1 EDC3 1.0 Introduction In the last set of notes (EDC2), we saw how to use penalty factors in solving the EDC problem with losses. In this set of notes, we want to address two closely related issues. What are, exactly, penalty factors? How to obtain the penalty factors in practice? 2.0 What are penalty factors? Recall the definition: Gi Gm G L i P P P P L ) , , ( 1 1 2 (1) In order to gain intuitive insight into what is a penalty factor, let’s replace the numerator and denominator of the partial derivative in (1) with the approximation of ΔP L /ΔP Gi , so:

Upload: truongdiep

Post on 03-Jul-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

1

EDC3

1.0 Introduction

In the last set of notes (EDC2), we saw how

to use penalty factors in solving the EDC

problem with losses. In this set of notes, we

want to address two closely related issues.

What are, exactly, penalty factors?

How to obtain the penalty factors in

practice?

2.0 What are penalty factors?

Recall the definition:

Gi

GmGL

i

P

PPPL

),,(1

1

2 (1)

In order to gain intuitive insight into what is

a penalty factor, let’s replace the numerator

and denominator of the partial derivative in

(1) with the approximation of ΔPL/ΔPGi, so:

2

Gi

L

i

P

PL

1

1

(2)

Multiplying top and bottom by ΔPGi, we get:

LGi

Gii

PP

PL

(3)

What is ΔPGi? It is a small change in

generation. But that cannot be all, because if

you make a change in generation, then there

must be a change in injection at, at least, one

other bus. Let’s assume that a compensating

change is distributed throughout all other

load buses according to a fixed percentage

for each bus. By doing so, we are embracing

the so-called “conforming load” assumption,

which indicates that all loads change

proportionally.

Therefore ΔPGi=ΔPD. But this will also

cause a change in losses of ΔPL, which will

be offset by a compensating change in swing

bus generation ΔPG1. So,

3

LDGGi PPPP 1 (4)

where we see generation changes are on the

left and load & loss changes are on the right.

Solving for ΔPGi-ΔPL (because it is in the

denominator of (3)), we get

1GDLGi PPPP (5)

Substituting (5) into (3), we obtain:

1GD

Gii

PP

PL

(6a)

Recognize that ΔPG1 in (6a) reflects the

losses, we have

LD

Gii

PP

PL

(6b)

So from (6b), we extract the following

interpretation of the penalty factor: It is the

amount of generation at unit i necessary to

supply ΔPD, as a percentage of ΔPD-ΔPL.

This depends on how the load is changed

(which is why we use the conforming load

assumption). If the change increases losses

(ΔPL>0), then Li>1. If the change decreases

losses(ΔPL<0), then Li<1.

4

An example will illustrate the significance

of (6a) & (6b). Consider Fig. 1. Observe that

the flows given on the circuits are into bus 2

(the flows along the line out of buses 1 and

3, respectively, are higher).

75 100 525

101 25 576

25 50

Increase load by 1 MW at each bus, compensated by gen increase at bus 2

1 2 3

76 101 526

100.8 28 576

49

1 2 3

9375.02.3

3

)2.0(3

32

L

Basecase

Increase load by 1 MW at each bus, compensated by gen increase at bus 3

76 101 526

101.2 25 579

24 52

1 2 3

074.18.2

3

)2.0(3

33

L

24

Fig. 1

5

One observes that L2<1. This is because a

load change compensated by a gen change at

bus 2 decreases the losses as indicated by

the fact that the bus 1 generation decreased

by 0.2 MW.

On the other hand, L3>1. This is because a

load change compensated by a gen change at

bus 3 increases the losses as indicated by the

fact that the bus 1 generation increases by

0.2. MW.

Why does the bus 2 generation reduce losses

whereas the bus 3 generation increases

losses?

Answer: Because increasing bus 2 tends to

reduce line flows, whereas increasing bus 3

tends to increase line flows.

So we see that in general, generators on

the receiving end of flows will tend to have

lower penalty factors (below 1.0); generators

on the sending end of flows will tend to

have higher penalty factors (above 1.0).

6

Because transmission systems are in fact

relatively efficient, with reasonably small

losses in the circuits, the amount of

generation necessary to supply a load

change tends to be very close to that load

change. Therefore penalty factors tend to be

relatively close to 1.0.

A list of typical penalty factors for the

power system in Northern California is

illustrated in Fig. 2. Generators marked to

the right are units in the San Francisco Bay

Area, which is a relatively high import area

for the Northern California system. Most of

the penalty factors for these units are below

1.0. Units having penalty factors>1.1 are

mainly units close to the Oregon border (a

long way from the SF load center), such that

they tend to add to the north-to-south flow

that results from the northwest hydro being

sold into the California load centers.

7

Fig. 2

But why do we actually call them penalty

factors? Consider the criterion for optimality

in the EDC with losses:

miP

PCL

Gi

Giii ,...1

)(

(7)

8

This says that all units (or all regulating

units) must be at a generation level such that

the product of their incremental cost and

their penalty factor must be equal to the

system incremental cost λ.

Let’s do an experiment to see what this

means. Consider that we have three identical

units such that their incremental cost-rate

curves are identical, given by

IC(PG)=45+0.02PG.

Now consider the three units are so located

such that unit 1 has penalty factor of 0.98,

unit 2 has penalty factor of 1.0, and unit 3

has penalty factor of 1.02, and the demand is

300 MW.

Without accounting for losses, this problem

would be very simple in that each unit

would carry 100 MW.

