elc 119r-s 1 elc 119r-s electrical safety refresher for subcontract electrical workers
TRANSCRIPT
2ELC 119R-S
OutlineIntroduction
1 Shock and Arc Flash
2 Electrical Hazard Mitigation
3 Technical work documentation (TWD)
4 Safe switching procedures
5 Wrap-Up
3ELC 119R-S
Introduction ~ 300 workplace electrocutions annually Estimated 20,000 shocks for every electrocution ~ 4000 injuries annually requiring days away ~3600 disabling electrical contact injuries
annually 10-15 workers hospitalized daily with electrical
burns 4-year average of 23 electrical events at SNL
4ELC 119R-S
Most Common Electrical Events at SNL
Short circuit of energized parts to ground Workers shocked from approaching nearer
than a safe distance from exposed live parts
Workers shocked from faulty equipment Workers shocked from
plugging/unplugging equipment
5ELC 119R-S
Module 1: Shock and Arc Flash
The passage of electric current through the
body from contact with an electric circuit (conductors).
Exposure to electrical energy may result in no injury
at all or may result in devastating damage or death.
Electrocution is death by electrical energy resulting
from the passing of a high magnitude electric current
through the body
5
6ELC 119R-S
Why Are We Susceptible to Injury by Electric Shock?
A. Our highly developed nervous system makes us extremely sensitive to even very small electric currents.
B. The passage of current through the body results in heating of tissue
Each of these interactions has serious
consequences.
6
7ELC 119R-S
Effects of Current on the BodyCurrent Value Effects
< 1 ma Barely Perceptible
1-5 ma Perceptible shock, reflex actions
5 ma GFCI trips Accepted as maximum harmless current
6-10 ma Painful shock, victim can “let-go”
10-20 ma Painful shock, victim can not let go
50-100 ma Ventricular Fibrillation possible
100-200 ma Ventricular Fibrillation likely
200 ma Severe burns, severe muscular contractions, chest muscles clamp the heart and stop it for the duration of the shock.
833 ma Current used by 100 watt light bulb
8ELC 119R-S
Effect of Current Passing Through the Body
Current can confuse or damage nerve control centers of lungs and heart
Heat damage caused by dissipation of energy- body acts as a resistor.
11ELC 119R-S
Factors Affecting Shock Remember Ohm’s Law: E=IR
Current: most important factor, though directly determined by voltage and body resistance.
Path of current: greater chance for survival if current passes through extremities only
Duration of Shock: according to IEEE std. 80, the maximum safe duration can be determined by using: t (seconds) = .116/(V/R)
12ELC 119R-S
ExampleIf an electrician gets a shock from a 277 volt light fixture, would he/she get “stuck” on the circuit? Let’s assume the worker was sweating and use a resistance value of 10,000 ohms.
I =E/R
I = 277/10,000
I = .0277 amps or ~28 ma
13ELC 119R-S
Is He/She Stuck?Current Value Effects
<1 ma Barely Perceptible
1-5 ma Perceptible shock, reflex actions
5 ma GFCI trips Accepted as maximum harmless current
6-10 ma Painful shock, victim can “let-go”
10-20 ma Painful shock, victim can not let go
50-100 ma Ventricular Fibrillation likely
100-200 ma Ventricular Fibrillation occurs
200 ma Severe burns, severe muscular contractions, chest muscles clamp the heart and stop it for the duration of the shock.
833 ma Current used by 100 watt light bulb
YES!
14ELC 119R-S
Example continued
Let’s also assume that the path of the current is hand to hand. How long does this person have before the shock could be considered fatal?
T = .116/(V/R)T = .116/(277/10,000)T = .116/.0277T = 4.18 seconds!
15ELC 119R-S
Voltage Thresholds
OSHA set threshold for hazardous energy at 50 volts
Hazard from applications lower than 50 are usually thermal not shock: batteries, super capacitors, etc.
At levels greater than 600 V, skin is usually penetrated driving resistance down.
