electrical distribution systems, questions & answers, part i

Download Electrical Distribution Systems, Questions & Answers, part I

If you can't read please download the document

Upload: hany-kheir

Post on 15-Nov-2014

62 views

Category:

Documents


0 download

DESCRIPTION

the parameters of the induction motors, steady state or transient state including starting and short circuit conditions of ac machines. the major components in the power distribution systems and nd how they are defined, calculation of line and cable constants, the different types of breakers, starters and switchgear assemblies, the necessary calculations to size the load breaking/interrupting/disconnecting devices for normal and fault conditions, the types and sources of power line disturbances, the effects of such disturbances on the major components of the power systems and the methods of reducing these damaging effects, the effects of using local capacitors in increasing the circuit capacity and how to size capacitors to improve the p.f. in motor circuits, to quantify the effect of direct and indirect lightning strokes on overhead distribution systems, the data that have to be available in order to perform any of the following studies: TRV, stability, load flow, fault/co-ordination, motor starting, reliability and switching transients, the procedure to calculate the following: basic values including base and p.u. values, load flow, fault current/voltage sensitivity, motor starting, reliability studies for simple radial systems, steel properties, switchboard instruments, meters, relays definition and what are the major modules of PLC plus the building blocks of an office automation system, the calculations to be performed if a major power transformer is to be protected against short circuits or overloads, the essential programs and data for the power systems analyst (or any other individual involved in electric power distribution and studies - for that matter).

TRANSCRIPT

ELECTRICALDISTRIBUTIONSYSTEMSI. Introductiontothecourse:thiscourseisprovidedinaquestion&answerformatandisdividedinto5 chapters,itwillbecomeextremelyusefultoyou:

Ifyouwanttoknowtheparametersoftheinductionmotors,theireffectonthestartingand normalperformanceofthemachine. Ifyouwanttoanalyzeanexistinga.c.machineorevaluateanewoneforitssteadystateor transientstateincludingstartingandshortcircuit. Ifyouwanttoknowthemajorcomponentsinthepowerdistributionsystemsandhoweach componentisdefined. Ifyouwanttocalculatethelineandcableconstantsfromtheinformationfoundinstandard tables. Ifyouwanttoknowthedifferenttypesofbreakers,startersandswitchgearassemblies.Also,if youwanttoknowhowtheyaredefined. Ifyouwanttodothenecessarycalculationstosizetheloadbreaking/interrupting/disconnecting devicesfornormalandfaultconditions. Ifyouwanttoknowthetypesandsourcesofpowerlinedisturbances.Also,ifyouwanttoknow theeffectsofsuchdisturbancesonthemajorcomponentsofthepowersystemsandthemethods ofreducingthesedamagingeffects. Ifyouwanttoknowtheeffectsofusinglocalcapacitorsinincreasingthecircuitcapacityand howtosizecapacitorstoimprovethep.f.inmotorcircuits. Ifyouwanttoquantifytheeffectofdirectandindirectlightningstrokesonoverheaddistribution systems. Ifyouwanttoknowwhatarethedatathathavetobeavailableinordertoperformanyofthe followingstudies:TRV,stability,loadflow,fault/coordination,motorstarting,reliabilityand switchingtransients. Ifyoutoknowtheproceduretocalculatethefollowing:basicvaluesincludingbaseandp.u. values,loadflow,faultcurrent/voltagesensitivity,motorstarting,reliabilitystudiesforsimple radialsystems. Ifyouwanttoknowhowsteelproperties,switchboardinstruments,meters,relaysaredefined andwhatarethemajormodulesofPLCplusthebuildingblocksofanofficeautomation system. Ifyouwanttoknowthecalculationstobeperformedifamajorpowertransformeristobe protectedagainstshortcircuitsoroverloads. Ifyouwanttoknowwhataretheessentialprogramsanddataforthepowersystemsanalyst(or anyotherindividualinvolvedinelectricpowerdistributionandstudiesforthatmatter).

Contents: 1. A.C.Electricmachinesparameters&performance.

2. Overheadandundegrounddistributionsystemscomponents. 3. Switchgear,circuitbreakers,MCCandstarters. 4. Powerlinedisturbancesandpowerquality. 5. Powersystemsstudies. Lesson1:ACelectricmachinesparameters&performance. 1) Whataretheparametersoftheinductionmotorsandwhataretheteststobeperformedonsuch machinestobeabletoobtainthevaluesoftheseparameters? 2)Howcantheperformanceofaninductionmotorbeanalyzed? 3)Whataretheimportantcharacteristicsthatareusedindefiningsynchronousmachines(in general)andsynchronousgenerators(inparticular)?Sketchtheequivalentcircuitunderthe differentconditionsofoperation. 4)Whatarethedatarequiredfromtestingtocalculatetheparametersofsynchronousmotors? 5)Sketchtheequivalentcircuitofsinglephasetransformerandlisttherequiredtests(tobe performedontransformers)toobtainthevaluesoftheparametersoftheequivalentcircuit? 6)Asolvedproblemregardingtherunning&startingperformanceofaninductionmotor. 7)Asolvedproblemregardingthecharacteristicsofsynchronousmachines. 8)Asolvedproblemregardingtheparametersofsinglephasetransformers. 9)Asolvedproblemregardingthecharacteristicsof3windingtransformers. 10)Summarizethemethodsusedincalculatingtheparametersofsynchronousandinduction machines. Lessonsummary References 1)Whataretheparametersoftheinductionmotorsandwhataretheteststobe performedonsuchmachinestobeabletoobtainthevaluesoftheseparameters? Theparametersoftheinductionmotorsare:thestatorresistanceperphase,statorleakage reactance/phase,rotorresistance/phase,rotorleakagereactance/phase,mainfluxsusceptance andconductance/phase.Formotorsunderstartingconditionstheparametersarethesameas aboveexceptthevaluesoftherotorresistanceandreactance(referredtothestator)arehigher (duetoskineffect)andlower(duetotheskineffect&saturation),respectively.Theteststobe performedonsuchmachinestobeabletocalculatetheparametersofthemachinearetheno load(opencircuit)andlockedrotor(shortcircuit)underfullandreducedvoltage.Thereduced voltagetestisruntogettheunsaturatedreactancevalues(forrotor&stator).Thedatatobe collectedfromthenoloadtestare:Primaryvoltage,thenoloadcurrentandpowerat75C(or25 andcorrectedto75);fromthelockedrotor:thevoltage,currentandpowerat75C;fromthe lockedrotor(reducedvoltage):thevoltageandcurrent.Forthefirst2tests,thenominalmotor voltageisapplied,ifpossible.Fig.1showstheequivalentcircuitofaS.C.I.M.

R1:statorresistanceperphase,X1:statorleakagereactance/phase,R2':rotorresistance/phase referredtostator,s:slip,X2':rotorleakagereactancereferredtostator,Bm:mainflux susceptance,Gm:mainfluxconductance. 2)Howcantheperformanceofaninductionmotorbeanalyzed? Theperformanceofinductionmotorscanbeanalyzedbystudyingthefollowingpoints:heating ofwinding/iron,efficiencyofmotor,powerfactorofmachine,pullout(maximum)torque, startingtorque,startingcurrentsandtheeffectoftheparametersonsuchpoints.a)Heatingof windingandiron:toreducewindingheatingrotorandstatorresistanceshavetobesmall. Thoughforahighstartingtorque,therotorresistancehastobehigh.Toreduceironlosses,the mainfluxhastobelow.Notethatthemainfluxandrotorcurrentaffectthetorque. b)Efficiency:tohaveahighefficiencymotor,thewindings(copper)andironlosseshavetobe kepttotheminimumpossible. c)Powerfactor:toachieveahighpowerfactormachine,theleakagereactances(statorand rotor)havetobelowi.e.lowreactivecurrent.Tohaveahighpullouttorque,thefluxhastobe high. d)Maximum(pullout)torque:tohaveahighpullouttorqueininductionmotors,primary (stator)andsecondary(rotor)reactancesshouldbekepttoaminimum,therotorresistancewill onlydeterminetheslipofthemaximumtorque. e)InrushCurrent:reactances(andforsmallmotors,theresistances)oftherotorandstator windingshavetobehightohavealowinrushcurrent. f)Startingtorque:therotorwindingresistancehastobehightogetahighstartingtorque,this contravenestheefficiencyrequirement. Ascanbeseenfromtheabove,theparametersofinductionmachines(i.e.theirdesign)area compromisetoachievetheoptimumstarting,pulloutandrunningperformancesrequiredbythe differentapplications.Whenamotorisexistingandthefollowingdataareavailable:motorHP, terminalvoltage,frequency,numberofpoles,statorresistance,windagelosses,strayloadlosses andtheothermotorparameters(ortheresultsofthetests),thefollowingarecalculated:the

rotorcurrentreferredtostator(I2'),startingtorque(Tst)andthepowertransferredbythe rotatingfieldtotherotor(Prot.f)forstartingperformanceanalysis.Fortherunning performance:theslip(s),statorandrotorcurrents,thedevelopedtorqueandpower,the efficiencyandthepowertransferredbyrotatingfieldatratedmotorHPandatpullout conditionsorstatesarecalculated. 3)Whataretheimportantcharacteristicsthatareusedindefiningsynchronousmachines (ingeneral)andsynchronousgenerators(inparticular)?Sketchtheequivalentcircuit underthedifferentconditionsofoperation. Thecharacteristicsofsynchronousmachinesthatdefinesuchmachinesarethenoload,short circuit,airgapandpotiertriangle. Todefineagenerator,thefollowingcharacteristicstobeinvestigated:noloadandairgap,short circuitandPotiertriangle,loadcharacteristics,externalcharacteristics,regulationcurve,short circuitratioandthedeterminationofthedirectaxisreactance. a)Noloadandairgap(unsaturated)ch/cs:itisexpressedonagraphwiththeYaxis representingthearmature(stator)e.m.f.(electromotiveforce)orthepoleflux,withtheXaxis representingthefieldcurrent(If)orthefieldm.m.f.(magnetomotiveforceinAmpereturn).The airgapch/csisastraightlinepassingthroughtheoriginandthesecondpointistheE(rated statorvoltage)valueatalowfieldcurrent(unsaturatedconditions).Thenoloadcharacteristics underunsaturatedconditioncoincideswiththeairgapcharacteristicsuptoapoint.Atthe pointwhereEistheratedinducedinthearmaturebythefluxproducedfromtheresultantmmf (Mr)thecharacteristicslineisnonlinear(bendinward)saturatedcondition.Theresultantmmf willconstituteoftwoportions:thatparttodrivethefluxthroughtheairgapandtheotherpart todrivethefluxthroughtheironpartsofthemagneticpath.Fig.2belowshowstheairgap,no load&shortcircuitlinesvs.If. b)Shortcircuitcharacteristics(Potiertriangle):theS.C.ch/csrepresentsthearmaturecurrent (Ia)asafunctionofthefieldcurrent(If)orofthefieldmmf(MMF)withthearmature terminalsshortcircuited.Itistakenatsynchronousspeedofthegenerator.TheS.C.ch/csisa straightlinepassingthroughtheoriginandthesecondpointwillhavetheXaxisequaltothe fieldMMFandtheYaxisequalthearmaturecurrent.Potiertrianglewillhavethefollowing importantquantities:armaturereactionmmfandtheleakagereactance(impedance)ofthe armature.Thecosf=0loadcharacteristicsisconstructedfromthenoloadch/csandPotier triangle. c)Loadcharacteristics:itistheterminalvoltageVasfunctionoffieldcurrent(If)orfieldmmf (Mf)forconstantloadcurrent(Ia)andpowerfactor(p.f.).Atafixedloadcurrent,thefield currentisrequiredtosustainthenoloadvoltageanditincreaseswiththedecreaseofcosf,this mainlytocounteractthearmaturereaction.Potiertrianglecanbedeterminedfromthenoload ch/csandtwopointsonthecosf=0loadch/cs. d)Externalcharacteristics:itisexpressedastheterminalvoltage(V)asfunctionoftheload current(Ia)atconstantIfandp.f.Forlaggingcurrent,thevoltagedropincreasesasthepower factordecreasesandviceversaforleadingcurrent.

e)RegulationCurve:itdescribesthefieldcurrentasfunctionofeithertheloadcurrentwith constantp.f.orthep.f.atconstantcurrent(Ia)providedthattheterminalvoltageiskept constant.Thefieldcurrentincreaseswiththeincreaseinloadcurrent(p.f.isconstantletssayat 1or.8),thefieldmmfhastoincreasetocompensateforthearmaturereactionincrease. f)Shortcircuitratio:itistheratioofthefieldcurrentrequiredtoproduceratedvoltageonopen circuittothefieldcurrentrequiredtoproduceratedcurrentonshortcircuit.ThesaturatedS.C. ratioisobtainedfromthenoloadcurveandtheratedarmaturecurrent(fieldmmftoproduce ratedVdividedbythemmfproducingtheratedcurrent).TogettheunsaturatedS.C.ratio, dividetheMMFvaluethatproducestheratedVfromtheairgapstraightline(itistheextension ofthelinearairgaplinethatistakenfromthenoloadcurve)bytheMMFproducingtherated currentundershortcircuitcondition.AlargeSCRindicatesasmallarmaturereactionwhich meansthatthemachineislesssensitivetoloadvariations.AsmallSCRmeansthatthemachine ismoresensitivetoloadvariations. g)Determinationofdirectaxissynchronousreactance(Xd):itisobtainedfromthenoload linearportion(orairgapline)andS.C.characteristics.Thefieldcurrentinducesthenominal voltageontheairgapline.Whenthestatorisshortcircuitedandthefieldcurrentismaintained atthesamelevelaswiththeopencircuitcondition,theinducedemfinthestatoristhesameas withthenoloadconditionbutinthiscaseitisconsumedbythedropduetothesynchronous impedance.TheunsaturatedshortcircuitratioisusedtocalculateXd,Xd=1/SCR. Fig.2abelowshowstheequivalentcircuitofthesynchronousmachineunderthedifferent conditions.

