conductivity of liquid as a mixture of liquids

with two different conductivities

σmc effective conductivity in the sedimentation zone

σR reference conductivity

σR,k reference conductivity of pixel k

σα conductivity change vector calculated by Tikhonov

regularization

σw∗1 conductivity change vector

σα∗ conductivity change vector calculated by Tikhonov

regularization with dynamic reference

ω excitation signal frequency

Page 18: Electromagnetic Sensing Techniques For Multi- Phase Flow

18

ABSTRACT

Multi-phase Flows (MPFs) exist in various chemical engineering and industrial

processes and the research on monitoring MPFs is of great importance. In this research,

electromagnetic sensing techniques in the monitoring of two industrial processes with

MPFs are studied, namely Clean-In-Place (CIP) and industrial oil-water separation.

In multifunctional food and detergent production lines, accurate identification of ending

point of the cleaning process for the previous product is crucial to ensure product

integrity. In this research, an optimization method with dynamic references based on

Tikhonov regularization is proposed and validated by monitoring a lab CIP circuit with

a commercial Electrical Resistance Tomography (ERT) system. The results prove that

the proposed method is capable of accurately identifying the ending point of CIP

process. Moreover, the comparisons made with several conventional image

reconstruction algorithms illustrate that significantly improved inverse calculation

results are obtained when the background conductivity largely differs from the reference

conductivity. Additionally, the feasibility of this novel approach is discussed.

Liquid-liquid separation is an important process in many chemical engineering

applications. The ability of monitoring this process, in particular with a non-contact

method is of high value. In this research, a novel sensing approach which adopts a

differential electromagnetic inductive sensor (DEMIS) and an FPGA-based (field-

programmable gate array) impedance analyser is proposed and implemented to monitor

the separation processes of an oil-in-water liquid system. The inductive sensor has a

concentric cylinder structure with its coils arranged differentially. It is optimised to

achieve a homogeneous sensitivity distribution in the sensing region. Electrical models

of the oil-saline separation processes are established. Experiments under different oil

and saline fractions, different agitation speeds and durations are conducted to validate

the capability of the system. Both simulation and experimental results have proved that

the proposed system is capable of monitoring oil/water separation process non-

intrusively and non-invasively with a relatively lower cost, higher reliability and less

complex structure, comparing to existing techniques.

Page 19: Electromagnetic Sensing Techniques For Multi- Phase Flow

19

DECLARATION

No portion of the work referred to in this thesis has been submitted in support of an

application for another degree of qualification of this or any other university or other

institution of learning.

Page 20: Electromagnetic Sensing Techniques For Multi- Phase Flow

20

COPYRIGHT STATEMENT

i. The author of this thesis (including any appendices and/or schedules to this thesis)

owns certain copyright or related rights in it (the “Copyright”) and he has given The

University of Manchester certain rights to use such Copyright, including for

administrative purposes.

ii. Copies of this thesis, either in full or in extracts and whether in hard or electronic

copy, may be made only in accordance with the Copyright, Designs and Patents Act

1988 (as amended) and regulations issued under it or, where appropriate, in accordance

with licensing agreements which the University has from time to time. This page must

form part of any such copies made.

iii. The ownership of certain Copyright, patents, designs, trade marks and other

intellectual property (the “Intellectual Property”) and any reproductions of copyright

works in the thesis, for example graphs and tables (“Reproductions”), which may be

described in this thesis, may not be owned by the author and may be owned by third

parties. Such Intellectual Property and Reproductions cannot and must not be made

available for use without the prior written permission of the owner(s) of the relevant

Intellectual Property and/or Reproductions.

iv. Further information on the conditions under which disclosure, publication and

commercialisation of this thesis, the Copyright and any Intellectual Property and/or

Reproductions described in it may take place is available in the University IP Policy

(see http://documents.manchester.ac.uk/DocuInfo.aspx?DocID=487), in any relevant

Thesis restriction declarations deposited in the University Library, The University

Library’s regulations (see http://www.manchester.ac.uk/library/aboutus/regulations) and

in The University’s policy on Presentation of Theses.

Page 21: Electromagnetic Sensing Techniques For Multi- Phase Flow

21

ACKNOWLEDGEMENTS

I would like to express my sincere appreciation to everyone who supported and

encouraged me throughout the four years of my Ph.D. research. It has been an honour

and also wonderful experience to work in the group of Sensing, Imaging and Signal

Processing. In particular, I want to express my thanks to:

My supervisor, Dr. Wuliang Yin, for his constant guidance, encouragement, and

patience along the way. I am always grateful for becoming his student, as he not only

led me into the right path in research, but also taught me to be a good person in life. No

words could be strong enough to express my appreciation to him and I could have never

gone so far without him.

Dr. Ruozhou Hou in School of Chemical Engineering and Analytical Science, the

University of Manchester, for selflessly providing critical supports and discussions for

my research and becoming a good friend of mine in personal life. Your professionality

and enthusiasm would always inspire me.

My dear colleagues, Jorge Salas Avila, for helping me with the experimental setup and

developing the measurement system; Dr. Yuedong Xie, for the helpful suggestions and

guidance in simulations and thesis writing; Dr. Yang Tao, for the support in publication;

and many more in SISP group who offered me help and suggestions in many ways.

Moreover, I want to thank my parents, Mr. Liangmei Wang and Mrs. Jianhua Sun, for

their love and encouragement which supports me for the entire time. I would also like to

thank my beloved wife, Qingna Zhou, who helped me going through the hard time and

took care of me with everything she had.

At last, I want to thank our baby, who still lies in his/her mother’s belly, for fighting

together with dad and mom for their Ph.D. degrees in the last few months. You will

always be our most precious gift and I wish you all the best in your future life.

Page 22: Electromagnetic Sensing Techniques For Multi- Phase Flow

22

LIST OF PUBLICATIONS

Journal paper:

1. S. Wang, R. Hou, J. R. Salas Avila, Y. Tao and W. Yin, "A Novel Approach to

Measuring Separation Process of Oil–Saline Using Differential Electromagnetic

Inductive Sensor and FPGA-Based Impedance Analyzer," in IEEE Sensors Journal, vol.

18, no. 19, pp. 7980-7989, 1 Oct.1, 2018.

Conference papers:

1. S. Wang, W. Yin, “Monitoring Cleaning-In-Place by Electrical Resistance

Tomography with Dynamic References”, Imaging Systems and Techniques (IST), 2016

IEEE International Conference on. IEEE, 2016.

2. S. Wang, Y. Liu, K. Andrikopoulos, W. Yin, “Design of a Low-Cost Integrated

Electrical Resistance Tomography(ERT) System Based on Serial Bus”, Imaging

Systems and Techniques (IST), 2016 IEEE International Conference on. IEEE, 2016.

Page 23: Electromagnetic Sensing Techniques For Multi- Phase Flow

23

Chapter 1 Introduction

In this chapter, the motivation of the presented research is firstly illustrated. Then the

aims, objectives and contributions of the study are introduced, followed by the

organization of the whole thesis.

1.1 Motivation

The research on multi-phase flows (MPFs) is an important topic in fluid mechanics. The

term ‘multi-phase flows’ defines any fluid flow with more than one phase or component

and the behaviour of MPFs is proved to be extremely complicated[1]. Numerous

parameters of MPFs have been studied in the past, corresponding to different research

objectives, e.g. flow pattern, transient behaviour, component volume fraction, liquid

level detection etc.[2-5]. In this research, two important industrial processes which

involve multi-phase flows were studied, namely Clean-In-Place (CIP) and industrial oil-

water separation.

1.1.1 Clean-In-Place (CIP)

CIP is an important industrial process in food and detergent plants. It aims at the

removal/cleaning of soil inside the production line, which can endanger the process

sterility, without dismantling the plant[6]. It has always been a crucial topic, especially

for plants with multifunctional production lines, to monitor and analyse the process of

CIP. The main objective of studying CIP is to minimize water, chemical and waste-

treatment costs[7]. This requires accurate indication of the ending point (the moment

when the soil in the lose-loop pipe system is fully cleaned) and locating the most

difficult part to be cleaned.

Page 24: Electromagnetic Sensing Techniques For Multi- Phase Flow

24

Electrical Resistance Tomography (ERT) is a non-intrusive technology which has been

widely adopted in industrial process monitoring. It involves the acquisition of boundary

voltages from sensors (electrodes) located on the periphery of an object, such as a

process vessel, pipeline, etc.[8, 9]. The boundary voltages vary with the change of

external electric field (normally triggered by the injection of current) which is caused by

the change of conductivity distribution on the electrode plane[10]. With inverse

algorithms, the boundary voltages can be computed into reconstructed cross-sectional

images of the conductivity distributions. Because of its rapid measurement speed,

imaging ability and relatively low cost, ERT has become a popular technique in

industrial process monitoring and analysis.

In this research, ERT is adopted as the main technique to monitor and analyse the CIP

process. The main advantages of ERT in this scenario, comparing to other existing

techniques, can be concluded as follows:

1. Non-intrusive and non-hazardous;

2. Relatively low cost;

3. The ability to visualize the interior component distribution.

1.1.2 Industrial oil/water separation

Monitoring the separation process of crude oil extracted from an oil well is of great

importance in the oil industry. One of the most prevailing separation devices is the

American Petroleum Institute (API) oil/water separator which is illustrated in Figure 1-1.

At the rear of the API separator, oil flows over the edge of the variable height weir and

is recovered through the oil outlet pipe. Water, on the other hand, is directly disposed of

through the outlet pipe connected to the bottom of the primary separation tank. The

Page 25: Electromagnetic Sensing Techniques For Multi- Phase Flow

25

separation speed of oil and water is mainly dependent on the oil/water ratio, and the

interface level determines the control strategy of two outlet valve openings which

eventually controls the residence time of the oil and water output. The residence time

represents the probability distribution of time that oil/water stay inside the separator in

continuous operations[11]. It is therefore essential that the separation process and

oil/water ratio in the separation tank are monitored continuously in order to ensure a

high production efficiency and product consistency.

Figure 1-1 Schematic diagram of API pilot-scale separator

1.2 Aims and objectives

The aims of this research is to develop novel approaches or technologies for measuring

the CIP process and industrial oil/water separation process that have significant

advantages against conventional methodologies. Respectively, the research objectives

for the two industrial processes include:

For monitoring CIP process,

Page 26: Electromagnetic Sensing Techniques For Multi- Phase Flow

26

1. Developing a new approach of monitoring CIP process with ERT to accurately locate

the ending point of the whole process, i.e. locating the most difficult pipe section to be

cleaned and capture the moment when it is fully cleaned;

2. Visualizing the component distribution inside the test region to locate the most

difficult position to be cleaned;

3. Comparing the inverse results calculated from measured voltages of the lab-scale CIP

process with conventional algorithms and applying corresponding optimization method

to achieve more accurate results.

For measuring industrial oil-water separation process,

1. Designing a novel and reliable sensor system capable of measuring oil/water

separation process both non-intrusively and non-invasively. The sensor system should

be able to monitor the completion level of the separation process and locate the ending

point;

2. Conducting electrical simulations of monitoring the oil/water separation process with

proposed sensor system to achieve a better understanding of how the changes of the

physical parameters in the liquid system lead to the changes in the sensor output;

3. Testing the sensor system under different separation conditions and validating the

sensor output results.

1.3 Contributions

The author’s research has contributed to the sensing techniques in the monitoring of

industrial process with multi-phase flow in several ways. The significance and novelty

of the research can be concluded as follows:

Page 27: Electromagnetic Sensing Techniques For Multi- Phase Flow

27

In the research of monitoring CIP using ERT with dynamic reference:

1. For the first time, a novel optimization method with dynamic reference was proposed

based on conventional Tikhonov regularization. The method involves the construction

of dynamic references for the inverse calculation in ERT based on the average level of

measured voltages. The dynamic reference helps in reducing the distortion of the

inverse solution caused by the significantly different conductivities between the test

region and the reference;

2. By applying this optimization method to the inverse calculation of conductivity

distribution during CIP process, the reliability of ERT is improved. More accurate

results were achieved throughout the process, especially when the test regions were

dominated by high conductivity components. In addition, the advantage of conventional

Tikhonov regularization still remained, which is the accurate indication of the ending

point. Experiments were carried out under different CIP conditions, e.g. flow rate and

pipe geometry. The results clearly indicated the ending point of the CIP process and the

most difficult parts to be cleaned in the test region, which are the most critical

objectives of the research.

In the research of measuring oil/water separation process using differential

electromagnetic inductive sensors (DEMIS):

1. For the first time, a novel, cost-effective, non-intrusive and non-invasive technique

was developed for measuring oil/water separation process. The merits of DEMIS will be

explained in Chapter 2 by comparing the proposed technique with existing techniques in

measuring oil-water separation;

Page 28: Electromagnetic Sensing Techniques For Multi- Phase Flow

28

2. A novel optimization method was proposed to homogenize the vertical sensitivity

distribution in the test region of the DEMIS. The method involves decreasing the ratio

between the diameters of the separation vessel and the coils. An optimum ratio was

determined to achieve a relatively homogeneous vertical sensitivity distribution while

maintaining the sensitivity values and system signal-to-noise ratio at a reasonable level.

3. In the simulation part of this research, a dynamic electrical model was constructed

based on the physical liquid-liquid separation model. The physical model explains the

division of different sections in the liquid system during the separation process based on

the transient behaviour of oil droplets, as well as the height change of interfaces

between corresponding sections. Moreover, the equivalent conductivity value in each

section was calculated based on the conductivities of oil and water, oil/water fraction

calculated from the interface heights and Maxwell Garnett mixing formula. Thus a time-

varying electrical liquid-liquid separation model can be constructed in the

electromagnetic simulation toolkit. The above method successfully explained how the

changes in physical parameters lead to the change in the electrical output signal from

the sensor.

4. The output signal from the DEMIS during the oil-water separation process was

validated by comparing it with the physical interface (water interface) height change

synchronously recorded by a camera. It is proved that the changing trend of output

signal matches with the physical process and it could indicate the ending point of the

separation process.

1.4 Organization of thesis

Chapter 1 introduces the motivations, aims and objectives, contributions and

organization of the thesis.

Page 29: Electromagnetic Sensing Techniques For Multi- Phase Flow

29

Chapter 2 is a general review for the background of this research. Existing mainstream

sensing techniques of multi-phase flow was firstly introduced to achieve a general

understanding of the state-of-the-art in this area. Then the two industrial processes to be

studied in the author’s PhD work, namely CIP and industrial oil-water separation

process, together with the state-of-the-art monitoring techniques was introduced in

Section 2.2 and 2.3 respectively. In the end of each section, the novelty of the research

methodology was explained by comparing the techniques adopted in this research with

other existing techniques.

In Chapter 3, Electrical Resistance Tomography (ERT) is used as a new approach to

analyse the comprehensive spatial and time-varying conductivity changes during lab-

scale CIP processes, aiming at locating the most difficult point to be cleaned in the pipe

circuit and the ending point of the whole cleaning process. The chapter starts with

introducing the fundamentals of ERT, including the definition of forward problem and

inverse problem, and some conventional algorithms for imaging reconstruction. Then

the experimental setup and procedure of ERT measurement for monitoring CIP process

are explained, as well as the analytical principles for identifying the ending point of

cleaning process, and evaluating the overall performance of reconstructed images. With

the measured voltages, preliminary images were constructed with conventional

algorithms and the merits and drawbacks were pointed out. Then an optimization

method with dynamic reference was proposed to overcome the corresponding

drawbacks and the optimized results were compared with the original ones. In the end,

results achieved from optimized algorithm under different cleaning flow rate and pipe

geometries were also presented to justify the suitability of the optimization method

under different cleaning conditions.

Page 30: Electromagnetic Sensing Techniques For Multi- Phase Flow

30

In Chapter 4, the fundamentals of the proposed three-coil differential electromagnetic

inductive sensor was firstly introduced. In addition, a sensitivity analysis based on

analytical calculation and field value extraction is illustrated which gives rise to the

optimized design of the sensor. The optimization aims at homogenizing the vertical

sensitivity distribution within the sensing region. Moreover, an equivalent electrical

model of the liquid-liquid separation model is derived based upon which simulations are

carried out to explain the evolution of sensor output signal with respect to separation

process. Finally, the simulation results under different prior mixing conditions, e.g.

oil/water fraction, agitation speed and duration, are presented and discussed.

In Chapter 5, the design of the experimental system was firstly demonstrated, including

the sensor system, mixing and separation system and measurement system, followed by

the experimental strategy. Moreover, the validation of the experimental system and

results were carried out. The measurement system was validated by measuring a known-

magnitude voltage signal, while the validation of sensor system, specifically the

sensitivity distribution in the sensing region, was carried out by continuously adding

same amount of saline and inspect the corresponding sensor output change. A critical

validation of the sensor output during a complete oil-water separation process was also

demonstrated. It involves comparing the sensor output signal with the saline interface

height change recorded by a camera synchronously. Finally, experiments were

conducted under different prior mixing conditions, e.g. agitation speed, duration and

oil/saline fraction. The experimental results are compared with simulation results in

Chapter 4 to assess the performance of the proposed system.

Chapter 6 is the conclusion of this research and recommendations for future works.

Page 31: Electromagnetic Sensing Techniques For Multi- Phase Flow

31

Chapter 2 Background of Sensing Techniques in the

Monitoring of Industrial Process with Multi-

Phase Flow

In this chapter, existing mainstream sensing techniques in the research of multi-phase

flow were firstly introduced to achieve a general understanding of the state-of-the-art in

this area. Then the two industrial processes to be studied in the author’s PhD work,

namely CIP and industrial oil-water separation process, together with the state-of-the-art

monitoring techniques were introduced in Section 2.2 and 2.3 respectively. In the end of

each section, the novelty of the research methodology was explained by comparing the

techniques adopted by the author with other existing techniques.

