REPORT NO. UCB/EERC-80/29 OCTOBER 1980 P382-111128 EARTHQUAKE ENGINEERING RESEARCH CENTER DYNAMIC PROPERTIES OF A TWELVE-STORY PREFABRICATED PANEL BUILDING by J.G. BOUWKAMP J.P. KOLLEGGER R.M. STEPHEN Report to the National Science Foundation COLLEGE OF ENGINEERING UNIVERSITY OF CALIFORNIA . Berkeley, California · REPRODUCED BY · · lfS. DEPARTlltIlT'OF COMMERCE SPRIltGfIEU!, VA 22161

Upload: others

Post on 30-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

REPORT NO.

UCB/EERC-80/29

OCTOBER 1980

P382-111128

EARTHQUAKE ENGINEERING RESEARCH CENTER

DYNAMIC PROPERTIESOF ATWELVE-STORYPREFABRICATEDPANEL BUILDING

by

J.G. BOUWKAMP

J.P. KOLLEGGER

R.M. STEPHEN

Report to the National Science Foundation

COLLEGE OF ENGINEERING

UNIVERSITY OF CALIFORNIA . Berkeley, California

· REPRODUCED BY

·1~~6~~flC~~C'~~~~~E· lfS. DEPARTlltIlT'OF COMMERCE

SPRIltGfIEU!, VA 22161

Page 2: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

For sale by the National Technical Informa­tion Service, U.S. Department of Commerce,Springfield, Virginia 22161.

See back of report for up to date listing ofEERC reports.

DISCLAIMERAny opinions, findings, and conclusions orrecommendations expressed in this publi­cation are those of the authors and do notnecessarily reflect the views of the NationalScience Foundation or the Earthquake En­gineering Research Center, University ofCalifornia, Berkeley

Page 3: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

FtEPORT DOCUMENTATION 11. REPORT NO.

PAGE NSF/RA-800596I~

3. Recipient's Accession No.

P8ft 1'1712 8

,U2860 0 3!

8. Performina Organization Rept. No.

UCBjEERC-80j29

5. Report Date

October 1980

7. Author(s)

J. G. Bouwkamp, J. P. Kollegger and R. M. Stephen

4. Title and Subtitle

Dynamic Properties of a Twelve-Story Prefabricated PanelBuilding

9. Performing Organization Name and Address 10. Project/Task/Work Unit No.

Earthquake Engineering Research CenterUniversity of California, BerkeleyRichmond Field Station47th Street and Hoffman BoulevardRichmond, Calif. 94804

11. Contract(C) or Graflt(G) No.

(C)

(G) PFR79-08257-2NF12. Sponsoring Organization Name and Address

National Science Foundation1800 G Street, N.W.Washington, D.C. 20550

13. Type of Report & Period Covered

14.

15. Supplementary Notes

16. Abstract (Limit: 200 words)

The results of forced and ambient vibrations studies of a twelve story apartmentbuilding, constructed with prefabricated wall panel and slab elements are presented.Dynamic characteristics, such as resonant frequencies, damping, and vertical andhorizontal mode shapes of the structure were determined and correlated with analyticalresults using the computer program TABS-77.

Rigid floor diaphragm action and serious structure-foundation interaction wereobserved. Including the foundation flexibility in the analytical model using experiment­al vibration data resulted in resonant frequencies and mode shapes showing excellentagreement with the test data. Accounting for the foundation flexibility using actualsoil and pile test data did not produce a satisfactory correlation with the dynamicvibration test results.

17. Document Analysis a. Descriptors

b. Identifiers/Open·Ended Terms

22. Price20. Security Class (This Page)

19. Security Class (This Report) 21. No. of Pages

/10\--------------+-_:--_-----

I

Release Unlimited

C. COSATI Field/Group

18. Availability Statemen~

(See ANSI-Z39.18) See Instructions on Reverse OPTIONAL FORM 2n (4-7n(Formerly NTI5--35)Department of Commerce

Page 4: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 5: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EARTHQUAKE ENGINEERING RESEARCH CENTER

DYNAMIC PROPERTIES OF A TWELVE STORYPREFABRICATED PANEL BUILDING

by

J. G. BouwkampJ. P. KolleggerR. M. Stephen

A Report to theNational Science Foundation

Report No. UCBjEERC-80j29College of Engineering

Department of Civil EngineeringUniversity of California

Berkeley, California

October 1980

Page 6: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 7: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

TABLE OF CONTENTS

TABLE OF CONTENTS .LIST OF FIGURES •LIST OF TABLESABSTRACT .

1. INTRODUCTION

1.1 General1.2 Acknowledgement.

2. DESCRIPTION OF BUILDING.

2.1 General2.2 Architectural Layout .2.3 Structural System .2.4 Soil Conditions .

3. FORCED VIBRATION STUDY .

3.i General3.2 Experimental Equipment

3.2.1 Vibration Generators.3.2.2 Accelerometers.3.2.3 Equipment for Measurement of Frequency.3.2.4 Recording Equipment .

3.3 Experimental Procedure and Data Reduction3.3.1 Resonant Frequencies3.3.2 Mode Shapes.3.3.3 Damping Capacities

3.4 Experimental Results •3.4.1 General3.4.2 Frequency Response Data .3.4.3 Mode Shapes.

3.5 Discussion of Experimental Results

4. AMBIENT VIBRATION STUDY

4.1 General4.2 Field Measurements

4.2.1 Measuring Equipment .4.2.2 Measurement Procedures .

Pagei

iiiv

vi

1

1

2

3

33

3

4

14

14

14

14

15

15

16

16

16

17

18

19

19

20

2223

45

45

46

46

47

Page 8: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 9: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

4.3 Data Analysis.4.3.1 Fourier Analysis4.3.2 Data Processing.4.3.3 Frequencies and Modes of Vibrations4.3.4 Damping

5. COMPARISON OF FORCED AND AMBIENT VIBRATION STUDIES

6. FORMULATION OF MATHEMATICAL MODEL

6.1 General.6.2 Computer Programs6.3 Modeling of Structure .6.4 Foundation Modeling. .

6.4.1 Vibration Test Data Process.6.4.2 Soil Data Process . .

6.4.2a Vertical Stiffness .6.4.2b Rotational Stiffness6.4.2c Lateral Stiffness

6.5 Analytical Results . .

7. CONCLUSIONS .

REFERENCES .

i i

Page4949494950

58

60

60606062626465666768

86

. . . 87

Page 10: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 11: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

LIST OF FIGURES

Figure

2.12.22.32.42.52.62.72.83.13.23.3

3.43.53.63.73.83.93.103.11

3.123.13

3.143.153.163.173.183~19

4.14.2

4.34.44.5

Wesley Manor Building.Typical Floor Plan .Typical Wall Panel Element .Typical Wall-Floor Joint ConnectionTypical Foundation PlanLocation of Soil BoringsLog of Borings .Key to Log of Borings .Vibration GeneratorVibration Force ys. Speed Non-Counterbalances .Location of Vibration GeneratorsCenter of Stiffness (C.S.), and Center of Mass (C.M.)Frequency Response:for NS 'Forcing.Frequency Response for EW Forcing .Frequency Response for Torsional ForcingLogarithmic Decay Data: 1st Mode NS (2.18 cps)Logarithmic Decay Data: 1st Mode EW (2.09 cps)Logarithmic Decay Data: 2nd Mode Torsion (1.76 cps)Fundamental NS Mode Shape (2.18 cps) .Vertical Mode Shape EW Forcing (1.76 cps) .Vertical Mode Shape EW Forcing (2.09 cps) .Vertical Mode Shape Torsional Forcing (1.76 cps) •Vertical Mode Shape Torsional Forcing (2.09 cps) .NS Floor Mode Shapes (2.18 cps)Floor Mode Sahpes EW Forcing (1.76 cps) .Floor Mode Shapes EW Forcing (2.09 cps) .Floor Mode Shapes Torsional Forcing (1.74 cps)Floor Mode Shapes Torsional Forcing (2.08 cps)Ambient Vibration Equipment.Location of Ranger Seismometers on the 12th Floor forResonant Frequency Response .Location of Ranger Seismometers for the Mode Shapes .NS Vertical Mode Shapes (2.23 cps)EW Vertical Mode Shape (1.80 cps) .

iii

Page

· 6

· 7· 8

9

1011

12132627

28

· 293031

· 32· 33

34· 35· 36· 37· 38· 39· 40

· 41· 42· 43· 44· 51

· 51· 52· 53.54

Page 12: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 13: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

4.64.74.86.16.26.3

6.46.56.66.76.8

6.9

6.10

6.11

6.126.13

6.146.156.166.17

Torsional Vertical Mode Shape (1.80 cps) .Torsional Vertical Mode Shape (2.19 cps) .Torsional Vertical Mode Shape (2.15 cps)Typical Wall Element Formulation2 Degree of Freedom Model for the Dummy Story .Experimental DataSoil Section .Shear:Nodulus of the Soil.Foundation Plan .Variation of Skin Friction and Axial Force in the Pile .Finite Element Modeling of the SoilSimplified Beam Foundation Model for the Rotational Stiffness.Variation of the Modulus of Soil Reaction kn .Pile Deflections .NS Vertical Mode Shapes (2.18 cps)EW Vertical Mode Shapes (1.76 cps) .EW Vertical Mode Shapes (2.09 cps)NS Floor Mode Shapes (2.18 cps) •EW Floor Mode Shapes (1.76 cps) .EW Floor Mode Shapes (2.09 cps) .

iv

Page55565770

71

71

72

73747576

77

78

79

80

818283

8485

Page 14: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 15: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

..

Table

3.1

3.2

3.3

3.44.14.25.1

6.16.2

6.3

6.4

LIST OF TABLES

Resonant Frequencies (cps) .Dampimg Ratios .Summary of the Building Response at ResonanceComparison of Fundamental Experimental and UBC PeriodsResonant Frequencies (cps) .Damping Ratios .Comparison of Resonant Frequencies and Damping Ratios .Dummy Story PropertiesLateral and Rotational Soil Stiffness .Vertical Pile StiffnessesExperimental and Analytical Frequencies

v

21

22

222450

50

58

63

646669

Page 16: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 17: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

ABSTRACT

The results of forced and ambient vibrations studies of a twelve

story apartment building, constructed with prefabricated wall panel and

slab elements are presented. Dynamic characteristics, such as resonant

frequencies, damping, and vertical and horizontal mode shapes of the

structure were determined and correlated with analytical results using

the computer program TABS-77.

Rigid floor diaphragm action and serious structure-foundation inter­

action were observed. Including the foundation flexibility in the

analytical model using experimental vibration data resulted in resonant

frequencies and mode shapes showing excellent agreement with the test

data. Accounting for the foundation flexibility using actual soil and

pile test data did not produce a satisfactory correlation with the

dynamic vibration test results.

vi

Page 18: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …
Page 19: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

1. INTRODUCTION

1.1 General

The design of multistory structures subjected to dynamic forces

resulting from foundation motions requires a consideration of both the

characteristics of the ground motion and the dynamic properties of the

structure. Ground motions as caused by an earthquake are random and,

although not prescriptible for aseismic design, have been fairly well

studied for certain well-known past earthquakes. The engineer is there­

for mainly interested in the dynamic properties of the structure when

designing for earthquake forces and is only indirectly concerned with the

ground motion characteristics.

High speed digital computers and more sophisticated idealizations

and computer model formulations of structures can predict the elastic and,

provided that proper non-linear algorithms can be defined, also the inelastic

response of such structures when subjected to earthquakes. However, the

accuracy of the results in large measure depend upon the computer model

formulation of the structure and its foundation. In order to determine the

accuracy of the calculated results and to accumulate a body of information on

the dynamic properties of structures, especially when these structures have

novel design features, dynamic tests have been conducted on full-scale

structures (1).

In order to evaluate the dynamic characteristics of a prefabricated

type structure, dynamic tests using both forced and ambient methods were

performed on the Wesley Manor Building in Campbell, California, a IIForest

City Dillon ll type prefab panel structure. Because of the potential advantages

of the ambient vibration method in dynamic testing of full-scale structures,

it was desirable to compare the results of both methods and to assess the

accuracy of each method in evaluating the dynamic properties of this structure.

1

Page 20: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

The building is described in Chapter 2, and the results of the dynamic

tests, from forced, as well as ambient vibration studies, are given in

Chapters 3 and 4, respectively. A comparison of the experimental results

obtained from both studies is presented in Chapter 5. For purposes of

correlation a mathematical model of the structural system was formulated, and

the calculated and experimental dynamic properties were compared. The for­

mulation of the mathematical model including the foundation, as based on

actual soil and pile data, and the analytical dynamic results obtained, are

described in Chapter 6. A general comparison and discussion of the experi­

mental and analytical results is presented in Chapter 7.

1.2 Acknowledgement

The authors gratefully acknowledge the financial support provided by

the National Science Foundation under Grant NSF PFR 79-08257-2NF. They also

wish to thank the owner, Wesley Manor, Inc.; the architects, Ogren, Juarez

and Givas, especially Mr Bob Ogren; and the contractors, Campbell Construction

Company of Sacramento and Tecon Pacific especially Mr. Jim Clark of Tecon

Pacific, for their help and cooperation in coordinating and carrying out

the test program.

2

Page 21: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

2. DESCRIPTION OF BUILDING

2.1 General

The Wesley Manor Building in Campbell (Fig. 2.1), a Forest City Dillon

reinforced concrete prefab building, was tested in October 1978. This

building system uses solid slab elements and cellular wall panels. At the

construction, reinforcement is placed in the cells which are -subsequently

grouted. As the modular design of the building system includes prefabricated

kitchen and bathroom units, construction progressed at a rate of about one

story every two days.

2.2 Architectural Layout

The overall floor dimensions of the Wesley Manor Building are approxi­

mately 164 1 x 80 1• The building has 12 stories for a total height of 105 1 -4".

The building contains only apartments, except for a portion of the first

floor where space is reserved for laundry rooms, mechanical rooms, lounge

and a reception area. The building is serviced by two elevators, located

in the center. In addition, stairwells are located on either end of the

building as shown in Fig. 2.2.

2.3 Structural System

The vertical and horizontal load-carrying system consists of reinforced

concrete shear walls in both the transverse and the longitudinal directions.

These walls have a typical thickness of 8 in. over the entire height of

the building. Wall reinforcement placed in the cells varies over the

height as shown in Figure 2.3. The minimum concrete strength for the

panels and grout is specified as f~ = 4000 psi. The overall wall design

effectively results in a shear wall system.

3

Page 22: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

The solid floor slab elements are 4 in. thick, with plan dimensions

of 8 1 by 22 1• At the site additional reinforcement is placed across the

22 ft. long s"lab functions (#4 x 41 -0" @ 18" c.c.) and a 4 in. concrete

topping is placed over these elements, thus resulting in a total slab thick­

ness of 8 in. Details of exterior and interior wall-to-f100r panel joints

are shown in Figure 2.4. The prefabricated kitchen and bathroom units have

a slab thickness of 8 in. with protruding reinforcing bars tying into

the adjacent 4 in. thick topping slab to provide continuity.

The structure is founded on piers with a diameter of 24 in. and

varying lengths from 30 1 to 53 1• The piers are located at intervals of

approximately 5 feet, as shown in Fig. 2.5. The same figure also shows

through solid lines the layout of the first-floor walls.

2.4 Soil Conditions

The following excerpts, describing the soil conditions at the site

and Figures 2.6 through 2.8 are taken from the report by LeRoy Crandall and

Associates, Consulting Geotechnical Engineers, Los Angeles, CA as provided

by the project architect.

"Evidence of existing fill (debris, etc.) was not encounteredin the exploration borings."

"The natural soil beneath the site consists of sandy silt, under­lain by sand, sandy silt, silty clay and clayey silt. The uppernatural soils are moderately firm to firm at ~resent moisturecontent but would become weaker and more compressible when wet.Below depths of 30 to 35 feet, the soils are firm to very firmwith layers of moderately firm soils." /

"Borings 1 through 3 (as identified in Fig. 2.6) wer~rilled usingrotary wash-type drilling equipment with drilling mud to preventcaving. The mud was removed following completion of the drillingto permit water level measurement. Observation 16~ hours afterremoval of the mud in Boring 2 indicated no water in the boring.

4

Page 23: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

Borings 4 and 5 were drilled to a depth of 50 feet using conven-

ti ona1 bucket-type dri 11 i ng equi pment and water was not encounteredwithin the depth explored. Since raveling occurred in Boring 5;however, casing or drilling mud was not used to extend the boring

to the desired depth."

The results of Boring 2, located under the center of the building,

is presented in Figure 2.7; the key to log of borings is shown in

Figure 2.8.

5

Page 24: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

6

>­w---'V1w3

N

Page 25: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

1'1 IIo 2

5'-11 3/4"if i ItN

I T I 1r-1 -

...J r- -T...J

"1r-1

LlJ

...J

3=22'-9"

...J

a::

-LlJ

~ + 79'-1

3=a::

(f)~

10'-3"-

(f)

1 _-- 22'-9"

---1~~1ELEVATORS

I -t,T F-23'-S"-+j I-

I

I II

2S '-4 3/4'

-,I -®-14'-03/4'1 ~ 6 at 22'-8" .1 r-14'-03/4'

... 164 1 - I 1/2 II •

~~_I i iT@­

®-®®-@0--

'-J

FIG. 2.2 TYPICAL FLOOR PLAN

Page 26: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

6th FLOOR

I st FLOOR

3rd FLOOR

9 th FLOOR

5th FLOOR

8th FLOOR

4th FLOOR

2nd FLOOR

7th FLOOR

IIth FLOOR

lOth FLOOR

12th FLOOR

2#9

IREINFORCING SYMETRICAL TO WALLi CENTER LINE

32'-0'II. 61'---1 ~_.....::.=..r-=---~

=-j ROOF1#7--

®1 #7

2

2#JJ--;<IIr"IT

@

2#11

®

1 #9---

®2 #9

@

2 #11@

2 #11

@

2#11

®

-co 2 #11,co @~ 2#11

®

b 2 #1 I ---j~+-m-6 @m-¢:..-1----lt=~HT-f1+_fnlfT1JI

FIG. 2.3 TYPICAL WALL PANEL ELEMENT

8

Page 27: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

ED WITHETE

1- ALL CELLS FILLV4000psi CONCR

1"/ f 4"TOPP'NG

"'- ,• -\,.

• '\ ,'"I

...... 211

"'--:ff:4atI2 I1 c.C1-

=f"~

'-v

at 12 11 c.c.

X 21-a ll COIL

ROD.

