electrical services concept design report social and ......electrical services concept design report...
TRANSCRIPT
Electrical Services
Concept Design Report
Social and Affordable Housing –
Stage 2
27 Durham St, Mount Druitt
Client:
Anglican Community Services T/A Anglicare
Level 2, 62 Norwest Boulevard
Baulkham Hills NSW 2153
(T) 02 9421 5333
Electrical Services Consultant:
Intrax Consulting Engineer t/a Insync Services
Suite 6.02, Level 6, 89 York Street
Sydney NSW 2000, Australia
(T) 02 9262 3400
File: 20180080 - Mount Druitt Site - Electrical Services Concept Design Report
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 2 of 26 Revision E – DA Issue
Review and Approval Record
Rev Date Description of Release Prepared By Reviewed By Approved By
A 29/06/18 For Information AR BL BL
B 09/07/18 For Information AR BL BL
C 26/10/18 For Information AR BL BL
D 01/11/18 For Information AR BL BL
E 04/12/18 DA Issue AR BL BL
This document is and shall remain the property of Insync Services. The document may only be
used for the purpose for which it was commissioned and in accordance with the Terms of
Engagement for the commission. Unauthorized use of this document in any form whatsoever is
prohibited.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 3 of 26 Revision E – DA Issue
Contents
1 Executive Summary 5
1.1 Summary 5
1.2 Code Compliance 5
1.3 Site HV Infrastructure 5
1.4 Communications Infrastructure 6
2 Introduction 7
2.1 Background 7
2.2 Aims 7
2.3 Briefing Documents 7
2.4 Development Description 7
2.5 Associated Services 7
3 Scope of Work 9
3.1 Extent of Services 9
3.2 Code Compliance 9
3.3 Scope of Work – Power Supply 9
3.4 Scope of Work - Lighting 10
3.5 Scope of Work - Communications 10
3.6 Scope of Work – Security, Access Control & Intercom System 10
3.7 Scope of Work – Dry Fire 10
3.8 Separation 10
4 Design Principles 11
4.1 Background 11
4.2 Cost & Efficiency 11
4.3 Quality & Longevity 11
4.4 Uniformity 11
4.5 Serviceability 11
5 Power Services 13
5.1 LV Power Infrastructure 13
5.2 Electrical Reticulation 13
5.3 Main Switchboard and Distribution Boards 14
5.4 Metering 14
5.5 Residential Apartment Power Outlets 15
5.6 Retail Tenancies/ Offices Power Outlets 15
5.7 Public Area Power Outlets 15
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 4 of 26 Revision E – DA Issue
6 Data Communications 16
6.1 Data Communications Services 16
6.2 Duct/Conduit Requirements – Lead In 16
6.3 Residential Apartment Data Outlets 16
6.4 Retail Tenancy/ Office Data Outlets 16
6.5 Public Area Data Outlets 17
7 Lighting Services 18
7.1 Internal Lighting Generally 18
7.2 External Lighting Generally 18
7.3 Controls 18
7.4 Development Illumination Level 18
7.5 Common Area Illumination Level 18
7.6 Exit & Emergency Lighting 19
7.7 Emergency Luminaires 19
8 Security Access Control, CCTV and Intercom Systems 20
8.1 Security Access Control System 20
8.2 Access Control 20
8.3 CCTV System 21
8.4 Entry Intercom System 21
9 MATV/ PayTV 22
10 Dry Fire Services 23
10.1 Electric Fire Generally 23
10.2 Automatic Fire Alarm and EWIS 23
11 Spatial Requirements 24
12 Appendix A – Concept Drawings & Schematics 26
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 5 of 26 Revision E – DA Issue
1 Executive Summary
1.1 Summary
This electrical services concept design report outlines the scope of works, design criteria,
components and materials which will be adopted by Insync Services for completion of the
electrical services design and documentation for the proposed Social and Affordable Housing –
Stage 2 development site at 27 Durham St, Mount Druitt.
The report will form the basis for communication of design principles to the Client for review,
comment and sign-off, such that the electrical services design and documentation can be
completed for the project.
1.2 Code Compliance
The electrical services covered by this concept design report will be designed to comply with the
following requirements;
Electrical
Services
Design Codes Proposed
Compliance
Power Supply National Construction Code
A.S.3000 (SAA Wiring Rules)
A.S.3008 – Selection Of Cables
NSW Installations and Wiring Rules
Deemed To Satisfy
Lighting System National Construction Code
A.S.2293 - Emergency & Exit Lighting
A.S.1158 – Road Lighting
A.S.1680 –General Lighting in a workplace Series
A.S.4282 –Control of the obtrusive effects of outdoor
lighting
Deemed To Satisfy
Communications
System
National Construction Code
A.S.3015 – Extra Low Voltage D.C. Power Supplies
Within Public Telecommunications Networks
Austel Technical Standard TS008 – Authorised Cabling
Products
Austel Technical Standard TS009 – Customer Cabling
Requirements
A.S.1367 – Coaxial Cable Systems
A.S.3080 – Information technology – generic cabling for
customer premises
A.S.3084 – Telecommunications installations pathways
and spaces in commercial buildings
Deemed To Satisfy
Fire Detection
System
National Construction Code
A.S.3786 – Smoke Alarms
A.S 1670 – Automatic Smoke Detection System
Deemed To Satisfy
*NCC – National Construction Code which includes:
• Volume 1 – Building Code of Australia – Class 2 to Class 9 Buildings
• Volume 2 – Building Code of Australia – Class 1 and 10 Buildings
• Volume 3 – Plumbing Code of Australia
1.3 Site HV Infrastructure
Insync Services has undergone an early maximum demand calculation to ascertain approximate
total load of the proposed site. The calculated electrical maximum demand for the site based on
AS/NZS 3000:2018 is calculated to be 920A/ph (635kVA). A new kiosk substation will likely be
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 6 of 26 Revision E – DA Issue
required for the proposed site. An application for connection to Endeavour Energy will be required
to ascertain the type of electricity supply to the building.
The pad-mount substation location shall comply with all clearances met in accordance to the
Level 3 ASP designer and local supply authority requirements.
An accredited Level 3 service provider (ASP) will be required to undergo the design and to
undergo an investigation for the most effective location the substation to connect to the existing
Endeavour Energy electricity network. Dial Before You Dig information suggests that the
electricity network is available along Durham St.
1.4 Communications Infrastructure
NBN fibre appears to be available in the area and is proposed to be used for the development.
Figure 1 – NBN Service Availability (www.nbnco.com.au)
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 7 of 26 Revision E – DA Issue
2 Introduction
2.1 Background
Anglicare has engaged Insync Services to provide building services consultancy for the proposed
Social and Affordable Housing – Stage 2 development site at 27 Durham St, Mount Druitt.
Specifically, Insync Services have been engaged to provide engineering consultancy concept
design reports to cover the following building services disciplines;
• Electrical Services
• Fire Services
• Hydraulic Servicers
• Mechanical Services
2.2 Aims
The aim of this concept design report is to provide a detailed description of the electric services
design proposals associated with the development. Specifically the report is intended to provide
a summary of the following;
• Identification of services to be provided.
• Description of the codes to which they will be installed.
• Description of the basis for design.
• Description of the required performance.
• Description of the materials to be used.
This document shall form the basis for communication of design principles and specific building
services design requirements to the Client and wider design team, such that the building services
design principles can be fundamentally incorporated into the architectural planning proposal to
be submitted for the development.
2.3 Briefing Documents
The electrical services engineering elements considered within this report have taken into
account the following briefing documentation and investigations;
• National Construction Code.
• Relevant Australian Standards.
• Authority design and guidelines.
• Authority Main Diagrams
• Preliminary architectural drawings prepared by Group GSA Pty Ltd.
2.4 Development Description
The proposed development scheme is yet to be finalised however for the purposes of this review
we have made the following assumptions;
1. The development will contain 1 level of basement carparking.
2. The development will contain ground floor retail.
3. The development will contain ground floor commercial.
4. The development will contain approximately 113 SAH rentals.
5. The development will contain approximately 60 private rentals.
6. The development will be less than 25m in effective height as Classified by the National
Construction Code.
7. The development will comply with Basix requirements, in terms of environmental
performance.
2.5 Associated Services
The associated services engineering elements will be considered in conjunction within this report
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 8 of 26 Revision E – DA Issue
are as follows;
• Fire Rated Construction as detailed by the Architect and Structural Engineer.
• Acoustic Performance as detailed by the Acoustic Engineer.
• Alternative Solutions as detailed by the Fire Engineer.
• Site specific requirements as detailed by the Mechanical Engineer.
• Site specific requirements as detailed by the Hydraulic Engineer.
• Site specific requirements as detailed by the Landscape Contractor.
• Site specific requirements as detailed by ASP3
• Site specific requirements as per NBN Co design guidelines.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 9 of 26 Revision E – DA Issue
3 Scope of Work
3.1 Extent of Services
The extent of Electrical services required throughout the development will include the following:
• Power Supply Systems
• Lighting Systems
• Communication Systems
• Security & Access Control systems
3.2 Code Compliance
The proposed code compliance for electrical services required throughout the development will
include the following:
Electrical Services Design Codes Proposed
Compliance
Power Supply National Construction Code
A.S.3000 (SAA Wiring Rules)
A.S.3008 – Selection Of Cables
A.S.3439 – Low Voltage Switchgear & Control Gear
Assemblies
NSW Installations and Wiring Rules
Deemed To
Satisfy
Lighting Design National Construction Code
A.S.2293 - Emergency & Exit Lighting
A.S.1158 – Road Lighting
A.S.1680 – Interior Lighting in a workplace
A.S.4282 – Control of the obtrusive effects of
outdoor lighting
Deemed To
Satisfy
Communications National Construction Code
A.S.3015 – Extra Low Voltage D.C. Power Supplies
Within Public Telecommunications Networks
Austel Technical Standard TS008 – Authorised
Cabling Products
Austel Technical Standard TS009 – Customer
Cabling Requirements
A.S.1367 – Coaxial Cable Systems
A.S.3080 – Information technology – generic
cabling for customer premises
A.S.3084 – Telecommunications installation
pathways and spaces in commercial buildings
Deemed To
Satisfy
Lightning
Protection
National Construction Code
A.S.1768 – Lightning Protection
Deemed To
Satisfy
3.3 Scope of Work – Power Supply
The electrical services engineering elements considered within this report are as follows;
• Site infrastructure and reticulation design systems with respect to the High Voltage work.