2.1 Existing sensing techniques in multi-phase flow

measurement

There is a wide range of techniques that enables the evaluation and analysis of the

properties of MPFs. Based on the interaction between the emission signal and the

sample, the techniques can be categorized as mechanical sensing, hydraulic sensing,

electrical sensing, acoustic sensing, radiative sensing, and microwave sensing[12].

2.1.1 Mechanical and hydraulic sensing

Mechanical sensing involves the transmission of force or motion from the fluid to

instruments. One typical example is the conventional water meters which translate the

displacement or velocity profile of the water flow into the meter reading of flow rate.

Hydraulic sensing in general denotes the measurement of liquid pressure. Pressure

measurement is adopted in many industrial processes as liquid pressure is always

correlated with other fluid parameters such as liquid level, flow rate, etc. One example

is the venturi meter (Figure 2-1), which takes advantage of measuring the pressure

Page 32: Electromagnetic Sensing Techniques For Multi- Phase Flow

32

difference of the fluid when flowing through vessels with different diameters and thus

acquires the flow rate of the fluid[13].

Figure 2-1 Venturi meter

2.1.2 Electrical sensing

Electrical sensing in MPFs consists of a large group of techniques which involve the

measurement of electromagnetic parameters of the fluid with the aid of external

electromagnetic field and interpreting them into the information regarding component

motion, distribution or volume fraction.

Electrical tomography, for example, is a popular technique in the monitoring and

analysing of industrial process with MPFs. The term ‘electrical tomography’ normally

includes Electromagnetic Tomography (EMT), Electrical Capacitance Tomography

(ECT) and Electrical Impedance Tomography (EIT), while Electrical Resistance

Tomography (ERT) is considered to be a particular case of EIT[14]. The above

electrical tomography techniques share a common basic aim, which is to obtain a set of

measurements through sensors locating at the periphery of the test region so as to

achieve the component distribution inside (normally presented by a reconstructed image

of the cross-section) with certain inverse calculation algorithms[15-17]. The choice of

Page 33: Electromagnetic Sensing Techniques For Multi- Phase Flow

33

techniques in different applications mainly depends on the target material in the MPFs

to be monitored. EMT is capable of monitoring liquid metal, mineral, magnetic

materials and ionised water with the coil sensor array arranged outside the process

vessel[18]. It aims at acquiring the material conductivity and permeability distribution

with mutual inductance measurements[19, 20]. In terms of ECT, the target electrical

parameter to be measured is the permittivity of the material[21]. The measurement is

implemented by measuring the capacitance change between capacitive electrode plates

(usually eight or 16) mounted on the exterior surface of the process vessel[22, 23].

Similarly, EIT focuses on measuring the impedance (both conductivity and permittivity)

change between a set of electrodes[24]. As the conductivity measurement requires the

injection of current or voltage into the material, electrodes for EIT measurement are

usually installed on the interior surface of the process vessel to have direct contact with

the materials inside[25, 26]. In addition, ERT is an extreme case of EIT which only

focuses on the measurement of conductivity[27]. A general comparison of the electrical

tomography methods is illustrated in Table 2-1.

Other electrical sensing techniques have been proposed by various researchers. G.

Lucas and etc. developed a four-sensor probe system to measure non-conductive bubble

velocity profile in air-water and oil-water flows[28, 29]. This is achieved by calculating

the time intervals taken from the output signals from each of the four conductance

sensors located with the probe. Contactless capacitively coupled conductivity detector

(C4D) is a popular sensing technique in organic and biochemical applications. To detect

small inorganic ions as well as organic and biochemical species, two tubular electrodes,

namely actuator electrode and pick-up electrode, are arranged on the target tube, e.g. a

capillary, and connected capacitively[30]. Du and Zhe developed a novel inductive

pulse sensor to detect metallic wear debris in rotating machinery lubrication oil

Page 34: Electromagnetic Sensing Techniques For Multi- Phase Flow

34

circuit[31]. The sensor consists a two-layer planar coil capable of detecting the

inductance change caused by the passage of metallic debris. Other electrical sensing

techniques exist in different research areas and we will not numerate here.

Table 2-1 General comparison of Electrical Tomography methods

Methods Sensor arrangement Target

parameter Typical material

EMT

Coil Array

Self/mutual

inductance

Metals

Minerals Magnetic materials

Ionized water

ECT

Capacitive Plates

Capacitance

Oil

De-ionized water Non-metallic powders

Polymers

Burning gases

EIT

Electrode Array

Impedance

Water/saline Biological tissue

Geological materials

Semiconductors

2.1.3 Acoustic, radiative and microwave sensing

Figure 2-2 Ultrasound velocity profiler

Page 35: Electromagnetic Sensing Techniques For Multi- Phase Flow

35

Acoustic sensing techniques are also widely adopted in the monitoring of MPFs.

Different approaches have been developed by researchers. The conventional method is

investigating the propagation and attenuation of sound wave, which relate to component

fraction and flow regime of the MPFs[32, 33]. However, in the measurement of bubbly

MPFs, the accuracy of conventional acoustic sensing techniques highly depends on the

ratio between sound wave length and the size of the bubbles. Hence the research on

ultrasonic sensing techniques were developed. Takeda proposed the ultrasonic velocity

profiler by emitting an ultrasound pulse with a transducer and receiving the reflected

echo with the same transducer, as shown in Figure 2-2[34]. The velocity profile can be

obtained by analysing the delay of the reflected signal and Doppler shift frequency.

Similar measuring principle can be adopted to the measurement of the bubble velocity

in gas-liquid system and solid concentration in liquid-solid system[35, 36].

Radiative sensing techniques are also very popular in the measurement of MPFs

because of their high accuracy and efficiency. There are two mainstream radiative

sensing approaches, namely densitometry and radiography. The main objective to apply

radiative densitometry is to measure the component fraction in the MPFs. The common

approach to implement the measurement is to place a radiation source on one side of the

pipe with MPFs inside and measure the intensity change of radiation beam after it

passes through the flow, as shown in Figure 2-3[37].

Page 36: Electromagnetic Sensing Techniques For Multi- Phase Flow

36

Figure 2-3 Common approach to implement radiative sensing on MPFs

Bishop and James[38] applied neural networks analysis in the detection of air/oil/water

three-phase flow with dual energy gamma densitometry to avoid complex and difficult

flow modelling for phase configuration. Further work of flow regime identification in

combination with gamma-ray attenuation is carried out by Salgado and Pereira[39].

However, to achieve more accurate test results with radiation measurement methods, it

would require either a longer measurement period or a more intense radiation

source[40].

Figure 2-4 Schematic of radiography system with multiple radiative sources and 2D

detectors

On the other hand, radiography aims at visualizing and measuring the phase distribution

in MPFs. One typical example is X-ray radiography which is not only widely used in

multi-phase flow measurement but also in various non-destructive testing (NDT) and

medical applications[41]. The measurement approach is similar to that of the radiative

densitometry, however multiple 2-dimentional (2D) detectors are adopted to record the

Page 37: Electromagnetic Sensing Techniques For Multi- Phase Flow

37

X-ray attenuation map of the target object generated with multiple X-ray beam

sources[42]. An example of the schematic of radiography system is shown in Figure 2-4.

In addition, it is worth mentioning neutron radiography as another novel radiography

technique, which gives rise to the capability of imaging materials that are difficult to be

visualized by X-rays and gamma-rays as the attenuation and diffraction characteristics

of neutron rays are peculiar[43, 44].

Microwave sensing techniques are used in many commercial multi-phase flow meters

(MFMs)[45]. The basis of the microwave technique is that the transmission of

microwaves through MPFs, e.g. mixture of water, oil and gas, is affected by both the

fraction of water and the thickness of the liquids[46]. By measuring amplitude and

phase change of a microwave signal, the component fractions of the flow can be

investigated[47]. Moreover, Wu and etc. developed the microwave tomographic system

with microwave sensors arranged around the pipe, similar to that of electrical

tomography, to generate cross-sectional images based on the measurements of the

scattered microwave field[48, 49].

It is understandable that some other sensing techniques for multi-phase flow might be

omitted in this section. The objective of this section is to give a general understanding

of the current status in the monitoring and analysis of MPFs. Some existing techniques

developed exclusively for the targeted industrial processes in this research (CIP and oil-

water separation) will be introduced in later sections.

Page 38: Electromagnetic Sensing Techniques For Multi- Phase Flow

38

2.2 Monitoring CIP with Electrical Resistance Tomography

(ERT)

2.2.1 State-of-the-art in monitoring CIP

Figure 2-5 Schematics of ultrasonic techniques in fouling detection. (a) Pulse echo

technique; (b) Transmission technique.

The most crucial aim in monitoring CIP process is to detect the existence of fouling on

the interior pipe wall. Several ultrasonic and acoustic methods for fouling detection

have been tried by other researchers. Two approaches using ultrasonic sensing

technique have been proposed to determine the thickness of the fouling, namely pulse

echo technique and transmission technique[50]. The pulse echo technique detects the

reflected echo generated by the same ultrasonic transducer and the delay of the signal is

related to the boundary height in the target zone, whereas the transmission technique

applies a transmitter and a receiver on the opposite side of the pipe to allow the

ultrasound travel through the sensing region and investigate the existence of fouling by

analysing the attenuation of the signal. The schematics of the above two techniques are

illustrated in Figure 2-5[51, 52]. However, the accuracy and signal strength would be

significantly affected by the shape of the fouling layer, air bubbles and solid particles in

the flow. In addition, the cost of instrumentation limits the possibility of pervasive

applications in practical applications.

Page 39: Electromagnetic Sensing Techniques For Multi- Phase Flow

39

Another sensing technique based on acoustic vibration was developed for fouling

detection. The basis of this technique is that fouling layers on the interior pipe wall

would change the acoustic resonance frequency of the pipe during vibration[53]. The

measurement can be implemented by planting a vibration source on the interior pipe

wall and detect the acoustic wave with a microphone nearby. This method shows great

advantage with vessels of complex structure, such as plate heat exchangers. However,

this technique still suffers from its invasive nature[50].

Electrolyte–insulator–semiconductor (EIS) pH sensor has been adopted by researchers

to judge the completion of CIP process. However, this method can only monitor the

flow near the surface of the semiconductor which might lead to false reading of the

completion stage of the whole process[54].

Chen and Li etc. developed a method of detecting the milk fouling by measuring the

electrical resistance of the liquid and fouling layer between two parallel stainless steel

electrode installed on the pipe wall[55]. However, this technique is only capable of

identifying the existence of fouling in the sensing area, and no such information is given

regarding the location of the fouling on the pipe wall.

2.2.2 Advantages of ERT in monitoring CIP

Comparing to existing techniques for fouling detection, the significant advantages of

ERT can be concludes as follows:

1. Relatively low cost and immunity to the interference from bubbles and solid

particles, comparing to ultrasonic techniques;

2. Non-invasive nature, comparing to acoustic vibration techniques;

Page 40: Electromagnetic Sensing Techniques For Multi- Phase Flow

40

3. The ability to give comprehensive phase distribution information over the cross-

section of sensing area, comparing to EIS pH sensor and electrical resistance

measurement.

2.3 Measuring industrial oil-water batch separation process

with Differential Electromagnetic Inductive Sensor (DEMIS)

2.3.1 State-of-the-art in measuring industrial oil-water batch

separation process

Various techniques have been developed for the monitoring of oil-saline separation

process. The techniques can be concluded as three main types, the mechanical methods,

the ultrasonic sensors and the segmented sensor probes.

2.3.1.1 Mechanical methods

Figure 2-6 Monitoring oil-water separation process with sight glass

One conventional mechanical method involves the use of a sight glass, and the

inspection of oil-water level is conducted by human eyes[56]. Figure 2-6 illustrates a

typical sight glass installed on a separation vessel. The sight glass is vertically aligned

and connected to the separation vessel with two pipes. The oil-water interface height in

Page 41: Electromagnetic Sensing Techniques For Multi- Phase Flow

41

the sight glass is the same with that in the separation vessel and hence can be inspected

visually.

However, impurities such as wax and scale in the multiphase flow could coat the wall

and obstruct the interface observation through the sight glass. Possibility also exists that

the pipes connect sight glass with main separation vessel could be obstructed with

impurities mentioned above.

Another technique takes advantage of mechanical sensors which, for example, employs

a level gauge with a sliding displacer of chosen density between oil and saline[57, 58].

The performance of this technique would still tend to be affected by the cleanness of the

fluid, as the displacer could be immobilised[59].

Figure 2-7 Monitoring oil-water separation process with motive pressure sensor

Researches on single traversing pressure component driven by a motion system were

reported in[60]. The system mainly consists of a pressure sensor and a motion control

unit, which are connected by a flexible cable (Figure 2-7). The motion control unit

Page 42: Electromagnetic Sensing Techniques For Multi- Phase Flow

42

controls the vertical position of the pressure sensor in the separation vessel, in order to

detect the vertical pressure distribution and locate the oil-water interface.

One problem of the system was that the wear and tear of motive components would

reduce the stability for online monitoring and increase the maintenance cost.

2.3.1.2 Ultrasonic sensor

Ultrasonic sensor has the virtue of being contactless and non-invasive. The technique

involves one pair or multiple pairs of ultrasonic transmitter and receiver installed on the

separation vessel. The transmitter generates pulses that travel through the liquid system

and the receiver receives the reflected acoustic signal from the interface between

different phases[61]. The received signal is a function of the liquid densities and the

travelling speed of pulse echo in the liquids, hence the interface levels can be located.

An example of the function of ultrasonic sensor in monitoring oil-water separation

process is shown in Figure 2-8.

Figure 2-8. Monitoring oil-water separation process with ultrasonic sensor

Page 43: Electromagnetic Sensing Techniques For Multi- Phase Flow

43

It is worth mentioning that an ultrasonic interface level detector was developed in

Norway Christian Michelsen Research (CMR) in 2005[62]. The proposed ultrasonic

sensor was attached to the outside bottom of separator vessel and significantly reduced

the time and complexity of installation. The pulse echo travels through the vessel wall

as well as the liquid system. However, the accuracy of all ultrasonic sensors may drop

significantly due to signal attenuations caused by the presence of air bubbles, foams and

emulsions in the system[63].

2.3.1.3 Electrical Tomography

Electrical Capacitance Tomography (ECT) in particular was tested by Isaksenet et. al.

for interface measurements[64]. The basic principle of ECT is to construct the cross-

sectional images of permittivity distribution based on the inter-electrode mutual

capacitance measurements of electrode pairs surrounding the process vessel[65, 66].

The main limitation of ECT for the application of oil-saline separation monitoring is

that the presence of a conductive phase in the system has a tremendous impact on the

quality of the reconstructed images as it would strongly interfere electrical signals

acquired by the capacitive electrodes[67].

Bennett and William investigated the possibility of applying Electrical Resistance

Tomography to the monitoring of oil-water separation[68]. However, ERT

measurement requires the existence of conductive path between all electrode pairs.

Hence the attempt was only carried out on the deoiling hydrocyclone in which the

sensing region is fully occupied by liquids.

2.3.1.4 Segmented sensor array

Vertically segmented sensor arrays are also widely adopted in industrial applications.

The basic idea of this type of sensors is by combining relevant local information from

Page 44: Electromagnetic Sensing Techniques For Multi- Phase Flow

44

each individual sensor cell to achieve comprehensive spatial phase distribution

information. A common approach of adopting segmented sensor array in the monitoring

of oil-water separation process is shown in Figure 2-9.

Figure 2-9 Monitoring oil-water separation process with segmented sensor array

There are four commonly used sensor types, and they are nucleonic sensors, pressure

sensors, capacitance sensors and inductive sensors.

The nucleonic density measurement is considered to be very reliable and accurate in

monitoring the interface level of oil-saline separation process[67]. The high

performance is achieved by the technique of dual-energy gamma densitometry, which

translates the attenuation information corresponding to the absorption coefficient of

materials into density profiles[69, 70]. However, the hazardous nature of gamma

radiation leads to extra health and environmental concerns[71].

With respect to pressure sensors, local liquid density profiles are acquired by

eliminating liquid height, and gauging pressure components from the output signal[72].

Page 45: Electromagnetic Sensing Techniques For Multi- Phase Flow

45

In practical applications, however, the measurement accuracy is likely to degrade when

the sensor surface is covered by wax or scale impurities in the flow.

In terms of the segmented capacitance sensors, various attempts have been made. The

basis of segmented capacitance sensors is to measure the capacitance between the two

capacitive plates installed in each sensor to acquire local permittivity information[62,

73]. However, the capacitive plates still suffer from the fouling layer built up by the

impurities and the space between the plates may eventually be blocked.

As another electrical sensing methodology, electromagnetic inductive sensors are

widely applied to the level measurement of single phase conductive liquid, e.g.

monitoring sea level[74]. A typical inductive sensor system consists of a transmitting

coil and a receiving coil. Alternating current is injected into the transmitting coil which

generates a primary magnetic field. Eddy currents will be induced within the conductive

liquid giving rise to a secondary field which can be detected by the receiving coil. Based

upon the induced voltage of the receiving coil, the information of conductivity can be

deduced[75]. In order to measure the multiple interface levels that typically exist in a

primary oil separator, inductive sensors are distributed evenly along the vertical probe

from which sufficient spatial impedance distribution information can be acquired. One

example is the Inductive Level Monitoring System (ILMS) developed by the ABB

Group[76]. Although the proposed sensor probes were in direct contact with the fluid,

impurities hardly had significant effect on the measurement accuracy. However, the

saline, if leaking into the wires, would short-circuit the sensor and cause the

malfunction of the entire system.

Page 46: Electromagnetic Sensing Techniques For Multi- Phase Flow

46

2.3.2 Advantages of DEMIS in monitoring oil separation process

In this research, we present a non-intrusive and non-invasive differential

electromagnetic inductive sensor (DEMIS) for monitoring oil-saline separation process.

The drawbacks of existing techniques have been illustrated in the last section.