17ELC 119R-S
Rescuing and TreatmentStep 1 – Check to see that the area is safe to enter
Step 2 - Call 911 immediately
Step 3- Rescue the victim with an insulated device (hot stick, rope, dry wood, etc)
Step 4 – Begin CPR
Step 5 - Continue resuscitation
Step 6 - Get medical attention for the victim
18ELC 119R-S
II Arc FlashA release of thermal energy from an electric arc
by the vaporization and ionization of materials,
reaching temperatures up to 35,000 °F.
Exposure to these extreme temperatures both
burns the skin directly and causes ignition of
clothing.
(2004 NFPA 70E)
19ELC 119R-S
Nature of the Arc Arc results from passing of current through air Terminals vaporize and serve as conductive medium
for ionized gasses Flash can extend further than 10’ from the source Pressure wave caused by rapid expansion of gases
with flying molten materials and shrapnel The blast can destroy structures, and knock workers
from ladders or across a room. The blast can rupture eardrums and collapse lungs.
21ELC 119R-S
Three Factors Affecting Arc Energy
Available short circuit current Duration of the arc Distance from the arc
22ELC 119R-S
Burns From the Arc
First degree: surface only. Skin is usually red and tender
Second degree: blistering of the skin. Most painful
Third degree: complete destruction of the skin with charring of tissue. Most dangerous –susceptible to infection. Skin can not heal itself.
25ELC 119R-S
Effects of the Arc- Burns
Burn Injury - Probability of Survival
0%
20%
40%
60%
80%
100%
20-29.9 30-39.9 40-49.9 50-59.9
Age Range - Years
% S
urv
ival 25% Body Burn
50% Body Burn
75% Body Burn
Arcs have ignited clothing 10’ from the arc and can be fatal when within a few feet
26ELC 119R-S
Accelerator Flash Incident
On October 11, 2004, at approximately 11:15 am,a subcontractor electrician working at an Accelerator Center received
serious burn injuries requiring hospitalization dueto an electrical arc flash that occurred during theinstallation of a circuit breaker in an energized
480-Volt (V) electrical panel.
31ELC 119R-S
From the Type A Investigation…
Description of Injuries:
Electrician received third degree burns on the face, chest, and legs and second degree burns on the arms, involving approximately 50% of his body. Because of the seriousness of his condition, the Board was not able to interview him.
32ELC 119R-S
Module 2: Electrical Hazard Mitigation
1. Plan your work
2. Analyze/identify the hazards
3. Control the hazards
4. Perform the work
5. Improve the process for the next operation
33ELC 119R-S
1910 CFR 851 and NFPA 70E All Department of Energy Facilities are
contractually required by law follow 10 CFR 851- Worker Safety and Health Protection Plan
851.23(a)(14) requires contractors to comply with NFPA 70E as a baseline.
70E is the industry standard for addressing electrical hazards in the workplace
Applying 70E standards nothing more than using integrated safety management
34ELC 119R-S
TURN IT OFF! Energized work no longer allowed at SNL
unless:“de-energizing introduces additional or increased
hazards or is infeasible due to equipment design or operational limitations” 70E 110.8.A.1
Most hazards can be controlled by insulating,
guarding, or by simply working de-energized
35ELC 119R-S
Electrically Safe Work ConditionFirst priority is to de-energize1. Review safety plan
2. Inspect equipment, disconnect energy sources, and lock and tag energy sources.
3. Post barricades and signs to establish the limited approach and flash protection boundaries.
4. Open enclosure, identify shorting devices, and discharge energy-storage devices if applicable.
5. Perform Zero Energy verification Test
6. Complete work
7. When the work is completed, test circuits, remove tools, and test gear, perform final check, and close enclosure
NOTE: Equipment is not considered de-energized until locked out and verified
36ELC 119R-S
Energized Work - provided justification requirements (slide 34) are met
Strict requirements addressing worker qualifications: Qualified Person: One who has the skills and knowledge related to
the construction and operation of the electrical equipment and installations and has received safety training on the hazards involved (Electrical Safety in the Workplace, 2004).
