![Page 1: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/1.jpg)
Electrical Hazards in the
Textile and Garment Industry
Practical Solutions for avoiding
danger
![Page 2: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/2.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 2
Introduction
Hazards arising from current flowing through the human body
Examples of “unacceptable” and “acceptable” situations
Fig. 1 by F. Kraugmann
![Page 3: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/3.jpg)
Hazards caused by electricity
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 3
Deadly failure at power rail
During non electrical maintenance
next to the power rail
Even the power rail was “finger safe”
Worker slipped off and the
screwdriver touched the power rails
Measurements
electrical hazards must be consider in
risk assessment too
Switch off electrical power
Cover power rails
Fig. 2 by BG ETEM
![Page 4: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/4.jpg)
Contact with hot and
harmful substances
Secondary hazardscurrent flowing
through human body
Hazards caused by electricity
Accidents caused by electricity can be divided into three main parts:
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 4
Fig. 3 by Napo [6] Fig. 4 by BG ETEM
Fig. 4 by BG ETEM
Fig. 5 by Napo [6]
![Page 5: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/5.jpg)
current flowing through the human body
The extent of injury reflects the impact of a series of factors, such as:
Amperage
Path of current
Frequency of current
Ambient conditions
(e.g. humidity, temperature)
Length of contact time
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 5
Fig. 6 by F. Kraugmann
![Page 6: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/6.jpg)
current flowing through the human body
- Can cause electric shock with a harmful effect on the internal
organs and their proper function
- Most vulnerable are cardiac activities
- Weak current mostly causes functional disorders, while heavy
current causes human tissue burn, especially if the current goes
in and out of the body
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 6
The current that may cause an injury is about 1/10th of the
current flowing through a light bulb!
![Page 7: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/7.jpg)
current flowing through the human body
The extent of injury reflects the impact of a series of factors:
Amperage
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 7
Injury: Amperage:
The lower limit of noticeability: 0,5 mA to 3 mA
Pain threshold: > 3,5 mA
Limit when you get stick on to it: 10 mA to 20mA
The lower limit of ventricular fibrillation: > 30 mA
Burn: > 2 A
Injury: Amperage:
The lower limit of noticeability: 0,5 mA to 3 mA
Pain threshold: > 3,5 mA
Limit when you get stick on to it: 10 mA to 20mA
The lower limit of ventricular fibrillation: > 30 mA
Burn: > 2 A
![Page 8: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/8.jpg)
current flowing through the human body
The resistor of a human body at 230 V in according
to the current path
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 8
current path resistor of human body
hand to hand 1000 Ω
foot to foot 1000 Ω
hands to feet 500 Ω
hand to feet 750 Ω
hand to chest 450 Ω
hands to chest 230 Ω
hand to backside 550 Ω
hands to backside 300 Ω
current (hand to hand) = 230V / 1000Ω = 230mA
The lower limit of ventricular fibrillation is about > 30mA
current (hand to hand) = 230V / 1000Ω = 230mA
The lower limit of ventricular fibrillation is about > 30mA
![Page 9: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/9.jpg)
Examples for “unacceptable” and “acceptable” conditions
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 9
Fig. 7 by IVSS [1] Fig. 8 by IVSS [1]
![Page 10: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/10.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 10
Examples for “unacceptable” and “acceptable” conditions
Fig. 9 by F. Kraugmann Fig. 10 by F. Kraugmann
![Page 11: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/11.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 11
Examples for “unacceptable” and “acceptable” conditions
Fig. 11 by F. Kraugmann Fig. 12 by F. Kraugmann
![Page 12: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/12.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 12
Examples for “unacceptable” and “acceptable” conditions
Fig. 14 by BG ETEMFig. 13 by F. Kraugmann
![Page 13: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/13.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 13
Examples for “unacceptable” and “acceptable” conditions
Fig. 15 by F. Kraugmann Fig. 16 by BG ETEM
![Page 14: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/14.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 14
Examples for “unacceptable” and “acceptable” conditions
Fig. 17 by F. Kraugmann Fig. 18 by BG ETEM
![Page 15: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/15.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 15
Examples for “unacceptable” and “acceptable” conditions
Fig. 19 by F. Kraugmann Fig. 20 by F. Tamberg
![Page 16: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/16.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 16
Examples for “unacceptable” and “acceptable” conditions
Fig. 21 by F. Kraugmann Fig. 22 by F. Kraugmann
![Page 17: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/17.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 17
Examples for “unacceptable” and “acceptable” conditions
Fig. 23:motor of textile crabbing machinery by F. Kraugmann
Fig. 24: Cable glands should be used to insert the cable into the metallic case by F. Kraugmann
Fig. 24 by BG ETEM
![Page 18: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/18.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 18
Examples for “unacceptable” and “acceptable” conditions
Fig. 25: findings found at spinning machines by F. Kraugmann
Fig. 26: Cable glands are missing by F. Kraugmann
Fig. 27: by F. Kraugmann
![Page 19: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/19.jpg)
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 19
Examples for “unacceptable” and “acceptable” conditions
Fig. 28:cable reel is not firmly clamped in the sockets anymore by F. Kraugmann
Fig. 29 by Napo [6]
![Page 20: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/20.jpg)
Summary
Basic rules for safe use of electrical equipment and tools:
It shall be designed and installed for safe operation
Periodic checks are definitely required
It shall be repaired safely and for safe further operation
Never by-pass the protective device
14.02.2017Electrical Hazards, Dipl.-Ing. Florian Kraugmann Seite 20
![Page 21: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/21.jpg)
List of references
[1] „Hazards arising from Electricity“, ISSA Section for Electricity
[2] “Golden Rules for Electrical Safety for the Layman”, ISSA Section for Electricity
[3] “Safety Rules for the Electrical Expert”, ISSA Section for Electricity
[4] „Sicherheit bei Arbeiten an elektrischen Anlagen“, BGI 519, BG ETEM
[5] „ Thermal hazards from electric fault arc“, DGUV Information 203-078, BG ETEM
[6] Pictures, Napo is co-produced by a European Consortium:
Electrical Hazards, Dipl.-Ing. Florian Kraugmann 14.02.2017 Seite 21
![Page 22: Electrical Hazards in the Textile and Garment Industry · Electrical Hazards in the Textile and Garment Industry Practical Solutions for avoiding danger. Electrical Hazards, Dipl.-Ing](https://reader031.vdocuments.mx/reader031/viewer/2022013010/5f0202dc7e708231d4022336/html5/thumbnails/22.jpg)
Further Information
Electrical Hazards, Dipl.-Ing. Florian Kraugmann 14.02.2017 Seite 22
www.bgetem.de
www.dguv.de
www.issa.com
www.suva.ch
www.napo.net
http://bangladeshaccord.org