Comparing to existing inductive sensing system, there are two main advantages of

DEMIS. The first and most important advantage is that the DEMIS locates outside the

separation vessel so the direct contact with fluids and the potential risk of short-circuit

caused by leaking are eliminated. Moreover, the sensor is free from contamination

caused by the impurities in the liquids. In addition, the relatively larger number of

sensors for existing segmented inductive sensor system would indicate a more complex

data acquisition and processing system is needed, while the DEMIS system requires less.

Page 47: Electromagnetic Sensing Techniques For Multi- Phase Flow

47

Chapter 3 Monitoring CIP Using Electrical Resistance

Tomography (ERT) with Dynamic Reference

In this chapter, Electrical Resistance Tomography (ERT) is used as a new approach to

analyse the comprehensive spatial and time-varying conductivity changes during a CIP

process, aiming at locating the most difficult point to be cleaned in the pipe circuit and

also the ending point of the whole cleaning process. The chapter starts with introducing

the fundamentals of ERT, including the definition of forward problem and inverse

problem, and some conventional algorithms for imaging reconstruction. Then the

experimental setup and procedure for ERT measurement during CIP process are

explained, as well as the analytical principles for identifying the ending point of

cleaning process and evaluating the overall performance of reconstructed images in

comparison with practical conductivity distribution in the pipe. With the measured

voltages, preliminary images were reconstructed with conventional algorithms and the

merits and drawbacks were pointed out. Hence an optimization method was proposed to

overcome the corresponding drawbacks and the optimized results were compared with

the original ones. In the end, results achieved from the optimized algorithm under

different cleaning flow rate and pipe geometries are also presented to justify the

suitability of the optimization under different circumstances.

3.1 Fundamentals of ERT

3.1.1 Sensitivity and forward problem

3.1.1.1 Sensitivity

Geselowitz [77] and Lehr [78] derived the equation of how mutual impedance measured

by a four-electrode arrangement changes in response to the conductivity change in a

Page 48: Electromagnetic Sensing Techniques For Multi- Phase Flow

48

volume conductor. Based on their achievements, Murai and Kagawa presented the basic

theorem of sensitivity in Electrical Impedance Tomography as follows[79]:

Equation 3-1

𝑆𝑘,𝑗 = −∫ �� 𝜑 ∙ �� 𝜓𝑑𝑎 ≈ −�� 𝜑 ∙ �� 𝜓

k stands for pixel number in the reconstructed image. j stands for voltage projection

formed by two electrode pairs. �� 𝜑 and �� 𝜓 are the electric field vectors in the

corresponding pixel when one of the electrode pairs is acting as the transmitter injecting

current into the field, while the other electrode pair is acting as the receiver, from which

the boundary voltage measurement is taken.

To acquire the electric field strength under each projection, a two-dimensional

simulation model (Figure 3-1) is constructed according to the size of sensors and pipe

diameter in practical experiments with Ansys Maxwell (electromagnetic simulation

toolkit).

Figure 3-1 Electromagnetic simulation model for sensitivity matrix calculation

Page 49: Electromagnetic Sensing Techniques For Multi- Phase Flow

49

The simulation model consists of three parts.

1. Polyester pipe wall with an inner diameter of 38.1 mm and an outer diameter of

43.1 mm;

2. 16 copper electrodes attached to the inner pipe wall, where electrode 1 locates at

3 o'clock, electrodes 2 to 16 are sequenced in anticlockwise direction evenly;

3. Test region filled with tap water (conductivity 0.06 S/m).

The mesh number in the test region is 10000 and the voltage across the excitation

electrode pair is 5 V.

Figure 3-2 Sensitivity distributions in part of the projections

With the aid of field calculator in the software and MATLAB programming, the electric

field strength under each projection can be achieved and the sensitivity distribution

under each projection can be calculated through Equation 3-1. Figure 3-2 displays the

sensitivity distributions under some of the projections.

Page 50: Electromagnetic Sensing Techniques For Multi- Phase Flow

50

The sensitivity values decrease with the distance to the electrodes, as the electric field

strength decreases. In addition, the sensitivity distributions are determined by the

geometry of test region and the distribution and shapes of electrodes. In practical ERT

tests, the electrodes and test region are always fixed, which indicates all measurements

taken by ERT planes with same geometry and sensor structure share the same

sensitivity distributions.

3.1.1.2 Forward problem

The core equation of the forward problem based on the sensitivity theorem is in [80].For

the measurement on projection j,

Equation 3-2

∆𝑉𝑗

𝑉𝑅,𝑗≈ −

∑ ∆𝜎𝑘 ∙ 𝑠𝑗,𝑘𝑤𝑘=1

∑ 𝜎𝑅,𝑘 ∙ 𝑠𝑗,𝑘𝑤𝑘=1

where w is the total number of pixels in the reconstructed image; 𝑠𝑗,𝑘 is the sensitivity of

kth pixel in projection j; 𝑉𝑅,𝑗 and 𝜎𝑅,𝑘 are the reference voltage in projection j and the

reference conductivity of pixel k respectively; ∆𝑉𝑗 and ∆𝜎𝑘 are the voltage change in

projection j and the conductivity change of pixel k.

This explains how changes in the conductivity distribution lead to corresponding

changes in the measured boundary voltages. The reference background is normally a

homogeneous background with a fixed conductivity. In this research, the reference

background material is tap water with the conductivity of 0.06 S/m. Hence the equation

can be derived as:

Equation 3-3

∆Vj

VR,j≈ −

1

σR∙∑ ∆σk ∙ sj,k

wk=1

∑ sj,kwk=1

Page 51: Electromagnetic Sensing Techniques For Multi- Phase Flow

51

Where σR is the reference conductivity. For Jj,k =sj,k

∑ sj,kwk=1

, Equation 3-3 can be derived

as:

Equation 3-4

∆Vj

VR,j≈ −

1

σR∙ ∑ (Jj,k

w

k=1∙ ∆σk) = −

1

σR∙ [Jj,1, Jj,2 ⋯Jj,w] ∗ [

∆σ1

∆σ2

⋮∆σw

]

For a total number of p projections, the voltage change vector can be presented as:

Equation 3-5

Vp∗1 =

[ ∆V1

VR,1

∆V2

VR,2

⋮∆Vp

VR,p]

= −1

σR∙

[ J1,1 J1,2 ⋯ J1,w

J2,1 J2,2 ⋱ J2,w

J3,1 J3,2 ⋯ J3,w

⋮ ⋮ ⋯ ⋮Jp,1 Jp,2 ⋯ Jp,w]

∗ [

∆σ1

∆σ2

⋮∆σw

]

Which could be simplified as:

Equation 3-6

𝑉𝑝∗1 = −𝐽𝑝∗𝑤 ∗ 𝜎𝑤∗1

where 𝐽𝑝∗𝑤 is the normalized sensitivity matrix,

Equation 3-7

𝐽𝑝∗𝑤 =

[ J1,1 J1,2 ⋯ J1,w

J2,1 J2,2 ⋱ J2,w

J3,1 J3,2 ⋯ J3,w

⋮ ⋮ ⋯ ⋮Jp,1 Jp,2 ⋯ Jp,w]

𝑉𝑝∗1is the voltage change vector,

Equation 3-8

Page 52: Electromagnetic Sensing Techniques For Multi- Phase Flow

52

𝑉𝑝∗1 = [∆𝑉1

𝑉𝑅,1,∆𝑉2

𝑉𝑅,2⋯

∆𝑉𝑝𝑉𝑅,𝑝

]

−1

𝜎𝑤∗1is the conductivity change vector,

Equation 3-9

𝜎𝑤∗1 = [∆𝜎1

𝜎𝑅,∆𝜎2

𝜎𝑅⋯

∆𝜎𝑤

𝜎𝑅]−1

3.1.2 Inverse problem and conventional algorithms

3.1.2.1 Inverse problem

The basic idea of inverse problem in ERT is to reveal the relationship between changes

of conductivity distribution in the field and measured boundary voltages.

Mathematically, this process is the inverse version of Equation 3-6:

Equation 3-10

𝜎𝑤∗1 = −𝐽𝑤∗𝑝

−1𝑉𝑝∗1

Due to the soft field nature of electrical tomography, this is a severely ill-posed inverse

problem because of the large condition number of sensitivity matrix (normally 106) and

insufficient number of independent measurements (less than the number of pixels)[81].

Hence regularizations need to be adopted to minimize errors in the inverse calculations.

3.1.2.2 Conventional algorithms

3.1.2.2.1 Linear Back Projection (LBP)

LBP is one of the first algorithms adopted in the attempt to reconstruct images for the

electrical tomography. It is less accurate but with rapid response speed for computing

because of its simplicity. The basic idea is to consider the sensitivity matrix 𝐽 as a linear

Page 53: Electromagnetic Sensing Techniques For Multi- Phase Flow

53

mapping from conductivity vector space to boundary voltage vector space (which is not

true for the soft field domain), so the transposed sensitivity matrix 𝐽�� can be considered

as the related mapping from boundary voltage vector space to conductivity vector

space[21]. Hence,

Equation 3-11

𝜎𝑤∗1 = −𝐽𝑤∗𝑝

𝑇𝑉𝑝∗1

LBP is not chosen as the main algorithm in this application because the calculation is

based on an assumption which will reduce the accuracy of the inverse results and the

prediction of the ending point of the cleaning process requires accurate inverse results.

This will be proved in the Section 3.3.1.

3.1.2.2.2 Iterative algorithms

There are numerous existing iterative algorithms for ill-posed inverse problems, such as

Gauss-Newton, Landweber, conjugate gradient and etc.[80, 82, 83]. The common

approach for iterative algorithms is to reduce errors and converge the result to the true

solution through iterative calculations[84]. Iterative algorithms are very effective in

static experiments as they can trade off computing time to minimize the error in the

result. However, they are not adopted in this application because the potentially long

computing time lowers the efficiency for real time online tests.

3.1.2.2.3 Tikhonov regularization

The main objectives of employing regularization in ill-posed problems are to impose the

prior assumptions, which are the reference values in the case of ERT, on the solution

and at the same time filter out the high-frequency components of the solution, which

correspond to the smallest singular values of the sensitivity matrix[85]. However, when

Page 54: Electromagnetic Sensing Techniques For Multi- Phase Flow

54

there is a significant difference between the prior assumption and the solution, the latter

could be seriously distorted after regularization is adopted.

Tikhonov regularization is a widely used algorithm for soft field tomography. The

explicit formula pattern is[27]:

Equation 3-12

𝜎𝛼 = (𝐽𝑇𝐽 + 𝛼2𝐼)−1𝐽

𝑇𝑉

𝐽𝑇

stands for the transpose of the sensitivity matrix and 𝐼 is an identity matrix.𝛼2 is

known as the regularization parameter, which controls the convergence level of the

result. We use 𝛼 square to imply that it should always be positive.

Tikhonov regularization is chosen to be the basic algorithms in this research because the

main objective of monitoring CIP is to find out the ending point which in principle is

defined as the point when the last fragment of soil is cleaned. This implies that the

solution values would be very close to the reference values, i.e. the conductivity

distribution in the test region is close to the reference background, under which

circumstance regularization method is most suitable. However, in the earlier stage of the

cleaning process where the test region is dominated with soil of high conductivity,

significant difference lies between the average conductivity value of testing region and

that of the reference background. In this case, it is essential to carry out corresponding

optimizations on conventional Tikhonov regularization method in order to fulfil

comprehensive analytical purposes.

Page 55: Electromagnetic Sensing Techniques For Multi- Phase Flow

55

3.2 Experimental setup and principles

3.2.1 Experimental setup

The lab CIP circuit is shown in Figure 3-3. The left end of the testing area is connected

to the soil tank and water tap through a three-way valve from which the cleaning flow

rate can be adjusted. In the current study, a non-Newtonian, shear thinning shampoo

was used as the soil. The right end leads to the drain with a valve. There are 2

removable test areas into which transparent pipes with different geometry can be

installed.

Figure 3-3 Simulated CIP circuit

In the present research, two different pipe geometries are studied. A ‘T-shape’ pipe

shown in Figure 3-4 is installed in one of the test areas and the other test area is placed

with a normal straight pipe. A total of four ERT planes, each with 16 electrodes, are

installed in the test pipe Planes 1 to 3 are in the straight pipe section and plane 4 is in

the sealed concave bottom, which in principle should be the most difficult one to be

cleaned. Electrodes on the planes are connected to a commercial ERT system in order

to implement the measurements.

Page 56: Electromagnetic Sensing Techniques For Multi- Phase Flow

56

Figure 3-4 'T-shape' pipe with the 4 ERT planes installed

The second pipe sample is a 1.5 inches straight pipe with a butterfly valve installed in

the middle (Figure 3-5 and 3-6). This is mainly a 1.5 inches straight section, but with a

disc in the middle to mimic a 1.5 inches butterfly valve in a fully open position. The

geometry is equipped with four electrode planes, two at the upstream and two at the

downstream of the disc. Two inner planes are at the immediate upstream and

downstream of the disc respectively. Theoretically, the third plane at immediate

downstream of the valve should be the most difficult one to be cleaned.

Figure 3-5 Schematic diagram of a straight pipe with a butterfly valve installed inside

Page 57: Electromagnetic Sensing Techniques For Multi- Phase Flow

57

Figure 3-6 Straight pipe with a butterfly valve installed inside

3.2.2 Experimental procedures

The procedure of the simulated cleaning-in-place test can be concluded to steps as

follows:

Step 1: Switch the three-way valve to the branch connected to water tap and fully fill

the test regions with tap water. Then the ERT system is switched on to start current

injection and voltage measurement for 25 seconds while each group of complete

ERT measurement takes 1 second. The averaged measured voltage values within this

step are considered to be the original reference values to reduce the deviation caused

by measurement errors.

Step 2: Switch off the ERT system and switch the three-way valve to the soil tank.

Fill the test area with the soil. Then the ERT measurements will be reinitiated and

last for approximately 15 seconds.

Step 3: Switch the valve to water tap and start the CIP process.

Step 4: After the test regions are visually fully cleaned, keep measuring for 20

seconds.

Page 58: Electromagnetic Sensing Techniques For Multi- Phase Flow

58

In conclusion, the contents in the test regions to be measured under each step are tap

water, soil, the mixture of soil and tap water, tap water (Figure 3-7).

Figure 3-7 Contents to be measured in the test region under each step of the simulation

test.

3.2.3 Measurement protocol

The measurement protocol adopted in this research is Adjacent Electrode Pair strategy,

which was presented by Barber in 1984 and has been the most commonly used

measurement protocol for ERT[86]. It involves injecting current to a neighbouring

electrode pair and measuring the voltages across all other neighbouring electrode

pairs[87]. Table 3-1 shows an example of adopting adjacent strategy on an 16-electrode

ERT system.

Table 3-1 Adjacent strategy on 16-electrode ERT system

Current injection Measured electrode pairs Number of measurements

(1,2) (3,4), (4,5), …, (14,15), (15,16) 13

(2,3) (4,5), (5,6), …, (15,16), (16,1) 13

(3,4) (5,6), (6,7), …, (15,16), (16,1) 12

… … …

(13,14) (15,16), (16,1) 2

(14,15) (16,1) 1

Tap Water

Soil MixtureTap

Water

Page 59: Electromagnetic Sensing Techniques For Multi- Phase Flow

59

The number of independent measurements for a N-electrode ERT system is N(N-

3)/2[88]. Hence the total number of measurements for a 16-electrode system is 104.

3.2.4 Analytical principles

The average conductivity of the soil is approximately 4-6 S/m while that of tap water is

around 0.06 S/m. Therefore, the maximum conductivity value of each ERT frame, i.e.

the maximum pixel value in each reconstructed image is extracted independently as the

criterion of judging the remaining presence of the soil. The ending point of cleaning

process can be located when the maximum conductivity value equals to the reference

conductivity, which indicates the high conductivity component in test region (soil) is

fully cleaned. Also, the average conductivity value in each frame is calculated to

investigate the overall conductivity level in each experimental step described in Section

3.2.2.

3.3 Inverse calculation results with LBP and Tikhonov

regularization

366 frames of data were acquired for each ERT plane during the CIP process under the

water flow rate of 5400 L/h and with the injection current of 5.11 mA. The injection

current is set accordingly to the conductivity variation range in the test region to achieve

valid measured voltages. The imaging speed is one frame per second. The ending point

of cleaning process for the T junction plane, where the most difficult point in the pipe

was fully cleaned, was shown to be around frame 340 according to visual inspection.

3.3.1 Linear Back Projection (LBP)

The inverse solutions generated with LBP are shown in Figures 3-8 and Figure 3-9.

Page 60: Electromagnetic Sensing Techniques For Multi- Phase Flow

60

Figure 3-8 Maximum conductivity values in all ERT planes during the cleaning process

calculated with LBP

Figure 3-8 shows the maximum conductivity values of all four ERT planes during the

cleaning process. The corresponding stages are labelled across the curves according to

the experimental procedure in Section 3.2.2. The maximum conductivity values of all

four planes kept constant at the beginning of the test when reference measurements

were taken. The signal of Plane 4 (T junction plane) dropped and stayed steady around

frame 340, which complies with visually inspected result when the T junction was fully

cleaned. Meanwhile, the signal for other three planes at the straight pipe section

dropped rapidly after the cleaning process was initiated around frame 35. Hence, it

proved that the results are capable of indicating the ending point of the cleaning process

at the location of each ERT plane. However, the steady maximum conductivity values

of plane 2 and plane 3 slightly exceed the conductivity of tap water (0.06 S/m) when

they are fully cleaned. The maximum conductivity values of all four planes during step

two are lower than the actual soil conductivity (4-6 S/m).

Figure 3-9 demonstrates the average conductivity values of all four ERT planes

calculated with LBP during the cleaning process. The signals drift around the reference

conductivity value in a small range in Step 3, which is acceptable. However, at frame 25

Page 61: Electromagnetic Sensing Techniques For Multi- Phase Flow

61

when the component in the test regions was suddenly changed from tap water to the soil,

the average conductivity values of all 4 planes jumped below the reference value, which

did not reflect the actual processes of the experiment.