Xs:statorleakagereactance,Xm:mainfluxreactance,Xf:fieldleakagereactance,Xd:damper leakagereactance.

4)Whatarethedatarequiredfromtestingtocalculatetheparametersofsynchronous motors? Theteststobeperformedonthesynchronousmachinesothattheparameterscanbecalculated are:theopencircuit(noload)characteristics,shortcircuitandtheairgapline.Fromthefirst test,twovaluesareobtained:thenominalstatorvoltatthefieldcurrentregistered;fromthe second:2pointsareobtained(4values):thenominalstatorcurrentanditscorrespondingfield currentandthestatorcurrent(Ia)atthefieldcurrentobtainedfromtheopencircuittest;from thefinaltest:thevoltageatthefieldcurrentequaltotheoneproducingthenominalcurrentin theprevioustest. 5)Sketchtheequivalentcircuitofsinglephasetransformerandlisttherequiredtests(to beperformedontransformers)toobtainthevaluesoftheparametersoftheequivalent circuit? Fig.3belowshowstheequivalentcircuitofasinglephasetransformer.Theteststobe performedontransformerssothattheparameters,whicharetheprimaryandsecondary windingsresistancesandreactancesplusthemainfluxsusceptanceandconductance,canbe calculatedare:thenoload(opencircuitedprimaryH.V.winding)testfromwhichtheopen circuitvoltonl.v.sideandthenoloadcurrentareobtained;theS.C.(l.v.windingshort circuited)fromwhich3valuesareregisteredtheS.C.lossesinW(orkw),theratedS.C. currentasseenfromtheprimarysideandthevoltagecirculatingsuchcurrent.Theprimary windingresistance(d.c.)shouldalsobemeasuredbyanohmmeterat25C.

R1:primarywindingresistance,X1:primarywindingleakagereactance,R2':secondary windingresistancereferredtotheprimarywinding,X2':secondarywindingreactancereferred totheprimary,Bm:mainfluxsusceptance,Gm:mainfluxconductance,r2':loadresistance referredtotheprimarywinding,x2':loadreactancereferredtotheprimary(inprimaryside terms). 6)A3phaseinductionmotor,3HP,440/220V,60HZ,4pole,1750rpm,hasthefollowing noloadtestresults:Vnl=440V,Inl=2.36A,Pnl=211W;lockedrotor(fullvoltage)results:

Ilr=29A,Vlr=440V,Plr=13.9KW;lockedrotor(reducedvoltage):Vlr1=76V,Ilr1=4.25A unsaturatedreactancecondition.Assumewindageloss=44W,strayloadloss=48W,skin effectfactors=1.3forrotorwindingresistance(referredtostator),.97forrotorreactance andstatorresistance/phase=2.26W.Determinethe6parametersoftheinductionmotor, itsstartingandrunningperformancedata,thetransientreactanceandthes.c.time constant,thes.c.currentafter1and2cyclesfromfaultinception.Calculatetheduration oftheinrushcurrentassumingJ=2lb.ft2fortherotatingparts. GIVEN:Vprim=440V,Ioc=2.36A,Poc=211W,Vlr=V1=440V,Ilr=29a,Plr=13.9KW, Vlrr=76V,Ilrr=4.25A,HP=3,r1@25C=2.26OHM,windageloss=44W,strayload loss=48W,skineffectforr2',x2'=1.3,0.97. SATURATEDREACTANCE: Zl=440/[(3).5(29)]=8.73W,Rl=13920/3(29)(29)=5.48W, X=[(8.73)2(5.48)2].5=6.8W,r1@75C=2.26[(234+75)/(234+25)]=2.69W, r2'=R1r1(@75C)=5.482.69=2.79W,X1=X2=X/2=3.4OHM. UNSATURATEDREACTANCE: Z=76/[(3.5)(4.25)]=10.3W,X=[(10.3)2(5.48)2].5=8.72W, X1=X/2=4.36OHM,Saturationfactor=4.36/3.4=1.3, includingforskineffect:r2'=2.79/1.3=2.14OHM, X2'=4.36/.97=4.5W,Xm=[(V1)(Ioc.X1)]/Ioc=[(440/3.5)(2.36)(4.36)]/2.36=103OHM, Ph+e=Poc3(Ioc)2(r1@75C)windagelosses=2113(2.36)2(2.69)44=122W. Assuming1/2theironlossesareduetothemainflux.Ph+e=122/2=61W Gm=Ph+e/3(E1)2={61}/{3[(440/3.5)(2.36)(4.36)]2}=3.43/10000MHO Rm=Gm.Xm2=[(3.43)/(10000)][103]2=3.66W STARTINGANDRUNNINGPERFORMANCE: Basevaluescalculations:Vb=440/3.5b=3x746/3x254=2.94A,Zb=254/2.94=86.5OHM. Pb=254x2.94=746W,Tb=7.04(3)(unitpower)/unitspeed=7.04x3x746/1800=8.8LB.ft. Parametersforstartingperformanceinp.u: r1=2.69/86.5=.0311,r2'=2.79/86.5=.0322,x1=x2'=3.4/86.5=.039(saturatedconditions). Parametersforrunningperformanceinp.u: r1=.0311,r2'=2.14/86.5=.0248,x1=4.36/86.5=.0504,x2'=4.5/86.5=.052(unsaturated). Parameterscommontoboth: Xm=103/86.5=1.19,Rm=3.66/86.5=.042p.u. Startingperformance:

r2'(1s)/s=0asatstandstills=1=(nsn)/ns

Z1=(r12+x12)=[(.03)2+(0.039)2]=0.05,tan1=x1/r1=51.4Z2'=[(.032)2+(.039)2]=.0506/_50.6 Zm=[(1.19)2+(.042)2]=1.19,tan11.19/.042=87.98 V1=I1.Z1+(I1)/[(1/Z2')+(Ym)] V1=I1[.05/_51.4+(1)/(1/.0506/_50.6)+(1/1.19/_87.98)];whereYm=1/Zm,V1=I1.Zeq, V1=1/_0 I1=V1/{.05/_51.4+{[(.0506)(1.19)/_138.58]/[.0506/_50.6+1.19/_87.98]}} I2'=I1[Zm/(Z2'+Zm)]=9.66/_50.4 Protfield=I2'2(r2'/s)=(9.66)2(.0322)=3p.u. Tst=3p.u.=3x8.8=26.4LB.ft RunningPerformance: s=.03,r2'(1s/s)=.8,Z1=.0593/_58.3,Z2'=.825/_3.6,Zm=1.19/_87.98, I1={1/_0}/{[.0593/_58.3]+[(.825/_3.6.1.19/_87.98)/(.825/_3.6+1.19/_87.98)]} Inputp.f.=cos38.2=.785 I2'=1.42/_38.2[1.19/_87.98/(.825/_3.6+1.19/_87.98)]=1.12/_5.74 Protfield=I2'2.(r2'/s)=(1.12)2(.0248/.03)=1.025p.u. Tdeveloped=1.025p.u.=1.025(8.8)=9.02LB.ft. MechanicallossTorque=7.04(strayloadloss+windage+mainfluxironloss)/ns(Torquebase) =7.04(48+44+61)/1800(8.8)=.068 Tnetdeveloped=1.025.068=.957p.u.x8.8=8.4LB.ft. Powerinput=3(1)(1.42)(cos38.2)=3.35p.u. Losses(statorcopper)=3(1.42)2(.0311)=.189p.u.

Losses(rotorcopper)=3(1.12)2x.0248=.093p.u. Noloadironlosses=122/746=.163p.u. Losses(strayload)=48/746=.064p.u. Losses(friction&windage)=.059p.u. Totallosses=.568p.u. Pdeveloped=3.35.568=2.78p.u.x746=2076W=2.78HP eff.=2.78/3.35=83% slip=3(1.12)2(.0248)/[3.35(.189+(.163/2))]=.03 snormal=3/2.78=.0324 spullout(@maxTorque)=[(1+(X1/Xm))(r2')/[X1+(1+(X1/Xm))X2'] =[(1.0+.0504/1.19)(.0248)/[.0504+(1.042)(.052)]=.246p.u.

r2'(1s/s)=0.0758(@s=.246),Z2'=r2'+r2'(1s/s)+jX2'={[r2'+r2'(1s/s)]2+X2'2}.5 =[(.0248+.0758)2+(.052)2].5=.113/_27.3tan1(.052)/(.0248+.0758)=27.3 I1=6.12/_41,I2'=5.85/_36,Protatingfield=I2'2(r2'/sp.o.)=3.44p.u. Tp.o.=3.44x8.8=30.2LB.ft. Tdeveloped(@3HP&s=.0324)=5250x3/1800(1.0324)=9.02Lb.ft StartingTorque/NormalTorque(rated)=3/1.025=2.92 PulloutTorque/ratedTorque=3.44/1.025=3.36 TransientAnalysis: Transientreactance=.0504+[(.052)(1.19)/(.052+1.19)]=X"=.1p.u. P.F.=.785,efficiency=83%,Ib=2.94A I1=3x746/.785(.83)(440)(1.732)=4.5A=1.53p.u. E1'=1[(.03+j.1)(1.53xcos38.2j1.53xsin38.2)]=.874p.u./_6 InitialS.C.current=.874/.1=8.74x2.94=25.7A To'=opencircuittransienttimeconstant=(X2+Xm)/2(pi)fr2,wherepi=3.141592654 T'=To'[X"/(X1+Xm)]=S.C.timeconstant IS.C.=InitialS.C.C.(et/T) To'=.052+1.19/2(pi)60(.0248)=.133sec. T'=.133(.1)/.124=.011sec. IS.C.(after1cyclei.e..0166sec.)=8.74(e.01666/.011)=2p.u. IS.C.(after2cycles)=8.74(.048)=.43p.u. StartingTime: Anapproximatesolutioniftheloadandmotorspeedtorquecurvesarenotavailableisas follows: t=J(rpm1rpm2)2(pi)/60gTn J=2lbft2,rpm1=1740,rpm2=0,g=32.2ft/sec,Tst=26.4,Trated(@ratedHP)=9.02 Tn=acceleratingtorquebetweenrpm2torpm1=Tst+Trated/2=(26.4+9.02)/2=17.7LB.ft. t=.7sec. 7)Asynchronousmachinerated45KVA,3phase,220Vl.l.,wastestedunderopencircuit (noload)andshortcircuit(lockedrotor),thefollowingweretheresults:OPENCIRCUIT: Vl.l.=220V,Ifield=2.84A,SHORTCIRCUIT:Iarm.1=118A(firstpoint),Ifield1=2.2A, Iarm.2=152A(secondpoint),Ifield2=2.84A,themachinewastestedatapowerfactor=0 fromshortcircuitedarmatureconditiontonoloadcondition.Thenoloadandairgap plustheshortcircuitcurvescanthusbeplotted(asshowninquestion3,fig.2above)and

thecharacteristicsofthemachinecanbeobtainedgraphically.Theairgaplineisplotted from:Ifield=2.2A,Vl.l.=202Vatratedarmaturecurrent=118A,assumes.c.loadlosses (3phaselosses)=1.8KW@25C,armatureresistance@25C=.0335W/phase,field resistance@25C=29.8W/phase.Calculatethesaturatedandunsaturatedreactance, theeffectivearmatureresistanceandthes.c.ratio.IfthismachinerunsasamotoratV= 230V,inputpowertoarmature=45KW,.8p.f.leadingcurrent,fieldcurrent=5.5A, thencalculatetheefficiencyofthemotor. Linetoneutralvoltage=202/1.732=116.7Vontheairgapline;forthesamefieldcurrentof 2.2a,ontheS.C.line,thearmaturecurrent=118amp. Thesaturatedreactance=Xs Theunsaturatedreactance=Xsairgap=116.7/118=.987OHM,ratioofunsaturatedreactanceto saturatedreactance=.987/.836=1.18 Shortcircuitratio=2.84/2.2=1.29(saturated),Xs(saturated)=1/1.29=.775p.u. Airgapfieldcurrentcorrespondingto220vlinelinearmaturevoltage=(220/202)(2.2)=2.39 A shortcircuitratio=2.39/2.2=1.086p.u.(unsaturated),Xs(unsaturated)=1/1.086=.92p.u. Thearmatureeffectiveresistance: S.C.loadloss/phase=1800/3=600W/ph. ra(eff)=600/(118)2=.043W/phase ra(eff)inp.u.=.04/(1)2=.04p.u. inp.u.:S.C.loadloss=1.8/45=.04p.u. ratioofa.c./d.c.resistance=.043/0335=1.28(skineffectandproximity) Note:armatureresistanceofm/csabovefewhundredsKVAislessthan0.01p.u. Forthem/coperatingasamotorwithleadingpowerfactor: Ia=45/(1.732)(.8)=141amp. Assumestrayloadlossof30%ofS.C.loadloss=.54KW Resistanceforcopperwindingofarmatureat75C=0.335[234+75/234+25]=.04OHM/ph Resistanceforcopperwindingoffieldat75C=29.8[(234+75)/(234+25)]=35.5OHM/ph ArmatureCulosses(assumera=.04or.035W/ph)=3Ia2ra=3(141)2(.04)=2.38KW FieldCulosses=(5.5)2(35.5)=1.07KWE=internalvoltageofmotor=VtIara= (230/1.732)(141)(.8+j.6)(.04)=128.4j3.4Vphase Vlinetoline=220Vatwhichcorelosses=1.2KW Totallosses=2.38+1.07+.56+1.2+.91=6.12KW Input=45+1.07=46.07KW Efficiency=1(6.12)/(46.07)=86.7%