This includes providing an application for connection to the electricity supply authority
(Endeavour Energy) and paying all associated fees.
• Low Voltage Power distribution systems
• Metering to suit strata arrangement
• Earthing systems and bonding
• Site Maximum Demand Calculation Estimates
• Electrical Spatial requirements (Electrical Risers, Switchrooms, and other electrical
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 10 of 26 Revision E – DA Issue
rooms).
• General and Permanent power provisions
• Cable Management Systems
• Building Management System Integration
3.4 Scope of Work - Lighting
The scope of work required will include, but not be limited to, the following:
• General internal lighting Systems
• Lighting Control system to comply to BCA Section J
• External lighting and integrated control systems
• Security lighting and public walkways.
• Exit and Emergency lighting systems (Non-monitored System)
• Luminaire schedule
3.5 Scope of Work - Communications
The scope of work required will include, but not be limited to, the following:
• Make application to NBN Co and carry out full design of NBN Co infrastructure to the full
requirements of the NBN Co design guideline for NBN Co final certification.
• Installation of NBN Co communications infrastructure
• Fibre Communication infrastructure provision residential apartment units and retail space
(Reticulation by developer. NBN fibre cabling and NBN active equipment by NBN Co.)
• CAT6a structured cabling from NBN Network Termination Device (NTD) to data outlets
(by Contactor)
• Communications Earthing and Bonding to NBN Co Requirements
• Communication Spatial requirements (IT rooms, Communication Riser, other IT
cupboards per common floor, internal residential apartment units, commercial, etc)
• Cable management systems
• Free to Air and Pay TV systems
3.6 Scope of Work – Security, Access Control & Intercom System
The scope of work required will include, but not be limited to, the following:
• Door Access Control facilities at site entry and building/foyer entry points.
• Intruder Detection monitoring facilities to the perimeter of the building, common and
circulation areas, within the lifts and carpark and building entrances. No door
monitoring to apartments.
• Lift Access Control System interface
• Video intercom system
3.7 Scope of Work – Dry Fire
• Main fire indicator panel with integral building occupant warning system (BOWS) at main
entry lobby to AS1670
• Mimic panels at alternative building entries as required
• Smoke detectors to AS1670
• Thermal detectors to AS1670
• Emergency speakers to AS1670
3.8 Separation
The scope of work required shall include, but not be limited to, the following:
• Services penetrations to be fire-rated to a standard detail and certified by a single company
across all trades. All to coordinate with all other service trades.
• Electrical services risers to be fire rated on a floor to floor basis (fire rate the vertical
penetrations through slabs).
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 11 of 26 Revision E – DA Issue
4 Design Principles
4.1 Background
Anglicare have specific requirements in terms of building services outcomes with regard to this
development including the following areas;
• Cost & Efficiency
• Quality & Longevity
• Uniformity
• Serviceability
All design shall be prepared with due regard to building services design such that the clients
overall objectives for the development can be realised. In particular, the spatial requirements
for building services shall be determined and incorporated into the architectural proposals from
first principles so that further development of the architectural proposals can be undertaken as
the design progresses without the need to backtrack and compromise architectural integrity of
the submission as a result of building services requirements that have not previously been
adequately considered.
4.2 Cost & Efficiency
The client has aggressive cost benchmarks which will be required to be achieved for the
procurement of this development. These benchmarks are not able to be achieved without the
fundamental integration and coordination of building services concurrent with development of the
architectural design. Specific areas for consideration include the following;
• Equipment location for maximum efficiency.
• Adequate floor to floor heights.
• Vertical alignment of services risers.
• Standardised design forms that bring cost savings through repetition.
• Development of typical components that can be pre-fabricated off site.
• Continuity of wet area locations at typical floor changes to reduce bulkheads below.
• Modular design of plant where applicable to match proposed construction staging.
• Selection of standard manufacture equipment that is readily available.
• Selection of low maintenance plant & equipment.
• Duplication of equipment where required to provide operational redundancy in critical
aspects of the buildings operation.
4.3 Quality & Longevity
The client requires a building that is fit for purpose in terms of the requirements for its ongoing
operation. Selection of plant and equipment shall provide trouble free operation over
the duration of its life cycle, aside from the regular maintenance program. Equipment
shall be selected with due consideration to having demonstrated proven reliability on similar
installations, in similar operating conditions. Equipment supply shall be via companies that can
demonstrate a long-term trading history in the Australian market, and have local agents capable
of providing the necessary technical support and parts availability as will be required throughout
the equipment’s life cycle.
4.4 Uniformity
Uniformity of type and manufacture of each specific type of equipment and accessory shall be
preserved throughout the whole installation. Where possible, the number of types of equipment
provided by an individual supplier shall be maximised.
4.5 Serviceability
The client requires a building that is fit for purpose in terms of the requirements for its ongoing
operation. Spatial allocation for plant and equipment shall provide due consideration for all ongoing
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 12 of 26 Revision E – DA Issue
maintenance requirements of the equipment, including total replacement of the equipment at
completion of its life cycle. Adequate clearance shall be provided around all equipment for
maintenance access, with due consideration given to aspects of Safety In Design principles as may
be applicable. Access shall be arranged so as to provide minimal disruption to the normal operation
of the building and minimise any inconvenience to the building occupants. Any need to alter or
damage building fabric to effect equipment maintenance shall be avoided under all
circumstances.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 13 of 26 Revision E – DA Issue
5 Power Services
Generally, the low voltage power design will cover the overall electrical infrastructure works and
power distribution system arrangement through to the retail outlet and residential apartments
and common areas including power supply to all services deemed to be essential to the safety
and normal operation to the site:
5.1 LV Power Infrastructure
• Liaison with the supply authority with respect to the calculated site maximum power
demand. Furthermore, the electrical design involvement will extend to include liaison and
coordination with a level 3 Accredited Service Provider to ensure service mains and
protective device coordination and grading are designed in accordance with the Supply
Authority Design Guidelines and AS3000 requirements.
• A main switchboard shall be provided for the site. The main switchboard shall be minimum
form 3bih and have a minimum fault current of 36kA for 1 second. The main switchboard
shall be rated to the full capacity of the kiosk substation.
• A combine electrical/communications riser cupboard will be provided on each level with
the intent of staggering electrical and communications equipment on alternating levels.
Apartment meters shall be situated on every alternative level.
• Common house electrical distribution boards shall service no more than 5 levels above
and 5 levels below the location of the house electrical distribution board.
• The power infrastructure will be designed to allow future growth. The power cables will
utilize cable support systems throughout the whole installations via heavy duty PVC
conduits, cable ladders, cable trays and catenary wires.
• For all spare conduits a draw string wire will be noted as a requirement for future
installation and alterations.
• The design will allow for separation with all other services be highlighted in accordance
with the Australian Codes.
• Electrical Pits will be specified to be of high insulation properties, high mechanical
strengths, chemical resistance and zero water absorption. Drainage will also be
highlighted to comply with the NSW Service and Installations Rules and the Australian
Codes.
5.2 Electrical Reticulation
The electrical reticulation will be sized to cater for the following load densities:-
• Consumer mains will have 25% spare capacity.
• Residential unmetered risers shall be sized on the calculated diversified maximum
demand as per AS3000, the NSW Services and Installation Rules and the supply authority
requirements.
• Residential apartment electrical supplies will be design with a minimum submain size of
63A single phase terminating in a 18 pole single phase load-centre distribution board. 3-
phase supplies are not proposed for the residential apartments.
• House service electrical supplies will be design with a minimum submain size of 100A 3-
phase terminating in 72 pole 3-phase distribution boards located within the electrical
cupboards.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 14 of 26 Revision E – DA Issue
• Calculated maximum demand plus 25% spare for Mechanical Services.
• Calculated maximum demand plus 10 % spare for lifts.
• Cable trays and riser ducts will be sized to allow for 30% space capacity for future
additional cabling.
5.3 Main Switchboard and Distribution Boards
• The proposed Main switchboard is generally required to be positioned within 50 meters
from the substation. This requirement is nominated within the NSW Services &
Installation Rules and is essential to minimise the cable length and size and subsequent
cost.
• In addition to cost, and provided that the site is effectively focus on a central path of
connection (being the spine of the building where electrical Risers will be located), other
factors will also be calculated such as voltage drop (maximum of 5%) and total earth
fault loop impedance which will provide an overview of the correct size and length
adequate enough to excite the protective device to operate and isolate to safety.
• The proposed main switchroom shall be located in close proximity to the location of the
substation but also located centrally to the footprint of the electrical risers (where the
maximum load will be delivered).
• The main switchboard shall be located within an electrical cupboard in the basement. The
main electrical cupboard shall be 2hr fire rated.
• The house distribution Boards will be located in the main electrical cupboard and
strategically throughout the building to service all the house electrical loads including
general power and lighting.
• Energy Monitoring for all other services will also be required (subject to NCC report), such
as essential/safety services, power and lighting, central hot water supply and other
ancillary plants for compliance with Section J of the NCC.
• All electrical risers will be designed to have space to accommodate an estimated total
floor apartment supply authority meters equal to minimum 250A 3-phase, together with
associated fuses and circuit breakers in accordance with the latest revision of the NSW
Service and Installation Rules.
5.4 Metering
Tariff Metering arrangement will be provided as follows:-
• House services meter for carpark/Basement level and common areas located in main
switchboard.
• Residential meter panels will be provided on each floor of each apartment.
• Retail meter will be located within the retail space.
Private meters to monitor energy consumed by:-
• Separate metering for Strata and SAH common areas
• Mechanical switchboard.
• Common area power for each switchboard.
• Common area lighting for each switchboard.
• Lifts.