Energized work must be authorized by Senior Manager Facilities Engineering- see your contract Sandia delegated representative (SDR)
Shock and Flash Hazard Analyses required. This can be accomplished using the table on slide 44. Remember 2 different hazards- shock and flash
37ELC 119R-S
Shock Hazard Analysis Required ANYTIME a worker crosses the
Limited Approach Boundary to exposed live parts
Must determine approach boundaries (Limited and Restricted) and required shock PPE (usually gloves and insulated tools)
Shock PPE required ANYTIME a worker crosses the Restricted Approach Boundary
38ELC 119R-S
Shock Approach Boundaries
Limited Approach Boundary (LAB) Level II authorization required Only qualified workers may cross * Boundary must be physically established
Restricted Approach Boundary (RAB) No unqualified workers Shock PPE required Shock PPE mainly consists of insulating gloves and tools
Refer to slide 44 for LAB and RAB approach distances and required PPE.
39ELC 119R-S
Flash Hazard Analysis
Required ANYTIME a worker crosses the flash protection boundary (FPB)
Must determine the Flash Protection Boundary and the PPE required for crossing this boundary
PPE and distances determined from table slide 44
40ELC 119R-S
Arc Flash Protection• PPE and flash protection boundary (FPB) in
CSSP will match that of arc flash hazard (AFH) label on equipment
• If the electrical equipment is not provided with an AFH warning label, PPE and FPB in CSSP will be determined using the table in slide 44.
41ELC 119R-S
Exposed Live PartLimited Approach Boundary (shock)Level II authorization requiredOnly qualified workers may cross – unqualified workers may cross if escorted by qualified worker and made aware of the hazards Boundary must be physically established
Flash Protection Boundary Distance and PPE determined from table in slide 42PPE required of ANYONE inside this boundary
Restricted Approach Boundary (shock)No unqualified workersShock PPE requiredShock PPE mainly consists of insulating gloves and tools
42ELC 119R-S
Hazard Risk Categories (HRC)
HRC 0: Single phase circuits operating at 50-208 volts HRC 1&2: Three-phase circuits operating between 120
and 600 volts HRC 3&4: Three-phase service entrance equipment and
switchgear operating between 120 and 600 volts, excluding those systems with a RED, Level V Arc Flash Hazard label.
43ELC 119R-S
Hazard Risk Categories (HRC)
Hazard Risk Above Forty Calories: All equipment identified with a Level V (red) Arc Flash Hazard label
Hazard Risk Greater Than 600 volts: Obtain flash hazard analysis. Exception: HRC 2 PPE shall be worn In 15 kV
manholes. Head, face and glove protection may be removed during cable terminations if no other work is being performed in the manhole.
44ELC 119R-S
Boundary and PPE TableEquipment Class
HRC
Flash Boundary
LAB, RAB
Required flash PP
Required shock PPE
PPE Code
208/240 1-ø 04’
3’ – 6”, contact
EWC
Class 0 gloves with leather protectors and insulated tools
Green
120/240, 277/480
3-ø non service entrance
1, 26’
4’, 1’
EWC + accessories
Class 0 gloves with leather protectors and insulated tools
Blue
120/240, 277/480
3-ø service entrance3
Contact FMOC project lead
4’, 1’
ISC
Class 0 gloves with leather protectors and insulated tools
Yellow
120/240, 277/480
3-ø service entrance4
Contact FMOC project lead
4’, 1’
ESC
Class 0 gloves with leather protectors and insulated tools
Orange
Equipment labeled greater than 40
calories or 600 voltsNA
Contact SDR, CO, or PM for assistance
Contact SDR, CO, or PM for assistance
Red
EWC: FR long sleeve shirt (min arc rating = 8) worn over untreated cotton t-shirt with FR pants (min arc rating = 11, safety glassesAccessories: hard hat w/FR rated face shield, hearing protection, and leather boots or shoesIWC: EWC + accessories + FR coveralls (min arc rating = 25) and double –layer switching hood.ESC: 40-calorie switching suit w/rated hood and gloves, leather boots and shoes.