8)Calculatetheequivalentcircuitparametersforthefollowingsinglephasetransformer. Theresultsoftheopencircuittest(H.V.wdgopen)are:Vo.c.=347V,Io.c.=18A,Po.c.= 980W.Theresultsfromtheshortcircuittest(L.V.wdgshorted)are:Vs.c.=70V,Is.c.= Irated,Ps.c.=1050W.The2windingtransformerratingsare:2400/347V,100KVA, primarywindingresistanceat25C=.24W.Also,calculatetheregulationandeffeciency atunityand.8p.f.fullloadcurrent. Transformerratio:2400/346V,Irated=(100)/2.4=41.6A Transformationratio=a=2400/346=7,Zsc=Vsc/Isc=70/41.6=1.68OHM Rsc=Psc/(Isc)2=1050/(41.6)2=.607OHM Xsc=[(1.68)2(.607)2].5=1.57OHMRsc(at75C)=.607[(234+75)/(234+25)]=.723OHM r1(at75C)=.24[234+75/234+25]=.28OHM r2'=Rscr1=.723.28=.44OHM X1=X2'=Xsc/2=.785OHM Fromopencircuittests:(L.V.wdg.excited): Ph+e=Po.c.(Io.c./a)2r1=980(18/7)2(.28)=978W E1=2400(Io.c./a)X1=2400(18/7)(.785)=2400V rm=gm(Xm)2=.00017(934)2=148OHM Zb=2400/41.6=57.7OHM,Zpu=1.68/57.7=.03pu Xpu=1.57/57.7=.027pu,Rpu=.0125p.u. Regulationandefficiency: Regulationat1p.f.:Reg.=(.0125)+(.027) 9)A3windingtransformer(primary,secondary,tertiary)singlephaserated7960V (1000KVA),2400V(500KVA)&2400V(500KVA).Theresultsofthes.c.testsareas follows: Test WDGExcited 1 2 1 1 WDGShortCircuited 2 3 AppliedVoltageValue 252 252 CurrentInExcitedWDG 62.7 62.7 Xm=2400/18/7=934OHM,gm=Ph+e/E12=.00017MHO

3 2 3 100 208 The3transformersareconnectedinaYDDconfigurationon13.8/2.4/2.4KV.Whenthetertiary windingsareshortcircuited(3phase),calculatethes.c.currentandthevoltageontheterminalsofthe secondarywindingsofthisbank.

Forprimarywinding:Vb=7960V,Ib=1000/7.96=125.4A Forsecondarywinding:Vb=2400V,Ib=1000/2.4=416A Forteritiarywinding:Vb=2400,Ib=416A Test 1 2 Zbetweenterminals 12 13 Vpu 252/7960=.0316 252/7960=.0316 Ipu 62.7/125=.5 62.7/125=.5 208/416=.5 Zpu=Vpu/Ipu .0632 .0632 .0832

3 23 100/2400=.0416 Z1=1/2[.0632+.0632.0832]=.0216pu Z2=1/2[.0832+.0632.0632]=.0416pu Z3=1/2[.0632+.0832.0632]=.0416pu

Isc=1/(.0216+.0416)=15.8p.u.(S.C.teritiary)=15.8x125.4=1984A V2=voltageonsecondarybuswhileteritiaryisshortcircuited=Is.c.xZ3IsecxZ2,Isecistheload current =15.8(.0416)1(.0416)=62.44.16=.5824p.u.TocalculatetheS.C.currentassumingabaseMVA=.5 MVA=500KVA: Znew=Zold[KVAnew/KVAold]p.u. Z3new=.5(.0416)=.0208,Z1new=.5(.0216)=.0108,Isc=1/.5(.0632)=1/(.0208+.0108)=31.6p.u., Ibase=500/7.96=62.8A,Isc=31.6(62.8)=1984A 10.Summarizethemethodsusedincalculatingtheparametersofsynchronousandinduction machines. Synchronousmachines: Positivesequence(synchronousparameters):Theairgap,noloadandshortcircuitcharacteristics:the machineisrunatsynchronousspeedintheproperdirection.Thethreephasearmatureterminalsare keptopenandlinetolinevoltagereadingsaretakenatdifferentfieldcurrent(arheostat)inthefield windingisusedtovarythefieldcurrent).Theexcitationisreducedtoaminimumandthe3phaseare shortedandthefieldreadingplusthecurrentflowinginoneofthelinesaretaken(todrawtheshort circuitunsaturatedcharacteristicslinepassingthroughtheorigin). Subtransientreactance:shortcircuitthefieldthroughanammeter,applyasinglephasevoltagetoany ofthethreelineterminals,rotatetherotorbyhand.Atthepositionindicatingmaximumfieldcurrentin thefieldammeter,halfthevoltameterreadinginthearmaturecircuitdividedbythearmaturecurrentin oneline(usinganammeterinoneofthelineterminals)isequalthesubtransientdirectaxisreactance. Attheminimumfieldcurrentreading,halfthearmaturevoltagedividedbythearmaturecurrentwill givethesubtransientreactanceintheqaxis. NegativeSequencereactance:thefieldisshortedonitself,twophasesareconnectedtoeachother throughanammeterandasinglephasevoltageisappliedtothisarmatureconfiguration.Thefieldis

rotatedatratedspeedandthevoltageappliedtothearmaturewillcorrespondtoapproximately circulatingtheratedmachinecurrent.Thenegativesequenceimpedance=V/1.7321(I).Thismethod canalsobeusedwithinductionm/cs. Zerosequenceimpedance:zerosequenceimpedanceismuchsmallerthanthepositiveandnegative andintheoryisclosetozero.Themachineisatstandstill,thefieldisopen,thesixterminalsofthe machineareavailableoutsidethemachineandthethreewindingsareconnectedinseries.Areduced voltageisappliedacrossthe3connectedwindingsandthezerosequenceimpedancewillbeequalto onethirdthevoltagereadonthevoltameterdividedbythecirculatedcurrentreadontheammeterin thearmaturecircuit. InductionMachine: Steadystatereactance:fromthethreetests,noload(opencircuit),lockedrotor(shortcircuit)full voltage(forsaturatedreactance)andlockedrotor(shortcircuit)reducedvoltage(forunsaturated reactance),theparametersareobtained. Transientreactance:iscalculatedfromtheparametersofthemachineobtainedfromtheabovetests.X" =[X2(Xm)/(X2+Xm)]+X1. SUMMARY: Inthischapter,theparametersandperformanceofa.c.electricmachineswerepresented.Thetests performedonsuchmachinestoobtaintheirparametersweregiven,theparametersandtheireffectson themachinesperformancewerecovered,too.Numericalexamplesweregiventoshowandclarifythe interrelationsbetweenthemachineparametersandtheperformance.Theinductionmachines parametersare:statorresistance&reactance,therotorresistanceandreactance,themainflux susceptanceandconductance.Theseparametersaffectthemachineduringstarting(inrushcurrent& startingtorque),atnominalload(fullloadcurrent&nominaltorque),andforthemaximum(pullout) machinetorque.They,also,affectthelosses(heatingofiron&winding),efficiencyandpowerfactor. Thecharacteristicsofsynchronousmachinesingeneralandgeneratorsinparticularpresentedinthis chapterwere:theairgapandnoload(armatureemforpolefluxvs.mmforfieldcurrent),shortcircuit (armaturecurrentvs.fieldcurrent),loadch/cs(terminalvoltagevs.fieldcurrentprovidedthattheload currentandthep.f.arekeptconstant),external(voltagevs.loadcurentwithconstantfieldcurrent& p.f.),regulation(fieldcurrentvs.loadcurrentwithconstantp.f.orfieldcurrentvs.p.f.withconstant loadcurrent,voltageiskeptconstantineithercase),shortcircuitratio(fieldcurrentproducingnominal voltageunderopencircuitconditionvs.fieldcurrentproducingratedcurrentunderarmatureshort circuitcondition)anddirectaxissynchronousreactancedetermination(whichisequalto1dividedby theSCR).Forthetransformers,2&3windingparameterswerepresentedandtheireffecton regulation/efficiencyof2windingstransformersandfor3windingsshortcircuitplusvoltage sensitivityoftheunfaultedbusweregivenandemphasizedbynumericalexamples. REFERENCES: 1. Greenwood,Allan"ElectricalTransientsinPowerSystems",Wiley. 2. Granger&Stevenson"PowerSystemAnalysis",McGrawHill.

3. Tuma,Jan"EngineeringMathematicsHandbook",McGrawHill. 4. Fitzgerald,Kingsley&Kusko"ElectricMachinery",McGrawHill. 5. Kheir,"AutomatingPowerSystemsAnalysis",Kheir Home page of VePi

Lesson2:Overheadandundergrounddistributionsystemscomponents. 1) HowwouldEPR(ethylenepropylenerubber)cables,upto35KV,beclassified? 2)HowwouldundergroundXLPE(crosslinkedpolyethylene)cablesclassified? 3)Whatarethedefiningparametersofcables? 4)Whatarethefactoryandsiteteststobeperformedoncables? 5)Whatarethedefiningparametersforlowvoltagesecondarycables? 6)Whatarethedifferenttypesoftransformersfoundindistributionsystems? 7)Whatarethedifferenttypesofoverheadswitches,padmountedswitchgearandthoseof lightninigarresters? 8)Whatarethestandardsthatgoverndistributiontransformers?Howaredistribution transformersdefined? 9)Howarewoodenandconcretepolesdefined? 10)Whatarethedifferentapplicationsofoilswitchesandwhataretheirdefiningparameters? 11)Howareoverheadairswitchesclassified? 12)Howarepadmountedswitchgeardefined? 13)Whataretheimportantparametersbywhichlightninigarrestersaredefined? 14)Howwouldcopperconductorsbedefined? 15)HowwouldACSR(aluminumconductorsteelreinforced)andASC(aluminumstranded

conductor)bedefined? 16)HowwouldAASC(aluminumalloystrandedconductor)andselfdampening/compact ACSRbedefined? 17)Whatarethedifferenttypesofcablesplicesandterminations? 18)Whatarethedifferenttypesofconnectorsandelbows? 19)Whatarethedesigntestsperformedontheseparableconnectors? 20)Whatarethedifferenttypesofinsulators,theirmaterialandcharacteristics? 21)WhatarethefunctionsofDAC(distributionautomationandcontrol)?Sketchthetypical undergrounddistributionarrangementsandtheoverheaddistributionsystem. 22)WhatarethemajorinformationobtainedfromadistributionsystemSCADA?Showablock diagramofthemajorcomponentsofaSCADA(systemsupervisorycontrol&dataacquisition). Sketchadiagramtoshowatypicalautomateddistributionsystemwithpowerand communicationlines. 23)WhatarethebasicmodulesinaPLC(programmablelogiccontroller)system?Sketcha frontplateof2ofthebasicmodules.Sketchablockdiagramshowingtheinterrelationofthe majormodules. 24)Asolvedproblemregardingconstantsofoverheadconductors? 25)Asolvedproblemregardingconstantsofundergroundcables? 26)Asolvedproblemregardingreflected&refractedpowersataconductor/cablejunction? 27)Asolvedproblemregardingpowertransformerprotection? Lessonsummary References 1)HowwouldEPR(ethylenepropylenerubber)cables,upto35KV,beclassified? TheclassificationofEPR(upto35KV)cablesisasfollows:thevoltageclass,theconductor material/size(whichisfunctionofthenormal/overload/shortcircuitcurrentvaluesandthe installationmethod/configuration),theinsulationthickness(whether100%or133%),jacketed orunjacketed,neutralsize(eitherfullor1/3rating),cableinconduitconfiguration/directburied orconcreteencasedconduits. 2)HowwouldundergroundXLPE(crosslinkedpolyethylene)cablesclassified? TheclassificationofXLPE(upto46KV)cablesisasfollows:thevoltageclass,theconductor material/size,insulationthickness,jacketedorunjacketed,neutral(concentricneutralandrating fullor1/3mainconductor)orshielded(Cutape),singleor3conductorcables,jackettype (whetherencapsulatedorsleeved),theuseofstrandfillorwaterblockingagentbetweenthe insulationandjacket. 3)Whatarethedefiningparametersofcables? Thedefiningparameterscanbeclassifiedbroadlyintodimensional,insulationmaterial propertiesandcurrentcarryingcapacity.Fordimensionalparameters,conductorsize/numberof strands/typeofstrands,diameteroverconductor,diameteroverinsulation,diameterover insulationscreen,numberandsizeofneutralconductorsortapedetails(thickness,width&lap type)anddiameteroverthejacketarethedefiningdata.Otherimportantdataare:weight/1000