-,- ~411all i!==:-:==~

....i II 4"

J ..-

#5 x4 1-IO II

V~

3/411 epIr- ""'\ /

cl:7 • /~

'- I.-.u

FIG. 2.4 TYPICAL WALL-FLOOR JOINT CONNECTION

9

Page 28: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

tII

(5)N

2) (6) (7) (8) (9) (12

1¥1 Eh~ I I I10.01 10.01 1°1°

° °

~

o

31-6" ---.!caa--(TYP.)

I°1°1 ::itl° °- - - .....

2411

<1> PILES- LENGTH, FROM 29 1-6" TO 52'-611

FIRSTFLOORWALLS

FIG. 2.5 TYPICAL FOUNDATION PLAN

Page 29: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

~--

rociom•

(!) V)

Z t!'- :z:0 ....

c::::-I 0- lXl::J ...Jm ....

(\J 0~ ci V)

0 0 LL.Z .m 0

« :z::E 0....

t->- <uI.LJ 0-I ...J

enI.LJ U)

~.

(\J

.t!'....LL.

•-ci0m

II

__L _II

J 3A'fI N01.1IW'fIH 01. ---O~'11\31n08 ~31S3H:>NIM

11

Page 30: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

55

50

~'::;I--

MLI CLAYEY SILT- BROWN

II

45 ML SANDY SILT-BROWN

9.0 1 1031 22 1 THIN LAYER OF SILTY SAND

ML CLAYEY SILl'- BROWN

95

90

18

12.51 99

521

17.51 99

BORING 2DATE DRILLED APRIL 16 1 1977

EQUIPMENT USED 5" DIAMETER ROTARY WASH

LOCATIONELEVATION 98.4

SANDY SILT - SOME CLAY, FEW GRAVEL, BROWN

SANDIER

THIN LAYERS OF SAND, FEW GRAVEL

THIN LAYERS OF 51 LTV SAND

SILTY CLAY- BROWN

SILTY SAND - FINE, ABOUT IQ% GRAVEL, BROWN

SAND- WELL GRADED, ABOUT 30 % GRAVEL BROWN

8

9

5.91131 1 71

IZ.31114

18.91109

IZ

ZZ

12

35#

10 I I I I I lili

15 1 I'Z.71 114 1 7 1 ~i

20 I I I I I II1I

25 I I 1 I 1 ll'!'JI I

30 I I I I I [::;yd

85

60

65

75

70

80SANDY SILT - SOME CLAY, ABOUT 10% GRAVEL

BROWN

THIN LAYERS OF SilT

SAND- WELL GRADED ABOUT 20% GRAVEL.GREYISH - BROWN

Ii'

50

18

70~«;.'l

51

55 I 1'7.71108115 I ~!:il

i(~1 ML

'I~!;60+1-+-1-1-1---111---+1~IiH

:;:·;dsw8.8 IIZ8 1 56 1 "t:':

,"',::,

65 I I I I I l;i:t.:1

50 +-- I I I I IiHI

35

30

40

45

UZ5

Iloon I I I 1:.;,.] I75

......N

40 I , I « f ,.Y,.-« I

FIG. 2.7 LOG OF BORINGS

Page 31: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

L. C. & A. SAMPLING: (Sampler Diameter - 1.0. = 2.625".0.0. = 3.188")

5 ~ Depth at which undisturbed sample taken

1__- Energy required to drive L C. & A. sampler 12", In ft. -kips per ft.:

Driving Weight = 350 lbs. Stroke = 1~'

STANDARD PENETRATION TEST:

22 ~ Depth at which test performed

LNumber of blows required to drive Standard Penetration sampler 12":

DATUM:

Ori'vi n9 Wei ght = 140 lbs. Stroke = 2~'

Elevations refer to assumed datum; see Plate 1.

CLASSIFICATION SYSTEM:

Unified Classification System (Plate A-3).

FIG. 2.8 KEY TO LOG OF BORINGS

13

Page 32: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

3. FORCED VIBRATION STUDY

3.1 General

The forced vibration study was carried out and completed during

October 1978. The bUilding was structurally completed prior to the

experimental work. The experimental apparatus employed in the dynamic test

is described below. The general experimental procedures, equipment used,

and procedures for data reduction applied, for forced vibration study

conducted are also described. Finally, the experimental results are presented

and discussed.

3.2 Experimental Equipment

The experimental apparatus employed in the tests were two vibration

generators, twelve accelerameters and equipment for the measurement and

recording of the frequency responses. The apparatus is described in the

following sections.

3.2.1 Vibration Generators

Forced vibrations were produced by two rotating-mass vibration

generators or shaking machines, one of which is shown in Fig. 3.1. These

machines were developed at the California Institute of Technology under

the supervision of the Earthquake Engineering Research Institute for the

Office of Architecture and Construction, State of California. Each machine

consists of an electric motor driving two pie-shaped baskets or rotors,

each of which produces a centrifugal force as a result of the rotation.

The two rotors are mounted on a common vertical shaft and rotate in

opposite directions so that the resultant of their centrifugal forces is

a sinusoidal rectilinear force. When the baskets are lined up, a peak

value of the sinusoidal force will be exerted. The structural design of

the machines limits the peak value of force to 5,000 lbs. This maximum

14

Page 33: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

force may be attained at a number of combinations of eccentric mass and

rotational speed, since the output force is proportional to the square of

the rotational speed as well as the mass of the baskets and the lead

plates inserted in the baskets. At higher speeds the eccentric mass

must be reduced in order not to surpass the maximum force of 5,000 lbs.

The maximum operating speed is 10 cps, and the minimum practical speed is

approximately 0.5 cps. At 0.5 cps with all lead plates in the baskets, a

force of 200 lbs. can be generated. The relaUonship between output

force and frequency of rotation of the baskets for different basket loads

is shown in Fig. 3.2.

The speed of rotation of each motor driving the baskets is controlled

by an electronic amplidyne housed in a control unit. The control unit

allows the machines to be synchronized or operated 1800 out-of-phase.

This makes it convenient to excite, in structures with a line of symmetry,

either torsional or pure translational vibrations without changing the

position of either machine. Acomplete description of the vibration gen­

erators is given in (2).

In the subject study the vibration generators were mounted on the

12th floor at the east and west sides of the building, as indicated in

Fig. 3.3; namely, about 80 feet. Associated vibration control and

recording equipment was also placed on the 12th floor.

3.2.2 Accelerometers

The transducers used to detect horizontal floor accelerations of the

building were Statham Model A4 linear accelerometers, with a maximum

rating of ± 0.25 g.

3.2.3 Equipment for MeasurernentofFreguency

For the vibration generators, the vibration excitation frequencies

were determined by measurement of the speed of rotation of the electric

15

Page 34: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

motor driving the baskets. A tachometer, attached to a rotating shaft

driven by a transmission belt from the motor, generated a sinusoidal signal

of frequency 300 times the frequency of rotation of the baskets. Hence,

the maximum accuracy of frequency measurements was ± 1 count in the total

number of counts in a period of 1 second (the gating period), i.e., ± 1/3

of 1% at 1 cps and ± 1/9 of 1 %at 3 cps.

3.2.4 Recording ~guipment

The electrical signals for all accelerometers were fed to amplifiers

and then to a Honeywell Model 1858 Graphic Data Acquisition System with

8-in. wide chart. In frequency-response tests, the digital counter reading

was observed and recorded manually on the chart alongside the associated

traces.

3.3 Experimental Procedure and Data Reduction

The quantities normally determined by a dynamic test of a structure

are: resonant frequencies, mode shapes, and damping capacities. The

experimental procedures and reduction of data involved in determining

these quantities are described in the next section.

3.3.1 Resonant Frequencies

With the equipment described on the previous page, resonant fre­

quencies are determined by sweeping the frequency range of the vibration

generators from 0.2 to 10 cps.

In the case of the vibration generators, the exciting frequency is

increased slowly until acceleration traces on the recording chart are

large enough for measurement. Above this level, the frequency is increased

in steps until the upper speed limit of the machine is reached. Near

resonance, where the slope of the frequency-response curve is changing

16

Page 35: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

rapidly, the frequency-interval steps are as small as the speed control

permits. These steps are relatively large in regions away from resonance.

Each time the frequency is set to a particular value, the vibration response

is given sufficient time to become steady-state, before the acceleration

traces are recorded. At the same time, the frequency of vibration, as

recorded on a digital counter, is observed and written on the chart with

its corresponding traces. Plotting the vibration response at each

frequency step results in a frequency-response curve.

Frequency-response curveS in the form of acceleration amplitude

versus exciting frequency may be plotted directly from the data on the

recording chart. However, the curves are for a force which increases

with the square of the exciting frequency, and each acceleration amplitude

should be divided by the corresponding square of its exciting frequency

to obtain so-called normalized curves equivalent to those for a constant

force (assuming linear stiffness and damping for the structural system).

If the original acceleration amplitudes are divided by the frequency to

the fourth power, displacement frequency-response curves for constant

exciting forces are obtained. In cases of fairly low damping (under 5% ),

there is little difference between results obtained for resonant fre­

quencies and damping capacities measured from the different curves.

3.3.2 Mode Shapes

Once the resonant frequencies of a structure have been found, the

mode shapes at each of these frequencies may be determined. In this study,

with twelve accelerometers available, it was decided to develop the mode

shapes by taking simultaneous measurements at each floor, with one

accelerometers kept in reserve.

The structure was vibrated at each of the resonant frequencies, and

the vibration amplitude was determined for all accelerometers at each

frequency.17

Page 36: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

It is generally necessary to make corrections to the recorded ampli­

tudes to compensate for differences between calibration factors for each

accelerometer. Absolute calibration is not required for mode shapes, and

cross-calibration is sufficient. The accelerometers and all equipment

associated with them in their respective recording channels are cross­

calibrated simply by placing them all together and measuring the vibration

amplitude of all the accelerometers when the structure is vibrated at

each of the resonant frequencies. Cross-calibration is generally carried

out at the beginning and end of each day. The average calibration factors

as derived from the pre- and post-test cross-calibration runs are used

to adjust the recorded amplitude.

In general, the number of points required to define a mode shape

accurately depends on the mode and the number of degrees of freedom in the

system. For example, in a dynamic test on a 15-story building (3) four

points were sufficient to define the first mode, whereas it required measure-

ments of the vibration of all 14 floors and the roof to define the fifth

mode shape accurately.

3.3.3 Damping Capacities

Damping capacities may be found from resonance curves in the normal­

ized frequency-response curves by the formula:

~ =t;f2f

where

~ = damping factor,

f = resonant frequency,

t;f = differences in frequency of the two points on the resonancecurve with amplitudes of 1/12 times the resonant amplitude.

18

Page 37: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

Strictly, the expression for ~ is only applicable to the displacement

resonance curve of a linear, single degree-of-freedom system with a small

amount of viscous damping. However, it has been used widely for systems

differing appreciably from that for which the formula was derived, and it

has become accepted as a reasonable measure of damping. In this respect,

it should be remembered that in the case of full-size civil engineering

structures, it is not necessary to measure damping accurately in a per­

centage sense. It is sufficient if the range in which an equivalent vis­

cous damping coefficient lies known. Meaningful ranges might be

defined as: under 1%, 1-2%, 2-5%, 5-10%, over 10% (1,4).

The bandwidth method described above is extremely useful when the

damping factor lies in the range of 1-10% of critical. However, if the

damping lies below 1%, difficulties may be encountered in observing suf­

ficient points on the resonance curve. Also, the small frequency difference

between two relatively large frequencies becomes difficult to measure

accurately. Above 10% of critical damping, resonance curves often become

poorly defined due to interference between modes, and the results from

the bandwidth method have little meaning.

3.4 Experimental Results

3.4.1 General

The vibration equipment was bolted to the 12th floor throughout

the test program as shown in Figure 3.3. Also shown are the centers of

stiffness (C.S.) and mass (C~M.) as derived analytically. The selection

of the location of the two vibration genreators is typically guided by

the structural layout of the building to be studied, and thus, the

anticipated dynamic response. In that respect, ideally, the shakers

should be placed along one of the center lines and as far apart as possible

19

Page 38: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

(the latter requirement to achieve a maximum torsional input under a

180o-out-of-phase excitation). As it was not possible in this case

to install the equipment along the EW center line, it was decided to place

the shakers as close as practically possible near that center line.

Admittedly, the center line itself is an arbitrary line as it is based in

the anticipated center of stiffness.

In general the vibration equipment allows excitation of a structure

in both the NS, EW and torsional modes. Even with a certain off-line

position (or eccentricity) of the equipment separate excitation of the

translational and torsional frequencies normally cause little trouble,

provided the translational and torsional resonance frequencies are

sufficiently separated and the structural damping is small (less than

2 to 3% of critical). However, the Wesley Manor Building was found to be

highly susceptible to a trnaslational (EW) - torsional coupling. Hence,

with the shakers operating in a translational longitudinal (EW) forcing

manner, the structure failed to develop a clean translational excitation.

Instead, at resonance, a combined translational-torsional motion developed.

In fact, the frequency response behavior of the building under longitudinal

translational excitation and torsional excitation was found to be virtually

identical, indicating the absence of a true translational resonance condition.

3.4.2 Frequency Response Data

The frequency response curves for North-South, East-West and torsional

forcing conditions are presented in Figures 3.4, 3.5 and 3.6. The first

figure shows a clear N-S translational resonance frequencies at about 2.2

cps. However, Figures 3.5 and 3.6 both indicate a large response at about

1.76 cps and a considerably smaller at about 2.10 cps. The results seem to

indicate that the translational and torsional resonance conditions coincide;

20

Page 39: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

an unusual condition. The basic response signals for the EW excitation were

EW accelerations, while for the torsional excitation (NS 1800 out-of-phase)

NS accelerations were recorded. In general, the curves are plotted in

the form of normalized displacement amplitude versus exciting frequency.

The ordinates were obtained by dividing the measured acceleration by the

square of the exciting frequency (cps) to obtain acceleration amplitudes

for a constant equivalent force amplitude, i.e., the force amplitude that

would be generated by the eccentric masses rotating at 1 cps. The values

thus obtained are divided by the square of the circular frequency (rad/sec)

to obtain normalized displacement amplitudes. Also presented in Figures 3.4

thru 3.6 are the actual exciting force (Fr ) and displacement amplitude (ur )

for each of the resonance frequencies, as well as the calculated damping

ratios.

The resonant frequencies and critical damping percentages derived

from the frequency response curves are summarized in Tables 3.1 and 3.2,

respectfully. Also shown in the last table are the damping values obtained

from free-vibration decay data. In that case the free vibration of the

building was recorded following resonance excitation and subsequent stoppage

of the vibration generators. The pertinent vibration data are plotted in

Figures 3.7 thru 3.9.

TABLE 3.1 RESONANT FREQUENCIES (cps)

Excitation

. NS

EWEW

TorsionalTorsional

Frequency (cps)

2.18

1.762.09

1.752.09

21

Page 40: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

TABLE 3.2 DAMPING RATIOS

Excitation (cps) From Resonance Curves From Decay Curves

NS (2.18) 2.2% 1.2%EW{1.76) 1.4% ---EW (2.09) 1.4% 2.8%Torsional (I. 75) 1.1% 1.8%Torsional (2.09) 1.3% ---

Finally, the exciting force (Fr ) generated by both shaking machines

and the corresponding displacement amplitude CUr) at resonance are tabulated

in Table 3.3

TABLE 3.3 SUMMARY OF THE BUILDING RESPONSE AT RESONANCE

I Excitation Force Response at 12th Floor [in.]orMoment Center West End

N-S (2.18 cps) I 5,905 LB 25. 62xl0- 3 -----

N-$ (2.22 cps) 984 LB 4.09xlO- 3 -----

E-W (l. 76 cps) 2,992 LB 20. 41xlO- 3 -----E-W (2.09 cps) 4,134 LB ! 11. 09x10- 3 -----

Tors. (I. 74 cps) 241,784 LBFT I ----- 41.84xlO- 3

Tors. (1. 76 cps) 141,256 LBFT f 31. 62xlO- 3

I-----

I

Tors. (1. 79 cps) 50,910 LBFT ----- I 9.18x10- 3

(2.08 cps)I I 20. 59xlO- 3Tors. 334,069 LBFT ! -----

II ITors. (2.12 cps) 73,214 LBFT j i 4.16xl0- 3

: ----- I

3.4.3 Mode Shapes

The vertical mode shapes under resonance are presented in Figures 3.10

thru 3.14. These mode shapes are plotted along vertical lines at the center

of the building and along a center line in the west side of the building.

22

Page 41: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

The NS motions are typically plotted to the right and the a~ motions to

the left of the two vertical axes (center and west side). As shown in

Fig. 3.10, a significant base rotation was recorded, indicating the need

to consider soil-structure interaction in any analytical procedure.

The horizontal mode shapes for both the 6th and 12th floor levels at

the different resonance frequencies are shown in Figures 3.15 thru 3.19.

General observations based on acceleration data recorded at different

slab locations, clearly indicated that the floor slabs acted as rigid

diaphragms. It should be noted that the NS resonance mode shapes are

NS-normalized at the center of the roof. However, all other mode shapes,

EW and torsional, are EW normalized at the center of the roof. Closer

Observation of the floor mode shapes at 1.76 cps for EW excitation and

1.74 cps for torsion indicates the clear absence of NS translation at the

center. However, for the 2.09 cps and 2.08 cps resonance conditions the

NS translational amounts to 30% - 40% of the normalized EW translational

modal component. The rotational contributions due to both EW and tor­

sional excitations are virtually the same, as shown in Figs. 3.16 and 3.17

(for EW excitation at 1.76 and 2.09 cps, respectively) and in Figs. 3.18 and

3.19 (for torsional excitation at 1.74 and 2.08 cps, respectively).

3.5 Discussion of Experimental Results

Only the first transaverse (N-S), longitudinal (E-W) and torsional

resonance frequencies could be excited. Equipment limitations prevented

the search for frequencies higher than 6.75 cps. Whereas the N-S mode

has only small contributions from E-W and torsional motion, the E-W and

torsional modes are highly coupled. This phenomenon is illustrated by the

frequency response curves of Figs. 3.4 and 3.5 with resonant frequencies

under both E-W and torsional excitation occurring at the same frequencies,

namely 1.76 cps and 2.09 cps.

23

Page 42: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

In case significant translational and torsional modal coupling occurs

at two resonant frequecnies, one could term the resonance condition with

the largest torsional components as the "torsional ll resonant frequency

and the other as the "translational" resonant frequency. However, as in

this case the torsional components are virtually identical, such identi-

fication is impossible. This rare condition makes modal identification

of the experimental data and a comparison with analytical results difficult.