Figure 3-9 Maximum conductivity values in all ERT planes during the cleaning process

calculated with LBP

The results have proved that, despite the fact LBP is capable of locating the ending

point of the cleaning process, it is not suitable for the monitoring of CIP due to the lack

of accuracy and the poor ability to handle the significant change of component

conductivity in test region.

3.3.2 Tikhonov regularization

3.3.2.1 Selection of regularization parameter

The regularization parameter controls the weight given to the minimization of the side

constraint and an optimal regularization parameter should fairly balance the perturbation

error and the regularization error in the regularized solution[89]. Improper selection of

the parameter would either lead to over smoothing of the result or excessive error level.

Numerous methods of parameter selection exist in literature, but in practice, empirically

choosing the parameter is widely adopted. In this work, image reconstruction results

under different regularization parameters were compared with visual inspection results

Page 62: Electromagnetic Sensing Techniques For Multi- Phase Flow

62

during cleaning process to determine the choice of appropriate regularization parameter

(Table 3-2).

Table 3-2 Image reconstruction results under different regularization parameters during

cleaning process for Plane 4

Regularization

Parameters

Frame Numbers

10 100 200 300 333

0.0007

0.007

0.07

0.7

Colorbar

In Table 3-2, image reconstruction results of Plane 4 under four different regularization

parameters throughout the cleaning process are implemented. All images were

reconstructed under the same range of color bar. The results under same order of

magnitude of regularization parameter have neglectable differences, so only the results

under different orders of magnitude were compared. Images for 0.0007 and 0.007

indicate that the percentage of error generated is exorbitant and no valid information can

be identified from those images. Images of 0.7 have shown a typical over-smoothed

occasion which indicates that the regularization parameter is too large. Eventually, 0.07

is selected to be the proper regularization parameter adopted in latter study as the

images reconstructed can match with visually inspected results.

Page 63: Electromagnetic Sensing Techniques For Multi- Phase Flow

63

3.3.2.2 Results

The inverse solutions of all four ERT planes during the entire cleaning process

calculated with Tikhonov regularization are shown in Figure 3-10 and 3-11.

The maximum and average conductivity values in above figures are converged to a

much smaller range near reference conductivity value comparing to those of LBP while

the curves are spikier. But the accuracy of the solutions near and after ending point is

significantly improved. The maximum conductivity values after ending point of all 4

planes stay steady at the reference level (0.06 S/m) with minor drifting, which enables

the position of ending point to be identified clearly. As for the average conductivity

curves, they are also very spiky and vibrate within a small range before the ending

points. Similar to the case of LBP, they cannot represent the practical processes either.

The performance can be explained by the convergent nature of Tikhonov regularization.

When the conductivity of the target to be tested is significantly different from the

reference value, the result will be distorted. In this experiment, from frame 25 when the

background material was changed from water to soil, the inverse solution was severely

distorted. When the overall conductivity level trended near the reference level, the

inverse solutions became more and more accurate.

Page 64: Electromagnetic Sensing Techniques For Multi- Phase Flow

64

Figure 3-10 Maximum conductivity values in all ERT planes during the cleaning process

calculated with Tikhonov regularization

Figure 3-11 Average conductivity values in all ERT planes during the cleaning process

calculated with Tikhonov regularization

In conclusion, Tikhonov regularization is more suitable for monitoring the ending point

of the cleaning process. However, due to its nature of converging the results to reference

conductivity values, corresponding optimization methods need to be carried out to

achieve more accurate results during the entire cleaning process.

Page 65: Electromagnetic Sensing Techniques For Multi- Phase Flow

65

3.4 Algorithm optimization with dynamic reference

3.4.1 Methodology

Figure 3-12 Relationship between measured boundary voltage and material conductivity

under same projection

Figure 3-13 Measured boundary voltages (U curves) comparison between pure water and

pure soil.

As an example, two ERT planes with the same dimension and structure are filled

respectively by two uniform conductive liquids of different conductivities 𝜎1 and

𝜎2(Figure 3-12). The projection paths under the same electrode pairs in the two planes

have the same shape. Hence, with fixed injection current on the transmitter electrode

pairs, the ratio of the measured boundary voltage across a receiver electrode pair in

Plane 1 to that of the same positioned pair in Plane 2 will equal to the ratio of the liquid

conductivity in Plane 2 to that of Plane1.

Similarly, for other pairs of electrodes, the complete sets of boundary voltage

measurements taken from the two planes, which are also known to be the 'U curves',

0 20 40 60 80 1000

200

400

600

800

1000

1200

1400

Reference Voltage (Water)

Projection Number

Volta

ge

mV

0 20 40 60 80 1000

5

10

15

Measured Voltage (Soil)

Projection Number

Volta

ge

mV

Page 66: Electromagnetic Sensing Techniques For Multi- Phase Flow

66

should also be proportional. This can be proved by Figure 3-13. Despite the deviations

caused by system noise, the two curves basically stay in the same shape.

Table 3-3 The ratio of measured voltage for each projection between the soil and water

background

Current

Injection

Receiver Electrode Pairs

02-03 03-04 04-05 05-06 06-07 07-08 08-09 09-10 10-11 11-12 12-13 13-14 14-15 15-16

16-01 1 2 3 4 5 6 7 8 9 10 11 12 13

01-02 14 15 16 17 18 19 20 21 22 23 24 25 26

02-03 27 28 29 30 31 32 33 34 35 36 37 38

03-04 39 40 41 42 43 44 45 46 47 48 49

04-05 50 51 52 53 54 55 56 57 58 59

05-06 60 61 62 63 64 65 66 67 68

06-07 69 70 71 72 73 74 75 76

07-08 77 78 79 80 81 82 83

08-09 84 85 86 87 88 89

09-10 90 91 92 93 94

10-11 95 96 97 98

11-12 99 100 101

12-13 102 103

13-14 104

60<ratio<80

80<ratio<100 Average Ratio: 75

Ratio>100

For all the corresponding measured voltage values under all projections, we also

calculated the ratios between water and soil background and the results are shown in

Table 3-3. 85 out of 104 ratios stayed between 60-80, which is the actual ratio between

the conductivities of the soil and water in our investigation.

3.4.2 Optimization procedure

The cause of the distortions in previous results calculated with Tikhonov regularization

is the significant difference between the measured boundary voltages and reference

voltages. On the other hand, if the reference voltages can vary dynamically with the

change of background conductivity distribution to approach the level of measured

voltages, the distortions can hence be reduced or even eliminated.

Page 67: Electromagnetic Sensing Techniques For Multi- Phase Flow

67

The average voltage level can be determined in many ways. The method adopted in this

experiment can be concluded as follows:

a) Extracting the 16 voltage values corresponding to the measurements taken from

where the distances between transmitter electrode pair and receiver electrode pair are

the smallest and the accuracies are the highest. The choice of 16 voltage values are the

most accurate because the path of electric field is the shortest so as to reduce the error;

b) Reducing abnormal large values by limiting them to the average level of peak values

in the reference voltage;

c) The median value of the 16 measured voltages is adopted as the criterion to judge the

average voltage level. The median value is adopted instead of average value to reduce

the impact of extremely large values caused by measurement errors.

Based on above method, the ratio between the average level of the measured voltages

and the reference voltages can be determined:

Equation 3-13

𝛾 = Vmm/VRm

𝑉𝑚𝑚 is the median value of the 16 chosen voltages from measured boundary voltages

and 𝑉𝑅𝑚 is that of the reference voltages. Hence, the dynamic reference voltages

corresponding to each frame is:

Equation 3-14

𝑉𝑅∗ = 𝛾 ∙ 𝑉𝑅

Furthermore, the formula of optimized Tikhonov regularization with dynamic reference

can be derived as:

Page 68: Electromagnetic Sensing Techniques For Multi- Phase Flow

68

Equation 3-15

��𝛼∗ = (𝐽

𝑇𝐽 + 𝛼2𝐼)−1𝐽

𝑇𝑉∗

Where

Equation 3-16

��𝛼∗ = [

𝜎1 − 𝛾 ∙ 𝜎𝑅

𝛾 ∙ 𝜎𝑅,𝜎2 − 𝛾 ∙ 𝜎𝑅

𝛾 ∙ 𝜎𝑅⋯

𝜎𝑤 − 𝛾 ∙ 𝜎𝑅

𝛾 ∙ 𝜎𝑅]−1

Equation 3-17

𝑉∗ = [𝑉1 − 𝑉𝑅

𝑉𝑅∗ ,

𝑉2 − 𝑉𝑅∗

𝑉𝑅∗ ⋯

𝑉𝑝 − 𝑉𝑅∗

𝑉𝑅∗ ]

−1

Hence the conductivity values calculated from Tikhonov regularization with dynamic

reference can be presented as:

Equation 3-18

��𝑤∗1 = [(��𝛼1∗ + 1) ∙ 𝛾 ∙ 𝜎𝑅, (��𝛼2

∗ + 1) ∙ 𝛾 ∙ 𝜎𝑅 ⋯(��𝛼𝑤∗ + 1) ∙ 𝛾 ∙ 𝜎𝑅]

3.5 Image reconstruction results calculated from Tikhonov

regularization with dynamic reference

3.5.1 Average conductivity values

Figure 3-14 illustrates the average conductivity values calculated from Tikhonov

regularization with dynamic reference in each frame. From frame 0 to around frame 25

when the testing regions were filled with tap water, the average conductivities of all

four ERT planes stayed at reference level (around 0.06 S/m). During frame 25 to 40, the

testing regions were filled by the soil with the average conductivity ranging from 4 to 6

S/m, as shown on the curves. The CIP process was then started from around frame 40.

The majority of the soil in straight pipe section (plane 1, 2 and 3) was flushed away and

the average conductivity dropped rapidly. The optimized ERT results indicate that plane

Page 69: Electromagnetic Sensing Techniques For Multi- Phase Flow

69

1 to 3 were cleaned around frame 40. As for plane 4, the majority of the soil still stayed

in the test region even after plane 1 to 3 were already fully cleaned. Then the amount of

soil starts to drop significantly from frame 50 until the plane is fully cleaned. In this

way, the average conductivity curves fully illustrate the whole process, which is an

important enhancement compared to conventional algorithms. This enables researchers

to analyse earlier stages of CIP.

Figure 3-14 Average conductivity values calculated from Tikhonov regularization with

dynamic reference

3.5.2 Maximum conductivity values

The maximum conductivity values of the four planes in each ERT frame calculated with

optimized Tikhonov regularization are shown in Figure 3-15 and Figure 3-16. Due to

system noise and the ill-conditioned nature of inverse problem, the maximum

conductivity values are slightly higher and spikier than the average conductivity values.

This is not critical as the main objective of analysing the maximum conductivity values

is to locate the ending point of the cleaning process. With the scale of Y axis narrowed

to 0~0.1 S/m, the ending point of all 4 planes can be clearly identified. Plane 1,2 and 3

in the straight pipe section were fully cleaned around frame 40, while plane 4 at the T

Page 70: Electromagnetic Sensing Techniques For Multi- Phase Flow

70

junction was fully cleaned around frame 340. Hence the ending point of the cleaning

process can be located at frame 340, which complies with the visually inspected result.

Figure 3-15 Maximum conductivity values calculated from Tikhonov regularization with

dynamic reference

Figure 3-16 Maximum conductivity values in smaller scale

3.5.3 Image reconstruction comparison

Table 3-4 illustrates the comparisons of reconstructed images between conventional

Tikhonov regularization and optimized Tikhonov regularization with dynamic reference.

Between frame 30 to 60, where the pipe is dominated by soil (highly conductive

Page 71: Electromagnetic Sensing Techniques For Multi- Phase Flow

71

component), the conventional Tikhonov regularization were not capable of providing

accurate reconstructed images as the average conductivity in the test region was

significantly different from the reference conductivity value. However, no significant

difference was discovered at later stage of the cleaning process (after frame 100) when

tiny amount of soil remained in the pipe and the average conductivity in the test region

was close to reference level. Above comparisons have shown the enhancement in image

reconstruction from the algorithm optimization at earlier stage of the cleaning process,

while the benefit of precisely locating the ending point still remained.

Table 3-4 Reconstructed image in Plane 4 comparisons between conventional and

optimized Tihonov regularization

Frame Numbers

10 30 60 100 200 300 333

Optimized

Algorithm

Conventional

Algorithm

Page 72: Electromagnetic Sensing Techniques For Multi- Phase Flow

72

3.6 Adopting Tikhonov regularization with dynamic reference

in different cleaning conditions

3.6.1 Results under higher flow rate with T pipe

Figure 3-17 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under higher flow rate. . a) Average conductivity

values; b) maximum conductivity values; c) maximum conductivity values in smaller scale.

The results of average and maximum conductivity values in Section 3.5 have shown the

capability of proposed optimization method with one set of measurement data from T

pipe against two conventional regularization algorithms. To validate its universal

feasibility, the optimized algorithm was applied to measurements taken under another

Page 73: Electromagnetic Sensing Techniques For Multi- Phase Flow

73

different flow rate, namely 8000 L/h. The visually inspected ending point of the

cleaning process (when the T junction was fully cleaned) was around Frame 170.

Results generated from Tikhonov regularization with dynamic reference are shown in

Figure 3-17.

Figures 3-17 a) is the average conductivity values in each frame, Figure 3-17 b) is the

maximum conductivity values in each frame and Figure 3-17 c) is Figure 3-17 b) in

smaller scale. Ending points and precise indication of conductivity level during the

whole process can still be observed from the two groups of optimized results,

respectively. Comparing with the 5400 L/h group, the ending point of the whole process

located at 170th frame, which is earlier than that in the 5400 L/h group. The above

results have proved the feasibility of adopting the optimization method with different

flow rates under the same pipe geometry.

3.6.2 Results with different pipe geometries

As the comparison group with T pipe under different flow rate has been implemented,

further investigation on a different pipe geometry was carried out as another

justification of universal feasibility study of this optimization method. The sample

group adopted a 1.5 inches straight pipe with a fully opened butterfly valve installed in

the middle (as introduced in Section 3.2.1). Four ERT planes were planted in the pipe,

two in the upstream of the valve and two in the downstream of the valve. The most

difficult ERT plane to be cleaned in principle is the third one (Plane 3) at immediate

downstream of the valve. Results calculated from the measurement data during the

cleaning process with the optimized Tikhonov regularization under two different flow

rates, namely 4100 L/h and 6200 L/h, are shown in Figures 3-18 and Figure 3-19.

Page 74: Electromagnetic Sensing Techniques For Multi- Phase Flow

74

Figure 3-18 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under 4100 L/h and butterfly valve. a) Average

conductivity values; b) maximum conductivity values; c) maximum conductivity values in

smaller scale.

The visually inspected ending point of the two cleaning process were around frame 75

and 70, respectively. The most difficult location to be cleaned indicated by the two

groups of results were both at Plane 3, which matched with theoretical assumption. The

ending point presented in Figure 3-18 c) and Figure 3-19 c) were around frame 75 and

70, which complied with the visually inspected result. For both groups of results, the

average conductivity values stayed between 5 to 7 S/m, despite very few spiky values.

Page 75: Electromagnetic Sensing Techniques For Multi- Phase Flow

75

The maximum conductivity values were slightly higher, but remained at reasonable

range. In conclusion, the results have proved that the optimization method is suitable for

ERT measurements in different pipe geometries.

Figure 3-19 Average and maximum conductivity values calculated from Tikhonov

Regularization with dynamic reference under 6200 L/h and butterfly valve. a) Average

conductivity values; b) maximum conductivity values; c) maximum conductivity values in

smaller scale.

Page 76: Electromagnetic Sensing Techniques For Multi- Phase Flow

76

3.7 Summary

In this chapter, a new approach to monitor and analyse the CIP process using ERT with

dynamic reference was proposed. With the fundamentals of ERT explained, three

conventional algorithms for the inverse problem calculation and image reconstruction

were compared, namely LBP, Tikhonov regularization and iterative algorithm.

Tikhonov regularization was proved to be more suitable in this research because of its

precision in locating the ending point of the cleaning process. However, the drawbacks

caused by the convergence nature of Tikhonov regularization should be eliminated to

achieve accurate inverse solution throughout the cleaning process, especially at the

earlier stage when the test regions were dominated by high conductivity components.

Thus, an optimization method with dynamic reference based on Tikhonov regularization

was proposed. The dynamic reference is generated by calculating the average level of

measured boundary voltages and correspondingly changing the reference voltages

proportionally. The result with optimized algorithm showed significant improvement

against conventional Tikhonov regularization. The merit of precisely locating the

ending point of the cleaning process remains, while the distortions caused by the

enormous conductivity difference between the testing region and reference. The

sharpness and reliability of the reconstructed images were also improved. In addition,

the results calculated with optimized algorithm and measured voltages under different

cleaning conditions, e.g. flow rate and pipe geometry, were compared to the visually

inspected results to justify the universal feasibility of the optimized algorithm in this

research.

However, drawbacks still exist in the optimization method. In the optimization

methodology, only uniform measured voltages, i.e. uniform U curves, were considered.

When the pipe is filled with roughly equal volume of soil and water, the shape of

Page 77: Electromagnetic Sensing Techniques For Multi- Phase Flow

77

measured voltage curve could be significantly different from the shape of original

reference voltage curve. Hence, the correspondingly generated reference will totally

distort the result. However, in this research, the majority of soil and mixture is flushed

away rapidly because of the high flow rate and the conductivity distribution within this

relatively short period is not the main objective, the drawback can thus be neglected

under this condition. If the dynamic reference optimization needs to be adopted in other

applications, this drawback should be considered in prior.

Page 78: Electromagnetic Sensing Techniques For Multi- Phase Flow

78

Chapter 4 Electromagnetic Simulations: Modelling

Three-Coil DEMIS and Oil-Saline Batch

Separation

In this chapter, the structure of the three-coil differential electromagnetic inductive

sensor was firstly introduced. In addition, a sensitivity analysis based on analytical

method is performed which gives rise to the optimized design of the sensor. Moreover,

an equivalent electrical model of the liquid-liquid separation model is derived based

upon which simulations are carried out to explain the evolution of sensor voltage with

respect to separation process. Finally, the simulation results are presented and discussed.