ftlength,sizeofreelsandlength/reel.Theinsulation/jacketdefiningparametersare:beforeand afteragingtensilestrengthandelongation,hotcreepelongation/set,dielectricconstant, capacitance(SIC)duringandafterthestabilityperiod,insulationresistanceconstant,water absorptionproperties.Thelastsetofdefiningparametersarethecurrentlevelsatthenominal voltageunderthedifferentoperatingconditionswhicharefunctionof:thelayoutandproximity ofcurrentcarryingcables,themethodoflaying/pullingofcables,provisionoffutureadditional loadswiththeircorrespondingmaximumallowablevoltagedropandfinallythemaximum acceptabletemperaturerise&durationforthecableinsulatingmaterial. 4)Whatarethefactoryandsiteteststobeperformedoncables? Thedifferenttypesofteststhatareperformedoncablesatthefactoryare:partialdischarge,DC resistanceofcentralconductor,AChighvoltagedielectricwithstandability,DChighvoltage withstandability,insulationresistance,physicaldimensionsofcablecomponents,coldbend,low temperatureimpact,jacketintegrity,waterpenetrationandhightemperaturedriptestforthe strandfill(ifapplicable).Forconductorshieldthetestsare:volumeresistivity,elongationat rupture,voidandprotrusions,irregularitiesverification.Fortheinsulationare:tensilestrength (agedandunaged)/elongationatrupture(agedandunaged)/dissipationfactor(orpower factor)/hotcreep(elongationandset)/voidsandcontamination/solventextraction(ifapplicable). Fortheinsulationshieldare:volumeresistivity/elongationatrupture/voidandprotrusions irregularities/strippabilityatroomtemperatureandat25C/waterboiltest.Forthejacketare: tensilestrength,elongationatrupture(agedandunaged),absorptioncoefficient(ofwater),heat shockanddistortion.Onthecablethefollowingtestsmaybeperformed:structuralstabilityand insulationshrinkbackforcertaininsulationmaterials.Thetestsperformedonsiteare:visual inspection,size/ratingsverificationandD.C.withstandabilitytestsatvoltagelevelbelowthose usedinthefactory. 5)Whatarethedefiningparametersforlowvoltagesecondarycables? Thedefiningparametersforl.v.secondarycablesare:materialofphaseconductor,numberof strands,classofstrand,typeofconductor(ie.concentric,compactorcompressed),conductor size,insulationthickness,overalldiameterpercable,overalldiameterperassembly(ie.triplex orquadruplex),theneutralconductorsize(equaltothephaseorreduced),ifapplicable, insulationandjacketmaterials,jacketthicknessandtheweightperassemblyper1000ftlength. 6)Whatarethedifferenttypesoftransformersfoundindistributionsystems? Thedifferenttypesoftransformersfoundindistributionsystemsare:Power(upto10MVA) liquidfilled(oil),power(over10upto100MVA)oilfilledwithradiators/fans(oneor2sets), singlephasedistributiontransformers/oilfilled(withorwithoutradiators/fans)upto500KVA, threephasedistributiontransformers/oilfilled(withorwithoutradiators/fans)upto1.5MVA, drytypepowertransformers/3phase300KVAto2MVAorsiliconefilledorepoxyresin insulatedforindoorinstallations.Alloilfilledtransformersareinstalledoutdoorunlessa speciallayoutwithfireproof(resisting)materialandappropriatebarriersareused,thenindoor installationispossible.Distributiontransformerscanbeofthepolemounted,vaultor padmountedtype.Theprimaryvoltageofpowertransformerscanbeashighas750KV,though

themostcommonare345KV,220KV,115KV,fordistributiontransformersashighas72KV thoughthemostcommonare34.5,25KV(27.6KV),15KV. 7)Whatarethedifferenttypesofoverheadswitches,padmountedswitchgearandthoseof lightninigarresters? Thedifferenttypesofoverheadswitchesare:eithersingleorthreephase,eithermanually operatedorelectric/manualoperated,eitherlocalcontrolorremote/localcontrol,oilinsulated orairorSF6.Thedifferenttypesofpadmountedswitchgearare:eithermanuallyor manually/motoroperated,controlledlocallyorlocally/remotely,airoroilorSF6/vacuum insulated,protectivedevicesareeitherfusesorelectronicdevices.Theconfigurationwill, generally,havefourcompartmentswithanycombinationoffuseorinterrupter,switch,solidor emptycompartment.Thedifferenttypesoflightningarrestersare:station,intermediate, distribution(heavyduty,normalorlightduty)andmayberiserpoletype. 8)Whatarethestandardsthatgoverndistributiontransformers?Howaredistribution transformersdefined? Thestandardsthatgoverndistributiontransformersare:CSA"Singlephase&threephase distributiontransformers"Std.C2,CSA"Drytypetransformers"C9,CSA"Guideforloading Drytypedistributionandpowertransformers"C9.1andCSA"Insulatingoil"C50.The distributiontransformersaredefinedasfollows:thevoltageratings(insulationclasslevelof primaryh.v.winding,theprimaryandsecondarywindingsratedvoltage),shortcircuit capabilityforafaultonthebushingsofthetransformer(currentvalueanditscorresponding duration),dielectrictestvalues(appliedvoltagefor1minute,fullwaveandchoppedBILand timetoflashoverforthechopped),outdoortransformerbushingsratings(definedbytheir insulationclass,60HZ1minute/dry,10second/wetdielectricwithstandability,thefullwaveand choppedBIL),audiblesoundlevelsandinducedvoltagetests. 9)Howarewoodenandconcretepolesdefined? Thewoodenpolesaredefinedasfollows:theclass(1to74500LBto1200minimumhorizontal breakingloadwhenapplied2ft.frompoletop),theminimumcircumferenceatpoletoplevel (27"to15"),lengthofpole(25to110ft,generally),minimumcircumferenceatthegroundlevel (distancefrombutt),thewoodspecies(WesternRedCedar,SouthernYellowPine,DouglasFir, WesternLarch),thetreatmentagainstattackfromfungiandinsects(eg.creosoteoil,ammonical copperfattyacid,pentachlorphenolorchromatedcopperarsenates)andtheweightperpole. Theconcretepolesaredefinedaccordingly:ultimateload(classAtoJ,600LBto4500LB, respectively),thelength,themanufacturingprocess(regularorprestressedclass),thesteel reinforcingrods(cage)tensilestrength,thediameter,theracewaydiameter,spacingand diameterofholesinthepole,groundingbars(galvanizedorcoated)surfacetreatment. 10)Whatarethedifferentapplicationsofoilswitchesandwhataretheirdefining parameters? Thedifferentapplicationsofoverheadoilswitchesinutilitydistributionsystemsare:general purposeforinductiveandresistiveloads&capacitor(capacitivecurrentswitching).The definingparametersare:theratedmaximumvoltage,thebasicimpulselevel,thedielectric

withstand,continuouscurrent,inductiveloadswitching,capacitiveswitchingcurrent,making current,momentarycurrent,shorttimecurrentrating;forthecontrolcircuit:nominalandrange ofoperatingvoltage,tripcoilcurrent.Theweight,dimensions,oilvolumeandspeedof operationfortheswitcharealsoimportantdefiningdata.Theothertwodevicesthatmayuseoil astheswitchingmediumarethesectionalizesandreclosers. 11)Howareoverheadairswitchesclassified? Thefollowingistheclassificationoftheairinsulatedswitchesaccordingtotheirbreakingtype: sidebreakswitches,verticalbreakanddoublebreak.Thedifferenttypesofmountingsforsuch switchesare:upright,vertical,triangular,tieredoutboardmountingandpedestal.Theinsulators oftheswitchmaybeepoxyorporcelain,thebaseisinsulatedorsteel. 12)Howarepadmountedswitchgeardefined? Padmountedswitchgearcanbedefined(specified)accordingly:theinsulatingmaterialusedi.e. airinsulated,oilorgas,thenominalvoltageclass,maximumoperatingvoltage,thebasic impulselevel,thecurrentratingsforthedifferentsidesi.e.continuouscurrent,loadinterruption (resistive,inductiveincludingnoloadtransformermagnetizingandcapacitiveincludingcable charging),momentary,faultclose,thedimensionsofthegear,theopeningforthecableentry, propertiesofsteelwork(likethicknessgauge,surfacetreatmentandfinish),theweightandthe assemblyvoltagewithstandabilitytests(A.C.andD.C.).Thespeedofoperation(currenttime curves)forthefusesorprotectivedeviceshadtobespecified. 13)Whataretheimportantparametersbywhichlightningarrestersaredefined? TheimportantparametersbywhichL.A.aredefinedare:dutycyclevoltage,impulsetestcrest voltage,powerfrequencyvoltage(dryandwetforoutdoorinstallations),impulsecurrent rating,maximumcontinuousoperatingvoltage,switchingsurgescapability,highcurrent/short timeandlowcurrent/longdurationrating,materialofhousing,designofinternalsie.gappedor gaplesselements(nonlinearresistancematerial). 14)Howwouldcopperconductorsbedefined? Theconstructionofcopperconductorsisdefinedasfollows:crosssectionarea,classof conductor(indicationofdegreeofflexibility),numberofwires,diameterofwire,tensile strength,elongation,diameterofconductor,type(concentriclays,compactorcompressed)and weightper1000ft. 15)HowwouldACSR(aluminumconductorsteelreinforced)andASC(aluminum strandedconductor)bedefined? Thedefiningparametersforaluminiumconductorsteelreinforceddesignsare:theAlarea,the totalconductorarea,steel/Alarearatio,numberofAlwires,diameterofAlwire,areaofsteel wire,diameterofsteelwire,diameterofcore(steel),diameterofconductor,tensilestrength, AWGsize,totalconductorweightper1000ft.andtheratioofAlweighttothetotalweight.The definingparametersforaluminiumstrandedconductorsare:thealuminumconductorarea,the quantity(number)ofAlwires,diameterofeachwire,thediameteroftheconductor,thetensile strength,theelongationandthetotalweightofconductorper1000ft. 16)HowwouldAASC(aluminumalloystrandedconductor)andselfdampening/compact

ACSRbedefined? ThedefiningparametersforAluminiumalloystrandedconductorsare:Alalloyareaandthe equivalentAlarea,numberofAlalloywire,diameterperwire,overalldiameterofconductor, AWG/KCMIL,weight/1000ft,tensilestrengthandelongation.Thedefiningparametersforself dampeningconductorsandcompactACSRare:aluminiumarea,totalconductorarea,steeltoAl area(ratio),numberofAlwires,numberofsteelwires,core(steel)diameter,overallconductor diameter,conductorweight/1000ftlength,ratioofAlweighttototalweight,tensilestrength andelongation. 17)Whatarethedifferenttypesofcablesplicesandterminations? Thedifferenttypesofcablesplicesare:tapped,heatshrinkableandcoldshrinkable.Themajor componentsofaspliceare:cableadapters,splicehousing,conductorcontact,conductiveinsert, retainingrings/tube,interferencefitandgroundingeye.Thedifferenttypesofcable terminationsare:thefullytaped,mouldedstressconeandtape,onepiecemouldedcable termination,porcelainterminators,heatshrinkablesandpotheads. 18)Whatarethedifferenttypesofconnectorsandelbows? Thedifferenttypesofconnectorsare:themechanical(forAland/orCuconductors),the compression,thewedge(toconnectmainconductorstotaps),hotlineclamps(themain overheadtoequipmentconnection)andthestirrups(wedgedorbolted).Thetwotypesof separableconnectors(elbows)arethedeadbreakandloadbreak.Themajorcomponentsof elbowsare:theconnector,themouldedinsulatingbody,cableadapter,thetestpoint,thesemi conducingshield,semiconductinginsert,groundingtabsthepullingeye,theprobe(forload break,itisfieldreplaceablewithabelativematerialarcfollower). 19)Whatarethedesigntestsperformedontheseparableconnectors? Thedesigntestsperformedontheelbowsare:partialdischargeinceptionandextinctionlevels (corona),withstandpowerfrequencyvoltagecapability(a.c.andd.c.),impulsevoltage withstandlevel,shorttimecurrentrating,switchingtest,faultclosurerating,currentcyclingfor insulatedanduninsulatedconnectors,cablepulloutfromelbow(connector),operatingforce, pullingeyeoperation,testpointcappullingtest,shieldingtest,interchangeability,accelerated thermalandsealinglife,testpointcapacitance(voltagepresenceindication)test. 20)Whatarethedifferenttypesofinsulators,theirmaterialandcharacteristics? Thedifferenttypesofinsulatorsare:thepin,thesuspensionandthepost(verticaland horizontal).Thedifferentinsulatorsmaterialsare:porcelain,glass,fibreglass,polymerand silicone.Thepropertiesofinsulatorscanbebroadlyclassifiedinto:mechanical,electrical, environmentalandmaintenance.Themechanicalcanfurtherbeclassifiedinto:differentloads theinsulatorsissubjectedtoduetoweightsofsupportedcomponents,shortcircuit,ice,etc. (normal,design,cyclic,torsional,overloadsexceptional),safetyfactors,singleormultiple insulatorassembliesandagingeffectonstrengthofinsulator.Theelectricalparametersdefining theinsulatorsare:BIL,powerfrequencywithstandability(dry,wetandflashoverlevel),leakage distance,powerarcseffect,performanceundersteepfrontvoltagewave,clearancesand performanceundercontamination.Theenvironmentalcharacteristicscanbefurtherbrokedown

into:insulatorageingunderultravioletraysanddryarcing,typeofcontamination,radio interferencevoltage,washingrequirements,corrosiveenvironmentsandtemperaturerange. 21)WhatarethefunctionsofDAC(distributionautomationandcontrol)?Sketchthe typicalundergrounddistributionarrangementsandtheoverheaddistributionsystem. Distributionautomationandcontrolfunctionscanbeclassifiedinto:loadmanagement,real timeoperationalmanagementandremotemetering.Thefirstfunctionmaybesubclassifiedinto: discretionaryloadswitching,peakloadpricing,loadsheddingandcoldloadpickup.The secondfunctionissubclassifiedinto:loadreconfiguration,voltageregulation,transformerload management,feederloadmanagement,capacitorcontrol,faultindication/location/isolation, systemanalysis/studies,state/conditionmonitoringandremoteconnect/disconnectofservices. Fig.4showstheundergroundarrangementsandfig.5showsthetypicaloverheadsystem.

22)WhatarethemajorinformationobtainedfromadistributionsystemSCADA?Showa blockdiagramofthemajorcomponentsofaSCADA(systemsupervisorycontrol&data acquisition).Sketchadiagramtoshowatypicalautomateddistributionsystemwithpower andcommunicationlines. ThemajorinformationobtainedfromaSCADAinapowerdistributionsystemare:indications (eg.statechangelikeopeningorclosingofcircuitbreakers,loadbreakswitches,reclosures, disconnects,operationofarelayorfaultindicators)ofeventsoralarms,levels(eg.oillevel,tap changerposition,readingfrompressuregauges),pulses(eg.energymetercounters), measurands(eg.current,voltage,powerreading,temperatureofoilorwindings,leakage current).Fig.6showsatypicalSCADAandfig.7showsasinglelineforanautomatedsystem.