The floor modes at the resonant frequencies were observed for the

12th and 6th floor. The floor slab behaved like a rigid diaphragm; a sig-

nificant result in the subsequent development of the analytical model of

this structure.

The damping factors were calculated from resonance curves (Figs. 3.4

through 3.6) and from force-vibration decay data (Figs. 3.7 through 3.9).

The results from the two methods, compared in Table 3.2, are reasonably

close and define a distinct damping ratio range of between 1 and 3%.

Finally, a comparison of the experimental resonance data with the

results of a standard UBC analysis of the fundamental period, as

T = 0.05 H;O- is of interest. The two different resonance data are presented

in Table 3.4.

TABLE 3.4 COMPARISON OF FUNDAMENTAL EXPERIMENTAL AND UBC PERIODS

Excitation Exp. Resonance UBC (sec.) Difference(sec.)

NS 0.46 0.59 - 22%

EW 0.57 0.41 + 39%0.48 +17%

As the experimental EW resonance conditions did not permit identifying the

fundamental EW resonance frequency, both resonance values are presented

in the table. Despite the uncertainty, the results indicate that for

24

Page 43: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

the short NS (or. according to the Code, the "weak" direction) the UBC

underestimates the effective stiffness (0.59 sec. versus 0.46 sec.).

This situation would effectively become worse if, according to the Code.

the foundation flexibility should be brought into account; thus increasing

the period to about 0.7 sec. On the other hand, a similar correction would

bring the Code and experimental EW resonance data in closer agreement.

However, most likely, the experimental data would still reflect a lower

stiffness condition in the longitudinal direction, than the Code would

imply.

25

Page 44: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

~lI' I

"

26

s..o...,"'s..Q)<:Q)

'"<:o.~...,"'s...0.~

>

......M

0>.~

u..

Page 45: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

MAXIMUM LOAD LIMIT = 5000 LBS.5000

en0z::>0ll.

ILl0 4000::>!::z(!)«:E

~ 30000::0LL

N «'-li=0::ILl 2000zI-

AMPLITUDE OF SINUSOIDALLYZ:::> VARYING INERTIA FORCE

ILl S2 = TWO SMALL WEIGHTS EACH..J BASKET(!) 1000 L3 = THREE PAIRS OF LARGEZ WEIGHTS EACH BASKET ETC.en..J NON-COUNTERBALANCED EXCITER

«I-0I- 0

0 2 4 6 8 10

VIBRATION EXCITER SPEED. CYCLES PER SECOND

FIG. 3.2 VIBRATION FORCE vs. SPEED NON-COUNTERBALANCED

Page 46: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

0 1/2"

5'-11 3/4"if i ItN

T I II i ilr--

..J ..J

T..J ..JW W~ .~

0: It) 0: 221-9 11~ -' ... 0.5' ~o -. + 79'·1

enjr-c.~ - en

• C.M. lI'-4~/2u-- "'-41/2"

I~FI,"-L * 1 221

-911

V '\I I

/"--"-3" f ".3·--li- ~23'_811--1

-'It '"r--:~ 28'-4 3/4 11

~

!®14'.03/4~ I. 6 at 22'· 8" ~ r-'4'. 0 3/4 "

... 164 I _ I 1/2 II )0.

®-@®

@­®-®®-®~

Nco

FIG. 3.3 LOCATION OF VIBRATION GENERATORS, CENTER OF STIFFNESS (C.S.) AND CENTER OF MASS (C.M.)

Page 47: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

E

2.62.52.4

WI t

S

ACCELEROMETERLOCATION

N

® Fr=984 LBUr =4.09 x 10-3 INe = 2.3 %

<D Fr = 5905 LB-3

Ur = 25.62 x 10 INe = 2.0%

2.1 2.2 2.3FREQUENCY (CPS)

2.01.9

FORCING NORTH-SOUTH

0' I I I I I I I I I

1.8

6

wo~ 5.....Ja..~<t1-_4ZNwo~wwenu ....... 3<tZ.....J-a.. '?Oen_o ~ 2oWN.....J<t~a::oZ

N1.0

FIG. 3.4 FREQUENCY RESPONSE FOR NS FORCING

Page 48: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

7 .CDR Q) Fr =2992 LB

Ur =20.41 x I03 1N

6 ' . c =1.4%FORCING

W .EAST-WEST

I \® Fr =4134 LB

NQ Ur= 11.09 x 103 IN::::> C ,. 1.4%.....

5...J WI IEQ....... )III

:2«..... - t t \ Sz(\J ACCELEROMETERW c...>::E W LOCATIONW en

w c...> "0 « z 3...J -g, '?O- -Q )(- 2QWN...J

+~ I«::Ea::: f= 1.760Z

01.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4

FREQUENCY (CPS)

FIG. 3.5 FREQUENCY RESPONSE FOR EW FORCING

Page 49: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

CD Fr =241,784 LBFT @) Fr = 334,069 LBFTUr =41.84 x 163 1N Ur = 20.59 x 10-3 IN( = 1.2% ( = 1.1 %

IS. FORCING ® Fr= 141,256 LBFT ® Fr =73,214 LBFTW TORSIONAL ~CD Ur =31.62 x 10-3 IN Ur =4.16 x 10-3 IN0 ( = 0.9% ( = 1.4 %:::> f= I.74t- @ Fr = 50,910 LBFT~0.. Ur = 9.18 x 10'3 IN N~ ( =1.1%«

tt- _ 10I

W IEZNWu f= 1.76~wwc/)

t/\ Sw u,

ACCELEROMETER,.... «z~- LOCATION0..'"c/)'o- -o )(0- 5WN:J«::Ea::0Z

01.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4

FREQUENCY (CPS)

FIG. 3.6 FREQUENCY RESPONSE FOR TORSIONAL FORCING

Page 50: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WN

I.O~

UJ 0.9'­C;:) 0.8r-zr 0.7

:E<t 0.6Zofi 0.5a:CD:> 0.4

CUJt:::!..J 03<t:Ea:oz

~ = 1.2 %

0.2b I 2 :3 .; 5 ~

NUMBER OF ELAPSED CYCLES

FIG. 3.7 LOGARITHMIC DECAY DATA: 1ST MODE NS (2.18 CPS)

Page 51: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

ww

1.0

I.LI 0.9C=> 0.8t-~ 0.7

:IE« 0.6Zoj:; 0.5<{0:m> 0.4

CI.LI~~ 0.3:IE0:oZ

~ =2.80/0

0.2' I I , , I •

o I 2 3 4 5NUMBER OF ELAPSED CYCLES

FIG. 3.8 LOGARITHMIC DECAY DATA: 1ST MODE EW (2.09 CPS)

Page 52: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

I.O~. I~ =1.8%1LI 0.90::::> 0.8....:J 0.70-:E« 0.6Z0j:; 0.5<ta:CD;; 0.4

w a-l::o 1LI

N

~ 0.3:Ea:0z

0.20 I 2 3 4 5 6

NUMBER OF ELAPSED CYCLES

FIG. 3.9 LOGARITHMIC DECAY DATA: 1ST MODE TORSION (1.76 CPS)

Page 53: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WEST CENTER

1.1039I

1.002?

0.926~

II0.713,

II~0.488

II

1°·327JO.243

IfO. 175

I.OO pI

0.917?

0.916/0

I0.789f

II

0.595J

III~0.434

II

7°·270

JO.204

I~ r°.l 52

~o 0

0.078 _ 0.096 0----uc~........-=~==----o-.......===-==-=-o~---

N-S ~I.....__~~...;;..;..:...;:..~_I__---+.1

FIG. 3.10 FUNDAMENTAL NS MODE SHAPE (2.18 CPS)

35

Page 54: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

1.277.

11.6

1.139

0.766

0.52

WEST CENTER1.00

0.876

0.571

0.337 0.343

0.227 0.234

0.161 0.251 lOI'-0

0.073 0.0790

0.083

~--j---EWgl. NS

EW

164.1 1

FIG. 3.11 VERTICAL MODE SHAPE EW FORCING (1.76 CPS)

36

Page 55: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WEST CENTER ~THIS VALUE

q 1.00 1.00'\ 0.33 REFLECTS NS--0 MOTION TYPICAL\

\ \0.718y 0.68~

0.604~0.654~

J0.593~0.604?

I ~I0.439 ~0.468 0.452\

II \

\/0.2920.350 0.326~

I \I \

0.208 f°.l80 0.199~\

0.155 ~0.131 0.148~, ,0.107 fO.0 93 0.101~ v

0.068 ,0

0.025 0----e

EW~l NS EW NS

J164.1'

FIG. 3.12 VERTICAL MODE SHAPE EW FORCING (2.09 CPS)

37

Page 56: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WEST

1.276~ 2.023~

1.162\ 1.81~1.142<1 01

\ I\ 1\ 1

O.756~ 1.277~

\ I\ I

0.509~ 10.825

\ I\ I

Q332~ 60.504

I0.230~ ~0.344

~ 0.161~ fO.338

o~_, 0.073

EW NS

79.9 1

(\JU)

oo

CENTER1.0(>-_

FIG. 3.13 VERTICAL MODE SHAPE TORSIONAL FORCING (1.76 CPS)

38

Page 57: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WEST CENTERoJ·OO _-00.401

0.741 Y 0.854rQ736~ 0.7771

0.573 \, 0.717p

\ I\ I

0.477~ 523~

\ I\ I\ I0.336y 10.319

\ I0.201b ~0.219

\ I0.150~ 1°.138

:; O.l04~ lo.102 ~

t~·=--==----.1'''9'0.-,.0.....2-.3~ ~~__-.a. _

EW

79.9

NS EW NS

FIG. 3.14 VERTICAL MODE SHAPE TORSIONAL FORCING (2.09 CPS)

39

Page 58: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

E

~

'- ,...-

I

w

s12th FLOOR

6th FLOOR

FIG. 3.15 NS FLOOR MODE SHAPES (2.18 CPS)

40

Page 59: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

12th FLOOR

6th FLOOR

FIG. 3.16 FLOOR MODE SHAPES EW FORCING (1.76 CPS)

41

E

Page 60: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

12 th FLOOR

6 th FLOOR

FIG. 3.17 FLOOR MODE SHAPES EW FORCING (2.09 CPS)

42

E

Page 61: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

12 th FLOOR

6th FLOOR

E

FIG. 3.18 FLOOR MODE SHAPES TORSIONAL FORCING (1.74 CPS)

43

Page 62: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

E

12th FLOOR

6th FLOOR

FIG. 3.19 FLOOR MODE SHAPES TORSIONAL FORCING (2.08 CPS)

44

Page 63: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

4. AMBIENT VIBRATION STUDY

4.1 General

Ambient vibration studies use field measurements of wind and micro­

tremor induced vibrations. The method has been in use for 45 years by

the United States Coast and Geodetic survey (6) to measure fundamental

periods of buildings. At present it is commonly used to identify higher

resonance frequencies and mode shapes (7,8,9,10,11,12).

The ambient vibration study of the dynamic properties of the structures

is a fast and relatively simply method of field measurements. It does

not interfere with normal building functions, and the measuring instruments

and equipment can be installed and operated by a small crew.

The objective of performing the ambient vibration study was to obtain

dynamic properties of the building and then compare these results with

those obtained from the forced vibration study to assess efficiency of

both techniques.

The ami bent vibration, experimental and analytical procedures were

first suggested by Crawford and Ward (7,12). An assumption in the analysis

technique is that the exciting forces are a stationary random process

possessing reasonably flat frequency spectrum. For multistory buildings

and other large above ground structures, the largest ambient vibrations

are produced by wind. If the frequency spectrum of the vibrational excit­

ing forces is reasonably flat, a structure subjected to this input will

respond in all its normal modes.

The vibration measuring equipment employed in the ambient vibration­

dynamic test is described below. The general experimental procedures and

procedures for data analyses applied are also described. Finally, the

experimental results are presented and discussed.

45

Page 64: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

4.2 Field Measurements

4.2.1 Measuring Equipment

The wind induced vibrations were measured using Kinemetric Ranger

5eismomenters, Model 55-1. The seismometer has a strong permanent magnet

as the seismic inertial mass moving within a stationary coil attached to

the seismometer case. 5mall rod magnets at the periphery of the coil

produce a reversed field which provides a destabilizing force to extend

the natural period of the mass and its suspension.

The resulting sei~ometer frequency was 1 Hz. Damping was set at

0.7 critical. The output for a given velocity is a constant voltage at

all frequencies greater than 1 Hz and falls off at 12 dB/octave for

frequencies less than 1 Hz.

The Kinemetrics Signal Conditioner, Model SC-1 (Fig. 4.1) was used

to amplify and control simultaneously four seismometer signals. The four

input channels have isolated circuitry to integrate and differentiate the

amplified input signal. All outputs are simultaneously or independently

available for recording. A modification to the signal conditioner allows

for outputing each channel separately or for taking the sum or difference

on two channels and outputing the average of those channels. Each channel

provides a nominal maximum gain of 100,000. An 18 dB/octave low pass

filter is available with a cut-off frequency continuously selectable

between 1 Hz and 100 Hz for each channel.

The amplified analog signals were recorded and directly converted to

digital format using the Kinemetrics Digital Data System, Model 005-1103.

A direct recording oscillograph was provided to display and monitor the

four signal levels during tape recordings. The data was digitized at 40

samples per second. The DDS-1103's rate of scan across multiple input

channels is 40,000 Hz. This rapid scan rate is sufficient to retain the

phase relationship between channels.

46

Page 65: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

A Rockland FFT 512/S Real-Time Spectrum Analyzer was used in order

to facilitate the rapid determination of the modal frequencies (Fig. 4.1).

This unit is a single channel analyzer with 512 spectral lines calculated

but only 400 lines displayed to reduce aliasing errors. Twelve analysis

ranges are provided from 0-2 Hz to 0-10 KHz.

4.2.2 Measurement Procedures

When measuring ambient and forced vibrations of the buildings, it is

usually assumed that the structure can be approximated by a one-dimensional,

damped discrete or continuous system. In most of the cases (10,11,13),

measurements indicate that for the level of excitation applied, floor

structures are sufficiently stiff so that the above assumption is acceptable.

In the experimental study of building vibration which is based on

the linear model, it is assumed that the resulting motions can be expressed

as the superposition of modes associated with the discrete frequencies

(14,15). This approach then requires a simultaneous measurement of motion

in a given direction at at least two different floors to obtain their

relative amplitude and phase, the two quantities needed to determine mode

shapes. During the measurements of wind induced vibrations, it is not

necessary to find the actual amplitudes that are recorded because all that

is eyer used in determining mode shapes is the relative amplitude of the

same two instruments.

The modal frequencies were obtained by placing seismometers near the

outer walls on the north and south and east and west sides of the 12th floor

of the building (see Fig. 4.2). They were oriented so that the signals from

the seismometers on the north and south sides could be used to detect

the east-west frequencies. Similarly, the signals from those on the

east and west sides were used to determine the north-south frequencies.

The signal conditioner was set so that seismometers 1 and 2 would be out-

47

Page 66: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

put as channel It giving the average of the sum of these two readings t and

channel 2t the average of the difference of seismometers 1 and 2. The out­

put of seismometers 3 and 4 were similarly averaged. In this waYt the

translational frequencies could be obtained from the average of the sum

of the seismoeter readings and the torsional frequencies from the average

of the differences of the seismoeters readings. TypicallYt the data was

recorded for a total of 300 seconds.

For determining the translational and torsional modest one pair of

seismometers always remained on the roof t as a reference placed near the

outer walls along either one of the building centerlines (see Fig. 4.3).

The second pair of seismometers was oriented in the same way and relocated

successively on each floor to allow the evaluation of the model response

over the height of the building (Figs. 4.4 through 4.8). As in the case

for determining the modal frequencies. the sum of the two seismometer

signals at each floor was averaged to give translational modal data. The

ratio of the two pairs of averaged readings provided a modal data point

normaltzed to the roof motion. Torsional modal information was obtained

in a similar manner t except that the difference t rather than the sum of

the seismometer signals at each floor level was used. On each channel

the low pass filter was set at 10 Hz to attenuate all higher frequencies.

thus completely remoVing electrical noise and other possible high frequency

vibrations. The voltage output to the recorder was adjusted to not exceed

about ±1.5 volts. The unattenuated calibration constant for the seiemometers

used was approximately 4.32 volts/in/sec. Corresponding first mode accel­

eration and displacement were about ± 0.03 x 10- 5 g and ± 5.5 x 10- 5 inches,

respectively.

48

Page 67: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

4.3 Data Analysis

4.3.1 Fourier Analysis

It is convenient to use Fourier transforms to analyze low level

structural vibrations (16), and exhibit the frequency content of the

recorded vibration, thus identifying modal frequencies when" the input

force frequency spectrum is reasonably flat. Comparing measured amplitude

and phase between various points on the structure provides an estimate

of the mode shape.

4.3.2 Data Processing

Four simultaneous outputs were recorded on magnetic tape during each

run. All runs were digitized at a sample rate of 40 discrete points per

second. Because of the high frequency filtering present in the field

instrumentation, no significant frequencies above 10 Hz were found in

the recordings. For the resonant frequency runs, 4096 data points were

selected for the translational and torsional modes. A total of 10 transforms

separated by 890 points were calculated and averaged over the 12107 data

points gathered.

For each mode shape run, 1024 data points were selected and a total

of 19 transforms were taken. The Fourier amplitude spectrum was an average

of the 10 transforms computed.

The spectral estimates were smoothed by 1/4, 1/2, 1/4 weights. The

1024 spectral estimates are uniformly distributed between 0 and 40 sample/

sec. giving a frequency resolution of 40/1024, or about 0.0391 Hz.

4.3.3 Frequencies and Modes of Vibrations

The natural frequencies of the excited modes are given in Table 4.1.

Mode sh~pes were calculated under both N-S and E-W forcing conditions as

49

Page 68: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

well as under torsion. The results, together with modal data from forced

vibrations are presented in Figs. 4.4 through 4.8.

TABLE 4.1 - RESONANT FREQUENCIES (cps)

Excitation Frequency IN-S 2.24E-W 1.82E-W 2.14

Torsional 1.82Torsional I 2.14

4.3.4 Damping

In the case of forced vibration study, damping in the structure can be

determined by the bandwidth method or by measuring a free vibration decay

response. In ambient vibration studies only the first method can be used,

provided that wind excitations are random and stationary in time (12).