4.1 Introduction of differential electromagnetic inductive

sensor

4.1.1 Sensor structure

Figure 4-1 Schematic of differential electromagnetic inductive sensor

Comparing to conventional inductive sensors, the differential electromagnetic inductive

sensor consists of one cylindrical transmitting coil T and two cylindrical receiving coils

Page 79: Electromagnetic Sensing Techniques For Multi- Phase Flow

79

R1 and R2 (Figure 4-1). The three coils are aligned vertically, with the transmitting coil

located in the middle to form two symmetrical testing areas A1 and A2. The transmitting

coil is connected to the excitation signal of the impedance analyser. The two receiving

coils are connected to form a differential structure.

While functioning, the primary magnetic field generated by the alternating current in the

transmitting coil induces the second magnetic field in the materials. The phase and

magnitude of the secondary magnetic field is determined by the conductivity and

permittivity distribution in the sensing regions, leading to the change of the mutual

inductance between the transmitting coil and receiving coils. The output voltage

measured by impedance analyser can be presented as:

Equation 4-1

𝑉𝑜 = | 𝑉1 − 𝑉2|

Where V1 and V2 are the real parts of the induced complex voltages of the two receiving

coils, determined by the conductivity distributions in A1 and A2. When the distributions

in the two testing areas are the same, the output voltage after calibration ideally should

be zero. When the distributions in the two testing areas are different, the induced

voltages will become unbalanced, thus produce an output.

4.1.2 Sensitivity distribution

Rosell and etc. defined the relative sensitivity in a two-coil system as the relative

change at the receiver output produced by a conductivity perturbation[90]. The

mathematical form of the definition is:

Equation 4-2

𝑆𝑟 =(𝛥𝑉𝑉𝑒

)

𝛥𝜎

Page 80: Electromagnetic Sensing Techniques For Multi- Phase Flow

80

Where 𝛥𝑉 is the perturbation of the induced voltage, 𝑉𝑒 is the detected signal for the

empty space and 𝛥𝜎 is the perturbation of conductivity

Dyck and Lowther showed that the local conductivity sensitivity at a spatial point in the

testing area of a two-coil sensor system can be derived as[91]:

Equation 4-3

Sσ = ET ∙ ER

Where ET and ER

are the local electric field vectors when either of the two coils is

excited by unit current and the testing area is empty. Yin and Peyton considered the

motion of a conductive component in the system and its effect on the sensitivity

calculations[92]. In the current investigation, however, this effect is expected to be

negligible, since the velocity of the conductive medium in the separation process is

rather small. Xu et al. proposed a method of calculating the sensitivity distribution

based on field value extraction[93]. It is based on the calculation of electric field when

each of the coils is excited by unit current. Based on the definition of magnetic vector

potential 𝐴 (equation 4-4), the differential form of ampere circuital theorem (equation 4-

5) and the relationship between magnetic field strength �� and magnetic flux density ��

when the medium is evenly distributed in the field (equation 4-6), the magnetic vector

potential can be derived into the Poisson equation as shown in equation 4-7.

Equation 4-4

�� = 𝛻 × 𝐴

Equation 4-5

𝛻 × �� = 𝐽

Equation 4-6

Page 81: Electromagnetic Sensing Techniques For Multi- Phase Flow

81

�� = �� /𝜇

Equation 4-7

𝛻2𝐴 = −𝜇𝐽

In above equations, 𝜇 is the permeability of medium and 𝐽 is the current vector in the

coil. By splitting the excitation coil into certain numbers of elements and assuming that

the current element in each coil element can be presented in the form of 𝐼 · 𝑑𝑙 , where 𝐼

is the amplitude of the excitation current and 𝑑𝑙 is the position vector of the

corresponding segment of the coil, the Equation 4-7 can be derived as:

Equation 4-8

𝐴 =𝜇0

4𝜋∮

𝐼𝑑𝑙

𝑟

𝑙

𝜇0 is the vacuum permeability, and 𝑟 is the distance between the coil elements and the

target point in sensing region. When the electric and magnetic field is under sinusoidal

transformation, the differential form of Faraday Law of electromagnetic induction:

Equation 4-9

𝛻 × �� = −∂��

𝜕𝑡

can be derived as:

Equation 4-10

𝛻 × �� = −𝑗𝜔��

𝜔 is the excitation signal frequency. Hence according to equation 4-4, the electric field

at the target point can be calculated as:

Equation 4-11

Page 82: Electromagnetic Sensing Techniques For Multi- Phase Flow

82

�� = −𝑗𝜔𝐴

According to equation 4-3 and 4-11, the local conductivity sensitivity can be calculated

as:

Equation 4-12

Sσ = ET ∙ ER

= −𝜔2𝐴𝑇 · 𝐴𝑅

𝐴𝑇 and 𝐴𝑅

are the magnetic vector potential at the target point when the transmitting

coil or the receiving coil is excited by unit current, which can be calculated with

equation 4-8. Hence the sensitivity distribution in the sensing region can be achieved.

In this research, the sensitivity distribution of a simulated two-coil system with the coil

diameter of 150 mm and coil distance of 125 mm was studied. Both coils are divided

into 72 equal parts to calculate the current elements on them. The relative sensitivity

distribution of an axial cross-sectional testing area with the height and length of 150

mm was analysed. The cross-section was divided into 41×41 segments and the relative

sensitivity value of each segment is calculated. The result is shown in Figure 4-2.

Figure 4-2 Sensitivity distribution in the axial cross-sectional testing area of a simulated

two-coil sensor system

Page 83: Electromagnetic Sensing Techniques For Multi- Phase Flow

83

The above results have shown that the sensitivity value is relatively higher near the coils,

which indicates that the sensor output will be more sensitive to conductivity changes

near the coils. To implement the measurement of oil/water separation process in this

research, it is essential to achieve a homogeneous vertical sensitivity distribution in the

sensing region. Hence, corresponding optimization needs to be carried out.

4.1.3 Sensitivity distribution with different vessel radii

In order to analyse the spatial sensitivity distribution, the sensitivity values of all the

pixels on the same horizontal cross-section are added together to obtain the

corresponding planar sensitivity of the horizontal cross-section. The planar sensitivity

values represent the sensitivity of each horizontal plane with respect to the conductivity

change of homogeneously distributed material on the plane.

Equation 4-13

𝑆𝑘 = ∑𝑆𝑐𝑘

𝑛

𝑐=1

Where Sk is the planar sensitivity of the kth horizontal plane, Sck is the sensitivity of the

cth element in the kth plane and n is the number of elements adopted in analytical

solution. Figure 4-3 illustrates a simplified and normalized planar sensitivity

distribution profile between the transmitting coil and one of the receiving coils. The

sensing region being studied in this section is a cylinder with the height of 125mm and

the radius of 75mm. The cylindrical test region between the two coils in Figure 4-2 was

divided into 41 individual horizontal planes with corresponding planar sensitivity and

each plane is divided into 1681 segments.

Page 84: Electromagnetic Sensing Techniques For Multi- Phase Flow

84

Figure 4-3 Simplified and normalized planar sensitivity distribution

Figure 4-4 Planar sensitivity distribution under different testing vessel radii

The primary task is to reduce the variation of the planar sensitivity. Given a fixed size

of sensor coils, the central axial region has more uniform sensitivity than the peripheral

region of the coils. However, the absolute sensitivity is weaker in the central region. It

is therefore important to choose an appropriate vessel size. Planar sensitivity

Page 85: Electromagnetic Sensing Techniques For Multi- Phase Flow

85

distributions under different radii of the sensing region were calculated and are shown

in Figure 4-4, in which R stands for the radius of the coils.

It is clear that the variation of planar sensitivity distribution reduces with the testing

vessel radius, yet the absolute sensitivity value also drops. The average planar

sensitivity values were calculated and are listed in Table 4.1.

Table 4-1 The average and standard deviation of the sensitivity values under different test

region radii

Testing Vessel Radius 1/6R 2/6R 3/6R 4/6R 5/6R R

Average Sensitivity (V2/m

2) 0.1456 0.5731 1.2545 2.1428 3.1745 4.1515

Standard Deviation (V2/m

2) 0.0132 0.0443 0.0697 0.0787 0.2346 0.6611

To be more intuitive, the relationship of testing vessel radius, average sensitivity value

and sensitivity standard deviation are plotted in Figure 4-5. The standard deviations are

presented in the form of error bars.

Since we arbitrarily fix the size of the coil, the strategy in choosing the radius of the

vessel is to try to adopt a vessel with a smaller radius which, however, also needs to

satisfy the requirement of signal-to-noise ratio (SNR). In practical applications, the radii

of coils can be determined according to the radius of the separation vessel and the

optimum ratio achieved in this research. When the testing vessel radius reduced to 4/6

of the coil radius, the average sensitivity value is nearly halved while the deviation

range is nine times smaller than the original sensitivity distribution. In addition,

experimental tests showed that the average SNR with this testing vessel radius and the

FPGA-based impedance analyser (which will be introduced in Chapter 5) is around 60

dB which meet our measurement requirements. Hence, a mixing/separation vessel with

Page 86: Electromagnetic Sensing Techniques For Multi- Phase Flow

86

a diameter of 10 cm is selected for both the simulation model in later sections and

experimental setup in next chapter.

Figure 4-5 Average planar sensitivity values and standard deviation under different

testing area radii

4.2 Electrical model of liquid-liquid separation

4.2.1 Liquid-liquid separation model

A variety of liquid-liquid separation models have been proposed from either the

experimental or theoretical perspective[94]. Jeelani and Harland, in particular, have

detailed the basic principles governing the batch separation of oil and water[95]. In a

typical separation process, the liquid system can be divided into four zones, namely, a

clear oil zone, a dense-packed zone, a sedimentation zone and a clear water zone, as

shown in Figure 4-6 (a). The clear oil zone and clear water zone are occupied with a

single phase liquid, namely oil and water, respectively. The sedimentation zone is the

region where oil droplets are going through the buoyance process. After the buoyance

process, the oil droplets stack in the dense-packed zone and the bulk coalescence

Page 87: Electromagnetic Sensing Techniques For Multi- Phase Flow

87

process continues. The heights of the interfaces between clear oil zone and dense-

packed zone (hc), dense-packed zone and sedimentation zone (hp), sedimentation zone

and clear water zone (hs) are the main objectives to be investigated in this theory.

Figure 4-6 (a) 4 sections defined in oil/water separation system. (b) Height change of the

boundaries of 4 sections with time

In general, oil drops would ascend to form the dense-packed zone and the oil drops at

the top of the dense-packed zone would simultaneously coalesce to form the clear oil

zone. Therefore, the height of the interface between the clear oil zone and dense-packed

zone would decline, while the height of the interface between the sedimentation zone

and clear saline zone would increase with time. Since the speed of the sedimentation is

faster than that of the coalesce of oil drops, the height of the interface between the

dense-packed zone and sedimentation zone decreases until an inflection point ti when all

the oil drops are stacked in the dense-packed zone. After ti, the height of the dense-

packed zone gradually diminishes as oil drops continue to coalesce which gives rise to a

clear separation of oil and saline. The evolution of the interfaces between the liquid

zones can be depicted in Figure 4-6 (b).

Page 88: Electromagnetic Sensing Techniques For Multi- Phase Flow

88

Yu and Mao combined above theory with the lifetime distribution of drops of equal size

at oil-water interface and developed a mathematical model to present the changing trend

of interfaces as functions of time[96]. The mathematical equations are presented as:

Before the inflection point:

Equation 4-14

hs = v0t − (v0 − vi)𝑡2

t𝑖

After the inflection point:

Equation 4-15

hp2 = (1 − 𝜀0)H0 + (1 −1

𝜀p)H0𝜀0(1 + k1𝑡

𝑘2)𝑒−𝑘3𝑡𝑘4

During the entire separation process:

Equation 4-16

hc = H0(1 − 𝜀0) + H0𝜀0(1 + k1𝑡𝑘2)𝑒−𝑘3𝑡𝑘4

Where hs denotes the interface height between the clear water zone and the

sedimentation zone prior to the inflection point ti. hc denotes the height of the interface

between the clear oil zone and dense-packed zone throughout the whole separation

process. The height of the interface between the dense-packed zone and sedimentation

zone prior and anterior to the inflection point ti are denoted as hp1 and hp2, respectively.

H0 is the initial height of dispersion, ε0 is the initial oil hold-up fraction, εp is the oil

holdup fraction in the dense-packed zone. The inflection point is represented as ti. The

initial sedimentation velocity of oil drops and the sedimentation velocity of oil drops at

the inflection point are denoted as v0 and vi respectively. The parameters k1, k2, k3 and k4

are fitting constants without clear physical meanings and they could be obtained by

Page 89: Electromagnetic Sensing Techniques For Multi- Phase Flow

89

fitting the equations with practical experiment results. In addition, Jeelani and Hartland

proposed the mathematical equation of the interface height between dense-packed zone

and sedimentation zone before inflection point as[95]:

Equation 4-17

hp1 = H0 −H0 − hsi

ti𝑡

Where The height hs at ti is represented as hsi. Hence, all the interface heights of the

theoretical oil/saline separation model can be obtained once the parameters in the

equations are obtained.

4.2.2 Effective conductivity model

In order to understand the induced voltage of the receiving coil, an electrical model

needs to be derived. Specifically, the effective conductivity of the liquid zones is

essential in the calculation of the voltage of receiving coil. The conductivity of clear

saline σ1 in our investigation is kept at 4 S/m while clear oil is considered to be

nonconductive. The oil hold-up fraction in dense-packed zone εp is considered to be

constant during the separation process. The effective conductivity of liquid as a mixture

of liquids with two different conductivities σ1 and σ2 can be calculated using the

Maxwell Garnett mixing formula[97]:

Equation 4-18

σmp = σ1 + 3𝜀pσ1

σ2 − σ1

σ2 + 2σ1 − 𝜀p(σ2 − σ1)

Where σmp is the effective conductivity. As the conductivity of oil σ2 is zero, the

equation can be simplified as:

Equation 4-19

Page 90: Electromagnetic Sensing Techniques For Multi- Phase Flow

90

σmp =2 − 2𝜀p

2 + 𝜀pσ1

The effective conductivity in the sedimentation zone σmc can also be calculated via the

similar approach. However, calculating the oil fraction in the sedimentation zone εs is

more complex, as it changes with time. Before the inflection point, the thickness of the

dense-packed zone should be:

Equation 4-20

Δh1 = hc − hp1

The thickness of the clear oil layer is correspondingly:

Equation 4-21

H0il = H0 − hc

Assuming oil droplets are evenly distributed in all cross-sections of the testing area,

thus the oil fraction in the sedimentation zone can be obtained as:

Equation 4-22

𝜀s =[H0𝜀0 − (H0il + Δh1𝜀p)]

hp1 − hs

Combining equations 4-19 and 4-22, the time-varying effective conductivity value in

sedimentation zone can be calculated.

Therefore, the whole electrical model of the separation process is obtained. In practical

scenario, the conductivity of crude oil is considered to be zero, and the real time

conductivity of saline can be measured through the saline released from saline outlet of

the separation vessel.

Page 91: Electromagnetic Sensing Techniques For Multi- Phase Flow

91

4.3 Simulation of the electrical liquid-liquid separation model

Table 4-2 Experimental profiles and model parameters adopted from [96] for H0=300 mm,

D=154 mm, εp=0.65, and one hour agitation time

Experiment No. 1 No. 2 No. 3

Agitation speed (RPM) 350 350 500

ε0 0.3 0.5 0.5

v0 (mm/s) 1.1 0.51 0.25

vi (mm/s) 0.08 0.15 0.06

ti (s) 153.7 165.0 348.9

hsi (mm) 91.4 54.9 52.6

k1 ( S-k2) 4.1801×10-9 1.4149×10-4 2.3575×10-4

k2 3.2264 1.8231 1.4828

k3 ( S-k4) 2.1941×10-5 1.0743×10-3 1.4160×10-3

k4 1.9770 1.4273 1.1780

Before conducting experiments, it is of benefit to study the sensor output by simulation

based upon the electrical model in Section 4.2 in order to gain a better insight of the

separation process. The model relies on additional sensors to acquire the parameters in

the interface height functions. For example, a digital charge-coupled device (CCD)

camera may be needed to capture the initial sedimentation velocity of oil drops v0 and

the sedimentation velocity of oil drops at the inflection point vi. In this section, we adopt

the parameters given in [96] and they are listed in Table 4-2. The parameters were

evaluated based on practical experiments carried out in a mixing vessel with the

diameter of 154 mm and height of 300 mm. With the interface heights and effective

conductivity values determined, simulations were carried out for the corresponding

separation models and coil sensors in Ansoft Maxwell (electromagnetic simulation

toolkit).

An example of calculated interface heights as functions of time with the model

parameters from experiment No. 2 is shown in Figure 4-7.

Page 92: Electromagnetic Sensing Techniques For Multi- Phase Flow

92

Figure 4-7 Interface heights in a theoretical oil/saline separation model under 350RPM

and oil fraction at 50%

The inflection point lies at 165 seconds after separation process begins. Comparing

Figure 4-7 with Figure 4-6(b), it can be told that the calculated interface height curves

comply with basic oil/water separation theories.

Figure 4-8 Geometry of the simulation model. (a) 3D model; (b) 2D model.

Page 93: Electromagnetic Sensing Techniques For Multi- Phase Flow

93

The 3D simulation geometry is shown in Figure 4-8(a). For the models applied in the

simulations, the transmitting coil is excited with a current of 1 A at 1 MHz and the

conductivity of saline is 4 S/m. The maximum length of mesh elements is set to be 1.5

mm. To improve simulation efficiency, a 2D simulation model of was constructed

(Figure 4-8(b)). It is the axial cross-section of the test region and sensor coils in the

right quadrant of the YZ plane which is symmetrical to the Z axis. Then we used the

default function in Maxwell to generate the solution of the cylindrical model.