23)WhatarethebasicmodulesinaPLC(programmablelogiccontroller)system?Sketch afrontplateof2ofthebasicmodules.Sketchablockdiagramshowingtheinterrelationof themajormodules. ThebasicmodulesofaPLCsystemare:theprocessor,theinput/output(theycanfurtherbe classifiedintodigitalandanalog),processcontrol(proportional/integral/derivative),stepper motor,interfacemodules(theycanbefurtherclassifiedinto:localandremote,localandremote transfer,network,networktransfer,multimedianetworkinterface,peripheraldevices(they includeloader/monitor,processcontrolstations,CRTprogrammers,handheldprogrammers, tapeloader).Fig.8showsthefrontplatesofthelocalandremoteinterfaceunits,fig.9showsa typicalblockdiagramincludingtheracks,interface/input/output/networkinterfacemodules.

24)Foranoverheadconductorwithsize=556.5MCM,aluminumcorewith19strands andoperatingvoltageof25KV,calculatethereactanceat60c/sand50HZper1000ft,the resistance(AL1350)per1000ft,thecapacitance,chargingcurrent/1000ftandsurge impedance. Given:Conductordetails:556.5MCM/19strands/Al1359. Nominalvoltage:25KV,frequency:60&50c/s,length1000ft,conductordiameter:.855" (fromtables),area:.437inch2(fromtablesor7.854(1000)(556.5)/(10+7)=.437in.2) L=(2)/(10+7)[ln(d/r')]H/m=(2/10+7)ln12(2)/.855(.7788)(at1ftspacing)

L=7.17(1000)/3.28(10+6)=2185/10000000H/1000ft. XL=2pi60L=.082OHM@60c/sandXL=.068OHM@50c/s,wherepi=3.141592654 R=.0927microOHMft(1000)/.437/(12)(12)=.0305ignoringskineffect,takingintoaccount

approximateskineffectthenR=.0305(1.15)=.035OHM

C=1/(10+9)(18)(lnd/r)F/m=1/(10+9)(18)(ln12/.855/2)=.0166/10+9 C=.0166(1000)/3.28(10+9)F/1000ft=5.08(109)farad/1000ft XC=1/2pifC=5.22(10+5)OHM, chargingcurrent=25000/1.732(5.2)(10+5)=.028amp/1000ft

Z=surgeimpedanceundertheseconditions=(L/C).5)=207OHM 25)ForanundergroundXLPEcable,size=250MCM,aluminum1350corewith37 strandsandoperatingon25KVsystem,calculatethereactanceat60&50HZper1000ft, resistanceper1000ft,capacitance,surgeimpedance,chargingcurrent/1000ft,speedof propagationofthewaveandtheinsulationresistance. Given:cabledata:250MCM,XLPE,AL1350,37strands,25KV,1000ftlength,conductor dia.:.575in,area=.196in2),dia.overinsulation:1.16",e=3.5,whereeisthedielectric constant L=(2/10+7)[ln12(2)/(.575)(.7788)=2427/(10+7)H/1000ftat1ftspacing XL=.092OHM@60c/sand.076OHM@50c/s R/1000ft=.0927(1000)(144)/.196=.068OHM(1.15)=.078OHM

C=3.5/)10+9)(18)(ln1.16/.575)=.277/(10)F/m(1000)/3.28=84/(10+9)F/1000ft Latinsulationneutralorsheath=2ln1.16/.575(.7788)/(10+7)=2(107)H/m Chargingcurrentfor1000ftcablelength=(25000/1.732)(31578)=.46amp. Z=surgeimpedance=(L/C).5)=27OHM,XC=1/2piC60=31578OHM/1000ft v=speedofpropagation=(1)/(LC).5)=1.34(10+8)m/sec. Volumetricinsulationresistance=(ra)(ln1.16/.575)/(2pl)(12)(2.54),whereraistheresistivity orspecificresistanceofthedielectric assumera=6(10+14),Rvolumetric=6(10+14)(.7)/191511=2193MegaOHM/1000ft. 26)Iftheoverheadconductorandtheundergroundcableofproblems24&25are connectedinseriesandavoltagewaveof25KVistravellingthroughtheoverheadportion, calculatethereflectedandrefractedpowersatthejunctionpoint. Zline=207,Zcable=27,KV=25 reflactedvoltage=(27207)25/1.732(207+27)=11.1KV refractedvoltage=(2)(27)(25)/1.732(207+27)=3.33KV refractedpower=3(Vph)(Vph)/Zcable=3(3.33)(3.33)/27=1232KW reflectedpower=3(11.1)(11.1)/207=1785KW 27)Providethedifferentialandgasaccumulation/suddenreleaseprotectiontoa100MVA powertransformer,220/25KVwith+/16%tapchanger.Assumethattheavailablerelays haveapickupsettingbetween2050%ofrelayratingwithanadjustableslopeof2050% andanotherwithfixedslopeandrestrainedpickupbetween20and50%and

unrestrainedpickupof8,13,20xrelaynominalcurrent.Thepressuregasrelayshavetwo settings,forthetrip5.217.2KPaandforthealarm200400CC.Thetapchangergas pressuretripcanbesetbetween35390KPa. Iexcitation=5%offullloadprimary,C.T.error=2.5%,relayrating=5A,C.T.primary current=1.5xfullloadcurrentoftransformer. Iprimary=100(1000)/(220)(1.732)=262A Isecondary=262x220/25=2300A Usinga1200/800/200:5AC.T.ontheprimaryside(theC.Tsaredeltaconnected),3500:5A C.T.onsecondaryside(theC.Tsarewyeconnected)ofthepowertransformer.Turnsratioof C.T.onprimarywinding=800/5=160,onsecondary=3500/5=700.Relaycurrentdueto primaryC.T.atf.l.=(262/160)1.732=2.8amp,relaycurrentduetosecondaryC.T.atf.l.= 2300/700=3.28amp,relaycurrentratio=3.28/2.8=1.17.Mismatchatmidpointchangerand fullload=17%. At220+16%=255KVtap,maintainingsecondaryvoltageat25KV,primaryfullloadcurrent =100(1000)/255(1.732)=226amp,relaycurrent=226/160(1.732)=2.45amp.,voltageof25 KVonthesecondarywhileprimary=22016%=185KVprimaryfullloadcurrent= 100(1000)/185(1.732)=312amp.,relaycurrent=312/160(1.732)=3.4A Mismatchfor+16%=3.28/2.45,mismatchfor16%=3.28/3.4whichare34%and4%, respectively.Themaximummismatch=34%,add6%assafetymargin.Thustheslope adjustment=40%(rangeis20to50%).Thepickuplevelunderfullloadcurrent= inacccuracies+escitingcurrent+allowanceforthelimitedrestraintatemergencyloadthrough currents=2.5(5/100)+(1.732)(5(262)/160)(100)+(3.282.45)=.125+.14+.83=1.1amp,the pickupsetting=40%(5)=2A(range20to50%). Theunrestrainedinstantaneoustripingcurrent=13x5=65amp.secondaryrelaycurrent. VERIFICATIONS:

Assuminga100MVAbaseand220/25KVbase,Ibase(@primaryside)=100/1.732)(220)= 262amp.,Ibase(@secondaryside)=2300amp. Assuminganinfinitesource,11%impedancetransformer,a3phasefaultonthesecondaryof thetransformerbeyondthedifferentialprotectionzonewillproduce9p.u.faultcurrent(1/.11), Iprimary=2358amp.,Isec.=20700amp.Thecurrentfromtheprimarysideintotherelay= (1.732)2358/16025.5amp.,fromthesecondaryside=20700//700=29.6amp.Amismatchof 29.6/25.5=16%. Assumingthetapchangertobeat220KV+16%=255KVandtheimpedance=14%,theshort circuitfaultcurrentofa3phasefault=1/.14=7.16p.u.,fullloadprimarycurrent=232amp., SCContheprimaryside=1661A,SCConthesecondaryside=16468A,relaycurrentfrom primaryside=1661(1.732)/160=18A,relaycurrentfromthesecondaryside=16468/700= 23.5,themismatch=30%. Assumingthetapchangerat220KV16%=185KVandtheimpedance=8%,a3phasefault

current=1/.08=12.5p.u.,primarycurrent=312A,SCConprimaryside=3900A,SCCon secondaryside=28750A,relaycurrentfromprim.side=42.2A,relaycurrentfromsec.side= 41.1A,mismatch=3% GASRELAYS: Maintankalarm=200cc,maintanktrip=17KPaabovestaticheadatrelaylevel,tapchangertrip= 100KPa. SUMMARY: Inthischapter,thedefiningparameters,classifications,testsandtypicalconfigurationsofdistribution systemscomponentswerepresented.ThegeneralpropertiesofmediumvoltageEPR&XLPEcables weregivenplusfactory&sitetests.Forlowvoltagesecondarycables,thedefiningparameterswere listed.Fortransformers,abroadclassificationwasgiven.ThedefiningparametersandtheCSA standardsthatgoverntheratings,design,manufacturingandtestingofdistributiontransformerswere presented.Othercomponentsfoundinoverheadandundergrounddistributionsystemswerecovered fromtheirtypesanddefiningparameterspointofview.Thesecomponentsare:lightningarresters, conductors,terminations,splices,connectors,elbowsandinsulators.Distributionsystemsautomation andSCADAwerepresentedbycoveringthefunctionsanddatacollectedfromsuchsystems.Typical systemsweregiventoclarifythistopic.ThemajormodulesfoundinatypicalPLC(programmable logiccontrollers)installationwerepresented.Thenumericalexamplesattheendofthischaptershowed howthelineandcableconstants(inductance,capacitance,resistance,inductive/capacitivereactances, surgeimpedance,chargingcurrentandpropagationspeed)andtheeffectofthesurgeimpedanceon travellingwavesarecalculated.Theyalsodemonstratedamethodtoselect/adjust/verifythesettingsof relays(differential&gas)usedintheprotectionofpowertransformers. REFERENCES: 1. 2. 3. 4. 5. 6. 7. Wildi,T"Electrotechnique",LesPressesdel'UniversitLaval. CSA,"CanadianElectricityCode",Part1,stdC22.1. CSA,"Singlephase&threephasedistributiontransformers",stdC2. Gonen"Electricpowerdistributionsystemsengineering",McGrawHill. Kurtz,"Thelineman's&cableman'sHandbook",McGrawHill. Perry,"ChemicalEngineershandbook",McGrawHill. ICEAS66524,"Crosslinkedthermosettingpolyethyleneinsulatedwire&cableforthe transmission&distributionofelectricalenergy". 8. ASTM2.03,"Nonferrousmetalproductselectricalconductors. 9. Brady,"Materialshandbook",McgrawHill. 10.Kheir,"ComputerProgrammingforPowerSystemAnalysts",Kheir.

Home page of VePi

Lesson3:Switchgear,circuitbreakers,MCCSandcontactors. 1) Whatarethedefiningparametersforlowvoltagecircuitbreakers? 2)Whatarethedefiningparametersformediumvoltagecircuitbreakers? 3)Whatarethedifferenttypesofinterruptingmediausedinm.v.c.b.?Whatarethecommon propertiesforsuchquenchingmedia? 4)Whatarethedifferenttypesofswitchgearassembliesandwhatarethesubclassificationof eachtype?Whatarethestandardsgoverningswitchgearassemblies&circuitbreakers?What arethetypesofbatteriesfoundinsuchequipment?Giveabriefdescriptionofeachtype. 5)Whatarethedefiningparametersforlowvoltagealternatingcurrentmagnetic contactors/starters? 6)Whatarethedefiningparametersofl.v.combinationstarters? 7)Whatarethedefiningparametersforfullvoltage2speedstarters? 8)Whatarethedefiningparametersoflowvoltage,reducedvoltagestarterunits? 9)Whatwouldatabledefiningthemotorprotectioncircuitbreakershaveasheadings? 10)Whatwouldatabledefiningmotorprotectionfuseshaveasheadings? 11)Whataretheheadingsofatabledefiningm.v.controllers? 12)Whatarethegeneralpropertiesofconstructionalandstainlesssteels? 13)Whatarethedifferenttypesofswitchboardinstrumentsandthedifferentmechanisms?What arethedefiningparametersforsuchdevices? 14)WhatarethedefiningparametersforKWH,KVARandsolidstatemeters?