Using the bandwidth method provided the dampings ratios as presented in

Table 4.2.

TABLE 4.2 - DAMPING RATIOS

Excitations

N-S (2.24 cps)E-W (1.82 cps)E-\~ (2.14 cps)

Torsional (1.82 cps) ITorsional (1.82 cps) i

Damping Factors

0.7 %0.9 %0.7 %1.2%0.8 %

50

Page 69: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

• • •

FIG. 4.1 AMBIENT VIBRATION EQUIPMENT

1+2 (N-S)

3+ 4 (E-W) r 1-2 (Torsion)

3-4 (Torsion)

4

2 1

3

0) TRANSLATIONAL MODE

4

2 1

~"

b) TORSIONAL MODE

FIG. 4.2 LOCATION OF RANGER SEISMOMETERS ON THE 12THFLOOR FOR RESONANT FREQUENCY RESPONSE

51

Page 70: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

enN

tN

2

2

12th FLOOR EW

4

4

3

OTHER FLOORS EW

12tb FLOOR NS

OTHER FLOORS NS

..

3

FIG. 4.3 LOCATION OF RANGER SEISMOMETERS FOR THE MODE SHAPES

Page 71: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

N

-------e-I79.9 1

R

12

II •10

- 9I'-/'()

LO 8mII

)( 7-I'-<0ex) 6 0

5

4

3

I.

----11--- 2-s to() a)

AMBIENT VIBRATION ---0- (2.23 cps)

FORCED VIBRATION • (2.18 cps)

FIG. 4.4 NS VERTICAL MODE SHAPE (2.23 CPS)

53

Page 72: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

R

12

II

10

9-l"-I'<)

10 8mII

)( 7-I"-1.0cri 6

5

4

3

2

S I"-eD

~----<ri

•I. 164.1'

N

--------

AMBIENT VIBRATION ---<>- (1.80 cps)

FORCED VIBRATION • (1.76 cps)

FIG. 4.5 EW VERTICAL MODE SHAPE (1.80 CPS)

54

Page 73: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

R 1.0ox

12,at

II /•10 oxl9 /

o x

8 /ox •

7 (x6 ox.

5 /ex

4 /r X

3 XI

2 /JM

AMBIENT VIBRATION ---0-- FROM E-W MOTION (I.SOeps)

AMBIENT VIBRATION )( FROM N-S MOTION (I.S0eps)

FORCED VIBRATION • (I.75 eps)

FIG. 4.6 TORSIONAL VERTICAL MODE SHAPE (1.80 CPS)

55

Page 74: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

--

1.0R •12

II

10

9

8

7

6

5

4

3

2 0

---------AMBIENT VI BRATION --0- (2.19 cps)

FORCED VIBRATION • (2.09cps)

FIG. 4.7 TORSIONAL VERTICAL MODE SHAPE (2.19 CPS)

56

Page 75: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

R x 0

12 III •10 xl9 xo

8 /.,7 /

x

6 xJo5 I

xo

4 IIt(()

3 ~2 Ieo

AMBIENT VIBRATION -0- FROM E-W MOTION (2.15 cps)

AMBIENT VIBRATION K- FROM N-S MOTION (2.15 cps)

FORCED VIBRATION .- (2.08 cps)

FIG. 4.8 TORSIONAL VERTICAL MODE SHAPE (2.15 CPS)

57

Page 76: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

5. COMPARISON OF FORCED AND AMBIENT VIBRATION STUDIES

The dynamic properties (resonant frequencies, modes of vibration and

damping values) of the Wesley Manor Building were determined by a full-scale

dynamic test using both forced and ambient vibration methods. Resonant

frequencies and damping factors from both studies are summarized and compared

in Table 5.1

The resonant frequencies from the forced vibration test are 2 to 4%

smaller than the resonant frequencies from the ambient vibration test.

This nonlinear effect reflects the greater effective stiffness under small

displacements. The same basic effects can be noted from the frequency shifts

under low levels of excitation, as illustrated in Figs. 3.4 and 3.6.

Equivalent viscous damping factors obtained from the two vibration

studies show some difference, indicating basically larger damping values

under increasing loads (or displacements). However, the differences are

not pronounced. In general, the results can be viewed more appropriately

as an indication of the range of damping, rather than as specific damping

values associated with each mode.

Mode shapes associated with translational (E-W and N-S) and torsional

excitations are compared in Figs. 4.4 through 4.8. The results from both

studies show good agreement.

TABLE 5.1 COMPARISON OF RESONANT FREQUENCIES AND DAMPING RATIOS

I Forced Vibration Ambient Vibration

Mode I Damping Ratios fromFrequency decay freq. response Frequency Damping

I (cps) curve curve (cps) Ratios

NS 2.18 1. 2 % 2.2 % 2.24 0.7 %-_.. '_.. ~- .. '-'-;'''-'' ....• -..... ,

EW 1. 76 - - - 1.4 % 1.82 0.9 %EW 2.09 1.8% 1.1 % 2.14 0.7 %

h_

Tors. 1. 75 2.8 % 1.4 % 1.82 1.2 %

Tors. j 2.09 - - - 1.3% 2.141

0.8 %1 ! io-.-_---J.

58

Page 77: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

Because of a total lack of vibration generation requirements and the

ease of equipment handling, the total field effort for ambient vibration

studies is significantly smaller than for forced vibration studies. Also,

because accurate frequence response data can not be generated under ambient

conditions, fewer measurements are required in such studies. Furthermore,

each meas~rement requires less time. On the other hand, data analysis is

slightly more complicate because of computer use for Fourier analysis.

59

Page 78: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

6. FORMULATION OF MATHEMATICAL MODEL

6.1 General

A mathematical computer model of the Wesley Manor Building was formulated

to assess its dynamic characteristics. The model was formulated using both

a rigid base and a flexible base. The computer program employed fn the

dynamic analysis of the model and the models themselves are described below.

6.2 Computer Program

TABS-77, a general computer program developed by the Division of

Structural Engineering and Structural Mechanics of the Department of Civil

Engineering at the University of California, Berkeley, was used to calculate

the frequencies and mode shapes of the building. A complete description

of this program is given in reference (17).

The dynamic analysis in this investigation were performed on a CDC 6400

digital computer using the standard TABS~77 program. The program considers

the floors rigid in their own plane and to have zero transverse stiffness.

All elements are assembled initially into planar frames and then transformed,

using the previous assumption, to three degrees of freedom at the center of

mass for each story level (2 translational, 1 rotational).

6.3 Modeling of Structure

The basic model of the building was formulated as a system of frames and

shear wall elements interconnected by floor diaphagms which were rigid in

their own plane and fixed at the 1st floor level.

All walls were treated as "wide columns". This required a reduction of

properties (I, A, Av) to the elastic centroid of each wall. Where a wall

is met by a perpendicularly oriented wall, a portion of the latter wall is

assumed acting as a flange and thus included in the resonant of inertia

calculation. For a IIhalf-flange ll condition, where two panels form a single

60

Page 79: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

corner, the effective flange width is considered as 1/6 of the overall

building height, or 11 1 -9". In case of a "full-flange Jl condition, as

shown in Fig. 6.1, the effective width is 1/3 of the height, or 23 1 -6".

The above assumption is based on the fact that the walls are effectively

interconnected at each floor level. The resulting dowel action over the

height of the building seems to justify the assumed wall coupling at least

under small amplitude vibrations.

Although not entirely correct for flanged shear walls, the shear area

(Av) for all walls were set to 5/6A, where A is the area of the wall parallel

to the direction of motion.

Wherever shear walls were positioned in one line parallel to the dir­

ection of motion, it was assumed that those walls would be coupled by a

portion of.the floor slab, having a width of 18 times the thickness of the

floor, or 12'. The effective span of these coupling girders was reduced

to the clear distance between the walls; a possible option of the TABS

program. In as far as the story deformation occur only over the clear dis­

tances between two stories, this effect needs to be captured. This can be

achieved by increasing the moment of inertia of each wall by the ratio

{Lo/Ll)3, where La is the story height and L1is the clear distance between

stories. In this case the amplification factor was typically {8.67/8)3 =

1.27. Fig. 6.1 illustrates the manner in which the shear walls were

idealized for the analysis.

In the analysis the modulus of elasticity for the reinforced concrete

was assumed as 4000 ksi. The effective floor mass, considering the floor

slab and structural walls only, was estimated at 53 kips sec2/ft. The rota­

tional mass, with a radius of gyration of 48.8 ft. was taken as 126,220 kips

sec2 /ft.

61

Page 80: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

6.4 Foundation Modeling

Initial analytical studies, assuming a rigid base, showed 30 to 50%

larger resonance frequencies than those obtained experimentally. Hence, it

was essential to account for the actual foundation stiffness. Two different

ways of obtaining stiffness values for the foundation, one using vibration

test data and the other using available soil data are described in the

following sections.

6.4.1 Vibration Test Data Process

The computer program TABS, used to compute the dynamic properties of

the structure, does not permit the input of rotational, lateral and vertical

springs at the foundation level. This makes it necessary to model a so

called IIdummy story" below the foundation level to account for the soil

stiffness. This can be achieved by determining for both the NS and EW

directions, dummy stories which properly reflect the translational and

rotational foundation stiffnesses for each direction. The solution of each

of the two 2-degree of freedom systems (see Fig. 6.2) follows from the

force-displacement relationship:

f::} = EI

4 6I - [2

-6 12[2 - P {::1 , where

M = overturning moment at the bas~,oV = base shear,or = base rotationm

rv = base displacement,

EI = flexural rigidity of dummy story, and

L = height of dummy story.

62

Page 81: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

With estimated constant floor masses of 53 kips sec 2/ft. for every

story and the measured rloor accelerations for the two fundamental trans­

lational modes it is possible to calculate the base shear and the over­

turning moment using the dynamic forces at the resonance frequency

(Fig. 6.3). Calculating the actual base displacement from the measured

acceleration at the base and approximating the base rotation by the secant

of the mode shape between the first and second floor, the force-displacement

relation can be solved for EI and L. The results for the uncoupled NS and

coupled EW/torsional modes are presented in Table 6.1.

TABLE 6.1 DUMMY STORY PROPERTIES

Mode Frequency (cps) L{ft) EI (kp. ft 2)

N-S 2.18 32.27 3.662*10 10

E-W/Torsion 1. 76 23.86 1. 962*10 10

E-W/Torsion 2.09 37.95 5.356*1010

As the dummy story height for both NS and EW directions has to be the same,

an optimum dummy story element had to be developed. Following several

alternatives, the length of the dummy story obtained from the uncoupled

NS mode was chosen for the analysis. Consequently the stiffness values for

the other modes had to be modified. The EI values were scaled by (Lo/L),

where Lo = 32.27 ft., thus setting the lateral stiffness right but changing

the rotational stiffness. The stiffnesses for the dummy as computed and

actually used in the model are summarized in Table 6.2. Using the dummy

story properties very good agreement between experimentally measured and

analytically computer frequencies and mode shapes could be achieved. But

since the prediction of the dynamic properties of a structure is essential ­

for a good design against earthquake loading, an attempt was made to model

the foundation using available information about the soil.

63

Page 82: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

TABLE 6.2 LATERAL AND ROTATIONAL SOIL STIFFNESS

From ExperimentalData

From Soil Data

N-S (2.18 cps)

4EIKROT = -L-

12EIKLAT =~

4.539 X 1012

L308 X 1010

[lb ftlrad]

r ~~ ]4.438 X 1012 11 b ftlLradJ

0.401 x 1010 [~~J*Soil Resistance

I:!i (1. 76 cps)

_ 4EIKROT - -L- 3. 291 x 1012 rl b f,t1

[ rad "J 19.277 X 10 12 - rigid

E-W (2.09 cps)

_ 4EIKROT - -L-

Actua lly usedin the Model

5.645 X 1012

6.020 X 1012

[lb ftJrad

nb ftJr rad

2.882 X 1012 - pile groupsI,II,III

12.7938 x 10 12 - flexiblestructure

E-W (1. 76 cps)

12EIKLAT =---cr

E-W (2.09 cps)

12EIKLAT = --c:rActually usedin the Model

6.4.2 Soil Data Process

1. 734 X 10 10 [~~] 0.401 X 10 10 [~~]*Soi1 Resistance

1.176 x 1010 [~~]

1. 734 X 10 10 [~~] II

The dynamic modulus of elasticity of the soil was determined by a seismic

downhole survey in boring 2 at the site (Fig. 6.4). The propagation velocity

of the shear waves was measured and together with the information about the

dry density used in the" formula v = IG*gjy (18), where

64

Page 83: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

v = velocity of the shear waves (ft/sec)

y = dry density (lbs/ft 3 )

g = constant of gravity (ft/sec 2 )

G = shear modulus of the soil (lbs/ft 2)

The increase of Gwith depth is shown in Fig. 6.5. A Poisson1s ratio of

0.3 was selected for the soil. It has to be noted that the shear modulus

decreases with higher shearing deformation and also depends on the frequency

of the loading. In this study constant values for G and v are used. The

structure is founded on piles as shown in detail in Fig. 6.6.

6.4.2a Vertical Stiffness

Since the piles are not resting on bedrock and the displacements

necessary to obtain point resistance are much larger than the displacements

for the development of skin resistance the point resistance was assumed

to be zero. A second assumption had to be made about the variation of the

skin friction along the pile. A triangular variation of skin friction with

the maximum at the top and zero at the pile point, yielding a parabolic

axial force distribution in the pile (see Fig. 6.7), was found to be in

agreement with experimental data (19) and previous modeling experience (20).

With these assumptions the stiffness Kp for each pile type could be calculated.

Because the pile transmits loads to the soil through friction, the skin

forces of the pile were applied to a finite element model of the soil directly,

rather than using a model of a pile-soil system and enforcing displacement

continuity at the nodes. The resulting axisymmetric 72 element model is

shown in Fig. 6.8, with the element G values based on the shear modulus data

presented in Fig. 6.5. The computer program FEAP (21) was used in this

analysis. The calculated displacement of the soil at the pile top permitted

an estimate of the soil stiffness Ks . The soil and pile stiffness were

65

Page 84: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

combined to give the stiffness of the pile-soil system for one pile in the

vertical direction by adding the flexibilities, I/Kv = I/Kp + I/Ks .

Table 6.3 summarizes the obtained values for the vertical stiffness (Kv).

The total vertical stiffness of the foundation is the sum of the individual

pile stiffnesses.

TABLE 6.3 VERTICAL PILE STIFFNESSES

(ft) Kp:(lbs/ft ) Ks(lbs/ft ),

Kv (lbs/ft)PHe Length I,

29.5 19.56 x 10' 4.35 X 10' 3.56 X 10'36.0 16.02 x 10' 5.06 X 10' 3.84 X 10'41. 5 13.24 x 10' 5.66 X 10' 3.97 X 10'

47.0 11. 92 x 10' 6.25 X 10' 4.10 X 10'

52.5 10.76 x 10' 6.85 X 10' 4.19 X 10'

6.4.2b Rotational Stiffness

The coordinates Ko'Vo of the resulting vertical stiffness of the entire

204 pile foundation were calculated using standard procedures (i.e., Vo =

(EKvi x Vi) ( E Kv;). Assuming that the pile-cap foundation plane remains

plane, or effectively the building acts as a rigid system, the rotational

stiffnesses of the entire foundation with respect to the NS and EW directions

can be determined (i.e., KROT-NS = E Kv; x~ , where Xi is the distance in

the EW direction between pile i and the center of stiffness), Table 6.2 shows

the results of these analyses and indicates for the NS direction an excellent

agreement between the calculated rotational stiffness and the experimentally

determined value. However, the calculated rotational stiffness for the

longer side of the building, in E-W direction, differs by a factor of about

6 from the experimental value. This result indicates that the assumption of

a rigid system is not true for the longer and more flexible direction of the

structure.

66

Page 85: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

In order to attempt to capture the effective foundation stiffness

several different stiffness assumptions were considered. For instance,

rather than considering the foundation as one single pile system, three

separate totally uncoupled rigid pile groups were considered as an alternative

system (see Fig. 6.6). In that case the combined EW rotational stiffness

was found to be in relatively close agreement with the experimental value;

namely, 2.88 x 1012 lb.ft/rad versus 3.30 x 1012 lb.ft/rad, respectively.

Of course using the separate three pile group approach for calculating the

NS rotational stiffness. the difference with the rigid approach is minimal.

and the agreement with the experimental results excellent.

A second alternative considered the entire building as a beam on an

elastic foundation. Without pursuing a detailed analysis, the building

was modeled as a simple beam, supported at the center of each of the earlier

noted three pile groups (see Fig. 6.9). The rotational stiffness in this

case, was found to be a factor of 4 too large. A more refined model. con­

sidering complete vertical shear deformation of the building and discrete

vertical pile stiffnesses may lead to a better correlation. However, such

an approach was considered beyond the basic scope of this investigation.

6.4.2c Lateral Stiffness

The later stiffness of a single pile was obtained by solving the. dl+u

equatlon EpI p dz4 = -p{z), where

EpI p = flexural regidity of the pile,

u = lateral deflection,

p{z) = reactive lateral pressure of the soil against the pile, and

z = depth.

This equation was solved numerically assuming that the ratio of pressure

(p(z)) to deflection (u) fulfills: p{z)/u = Kh = nh x z (22), where

67

Page 86: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

K= soil reaction modulus, and

n =coefficient of soil reaction (empirical quantity).

The coefficient of soil reaction was determined using a formula given by

Vesic (23),

B = diameter of the pile

Es = modulus of elasticity of the soil

v =Poisson's ratio for the soil (=0.3).

According to this assumption the soil reaction modulus Kh

increases

with depth as shown in Fig. 6.10. The pile deflections for both a rotation-

ally free and rotationally fixed pile head are shown in Fig. 6.11 and indicate

that the lateral deflections are almost zero below the 8 foot level. Thus,

it can be concluded that, in this case, the lateral pile stiffness only

depends on the soil properties of the uppermost layer.

Summing the lateral stiffness of all piles results in a total lateral

stiffness KLAT of 0.401 x 10 10 lb/ft, as noted in Table 6.2. This stiffness

is only about 25 to 30% of the experimentally derived values. This result

is not surprising as the total lateral stiffness is actually a result of

not only the lateral pile resistance but also, and seemingly more important,

of the resistance provided by the soil against the pile-cap beams and by

the possible friction between soil and floor slab.

6.5 Analytical Results

The final analytical model used in the correlative analyses had a simple

32 1 -4" high dummy story as discussed previously. The analytical results and

the experimental data for both forced and ambient vibration tests are pre­

sented in Table 6.4. Also presented are the analytical results assuming a

rigid base.