4.4 Simulation results and discussions

Figure 4-9 Induced voltage in both receiving coils and the differential output when oil

fraction is 50% and agitation speed is 350RPM

With the No.2 separation profile in Table 4-2, the simulated real parts of the induced

voltages (which indicates the distribution of conductivity components) during the

separation process in both receiving coils (V1 and V2 respectively) and the differential

output are shown in Figure 4-9.

It can be seen that voltage in the upper receiving coil decreases with time. This is

because in the upper testing zone A1 (see Figure 4-1), when a separation process starts,

Page 94: Electromagnetic Sensing Techniques For Multi- Phase Flow

94

the volume of saline would gradually decrease while the volume of oil would increase.

The increasing voltage in the lower receiving coil can be explained similarly. The

overall differential output of the sensor system would increase with time.

For comparison, simulations under different separation speeds were considered. The

separation speed of the liquid system is mainly dependent on the buoyance and

coalescence of the oil droplets. The buoyance velocity of an independent sphere oil

droplet in the continuous water phase can be calculated by Stokes' law[98]:

Equation 4-23

𝑣 =2

9∙(𝜌𝑤 − 𝜌𝑜)

𝜇𝑜∙ 𝑔 ∙ 𝑅2

Where g is gravitational acceleration, ρ0 and ρw are the mass density of oil and water

respectively, μo is the dynamic viscosity of oil and R is the radius of the oil droplet. This

equation indicates that the buoyance speed decreases as the oil droplet size decreases.

Coalescence process can be divided into two categories, which are the binary

coalescence while the oil droplets ascend, and the bulk coalescence in the dense-packed

layer [99]. Smaller oil droplet size at the initial stage will lead to lower bulk coalescing

rate. Hence when the oil/saline liquid system is agitated with higher rotational speed,

smaller oil droplets will be generated, and the separation speed should be slower.

Figure 4-10 compares the simulated differential sensor outputs of two separation

process, using profiles No. 2 and No. 3 in Table 4-2. The liquid systems were agitated

with same duration under 350 RPM and 500 RPM, with the oil fraction being fixed at

0.5. The results indicate that at the oil fraction of 0.5, the separation time can be

significantly influenced by the agitation speed and the simulation result complies with

above hypothesis.

Page 95: Electromagnetic Sensing Techniques For Multi- Phase Flow

95

Figure 4-10 Simulated sensor outputs of two separation process from the same liquid

system agitated with same time length and different speeds

Figure 4-11 Simulated sensor outputs of two separation process from the two liquid system

with different oil fractions agitated with same time length and speed

Figure 4-11 illustrates the simulated sensor outputs of two separation process using

profiles No. 1 and No. 2 in Table 4-2. The two liquid systems have different oil holdup

fractions, namely 0.5 and 0.3 and they were both agitated with the rotational speed of

350 RPM for one hour.

The inflection point of these two separation processes are similar (153.7 seconds and

165 seconds). However, by reading the differential sensor output, the separation process

Page 96: Electromagnetic Sensing Techniques For Multi- Phase Flow

96

under the oil fraction of 0.3 seems to end earlier than that under the oil fraction of 0.5.

This is because when the oil fraction is 0.3, the separation process would go through the

stage that the lower sensing area A2 is completely occupied with clear saline, while the

separation process carries on in upper sensing area A1. The difference of saline volumes

in the two sensing areas will remain the same and the main factor that determines the

output of sensor system is the distribution of saline in A1. Ideally if the sensitivity

distribution in both sensing regions are homogeneous, the differential sensor output will

stay constant. However, small variations still exist in sensitivity distribution which led

to the minor deviation of the output. In addition, the final stable value of differential

output is lower when the oil fraction is lower. This is because the difference of saline

volume in two testing areas is smaller.

It is also noticed that the curves in above two figures are not perfectly smooth. This is

caused by the mesh noise.

4.5 Summary

The objective of this chapter was to understand and simulate the function of differential

electromagnetic inductive sensor during the monitoring of oil/water separation process.

The structure of the sensor was firstly illustrated and the sensitivity distribution inside

the sensing region was calculated. The goal was to investigate the variation of vertical

sensitivity distribution so that corresponding optimization method could be applied.

Afterwards, mathematical oil/water separation models were studied based on the theory

of liquid interface height variation and Maxwell Garnett mixing formula. Detailed

model parameters under different mixing speeds and oil fractions from previous work

by other researchers were applied to the proposed models. At last, electromagnetic

Page 97: Electromagnetic Sensing Techniques For Multi- Phase Flow

97

simulations were carried out with separation models and simulated sensor to validate

the theoretical sensor output during different oil/water separation processes.

In the beginning, based on the concentric cylindrical structure of the sensor, the axial

cross-sectional sensitivity distribution was calculated based on analytical solution and

field value extraction. Afterwards, the vertical sensitivity distribution was simplified

into planar sensitivity distribution with the assumption of homogeneous distribution of

oil droplets on horizontal planes. The calculated planar sensitivity values showed that

the vertical distribution needs to be homogenized. Hence the approach of reducing

sensing region radius was proposed. Since this approach was a trade-off between

absolute sensitivity values and sensitivity variation range, vertical planar sensitivity

distributions under different sensing region radii were calculated and an optimum

choice of the radius was made. The sensitivity variation was reduced by nine times

while the average sensitivity value was halved. The SNR of the sensor output based on

the chosen radius of the sensing region and measurement and sensor systems adopted in

Chapter 5 was also tested and proved to meeting our requirements of measurement.

Then the theoretical oil/water separation process was investigated as well as the

mathematical equations that present the variation of liquid interfaces during the

separation process. By applying separation parameters fitted with practical separation

processes to the equations and calculating effective conductivity values in

corresponding zones, separation models that can be used in electromagnetic simulations

were constructed. Differential electromagnetic inductive sensor and separation models

with different pre-mixing conditions and oil fractions are simulated in the

electromagnetic simulation software package to establish theoretical output of the

Page 98: Electromagnetic Sensing Techniques For Multi- Phase Flow

98

sensor during separation processes and gain a better understand of how the change of

physical parameters lead to the change of sensor output.

The simulation results showed that the sensor is able to illustrate the progress of

oil/water separation process. The difference in separation speed could be identified

through the output signal and the output response to different oil fractions were also

presented. Hence the feasibility of carrying out practical measurement of oil/water

separation process with proposed sensor system was validated.

Page 99: Electromagnetic Sensing Techniques For Multi- Phase Flow

99

Chapter 5 Experimental System and Results In

Monitoring Oil-Water Separation With DEMIS

In this chapter, the design of the experimental system was firstly demonstrated.

Moreover, the validation of the system and experimental results were carried out.

Finally, experiments were conducted under different process conditions, e.g. agitation

speed, duration and oil-saline fraction, to assess the performance of the proposed system.

5.1 Experimental setup and testing strategy

Figure 5-1 Experimental system setup

The experimental system consists of three main parts, a differential electromagnetic

inductive sensor, field-programmable gate array (FPGA)-based impedance analyser, and

mixing and separation system (Figure 5-1).

Page 100: Electromagnetic Sensing Techniques For Multi- Phase Flow

100

5.1.1 Sensor system

The three coils of the differential electromagnetic sensor were winded around a

transparent plastic vessel with an outer diameter of 150 mm and a height of 300 mm.

The distance between coils is 125 mm with the transmitting coil locating in the middle

and the two receiving coils lying on the top and bottom, respectively. Each coil has five

turns of plastic-isolated copper wire. The transmitting coil was connected to the

excitation end of the FPGA-based impedance analyser and the two receiver coils were

connected together to form the differential structure and then connected to the

impedance analyser for the measurement of output signals.

5.1.2 Mixing and separation system

Figure 5-2 (a)Hardwood rod coated with black thermal plastic tube; (b) 3D-printed plastic

impeller

The mixing and separation system consists of 2 parts, a stirrer and a plastic baffled

vessel (Fig. 2). The stirrer (RZR 1, Heidolph UK) could achieve a maximum rotational

speed of 1700 RPM. The original rod and impeller attached to the stirrer are metallic,

which will interfere with inductance measurements. Hence, they are replaced with a

hardwood rod coated with thermal plastic and a 3D-printed plastic impeller respectively

(Figure 5-2). The diameter of impeller is 4cm and the length of rod is 30 cm. These

Page 101: Electromagnetic Sensing Techniques For Multi- Phase Flow

101

dimensions are chosen to make sure that the distance between the stirrer and coils is big

enough to minimise any possible interference.

The vessel is cylindrical with a diameter of 10cm. The vessel diameter is 2/3 of the coils

as the sensitivity distribution investigation in Section 4.1.3 suggests this is the optimal

choice for measurements. Four full-length baffles are installed evenly on the inner

vessel wall to avoid air entrapment and surface fluctuation during the mixing process.

5.1.3 FPGA-based impedance analyser

Figure 5-3 System block diagram

A custom digital instrument is developed for measuring the impedance changes of the

sensor due to magnetic induction. The instrument generates a sinusoidal signal for

sensor excitation; digital signal demodulation is implemented to obtain the in-phase and

quadrature components of the sensor response. The Zynq-7020 system on a chip (SoC)

is the backbone of the system; this chip integrates a Xilinx 7-series FPGA and an ARM

Page 102: Electromagnetic Sensing Techniques For Multi- Phase Flow

102

dual Cortex-A9 based processor[100]. The instrument exploits the chip capabilities by

implementing the signal generation and I/Q demodulation modules using the hardware

benefits of the FPGA. The ARM processor is used for data transferring between the

FPGA and a host computer.

The block diagram of the system is shown in Figure 5-3. The main elements of the

system include an FPGA for signal generation and I/Q demodulation, analogue-to-

digital (ADC) and digital-to-analogue (DAC) converters, a front-end circuitry, and a

host PC for data log, display and control.

The main elements of the Analogue/Digital block of Fig. 8 are the DAC and ADC

circuits. For the DAC, an AD9767 from Analog Devices is used; it has two 14-bit

outputs and up to 125 MSPS update rate. DAC outputs are followed by a differential-

current to differential-voltage conversion and low-pass filtering stage. For the ADC an

AD6645 from Analog Devices is used; it has 14-bit resolution and a maximum

sampling rate of 105 MSPS. The reason to choose 14-bit resolution ADC is because it

can satisfy the requirement for SNR (above 80 dB) with a relatively lower cost. The

parallel digital output of the ADC is directly interfaced with the Zynq-7020 FPGA. The

ADC input stage includes differential voltage translation; input swing range is ±0.55 V

centred at 2.4 V.

The front-end circuitry conditions and amplifies the excitation and measured signals.

The output of instrument at the last amplification stage is composed of a differential

pair of power amplifiers. Output voltage amplitude is 16 Vrms and fed to the excitation

coil. The detection circuitry includes a RF transformer followed by several differential

receivers to amplify the measured signal and feed it to the ADC. Input voltage

amplitude is in millivolt range ~4 mV. Up to four measurement channels can be

Page 103: Electromagnetic Sensing Techniques For Multi- Phase Flow

103

multiplexed and the signal gain is programmable thought the host PC. A similar

architecture was presented in [75] for conductive flow measurements.

For all experiments presented, excitation frequency is set to 1 MHz. The sampling

frequency is 100 MHz. Data rate output is 25,000 samples per second (I/Q data).

Samples are sent to a PC through an Ethernet link.

The custom instrument architecture gives two main advantages in author's opinion.

1) The hardware front-end can be customized according to the sensor/sample needs and

experimental setup. A power amplifier is integrated for sensor excitation (16 Vrms as

stated in manuscript). A millivolt range (~4 mV) input is expected. Integrating active

amplification stages to commercial instruments commonly degrades instrument

performance.

2) High data-rate output at high SNR for observing processes with different dynamics.

An FPGA is used as the core of the instrument for digital signal synthesis and

demodulation. FPGA can implement digital demodulation at high speed rates (100 MHz

as stated in the manuscript). This gives the possibility to capture the dynamics of the

process with great detail during all the stages. Commonly, there is a compromise

between the sample rate and the SNR, a good balance between these two figures is

achieved with the custom instrument.

5.1.4 Testing strategy

The experimental investigation started with the validation of the instrument by

measuring voltage signals, followed by the investigation of the vertical sensitivity

distribution in the sensing region. Then a test result example was presented and

compared with camera recorded saline interface height profile for validation purpose.

Page 104: Electromagnetic Sensing Techniques For Multi- Phase Flow

104

Finally, experiments with different agitation speeds, mixing durations and oil fractions

were conducted, and the results were discussed. To simulate practical industrial

applications, the liquid level has been kept constant throughout, at the same height as

that of the top receiving coil. Two different oil fractions, 50% and 33%, were

investigated respectively. Tests of higher oil fractions were not conducted as the

separation process under such conditions were difficult to visualise. Results of two

different agitation speeds (900 RPM and 1700 RPM) were compared under the 50% oil

fraction and only 1700 RPM was tested under the 33% oil fraction as the mixing

efficiency was too low at lower agitation speeds. For each agitation speed, three levels

of mixing time, namely 30 seconds, 5 minutes and 15 minutes were investigated, in

order to compare the separation processes under different droplet sizes. Each test with

different combination of agitation speeds and mixing times were repeated for three

times to verify the repeatability of the experiments.

5.1.5 Choice of parameters

In this section, the choices of some of the critical parameters in the designed system are

discussed.

(1) Optimization with reduced vessel/coil diameter ratio

From the analytical result of the sensitivity distribution in the last chapter, the

optimum vessel/coil diameter ratio of 2:3 is applied to the designed system.

With this optimization method, the variation of sensor output during a oil/water

separation process becomes more smooth and the suddenly change of signal

caused by heterogeneous sensitivity distribution is avoided. Hence, a better

correlation between sensor output signal and oil/water interface height change

can be achieved.

Page 105: Electromagnetic Sensing Techniques For Multi- Phase Flow

105

(2) Number of turns of the coils

In the proposed sensor system, there are five turns of each coil. With the

increasing number of turns, the induced voltage in receiving coils will be

enhanced. However, it will also reduce the resonance frequency of the coils. To

avoid the measurement frequency meets the resonance frequency, we chose

relatively fewer number of turns;

(3) Excitation frequency and voltage

The excitation frequency and voltage are the highest we can achieve from the

measurement system to achieve maximum signal strength.

5.2 Experiment and discussion

In this section, experiments with the proposed sensor and mixing-separation system

were undertaken. Firstly, the validation of the FPGA-based impedance analyser was

carried out and the sensitivity distribution in the designed sensor system was

investigated. Then the sensor output signal was linked to the saline interface height

change recorded by camera to validate the sensor output. Finally, differences of the

sensor outputs were compared to the changes of mixing conditions such as agitation

speed, mixing duration and oil fraction. Based upon these validations and comparisons,

the sensor’s capability of identifying the completion level and separation speed under

different process conditions was investigated.

The separation process of oil and saline highly relies on the oil droplet size distribution.

The oil droplet size distribution is determined by the agitation speed and mixing

duration. With higher agitation speed and longer mixing duration, the separation speed

is expected to be slower.

Page 106: Electromagnetic Sensing Techniques For Multi- Phase Flow

106

5.2.1 Instrument performance inspections

Figure 5-4 shows the instrument performance for measuring a voltage signal. The

figure shows the nominal value of the input signal in the ‘x’ axis; voltage range is in

millivolt range. Instrument measured values for the magnitude is plotted in the ‘y’ axis.

A proportional increase in the measurement can be observed for the corresponding

increase in the input signal. For this experiment an SNR greater than 85 dB is achieved

for all measurement points.

Figure 5-4 The instrument performance for measuring a voltage signal

5.2.2 Validation of sensitivity distribution

Experimental tests were carried out to evaluate the actual sensitivity distribution by

continuously adding same volume of saline into the separation vessel. The

corresponding output signal change is shown in Figure 5-5. According to Equation 4-1

and the sensitivity theory, when the planar sensitivity distribution is uniform, the sensor

Page 107: Electromagnetic Sensing Techniques For Multi- Phase Flow

107

outputs tend to increase proportionally before the interface of saline reaches the

transmitting coil plane and drop proportionally after the interface exceeds the plane. The

-shaped curve in Figure 5-5 implies that the vertical sensitivity distribution is uniform

enough for the experiment.

Figure 5-5 Experimental test result for vertical sensitivity distribution with saline

5.2.3 Experimental result example

Figure 5-6 shows the sensor output during a complete test cycle. The oil fraction in this

test was 50%. Initially (i.e., t = 0) the oil and saline stayed in two separate phases, with

the top sensing region A1 being filled with the oil and the bottom sensing region A2

being filled with the saline. At this stage the differential sensor output would be at

maximum. Mixing then started under the agitation speed of 1700RPM. It can be seen

that the output signal started to drop rapidly as the system was getting homogeneous,

and the conductivity distribution differences in the two sensing regions were

disappearing. After 30 seconds, mixing was stopped, and the oil/saline phases were

allowed to separate naturally for 500 seconds. As the separation process proceeded, the

difference of saline volume between A1 and A2 gradually increased, which led to the

0 500 1000 1500 20000.12

0.125

0.13

0.135

0.14

0.145

0.15

Saline volume (cm3)

Se

nso

r o

utp

ut

(V)

Page 108: Electromagnetic Sensing Techniques For Multi- Phase Flow

108

increase of the sensor output. When the oil/saline distribution recovered to the initial

level (i.e. oil and saline are completely separated), the sensor output stayed steady and

indicated that the separation process is finished.

Figure 5-6 Single test result under 1700RPM, 30 seconds mixing and 500 seconds

separation, oil fraction 50%

For analytical purpose, the separation part of the curve is plotted in Figure 5-7.