15)Whatarethedifferentconstructionsofprotectiverelays?Givethedefiningparametersfor thedifferenttypesofthefollowingrelays:overcurrent,over/undervoltage,differentialand distance. 16)Asolvedproblemregardingthesizingofthebreakingdevicesofaswitchgearassembly. Lessonsummary References 1)Whatarethedefiningparametersforlowvoltagecircuitbreakers? Thedefiningparametersoflowvoltagecircuitbreakersare:theratedvoltage,thecircuitbreaker currentrating,symmetricalinterruptingcapacity(withinstantaneousanddelayedintegral protectiverelays),closeandlatchratingforasecond,thesensorscurrentratio,thefunctions ofprotectionontheintegralovercurrentprotectivedevice,electrically/manuallyoperatedor manuallyonly,theweightanddimensionsofcircuitbreakers,theindicatorsoftheintegral protectivedevice(ifavailable).Forelectricallyoperatedbreakers,therangeofoperating voltagesandcurrentsplusthenominalvaluesforthesolenoids/motors/tripcoilsareimportant parameters,too. 2)Whatarethedefiningparametersformediumvoltagecircuitbreakers? Thedefiningparametersofmediumvoltagecircuitbreakersare:thevoltageratings(nominal, maximumandminimum),the3phaseMVAbreakerrating,theratedcurrent,theKfactor (Max./Min.ratio),symmetricalinterruptingratings(atmaximum,nominalandminimum voltage)inKA,theasymmetricalfactor,theshorttimerating,thecloseandlatch,theinsulation level(powerfrequency,impulselevel),theweight,thedimensions,theinterruptingmedium,the TRVcapability,anyarcingmediummonitoringdevices,circuitbreakerclosingtime,tripping time,interruptingtime,springchargingtime,thecontrolvoltages(nominalandrange),the springchargingcurrent,closecoilcurrentrequirement,thetripcoilcurrentratingandsurges switchingcapabilities. 3)Whatarethedifferenttypesofinterruptingmediausedinm.v.c.b.?Whatarethe commonpropertiesforsuchquenchingmedia? Theinterruptingmediausedinmediumvoltagecircuitbreakersare:air,oilSF6andvacuum. Thegeneralpropertiesoffluidsusedinarcextinguishingchambersinm.v.c.b.are:high dielectricstrengthofthegasorliquid,thermallyandchemicallystable,noninflammable,high thermalconductivity,lowdissociationtemperature,shortthermaltimeconstant,shouldnot produceconductingmaterialduringarcing.Gasesusedsofarinm.v.c.b.canbeclassifiedinto simple(air)orelectronegative(SF6). 4)Whatarethedifferenttypesofswitchgearassembliesandwhatarethesubclassification ofeachtype?Whatarethestandardsgoverningswitchgearassemblies&circuitbreakers? Whatarethetypesofbatteriesfoundinsuchequipment?Giveabriefdescriptionofeach type. Thedifferenttypesforswitchgearassembliesare:indoorandoutdoor.Thesubclassificationfor theindooris:standard,sprinklerproof,arcproof,dustproof,seismicproof,metalclad constructionvs.metalenclosed,enclosurewithorwithoutadriphood;fortheoutdooris:walk

in,walkinwithworkingarea,walkindoublerow,nonwalkinwithorwithoutworkingarea, enclosureforcable/busentryortransformerthroat,enclosurewiththermalinsulation/isle heatersandfinallyindoorcubicledesigninstalledinanoutdoorhouse. Thestandardsthatgoverncircuitbreakers/switchgeardesigntestingandapplicationare:ANSI C37seriesincluding.09"TestprocedureforA.C.highvoltagecircuitbreakersratedona symmetricalcurrentbasis",.04"RatingstructureforA.C.highvoltagecircuitbreakersratedon asymmetricalcurrentbasis",.06"PreferredratingsandrelatedrequiredcapabilitiesforA.C. highvoltagecircuitbreakersratedonasymmetricalcurrentbasis",.20"Switchgear assemblies",IEC56"HighvoltageA.C.circuitbreakers",IEC60series"Highvoltagetest techniques",IEC694"Commonclausesforhighvoltageswitchgearandcontrolgear", C22.2#31"switchgearassemblies"andCAN3C13"Instrumenttransformers.". Thedifferenttypesofstationarybatteriesusedinconjunctionwiththeseequipmentare:lead acidandnickelcadmium.Thefirsthasthreepossibilitiesofpositiveplateswhichare:the pasted,multitubularandplantetype.Thenegativeplateswillbeofthepastedtype,thegridfor theplanteandmultitubularismadeofleadantimonyandthatforthepastedismadeofeither leadantimonyorleadcalcium.Theactivematerialinthe+veplateisleadoxideandintheve plateisspongelead.Theelectrolyteisasolutionofdilutedsulphuricacidwithspecificgravity ofapproximately1.2.Forthenickelcadbatteries,theplatesmaybeofthepocketorthesintered type.Theactivematerial(nickelhydratedforthe+veplateandcadmiumspongefortheve)is placedinnickelplatedsteelholders.Theelectrolyteisasolutionofpotassiumhydroxidediluted inwaterwithaspecificgravityof1.16to1.19at25C. 5)Whatarethedefiningparametersforlowvoltagealternatingcurrentmagnetic contactors/starters? Thedefiningratingsforlowvoltagealternatingcurrentmagneticcontactors/startersare:the NEMAsize,thevoltagerating,themaximumHPforsinglephaseandthreephasemotors(for bothnonplugging/nonjoggingandplugging/joggingapplications),thecontinuouscurrentrating ofthecontactor/starter,theservicelimit,transformerswitchingcapabilityratingforsingleand threephaseapplications,thecapacitiveswitchingcapability(involtandKVAR),the dimensions,theweights,theoverloadprotectiveelementtypeandrating. 6)Whatarethedefiningparametersofl.v.combinationstarters? Thedefiningparametersoflowfullvoltagecombinationstarterunits:thestartersize,the maximummotorHPatthedifferentstandardvoltages(200v,230,460and575v),whetherthe unitisreversingornonreversing,thefuseorcircuitbreakersize(usedasaprotectionagainst shortcircuitorprotection/loadbreakdevice),thesizeoftheunitininchesorspacefactor,the weightoftheunit,methodofattachmenttoriserbusbarsofMCC(boltonorplugin)andsize plustypeofmotoroverloadprotectionelement/relay. 7)Whatarethedefiningparametersforfullvoltage2speedstarters? Thedefiningparametersforfullvoltage2speedstarterunitsare:thestartersize,theHP (maximum)atthedifferentnominalvoltages,thecircuitbreakerorfusesizefortheshortcircuit protection,thedimensionininchesorspacefactorforthe1windingand2windingmotor

starterunit,unitweight,methodofattachmenttoMCCandthetypeplussizeofo/cprotection device. 8)Whatarethedefiningparametersoflowvoltage,reducedvoltagestarterunits? Thedefiningparametersoflowvoltagereducevoltagestarterunits(applicabletopartwinding andautotransformerunits):thestartersize,themaximummotorHPatthedifferentrated voltages,thecircuitbreakerorfuserating,thedimensionsorspacefactorfortheunits,the weight,thesizeplustypeoftheo/lelement,theinstallationmethodintheMCC. 9)Whatwouldatabledefiningthemotorprotectioncircuitbreakershaveasheadings? Thetablewillhavethefollowingheadings:3phasemotorHP,themotorfullloadcurrentatthe differentnominalvoltages,thecircuitbreakercontinuouscurrent,thedifferentadjustments(eg. 7x/11x/13x),theweightanddimension,theadjustablerange. 10)Whatwouldatabledefiningmotorprotectionfuseshaveasheadings? Thefusesformotorprotectiontablewillhavethefollowing:themaximummotorHPrating,the motorfullloadcurrentrating,thefusesizeforthedifferentvoltageclasses,thefusetype(50KA interruptingfuse,HRC200KAI.c.,codefuse10KAorsizeLover600a200KA),thefuse weight. 11)Whataretheheadingsofatabledefiningm.v.controllers? Thetableforamediumvoltagecontroller(contactorandfuse)willhavethefollowingheadings: thecontactormaximumcontinuouscurrent,theinterruptingcapacity(atthespecifiedKV),the designation,thevoltageratingandrange,theinterruptingcapacityofthefuse(inKAandMVA @theratedvoltage),themaximumHPmotorratingforthemotordesign/p.f./voltage/controller currentrating,thedielectricwithstandvoltage,thecontrollertype(fullvoltage,reversingvs nonreversing,reducedvoltageautotransformervsreactor).Them.v.fusesforcontrollerscan bedefinedwhenthefollowingvaluesaregiven:themotorlockedrotorcurrent,motorfullload currentxservicefactor,themaximumcontinuouscurrentratingofthefuseinsidethe compartment,thefusesize,thepeakcurrentletthroughcharacteristics. 12)Whatarethegeneralpropertiesofconstructionalandstainlesssteels? Themechanicalpropertiesofconstructionalsteelsare:theASTMdesignations,thethickness range,yieldpoint,elongationasapercentofthelength(eg.in8inches),tensilestrengthand weldability.Thoseforstainlesssteelare:A1SIdesignation,condition,.2%yieldpoint, elongationin2incheslength,tensilestrengthandareareduction. 13)Whatarethedifferenttypesofswitchboardinstrumentsandthedifferent mechanisms?Whatarethedefiningparametersforsuchdevices? Thedifferenttypesofswitchboardinstruments:voltmeters,wattmeters(singlephaseand polyphase),varmeters,powerfactormeters,frequencymeters,ammeters.Thedifferent mechanismsare:tautbandsuspension,repulsionvane,electrodynamic,D'Arsonval/zenerdiode. Thedefiningparameters:impedance,inputresistance,inductance,voltampere/W/RVA/p.f.of mechanism(burden),mechanismtype(selfcontainedortransformer),instrumenttransformer ratio,scaleandunits/scaledivision. 14)WhatarethedefiningparametersforKWH,KVARandsolidstatemeters?

ThedefiningparametersofKWHmetersare:typeofmeterandnumberofelements,connection method,weight/dimension,burdendataforeachtype/elementsnumber(phase,potentialcircuit andcurrentcircuit),KVAattachmentdata(meter,volt,scale/multiplier,amprange),disk constantWH/diskrevolution,registerratio.ThoseforKVARare:burden(potentialandcurrent circuits),weightanddimensions(forthedifferentdesigns),temperaturerise,ratingsand enclosuresforthedifferenttypes/numbersofelements.Thoseforsolidstatemetersare: potentialinputratings(inputvoltage,impedance,burden,overloadcapability,currentinput ratings(burden,inputcurrentandimpedance,overload),weight&dimensions,controlpower requirements,communicationcapability(protocol,baudrate,standards),measuredparameters (measurands). 15)Whatarethedifferentconstructionsofprotectiverelays?Givethedefining parametersforthedifferenttypesofthefollowingrelays:overcurrent,over/undervoltage, differentialanddistance. Relayscanbeclassifiedbasedontheirconstructionintoelectromechanical(magneticinduction, magneticattraction,thermalandD'Arsonval),solidstateandmicroprocessor/digitalbased. Thedefiningparametersforelectromechanicalbasedo/crelaysare:weightanddimensions, typeofrelaytimecurrentcharacteristicscurves(inversedefiniteminimumtime,shorttime, veryinverse,extremelyinverse),currenttaprange,timedialrange,operatingtime,burdenand thermalratings(continuouscurrent,1sec.ratingandpowerfactor,attapsetting,at3timestap, at10timestapandat20timestap).Thoseforo/csolidstaterelaysare:weightanddimensions, currentrating,frequency,d.c.supplyvoltageandburden,burdenonC.T.,settingrangeforthe instantaneousandtimedelayfunctions,timemultipliersetting,operatingtimesfortimedelay andinstantaneousfunctions.Theparametersforthemicroprocessorbasedare:weightand dimensions,ratedcurrent,settingrange,ratedcurrentforthegroundfaultunitandthesetting range,operatingtimes,burden,overloadcapacity,controlpowervoltageandburden,resetting timesandcontactsratings. Thedefiningparametersfortheover/undervoltageelectromechanicalrelaysare:theweightand dimensions,thecontinuousinputvoltagerating,theshorttime(eg.2minute)voltagerating,the taps'range,burden,timedialrange.Those,forthesolidstateare:weightanddimension,input voltageratings,pickuprange,dropoutsettingrange,timedelaysetting(pickupanddropout), control(auxiliary)supplyvoltageandrange. Thedefiningparametersforaelectromechanicaldifferentialrelaysare:theweightand dimensions,theapplicationi.e.transformerdifferentialormotororgeneratordifferential protection,numberofphasesi.e.singleorthreephase,numberofoperateandrestraintcircuits, minimumtripcurrent,burden,operatingtime,typei.e.fixedorvariablepercentage(biased) relay,currentinputs. Thedefiningparametersforsolidstatepercentage(biased)relayswithinstantaneoustripping andharmonicsrestraint:weightanddimensionsincludinginterposingrelays(ifany),the currentsinput,overloadcapacity,frequency,interposingC.T.ratio(ifany),burden,operating current,restraintcurrentsettings,unrestrainedcurrentsettingrange,operatetime,resetratio,

orderofharmonicsrestrainedi.e.2ndor5th,auxiliarypowervoltageandpowerconsumption, burdenofoperatingandrestraintcircuits. Thedefiningparametersfortheelectromechanicaldistancerelaysare:theweightand dimensions,characteristicstypei.e.impedance/reactance/admittance/angleimpedance (OHM)/offsetMHO/modifiedimpedance/complex/elliptical/quadrilateral,relayreach,taps, variationinreachandmaximumtorqueangleovertherangeoftaps,burdenoninstrument transformers.Thoseforsolidstaterelays,theparametersare:weightanddimensions,input circuits,burden,controlvoltageandconsumption,characteristicstorque(angle),resetratio. 16)Aunitsubstationisconnectedtotheutilitylinethrougha25KVcircuitbreakerwhich feedsa5MVAtransformer,5%impedance3phase,25KV/600v.Thelowvoltagewinding ofthetransformerisconnectedthrougha600vmainbreakertoalowvoltageswitchgear. Theswitchgearhas3circuitbreakersfeedingeacha400HPmotor,.25reactance,1800 RPM.Afourthcircuitbreakerisfeedinga750KVA,4.5%impedance600/208vandthe lastbreakerinthislineupfeedstheother600/347vloads(2MVA).Forafault(LLL)on themainbus,calculatethefaultcurrentwithandwithoutmotorcontributionandgivethe contributionofeachmotor.Calculatealsothemotorbreakerfaultcurrentforafaulton themotorterminals.Assumeoninfinitesource.Givethebreakers'sizeonthelowvoltage sideoftransformer,giveatypicalunitsubstationlayout.

MVAbase=5,KVbase(primarysideofpowertransformer)=25,KVbase(secondaryside)=.6, Ibase=5(1000)/1.732(.6)=4811amp=fullloadcurrent.Fullloadcurrentonprimaryside= 4811(600)/25000=115amp.Faultcurrentfor3phasefaultonmainbus=1/.05=20p.u.= 20(4811)=96KA(fromsuplyside).