68

Page 87: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

TABLE 6.4 EXPERIMENTAL AND ANALYTICAL FREQUENCIES (cps)

\

i Experimentr'Forced 1 AmbientVibration I Vibration

Analysis ~Rigid I Flexible I

Base j Foundation 1

!

!III

ForcingDirection

E-WjTorsionE-WjTorsionN-S

1. 762.092.18

1.82

2.142.24

II 2.27I 2, 2.7i

! 3.14

1.71

2.082.19

Code

2.441.69

The results for the flexible base condition agree very well with the

experimental forced-vibration data. The slightly higher frequencies for

the ambient vibration results clearly indicates a foundation non-linearity.

In fact a softening of the foumdation modes increased forcing and displacements

levels as noted, could be expected.

For each of the three basic resonance frequencies the vertical center-

line mode shapes for both the experimental and analytical results are shown

in Figs. 6.12 through 6.14. The horizontal mode shapes for the 6th and

12th floors for the same resonance conditions are presented in Figs. 6.15

through 6.17. The results show in general an excellent agreement between

experimental and analytical data.

69

Page 88: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

NO DEFORMATION INSHADED AREA(REDUCES EFFECTIVELENGTH OF GIRDER)

DUMMY STORY

ELASTIC PROPERTIES(E,l ,A) OF WALL ELEMENTREDUCED TOCENTER LINE

12' PORTION OF/t'r.,4-- FLOOR SLAB COUPLES

WALL ELEMENTS

---~COLUMN WIDTH

IDEALIZED WALL ELEMENTS FOR

ANALYSIS ALONG LINE @

SECTION

WALL ELEMENTS ALONG L1NE@

i 13'.'O~2'

r33'1 ~28'1@~ ;:;lK ---.

CENTER OFJ 22'· a"STIFFNESS _, 1.

'EFFECTIVE~ WIDTH =17'_6"

FIG. 6.1 TYPICAL WALL ELEMENT FORMULATION

70

Page 89: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

L

FIG. 6.2 2 DEGREE OF FREEDOM MODEL FOR THE DUMMY STORY

ROOF12II1098765432I

U--+-MEASURED FLOOR ACCELERATION

'r"ii:::~ LUMPED FLOOR MASS

.............,...........I§f FLOOR ROTATION AND DISPLACEMENT

DUMMY STORY

FIG. 6.3 EXPERIMENTAL DATA

71

Page 90: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

5.5 t-sw-t SAND- WELL GRADED, 20% GRAVEL, BROWN

MLSANDY SILT - SOME CLAY. FEW

GRAVEL. BROWNML

SANDY SILT-SOME CLAY. FEW GRAVEL,BROWN

SANDY SILT- SOME CLAY, FEW ROOTS,ML I BROWN

SANDIER

12.0tM'i:i SANDY SILT- BROWN

ABOUT 10% GRAVEL

THIN LAYERS OF SILTY SANDTHIN LAYERS OF SAND AND FEW GRAVEL

SANDIER20.9 t-ei:1 SANDY CLAY- 10% GRAVEL, BROWN

I:z:r// I 05

SAND- WELL GRADED,20%GRAVEL,-- GREYISH - BROWN

ML I CLAYEY SILT- BROWN

SW ! SAND -- WELL GRADED, 20% GRAVEL,GREYISH - BROWN

....c:>za:oCIl

Is.sL. JSANDY SILT- BROWN--T"'MLl

25.0t-ML1 SANDY SILT - SOME CLAY, BROWN

45.5. SW

N

<:>:l:

~CIl

THIN LAYERS OF SAND

34.4SILTY SANO- FINE 10% GRAVEL

SANDY SILT - SOME CLAY, 10% GRAVEL,BROWN 60.0

ML ISANDY SILT- BROWN

ML I CLAYEY SILT - BROWN

75.0

61.0. SW I SAND - WELL GRADED, 20% GRAVEL.-- GREYISH-BROWN

SAND- WELL GRADED ABOUT 30%-- GRAVEL, BROWN 400M . - ~CL SILTY CLAY- FEW GRAVEL BROWN

41.6 ABOUT 10% GRAVEL

ML CLAYEY SILT- BROWN

25.01 CLTHIN LAYERS OF GRAVEL

SW I SAND - WELL GRADED, ABOUT 20% 3 3.9~-- GRAVEL, BROWN 35.4lsw

<:>:!:II::g

57 01----01 57.0,. ,SM ISILTYSAND- FINE 25% GRAVEL, ML

BROWN

52.0

60.0

33.1

28.4 'tiel CLAYEY SILT- BROWN

.......N

FIG. 6.4 SOIL SECTION

Page 91: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

5

4~ 1/ y y v G 'V 2 • '1.t 9

5.1 99.0 607 1.134 x 106

- 10.8 105.6 720 1. 702 X 106

CD0 15.5 114.0 803 2.285 x 106

- 3- 20.4 114.0 872 2.695 x 10 6

...... fNI 24.7 112.9 892 2.792 x 106

Vol .--- 30.0 109.6 938 2.998 x 106

......(/) 34.3 119.4 945 3.314 x 106

, ~ , 2 . 40.0 124.0 976 3.672 x 106

C)45.9 103.4 991 3.157 x 106

53.1 106.9 1006 3.363 x 10 6

59.4 119.0 1019 3.841 x 10 6

65.1 129.3 1071 4.610 x 10 6

70.0 132.4 1108 5.053 x 106

74.7 135.4 1127 5.346 x 10 6

59.4 65. I 70 74.75.1 10.8 15.5 20.11 24.7 30 34.3 40 45.9 53.1

DEPTH (ft)

o I I I I I , , I I I I I I , I

o

FIG. 6.5 SHEAR MODULUS OF THE SOIL

Page 92: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

I

""-J..j:::>

2)__CfJ ~---I'~rJd I

)I----+-~~----l~nfO ddIl_d cr; : aft : ~ c c roiO"Ilo I ~:l.T. I r-. Iblt,I==~'1 I

3 1-6"--..jetlOt-(TYP.)

c®f-----rOI II IL J

FIRSTFLOORWALLS

PILE LENGTH

a = 29.5 ft.b = 36.0 ft.c = 41.5ft.d = 47.0ft.e =52.5ft.

FIG. 6.6 FOUNDATION PLAN

Page 93: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

o

z

Qo poCo)

p 0 (z) =(I- .L)o

Qo

2Q{Z) =Qo{l- 2z + Z2}o 0

FIG. 6.7 VARIATION OF SKIN FRICTION AND AXIAL FORCE IN THE PILE

75

Page 94: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

IAXIS OF SYMMETRY

I

I

I

I

I

I

'.

FIG. 6.8 FINITE ELEMENT MODEL OF THE SOIL

76

0.0

5.0

10.0

15.0

20.0

25.0

29.5

36.0

41.5

52.5

60.0

70.0

80.0

90.0

100.0

Page 95: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

ROOF

12

II

10

9

8 XX7

104'6

5

4

3

2

_L I

~~-80'---+.1

~ 52.13,---+,-52.13'--'/

14---------160'---------+1

FIG. 6.9 SIMPLIFIED BEAM FOUNDATION MODEL FOR THE ROTATIONAL STIFFNESS

77

Page 96: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

25

30

Z [ftJ

FIG. 6.10 VARIATION OF THE MODULUS OF SOIL REACTION kn

78

Page 97: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

~------0.03627" ~

I: FREE PILE HEAD~--0.01465'-' -~.I FIXED PILE HEADP=2400 Ibs.

I2345678

30'

20

....1.-_- 30 PILE - DEFLECTIONS

FIXED PILE HEAD:: 24000 : 1.6387 x 106 [~:.] = 1.966 x 107 [~~JKLATERAL 0.01465 I .]

FREE PILE HEAD: _ 24000 =0.6617 X106 [~Ibn:] =0.794 X107 r.;:']KLATERAL - 0.03626 L

G 6 11 PILE DEFLECTIONSFl. .

79

Page 98: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

WEST CENTER. (1.0°1' 000

1.103s> (0.92>t 0.977

1.002/ (0.84rO.916

00921 (0.751f 0.789

I 0.67)J

I I0.713p (0.58>t 0.595

I (Q50¥

I IJ0.488 (0.42) ~ 0.4345

I (0.34) JI I

10.327 (0.26) 10.270

10.243 (0.20) J0 0 204

JO.175 (0.13) /00152 ::lo I Qd 0.1078 0.08) 0.096 00-- ---'e..;,,;,,;,,;;o.:=:::=====::;~=:=---""''''''''====-===-o=*,,---

N-S N-S, I'

79.91

..

-0- EXPERIMENTAL• ANALYTICAL ( )

FIG. 6.12 NS VERTICAL MODE SHAPES (2.18 CPS)

80

Page 99: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

(O.33) 0.343

0.346 (O.23) 0.234

0.161 0.251 (O.l5) 0.142

0.083 0.073 (0.08) 0.079r-~--EW NS EW 10

en .....0

0 00 164.1 1

WEST CENTER

(1.52), 01.00\\

1.277 1.379

1.16 1.189

1.139 1.121

(O.96)

0.766 (O.82) 0.876

(O.69)

0.52 (O.56) 0.571

{O.44}

-0- EXPERIMENTAL• ANALYTICAL ( )

FIG. 6.13 EW VERTICAL MODE SHAPES (1.76 CPS)

81

Page 100: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EW g' NS

0.155

0.107

(0.42)

0.326 (0.33)

(0.26)

0.199 (0.19)

0.148 (0.13)

0.101 (O.OS) v0

.0.068 0----n.

EW

164.0'

CENTER THIS VALUE 0.331.00,,(0.95) _/REFLECTS NS

) MOTION TYPICAL

(0.S6)~\0.6S

\ \(0.77)~f604

(0.68)~O.593

(0.59)~

(0.50) .452

0.71Sr0.654J

0.604/

IIt·468

./I1°·292IIrO. ISO

~0.131,pO.093

WEST

0.20S

0.350

0.439

, 1.00

\

-0- EXPERIMENTAL• ANALYTICAL ( )

FIG. 6.14 EW VERTICAL MODE SHAPES (2.09 CPS)

82

Page 101: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

w

r...------- ---TI

I N rII ,, .1 r

I r ,, J ,,I

11'----______ "'E-

Is

12 th FLOOR

, ;,II ,, I ,

1I r II I

IIII

6th FLOOR

--EXPERIMENTAL--- ANALYTICAL

FIG. 6.15 NS FLOOR MODE SHAPES (2.18 CPS)

83

Page 102: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

12th FLOOR

6th FLOOR

--EXPERIMENTAL--- ANALYTICAL

FIG. 6.16 EW FLOOR MODE SHAPES (1.76 CPS)

84

E

Page 103: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

12th FLOOR

E

6th FLOOR

-- EXPERIMENTAL--- ANALYTICAL

FIG. 6.17 EW FLOOR MODE SHAPES (2.09 CPS)

85

Page 104: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

7. CONCLUSIONS

The results presented herewith clearly show that forced and ambient

vibration studies can be carried out effectively and show very good agree­

ment. Considering a frequency range of up to about 7 HZ t only the three

fundamental modes of vibration could be identified t thus indicating that

the building would basically respond to seismic excitation in a first

mode motion. The dynamic tests indicate a high coupling between the

translational EW and torsional modes. This highly coupled response could

possibly be reduced by changing the floor plan layout.

Neglecting the foundation flexibility (rigid base model)t shows an

overestimation of the experimental frequencies by 30 to 50%. Thus t in

the analysis of rigid structures on flexible foundations t the soil-structure

interaction must be considered. In order to account for the flexibility

of the foundation a dummy story was added to the analytical model in

this case. Two approaches were used in determining stiffness values for

the foundation t one using vibration test data and the other using available

soil-pile data. In using the soil-pile data difficulty was encountered

in evaluating the effective pile stiffness especially in assessing the

dynamic behavior of the soil-structure system in the longitudinal direction

of the building. With the final analytical model used t taking into account

the flexible foundation through the addition of a dummy storYt very good

agreement was obtained with the experimental data.

86

Page 105: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

REFERENCES

1. Bouwkamp, J. G. and Rea, Dixon, "Dynamic Testing and Formulation ofMathematical Models·" Chapter VIII in Earthquake Engineering, R. L.Wiegel, Editor, Prentice-Hall, 1970.

2. Hudson, D. E., "Synchronized Vibration Generators for Dynamic Testsof Full Scale Structures", Earthquake Engineering Research LaboratoryReport, California Institute of Technology, Pasadena, 1962.

3. Rea, D., Bouwkamp, J. G. and Clough, R. W., "The Dynamic Behavior ofSteel Frame and Truss Buildings", AISI, Bull. No.9, April 1968.

4. Petrovski, J. and Jurukovski, D., "Dynamic Properties of StructuresFrom Full-Scale Forced Vibration Studies and Formulation of Mathe­matical Models", UNESCO Interregional Seminar on Low Cost ConstructionResistant to Earthquake and Hurricanes, Skopje, November 1971.

5. Bouwkamp, J. G., Kollegger, J. P., and Stephen, R. M., "Dynamic Propertiesof a Eight-Story Prefabricated Panel Building", Report No. EERC/UCB­80-30, Earthquake Engineering Research Center, University of California,Berke1ey, 1980.

6. U.S. Coast and Geodetic Survey, "Earthquake Investigations in California,1934-1935", Special Publication No. 201, U.S. Dept. of Commerce,Washington, D.C., 1936.

7. Crawford, R. and Ward, H. S., "Determination of the National Periodsof Buildings", Bull. Seis. Soc. Am., 54, 1964, pp. 1743-1756.

8. Kawasumi, K. and Kanai, K., II Sma11 Amplitude Vibration of ActualBUildings ll

, Proc. First World Conf. Earthquake Eng., Berkeley, 1956.

9. McLamore, V. R., "Ambient Vibration Survey of Chesapeake Bay Bridge",Teledyne Gestronics, Rep. No. 0370-2150, 1970.

10. Stephen, R. M., Hollings, J. P. and Bouwkamp, J. G., "DynamicBehavior of a Multistory Pyramid~Shaped Building ll

, Report No. EERC/UCB­73-17, Earthquake Engineering Research Center, University of California,Berkeley, 1973.

11. Trifunac, M. D., "Wind and Microtremor Induced Vibrations of a Twenty­Two Story Steel Frame Building ll

, Earthquake Engineering ResearchLaboratory, EERL 70-10, California Institute of Technology, Pasadena,1970.

12. Ward, H. S. and Crawford, R., "Wind Induced Vibrations and BuildingModes", Bull. Seis. Soc. Am., 56, 1966, pp. 793-813.

13. Petrovski, J., Jurukovski, D. and Perconkov, S., "Dynamic Propertiesof Multistory Trade Building and Formulation of the Mathematical Mode]lI,Publ. No. 24, Institute of Earthquake Engineering and EngineeringSeismology, University of Skopje, 1971.

14. Caughey, T. K., IIClassical Normal Modes in Damped Linear Systems",J. Appl. Mech., ~, 1960, pp. 269-271.

87

Page 106: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

15. Clough, R. W. and Penzien, J., Dynamics of Stnuctures, McGraw-Hill,1975.

16. Stephen, R. M., Wilson, E. L., Bouwkamp, J. G., and Button, M.,"Dynamic Behavior of a Pedestal-Base Multistory Building", Report No.EERC/UCB-78~13. Earthquake Engineering Research Center, University ofCalifornia, Berkeley, 1978.

17. Wilson, E. L., Dovey, H. H., and Habibullah, A., "Three DimensionalAnalysis of Building Systems--TABS-77", Report No. EERC/UCB-72-8,Earthquake Engineering Research Center, University of California,Berkeley, 1912.

18. Beton-Kalender 1978, Prof. Dr. Ing. F. P. MUller, UniversitatKarl sruhe, II Baudynami k".

19. Ottaviani, M. and Marchetti, S., "0bserved and Predicted Test 'PileBehavior", International Journal for Numerical and Analytical Methodsin Geomechanics, Vol. 3, 1979.

20. Penzien, J. et al, "Seismic Analysis of the Charaima Building,Caraball eda , Venezuela", EERC/UCB-70-4. University of California,Berkeley, 1970.

21. Zienkiewicz, O. C., The Finite Element Method, McGraw-Hill 1977,Chap. 24, Taylor, R. L., i1Computer Procedures for Finite Element Analysis".

22. Vesic, A. S., "Design of Pile Foundation", National CooperativeHighwat Research Program #42.

23. Bowles, J.E., Foundation Analysis and Design, McGraw-Hill, 1977.

88

Page 107: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EARTHQUAKE ENGINEERING RESEARCH CENTER REPORTS

NOTE: Numbers in parenthesis are Accession Numbers assigned by the National Technical Information Service; these arefollowed by a price code. Copies of the reports may be ordered from the National Technical Information Service, 5285Port Royal Road, Springfield, Virginia, 22161. Accession Numbers should be quoted on orders for reports (PB --- ---)and remittance must accompany each order~ Reports without this information were not available at time of printing.Upon request, EERC will mail inquirers this information when ·it becomes available.