45ELC 119R-S
Example Arc Flash Labels Level I (HC-0) Label Level II (HC-1 and HC-2)
Label WARNING ARC FLASH & SHOCK HAZARD
BUILDING 752 LOCATION PANEL 1BH1
INCIDENT ENERGY @ 18”
6.9 cal/cm2 HAZARD
CATEGORY 2
APPROACH BOUNDARY 3.8 ft PPE LEVEL II
SOURCE TF-0752-1 MAXIMO
DATE 10/05/07
WARNING ARC FLASH & SHOCK HAZARD
BUILDING 867 LOCATION PANEL MSB1
INCIDENT ENERGY @ 18”
< 2 cal/cm2 HAZARD
CATEGORY 0
APPROACH BOUNDARY 3 ft PPE LEVEL I
SOURCE TF-0867-1 MAXIMO
DATE 10/05/07
46ELC 119R-S
Electro-Magnetic Energy Whenever you have electric power, electric and
magnetic fields will be generated. The electric field is often generated by the
alternating voltage of the electrical system. The higher the voltage, the greater the electric field. Taken together, electric and magnetic fields are often referred to as electromagnetic radiation.
The main effect of exposure to EME is heating of tissue and organs.
There are rooftop antennas at Sandia that emit varying levels of EME so contact your ES&H coordinator before approaching them
47ELC 119R-S
Worker Responsibilities Familiarize yourself with procedures and
work plans- CSSP Be aware of your surroundings Obey all warnings signs and regulations Always use proper PPE (slide 44) Stop work if an unsafe and/or unexpected
condition arises Consider ALL electrical equipment energized
unless locked out and verified de-energized
48ELC 119R-S
Worker Responsibilities• Do NOT perform unjustified energized work• Do not wear jewelry when performing energized
work• Report ALL accidents, regardless of severity to
Safety Officer/Supervisor• Immediately report to your supervisor, anyone
known to be under the influence of drugs or alcohol
• Be aware of secondary hazards- beryllium, radiation, noise, etc
• Be responsible for your own safety!
49ELC 119R-S
Planning Your Work Planning is a key element in performing work safely
and is the first step in the ISMS process. OSHA and 70E require a job briefing be held before
any electrical work operation begins. All personnel involved in the job shall be briefed on the
safety concerns, energy source controls and precautions regarding their assignments.
Should work conditions change or unanticipated hazards appear, additional briefings should be held.
Planning must be documented!
50ELC 119R-S
Planning Your Work continued
Consider ALL hazardsWhen changing a ballast, what hazards are
involved besides electricity and working from heights?
Is there an asbestos issue? Is the fixture in an area known to have
dangerous levels of Beryllium?How about radiation?
51ELC 119R-S
Planning Your Work continued
• The meeting must cover the following questions:– Do I thoroughly understand the job?– Do I thoroughly understand my role in the job?– Am I aware of all the hazards I may encounter?– Am I knowledgeable of all the safety rules and
required personal protective equipment that apply to the job?
52ELC 119R-S
Performing Your Work All circuits must be considered energized until
LOTO’d and verified de-energized Several events at SNL have been the result of failure to
verify de-energized Performance of the 0 energy verification still
requires PPE and boundary establishment (slide 44)
Do you have to do this hot? Physically establish the limited approach boundary
(slide 44) Boundary must keep unqualified workers out of area Boundary must warn workers of the hazards inside the
area
53ELC 119R-S
Performing Your Work Wear the appropriate PPE
Shirt must be buttoned and sleeves rolled down Flash PPE is required when inside the flash protection boundary (slide 44)
Crossing the restricted approach boundary requires gloves and insulated tools (slide 44) Maintain your gloves Are they out of testing date requirements?
Use the right tools for the job Is you meter rated for the task? Several events at SNL have occurred due to use of an inappropriate meter
Do not deviate from job plan. If work outside of scope is required stop and re-evaluate with all involved
co-workers.