• Other significant loads as required by BCA Section J8.3.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 15 of 26 Revision E – DA Issue
5.5 Residential Apartment Power Outlets
General Purpose Outlets (GPO’s) will be provided typically as listed below:
Location Comments/Others
Bedrooms 1 x DGPO in each bedroom for general power
circuit adjacent bed (one side only)
1 x DGPO for NBN NTD (one bedroom only
within robe)
Bathroom/ Ensuite 1 x DGPO within vanity
1 x isolator for exhaust fan
Laundry 1 x DGPO for washing machine & dryer
1 x isolator for exhaust fan
Study (If applicable) 1 x DGPO
Kitchen 1 x GPO for dishwasher
2 x DGPO for general use
1 x single phase 32A isolator for cooktop &
oven
1 x isolator for rangehood
1 x GPO for hot water unit
1 x GPO for fridge
Load center location proposed over fridge
location
Lounge 1 x DGPO for TV/PayTV
2 x DGPO for general use
Dining 1 x DGPO for general use
Balcony 1 x single phase 20A isolator for A/C (Strata
units only) (weatherproof)
5.6 Retail Tenancies/ Offices Power Outlets
Location Comments/Others
Retail/ Childcare/ Respite 1 x GPO per 15m for cleaners
1 x DGPO for NBN NTD
Other power requirements TBC
5.7 Public Area Power Outlets
Location Comments/Others
Corridor 1 x GPO per 15m for cleaners
Electrical Risers 1 x DGPO (electrical)
Communications Risers 1 x DGPO (communications)
1 x DGPO (security)
Combined Electrical/Communication
Risers (Where applicable)
1 x DGPO (electrical)
1 x DGPO (communications)
1 x DGPO (security)
Foyer 1 x DGPO
Communications Room 6 x DGPO (NBN Provision, security, MDL, FIP
and Lifts)
1 x GPO for CCTV
1 x DGPO for Security
Main Switchroom 2 x DGPO General power
Carpark 1 x DGPO per 30m
Plant Rooms As required by other services
Minimum 2 x DGPO for general use
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 16 of 26 Revision E – DA Issue
6 Data Communications
6.1 Data Communications Services
The Electrical Contract Works related to the data communication and NBN requirements of this
project will comprise of the following:
• Design of data communication reticulation systems and associated accessories for
future fibre cable entry into the site and to each residential apartment via dedicated
communications route.
• Co-ordination of fibre lead-in conduit from new NBN pit appropriate to site
• Provision of adequate spatial clearance as per NBN’s requirements in the
communications cupboard and dedicated communications riser.
• Schematically design for NBN Co active equipment for all Network Termination Device
per commercial tenancy and Fibre Termination Devices per each floor.
• Full Design of horizontal pathways i.e. conduit from communications riser to each
individual commercial tenancy per floor for NBN Co approval.
6.2 Duct/Conduit Requirements – Lead In
The Design will allow for 2 x 100mm DIA communications conduit from the new NBN reticulation
outside site boundary into to the main communications room.
The lead in conduits will run into the main communications room, where future NBN Co fibre
cable and equipment will be installed by NBN Co.
Furthermore, the design will provide schematic for all designated communication conduits to be
installed from the main communications room to each residential apartments and retails
tenancies via Fibre Distribution Terminals (FDTs located in common electrical/ communications
cupboards) and apartment Network Termination Devices (NTDs located in bedroom robe).
6.3 Residential Apartment Data Outlets
Location Comments/Others
Bedrooms 1 x Data outlet in each bedroom adjacent
bed for general use
4 x Data outlets for NBN NTD (one bedroom
only within robe)
Bathroom/ Ensuite Nil
Laundry Nil
Study (If applicable) 1 x Data outlet for general use
Kitchen Nil
Lounge 2 x Data outlets for TV/PayTV
1 x Data outlet for phone
Dining Nil
Balcony Nil
6.4 Retail Tenancy/ Office Data Outlets
Location Comments/Others
Retail/ Childcare/ Respite 4 x Data outlets for NBN NTD
Other data outlet requirements TBC
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 17 of 26 Revision E – DA Issue
6.5 Public Area Data Outlets
Location Comments/Others
Main Communications Room 1 x Data outlet for security panel
1 x Data outlet for CCTV network video
recorder
Communications Cupboard 1 x Data outlet for MDL
1 x Data outlet for security panel
Lobby 1 x Data outlet for FIP
Lifts 1 x Data outlet per lift
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 18 of 26 Revision E – DA Issue
7 Lighting Services
7.1 Internal Lighting Generally
Generally all internal lighting will be designed in accordance to Australian Standard AS1680 and the
NCC2016 (consideration to people with disability lighting levels and glare will be emphasized and
implemented).
7.2 External Lighting Generally
Generally all external lighting will be designed in accordance to Australian Standard AS1158 and
AS4282. These standards focus on road lighting taking into account public safety for better visibility
during the night, theft, security and crimes within a given suburb and also preventing disturbances
via glare emitting from the luminaires to the neighboring sites.
7.3 Controls
The lighting design will ensure compliance to the National Construction Code in particular section
J6 for energy saving during occupied and unoccupied space.
By utilizing control methods within common areas such as motion sensors and zoning,
photoelectric sensors, Timers and others means of control to ensure minimization of the building
energy consumption and subsequent carbon footprint reduction.
Residential apartments will be solely controlled via manual light switches
7.4 Development Illumination Level
Generally lighting in the apartments will be designed as follows:
Area Lighting Level Other/Comments
Bedrooms 100 Lux LED Oyster (non-dimmable, 3000k)
Bathrooms/ Ensuites 100 Lux
LED recessed downlight (non-
dimmable, 3000k)
Laundry 80 Lux LED Oyster (non-dimmable, 3000k)
Study (If applicable) 100 Lux LED Oyster (non-dimmable, 3000k)
Kitchen 160 Lux LED Oyster (non-dimmable, 3000k)
Lounge 100 Lux LED Oyster (non-dimmable, 3000k)
Dining 100 Lux LED Oyster (non-dimmable, 3000k)
Balcony N/A Wall mounted LED light proposed
(Weatherproof, non-dimmable, 3000k)
7.5 Common Area Illumination Level
Area Lighting Level Other/Comments
Corridor 80lux LED recessed Downlight (non-
dimmable, 3000k)
General Basement
Carpark
40lux LED Surface batten,4000k non-
dimmable, Weatherproof)
Carpark Entry
- First (15m)
- Next (4m)
- Night-Time
800lux
160lux
160lux
Surface mounted LED Low Bay (non-
dimmable, 4000k, Weatherproof)
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 19 of 26 Revision E – DA Issue
- Aisles, Ramps
and circulations
40lux
Fire Stairs 80lux LED Surface batten (4000k non-
dimmable)- 24hr circuit
Plant
Room/Switchroom
Communications room
160lux LED Surface batten (4000k non-
dimmable, Weatherproof)
External Security 50lux LED Bollard Downlight (Asymmetric
Forward throw beam, Weatherproof)
External Lighting To AS1158 & AS4282 LED controlled via Time Clock and
Photo-electric Cell
Foyer 160Lux LED Downlights, 3000k, flood beam,
non-dimmable
7.6 Exit & Emergency Lighting
A complete emergency lighting system incorporating self-contained emergency luminaires and
exit signs will be designed in accordance with the requirements of AS 2293.
All emergency luminaires and illuminated exit signs will be designed and checked for the
following:-
- Compliance with AS 2293.
- Be classified by an approved Authority in accordance with AS 2293, with the classification
being clearly marked on the luminaire label.
- Be numerically identified with a permanent approved engraved label with numbers
corresponding with the log book identification and as-installed drawings.
- Be circuited in accordance with the intent of AS 2293, enabling testing to be performed
without interruption to general lighting.
7.7 Emergency Luminaires
Emergency luminaires and exit signs shall comply with AS 2293 and be National Construction
Code (NCC). Each emergency lighting unit will be of the self-contained single point type complete
with LED light source, batteries, dual rate battery charger, inverter, test switch and light emitting
diode to indicate that the charger is operating.
Where emergency lighting units are contained within normal luminaires, the batteries and
associated control equipment will be housed on a separate metal enclosure attached to the
luminaire and located so that the batteries are not affected by the high temperatures generated
within the luminaire during normal operation.
Emergency exit luminaires will be of the ‘Running Man’ pictorial type complete with arrows as
required and classified by an approved authority in accordance with AS/NZS2293.1, with the
classification being clearly identified on the luminaire label.
All distribution boards will be labelled in accordance with AS2293 to indicate circuits which supply
emergency luminaires.
Emergency light test switches will be located within house distribution boards.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 20 of 26 Revision E – DA Issue
8 Security Access Control, CCTV and
Intercom Systems
8.1 Security Access Control System
The system will be a standalone system of the fully programmable type. The central hub will be
housed in the main communications room in the basement or where shown on the electrical
drawings. Additional control equipment will be located throughout the development within
communications cupboards on floors where required, in tamperproof enclosures. The system will
utilise distributed intelligence so it can continue to function locally in the event of communication
errors or loss of the central control hub.
All building entry points will be provided with a card reader style door access point. Each of the
lobbies will operate independently of each other on programmed time sequencing as directed by
the building operator.
Security card reader and reed switches will not be installed at apartment doors.
The system will utilize proximity card style access cards or tokens with card readers. Proximity
cards will be key fob type.
Secure doors will incorporate mortise lock, magnetic door hold devices or electric strikes suitable
to match the door style and hardware. Secure doors will be electrically locked and operable by
either presenting a valid access card or access being granted through the entry intercom system.
One the secure side of doors, a pushbutton to unlock doors will be provided. External entrances
will additionally utilize reed switches for monitoring of unauthorised entry or forced entry at
external doors to the building and to areas requiring an increased level of security e.g. plant
rooms, main switch room and building communications room.
The car park roller shutter/door system, will contain an interface to facilitate access to the car
park for residents and other authorised via dual technology proximity and radio remote key fobs.
A pedestal will be located at entrance and exits to the car park to facilitate the mounting of
intercom entry/exit stations.
The pedestal if required will be mounted to enable use from a standard sedan car window and
no inhibit traffic flow.
Additionally, radio frequency remote control access buttons, for issue to building occupants, will
be utilised for resident vehicular access to the car park. Each proximity/ radio remote control
will be individually identifiable by the security system and have events recorded in the security
system log. Provide a carpark roller shutter open/close pushbutton in the building manager’s
office or other nominated personnel.
An induction loop will be installed within the car park to enable the car park door to automatically
open upon detection if exiting vehicles.
The system will also be interfaced to the lift control system to limit access various floors as
programmed. The lift control interface will operate to control access for residents to their floor
level only and other common areas. Visitor access would also be controlled such that the lift
would only allow visitor access to the level associated with their entry intercom call.