EERC 67-1

EERC 68-1

EERC 68-2

EERC 68-3

EERC 68-4

EERC 68-5

EERC 69-1

EERC 69-2

EERC 69-3

EERC 69-4

EERC 69-5

EERC 69-6

EERC 69-7

EERC 69-8

"Feasibility Study Large-Scale Earthquake Simulator Facility," by J. Penzien, ,J.G. Bouwkamp, R.W. Cloughand D. Rea - 1967 (PB 187 905)A07

Unassigned

"Inelastic Behavior of Beam-to-Co1umn Subassemb1ages Under Repeated Loading," by V.V. Bertero -1968{PB 184 888)A05

"A Graphical Method for Solving the Wave Reflection-Refraction Problem," by H.D. McNiven and Y. Mengi -1968(PB 187 943)A03

"Dynamic Properties of McKinley School Buildings," by D. Rea, J.G. Bouwkamp and R.W. Clough-1968(PB 187 902)A07

"Characteristics of Rock Motions During Earthquakes," by H.B. Seed, I.M. Idriss and F .W. Kiefer - 1968(PB 188 338) A03

"Earthquake Engineering Research at Berkeley," - 1969 {PB 187 906)A11

"Nonlinear Seismic Response of Earth Structures," by M. Dibaj and J. Penzien -1969 {PB 187 904)A08

"Probabilistic Study of the Behavior of Structures During Earthquakes," by R. Ruiz and J. Penzien - 1969(PB 187 886)A06

"Numerical Solution of Boundary Value Problems in Structural Mechanics by Reduction to an Initial ValueFormulation," by N. Distefano and J. Schujman - 1969 (PB 187 942)A02

"Dynamic Programming and the Solution of the Biharmonic Equation," by N. Distefano -1969 (PB 187 941)A03

"Stochastic Analysis of Offshore Tower Structures," by A.K. Malhotra and J. Penzien -1969 {PB 187 903)A09

"Rock Motion Accelerograms for High Magnitude Earthquakes," by H.B. Seed and I.M. Idriss-1969 (PB187940)A02

"Structural Dynamics Testing Facilities at the university of California, Berkeley," by R.M. Stephen.J.G. Bouwkamp, R.~l. Clough and J. Penzien -1969 (PB 189 111)A04

EERC 69-9 "Seismic Response of Soil Deposits Underlain by Sloping Rock Boundaries," by H. Dezfulian and H.B. Seed1969 {PB 189 114)A03

EERC 69-10 "Dynamic Stress Analysis of Axisymmetric Structures Under Arbitrary Loading," by S. Ghosh and E.L. Wilson1969 (PB 189 026)A10

EERC 69-11 "Seismic Behavior of MUltistory Frames Designed by Different Philosophies," by J.C. Anderson andV. V. Bertero - 1969 {PB 190 662)AIO

EERC 69-12 "Stiffness Degradation of Reinforcing Concrete Members Subjected to Cyclic Flexural Moments," byV. V. Bertero, B. Bresler and H. Ming Liao - 1969 (PB 202 942) A07

EERC 69-13 "Response of Non-Uniform Soil Deposits to Travelling Seismic Waves," by H. Dezfu1ian and H.B. Seed-1969(PB 191 023)A03

EERC 69-14 "Damping Capacity of a Model Steel Structure," by D. Rea, R.W. Clough and J.G.Bouwkamp-1969 {PB190663)A06

EERC 69-15 "Influence of Local Soil Conditions on Building Damage Potential during Earthquakes," by H.B. Seed andI.M. Idriss - 1969 {PB 191 036)A03

EERC 69-16 "The Behavior of Sands Under Seismic Loading Conditions," by M.L. Silver and H.B. Seed-1969 {AD714982)A07

EERC 70-1 "Earthquake Response of Gravity Dams," by A.K. Chopra -1970 {AD 709 640)A03

EERC 70-2 "Relationships between Soil Conditions and Building Damage in the Caracas Earthquake of July 29, 1967," byH.B. Seed, LM. Idriss and H. Dezfulian - 1970 (PB 195 762)A05

EERC 70-3 "Cyclic Loading of Full Size Steel Connections," by E.P. Popov and R.M. Stephen -1970 {PB 213 545)A04

EERC 70-4 "Seismic Analysis of the Charaima Building, Caraballeda, Venezuela," by Subconunittee of the SEAONC ResearchCommittee: V.V. Bertero, P.F. Fratessa, S.A. Mahin, J.H. Sexton, A.C. Scorde1is, E.L. Wilson, L.A. Wyllie,H.B. Seed and J. Penzien, Chairman-1970 (PB 201 455)A06

89

Page 108: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EERC 70-5 "A Computer Program for Earthquake Analysis of Dams," by A.K. Chopra and P. Chakrabarti -1970 (AD 723 994)A05

EERC 70-6 "The Propagation of Love Waves Across Non-Horizontally Layered Structures," by J. Lysmer and L.A. Drake1970 (PS 197 896)A03

EERC 70-7 "Influence of Base Rock Characteristics on Ground Response," by J. Lysmer, H.B. Seed and P.B. Schnabel1970 (PS 197 897)A03

EERC 70-8 "Applicability of Laboratory Test Procedures for Measuring Soil Liquefaction Characteristics under CyclicLoading," by H.B. Seed and W.H. Peacock - 1970 (PB 198 016)A03

EERC 70-9 "A Simplified Procedure for Evaluating Soil Liquefaction Potential," by H.B. Seed and I.M. Idriss - 1970(PB 198 009)A03

EERC 70-10 "Soil Moduli and Damping Factors for Dynamic Response Analysis," by H.B. Seed and I.M. Idriss-1970(PB 197 869)A03

EEEC 71-1 "Koyna Earthquake of December 11, 1967 and the Performance of Koyna Dam," by A.K. Chopra and P. Chakrabarti1971 (AD 731 496)AOG

EERC 71-2 "Preliminary In-Situ Measurements of Anelastic Absorption in Soils Using a Prototype Earthquake Simulator,"by R.D. Borcherdt and P.W. Rodgers - 1971 (PB 201 454)A03

EERC 71-3 "Static and Dvnamic lInalysis of Inelastic Frame Structures," by F.L. Porter and G.H. Powell -1971(PS 210 135)A06

EERC 71-4 "Research Needs in Limit Design of Reinforced Concrete Structures," by V.V. Bertero -1971 (PS 202 943)A04

EERC 71-5 "Dynamic Behavior of a High-Rise Diagonally Braced Steel Building," by D. Rea, A.A. Shah and J .G. Bouwr.m,lp1971 (PB 203 584)A06

EERC 71-6 "Dynamic Stress Analysis of Porous Elastic Solids Saturated with Compressible Fluids," by J. Ghaboussi andE. L. Wilson - 1971 (PB 211 396)A06

EERC 71-7 "Inelastic Behavior of Steel Beam-to-Column Subassemblages," by H. Krawinkler, V.V. Bertero and E.P. Popov1971 (PB 211 335)A14

EERC 71-8 "Modification of Seismograph Records for Effects of Local Soil Conditions," by P. Schnabel, H.B. Seed andJ. Lysmer - 1971 (PB 214 450)A03

EERC 72-1 "Static and Earthquake Analysis of Three Dimensional Frame and Shear Wall Buildings," by E.L. Wilson andH.H. Dovey - 1972 (PB 212 904)A05

EERC 72-2 "Accelerations in Rock for Earthquakes in the Western United States," by P.B. Schnabel and H.B. Seed-1972(PB 213 100)M3

EERC 72-3 "Elastic-Plastic EarthqUake Response of Soil-Building Systems," by T. Minami -1972 (PB 214 868)A08

EERC 72-4 "Stochastic Inelastic Response of Offshore Towers to Strong Motion Earthquakes," by M.K. Kaul-1972(PB 215 713)A05

EERC 72-5 "Cyclic Behavior of Three Reinforced Concrete Flexural Members with High Shear," by E.P. Popov, V.V. Berteroand H. Krawinkler- 1972 (PB 214 555)A05

EERC 72-6 "Earthquake Response of Gravity Dams Including Reservoir Interaction Effects," by P. Chakrabarti andA.K. Chopra - 1972 (AD 762 330)A08

EERC 72-7 "Dynamic Properties of Pine Flat Dam," by D. Rea, C. Y. Liaw and A.K. Chopra - 1972 (AD 763 928)A05

EERC 72-8 "Three Dimensional Analysis of Building Systems," by E.L. Wilson and H.H. Dovey -1972 (PB 222 438)A06

EERC 72-9 "Rate of Loading Effects on Uncracked and Repaired Reinforced Concrete Members," by S. Mahin, V. V. Bertero,D. Rea and M. Atalay -1972 (PB 224 520)A08

EERC 72-10 "Computer Program for Static and Dynamic Analysis of Linear Structural Systems," by E.L. Wilson, K.-J. Bathe,J.E. Peterson and H.H,Dovey -1972 (PB 220 437)AD4

EERC 72-11 "Literature Survey-Seismic Effects on Highway Bridges," by T. Iwasaki, J. Penzien andR.W. Clough-1972(PB 215 6l3)A19

EERC 72-12 "SHAKE-A Computer Program for Earthquake Response Analysis of Horizontally Layered Sites," by P.B. Schnabeland J. Lysmer - 1972 (PB 220 207)A06

EERC 73-1 "Optimal Seismic Design of Multistory Frames," by V.V. Bertero and H. Kamil-1973

EERC 73-2 "Analysis of the Slides in the San Fernando Dams During the Earthquake of February 9, 1971," by H.B. Seed,K.L. Lee, I.M. Idriss and F. Makdisi - 1973 (PS 223 402)A14

90

Page 109: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EERC 73-3 "Computer Aided Ultimate LOad Design of Unbraced Multistory Steel Frames," by M.B. El-Hafez and G.H. Powell1973 (PB 248 3l5)A09

EERC 73-4 "Experimental Investigation into the Seismic Behavior of Critical Re~ions of Reinforced Concrete Componentsas Influenced by Moment and Shear," by M. Celebi and J. Penzien - 1973 (PB 215 884)A09

EERC 73-5 "Hysteretic Behavior of Epoxy-Repaired Reinforced Concrete Beams," by M. Celebi and J. Penzien - 1973(PB 239 568)1\03

EERC 73-6 "General Purpose Computer Program for Inelastic Dynamic Response of Plane Structures," by A. Kanaan andG.H. Powe11- 1973 (PB 221 260)A08

EERC 73-7 "1\ Computer Program for Earthquake Analysis of.Gravity Dams Including Reservoir Interaction," byP. Chakrabarti and A.K. Chopra -1973 {AD 766 271)A04

EERC 73-8 "Behavior of Reinforced Concrete Deep Beam-Column Subassemblages Under Cyclic LOads," by O. Kustu andJ.G. Bouwkamp -1973 {PB 246 117)A12

EERC 73-9 "Earthquake Analysis of Structure-Foundation Systems," by A.K. Vaish and A.K. Chopra -1973 (AD 766 272)A07

EERC 73-10 "Deconvolution of Seismic Response for Linear Systems," by R.B. Reimer - 1973 (PB 227 179)A08

EERC 73-11 "SAP IV: A Structural Analysis Program for Static and Dynamic Response of Linear Systems," by K.-J. Bathe,E.L. Wilson and F.E. Peterson -1973 (PB 221 967)A09

EERC 73-12 "Analytical Investigations of the Seismic Response of Long, Multiple Span Highway Bridges," by W.S. Tsengand J. Penzien - 1973 (PB 227 816)AIO

EERC 73-13 "Earthquake Analysis of Multi-Story Buildings Including Foundation Interaction," by A.K. Chopra andJ.A. Guti",rrez - 1973 (PB 222 970)A03

EERC 73-14 "ADAP: A Computer Program for Static and Dynamic Analysis of Arch Dams," by R.W. Clough, J.M. Raphael andS. Mojtahedi - 1973 (PB 223 763)1\09

EERC 73-15 "Cyclic Plastic Analysis of Structural Steel Joints," by R. B. Pinkney and R.W. Clough -1973 (PB 226 843)A08

EERC 73-16 "QI.'AD-4: A Computer Program for Evaluating the Seismic Response of Soil Structures by Variable DampingFinite Element Procedures," by I.M. Idriss, J. Lysmer, R. Hwang and H.B. Seed-1973 (PB 229 424)A05

EERC 73-17 "Dynamic ,;,-havior of a Multi-Story Pyramid Shaped Building," by R.M. Stephen, J.P. Hollings andJ.G. Bouwkamp -1973 (PB 240 718)A06

EERC 73-18 "Effect of Different Types of Reinforcing on Seismic Behavior of Short Concrete Columns," by V.V. Bertero,J. Hollings, O. Kustu. R.M. Stephen and J.G. Bouwkamp-1973

EERC 73-19 "Olive View Medical Center Materials Studies, Phase I," by B. Bresler and V. V. Bertero - 1973 (PB 235 986)A06

BERC 73-20 "Linear and Nonlinear Seismic Analysis Computer Programs for Long MUltiple-Span Highway Bridges," byW.S. Tseng and J. Penzien -1973

BERC 73-21 "Constitutive Models for cyclic Plastic Deformation of Engineering Materials," by J .M. Kelly and P.P. Gillis1973 (PB 226 024)A03

BERC 73-22 "DRAIN - 2D User's Guide," by G.H. Powell-1973 (PB 227 016)1\05

BERC 73-23 "Earthquake Engineering at Berkeley - 1973," (PB 226 033) All

EERC 73-24 Unassigned

EERC 73-25 "Earthquake Response of Axisymmetric Tower Structures Surrounded by Water," by C. Y. Liaw and A.K. Chopra1973 (AD 773 052)A09

EERC 73-26 "Investigation of the Failures of the Olive view Stairtowers During the San Fernando Earthquake and TheirImplications on Seismic Design," by V.V. Bertero and R.G. Collins -1973 (PB 235 106)A13

EERC 73-27 "Further Studies on Seismic Behavior of Steel Beam-Column Subassemblages." by V.V. Bertero, H. Krawinklerand E.P. Popov-1973 (PB 234 172)A06

EERC 74-1 "Seismic Risk Analysis," by C.S. Oliveira-1974 (PB 235 920)A06

EERC 74-2 "Settlement and Liquefaction of Sands Under Multi-Directional Shaking," by R. Pyke, C.K, Chan and H.B. Seed1974

EERC 74-3 "Optimum Design of Earthquake Resistant Shear Buildings," by D. Ray, K.S. Pister and A.K. Chopra -1974(PB 231 172)A06

EERC 74-4 "LUSH - A Computer Program for Complex Response Analysis of Soil-Structure Systems," by J. Lysmer, T. Udaka,H.B. Seed and R, Hwang -1974 (PB 236 796)A05

91

Page 110: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EERC 74-5 "Sensitivity Analysis for Hysteretic Dynamic Systel11S: Applications to Earthquake Engineering," by D. Ray1974 {PB 233 213)A06

EERC 74-6 "Soil Structure Interaction Analyses for Evaluating SeisJ1lic Response," by H.B. Seed, J. Lysmer and R. Hwang1974 {PB 236 519)A04

EERC 74-7 Unassigned

EERC 74-8 "Shaking Table Tests of a Steel Frame - A Progress Report," by R.W. Clough and D. Tang -1974 {PB 240 8(,9)A03

EERC 74-9 "Hysteretic Behavior of Reinforced Concrete Flexural Members with Special Web Reinforcement," byV.V. Bertero, E.P. Popov and T.Y. Wang - 1974 {PB 236 797)A07

EERC 74-10 "Applications of Reliability-Based, Global Cost Optimization to De'sign of Earthquake Resistant Structures,"by E. Vitiello and K.S. Pister -1974 (PB 237 231)A06

EERC 74-11 "Liquefaction of Gravelly Soils Under Cyclic Loading Conditions," by R.T. Wong, H.B. Seed and C.K. Chan1974 (PB 242 042)A03

EERC 74-12 "Site-Dependent Spectra for Earthquake-Resistant Design," by H.B. Seed, C. Ugas and J. Lysmer -1974(PB 240 953)A03

EERC 74-13 "Earthquake Simulator Study of a Reinforced Concrete Frame," by P. Hidalgo and R.W. Clough -1974(PB 241 9~4)A13

EERC 74-14 "Nonlinear Earthquake Response of Concrete Gravity Dams," by N. Pal -1974 (AD/A 006 583)A06

EERC 74-15 "Modeling and Identification in Nonlinear Structural Dynamics - I. One Degree of Freedom Models," byN. Distefano and A. Rath - 1974 (PB 241 548)A06

EERC 75-1 "Determination of Seismic Design Criteria for the Durnbarton Bridge Replacement Structure, Vol. I: Description,Theory and Analytical Modeling of Bridge and Parameters," by F. Baron and S. -H. Pang - 1975 (PB 259407)A15

EERC 75-2 "Determination of Seismic Design Criteria for the Durnbarton Bridge Replacement Structure, Vol. II: NumericalStudies ,and Establishment of Seismic Design Criteria," by F. Baron and S.-H. Pang-1975 (PB 259 408)All(For set of EERC 75-1 and 75-2 (PB 259 406»)

EERC 75-3 "Seismic Risk Analysis for a Site and a Metropolitan Area," by C.S. Oliveira -1975 {PB 248 134)A09

EERC 75-4 "Analytical Investigations of Seismic Response of Short, Single or MUltiple-Span Highway Bridges," byM. -C. Chen and J. Penzien - 1975 (PB 241 454) A09

EERC 75-5 "An Evaluation of Some Methods for Predicting Seismic Behavior of Reinforced Concrete Buildings," by S.A.Mahin and V.V. Bertero -1975 (PB 246 306)A16

EERC 75-6 "Earthquake Simulator Study of a Steel Frame Structure, Vol.' I: Experimental Results," by R. w. Clough andD.T. Tang - 1975 (PB 243 981)A13

EERC 75-7 "Dynamic Properties of San Bernardino Intake Tower," by D. Rea, C.-Y. Liaw and A.K. Chopra-1975 (AD/A008406)A05

EERC 75-8 "Seismic Studies of the Articulation for the Durnbarton Bridge ReplaceJ1lent Structure, Vol. I: Description,Theory and Analytical Modeling of Bridge Components," by F. Baron and R.E. Hamati -1975 (PB 251 539)A07

EERC 75-9 "Seismic Studies of the Articulation for the Durnbarton Bridge Replacement Structure, Vol. 2: NumericalStudies of Steel and Concrete Girder Alternates," by F. Baron and R.E. Hamati-1975 {PB 251 540)AIO

EERC 75-10 "Static and Dynamic Analysis of Nonlinear Structures," by D.P. Mondkar and G.H. Powe11-1975 {PB 242 434)A08

EERC 75-11 "Hysteretic Behavior of Steel Columns," by E.P. Popov, V.V. Bertero and S. Chandramouli-1975 {PB252 365)All

EERC 75-12 "Earthquake Engineering Research Center Library Printed Catalog," -1975 {PB 243 711)A26

EERC 75-13 "Three Dimensional Analysis of Building Systems {Extended Version)," by E.L. Wilson, J.P. Hollings andH.H. Dovey - 1975 (PB 243 989)A07

EERC 75-14 "Determination of Soil Liquefaction Characteristics by Large-Scale Laboratory Tests," by P. DeAlba,C.K. Chan and H.B. Seed - 1975 {NUREG 0027)A08

EERC 75-15 "A Literature Survey - Compressive, Tensile, Bond and Shear Strength of Masonry," by R.L. Mayes and R.W.Clough - 1975 {PB 246 292)AIO

EERC 75-16 "Hysteretic Behavior of Ductile Moment Resisting Reinforced Concrete Frame Components," by V.V. Bertero andE.P. Popov -1975 {PB 246 388)AOS

EERC 75-17 "Relationships Between Maximum Acceleration, Maximum Velocity, Distance from Source, Local Site Conditionsfor Moderately Strong Earthquakes," by H.B. Seed, R. Murarka, J. Lysmer and I.M. Idriss-1975 {PB 248 172)A03