But with losses, the problem is as follows:

9

λ=0.98(45+0.02PG1)=44.1+0.196PG1

λ=1.0(45+0.02PG2)=45+0.02PG2

λ=1.02(45+0.02PG3)=45.9+0.0204PG3

Putting these three equations into matrix

form results in:

300

9.45

45

1.44

0111

10204.000

1002.00

1000196.0

3

2

1

G

G

G

P

P

P

Solving in Matlab yields:

9875.46

31.53

37.99

32.147

3

2

1

G

G

G

P

P

P

One notes that the unit with the lower

penalty (unit 1) was “turned up” and the unit

with the higher penalty (unit 3) was “turned

down.” The reason for this is that unit 1 has

a better effect on losses.

10

3.0 Penalty factor calculation

There are several methods for penalty factor

calculation. We will review several of them

in this section.

This method is described in [1]. Consider a

power system with total of n buses of which

bus 1 is the swing bus, buses 1…m are the

PV buses, and buses m+1…n are the PQ

buses.

Consider that losses must be equal to the

difference between the total system

generation and the total system demand:

DGL PPP (8)

Recall the definition for bus injections,

which is

DiGii PPP (9)

Now sum the injections over all buses to get:

11

DG

n

i

Di

n

i

Gi

n

i

DiGi

n

i

i

PPPP

PPP

11

11

)(

(10)

Therefore,

n

i

iL PP1 (11)

Now differentiate with respect to a particular

bus angle θk (where k is any bus number

except 1) to obtain:

nkPPPPPP

k

n

k

m

k

m

kkk

L ,...,2,121

(12)

Assumption to the above: All voltages are

fixed at 1.0; this relieves us from accounting

for variation in power with angle through

the voltage magnitude term. Otherwise, each

term in (12) would appear as

k

k

k

i

k

i V

V

PP

12

Now let’s assume that we have an

expression for losses PL as a function of

generation PG2, PG3,…,PGm, i.e.,

PL=PL(PG2, PG3,…,PGm) (13)

Then we can use the chain rule of

differentiation to express that

nkP

P

PPP

P

PPP

k

m

Gm

GL

kG

GL

k

L ,...,2,)()( 2

2

(14)

In (14), we assume that at generator buses,

loads are constant, and ∂PGi/∂θi=∂Pi/∂θi.

Subtracting (14) from (12), we obtain, for

k=2,…,n:

k

n

k

m

Gm

GL

k

m

G

GL

kk

k

L

k

m

Gm

GL

kG

GL

k

L

k

n

k

m

k

m

kk

PP

P

PPP

P

PPPP

PP

P

PPP

P

PP

PPPPPP

1

2

21

2

2

121

)(1

)(10

_________________________________________

(14) from )()(

(12) from

Now bring the first term to the left-hand-

side, for k=2,…,n

13

Writing the above

k

n

k

m

Gm

GL

k

m

G

GL

kk

PP

P

PPP

P

PPPP

1

2

21 )(1

)(1

The above equation, when written for

k=2,…,n, can be expressed in matrix form as

2

1

2

12

2

222

2

1

1

)(1

)(1

P

P

P

PP

P

PP

PPP

PPP

Gm

GL

G

GL

n

n

n

m

n

nm

(15)

The matrix on the left-hand side is the

transpose of the upper left-hand submatrix

of the power flow Jacobian (we called it

JPθ

), and so codes are readily available to

compute it. The elements of the right-hand-

side vector may be found by differentiating

the real power equation for bus 1, which is:

)sin()cos(1

111111

N

i

iiiii BGVVP (16)

with respect to each angle, resulting in

14

iiiiii

BGVVP

11111

1 cossin||||

The solution vector contains the inverse of

the penalty factors in the first m-1 terms.

4.0 Using loss formula

The method of loss formula results in an

approximate expression given by

000 BPBPBPP GT

GTGL (17)

where PG is the vector of generation

Gm

GTG

P

P

P 1

(18)

Development of the coefficient matrices in (17)

has been done in several ways. The first edition of

the W&W text (1986) presented a method

developed by Meyer [2] in Appendix B of chapter

4; it was removed from the second edition.

I developed another method based on the work of

Kron, which is partially articulated in the book by

El-Harawry and Christenson, and attached to the

end of these notes.

15

Some important similarities in the methods:

1. Both are dependent on the following

assumptions:

Each bus can be clearly distinguished as

either a load bus or a generation bus.

Reactive generation varies linearly with

generation, i.e., Qgk=Qgo+fkPgk.

2. Both end up with expressions for PL of

the same form.

3. Both expressions for PL are dependent on

the elements of the Zbus matrix.

But there is one major difference between

the formulations in that Kron’s approach

makes no assumption regarding conforming

loads. However, the method of W&W

(Meyers) does, i.e., in Meyer’s approach, all

loads must increase or decrease uniformly.

We assume that we have the so-called B-

coefficients in the example which follows.

16

17

18

19

20

21

[1] A. Bergen and V. Vittal, “Power System Analysis,” Prentice-Hall, 2000.

[2] W. Meyer, “Efficient computer solution for Kron and Kron-Early Loss

Formulas,” Proc of the 1973 PICA conference, IEEE 73 CHO 740-1, PWR,

pp. 428-432.