Xmotor=.25(5000/350)=3.5p.u.(assumingmotorp.f.=.85) 3motorscotributionfora3phasefaultonmainbus=1/1.16=.85p.u.=.85(4811=4089amp. Totalfaultcurrent=96+4=100KA Contributionpermotor=.283(4811)=1370amp. ForLLLfaultonmotorterminals,thefaultcurrentthroughthemotorbreaker=2(1.37)+96= 98.7KA. Motorfullloadcurrent=400(746)/1.732(.85)(.9)(600)=375amp.(assumingamotorefficiency of.9) F.L.currentto750KVAtransformer=750(1000)/1.732(600)=722amp. F.L.currenttothe2MVAload=2000/1.732(.6)=1924amp. Forthemainlowvoltagecircuitbreaker: Continuouscurent(framesize)=5000amp.,I.C.=120KA Forthemotorscircuitbreakers(fusedorcurrentlimiting): Continuouscurrent=800Amp,I.C.=100KA,Sensorsratio+400/5amp. Forthe750KVAtransformer(fusedorcurrentlimiting): Continuouscurrent=1600amp.,I.C.=100KA,Sensor=800/5amp. Forthe2MVAload(fusedorcurrentlimiting): Continuouscurrent=2000amp.,I.C.=100KA,Sensor=2000/5amp. Fig.11showsthetypicallayout.

SUMMARY:

Inthischapter,circuitbreakers,switchgearassemblies,startersandcontrollerswerepresented fromthedefinition,standardsandbriefdescriptionpointsofview.Forlowvoltagecircuit breakers,thecoverageincludedtheratingsofthepowerandelectriccontrolcircuits.For mediumvoltagecircuitbreakersandswitchgearassemblies,thecoverageincludedthebreakers interruptingmedia,breakersratings,governingstandards,differenttypesofswitchgear assembliesandtypesofstationarybatteriesfoundinsuchassemblies.Forl.v.starters,the coverageincludedthedefiningparametersforthefollowingdevices:contactors,combination starters(fullvoltage/singlespeed,fullvoltage/twospeed,autotransformer/partwindingreduced voltage),motorprotectionfusesandmagneticelementonlycircuitbreakers).Formedium voltagestarters,thecoverageincludedthecontactorsandfusedefiningparameters.Certain relatedmiscellaneoustopicswerealsocoveredbrieflylikethegeneralpropertiesof constructional&stainlesssteel,switchboardinstrumentstypes&mechanisms,metersdefining parametersandrelaystypes&definingparameters. Thenumericalexampleattheendofthisunitclarifiedtheselectionofbreakersina hypotheticalunitsubstationincludingthecontinuouscurrent,interruptingcapacityandsensors ratioforeachbreaker. References: 1. Wildi,T."Electrotechnique",LesPressesdel'UniversitLaval. 2. IEEE"Recommendedpracticeforprotection&coordinationofindustrial&commercialpower systems"std242. 3. CSA"Switchgearassemblies"stdC22.2no.31. 4. CSA"Instrumenttransformers"stdCAN3C13. 5. Wadhwa,C."Electricalpowersystems",Wiley. 6. Kheir"Computerprogrammingforpowersystemsanalysts",Kheir. Home page of VePi

Lesson4:Powerlinedisturbances. 1) Whatarethedisturbancesfoundinpowersystems? 2)Whatarethesourcesofdisturbancesinpowersystems?Sketch4examplesforthesourcesof disturbances. 3)Whataretheeffectsofsuchdisturbancesonthemajorelementsofpowersystems? 4)Whataretheindicatorsofthequalityofpowerinaplant? 5)Whatarethemethodsusedtoreducethesedisturbances?Sketchtwoofthedevicesusedin reducingthesteadystatedisturbances.Whatarethemajorstandardsthatarepowerquality related? 6)Whatarethemajorhardwarecomponentsinanofficeautomationsystem?Whatarethe majorresponsibilitiesofanoperatingsystem?Whatarethedifferenttypeslocalareanetworks andwhatarethedifferenttypesoftransmissionmediausedwithLANs. 7)Asolvedproblemregardingtheeffectofapplyingcapacitorsinimprovingthepowerfactorof acircuit. 8)Asolvedproblemregardingthequantificationoflightningstrokes. Lessonsummary References 1)Whatarethedisturbancesfoundinpowersystems? Disturbancesfoundinpowerlinescanbeclassifiedintosteadystateandtransients.Steadystate canfurtherbeclassifiedintoharmonicsandvoltagenotching.Thetransientsdisturbancescan befurtherclassifiedinto:brownouts(undervoltage),overvoltage,sags,surges,frequency variations,powerlinenoise,radiofrequencyinterference. 2)Whatarethesourcesofdisturbancesinpowersystems?Sketch4examplesforthe

sourcesofdisturbances. Thesourcesofsteadystateand/ortransientdisturbancesoriginatefromoutsidethepremisesas wellfrominside.Thesourcescanbeclassifiedbroadlyintoenvironmental(eg.lightning), operational(eg.switching),failure(eg.arcinggrounds)conditions.Thesourcesofsteadystate disturbancescanbearcfurnaces,welders,saturablereactors,rectifiers,thyristorcontrolled loads,variablevoltage/frequencydrives,uninterruptablepowersupply,magnetizingcurrents. Thesourcesfortransientdisturbancescanbeinductive/capacitiveloadsswitching,photocopiers, airconditioners,motors(switchingstartingandstopping),ballasts,lightswitches.Fig.12 shows4examplesforsourcesofdisturbancesinpowersystems.

3)Whataretheeffectsofsuchdisturbancesonthemajorelementsofpowersystems? Theeffectsthatthesteadystatedisturbanceshaveonthemajorelectricalequipmentare: _Motorandgenerators:atharmonicfrequencies,copperandironlossesincreaseand consequentlytheinsulationtemperature.Atextremeconditions,generatorscanhuntandmotors aresubjectedtopulsatingtorques. _Transformers:operatingundersustainedovervoltageconditionsmeansmorecopperandiron losses,thusoverheating.Duetothenonlinearcharacteristicsoftheironcore,overexcitingthe transformerwillcausethesteadystateexcitingcurrenttoincreasesignificantly(itisthepoint ontheflatportionofthevoltage/excitingcurrentcurveofthecore).Thiscurrentisreachin third&fifthharmonics,thushormonicsareinjectedintothesystem. _Powercables:overvoltageswillstresstheinsulation.Duetoresonanceconditions(betweenthe cablecapacitanceandloadinductance)fromotherthanfundamental(highharmonicsorder), thecablemaybesubjectedtoahighresonantvoltagewhichmaystartspartialdischargeinthe voidsfoundintheinsulatingmaterialThepartialdischargemayeventuallyleadstothefailure ofthecable.Harmonicsmaycausehigherskineffectthusoverheatingofconductorandthe insulationwilloperatecontinuouslyunderhighertemperatures. _Capacitors:atresonancefrequency,higherthenratedvoltagemaybeimposedontheunitand higherthanratedcurrentmayflowthroughthecapacitorblowingfusesoroverheatingtheunit. _Switchgearandmotorcontrolcentres:overheatingduetoincreasedlossesmaycausea reductionintheinsulationlife. _Protectiverelaying:nuisancetrippingornotrippingofelectromechanicalrelays(duetotorque ofharmoniccomponents),maloperationofnoneRMSsensing(peak)solidstaterelays.

_Metersandinstruments:positiveandnegativeerrorsarepossibleinelectromechanicalmeter readings. _Electronicequipment:misoperationorerraticoperationofmicroprocessorbasedandsolid statedeviceswhenhighharmonicsandvoltagenotchingarepresentinthecircuitsfeedingsuch devices. _Circuitbreakers:harmonicscancausethebreakerinsulationtobestressedduetoovervoltage andcurrentcarryingpartstobeoperatedathigherthannormaltemperatures.Thismayleadto failureofcircuitbreakerswhileintheclosedoropenedposition. _Communications:whencommunicationlinesareincloseproximitytohighharmonicscontent powerlines,interferencemayoccurwithdataandsignalstransmittedonthecommunication lines,sparioussystemresponsesatthereceivingendmayoccur. _Otherdeviceslikeballastsmayfail,clocksandpagingsystemsmaymalfunction. Theeffectsoftransientsare: _Motors:mayfailifsubjectedtoprolongedperiodofundervoltages,overvoltageswillstressthe insulationandeventuallywillcausetheinsulationtofail. _Heatersandlighting:Overvoltagewillcausethedevicetorunhotandifleftforalongperiod itmayburnitselfout. _Electronicdevicesaresusceptibletonoiseandspikes.Failureinpowersupplies/boardsand burningofchipswillbetheresult. _Transformers:overvoltageforprolongedtimeswillstresstheinsulation(andmayeventually causeafailure)andwillincreasetheharmonic(higherorder)levelinthesystem.Spikesmay causeaninsulationfailure. _Supervisorycontrolequipment:maymalfunctionfromelectromagneticinterference. 4)Whataretheindicatorsofthequalityofpowerinaplant? Theindicatorsofthequalityofpowerintheplantare: _Thelengthoffeedertowhichtheserviceisconnected.Itisimportanattoknowwhetherthe lineisanoverheadoranundergroundoneoramixofboth,ifthelastwhatistheproportionality ofoverheadtothetotalfeederlength.Ifitisanoverheadline,thedegreeofexposuretotrees, lightninig,trafficandcontaminantsmayindicatethequalityofpowertobeexpected.Onthe otherhand,ifundergroundcablesareusedthe,methodoflaying/pullingcablesmaygivean indicationofthequality.Theoperationphilosophyoftheutilityincludingfault indication/isolation/restoration,maintenanceproceduresandcablesfaulthandlingmayalso indicatetheaveragenumberoffailuresandthedurationperfailureforthefeeder. _Utilityphilosophyregardingtheuseofreclosures,sectionalizes,voltageregulators,lightning arresters,capacitorsandtheadjustmentsofovercurrentrelaysonthefeeders/reclosersandfuse sizing.Certaincomponentsimprovethequalitybutothersmayjeoperdizeitortheavailability ofthepowersource. _Thetotalnumberoffeedersconnectedtothetransformerstationbusundernormaland emergencysituationsasafaultonanyfeederwillaffectthevoltageonthestationbus. _Thesitehasanyequipmentthatwouldpumpdirtypowerintothesystem.Theknowledgeof

theequipmentconnectedtothesamefeederthatmaycauseharmonics,spikes,sags,etc.....tobe injectedintothesystemorsuperimposedonthenormalvoltageisimportanttoknowifpower qualityisanisue. 5)Whatarethemethodsusedtoreducethesedisturbances?Sketchtwoofthedevicesused inreducingthesteadystatedisturbances.Whatarethemajorstandardsthatarepower qualityrelated? Themitigationmethodstoproducetheeffectsofsuchdisturbancesare: Forsteadystatedisturbances:shuntfilters,seriesfilters,zerosequencefilter,phase multiplication,harmonicsinjection,thedesignofthepowersystem,reactorsorisolation transformer,reducingsystemimpedance.Fig.13showstwotypesofsuchdevices. Fortransientsdisturbances:builtinfilters,dedicatedlines/isolatedgrounds,regulation transformers,isolationtransformers,saturatedtransformers,ferroresonanttransformers,ultra isolationferroresonanttransformers,lineconditioners,clampingdevices,standbypower sources,uninterruptablepowersupplies(UPS). Thestandardsthatarerelatedtopowerqualityare:ANSI/IEEE519"Recommendedpractices andrequirementsforharmoniccontrolinelectricalpowersystems"(formerlyGuidefor harmoniccontrolandreactivecompensationatstaticpowerconverter),IEC1004series "Electromagneticcompatability"andANSI62series"SurgearrestersforA.C.powercircuits" plusCSA233series"SurgearrestersforA.C.systems".

6)Whatarethemajorhardwarecomponentsinanofficeautomationsystem?Whatare themajorresponsibilitiesofanoperatingsystem?Whatarethedifferenttypeslocalarea networksandwhatarethedifferenttypesoftransmissipnmediausedwithLANs. Themajorhardwarecomponentsare:themotherboard,microprocessor(CPU),diskdrives, monitorsandadapters(theyincludemonochromedisplayandadapter,colourgraphics, enhancedcolourdisplay,videographicsarray,supervideographicscards),keyboards,plotters, printers,modemsandotherinputdeviceslikemouse,joystickandinterfaces(forSCADA systemsorfromPLCsystems).Theoperatingsystemisresponsibleforinitializingthesystem, performingstartuptests,openingandcopyingthenecessaryfilesintomemory,givingcontrol totheuserandsoftwarerunundertheoperatingsystem.Localareanetworkstypesare: contentiontype,reservationorroundrobinoringeneralcanbeclassifiedintodistributedor centralizedcontrol.Thetransmissionmediamaybeanyofthefollowing:twistedpaircopper cable,coaxialcable,fiberopticsorlineofsight. 7)A20HPmotor,575v,3phase,.75p.f.,.85efficiency,calculatethecapacitorratingto improvethepowerfactorto.95,theincreaseincurrentflowthroughthemotorcircuitto otherconnectedloadsprovidedthattheapparentpowerremainsthesameinbothcases. MotorKWat.75p.f.=20(.746)=14.9KW KVAat.75p.f.=19.866,KVAR=[KVA2KW2].5=13.14 MotorKWat.95p.f.=14.9KW,KVA=14.9/.95=15.68

KVAR2=[15.68214.92].5=4.88 KVAR1KVAR2=13.144.88=8.26KVAR=capacitorrating.