EERC 75-18 "The Effects of Method of Sample Preparation on the Cyclic Stress-Strain Behavior of Sands," by J. Mulilis,C.K. Chan and H.B. Seed-1975 (Summarized in EERC 75-28)

92

Page 111: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EERC 75-19 "The Seismic Behavior of Critical Regions of Reinforced Concrete Components as Influenced by Moment, Shearand Axial Force," by M. B. AtaJ-ay and J. Penzien - 1975 (PB 258 842) An

EERC 75-20 "Dynalllic Properties of an Eleven Story Masonry Building," by R.M. Stephen, J.P. Hollings, J.G., Bouwkamp andD. Jurukovski - 1975 (PB 246 945)A04

EERC 75-21 "State-of-the-Art in Seismic Strength of Masonry - An Evaluation and Review," by R.L. Mayes and R.W. Clough1975 (PB 249 040)A07

EERC 75-22 "Frequency Dependent Stiffness Matrices for Viscoelastic Half-Plane Foundations," by A.K. Chopra,P. Chakrabarti and G. Dasgupta - 1975 (PB 248 121)1'.07

EERC 75-23 "Hysteretic Behavior of Reinforced Concrete Framed Walls," by T.Y. Wong, V.V. l3ertero and E.P. Popov-1975

EERC 75-24 "Testing Facility for Subassemblages of Frame-Wall Structural Systems," by V.V. Bertero, E.P. Popov andT. Endo-1975

EERC 75-25 "Influence of Seismic History on the Liquefaction Characteristics of Sands," by H.B. Seed, K. Mori andC.!':. Chan - 1975 (Summarized in EERC 75-28)

EERC 75-26 "The Generation and Dissipation of Pore Water Pressures during Soil Liquefaction," by H.B. Seed, P.P. Martinand J. Lysmer - 1975 (PB 252 648) 1'.03

EERC 75-27 "Identification of Research Needs for Improving Aseismic Design of Building Structures," by V. V. Bertero1975 (PB 248 136)A05

EERC 75-28 "Evaluation of Soil Liquefaction Potential during Earthquakes," by H.B. Seed, I. Arango and C.K. Chan -1975(I.'UREG 0026) A13

EERC 75-29 "Representation of Irregular stress Time Histories by Equivalent Uniform Stress Series in LiquefactionAnalyses," by H.B. Seed, LM. Idriss, F. Makdisi and N. Banerjee -1975 (PB 252 635)1'.03

EERC 75-30 "FLUSH - A Computer Program for Approximate 3-D Analysis of Soil-Structure Interaction Problems," byJ. Lysmer, T. Udaka, C.-F. Tsai and H.B. Seed -1975 (PB 259 332}A07

EERC 75-31 "ALUSH - A Computer Program for Seismic Response Analysis of Axisymmetric Soil-Structure Systems," byE. Berger, J. Lysmer and H.B. Seed-1975

EERC 75-32 "TRIP and TRAVEL - Computer Programs for Soil-Structure Interaction Analysis with Horizontally TravellingWaves," by T. Udaka, cT. INsmer and floB. Seed-1975

EERC 75-33 "Predicting the Performance of Structures in Regions of High Seismicity," by J. Penzien-1975 (PB 248 130)1'.03

EERC 75-34 "Efficient Finite Element Analysis of Seismic Structure - Soil - Direction," by J. Lysmer, H. B. Seed, T. Vdaka,R.N. Hwang and C.-F. Tsai -1975 (PB 253 570)1'.03

EERC 75-35 "The Dynamic Behavior of a First Story Girder of a Three-Story Steel Frame Subjected to Earthquake Loading,"by R.W. Clough and L.-Y. Li-1975 (PB 248 84l}A05

EERC 75-36 "Earthquake Simulator Study of a Steel Frame Structure, Volume II -Analytical Results," by D.T. Tang - 1975(PB 252 926)1'.10

EERC 75-37 "ANSR-I General Purpose Computer Program for Analysis of Non-Linear Structural Response," by D.P. Mondkarand G.H. Powell - 1975 (PB 252 386}A08

EERC 75-38 "Nonlinear Response Spectra for Probabilistic Seismic Design and Damage Assessment of Reinforced ConcreteStructures," by M, Murakami and J. Penzien - 1975 (PB 259 530) 1'.05

EERC 75-39 "Study of a Method of Feasible Directions for Optimal Elastic Design of Frame Structures Subjected to Earth··quake Loading," by N.D. Walker and K. S. Pister - 1975 (PB 257 7Bl)A06

EERC 75-40 "An Alternative Representation of the Elastic-Viscoelastic Analogy," by G. Dasgupta and J .L. Sackman - 1975(PB 252 173) AD3

EERC 75-41 "Effect of Multi-Directional Shaking on Liquefaction of Sands," by H.B. Seed, R. Pyke and G.R. Martin -1975(PB 258 78l}A03

EERC 76-1 "Strength and Ductility Evaluation of Existing Low-Rise Reinforced Concrete Buildings - Screening Method," byT. Okada and B. Bresler -1976 (PB 257 906}All

EERC 76-2 "Experimental and Analytical Studies on the Hysteretic Behavior of Reinforced Concrete Rectangular andT-Beams," by S.-Y.M. Ma, E.P. Popov and V.V. Bertero-1976 (PB 260 843}A12

EERC 76-3 "Dynamic Behavior of a Multistory Triangular-Shaped Building," by J. Petrovski, R.M. Stephen, E. Gartenbaumand J. G. Bouwkamp - 1976 (PB 273 279)1'.07

EERC 76-4 "Earthquake Induced Deformations of Earth Darns," by N. Serff, H.B. Seed, F.I. Makdisi & C.-Y. Chang - 1976(PB 292 065)1'.08

93

Page 112: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

EERC 76-5 "Analysis and Design of Tube-Type Tall Buildinq Structures," by H. de Clercq and G.H. Powell -1976 (PB 252220)AIO

EERC 76-6 "Time and Frequency Domain Analysis of Three-Dimensional Ground Motions, San Fernando Earthquake," by T. Kubeand J. Penzien (PB 260 556)All

EERC 76-7 "Expected Performance of Uniform Building Code Design Masonry Structures," by R.L. Mayes, Y. ornate, S.W. Chenand R.W. Clough - 1976 (PB 270 098)A05

EERC 76-8 "Cyclic Shear Tests of Masonry Piers, Volume 1 - Test Results," by R.L. Mayes, Y. Ornote, R.W.Clough - 1976 (PB 264 424)A06

EERC 76-9 "A Substructure Method for Earthquake Analysis of Structure - Soil Interaction," by J .A. Gutierrez andA.K. Chopra - 1976 (PB 257 783)A08

EERC 76-10 "Stabilization of Potentially Liquefiable Sand Deposits using Gravel Drain Systems," by H.B. Seed andJ.R. Booker-1976 (PB 258 820)A04

EERC 76-11 "Influence of Design and Analysis Assumptions on Computed Inelastic Response of Moderately Tall Frames," byG.H. Powell and D.G. Row-1976 (PB 271 409)A06

EERC 76-12 "Sensitivity Analysis for Hysteretic Dynamic Systems: Theory and Applications," by D. Ray, K.S. Pister andE. Polak - 1976 (PB 262 859)A04

EERC 76-13 "Coupled Lateral Torsional Response of Buildings to Ground Shaking," by C.L. Kan and A.K. Chopra ­1976 (PB 257 907)A09

EERC 76-14 "Seismic Analyses of the Banco de America," by V. V. Bertero, S.A. Mahin and J.A. Hollings - 1976

EERC 76-15 "Reinforced Concrete Frame 2: Seismic Testing and Analytical Correlation," by R.W. Clough andJ. Gidwani - 1976 (PB 261 323)A08

EERC 76-16 "Cyclic Shear Tests of Masonry Piers, Volume 2 - Analysis of Test Results," by R.L. Mayes, Y. Omoteand R.W. Clough - 1976

EERC 76-17 "Structural Steel Bracing Systems: Behavior Under cyclic Loading," by E.P. Popov, K. Takanashi andC.W. Roeder - 1976 (PB 260 715)A05

EERC 76-18 "Experimental Model Studies on Seismic Response of High Curved overcrossings," by D. Williams andW.G. Godden - 1976 (PB 269 548)A08

EERC 76-19 "Effects of Non-Uniform Seismic Disturbances on the Dumbarton Bridge Replacement Structure," byF. Baron and R.E. Hamati - 1976 (PB 282 981)A16

EERC 76-20 "Investigation of the Inelastic Characteristics of a Single Story Steel Structure Using SystemIdentification and Shaking Table Experiments," by V.C. Matzen and H.D. McNiven - 1976 (PB 258 453)A07

EERC 76-21 "Capacity of Columns with Splice Imperfections," by E.P. Popov, R.M. Stephen and R. Philbrick - 1976(PS 260 378) A04

EERC 76-22 "Response of the Olive View Hospital Main Building during the San Fernando Earthquake," by S. A. Mahin,V.V. Bertero, A.K. Chopra and R. Collins - 1976 (PB 271 425)A14

EERC 76-23 "A Study on the Major Factors Influencing the Strength of Masonry Prisms," by N.M. Mostaghel,R.L. Mayes, R. W. Clough and S.W. Chen - 1976 (Not published)

£ERC 76-24 "GADFLEA - A Computer Program for the Analysis of Pore Pressure Generation and Dissipation duringCyclic or Earthquake Loading," by J.R. Booker, M.S. Rahman and H.B. Seed - 1976 (PB 263 947)A04

EERC 76-25 "Seismic Safety Evaluation of a RiC School Building," by B. Bresler and J. Axley - 1976

EERC 76-26 "Correlative Investigations on Theoretical and Experimental Dynamic Behavior of a Model BridgeStructure," by K. Kawashima and J. Penzien - 1976 (PB 263 388) All

EERC 76-27 "Earthquake Response of Coupled Shear Wall Buildings," by T. Srichatrapimuk - 1976 (PB 265 157)A07

EERC 76-28 "Tensile Capacity of Partial Penetration Welds," by E.P. Popov and R.M. Stephen - 1976 (PB 262 899) A03

EERC 76-29 "Analysis and Design of Numerical Integration Methods in Structural Dynamics," by H.M•.Hilber - 1976(PB 264 410) A06

EERC 76-30 "Contribution of a Floor System to the Dynamic Characteristics of Reinforced Concrete Buildings," byL.E. Malik and V.V. Bertero - 1976 (PB 272 247)A13

EERC 76-31 "The Effects of Seismic Disturbances on the Golden Gate Bridge," by F. Baron, M. Arikan and R.E. Hamati _1976 (PB 272 279)A09

EERC 76-32 "Infilled Frames in Earthquake Resistant Construction," by R.E. Klingner and V.V. Bertero - .1976(PB 265 892)A13

94

Page 113: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

UCB/EERC-77/01 "PLUSH - A Computer Program for Probabilistic Finite Element Analysis of Seismic soil-Structure Inter­action," by M.P. Romo Organista, J. Lysmer and H.B. Seed - 1977

UCB/EERC-77/02 "Soil-Structure Interaction Effects at the Humboldt Bay Power Plant in the Ferndale Earthquake of June7, 1975," by J.E. valera, H.B. Seed, C.F. Tsai and J. Lysmer - 1977 (PB 265 795)11.04

UCB/EERC-77/03 "Influence of Sample Disturbance on Sand Response to Cyclic Loading," by K. Mori, H.B. Seed and C.K.Chan - 1977 (PB 267 352)11.04

UCB/EERC-77/04 "Seismological Studies of Strong Motion Records," by J. Shoja-Taheri - 1977 (PB 269 655)11.10

UCB/EERC-77/05 "Testing Facility for Coupled-Shear Walls," by L. Li-Hyung, V.V. Bertero and E.P. Popov - 1977

UCB/EERC-77/06 "Developing Methodologies for Evaluating the Earthquake Safety of Existing Buildings," by No. 1 -B. Bresler; No.2 - B. Bresler, T. Okada and D. Zisling; No. 3 - T. Okada and B. Bresler; No.4 - V.V.Bertero and B. Bresler - 1977 (PB 267 354)11.08

UCB/EERC-77/07 "A Literature Survey - Transverse Strength of Masonry Walls," by Y. ornote, R.L. Mayes, S.W. Chen andR.W. Clough - 1977 (PB 277 933)11.07

UCB/EERC-77/08 "DRAIN-TABS: A Computer Program for Inelastic Earthquake Response of Three Dimensional Buildings," byR. Guendelman-Israel and G.H. Powell - 1977 (PB 270 693)11.07

UCB/EERC-77/09 "SUBWALL: A Special Purpose Finite Element Computer Program for Practical Elastic Analysis and Designof Structural Walls with Substructure Option," by D.Q. Le, H. Peterson and E.P. Popov - 1977(PB 270 567)A05

UCB/EERC-77/10 "Experimental Evaluation of Seismic Design Methods for Broad Cylindrical Tanks," by D.P. Clough(PB 272 280)11.13

UCB/EERC-77/11 "Earthquake Engineering Research at Berkeley - 1976," - 1977 (PB 273 507)11.09

UCB/EERC-77/12 "Automated Design of Earthquake Resistant Multistory Steel Building Frames," by N. D. Walker, Jr. - 1977(PB 276 526)11.09

UCB/EERC-77/13 "Concrete Confined by Rectangular Hoops Subjected to Axial Loads," by J. Vallenas, V.V. Bertero andE.P. Popov - 1977 (PB 275 165)A06

lJCB/EERC-77/14 "Seismic Strain Induced in the Ground During Earthquakes," by Y. Sugimura - 1977 (PB 284 201)11.04

UCB/EERC-77/15 "Bond Deterioration under Generalized Loading," by V.V. Bertero, E.P. Popov and S. Viwathanatepa - 1977

UCB/EERC-77/16 "Computer Aided optimum Design of Ductile Reinforced Concrete Moment Resisting Frames," by S.W.Zagajeski and V.V. Bertero - 1977 (PB 280 137)11.07

lJCJ3/EERC-77/17 "Earthquake Simulation Testing of a Stepping Frame with Energy-Absorbing Devices," by J .M. Kelly andD.F. Tsztoo - 1977 (PB 273 506)11.04

UCB/EERC-77/18 "Inelastic Behavior of Eccentrically Braced Steel Frames under Cyclic Loadings," by C.W. Roeder andE.P. Popov - 1977 (PB 275 526)A15

UCB/EERC-77/19 "A Simplified Procedure for Estimating Earthquake-Induced Deformations in Dams and Embankments," by F.I.Makdisi and H.B. Seed - 1977 (PB 276 820)A04

UCB/EERC-77/20 "The Performance of Earth Dams during Earthquakes," by H.B. Seed, F.r. Makdisi and P. de Alba - 1977(PB 276 821)11.04

UCB/EERC-77/2l "Dynamic Plastic Analysis Using Stress Resultant Finite Element Formulation," by P. Lukkunapvasit andJ.M. Kelly - 1977 (PB 275 453)A04

UCB/EERC-77/22 "Preliminary Experimental Study of Seismic uplift of a Steel Frame," by R.W. Clough and A.A. Huckelbridge1977 (PB 278 769)11.08

UCB/EERC-77/23 "Earthquake Simulator Tests of a Nine-Story Steel Frame with Columns Allowed to Uplift," by A.A.Huckelbridge - 1977 (PB 277 944)11.09

UCB/EERC-77/24 "Nonlinear Soil-Structure Interaction of Skew Highway Bridges," by M.-C. Chen and J. Penzien - 1977(PB 276 176)11.07

UCB/EERC-77!25 "Seismic Analysis of an Offshore Structure Supported on Pile Foundations," by D.D.-N. Liou and J. Penzien1977 (PB 283 180)11.06

UCB/EERC-77/26 "Dynamic Stiffness Matrices for Homogeneous Viscoelastic Half-Planes," by G. Dasgupta and A.K. Chopra ­1977 (PB 279 654)11.06

UCB/EERC-77/27 "A Practical Soft Story Earthquake Isolation System," by J .M. Kelly, J .~I. Eidinger and C.J. Derham ­1977 (PB 276 814)11.07

UCB/EERC-77/28 "Seismic Safety of Existing Buildings and Incentives for Hazard Mitigation in San Francisco: An

Exploratory Study," by A.J. Meltsner - 1977 (PB 281 970)11.05

UCB/EERC-77!29 "Dynamic Analysis of Electrohydraulic Shaking Tables," by D. Rea, S. Abedi-Hayati and Y. Takahashi1977 (PB 282 569)A04

UCB/EERC-77!30 "An Approach for Improving Seismic - Resistant Behavior of Reinforced Concrete Interior Joints," byB. Galunic, V.V. Bertero and E.P. Popov - 1977 (PB 290 870)11.06

95

Page 114: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

UCB/EERC-78/0l

UCB/EERC-78/02

UCB/EERC-78/03

UCB/EERC-78/04

UCB/EERC-78/05

UCB/EERC-78/06

UCB/EERC-78/07

UCB/EERC-78/08

UCB/EERC-78/09

UCB/EERC-78/l0

UCB/EERC-78/11

UCB/EERC-78/l2

UCB/EERC-78/13

UCB/EERC-78/14

UCB/EERC-78/15

UCB/EERC-78/16

"The Development of Energy-Absorbing Devices for Aseismic Base Isolation Systems," by J.M. Kelly andD.F. Tsztoo - 1978 (PB 284 978)A04

"Effect of Tensile Prestrain on the Cyclic Response of Structural Steel Connections, by J. G. Bouwkampand A. Mukhopadhyay - 1978

"Experimental Results of an Earthquake Isolation System using Natural Rubber Bearings," by oJ.M.Eidinger and J.M. Kelly - 1978 (PB 281 686)A04

"Seismic Behavior of Tall Liquid Storage Tanks," by A. Niwa - 1978 {PB 284 017)A14

"Hysteretic Behavior of Reinforced Concrete Columns Subjected to High Axial and Cyclic Shear Forces,"by S.W. Zagajeski, V.V. Bertero and J.G. Bouwkamp - 1978 (PB 283 858)A13

"Inelastic Beam-Column Elements for the ANSR-I Program," by A. Riahi, D.G. Rowand G.H. Powell - 1978

"Studies of Structural Response to Earthquake Ground Motion," by O.A. Lopez and A.K. Chopra - 1978{PB 282 790)A05

"A Laboratory Study of the Fluid-Structure Interaction of Submerged Tanks and Caissons in Earthquakes,ltby R.C. Byrd - 1978 (PB 284 957)A08