Figure 5-7 Sensor output signal during separation process

Page 109: Electromagnetic Sensing Techniques For Multi- Phase Flow

109

The trend and shape of the test result are generally consistent with the simulated

differential output result in Figure 4-9. However, differences still exist:

(a) Offset and variation range

The variation range of the test result (from 0.0002 V to 0.0016 V) is different to that of

the simulation result (from 0 V to 0.0006 V). This was caused by the differences in the

excitation signal and coil structure. In the simulations, the transmitting coil was excited

with unit current, while in the experiments, the transmitting coil was excited with 16

Vrms voltage. In addition, the practical coil structure is imperfect comparing to that in

the simulations.

When the oil/saline liquid system is homogeneous, the output of an ideal sensor system

excluding the influence from background materials should be zero, e.g. the simulation

results. However, the imperfection of practical coil structure and the background

materials together generated an offset to the measurements.

(b) Initial separation speed

At the initial stage of the experimental separation process, the signal increases slower

than simulation result. This is because in the simulations, the liquid system started the

batch separation process from steady state. However, when the separation process was

initiated in practical experiments, the liquid system suffers from an initial turbulence

from the terminated mixing process which slows down the separation process.

5.2.4 Validation of sensor output

A camera was set up to record the separation of the oil saline mixture while the sensor

output was logged simultaneously. The oil fraction was 50% in this experiment and the

initial height of the interface between oil and saline was 125 mm. Firstly, the liquid

Page 110: Electromagnetic Sensing Techniques For Multi- Phase Flow

110

system was mixed for 30 seconds under the agitation speed of 1700 RPM. Then mixing

was stopped to allow the mixture to separate for 270 seconds. Figure 5-8 shows some of

the screenshots from the recorded video during the separation process . A clear interface

between saline and the and oil/saline mixture can be observed in the video. Changes of

the interface height were measured at against time and the results were compared with

the sensor output in Figure 5-9.

Figure 5-8 Part of the screenshots from the recorded video during the separation process

Figure 5-9 Comparison between sensor output and saline interface height change during

the separation process

The interface height indicates the completion level of the separation process. From the

comparison in Figure 5-9, it is clear that the overall trend of sensor signal change is

consistent with the observed interface height change. The signal started to increase

when separation began and became steady when the separation process was

Page 111: Electromagnetic Sensing Techniques For Multi- Phase Flow

111

approaching the end. However, differences exist between the two curves. This could be

explained with the structure of oil-saline separation system mentioned in Section 4.2.

The liquid above clear saline includes oil and oil/saline mixture. The sensor output

reflects the distribution of both clear saline and the saline component in oil/saline

mixture, while the saline interface height change captured by camera only indicates the

level of clear saline in the vessel. Hence the difference of the two curves is caused by

the saline component in oil/saline mixture.

In conclusion, the comparison between the sensor output signal and visually observed

saline interface height change shows that the proposed instrument is capable of

detecting the final separation stage of the process. This serves as an initial validation of

the application of DEMIS in monitoring oil-saline separation. Further validation which

involves on-site facilities would be useful and we leave it for further studies.

5.2.5 Experiment results under different mixing conditions

5.2.5.1 1700 RPM agitation speed and 50% oil fraction

Figure 5-10 shows the variations of the sensor output as a function of time when the

agitation speed and oil fraction were fixed at 1700 RPM and 50% respectively. Tests

with three different mixing durations, namely, 30 seconds, 5 minutes and 15 minutes

were investigated. Each experiment was repeated for three times and the corresponding

sensor outputs were recorded. It can be seen from Figure 5-10 that the results in each

experiment are highly repeatable and consistent.

Page 112: Electromagnetic Sensing Techniques For Multi- Phase Flow

112

Figure 5-10 Sensor outputs of repeated experiments under agitation speed of 1700 RPM,

oil fraction 50%. (a) mixing duration 30 seconds; (b) mixing duration 5 minutes; (c)

mixing duration 15 minutes.

In Figure 5-11, the averaged sensor outputs of the three repeat experiments during the

separation stage for the three different mixing durations are compared. The standard

deviation on each time point is also calculated and presented on the curves as error bars.

The starting points of the three curves are rather close to each other, which indicates that

the liquid systems were all fully mixed and the volume distributions of oil were similar

in all three groups when the separation started. However, the difference in separation

speeds under different mixing durations can be observed clearly. This can be attributed

to the different oil droplet sizes. The longer the mixing duration, the smaller the average

Page 113: Electromagnetic Sensing Techniques For Multi- Phase Flow

113

droplet size, and the slower the separation speed. After the separation completed, the

sensor output value of the three groups stayed approximately at the same level as the

one before mixing started. This shows that the oil and saline recovered to the state

where they were completely separated.

Figure 5-11 Average sensor outputs of the repeated test under 1700 RPM during

separation process

5.2.5.2 900 RPM agitation speed and 50% oil fraction

Figure 5-12 Average sensor outputs of the repeated test under 900RPM during separation

process with error bars

Page 114: Electromagnetic Sensing Techniques For Multi- Phase Flow

114

The experiment results when the agitation speed was 900 RPM are shown in Figure 5-

12. In this case, at the beginning of the separation process, the average initial sensor

output values of the three groups were different. The initial value was larger when the

mixing duration was shorter. This is mainly because the liquid system was not fully

mixed and there was an oil layer remaining at the top of the mixing vessel, resulting in a

higher differential output from the sensors when the separation started. In addition, the

standard deviations of the repeat tests were also getting larger comparing to those of the

1700 RPM agitation speed. When the liquid system was not fully mixed, the oil droplet

size distribution would become much more spread out, which led to large variations of

the differential sensor output. It should be noted that the overall separation speed was

still slower when the mixing duration became longer, as the resulted average oil droplet

size was correspondingly smaller.

5.2.5.3 Results under 1700RPM agitation speed and a lower oil

fraction of 33%

Figure 5-13 presents the results with the agitation speed of 1700RPM but a lower oil

fraction of 33%.

Figure 5-13 Average sensor outputs of the repeated test at oil fraction of 33% under

900RPM during separation process with error bars

Page 115: Electromagnetic Sensing Techniques For Multi- Phase Flow

115

It can be seen that the results are also highly consistent with the simulation results. The

difference in separation speed among the three groups is the result of different mixing

time, which leads to different average oil droplet sizes. Same as the simulation results,

the curves of separation process enter stable stage earlier than that of the groups with

the oil fraction of 50%. The reason has already been explained in the simulation result

as when the lower testing area is filled with clear water, the change of sensor output will

depend on the saline phase distribution in the top sensing region.

5.3 Summary

In this chapter, the experimental sensor and measurement systems were designed and

investigated. Firstly, a brief introduction of the sensor system and mixing/separation

system was presented. Then the architecture and advantages of the FPGA based

impedance analyser were illustrated.

In the experiments and discussion section, the validations of the proposed system and

sensor output results were firstly described. The validation of measurement system was

carried out by measuring a voltage with known magnitude. The validation of the sensor

system was implemented by continuously adding same amount of saline and investigate

the sensor output change so as to validate that the vertical planar sensitivity distribution

is homogenous. Then the sensor output measured during a complete mixing and

separation process was presented and compared with the simulation results in Chapter 4.

The comparison indicated that the sensor output complied with simulated result, while

the differences between them were explained. In addition, the sensor output during the

separation process was compared with the interface height change recorded by a camera

synchronously. The comparison made between the sensor output signal and saline

interface height during the same separation process indicates that the proposed

Page 116: Electromagnetic Sensing Techniques For Multi- Phase Flow

116

instrument is capable of detecting the final separation stage of the process. At last,

experiments under different oil-saline fractions (33% and 50%), different agitation

speeds (900 RPM and 1700 RPM) and durations (0.5 minutes, 5 minutes and 15

minutes) have been conducted. Each experiment was repeated three times and the error

of the sensor outputs for repeated experiments was within 16%.

The validations showed satisfactory and reliable performance from the proposed system

for measuring the mixing and separation process of oil and saline. The sensor output

during separation processes under different agitation conditions were in good agreement

with the simulation results in Chapter 4. The results indicate that the proposed sensor

system is able to measure the separation process of oil and saline under different process

conditions. Considering the practical oil-saline separation as a continuous process, the

measurement information could be interpreted into the interface location information in

the separation vessel and saline and oil outlet speed can be adjusted accordingly to

guarantee product quality. In conclusion, the non-intrusive and non-invasive nature of

the electromagnetic inductive sensing technique suggests it is a promising method for

in-situ monitoring of oil-saline separations in industrial applications. To apply this

technique in real world application, there are a few problems that remains to be solved:

(1) As the DEMIS is mounted outside the separation vessel and there is a gap

between coils and the vessel, an optimum sensor structure needs to be designed

to fit it in a pilot-scale separator and corresponding electromagnetic isolation

method needs to be developed to prevent environment interference;

(2) When the scale goes up from lab scale to pilot scale, corresponding

optimizations need to be carried out in order to enhance the signals;

Page 117: Electromagnetic Sensing Techniques For Multi- Phase Flow

117

(3) Real world oil/water separation is a continuous process, hence a correlation

method between sensor output signal and oil/water interface height needs to be

developed.

Page 118: Electromagnetic Sensing Techniques For Multi- Phase Flow

118

Chapter 6 Conclusions and Future Works

This chapter presents the conclusions drawn from the simulation and experiment results

in previous chapters. Based on the conclusions, recommendations for possible future

works are illustrated.

6.1 Conclusions

The research conducted in this thesis concerns two industrial processes, namely the CIP

and oil-water separation process. The techniques adopted to analyse the two processes

are ERT and DEMIS, respectively.

6.1.1 Monitoring CIP using ERT with dynamic reference

The aim of monitoring and analysing CIP are to locate the most difficult section to be

cleaned and indicate the ending point of the whole process, in order to eliminate

unnecessary waste of water, chemical and waste-treatment cost.

According to our first research objective, ERT is adopted as the main technique to

monitor CIP in this research for its non-intrusive and non-hazardous nature while the

cost is relatively low. To implement ERT measurements, certain number of electrodes

(normally a group of eight or 16) are mounted on the interior pipe wall at the target pipe

sections. The measurement involves injecting current to certain electrode pairs and

measuring the voltage across all other neighbouring electrode pairs, which is defined as

‘adjacent strategy’. The complete set of measured voltage is then calculated using the

sensitivity matrix acquired from electromagnetic simulation and certain inverse problem

algorithms to obtain the conductivity distribution at the cross-section of the test region.

Page 119: Electromagnetic Sensing Techniques For Multi- Phase Flow

119

The second research objective is to visualize the component distribution inside the test

region to locate the most difficult position to be cleaned. The conductivity distribution

presents the location of the last soil residue in the test region which indicates the most

difficult section to be cleaned, and the evolution of maximum conductivity value

indicates the ending point of the cleaning process. The inverse calculation is severely

ill-posed, thus the proper choice of algorithm is critical to achieve the most accurate

result.

According to the third research objective, three mainstream inverse algorithms were

compared, namely LBP, Tikhonov regularization and iterative algorithms. Tikhonov

regularization showed significant advantage with satisfying performance near the d x

ending point and relatively low computational cost. However, with the reference

conductivity chosen to be the conductivity of tap water, the inverse calculation results

during the stage when the test regions were occupied by highly conductive component

(soil and the mixture of soil and water) was distorted due to the convergence nature of

Tikhonov regularization. Hence a novel optimization method was proposed to eliminate

the distortion. The optimization was implemented by configurating dynamic reference

voltages at all ERT frames corresponding to the level of measured voltages. The

dynamic reference voltages are proportional to the reference voltages measured when

the test region was filled with tap water, and the ratio between them was calculated

under certain strategy. The optimized results showed significant improvement under

high conductivity background, while the advantage of indicating the ending point of the

CIP process still remained. In addition, the optimized Tikhonov regularization with

dynamic reference was applied to the measurement data taken with different pipe

geometries and water flow rates. The consistent performance has proved the universal

feasibility of this optimized algorithm in this research.

Page 120: Electromagnetic Sensing Techniques For Multi- Phase Flow

120

6.1.2 Measuring oil-water separation process using DEMIS

The aim of monitoring industrial oil/water separation process is to ensure high

production efficiency and product consistency.

According to the first research objective, we proposed a novel sensing technique,

namely Differential Electromagnetic Inductive Sensor (DEMIS), which is capable of

monitoring the oil-water separation process non-intrusively and non-invasively with a

relatively low cost and complexity. The sensor is based on two differentially connected

cylindrical receiving coils and one cylindrical transmitting coil lies in the middle of

them. The three coils form two neighbouring test regions of which the sensor output is

determined by the difference between the mutual inductances. In this research, only the

conductive component of the mutual inductance (saline) was taken into consideration.

To implement the second research objective, the sensitivity distribution in the test

region was mapped using field vector extraction. It is soon discovered that the

sensitivity distribution needs to be homogenized as the sensitivity value is significantly

higher near the coils. A corresponding optimization method was proposed by decreasing

the ratio between the diameters of the separation vessel and the coils. As this method is

a trade-off between the sensitivity value and homogeneity, an optimum ratio was chosen

to satisfy both SNR and measurement accuracy of the system. Moreover, in order to

understand how the change in physical parameters of the liquid system leads to the

change in electrical sensor output, electrical simulations of monitoring oil-water

separation process with the proposed sensor system were conducted. An electrical

simulation model was constructed based on physical oil-water separation model. In the

physical liquid-liquid separation model, the liquid system was divided into four zones

based on the behaviour of oil droplets. The evolution of interfaces between different

Page 121: Electromagnetic Sensing Techniques For Multi- Phase Flow

121

zones can be presented as functions of time with parameters of the liquid system. The

oil fraction of each zone was also calculated and the equivalent conductivities of them

were expressed as functions of time using Maxwell Garnett mixing formula. In this way

the electrical simulation model of the oil-water separation system was implemented. By

adopting the parameters of oil-water separation system provided in other literatures,

simulations of the sensor output were carried out during separation processes under

different pre-mixing conditions, e.g. agitation speed, mixing duration and oil fraction.

The results complied with theoretical assumptions which proves the possibility of

monitoring oil-water separation process with the proposed sensor.

Based on the design and simulation of the sensor system, an experimental system was

implemented to accomplish the third research objective. The experimental system

consists of the sensor system, measurement system and mixing/separation system. The

structure of the sensor system is the same with the simulation model. The main

instrument adopted in the measurement system is a FPGA-based impedance analyser

and the architecture and advantages of which was well illustrated. The ratio between the

diameters of the coils and the vessel adopted in the mixing/separation system follows

the optimum ratio discussed in previous research. In the experimental section,

validations of the measurement instrument and the sensitivity distribution of the sensor

were firstly carried out. Then the sensor output during an oil-saline separation process

was validated by comparing it to the saline interface height change recorded with a

camera synchronously. At last, experiments under different pre-mixing conditions were

conducted. The validations and results have proved that the proposed sensing technique

is a promising method for in-situ monitoring of oil-water separation in industrial

applications.

Page 122: Electromagnetic Sensing Techniques For Multi- Phase Flow

122

6.2 Future work

Based on the conclusions drawn from this research, future works are suggested in

following aspects:

1. For the research in monitoring CIP using ERT with dynamic reference,

(1) The proposed optimization method with dynamic reference was designed

exclusively for the monitoring and analysis of the CIP process. The existence

duration of soil-water mixture in the pipe is short enough to be neglected. Hence

the background material in the test region is always considered to be

homogenous or nearly homogenous, which leads to uniform measured voltages

comparing to the reference voltages. However, when the optimization method is

applied to the measurement of mixture which consists of similar amount of both

high and low conductivity components, additional research should be carried out

to acquire more accurate results.

(2) This research still stays in the laboratory stage. It would be interesting to design

a practical system which enables the proposed system and method to monitor in-

situ real-time CIP process in a product plant.

(3) It is worth considering to apply the proposed method to the monitoring of other

industrial processes which share similar criteria of measurement. As an example,

waste water treatment requires the complete removal of impurities such as

electrolyte or heavy metal ions which would increase the conductivity of water.

By using ERT with dynamic reference, the conductivity of the liquid flow can

be monitored to ensure above impurities are fully removed.

2. For the research in measuring industrial oil-water separation process with

DEMIS,

Page 123: Electromagnetic Sensing Techniques For Multi- Phase Flow

123

(1) The differential structure of the sensor is currently implemented by connecting

the two receiving coils differentially. However, theoretically the sensor output

would be the same when two liquid systems share opposite fractions of oil and

saline, e.g. one liquid system has 30% of oil and the other liquid system has 30%

of saline. It would be worth considering to connect the two receiving coils

separately to the measurement system to acquire the induced voltages

independently and implement the differential calculation through data

processing. When the induced voltage in the upper receiving coil is zero, it

indicates that the upper test region is fully occupied with oil and the oil faction is

over 50%. In this way, the confusion on the oil fraction could be eliminated;

(2) In practical scenario, it is essential to know the conductivity of water in the

separation vessel to determine the offset value of sensor output. Hence a real-

time conductivity measurement system connected to the water outlet of the

vessel should be designed and embedded to the current system;

(3) Also in practical scenario, as the diameter of the coils is larger than that of the

separation vessel, further discussion and research need to be carried out with

field engineers to find a solution of installing the sensor to the separation vessel

without obstructing the separation process;

(4) The in-situ environment is complicated and the sensor signal could be interfered

in many ways. Hence proper electromagnetic isolation would be essential to

guarantee the reliability of the measurements.

Page 124: Electromagnetic Sensing Techniques For Multi- Phase Flow

124

REFERENCES

1. Brennen, C.E., Introduction to Multiphase Flow, in Fundamentals of Multiphase

Flow. 2005, Cambridge University Press New York. p. 1-28.

2. McQuillan, K. and P. Whalley, Flow patterns in vertical two-phase flow.

International Journal of Multiphase Flow, 1985. 11(2): p. 161-175.

3. Taitel, Y., O. Shoham, and J. Brill, Simplified transient solution and simulation

of two-phase flow in pipelines. Chemical engineering science, 1989. 44(6): p.