The access control system will be provided with facilities to allow for remote monitoring from a
security service.
8.2 Access Control
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 21 of 26 Revision E – DA Issue
Access Control are to be used to control access and flow of traffic in the following areas:
• Car park entry and exit for the combined development.
• Main entry lobbies at Ground Level.
• All lifts: lift-by-lift, floor-by-floor control (after hours and as required by tenants).
Card readers located off car park entries, lift lobbies, front entry doors and secure rooms will
control access into the areas nominated. Exit from the area will be via free egress with PIR
“request-to-exit” sensors to temporarily deactivate door open alarm from within the secure area
and credential readers on the car park entries and fire stair doors. Egress doors will have single-
handed action to exit.
8.3 CCTV System
A closed circuit television (CCTV) system will be provided to monitor the major entry and exit
points of the building, and basement and foyer spaces, including fire stair egress points.
Internal cameras will monitor the building main entrance and car park entrance and main
entrance foyer.
The system will be of the digital, IP based and colour type. Monitoring stations for the CCTV
system shall be set up for remote monitoring from an external security service.
The system will operate on a 24-hour basis and be capable of storing up to 30 days of storage
footage on site utilising a networked hard drive storage device. Storage equipment shall be
located in the main communications rooms. The system will be provided with facilities to record
information and store on site, and also store off site, if required
8.4 Entry Intercom System
A colour video intercom system will be provided to allow communication between visitors and
residents for visitor access. The system shall be of the fully digital type and interfaced with the
building access control system to enable opening of the front entrance doors, activation of
appropriate lift access and operation of car park roller shutters.
Entry panels shall be provided external to the front entrance of the building lobbies, and the car
park entrance for visitor access to parking spaces. Each entry panel shall be of the recessed and
vandal proof type and contain a keypad for addressing each tenancy number, colour camera to
allow viewing of caller to building occupants, and full duplex audio facilities.
Each residential apartment shall be provided with an intercom station complete with colour
screen to view entry door call, full duplex hands free type audio facilities, and separate buttons
for opening each separate entrance point. Intercom stations shall be of the recessed and flush
type.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 22 of 26 Revision E – DA Issue
9 MATV/ PayTV
A new MATV/ PayTV system will be installed within the development. The MATV system will
utilise a 5-wire solution with head-end located at the main communications room. RG11 and
RG6 coaxial cable backbone is proposed to the residential apartments. Splitters shall be located
within communications cupboards and residential apartments. A new MATV Antenna will be
installed on each building roof.
A new PayTV satellite dish will be installed on each building roof to enable Foxtel. The entire
PayTV system will be Foxtel compliant and installed by a suitably qualified contactor with Foxtel
accreditation.
MATV/ PayTV outlets will be installed within lounge rooms only.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 23 of 26 Revision E – DA Issue
10 Dry Fire Services
10.1 Electric Fire Generally
The fire detection system will be designed to comply with the NCC and the fire detection
standards AS1670.1 and AS1670.4.
The proposed design will have a central Fire Indicator Panel (FIP) with integral Emergency
Warning & Intercom System (EWIS) at the main entrance.
Mimic Panel may also be provided at a secondary entrance to the building or at the building
manager or security office.
10.2 Automatic Fire Alarm and EWIS
The following table provides the design criteria and performance requirements for the dry fire
services systems within the building:
Item Area Fire Detection SSEP
1 Main Switchroom Smoke Detector to
AS1670.1:2015
Horn Speaker
2 Building Common Areas Smoke Detector to
AS1670.1:2015
Recessed ceiling
speaker
3 Residential Apartments AS3786 smoke
alarms
Recessed speakers
in bedrooms
4 Electrical Risers Smoke Detector to
AS1670.1:2015
-
6 Mechanical Return Air Inlet Smoke Detector to
AS1670.1:2015
-
7 Basements Thermal Detector to
AS1670.1:2015
“smoke zone control
systems”
Horn Speaker
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 24 of 26 Revision E – DA Issue
11 Spatial Requirements
Project: 27 Durham St, Mount Druitt
Project Number: 20180080
Engineer: Alexander Rodriguez
Revision: E
11.1 Electrical Services:
Ite
m
Description Area Configuration Comments
1 1 x pad mount
transformer
18m2 2.75m x 5.5m
(Easement)
Fire blast clearance within 3m from
building and mechanical ventilation
clearance to be 6m radius from the top of
the substation housing.
2 Main Switchboard
Cupboard
15m2 5.0m x 3.0m x
3.0m high
Fire rated Switchroom (2hr) as near as
possible to sub-station for economy. Two
exit doors required.
3 Combined
Electrical/
Communications
Cupboard (Where
applicable)
0.8m2 1.6m x 0.5m Typical cupboard on all residential floors of
the building, with a 0.6m clearance
required in front of cupboard calculated
from the cupboard door in the open
position. Cupboard to be smoke sealed
with non-combustible metallic lining on
the inside of the cupboard doors
4 Electrical
Cupboard
0.8m2 1.6m x 0.5m Typical cupboard on all residential floors of
the building, with a 0.6m clearance
required in front of cupboard calculated
from the cupboard door in the open
position. Cupboard to be smoke sealed
with non-combustible metallic lining on
the inside of the cupboard doors
11.2 Communication Services:
Ite
m
Description Area Configuration Comments
1 Main
Communications
Room
12m2 4.0m x 3.0m
2 Communications
Cupboard
0.45m2 0.9m x 0.5m
11.3 Dry Fire Services:
Ite
m
Description Area Configuration Comments
1 Fire Indicator
Panel Cupboard
W D
0.7m x 0.5m
FIP located within cupboard at main
building entry at ground level recessed
with 500mm clearance on either side of
the panel and a 1000mm in front of the
panel
2 Fire Indicator
Mimic Panel (As
required)
0.15m x 0.1m Locate within alternate main building
entry of at ground level.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 25 of 26 Revision E – DA Issue
Note: All riser sizes shown above are provided as minimum requirement to satisfy future works.
These are preliminary sizes to fit expected services. Final riser sizes to be confirmed once service
layouts are completed. All dimensions are provided for internal configuration.
Electrical Services Concept Design Report 27 Durham St, Mount Druitt 4th December 2018
Insync Services Page 26 of 26 Revision E – DA Issue
12 Appendix A – Concept Drawings &
Schematics
RL 38.220
DA31001
DA31001
DA31002
DA31002
DA31011
DA31011
DA31012
DA31012
RL 38.220
96 CAR SPACES
WASTEROOM
CAR PARKEXHAUST
FAN ROOM
COLDWATERPUMPROOMMAIN
COMMS.ROOM
WASTE ROOM EX. TO ROOF
FIREHYDRANT/
SPRINKLERSTORAGE
TANKS
5 x 1100L BINS16 x 240L RECYCLING BINS
9 x1100L BINS28 x 240L RECYCLING BINS
FIREHYDRANT
PUMPROOM
6120
DEEP SOIL ZONE ABOVE
AIR LOCK
ELEC MAINSWITCHROOM
MOTORCYCLE PARKING x7
GREASEARRESTOR
ROOM
5600
180 m²
OSD TANK
1000
5800
1000
5800 FIREHYDRANT/
SPRINKLERSTORAGE
TANKS
1655 BICYCLE RACKS
x11
MOTORCYCLE PARKING x4
1540
3720
SAH
68 69 70
76 75 74 73 72 71
5053
3
2
1
10 11
41 40
1912 13 14 15 16 17 25
6463
78
54 55 56 57 58
31
81 80 7984 83 8287 86 8590 89 8893 92 91
21
27
28
29
65 66 6762
45 39
32
6 7 8
52
33
34
94
5
44 43
9
42 38 37 36 35
95
61
22 23 24
96
46
47
48
4
51
26
49
59
18
77
30
20
60
SAH SAH SAH SAH SAH SAH SAH SAH
SAHSAHSAHSAHSAHSAHSAHSAHSAHSAH
SAH
SAH
SAH
SAH
SAH
SAH
SAHSAH
SAH SAH SAH
SAH
SAH
SAH
SAH
SAH
DEEP SOIL ZONE ABOVE
6100
1000VI
SVI
SVI
SFH
1000
4820
1000
UP
UP
UP
DEEP SOIL ZONE ABOVE
DEEP SOIL ZONE ABOVE
DA11023
DA1102
4
DA1102 5 BIN
HOIS
T
EXHAUST
CARPARK EXHAUSTRISER TO ROOF
WASTE ROOMEX. TO ROOF
PUMP ROOMEX. TO ROOF
PUMP ROOMSUPPLY
FH
1000
CARPARK SUPPLYAIR TO ROOF
Group GSA Pty Ltd ABN 76 002 113 779Level 7, 80 William St East Sydney NSWAustralia 2011 www.groupgsa.com
T +612 9361 4144 F +612 9332 3458
architecture interior design urban design landscapenom architect M. Sheldon 3990
Project No
Approved
Verified
Plotted and checked by
Drawing Created (by)
Drawing Created (date)
Scale
Issue
This drawing is the copyright of Group GSA Pty Ltd and may not be altered, reproduced or transmitted in any form or by any means in part or in whole without the written permission of Group GSA Pty Ltd. All levels and dimensions are to be checked and verified on site prior to the commencement of any work, making of shop drawings or fabrication of components. Do not scale drawings. Use figured Dimensions.