"Model for Evaluating Damageability of Structures," by 1. Sakamoto and B. Bresler - 1978

"Seismic Performance of Nonstructural and Secondary Structural Elements," by 1. Sakamoto - 1978

"Mathematical t-1odelling of Hysteresis Loops for Reinforced Concrete Columns," by S. Nakata, T. Sprouland J. Penzien - 1978

"Damageability in EXisting Buildings,lI by T. Blejwas and B. Bresler - 1978

"Dynamic Behavior of a Pedestal Base Multistory Building," by R.M. Stephen, E.L. Wilson, J.G. Bouwkampand M. Button - 1978 (PB 286 650)A08

"Seismic Response of Bridges - Case Studies," by R.A. Imbsen, V. Nutt and J. Penzien - 1978(PB 286 503)AIO

"A Substructure Technique for Nonlinear Static and Dynamic Analysis,'" by D.G. Rowand G.H. Powell ­1978 (PB 288 077)AIO

"Seismic Risk Studies for San Francisco and for the Greater San Francisco Bay Area, n by C.S. Oliveira ­1978

UCB/EERC-78/l7 "Strength of Timber Roof Connections Subjected to Cyclic toads," by P. Gulkan, R.t. Mayes and R.W.Clough - 1978

UCB/EERC-78/l8 "Response of K-Braced Steel Frame Models to Lateral Loads," by J.G. Bouwkamp, R.M. Stephen andE.P. Popov - 1978

UCB/EERC-78/19 "Rational Design Methods for tight Equipment in Structures Subjected to Ground Motion," byJ.L. Sackman and J.M. Kelly - 1978 (PB 292 357)A04

UCB/EERC-78/20 "Testing of a Wind Restraint for Aseismic Base Isolation," by J .M. Kelly and D.E. Chitty - 1978(PB 292 833)A03

UCB/EERC-78/2l "APOLLO - A Computer Program for the Analysis of Pore Pressure Generation and Dissipation in HorizontalSand Layers During Cyclic or Earthquake Loading," by P.P. Martin and H.B. Seed - 1978 {PB 292 835)A04

UCB/EERC-78/22 "Optimal Design of an Earthquake Isolation System," by M.A. Bhatti, K.S. Pister and E. Polak - 1978(PB 294 735)A06

UCB/EERC-78/23 "MASH - A Computer Program for the Non-Linear Analysis of Vertically propagating Shear Waves inHorizontally Layered Deposits," by P.P. Martin and H.B. Seed - 1978 (PB 293 101)A05

UCB/EERC-78/24 "Investigation of the Elastic Characteristics of a Three Story Steel Frame Using System Identification,"by I. Kaya and H.D. McNiven - 1978

UCB/EERC-78/25 "Investigation of the Nonlinear Characteristics of a Three-Story Steel Frame Using SystemIdentification," by 1. Kaya and H.D. McNiven - 1978

UCB/EERC-78/26 "Studies of Strong Ground Motion in Taiwan," by Y.M. Hsiung, B.A. Bolt and J. Penzien - 1978

UCB/EERC-78/27 "Cyclic Loading Tests of Masonry Single Piers: Volume 1 - Height to Width Ratio of 2," by P .A. HidaJ.')o,R.t. Mayes, H.D. McNiven and R.W. Clough - 1978

UCB/EERC-78/28 "Cyclic Loading Tests of Masonry Single Piers: Volume 2 - Height to Width Ratio of 1," by S.-W.J. Chen,P.A. Hidalgo, R.t. Mayes, R.W. Clough and H.D. McNiven - 1978

UCB/EERC-78/29 "Analytical Procedures in Soil Dynamics," by J. Lysmer

96

1978

Page 115: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

UCB/ESRC-79/Cl "Hysteretic Behavior of Light"....eight: ?einfor=~c. Con::rete De'~T..-Coll~'n..'1 S:..:.ba:5~€:!:'.olages,It by B. ?orzan.i,E.? Popov and V.V. Bertero - April 197)!P5 29g 25i)n06

UCB/E2RC-79/02 "Ths Cevelcpt:'l.ent of a ~·!a-=.ha~atical ~hdel ~o ~reCi:::t t.1-L~ Flexur3.1 !"-tasponse of P.eir.forced CO:lcrete Bea.":,,sto Cyclic Loads, Using 5yste", IdentJ.ficati::>r.," by J. Stanton & H. :·lc:liven - Jan. 1973(PB 295 875)A10

UCB/EERC-79/03 "Linear and Nonli:lear Eart..iotquak-: ResfOnse of Simp,le Torsionally Coupled Systems," by C.L. Kan andA.K. ~opra - Feb. 1979(F3 298 2621A06

UCB/E'E?C-i9,/04 "A ~·lache...":1atica1 M:Jcdel 0 f :·!asonry for Prec.icti::.g its Linear S.aismic Respc>nse O\aracceristics," byY. Men;i ~~j H.D. McNi.,en - Feb, 1979(P3 298 2661A06

UCB/EE~C-79/05 t1~!echanical Behavior of Ligh1:'tleigh.'t. Co!\c!:!;!.te Confi:\ed ~y Differ~nt '1"'lpes of Lat.eral· Reinforcer:t~nt,"by x.~. ~~nrique, V.V. 3ertero and E.P. ?opo., - May 1979(P3 301 1141A06

UCB/EEP.c-73/06 "Static Tilt Tests of a Tall C"jlindrical Liquid Storage Tank," by R.W. Clough and .... :-;iwa - Feb. 1979(PB 301 167) A06

UCB/EERC- 79/07 "The Design of Steel E..,ergy l\llsorbing Restrainers and Their Incorporation into Nuclear Power Plantsfor En.'lanced Safety: Volume 1 - S=a"""1 Report," by !?N. Spencer, V.? Zackay, and E.R. Parker ­Feb. 1979(UC3/EERC-79/07) ...09

UCB/EERC-79/08 "The Design of Steel Energy lI.bsorbing Restrainers and Their Incorporation into Nuclear Po>ler Plantsfor E.rL.'=-ta..."1ced Safety: Volume 2 - The Devalopment. of Analyses for Reactor Systet:\ Piping, ItUSir.'l.pl~ Svste~'

by Z~.C .. Lee, J. Penzie:1, A.K. C'lopra a.?'!.d K, S'.,;,zu.l<.i "Cor.tplex Syst:ems" by G.H. Powell, E.L .. Wilson,R.W. Clough and D.G. Row - Feb. 1979(UCB/EERC-79/08}A10

UCB/EERC-79/09 "The Design of Steel Energy Absorbing Restrainers a."ld Their Incorporation into Nuclear P""er Pla..,tsfor Enh~,ced Safety: Volume 3 - Evaluation of Corr:mercial Steels, II by rtl.S. Owen, R.:-i.N. pelloux,R.O. Ritchie, M. Faral, T. Ohhashi, J. Toplosky, S.J. Hartman, V.F. zackay and B.R. Parker -Feb. 1979(UCB/EERC-79/09,A04

UCB/EERC-79/l0 "The Design of Steel Energy Absorbing Restrai::ers and Their Incorporation into Nuclear Power Plantsfor En:-.anced Safety: Volu.~ 4 - A Review of Energy-Absorbing oe'f;ices," by J 'OM. Kelly andM.S. Skinner - Feb. 1979 (UCB/EERC-79/10)A04

UCB/EEaC-79/11 "Conservatism In Su..,..mation Rules for Closely Spaced Modes," by J.M. l<elly a..,d J.L. Sackman - May1979(P3 301 328)A03

OCB/EERC-79/l2 "Cyclic Loadi.ng Tests of Nasonry Single piers; Volume 3 - Height to Width P.atio of 0.5," byP.A. Hidalgo, R.L. ~~yes, H.D. McNiven and R.W. Clough - May 1979(PB 301 321}A08

UCB/EERC-79/13 "Cyclic Behavior 0 f Dense Course-Grained :-!aterials in Relation to tl'le Seismic Stability of Dams," byN.G. Banerjee, H.B. Seed ~.,d C.I<. ~an - J~e 1979(FB 301 373)Al3

UCB/EERC-i9/l4 "Se ismi= Be~avior of Reinforced COncreteI:lterior Eeam-Colu.rnn Subassemblages," by s. Viwat.~anatepa,

E.P. Popov and V.V. Bertero - June 1979(1'3 301 326}AlO

UCB/EERC-79/1S "Opti:nal Dasign of Localized Nonlinear Syste:as wit." Dual Pe!"forma."'l"e Criteria Under EarthquakeExcitations," by ~I.A. Bhatti - July 1979(FB 80 167 109)A06

UCB/EEP.c-79/16 "QPTOYN - A C-anaral Purpose Optimization Program for Problems with or ~ithout Dynamic Constraints,"by M.A. Bhatti, E. Polak ~.,d K.S. Pister - July 1979(PB 80 167 091}AOS

UCB/EEl<.:-79/17 "A.'lSR-II, Flnalysis of Nonlinear Structural Response, Users Manual," by D.P. ~:OndJ<ar and G.H. Powell­July 1979(?B 80 113 3011AOS

UCB/EERC-79/18 "Soil Structure Interaction in Different Seistr.i.c Enviromnents," A.. Gorr.ez-Masso, J. Lysrner, J.-C. Chenand H.B. Seed - August 1979(PB 80 101 520}A04

UCB/EERC-79/19 "AR.'IA ~bdels for Earthquake Ground Motions," by M.K. Chang, J.W. Kwiatkowski, R.F. Nau, R.M. Oliverand K.S. pister - July 1979(PB 301 166)A05

UCB/EERC-79/20 "Hysteretic Behavior of Reinforced Concrete Structural Walls," by J.M. Vallenas, V.V. Bertero andE.P. Popov - August 1979(PB 80 165 905)Al2

UCB/EERC-79/21 "Studies on High-Fr"quency Vibrations of Buildings - 1: The Co1U1lU\ Effect," by J. Lubliner - August1979(PB 80 158 553) A.03

UCB/EERC-7"3/22 "Effects of Generalized Loadings on Bond Reinforcing Bars Embedded in Confined Concrete Blocks," byS. Viwathanatepa, E.p. Popov a.~d V.V. Bertero - August 1979

lOCB/EERC-79/23

UCII/EERc-79/24

"Sha1<ing Table Study of Single-Story ~fa50nry :iouses, Volu..'1e 1: Test Structures 1 anj 2," by P. GUlkan,R.L. Mayes a..,d R.W. Clough - Sept. 1979

"Shaking Table Study of Single-Story Hasonry Rouses, volume 2: Test Structures 3 and 4, " by P. GUlkan,R.L. Mayes and R.W. Clough - Sept. 1979

UCB/EERC-79/25 "Shaking Table Study of Single-Stor'f ;\asonrf Houses, Volt:...e 3: S=ry, Conclusions and Reco=.endatior.s,"by R.W. Clough, R.L. ~~yes and P. Gu1ka.., - Sept. 1979

UCB/EERC-79/26 "Recom:nendations for a U.S. -Japan Cooperative Research Program Utilizing Large-Scale Tes ting Facilities,"by U.S.-Japan Flanning Group - Sept. 1979(PB 301 407}A06

UCB/EERC-79/27 "Eart!"'.quake-Induced Liquefaction Near La'"<e Ana,:itlan, Guatemala," by ~L.B. Seed, t .. Arango, CooK. Chan,A. Gornez-"~sso and R. Grant de Ascoli - Sept. 1979(~~REG-CRl341)A03'

UCB/EE?.c-79/28 ItInfill Panels: Tr.eir Influence on Seismic Response of Buildings," by .:r.W. Axley and V.v. Bertero ­Sept. 1979(PB 80 163 371}AlO

UCB/EE?.c-79/29 "3D TrJ.Ss !lar Ele",,,nt ('I'Jpe 1) for the ANSR-II Program," by D.? Mondkar and G.H. Powell - NOV. 1979(PB 80 169 7C9)A02

UCB/EERC-79!30

UCB/EERC-79/31

"20 Baa.."'!-COlunn Ele:r.ent (T"['2e 5 - !?a:al1.el Ele..":'.e:r.t """o1"J) for t:-.e 1I.l:SR-II Program, " by D.G. Row,G.H .. P"",,e11 and D.P. :·bnd.i<ar - Cec. 1979 (1'9 80 167 224) A03

"3D 3ea:n-CO 1ur:U\ Element ('!'"JPe 2 - Parallel Elen"'.e:1t 'Theory) for the M:SR-II Progrfu'"n, " by A. iliahi,G.!!. Fo·"ell a."ld D.? !>bndk.ar - Dec. 1979 (1'9 SO 167 216) A03

OCB/E:EaC-79/32 liOn Res!=o:lse of 3truct".lre:s to Stationary Excita~ion,1I by A. Der Kiureghian - Dec. 1979(PB 801'56 929)A03

UCB/EERC-79/33 "Undisturbed S:ir.".plir.g and Cyclic Load Test-in; of Sa.."1.c.s," by S .. Singh, H.B. Seed and C.K .. C:-.~n -De~. 1973 (

UCB/EERC-79/34 "I:1teracti::>n Effects of Simultaneous Torsional a.."ld COmpressional COjcIie Loading of Sand, II byP.M. Griffin and W.N. ~ouston - Dec. 1973

97

Page 116: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

UCB/EERC-80/01

UCB/EERC-80/02

UCB/EERC-80/03

UCB/EERC-80/04

UCB/EERC-80/05

UCB/EERC-80/06

UCB/EERC-80/07

UCB/EERC-80/08

UCB/EERC-80/09

UCB/EERC-80/10

UCB/EERC-80/11

UCB/EERC-80/12

UCB/EERC-80/13

UCB/EERC-80/14

UCB!EERC-80/15

UCB/EERC-80/16

"Earthquake Response of Concrete Gravity Dams IncludingHydrodynamic and Foundation Interaction Effects," byA.K. Chopra, P. Chakrabarti and S. Gupta - 1980

"Rocking Response of Rigid Blocks to Earthquakes,"by C.S. Yim, A.K. Chopra and J. Penzien - 1980

"optimum Inelastic Design of Seismic-ResistantReinforced Concrete Frame Structures," byS.w. Zagajeski and V.V. Bertero - 1980

"Effects of Amount and Arrangement of viall-PanelReinforcement on Hysteretic Behavior of ReinforcedConcrete Walls," by R. Iliya and V.V. Bertero - 1980

'~Shaking Table Research on Concrete Dam Models," byA. Niwa and R.W. Clough - 1980

"Piping With Energy Absorbing Restrainers: ParameterStudy on Small Systems," by G.H. Powell, C. OUghourlianand J. Simons - 1980

"Inelastic Torsional Response of Structures Subjectedto Earthquake Ground Motions," by Y. Yamazaki - 1980

"Study of X-Braced Steel Frame Structures UnderEarthquake Simulation," by Y. Ghanaat - 1980

"Hybrid Hodelling of Soil-Structure Interaction," byS. Gupta, T.W. Lin, J. Penzien and C.S. Yeh - 1980

"General Applicability of a Nonlinear Model of a OneStory Steel Frame," by B. I. Sveinsson andH. McNiven - 1980

"A Green-Function f.lethod for Wave Interaction with aSubmerged Body," by W. Kioka - 1980

"Hydrodynamic Pressure and Added Mass for AxisymmetricBodies," by F. Ni1rat - 1980

"Treatment of Non-Linear Drag Forces Acting on OffshorePlatforms," by B.V. Dao and J. Penzien - 1980

"2D Plane/Axisymmetric Solid Element (Type 3 - Elasticor Elastic-Perfectly Plastic) for the ANSR-II Program,"by D.P. Mondkar and G.H. Powell - 1980

"A Response Spectrum Hethod for Random Vibrations," byA. Der Kiureghian - 1980

"Cyclic Inelastic Buckling of Tubular Steel Braces,"by V.A. Zayas, E.P. Popov and S.A. Mahin - 1980

98

Page 117: DYNAMIC PROPERTIES OF ATWELVE-STORY PREFABRICATED …

UCBjEERC-BOj17 "Dynamic Response of Simple Arch Dams IncludingHydrodynamic Interaction," by C.S. Porter andA.K. Chopra - 1980

UCBjEERC-80j18 "Experimental Testing of a Friction Damped AseismicBase Isolation System with Fail-Safe Characteristics,"by J.M. Kelly, K.E. Beucke and M.S. Skinner - 1980

UCBjEERC-80j19 "The Design of Steel Energy-Absorbing Restrainers andtheir Incorporation into Nuclear Power Plants forEnhanced Safety (Vol IB): Stochastic Seismic Analysesof Nuclear Power Plant Structures and Piping SystemsSubjected to Multiple Support Excitations," byM.C. Lee and J. penzien - 1980

UCBjEERC-80j20 "The Design of Steel Energy-Absorbing Restrainers andtheir Incorporation into Nuclear Power Plants forEnhanced Safety (Vol lC): Numerical Method for DynamicSubstructure Analysis," by J.M. Dickens and E.L. Wilson19BO

UCBjEERC-BOj21 "The Design of Steel Energy-Absorbing Restrainers andtheir Incorporation into Nuclear Power Plants forEnhanced Safety (Vol 2): Development and Testing ofRestraints for Nuclear piping Systems," by J.M. Kellyand M.S. Skinner - 19BO

UCBjEERC-80j22 "3D Solid Element (Type 4-Elastic or Elastic-Perfect1y­Plastic) for the ANSR-II Program," by D.P. Mondkar andG.H. Powell - 1980

UCB/EERC-BOj23 "Gap-Friction Element (Type 5) for the ANSR-II Program,"by D.P. Mondkar and G.H. Powell - 1980

UCBjEERC-80j24 "U-Bar Restraint Element (Type 11) for the ANSR-IIProgram," by C. Oughourlian and G.H. Powell - 1980

UCBjEERC-80j25 "Testing of a Natural Rubber Base Isolation System byan Explosively Simulated Earthquake," by J.M. Kelly1980

UCBjEERC-BOj26 "Input Identification from Structural VibrationalResponse," by Y. Hu - 19BO

UCBjEERC-BOj27 "Cyclic Inelastic Behavior of Steel Offshore Structures,"by V.A. Zayas, S.A. Mahin and E.P. Popov - 1980

UCBjEERC-80j28 "Shaking Table Testing of a Reinforced Concrete Framewith Biaxial Response," by M.G. Oliva and R.W. Clough1980

UCBjEERC-BOj29 "Dynamic Properties of a Twelve-Story PrefabricatedPanel Building," by J.G. Bouwkamp, J.P. Kollegger andR.M. Stephen - 1980

99