1353-1359.

4. Gregory, G., M. Nicholson, and K. Aziz, Correlation of the liquid volume

fraction in the slug for horizontal gas-liquid slug flow. International Journal of

Multiphase Flow, 1978. 4(1): p. 33-39.

5. Yang, W., M. Brant, and M. Beck, A multi-interface level measurement system

using a segmented capacitance sensor for oil separators. Measurement Science

and Technology, 1994. 5(9): p. 1177.

6. J. Mendes, A.P., L.F. Melo, Monitoring cleaning-in-place of shampoo films

using nanovibration technology. Sensors and Actuators, 2009. B 136: p. 376-

382.

7. J.C. Stewart, D.A.S., Clean in Place. Chemical Engineering, 1996. 103(1): p. 72.

8. M.S.Beck, Process Tomography: Principles, Techniques and Applications. 1995:

Butterworth-Heinemann Ltd.

9. Scott, D.M., Process Imaging For Automatic Control. 2005: Taylor&Francis

Group.

10. Borcea, L., Electrical impedance tomography. Inverse Problems, 2002. 18: p.

R99-R136.

11. Behin, J. and M. Aghajari, Influence of water level on oil–water separation by

residence time distribution curves investigations. Separation and purification

technology, 2008. 64(1): p. 48-55.

12. Falcone, G., Multiphase Flow Metering Principles. Developments in Petroleum

Science, 2009. 54: p. 33-45.

13. Nasr, G. and N. Connor, Natural Gas Engineering and Safety Challenges. 2016:

Springer.

14. H.S. Tapp, A.J.P., E.K. Kemsley, R.H. Wilson, Chemical engineering

applications of electrical process tomography. Sensors and Actuators, 2003. B

92: p. 17-24.

15. York, T.A., Status of electrical tomography in industrial applications. Journal of

Electronic Imaging, 2001. 10(3): p. 608-620.

16. W.Q. Yang, D.M.S., T.A. York and H. McCann, An image-reconstruction

algorithm based on Landweber's iteration method for electrical-capacitance

tomography. Meas. Sci. Technol., 1999. 10: p. 1065-1069.

17. Fraser Dickin, M.W., Electrical resistance tomography for process applications.

Meas. Sci. Technol., 1995. 7: p. 247-260.

18. Peyton, A., et al. Development of electromagnetic tomography (EMT) for

industrial applications. Part 1: Sensor design and instrumentation. in 1st World

Congress on Industrial Process Tomography. 1999.

19. Yu, Z., et al., Imaging system based on electromagnetic tomography (EMT).

Electronics Letters, 1993. 29(7): p. 625-626.

Page 125: Electromagnetic Sensing Techniques For Multi- Phase Flow

125

20. Al-Zeibak, S. and N. Saunders, A feasibility study of in vivo electromagnetic

imaging. Physics in Medicine & Biology, 1993. 38(1): p. 151.

21. Yang, W. and L. Peng, Image reconstruction algorithms for electrical

capacitance tomography. Measurement Science and Technology, 2002. 14(1): p.

R1.

22. Yang, W., Hardware design of electrical capacitance tomography systems.

Measurement Science and Technology, 1996. 7(3): p. 225.

23. Yang, W., Design of electrical capacitance tomography sensors. Measurement

Science and Technology, 2010. 21(4): p. 042001.

24. M. Cheney, D.I.a.J.C.N., Electrical impedance tomography. SIAM review, 1999.

41(1): p. 85-101.

25. George, D., et al., Validation of electrical-impedance tomography for

measurements of material distribution in two-phase flows. International Journal

of Multiphase Flow, 2000. 26(4): p. 549-581.

26. Heikkinen, L., et al., Real time three-dimensional electrical impedance

tomography applied in multiphase flow imaging. Measurement Science and

Technology, 2006. 17(8): p. 2083.

27. Holder, D.S., Electrical impedance tomography: methods, history and

applications. 2004: CRC Press.

28. Lucas, G. and R. Mishra, Measurement of bubble velocity components in a

swirling gas–liquid pipe flow using a local four-sensor conductance probe.

Measurement Science and Technology, 2005. 16(3): p. 749.

29. Gary Lucas, X.Z., Suman Pradhan, Optimisation of four-sensor probes for

measuring bubble velocity components in bubbly air-water and oil-water flows.

Flow Measurement and Instrumentation, 2011. 22: p. 50-63.

30. Kubáň, P. and P.C. Hauser, A review of the recent achievements in capacitively

coupled contactless conductivity detection. Analytica chimica acta, 2008. 607(1):

p. 15-29.

31. Du, L. and J. Zhe, A high throughput inductive pulse sensor for online oil debris

monitoring. Tribology International, 2011. 44(2): p. 175-179.

32. Ardron, K. and R. Duffey, Acoustic wave propagation in a flowing liquid-

vapour mixture. International Journal of Multiphase Flow, 1978. 4(3): p. 303-

322.

33. Atkinson, C. and H. Kytömaa, Acoustic wave speed and attenuation in

suspensions. International Journal of multiphase flow, 1992. 18(4): p. 577-592.

34. Takeda, Y., Velocity profile measurement by ultrasonic Doppler method.

Experimental thermal and fluid science, 1995. 10(4): p. 444-453.

35. Murai, Y., et al., Turbulent bubbly channel flow investigated by ultrasound

velocity profiler. Journal of Fluid Science and Technology, 2006. 1(1): p. 12-23.

36. Wang, T., et al., Application of Doppler ultrasound velocimetry in multiphase

flow. Chemical Engineering Journal, 2003. 92(1-3): p. 111-122.

37. Thorn, R., G. Johansen, and E. Hammer, Recent developments in three-phase

flow measurement. Measurement Science and Technology, 1997. 8(7): p. 691.

38. C. M. Bishop, G.D.J., Analysis of multiphase flows using dual-energy gamma

densitometry and neural networks. Nuclear Instruments and Methods in Physics

Research, 1993. A327: p. 580-593.

39. César Marques Salgado, C.M.N.A.P., Roberto Schirru, Luis E.B. Brandão, Flow

regime identification and volume fraction prediction in multiphase flows by

means of gamma-ray attenuation and artificial neural networks. Progress in

Nuclear Energy, 2010. 52: p. 555-562.

Page 126: Electromagnetic Sensing Techniques For Multi- Phase Flow

126

40. Van Santen, H., Z.I. Kolar, and A.M. Scheers, Photon Energy Selection for Dual

Energy γ- and/or X-ray Absorption Composition Measurements in Oil-Water-

Gas Mixtures. Nuclear Geophysics, 1995. 9(3): p. 193-202.

41. Narabayashi, T., et al., MEASUREMENT OF PHASE DISTRIBUTION

PHENOMENA IN HIGH PRESSURE STEAM-WATER TWO PHASE FLOW.

Dynamics of Two-Phase Flows, 1992: p. 423-438.

42. Heindel, T.J., A review of X-ray flow visualization with applications to

multiphase flows. Journal of Fluids Engineering, 2011. 133(7): p. 074001.

43. Mishima, K. and T. Hibiki, Development of high-frame-rate neutron

radiography and quantitative measurement method for multiphase flow research.

Nuclear Engineering and Design, 1998. 184(2-3): p. 183-201.

44. Takenaka, N., et al., Application of neutron radiography to visualization of

multiphase flows. Flow Measurement and Instrumentation, 1990. 1(3): p. 149-

156.

45. Falcone, G., et al. Multiphase flow metering: current trends and future

developments. in SPE annual technical conference and exhibition. 2001. Society

of Petroleum Engineers.

46. Ashton, S., et al. Development and trial of microwave techniques for

measurement of multiphase flow of oil, water and gas. in SPE Asia Pacific Oil

and Gas Conference. 1994. Society of Petroleum Engineers.

47. Wylie, S., A. Shaw, and A. Al-Shamma'a, RF sensor for multiphase flow

measurement through an oil pipeline. Measurement Science and Technology,

2006. 17(8): p. 2141.

48. Wu, Z., et al., Microwave-tomographic system for oil-and gas-multiphase-flow

imaging. Measurement Science and Technology, 2009. 20(10): p. 104026.

49. Wu, Z., Developing a microwave tomographic system for multiphase flow

imaging: advances and challenges. Transactions of the Institute of Measurement

and Control, 2015. 37(6): p. 760-768.

50. Withers, P.M., Ultrasonic, acoustic and optical techniques for the non-invasive

detection of fouling in food processing equipment. Trends in food science &

technology, 1996. 7(9): p. 293-298.

51. T.R. Hay, J.L.R., Fouling detection in the food industry using ultrasonic guided

waves. Food Control, 2003. 14: p. 481–488.

52. K.R. Lohr, J.L.R., Ultrasonic guided wave and acoustic impact methods for pipe

fouling detection. Journal of Food Engineering, 2003. 56: p. 315–324.

53. da Silva, J.J., et al., Non-invasive fast detection of internal fouling layers in

tubes and ducts by acoustic vibration analysis. IEEE Transactions on

Instrumentation and Measurement, 2009. 58(1): p. 108-114.

54. Schöning M J, B.D., Rolka D, et al., CIP (cleaning-in-place) suitable “non-

glass” pH sensor based on a Ta 2 O 5-gate EIS structure. Sensors and Actuators,

2005. 111(B): p. 423-429.

55. Chen, X.D., et al., On-line fouling/cleaning detection by measuring electric

resistance––equipment development and application to milk fouling detection

and chemical cleaning monitoring. Journal of Food Engineering, 2004. 61(2): p.

181-189.

56. Fowles, G., Flow, level and pressure measurement in the water industry. 1993:

Butterworth-Heinemann.

57. Nyce, D., Magnetostrictive linear position sensors. Sensors-the Journal of

Applied Sensing Technology, 1999. 16(11): p. 38-47.

Page 127: Electromagnetic Sensing Techniques For Multi- Phase Flow

127

58. Pasquale, M., Mechanical sensors and actuators. Sensors and Actuators A:

Physical, 2003. 106(1): p. 142-148.

59. Jaworski, A.J. and G. Meng, On-line measurement of separation dynamics in

primary gas/oil/water separators: challenges and technical solutions—a review.

Journal of Petroleum Science and Engineering, 2009. 68(1): p. 47-59.

60. Arvoh, B.K., N.-O. Skeie, and M. Halstensen, Estimation of gas/liquid and

oil/water interface levels in an oil/water/gas separator based on pressure

measurements and regression modelling. Separation and Purification

Technology, 2013. 107: p. 204-210.

61. Hauptmann, P., N. Hoppe, and A. Püttmer, Application of ultrasonic sensors in

the process industry. Measurement Science and Technology, 2002. 13(8): p.

R73.

62. Bukhari, S.F.A. and W. Yang, Multi-interface level sensors and new

development in monitoring and control of oil separators. Sensors, 2006. 6(4): p.

380-389.

63. Hjertaker, B.T., G.A. Johansen, and P. Jackson. Recent developments in

hydrocarbon separator interface imaging. in Proc. of SPIE. 2001.

64. Isaksen, O., A. Dico, and E.A. Hammer, A capacitance-based tomography

system for interface measurement in separation vessels. Measurement Science

and Technology, 1994. 5(10): p. 1262.

65. Yang, W., Further developments in an ac-based capacitance tomography system.

Review of Scientific Instruments, 2001. 72(10): p. 3902-3907.

66. Shafquet, A., et al., Estimation of gas void formation in statically cooled waxy

crude oil using online capacitance measurement. International Journal of

Multiphase Flow, 2015. 75: p. 257-266.

67. Yang, W., Sensors and instrumentation for monitoring and control of multi-

phase separation. Measurement and Control, 2006. 39(6): p. 178-184.

68. Bennett, M. and R. Williams, Monitoring the operation of an oil/water

separator using impedance tomography. Minerals Engineering, 2004. 17(5): p.

605-614.

69. Abouelwafa, M. and E. Kendall, The measurement of component ratios in

multiphase systems using alpha-ray attenuation. Journal of Physics E: Scientific

Instruments, 1980. 13(3): p. 341.

70. Kumara, W., B. Halvorsen, and M. Melaaen, Single-beam gamma densitometry

measurements of oil–water flow in horizontal and slightly inclined pipes.

International Journal of Multiphase Flow, 2010. 36(6): p. 467-480.

71. Meribout, M., A. Al Naamany, and K. Al Busaidi, Interface layers detection in

oil field tanks: a critical review, in Expert Systems for Human, Materials and

Automation. 2011, InTech.

72. Skeie, N.O. and M. Halstensen, Level estimation in oil/water separators based

on multiple pressure sensors and multivariate calibration. Journal of

Chemometrics, 2010. 24(7‐8): p. 387-398.

73. Jaworski, A.J. and T. Dyakowski, Measurements of oil–water separation

dynamics in primary separation systems using distributed capacitance sensors.

Flow Measurement and Instrumentation, 2005. 16(2): p. 113-127.

74. Yin, W., et al., Simultaneous noncontact measurement of water level and

conductivity. IEEE Transactions on Instrumentation and Measurement, 2008.

57(11): p. 2665-2669.

75. Yang, T., et al., A high frequency digital induction system for condutive flow

level measurements. Flow Measurement and Instrumentation, 2014. 37: p. 83-91.

Page 128: Electromagnetic Sensing Techniques For Multi- Phase Flow

128

76. Asskildt, K. and P. Hansson, New measuring sensor for level detection in subsea

separators. ABB Review, 1999(4): p. 11-17.

77. Geselowitz, D.B., An Application of Electrocardiographic Lead Theory to

Impedance Plethysmography. IEEE Transactions on Bio-medical Engineering,

1971. BME-18(No. 1): p. 38-41.

78. Lehr, J., A Vector Derivation Useful in Impedance Plethysmographic Field

Calculations. IEEE Transactions on Biomedical Engineering, 1972. BME-19(2):

p. 156-157.

79. Murai, T. and Y. Kagawa, Electrical impedance computed tomography based on

a finite element model. Biomedical Engineering, IEEE Transactions on, 1985(3):

p. 177-184.

80. Wang, M., Inverse solutions for electrical impedance tomography based on

conjugate gradients methods. Measurement Science and Technology, 2001.

13(1): p. 101.

81. Yang, W., et al., An image-reconstruction algorithm based on Landweber's

iteration method for electrical-capacitance tomography. Measurement Science

and Technology, 1999. 10(11): p. 1065.

82. Li, Y. and W. Yang, Image reconstruction by nonlinear Landweber iteration for

complicated distributions. Measurement Science and Technology, 2008. 19(9): p.

094014.

83. Schweiger, M., S.R. Arridge, and I. Nissila, Gauss-Newton method for image

reconstruction in diffuse optical tomography. Phys Med Biol, 2005. 50(10): p.

2365-86.

84. Yorkey, T.J., J.G. Webster, and W.J. Tompkins, Comparing reconstruction

algorithms for electrical impedance tomography. Biomedical Engineering, IEEE

Transactions on, 1987(11): p. 843-852.

85. Polydorides, N., Image reconstruction algorithms for soft-field tomography.

2002, University of Manchester: UMIST.

86. D.C. Barber, B.H.B., I.L. Freeston, Imaging Spatial Distributions of Resistivity

Using Applied Potential Tomography -APT. Information Processing in Medical

Imaging, 1984: p. 446-462.

87. P.J. Holden, M.W., and R. Mann, Imaging stirred-vessel macromixing using

electrical resistance tomography. American Institute of Chemical Engineers,

1998. 44(4): p. 780-790.

88. X. Deng, F.D., L. Xu, X. Liu and L. Xu, The design of a dual-plane ERT system

for cross correlation measurement of bubbly gas/liquid pipe flow. Meas. Sci.

Technol., 2001. 12: p. 1024-1031.

89. Krawczyk-StańDo, D. and M. Rudnicki, Regularization parameter selection in

discrete ill-posed problems—the use of the U-curve. International Journal of

Applied Mathematics and Computer Science, 2007. 17(2): p. 157-164.

90. Rosell, J., R. Casanas, and H. Scharfetter, Sensitivity maps and system

requirements for magnetic induction tomography using a planar gradiometer.

Physiological measurement, 2001. 22(1): p. 121.

91. Dyck, D., D. Lowther, and E. Freeman, A method of computing the sensitivity of

electromagnetic quantities to changes in materials and sources. IEEE

Transactions on Magnetics, 1994. 30(5): p. 3415-3418.

92. Yin, W. and A.J. Peyton, Sensitivity formulation including velocity effects for

electromagnetic induction systems. Magnetics, IEEE Transactions on, 2010.

46(5): p. 1172-1176.

Page 129: Electromagnetic Sensing Techniques For Multi- Phase Flow

129

93. Xu, K., et al., Sensitivity derivation and calculation of electromagnetic

tomography (EMT) sensor based on field value extraction. Chinese Journal of

Sensors and Actuators, 2011. 24(4): p. 543-547.

94. Al-Zuhair, S., Using liquid–liquid deep settling model in determining the design

parameters of crude palm oil settler. Separation and purification technology,

2004. 35(2): p. 133-140.

95. Jeelani, S. and S. Hartland, Effect of dispersion properties on the separation of

batch liquid− liquid dispersions. Industrial & engineering chemistry research,

1998. 37(2): p. 547-554.

96. Yu, G.Z. and Z.S. Mao, Sedimentation and coalescence profiles in liquid‐liquid

batch settling experiments. Chemical engineering & technology, 2004. 27(4): p.

407-413.

97. Faraj, Y., et al., Measurement of vertical oil-in-water two-phase flow using dual-

modality ERT–EMF system. Flow Measurement and Instrumentation, 2015. 46:

p. 255-261.

98. Batchelor, G., An Introduction to Fluid Mechanics, 615 pp. Cambridge

University Press, New York, 1967.

99. Jeelani, S.A.K. and S. Hartland, Prediction of steady state dispersion height

from batch settling data. AIChE journal, 1985. 31(5): p. 711-720.

100. Xilinx, Zynq-7000 All Programmable SoC.