Drawing Title
Project Title
Client
PO Box 167, BroadwayNSW 2007
BLACKETT MAGUIRE + GOLDSMITHBCA/DDA Consultant
Suite 29, Level 8, 820 Adelaide StreetBrisbane QLD 4000
ELEPHANTS FOOTWaste Consultant
Level 11, 345 George StreetSydney NSW 2000
NORTHROPStructural Engineer
OLSSON FIREFire Engineer
Drawing No
AmendmentsIssue Description Date
DA SUBMISSION
Suite 6.02, Level 6, 89 York StreetSydney NSW 2000
INSYNC SERVICESServices Engineers
Suite 102, 506 Miller StreetCammeray NSW 2062
PTCTraffic Engineer
North Point
1 : 200
3/12
/201
8 5:
34:3
8 PMJ
BASEMENT 1 GA PLAN
ANGLICARE -MT DRUITT
ANGLICARE
DA2000180350
12/09/18
LL
MB
LMC
LR
1 : 2001 BASEMENT LEVEL PLAN
PARKINGTOTAL: 54 STRATA SPACES (INC 8 ACCESSIBLE)
35 SAHF SPACES (INC 3 ACCESSIBLE SPACES)13 VISITOR PARKING (INC 10 ON GRADE)4 ANGLICARE OFFICE SPACES1 RETAIL SPACE (ON GRADE)11 MOTORCYCLE SPACES11 BICYCLE SPACES
A DRAFT 20/07/2018B DRAFT 03/08/2018C DRAFT 14/08/2018D DRAFT 03/09/2018E ISSUE FOR PRE-DA 10/09/2018F ISSUE FOR PRE-DA 12/09/2018G ISSUE FOR INFORMATION 19/10/2018H ISSUE FOR VALUE MANAGEMENT 26/10/2018I ISSUE FOR INFORMATION 06/11/2018J ISSUE FOR INFORMATION 08/11/2018
ELECTRICAL MAIN SWITCH ROOM:- MIN 5000 x 3000 CLEAR INTERNAL- 2HR FIRE RATED- 2 POINTS OF EXIT. PREFERRABLE ONEWITH DOUBLE LEAF DOORS
MAINCOMMUNICATIONSROOM:- 4000 x 3000
Electrical ServicesEngineer: ARDate: 04/12/2018
Suite 6.02,Level 6,89 York StreetSydney NSW 2000
Tel: (02) 9262 3400Fax: (02) 9262 3422
TOP OF GUTTER RL55.74
TOP OF GUTTER RL55.50
USG
46.2
8
USG 46.08
40.66
41.16
41.64
43.24
16.7
719
°59'
40"
16.7
719
°59'
40"
85.16102°42'50"
4.78
192°
38'
15.08102°42'50"
41
40.4
2
40.8
6
42.9
3
46.0
4
41.4
7
41.4
9
40.4
4
40.4
1
40.5
040
.55
43.6
0
43.08
40.5
2
40.5
7
40.7040.67
40.64 40.8840.91
41.05
40.98 41.07
41.14 41.36
41.30 41.56
41.64 41.68
41.60 41.89 41.9941.96
42.10
42.15
41.73
40.55
40.5
8
40.5
440
.57
40.6
140
.83
40.7
640
.89
40.9
6
41.6
1
41.5
4
42.2
9
42.3
4
42.5
2
42.4
6
41.9342.21
42.15 42.42
42.48
41.0
0
41.9241.9
5
41.7
8
41.6741.6241.7
0
41.5
6
41.4
5
41.4
0
41.4
7
41.2
9
41.0
2
40.9
0
40.8
3
40.9
2
40.7
0
40.4
8
40.3
7
40.2
0
40.1
9
40.3
5
40.3
840.4
0
40.4
0
40.4
1
40.4
3
42.3
8
42.0
0
41.2
541
.35
40.76
40.66
40.5140.57
40.4440.29
40.31
40.44
42.0
2
42.2
1
41.8841.8841.6541.5541.4141.3441.1540.8840.7840.5640.3440.1440.14
40.1
8
40.23
40.25
40.25
40.27
40.2
9
42.2
5
41.8
6
41.2
0
40.6
340
.43
40.27
40.3
0
42.06
41.9
0
41.6
6
41.5
8
41.4
4
41.3
7
41.3
6
41.3
7
41.3
4
41.3
1
41.1
7
41.0
0
40.9
0
40.8
0
40.5
8
40.3
8
40.2
5
40.2
2
40.2
4
40.2
640.2
8
40.2
9
40.3
1
40.3
3
42.2
7
41.8
8
41.5
9
41.2
4
40.6
5
40.4
6
40.3
4
40.3
340
.33
42.1
0
40.6
5
40.7
7
40.9
5
41.0
6
41.2
0
41.5
0
41.7
6
41.8
1
41.2
8
41.7
1
42.7
3
43.4
6
43.0
2
39.9
4
IL 3
8.19
IL 38.38
� 0.525 � 0.450
� 0
.400
� 0
.525
18 m²
MANAGER'SROOM
DA3003 1
DA30041
DA3002
1
DA3001
1
DA3005 1
DA30042 DA3005 2 DA30032
DA31001
DA31001
DA31002
DA31002
DA31011
DA31011
DA31012
DA31012
BLOCK B BLOCK CBLOCK A
PEDESTRIAN PATH
VISITOR PARKING
31 m²
NEIGHBOURHOOD
RL 41.500
RL 41.500RL 41.500
RL 41.500
THREE STOREY BRICKRESIDENTIAL FLAT BUILDING THREE STOREY BRICK
RESIDENTIAL FLAT BUILDING
NO.19 BRICK COTTAGE
M O
U N
T
D R
U I T
T
R O
A D
D U R H A M S T R E E T
38 m²
STUDIOSAH TYPE
2B05
35 m²
STUDIOSAH TYPE
1B04
36 m²
STUDIOSAH TYPE
1B03
51 m²
1 BED SAHTYPE 2
B06
51 m²
1 BED SAHTYPE 1B
B08
53 m²
1 BED SAHADAPTABLE
TYPE 1B07
55 m²
COMMUNALSPACE 63 m²
1 BEDSTRATATYPE 3
C05
72 m²
2 BEDSTRATATYPE 1
C02
71 m²
2 BEDSTRATATYPE 1
C04
40 m²
STUDIOSTRATA
ADAPTABLETYPE 1
C03
27 m²
BAL / POSB01
14 m²
BAL / POSB02
15 m²
BAL / POSB04
14 m²
BAL / POSB05
12 m²
BAL / POSB07
23 m²
BAL / POSB08
19 m²
BAL / POSB06
GASMETERROOM
46 m²
BUILDINGCOMMON
AREA
16 m²
BAL / POSC02
18 m²
BAL / POSC03
32 m²
BAL / POSC04
1.8M BOUNDARY FENCE
14120
14120H
RL 41.500
ENTRY TO CARPARK
23 m²
BAL / POSC01
COMMUNALOPENSPACE
OUTDOOR
COMMUNALOPENSPACE
OUTDOOR
RL 41.500
RL 41.500
POWERPOLE
RL 41.500
RL 41.920
LOADINGAREA
3000
5300
2750
DEEP SOIL ZONE
DEEP SOIL ZONE
TOP OF KERB 41.720BOTTOM OF KERB 41.58
RL 41.589
BIN
HOIS
T
RL 41.631
4.5m CLEAR HEADHEIGHT
DEEP SOIL ZONE
1:81:4
1:20
1.2M METAL FENCING
1.2M METAL FENCING
MAILBOXES
SUBSTATION
30 m²
BUILDINGCOMMON
AREARL 41.500
105 m²
ANGLICAREHUB
51 m²
1 BED SAHTYPE 1
C01
73 m²
2 BEDSTRATATYPE 6
B01
36 m²
STUDIOSAH TYPE
1B02
RL 41.500
NH
14 m²
BAL / POSB03
RL 41.500
1 2 3 4 5 6 7 8 9 10 11DEEP SOIL ZONE
1000FH
1000
1000
UP
UP
UP
1000
COMMUNALOPENSPACE
OUTDOOR
1000
UP
VIS VIS VIS VIS VIS VIS VIS VIS VIS VISRET
50 m²
1 BED SAHTYPE 1
A01
37 m²
BUILDINGCOMMON
AREARL 41.500
26 m²
BAL / POSA02
23 m²
BAL / POSA01
RAM
P UP
1:1
4
70 m²
2 BEDSTRATATYPE 1
A02
28 m²
BAL / POSC05
DA11023
DA1102
2
DA1102
4
DA1102 5
5 x1100L BINS15 x 240L RECYCLING BINS
RL 41.631
RAMP UP 1:35
1:40
1:100
1:14 1:14RL 41.050RL 40.600
MAILB
OXES
MAILBOXES
EXHAUST
ELEC
COM
CARPARK EXHAUST
KITCHEN EXHAUST
WASTEROOM EXHAUST
WASTE ROOMEXHAUST
PUMP ROOMEX. TO ROOF
PUMP ROOMSUPPLY
WASTEROOM EXHAUST
A/C PLANT
A/C PLANTA/C PLANT
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
9m S
IDE
SETB
ACK
(5-8
stor
eys)
- AD
G (H
ABIT
ABLE
)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m
SID
E SE
TBAC
K (5
-8 st
orey
s) -
ADG
(NON
-HAB
ITAB
LE)
6m REAR SETBACK - DCP
6m S
IDE
SETB
ACK
- DCP
9m FRONT SETBACK (3 or more storeys) - DCP
7.5m FRONT SETBACK (1-2 storeys) - DCP
9m F
RONT
SET
BACK
(3 o
r mor
e sto
reys
) - D
CP
7.5m
FRO
NT S
ETBA
CK (1
-2 st
orey
s) -
DCP
6m REAR SETBACK - DCP
FIRE ISOLATED PASSAGE
FIRE SPRINKLERBOOSTER
DOUBLE PILLARHYDRANT
ELE/
COM
HYD
MIMIC P.
ELE/COM
HYD
MIMIC P.
FIP
RL 42.105 RL 42.210
RL 42.332RL 42.227
RL 41.350
RL 41.440
RL 42.227 RL 42.332
HYD
10001000
FH
1000
FH
FH
FH
F.EX
F.EX
F.EX
CARPARK SUPPLYAIR TO ROOF
Group GSA Pty Ltd ABN 76 002 113 779Level 7, 80 William St East Sydney NSWAustralia 2011 www.groupgsa.com
T +612 9361 4144 F +612 9332 3458
architecture interior design urban design landscapenom architect M. Sheldon 3990
Project No
Approved
Verified
Plotted and checked by
Drawing Created (by)
Drawing Created (date)
Scale
Issue
This drawing is the copyright of Group GSA Pty Ltd and may not be altered, reproduced or transmitted in any form or by any means in part or in whole without the written permission of Group GSA Pty Ltd. All levels and dimensions are to be checked and verified on site prior to the commencement of any work, making of shop drawings or fabrication of components. Do not scale drawings. Use figured Dimensions.
