earthing of 11kv and 33kv rural substations - · pdf file•the neutral earthing resistors...

12
Jan 2016 Earthing of 11kV and 33kV Rural Substations

Upload: vokiet

Post on 15-Mar-2018

280 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Jan 2016

Earthing of 11kV and 33kV Rural Substations

Page 2: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Earthing Overview

• Earthing is not a ‘black art’ – but it is not simple either!

• An effective and functional earthing system is a legal requirement:

• Electricity at Work Regulations (1989)

• Electrical Safety, Quality and Continuity Regulations (2002)

• Earthing is governed by many different standards:

• ENA TS 41-24, ENA S34, BS EN 50522, BS 7671, BS EN 60479, DNO requirements and IEEE-80

• If an Earth Potential Rise (EPR) is less than 430V a site is classed as ‘cold’ and

touch and step voltages are considered to be acceptable.

• Where an EPR exceeds 430V special measures are required.

www.sp-eng.co.uk

Page 3: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Common Assumptions Can be Dangerous!

• Earthing at 33kV and 11kV substations is simple.

• If normal DNO practice is followed the design will be ok.

• The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels - so

secondary substations will not be classed as hot.

• Fences should always be independently earthed.

• Areas outside the substation do not need to be considered.

• There is no risk of transferred potential.

• HV and LV earths should always be combined.

www.sp-eng.co.uk

Page 4: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Secondary Substation Earthing Considerations

• Rural secondary substations have many issues that can make them difficult:

• They are usually overhead line fed - so there are no metallic return paths.

• Hot zones can extend significantly beyond the substation or transformer.

• Soil resistivity can often be poor, and getting a low grid impedance is challenging.

• Substations are physically small so only have a limited area in which to install an earth grid.

• Livestock are very susceptible to step voltages.

• The ground nearby can be very muddy and wet (i.e. low resistivity)

www.sp-eng.co.uk

Page 5: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Example – 11kV Substation

• Consider a simple 11kV rural substation:

• Fed via overhead lines & No other metallic paths

• Earth fault level (IE) of 450A

• Earth grid impedance (ZE) of 9 Ohms

• EPR = IE * ZE

• EPR = 4050V !!!

• Although the fault level is low, the site must be classed as hot.

• This design could present a significant hazard to personnel and livestock!

www.sp-eng.co.uk

Page 6: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Example – Step Profile of 11kV Rural Substation

www.sp-eng.co.uk

Page 7: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Example – Touch Profile of 11kV Rural Substation

www.sp-eng.co.uk

Page 8: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Livestock Considerations

• A standard earthing design approach is not sufficient

• Livestock are very susceptible to step voltages:

• No protective footwear (!!!)

• Longer step length

• Often in wet and muddy fields (i.e. low resistivity)

• A Step voltage gradient as low as 40V is enough to kill a horse.

• Accidental death of livestock can lead to costs and negative publicity.

• BS EN 60479-4 provides details on fibrillation current for animals.

www.sp-eng.co.uk

Page 9: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Design Approach

• Any rural substation’s earthing design should be carefully evaluated.

• Reliance on DNO standard practices is not recommended!

• Site soil resistivity surveys are usually required.

• Hand calculations are laborious and use of simulation software is beneficial:

• Quickly evaluate the EPR and grid impedance

• Calculate Touch and Step Voltages

• Provide contour maps of the touch and step voltage profiles

• SPE uses industry leading software package ETAP for earthing studies

www.sp-eng.co.uk

Page 10: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Mitigation Measures

• When faced with a difficult earthing design, the standard approach is to add

more conductor and earth rods.

• This isn’t always beneficial as costs can be expensive and rods in proximity to

each other have reduced effectiveness.

• Alternative methods include:

• Deep earth electrodes

• Increase tripping time

• Use of protective surface layer

• Satellite earthing grid

• Ground enhancing materials (Bentonite, Marconite etc.)

www.sp-eng.co.uk

Page 11: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

Summary

• Correct earthing design is a legal responsibility.

• Small rural substations fed via overhead lines can often have a high EPR and be

classified as ‘Hot’.

• Relying on DNO standard designs is not appropriate.

• The zone of influence from a rural substation can pose a risk to personnel and

livestock.

• Livestock are very sensitive – a step voltage of 40V can be enough to kill.

• Soil resistivity surveys are always recommended.

• A good earthing design does not just simply add more conductor and rods.

www.sp-eng.co.uk

Page 12: Earthing of 11kV and 33kV Rural Substations - · PDF file•The Neutral Earthing Resistors on the 11kV and 33kV limit fault levels ... •They are usually overhead line fed ... •Although

What Next?

• All questions welcome!

• SPE’s website has a lot of further information, or contacts us to discuss your

issue.

• www.sp-eng.co.uk

[email protected]

• How can SPE help you with your design?

www.sp-eng.co.uk