KW=[19.86624.882].5=19.25KW Theadditionalpowerthatmaybetransferredduetothelocalcapacitor= 19.2514.9=4.35KW Atunityp.f.theadditionalcurrent=4.35/(575)(3)/(1.732)=4.36amp. Motorf.l.currentat.95p.f.=20(.746)/(1.732)(.95)(.85)575=18.5amp. 8)Ashortoverheadlinerated25KVnominalandissupportedonwoodenpolesat40ft fromgroundwith400KVdryBIL.Calculatethestrokecurrentthatwillcausethislineto flashoveriftheindirectlightningstrikehits20ftfromthephaseconductor.Calculatethe distancebetweenthelightningarresterssothata20KAlightningstrikeof8/20secwill notcausethelinetoflashover.RepeattheinterL.A.distanceifthewaveshapeassumes 4/10s. V=20.h.k.Ia/y;whereVisthevoltagethatwillcauseaflashover=400KV,k=1.2,histhe heightofconductorfromgroundlevel=40ft,yisthedistanceofthestrokefromtheconductor, Iaisthestrokecurrent. Ia=400(20)/20(1.2)(40)=8.33KA Assumea200ohmlinesurge(characteristics)impedance,voltagebuildupatpointofhitting= Z(I)/2=200(20)/2=2000KVpeak Thevoltagerisestopeakvaluein8s.Thustherateofriseofthiswave= 2000/8=250KV/s. Theinsulationlevelof400KVisreachedin400/250=1.6s. Thedistancebetweenarresters=1.6(.9)(984)/2=700ft Thedistancefor4/10swave=350ft SUMMARY: Inthischapterthelinedisturbanceswerepresented.Thetypes,sources,effectsonthe equipmentinthepowersystemsandthemetigationmethodsofsteadystateandtransient disturbancesweregiven.Theindicatorsthatmaybeusedinevaluatingoranalyzingthequality ofpowertobeexpectedatanylocationwerelisted.Thestandardsthatgovernthedesignofthe equipmentinordertominimizetheirdangereouseffectsofpumpingharmonicsorcausing voltagenotcheswerelisted.Thestandardsthatgoverntheprotectingdevicesthatwouldprotect theequipmentfromtheeffectsofsuchdisturbanceswerealsogiven.Also,themajorelements ofanofficeautomationsystemwerepresented.Theseelementscangeneratedirtypowerorbe affected(itselectroniccomponents&devices)fromdirtypowergeneratedelsewhereinthe interconnectedpowersystem.Thefirstofthelasttwonumericalexamplesshowedtheeffectof theapplicationoflocalcapacitorswithmotors.Capacitorswillimprovethep.f.andwill increasethecapacityofthefeedercircuit.Thesecondnumericalexamplequantifiedinasimple mannertheeffectofandtheflashoverlevelsofindirectanddirectlightninigstrokes. References:

1. Greenwood,Allan"Electricaltransientsinpowersystems",Wiley. 2. Wadhwa,C.L."Electricalpowersystems",Wiley. 3. IEEE"Recommendedpracticeforpowersystemanalysis",std399. Home page of VePi

Lesson5:Powersystemsstudies. 1) Whatarethegeneralrequirementsforanypowersystemsstudy? 2)WhatarethedatarequiredtoperformTRVcalculations? 3)Whatarethedatarequiredtoperformastabilitystudy? 4)Whatarethedatarequiredtoperformfaultcalculations?Toperformacoordinationstudy, whataretherequireddata? 5)Whatarethedatarequiredtoperformloadflowstudies?Whataretheiterativemethodsthat maybeusedinthecalculations? 6)Whataretherequireddataforswitchingtransientsstudies? 7)Whatarethedifferenttypesofmotorstartingstudies?Whatarethereequireddatatoperform suchstudies? 8)Whatarethemajorcomponentsinanindustrialsystemreliabilitystudy?Whatarethe requireddatatoperformsuchstudiesandwhatistheoutcome? 9)Whatarethecomponentsofadistributionutilitysystem?Whataretherequireddataandwhat istheoutcomeofsuchstudies? 10)Whatarethegeneraldatarequiredtoperformsteadystateandtransientstatestability calculations? 11)Whatarethebuildingblocksofanelectricalpowersystemsstudiesinformationsystem? 12)Asolvedproblemregardingtheprinciplecalculationsinvolvedwhenanalyzingapower distributionsystem. 13)Whataretheessentialcomputerprogramsforthepowersystemsanalyst? Lessonsummary References 1)Whatarethegeneralrequirementsforanypowersystemsstudy? Thegeneralrequirementsthatarecommonforallpowersystemsstudyare:thesingleline diagramfortheplant(orpartof)understudy,therating/type/makeforallsystemelements withinthestudyboundaries,anyavailabletestreportsormanualsandtheelementary (schematic)orconnection(wiring)diagrams. 2)WhatarethedatarequiredtoperformTRVcalculations? ThedatarequiredtoperformaTRVstudyare:theeffectiveinductancesandcapacitancesatthe TRVfrequencies(fromthenominalvoltagefrequency)forbushings,buses,powerand instrumenttransformersnearthecircuitbreakertobeswitched;thenumberoflinesorcables connectedtothebusatthetimeoffault,theirequivalentsurgeimpedance,length,termination andinterconnection;thetypeoffault,magnitudeoffaultcurrentandthevaluescontributed fromthelocalsources. 3)Whatarethedatarequiredtoperformastabilitystudy? Thedatarequiredtoperformastabilitystudyare: _Systemdata:impedanceoflines,cables,reactorsandanyotherseriescomponents;KVA

rating,impedance,voltageratings,ratio,windingconnection,availabletaps,typeoftapchanger controlandtapstepsize;shortcircuitcapacityofutilitysupply,KVARofcapacitorbanks (majorones);descriptionofnormalandemergency(contingency)switchingarrangements. _Loaddata:realandreactiveloadsonallsignificantloadbusesinthesystem. _Rotatingmachinedata:mechanicalandelectricalpowerratings,inertiaconstantofallrotating parts,speed,active/reactivepower(forgenerators)orspeed/torquecharacteristics(ifmotor),no load/airgapandlockedrotorcharacteristicscurves,reactancesandtimeconstants, damping/excitation/governor/steamsystems(ifapplicable)limitsandtimeconstraintsformajor synchronousmachines.Forminorsynchronousmachines,thefollowingdatawouldberequired: mechanical/electricalpowerratings,inertiaspeedanddirectaxissynchronousreactance.For majorinductionmachines,therequireddataare:mechanical/electricalratings,inertia,load speedtorquecurves,positiveandnegativesequencecircuitdataanddescriptionofmotor startingarrangements.Forminorinductionmachinetherequireddataarethe electrical/mechanicalpowerthesequenceequivalentimpedancecircuitandstarting arrangements(ifany). _Typeofdisturbancestobestudiedforexample:initialswitchingstatus,faultconditions,other switchingoperations.Thelimitsofacceptablevoltage,currentsandpowerswingsarealso importantforsuchstudies.Protectiverelaysdata,settingandoperatingtimes/includingclearing timeofswitchingdevicesarealsorequiredtocomparewiththestudyoutcometoverifythe transientstabilitystateforthespecificoperation(condition). 4)Whatarethedatarequiredtoperformfaultcalculations?Toperformacoordination study,whataretherequireddata? Thedatarequiredtoperformfaultcalculationsare:thepositive/negative/zerosequence impedancesofthesystemunderstudy,toachievethisrequirementthefollowingdatahavetobe available:size,lengthandmethodoflayingforallcablesinthesystemunderstudy,the overheadconductorssize,typeandconfiguration,transformersKVA/impedance(withits base)/tapchangerlimitsandstepsize/impedancepertapstep/primaryandsecondary voltage/methodofneutralgroundingandpertinentdata,fortheinductionorsynchronous motors:therating/subtransientreactance/transientreactance/speed/XtoRratio,thecurrent limitingreactors(ifany). Forthecoordinationstudythefollowingdataareessential:therelayscurrenttime characteristicscurves,fusestotalclearingtimecurrent/minimummeltingtimecurrent characteristicscurves,totalavailable3phaseshortcircuitcurrentinthesystem,damagecurves forcables/transformers,inrushcurrentstoinductionmotorsandtheirdurations,inrushcurrent fortransformersandduration,relaysburdendata,instrumenttransformers saturation/excitation/accuracy/ratio/tapsnumberandratiosdata. 5)Whatarethedatarequiredtoperformloadflowstudies?Whataretheiterative methodsthatmaybeusedinthecalculations? Thepertinentdatarequiredforloadflowstudiesare:forgenerators:active(real)powerandthe maintained(constant)voltage,forloads:therealandreactivepower(scheduledandconstant

overtheperiodofthestudy),fortheslackbus:thevoltageandphaseangleatthebus(bothare keptconstantovertheperiodofthestudy),theadmittancematrixofthemodellednetwork(this willincludetheadmittanceofinterconnectingpowerlinesandtheshuntbranches),forthe transformers:ratings,tapstepsandnumber(ifapplicable). Anyofthefollowingiterativemethodsmaybeused:GaussSeidel,NewtonRaphsonorFast decoupledmethod. 6)Whataretherequireddataforswitchingtransientsstudies? Therequireddataforswitchingtransientsstudiesare: _Utilityinformation:seriesresistanceandreactance,zerosequenceand+vesequenceparallel capacitance,minimumandmaximumavailableandfutureshortcircuitlevels,maximumand minimumvoltagesandoperationdescription/reclosingprocedure. _Transformersdata:ratings,connections,windingsarrangementdetails,tapchangersdetails, (steps,limits),leakagereactanceandresistance(+veandzerosequence),noloadvoltagevs excitingcurrent,basevoltage/current,neutralgroundingdetails. _Capacitordata:MVARormicrofarad,voltagerating,connections,neutralgroundingdetails, switchingdevicedetails,tunningreactorsdata(ifapplicable). _Cablesandconductors:length,size,arrangement,conduitdetails,insulation/shield/sheath details. _Surgearresters:location,ratings. _Groundingresistors:ratingsimpedance. _Reactors:ratings,impedance(foralltaps). _Rotatingmachines:regulatortype(ifapplicable)andsubtransient/transientreactances. _Operatingmodes:sequenceandconditionofeachoperationofswitchingdevices,actionof protectiveschemeagainstovervoltageandundervoltage. 7)Whatarethedifferenttypesofmotorstartingstudies?Whatarethereequireddatato performsuchstudies? Thedifferenttypesofmotorstartingstudiesare:voltagedrop(snapshot),detailedvoltage profile(timedependentbusvoltageanalysis)andmotortorque/accelerationtimeanalysis. Thedatarequiredmayvaryfunctionofthedegreeofthedetail(thedepth)ofthestudy:utility andgeneratorimpedances,transformersimpedance,cablessizes/number/material/conduit type/reactance/resistance,overheadconductorssizes/type/quantity/material/resistanceand reactance,loadtype(constantimpedanceorapparentpowerorcurrent)/powerfactor/load factor/inrushcharacteristics,loadandmotorrotatingpartsinertia,inertiaofmechanical couplingoranygearing,speedtorquecharacteristicsofbothmotorandload,speedvscurrent andpowerfactorcurves. 8)Whatarethemajorcomponentsinanindustrialsystemreliabilitystudy?Whatarethe requireddatatoperformsuchstudiesandwhatistheoutcome? Themajorcomponentsthatmaybeincludedinareliabilitystudyforanindustrialsystemare: m.v.circuitbreakers,m.v.disconnectswitches,powerordistributiontransformers,underground cablesandcablesplices,cableterminations,lowvoltagecircuitbreakers,lowvoltageand

mediumvoltageswitchgearassemblies(withinsulatedoruninsulatedbus)andutilityservice. Thedatarequiredtoperformareliabilitystudyare:thefailurerates(failuresperyear)andhours ofdowntime/failureforeachequipmentorcomponentincludedinthestudy.Theoutputhasto beanumberproportionaltotheforcednumberofhoursofdowntimeperyearforthesystem understudy. 9)Whatarethecomponentsofadistributionutilitysystem?Whataretherequireddata andwhatistheoutcomeofsuchstudies? Themajorcomponentsthatcanbeconsideredinadistribution,utility,systemare:thepower transformerinthetransformerstation,thehighvoltagedisconnectswitch,themediumvoltage circuitbreakersandswitchgearassemblies,theinsulators,thecableterminations,theoverhead conductors/undergroundcablesandsplices,thepadmountedswitchgearandthedistribution transformers.Thedatarequiredtoperformareliabilitystudyforsuchasystemare:thenumber oftaps(branches)offthemainfeeder,thenumberofsegmentsperlineortap,thelengthper segment,theexposurefactorpersegment,theconductorfactorpersegment,theupstream device(fuse,breaker,recloser,sectionalizer)factorforeachsegmentandtheweightednumber ofcustomersinterruptedwhenthesegmentfails.Also,thefollowingdataarerequired:number offailuresperyearandnumberofhoursperfailureforeachcomponentsinthesystemincluding theoverheadandundergrounddistributionnetwork.Theoutputwillhavetwotypesofnumbers oneproportionaltotheannualinterruptiontimeandthesecondproportionaltocustomerhours ofinterruption. 10)Whatarethegeneraldatarequiredtoperformsteadystateandtransientstate stabilitycalculations? Forasteadystatestability(i.e.beforeafaultconditionorswitchingoperation,forexample),the datarequiredare:thevoltageatbothbusesthathavethepowerflowinginbetween,the impedanceofthelineandtheangledifferencebetweenthetransmittingandreceivingbuses. Thefollowingdatawouldberequiredtoperformatransientstatestabilitystudy: _Duringswitchingorfaults:poweroutofgenerator,selfconductanceofbuses,transfer admittancebetweenalltheconnectedbuses,angulardisplacementofeachtwoadjacentbuses (machinesorinfinitebus),resistanceandreactancebetweeneachtwoconnectedbuses,the generatorconstants(ifapplicable). _Postfaultclearing:thesamedataasforduringthefaultcondition. 11)Whatarethebuildingblocksofanelectricalpowersystemsstudiesinformation system? Theinformationsystemthatisusedtoperformpowersystemsstudiesmusthave(butnotlimited to):reliabilitydata(failuresandhours/failurefordifferentequipment,typicalreactancevalues forinductionandsynchronousmachines,resistanceandreactancevaluesofCopperand Aluminumconductors,reactancevaluesoftypical3phasecablecircuitsindifferentconduit materials,X/R