Drawing Title
Project Title
Client
PO Box 167, BroadwayNSW 2007
BLACKETT MAGUIRE + GOLDSMITHBCA/DDA Consultant
Suite 29, Level 8, 820 Adelaide StreetBrisbane QLD 4000
ELEPHANTS FOOTWaste Consultant
Level 11, 345 George StreetSydney NSW 2000
NORTHROPStructural Engineer
OLSSON FIREFire Engineer
Drawing No
AmendmentsIssue Description Date
DA SUBMISSION
Suite 6.02, Level 6, 89 York StreetSydney NSW 2000
INSYNC SERVICESServices Engineers
Suite 102, 506 Miller StreetCammeray NSW 2062
PTCTraffic Engineer
North Point
1 : 200
3/12
/201
8 5:
35:0
3 PMJ
GROUND FLOOR GAPLAN
ANGLICARE -MT DRUITT
ANGLICARE
DA2001180350
10/09/18
LL
MB
LMC
LR
1 : 2001 GROUND LEVEL PLAN
A DRAFT 13/07/2018B DRAFT 20/07/2018C DRAFT 03/08/2018D DRAFT 14/08/2018E DRAFT 03/09/2018F ISSUE FOR PRE-DA 10/09/2018G ISSUE FOR INFORMATION 19/10/2018H ISSUE FOR VALUE MANAGEMENT 26/10/2018I ISSUE FOR INFORMATION 06/11/2018J ISSUE FOR INFORMATION 08/11/2018Electrical Services
Engineer: ARDate: 04/12/2018
Suite 6.02,Level 6,89 York StreetSydney NSW 2000
Tel: (02) 9262 3400Fax: (02) 9262 3422
Calculated ElectricalMaximum Demand:920A (635kVA)
Likely Supply: KioskSubstation
Note: Supply to beconfirmed byEndeavour Energy
MIMIC PANEL(WALL MOUNTED) MIMIC PANEL
(WALL MOUNTED)
FIP CUPBOARD:- MIN 700 x 500mm
KIOSK SUBSTATION:- EASEMENT 2750 x 5300- 3000 BLAST RADIUS AROUND SUBSTATION- 6000 AWAY FROM BUILDING OPENINGS- 10000 AWAY FROM FIRE BOOSTER
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
ELECTRICAL CUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ON INSIDEOF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDINGCOMMUNICATIONS CUPBOARD:
- MIN 900 x 500mm- PREFERRABLE FOR CUPBOARDTO LINE VERTICALLY UP THEBUILDING
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
DA3003 1
DA30041
DA3002
1
DA3001
1
DA3005 1
DA30042 DA3005 2 DA30032
DA31001
DA31001
DA31002
DA31002
DA31011
DA31011
DA31012
DA31012
54 m²
1 BED SAHTYPE 5
B08
35 m²
STUDIOSAH TYPE
1B12
35 m²
STUDIOSAH TYPE
1B13
39 m²
STUDIOSAH TYPE
2B15
35 m²
STUDIOSAH TYPE
1B14
51 m²
1 BED SAHTYPE 2
B16
BLOCK B BLOCK CBLOCK A
53 m²
1 BED SAHADAPTABLE
TYPE 1B18
51 m²
1 BED SAHTYPE 1B
B17
13 m²
BAL / POSA05
10 m²
BAL / POSA03
10 m²
BAL / POSA07
6m REAR SETBACK - DCP
6m S
IDE
SETB
ACK
- DCP
9m FRONT SETBACK (3 or more storeys) - DCP
7.5m FRONT SETBACK (1-2 storeys) - DCP
9m F
RONT
SET
BACK
(3 o
r mor
e sto
reys
) - D
CP
7.5m
FRO
NT S
ETBA
CK (1
-2 st
orey
s) -
DCP
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
9m S
IDE
SETB
ACK
(5-8 s
tore
ys) -
ADG
(HAB
ITAB
LE)
35 m²
STUDIOSAH TYPE
1B11
35 m²
STUDIOSAH TYPE
1B10
35 m²
STUDIOSAH TYPE
1B09
79 m²
2 BEDSTRATATYPE 2
A05
71 m²
2 BEDSTRATATYPE 3
A07
50 m²
1 BED SAHTYPE 1
A04
78 m²
2 BEDSTRATATYPE 4
A03
51 m²
1 BED SAHTYPE 4
A06
CORRIDOR
CORRIDOR
CORRIDOR
4 m²
BAL / POSB15
4 m²
BAL / POSB14
1800
72 m²
2 BEDSTRATATYPE 1B
C08
71 m²
2 BEDSTRATATYPE 1
C10
40 m²
STUDIOSTRATA
ADAPTABLETYPE 1
C09
70 m²
2 BEDSTRATATYPE 1C
C07
53 m²
1 BED SAHTYPE 6
C06
69 m²
2 BEDSTRATATYPE 5
C05
4 m²
BAL / POSB13
4 m²
BAL / POSB12
4 m²
BAL / POSB11
4 m²
BAL / POSB10
4 m²
BAL / POSB09
8 m²
BAL / POSB17
8 m²
BAL / POSB18
12 m²
BAL / POSB16
14 m²
BAL / POSB08
12000
12600
9000
6100
6240
H
NH
NH
HIGH WINDOW
HIGH WINDOW
HIGH WINDOW
HIGH WINDOW NH
NHH
H NH
HNH
HNH
HIGH
WIN
DOW
HNH
11 m²
BAL / POSC05
14 m²
BAL / POSC06
11 m²
BAL / POSC09
11 m²
BAL / POSC08
11 m²
BAL / POSC07
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m
SID
E SE
TBAC
K (5
-8 st
orey
s) -
ADG
(NON
-HAB
ITAB
LE)
6m REAR SETBACK - DCP
14 m²
BAL / POSA06
ELE/
COM
HYD
ELE/COM
ELEC
COM
HYD
1SK0002
2SK0001
HIGH
WIN
DOW
13310
12000
3000
1000FH
1000
1000
1000 UP
UP
UP1000 1000
1000FH
11 m²
BAL / POSC10
13 m²
BAL / POSA04
DA11023
DA1102
2
DA1102
4
DA1102 5
F.EX
HIGH
WIN
DOW
HIGH
WIN
DOW
4.5m CLEAR HEADHEIGHT
VOID
EXHAUST
CARPARK EXHAUSTKITCHEN EXHAUST
WASTEROOM EXHAUST
WASTE ROOMEXHAUST
PUMP ROOMEX. TO ROOF
WASTEROOM EXHAUST
HYD
FH
FH
CARPARK SUPPLYAIR TO ROOF
Group GSA Pty Ltd ABN 76 002 113 779Level 7, 80 William St East Sydney NSWAustralia 2011 www.groupgsa.com
T +612 9361 4144 F +612 9332 3458
architecture interior design urban design landscapenom architect M. Sheldon 3990
Project No
Approved
Verified
Plotted and checked by
Drawing Created (by)
Drawing Created (date)
Scale
Issue
This drawing is the copyright of Group GSA Pty Ltd and may not be altered, reproduced or transmitted in any form or by any means in part or in whole without the written permission of Group GSA Pty Ltd. All levels and dimensions are to be checked and verified on site prior to the commencement of any work, making of shop drawings or fabrication of components. Do not scale drawings. Use figured Dimensions.
Drawing Title
Project Title
Client
PO Box 167, BroadwayNSW 2007
BLACKETT MAGUIRE + GOLDSMITHBCA/DDA Consultant
Suite 29, Level 8, 820 Adelaide StreetBrisbane QLD 4000
ELEPHANTS FOOTWaste Consultant
Level 11, 345 George StreetSydney NSW 2000
NORTHROPStructural Engineer
OLSSON FIREFire Engineer
Drawing No
AmendmentsIssue Description Date
DA SUBMISSION
Suite 6.02, Level 6, 89 York StreetSydney NSW 2000
INSYNC SERVICESServices Engineers
Suite 102, 506 Miller StreetCammeray NSW 2062
PTCTraffic Engineer
North Point
1 : 200
3/12
/201
8 5:
35:1
6 PMI
LEVEL 1 GA PLAN
ANGLICARE -MT DRUITT
ANGLICARE
DA2002180350
10/09/18
LL
MB
LMC
LR
1 : 2001 LEVEL 1 PLAN
A DRAFT 13/07/2018B DRAFT 20/07/2018C DRAFT 03/08/2018D DRAFT 14/08/2018E DRAFT 03/09/2018F ISSUE FOR PRE-DA 10/09/2018G ISSUE FOR INFORMATION 19/10/2018H ISSUE FOR VALUE MANAGEMENT 26/10/2018I ISSUE FOR INFORMATION 06/11/2018
Electrical ServicesEngineer: ARDate: 04/12/2018
Suite 6.02,Level 6,89 York StreetSydney NSW 2000
Tel: (02) 9262 3400Fax: (02) 9262 3422
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
ELECTRICAL CUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ON INSIDEOF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDINGCOMMUNICATIONS CUPBOARD:
- MIN 900 x 500mm- PREFERRABLE FOR CUPBOARDTO LINE VERTICALLY UP THEBUILDING
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
DA3003 1
DA30041
DA3002
1
DA3001
1
DA3005 1
DA30042 DA3005 2 DA30032
DA31001
DA31001
DA31002
DA31002
DA31011
DA31011
DA31012
DA31012
CORRIDOR
51 m²
1 BED SAHTYPE 2
B27
53 m²
1 BED SAHADAPTABLE
TYPE 1B28
51 m²
1 BED SAHTYPE 1B