54ELC 119R-S
Module 2 Conclusion Severe hazards associated with energized electrical work Energized work is now the exception- not the norm- Turn
–it-off! NFPA 70E provides sound guidance for electrical safety
in the workplace Applying the standard is basic ISMS- identify the hazard,
control the hazard Remember there are two primary hazards (shock and
flash) that must be analyzed and controlled independently
55ELC 119R-S
Module 3: TWD RequirementsQ: What is considered energized work at SNL? A: Any activity inside the Limited Approach
Boundary (LAB) Crossing the LAB for ANY reason must meet
the 70E justification requirements of 110.8.A.1 (slide 35)
ALL energized work requires a technical work document
Why? This should be your first question when asked to work energized.
56ELC 119R-S
Contract Specific Safety Plan (CSSP)
The CSSP is the required technical work document for all energized work at SNL performed by a facilities subcontractor
The CSSP must incorporate the required energized work permit elements required in NFPA 70E 130.1B2
57ELC 119R-S
Content of the CSSP1. A description of the circuit/part to be worked on and its
location
2. Justification of why the work must be performed energized. Remember that some troubleshooting could be accomplished with an Ohm meter.
3. A description of safe work practices to be employed (second person, safety watch, Barriers, etc)
4. Results of the shock hazard analysis (voltage the employee(s) will be exposed to) – slide 44
5. Determination of shock approach boundaries (LAB, RAB, PAB) using table slide 44
58ELC 119R-S
Content of the CSSP continued
6. Results of the flash hazard analysis (determination of the Flash Protection Boundary and the caloric exposure based on table slide 44
7. The necessary personal protective equipment- shock and flash
8. Means used to restrict access of unqualified personnel to the area (chains, flagging, signage, etc)
9. Evidence of completion of a pre-job briefing including topics covered- checklist
10. Energized work approvals (workers, Managers, Senior Managers)
59ELC 119R-S
Insulated Tools Insulated tools, rated for the system voltage, are
required when contacting any energized component. Insulated tools should be listed under # 3. Ground hooks shall also be listed here.
If the insulated tool can prevent the user from
crossing the restricted approach boundary and flash protection boundary, PPE will not be required (except safety glasses).
60ELC 119R-S
Module 4 Safe Switching Procedures
Three hazards associated with switching breakers or disconnectsShockExplosionArc flash/blast
61ELC 119R-S
Shock
Rare when switching because cover should be in place.
Remember shock boundaries 30,000 non-fatal shocks each year in the
workplace… 247 died from electrocution in 2006…
down from 251 in 2005.
62ELC 119R-S
Breaker Explosion
Counterfeit Products Sub-standard
components No NRTL listing
Improper Sizing Improperly rated for
available fault current
64ELC 119R-S
Operating Breakers and Disconnects
Use one hand when possible. For side-handled switches, stand as far away
to the side as possible to operate the switch. For panel-mounted breakers, do not stand in
front of the panel when operating the breaker. Do not expose unprotected portions of the
body/face to the potential blast.
65ELC 119R-S
Review – Switching OperationsDisconnect Rating Required PPE (Hazard
Category)Up to and including 60 amps (< 600 volts)
HC 0 *
>60 up to and including 200 amps (< 600 volts)
HC 2 *
> 200 amps (< 600 volts) and all > 600 volts
Must be analyzed by a qualified person. Contact
electrical safety for evaluation.
•Arc flash labels supersede this table
•reference slide 44 for specifics
66ELC 119R-S
Module 4 Conclusion Switching can be hazardous Wear appropriate PPE Obtain AIC and clearing times prior to switching Never switch breakers or disconnects under trip
conditions - call facilities Never close a breaker or disconnect if uncomfortable Use Left hand rule to keep body away from
disconnect when closing
67ELC 119R-S
Course Wrap-Up You seldom get a second chance with electricity Most electrical accidents are caused by unseen or
unanticipated hazards Take your time! Never deviate from procedures If circumstances or conditions change- STOP and
re-evaluate Work on energized equipment is restricted at SNL Maintain tools, test equipment, and PPE Never rely on others for your safety