B29
54 m²
1 BED SAHTYPE 5
B19
35 m²
STUDIOSAH TYPE
1B24
35 m²
STUDIOSAH TYPE
1B20
35 m²
STUDIOSAH TYPE
1B22
35 m²
STUDIOSAH TYPE
1B25
38 m²
STUDIOSAH TYPE
2B26
35 m²
STUDIOSAH TYPE
1B21
4 m²
BAL / POSB26
4 m²
BAL / POSB25
4 m²
BAL / POSB24
4 m²
BAL / POSB23
4 m²
BAL / POSB22
4 m²
BAL / POSB21
4 m²
BAL / POSB20
8 m²
BAL / POSB19
8 m²
BAL / POSB29
8 m²
BAL / POSB28
9 m²
BAL / POSB27
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)6m REAR SETBACK - DCP
6m S
IDE
SETB
ACK
- DCP
9m FRONT SETBACK (3 or more storeys) - DCP
7.5m FRONT SETBACK (1-2 storeys) - DCP
9m F
RONT
SET
BACK
(3 o
r mor
e sto
reys
) - D
CP
7.5m
FRO
NT S
ETBA
CK (1
-2 st
orey
s) -
DCP
6m REAR SETBACK - DCP
51 m²
1 BED SAHTYPE 4
A12
13 m²
BAL / POSA11
10 m²
BAL / POSA08
10 m²
BAL / POSA13
79 m²
2 BEDSTRATATYPE 2
A11
71 m²
2 BEDSTRATATYPE 3
A13
51 m²
1 BED SAHTYPE 1
A10
50 m²
1 BED SAHTYPE 1
A09
78 m²
2 BEDSTRATATYPE 4
A08
CORRIDOR
8 m²
BAL / POSA10
8 m²
BAL / POSA09
8 m²
BAL / POSA12
CORRIDOR
WASTE ROOMEXHAUST
72 m²
2 BEDSTRATATYPE 1B
C14
71 m²
2 BEDSTRATATYPE 1
C16
40 m²
STUDIOSTRATA
ADAPTABLEC15
70 m²
2 BEDSTRATATYPE 1C
C13
53 m²
1 BED SAHTYPE 6
C1269 m²
2 BEDSTRATATYPE 5
C11
8 m²
BAL / POSC12
11 m²
BAL / POSC14
6 m²
BAL / POSC15
11 m²
BAL / POSC13
ELE/
COM
HYD
ELE/COM
ELEC
COM
HYD
1000FH
1000
1000
UP
UP
UP
35 m²
STUDIOSAH TYPE
1B23
11 m²
BAL / POSC16
1000FH
1000FH
11 m²
BAL / POSC11
DA11023
DA1102
2
DA1102
4
DA1102 5
F.EX
14150
16930
12015
12000
12000
HIGH
WIN
DOW
HIGH
WIN
DOW
HIGH
WIN
DOW 12600
12600
HNH 13310
EXHAUST
CARPARK EXHAUSTKITCHEN EXHAUST
WASTEROOM EXHAUST
PUMP ROOMEX. TO ROOF
WASTEROOM EXHAUST
HYD
FH
1000
CARPARK SUPPLYAIR TO ROOF
1 BED SAHTYPE 1
A15
1 BED SAHTYPE 1
A16
BAL / POSA15
BAL / POSA16
1 BED SAHTYPE 1
A27
1 BED SAHTYPE 1
A28
BAL / POSA27
BAL / POSA28
FS
1 BED SAHTYPE 1
A22BAL / POS
A22
BAL / POSA21
1 BED SAHTYPE 1
A21
54 m²
1 BED SAHTYPE 5
17 m²BAL / POS
40 m²
STUDIOSTRATA
ADAPTABLE11 m²
BAL / POS
Group GSA Pty Ltd ABN 76 002 113 779Level 7, 80 William St East Sydney NSWAustralia 2011 www.groupgsa.com
T +612 9361 4144 F +612 9332 3458
architecture interior design urban design landscapenom architect M. Sheldon 3990
Project No
Approved
Verified
Plotted and checked by
Drawing Created (by)
Drawing Created (date)
Scale
Issue
This drawing is the copyright of Group GSA Pty Ltd and may not be altered, reproduced or transmitted in any form or by any means in part or in whole without the written permission of Group GSA Pty Ltd. All levels and dimensions are to be checked and verified on site prior to the commencement of any work, making of shop drawings or fabrication of components. Do not scale drawings. Use figured Dimensions.
Drawing Title
Project Title
Client
PO Box 167, BroadwayNSW 2007
BLACKETT MAGUIRE + GOLDSMITHBCA/DDA Consultant
Suite 29, Level 8, 820 Adelaide StreetBrisbane QLD 4000
ELEPHANTS FOOTWaste Consultant
Level 11, 345 George StreetSydney NSW 2000
NORTHROPStructural Engineer
OLSSON FIREFire Engineer
Drawing No
AmendmentsIssue Description Date
DA SUBMISSION
Suite 6.02, Level 6, 89 York StreetSydney NSW 2000
INSYNC SERVICESServices Engineers
Suite 102, 506 Miller StreetCammeray NSW 2062
PTCTraffic Engineer
North Point
1 : 200
3/12
/201
8 5:
35:3
3 PMA
LEVEL 2-7 GA PLAN
ANGLICARE -MT DRUITT
ANGLICARE
DA2003180350
11/02/18
Author
Checker
Designer
Approver 1 : 2001 LEVEL 2-7 PLAN
1 : 2002 LEVEL 7 BALCONY LAYOUT
1 : 2003 LEVEL 5 BALCONY LAYOUT
1 : 2004 LEVEL 4 & 6 BALCONY LAYOUT
1 : 2005 BUILDING B - LEVEL 3-5-7 BALCONY LAYOUT 1 : 2006 BUILDING C - LEVEL 3-5-7 BALCONY LAYOUT
A ISSUE FOR INFORMATION 06/11/2018
Electrical ServicesEngineer: ARDate: 04/12/2018
Suite 6.02,Level 6,89 York StreetSydney NSW 2000
Tel: (02) 9262 3400Fax: (02) 9262 3422
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
ELECTRICAL CUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ON INSIDEOF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDINGCOMMUNICATIONS CUPBOARD:
- MIN 900 x 500mm- PREFERRABLE FOR CUPBOARDTO LINE VERTICALLY UP THEBUILDING
COMBINED ELECTRICAL/COMMUNICATIONSCUPBOARD:- MIN 1600 x 500mm- SMOKE SEALED- NON-COMBUSTIBLE METALLIC LINING ONINSIDE OF CUPBOARD DOOR- PREFERRABLE FOR CUPBOARD TO LINEVERTICALLY UP THE BUILDING
RL 66.300
DA3003 1
DA30041
DA3002
1
DA3001
1
DA3005 1
DA30042 DA3005 2 DA30032
DA31001
DA31001
DA31002
DA31002
DA31011
DA31011
DA31012
DA31012
BLOCK B BLOCK CBLOCK A
6m REAR SETBACK - DCP
6m S
IDE
SETB
ACK
- DCP
9m FRONT SETBACK (3 or more storeys) - DCP
7.5m FRONT SETBACK (1-2 storeys) - DCP
9m F
RONT
SET
BACK
(3 o
r mor
e sto
reys
) - D
CP
7.5m
FRO
NT S
ETBA
CK (1
-2 st
orey
s) -
DCP
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
9m REAR SETBACK (5-8 storeys) - ADG (HABITABLE)
9m S
IDE
SETB
ACK
(5-8 s
tore
ys) -
ADG
(HAB
ITAB
LE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m
SID
E SE
TBAC
K (5
-8 st
orey
s) -
ADG
(NON
-HAB
ITAB
LE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m REAR SETBACK (5-8 storeys) - ADG (NON-HABITABLE)
4.5m
SID
E SE
TBAC
K (5
-8 st
orey
s) -
ADG
(NON
-HAB
ITAB
LE)
6m REAR SETBACK - DCP
LIFT OVERRUN
SKYLIGHT
FIRE STAIR ACCESS HATCH
SKYLIGHT
SKYLIGHT
SKYLIGHT
SKYLIGHT
FIRE STAIR ACCESS HATCH
LIFT OVERRUN
SKYLIGHT
SKYLIGHT
SKYLIGHT
LIFT OVERRUN
SKYLIGHT
SKYLIGHT
HOTWATER PLANT 3.5M x 2.5M x 1.8M(H)
FIRE STAIR ACCESS HATCH
SKYLIGHTSKYLIGHT
HOTWATER PLANT 3.5M x 2.5M x 1.8M(H)
HOTWATER PLANT 3.5M x 2.5M x 1.8M(H)
SKYLIGHT
DA11023
DA1102
2
DA1102
4
DA1102 5
MATV ANTENNA/ PAYTV SATELLITE DISH
MATV ANTENNA/ PAYTV SATELLITE DISH
MATV ANTENNA/ PAYTV SATELLITE DISH
Group GSA Pty Ltd ABN 76 002 113 779Level 7, 80 William St East Sydney NSWAustralia 2011 www.groupgsa.com
T +612 9361 4144 F +612 9332 3458
architecture interior design urban design landscapenom architect M. Sheldon 3990
Project No
Approved
Verified
Plotted and checked by
Drawing Created (by)
Drawing Created (date)
Scale
Issue
This drawing is the copyright of Group GSA Pty Ltd and may not be altered, reproduced or transmitted in any form or by any means in part or in whole without the written permission of Group GSA Pty Ltd. All levels and dimensions are to be checked and verified on site prior to the commencement of any work, making of shop drawings or fabrication of components. Do not scale drawings. Use figured Dimensions.
Drawing Title
Project Title
Client
PO Box 167, BroadwayNSW 2007
BLACKETT MAGUIRE + GOLDSMITHBCA/DDA Consultant
Suite 29, Level 8, 820 Adelaide StreetBrisbane QLD 4000
ELEPHANTS FOOTWaste Consultant
Level 11, 345 George StreetSydney NSW 2000
NORTHROPStructural Engineer
OLSSON FIREFire Engineer
Drawing No
AmendmentsIssue Description Date
DA SUBMISSION
Suite 6.02, Level 6, 89 York StreetSydney NSW 2000
INSYNC SERVICESServices Engineers
Suite 102, 506 Miller StreetCammeray NSW 2062
PTCTraffic Engineer
North Point
1 : 200
3/12
/201
8 5:
35:3
6 PMI
ROOF PLAN
ANGLICARE -MT DRUITT
ANGLICARE
DA2004180350
10/09/18
LL
MB
LMC
LR
1 : 2001 ROOF LEVEL PLAN
A DRAFT 13/07/2018B DRAFT 20/07/2018C DRAFT 03/08/2018D DRAFT 14/08/2018E DRAFT 03/09/2018F ISSUE FOR PRE-DA 10/09/2018G ISSUE FOR INFORMATION 19/10/2018H ISSUE FOR VALUE MANAGEMENT 26/10/2018I ISSUE FOR INFORMATION 06/11/2018
Electrical ServicesEngineer: ARDate: 04/12/2018
Suite 6.02,Level 6,89 York StreetSydney NSW 2000
Tel: (02) 9262 3400Fax: (02) 9262 3422
MATV ANTENNA/PAYTV SATELLITEDISH
MATV ANTENNA/PAYTV SATELLITEDISH
MATV ANTENNA/PAYTV SATELLITEDISH
RL:BASEMENT
37.70
RL:GROUND
41.000
RL:L1
45.000
RL:L2
48.100
RL:L3
51.200
RL:L4
54.300
RL:L5
57.400
RL:L6
60.500
RL:L7
63.600
RL:RF
66.700
RL:L1
45.100
RL:L2
48.200
RL:L3
51.300
RL:L4
54.400
RL:L5
57.500
RL:L6
60.600
RL:L7
63.700
RL:RF
66.800
RL:GROUND
42.000
RL:L1
45.600
RL:L2
48.700
RL:L3
51.800
RL:L4
54.900
RL:L5
58.000
RL:L6
61.100
RL:L7
64.200
RL:RF
67.300
RL:GROUND
42.500
LV HV
MAIN SWITCHBOARD HOUSE DISTRIBUTION BOARD-B1-1
MP
RESIDENTIAL METER PANELLOAD CENTERS(6 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
HOUSEDISTRIBUTION
BOARD-1
TEE
TEE
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(5 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
MP
RESIDENTIAL METER PANEL
LOAD CENTERS(6 x APARTMENTS)
LOAD CENTERS(6 x APARTMENTS)
TEE
TEEHOUSE
DISTRIBUTIONBOARD-3
MP
RESIDENTIAL METER PANELLOAD CENTERS(8 x APARTMENTS)TEE
HOUSEDISTRIBUTION
BOARD-2
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)TEE
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)TEE
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)TEE
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)TEE
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)TEE
MP
RESIDENTIAL METER PANELLOAD CENTERS(11 x APARTMENTS)
SHOP DB MANAGERS DB
HOUSE DISTRIBUTION BOARD-B1-2
Job No:Scale:
Date:
Drawing Title:Services Consultant:THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BEREPRODUCED IN ANY FORM AS A WHOLE OR IN PART WITHOUTTHE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICES PTY.LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THEINTEREST OF INSYNC SERVICES PTY. LTD. THIS DRAWINGCONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTYOWNED BY INSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129INSYNC SERVICES
Project:
20180076(A3)Dwg No:
29/06/18N.T.S.E-MTD-01
ELECTRICAL SCHEMATICDIAGRAM
SOCIAL AND AFFORDABLE HOUSING FUNDSTAGE 2MT DRUITT
RL:BASEMENT
37.70
RL:GROUND
41.000
RL:L1
45.000
RL:L2
48.100
RL:L3
51.200
RL:L4
54.300
RL:L5
57.400
RL:L6
60.500
RL:L7
63.600
RL:RF
66.700
RL:L1
45.100
RL:L2
48.200
RL:L3
51.300
RL:L4
54.400
RL:L5
57.500
RL:L6
60.600
RL:L7
63.700
RL:RF
66.800
RL:GROUND
42.000
RL:L1
45.600
RL:L2
48.700
RL:L3
51.800
RL:L4
54.900
RL:L5
58.000
RL:L6
61.100
RL:L7
64.200
RL:RF
67.300
RL:GROUND
42.500
NTD
NETWORK TERMINATIONDEVICES (RETAIL/ COMMERCIAL)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
NBNBOUNDARY PIT
PDHPREMESISDISCTRIBUTION HUB
FDT E-NTD
6 x OUTDOOR NETWORKTERMINATION DEVICES
TO ESSENTIAL SERVICES DATA OUTLETS(3xLIFTS, FIP, SECURITY, MDL)
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO TENANCY DATAOUTLETS
NTD
NETWORK TERMINATIONDEVICES (5 x APARTMENTS)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO DATA OUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (8 x APARTMENTS)
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO TENANCY DATAOUTLETS
FDT
FIBER DISTRIBUTIONTERMINAL
TO TENANCY DATAOUTLETS
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
TO DATA OUTLETS
TO DATA OUTLETS
TO DATA OUTLETS
TO DATA OUTLETS
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (11 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
NTD
NETWORK TERMINATIONDEVICES (6 x APARTMENTS)
Job No:Scale:
Date:
Drawing Title:Services Consultant:THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BEREPRODUCED IN ANY FORM AS A WHOLE OR IN PART WITHOUTTHE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICES PTY.LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THEINTEREST OF INSYNC SERVICES PTY. LTD. THIS DRAWINGCONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTYOWNED BY INSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129INSYNC SERVICES
Project:
20180076(A3)Dwg No:
29/06/18N.T.S.E-MTD-02
COMMUNICATIONS SCHEMATICDIAGRAM
SOCIAL AND AFFORDABLE HOUSING FUNDSTAGE 2MT DRUITT
RL:BASEMENT
37.70
RL:GROUND
41.000
RL:L1
45.000
RL:L2
48.100
RL:L3
51.200
RL:L4
54.300
RL:L5
57.400
RL:L6
60.500
RL:L7
63.600
RL:RF
66.700
RL:L1
45.100
RL:L2
48.200
RL:L3
51.300
RL:L4
54.400
RL:L5
57.500
RL:L6
60.600
RL:L7
63.700
RL:RF
66.800
RL:GROUND
42.000
RL:L1
45.600
RL:L2
48.700
RL:L3
51.800
RL:L4
54.900
RL:L5
58.000
RL:L6
61.100
RL:L7
64.200
RL:RF
67.300
RL:GROUND
42.500
SECSECURITYHEAD-END
SECSECURITYPANEL
SECES
R
ES
R
ES
R
INTMAIN INTERCOM
VIDEO PANEL
APARTMENT VIDEOINTERCOMS
NVRCCTV NETWORKVIDEORECORDER
CCTV CAMERAS
ES
R
SECES
R
ES
R
SECES
R
ES
R
SECES
R
SECES
R
ES
R
ES
R
SECES
R
ES
R
SECES
R
ES
R
SECES
R
SECES
R
ES
R
ES
R
SECES
R
ES
R
SECES
R
ES
R
SECES
REXP
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS(6 x APARTMENTS)
I
I
APARTMENT VIDEOINTERCOMS(RETAIL/ COMMERCIAL)
I
I
EXP
EXP
EXP
APARTMENT VIDEOINTERCOMSEXP
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS(11 x APARTMENTS)
I
I
APARTMENT VIDEOINTERCOMS(8 x APARTMENTS)
I
I
EXP
EXP
EXP
APARTMENT VIDEOINTERCOMSEXP
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS
I
I
APARTMENT VIDEOINTERCOMS(5 x APARTMENTS)
I
I
EXP
EXP
EXP
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
Job No:Scale:
Date:
Drawing Title:Services Consultant:THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BEREPRODUCED IN ANY FORM AS A WHOLE OR IN PART WITHOUTTHE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICES PTY.LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THEINTEREST OF INSYNC SERVICES PTY. LTD. THIS DRAWINGCONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTYOWNED BY INSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129INSYNC SERVICES
Project:
20180076(A3)Dwg No:
29/06/18N.T.S.E-MTD-03
SECURITY SCHEMATICDIAGRAM
SOCIAL AND AFFORDABLE HOUSING FUNDSTAGE 2MT DRUITT
RL:BASEMENT
37.70
RL:GROUND
41.000
RL:L1
45.000
RL:L2
48.100
RL:L3
51.200
RL:L4
54.300
RL:L5
57.400
RL:L6
60.500
RL:L7
63.600
RL:RF
66.700
RL:L1
45.100
RL:L2
48.200
RL:L3
51.300
RL:L4
54.400
RL:L5
57.500
RL:L6
60.600
RL:L7
63.700
RL:RF
66.800
RL:GROUND
42.000
RL:L1
45.600
RL:L2
48.700
RL:L3
51.800
RL:L4
54.900
RL:L5
58.000
RL:L6
61.100
RL:L7
64.200
RL:RF
67.300
RL:GROUND
42.500
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
DT
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
(6 x APARTMENTS)
TO MATV OUTLETS2 WAY SPLITTER
(RETAIL/ COMMERCIAL)
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
DT
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
(8 x APARTMENTS)
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
(11 x APARTMENTS)
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
DT
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
(6 x APARTMENTS)
LAUNCHAMPLIFIER240V
TO MATV OUTLETS2 WAY SPLITTER
TO MATV OUTLETS2 WAY SPLITTER
LAUNCHAMPLIFIER240V
(5 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(11 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
(6 x APARTMENTS)
Job No:Scale:
Date:
Drawing Title:Services Consultant:THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BEREPRODUCED IN ANY FORM AS A WHOLE OR IN PART WITHOUTTHE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICES PTY.LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THEINTEREST OF INSYNC SERVICES PTY. LTD. THIS DRAWINGCONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTYOWNED BY INSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129INSYNC SERVICES
Project:
20180076(A3)Dwg No:
29/06/18N.T.S.E-MTD-04
MATV SCHEMATICDIAGRAM
SOCIAL AND AFFORDABLE HOUSING FUNDSTAGE 2MT DRUITT
RL:BASEMENT
37.70
RL:GROUND
41.000
RL:L1
45.000
RL:L2
48.100
RL:L3
51.200
RL:L4
54.300
RL:L5
57.400
RL:L6
60.500
RL:L7
63.600
RL:RF
66.700
RL:L1
45.100
RL:L2
48.200
RL:L3
51.300
RL:L4
54.400
RL:L5
57.500
RL:L6
60.600
RL:L7
63.700
RL:RF
66.800
RL:GROUND
42.000
RL:L1
45.600
RL:L2
48.700
RL:L3
51.800
RL:L4
54.900
RL:L5
58.000
RL:L6
61.100
RL:L7
64.200
RL:RF
67.300
RL:GROUND
42.500
FIP SIP SIPSSISEP
Job No:Scale:
Date:
Drawing Title:Services Consultant:THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BEREPRODUCED IN ANY FORM AS A WHOLE OR IN PART WITHOUTTHE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICES PTY.LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THEINTEREST OF INSYNC SERVICES PTY. LTD. THIS DRAWINGCONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTYOWNED BY INSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129INSYNC SERVICES
Project:
20180076(A3)Dwg No:
29/06/18N.T.S.E-MTD-05
DRY FIRE SCHEMATICDIAGRAM
SOCIAL AND AFFORDABLE HOUSING FUNDSTAGE 2MT DRUITT