Mounting and operating instructions
DSTHX-2 COMBINED TEMPERATURE AND RELATIVE HUMIDITY DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 2 - 10
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
OPERATIONAL DIAGRAMS 5
WIRING AND CONNECTIONS 5
MOUNTING & OPERATING INSTRUCTIONS IN STEPS 5
OPERATING INSTRUCTIONS 8
MODBUS REGISTER MAPS 9
VERIFICATION OF INSTALLATION INSTRUCTIONS 10
TRANSPORT AND STORAGE 10
WARRANTY AND RESTRICTIONS 10
MAINTENANCE 10
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 3 - 10
back to the table of contents
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, mounting and operating instructions and study the wiring and connection diagram before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product.
For safety and licensing (CE) reasons, unauthorised conversion and / or modifications of the product are inadmissible.
The product should not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Long-term exposure to chemical vapours in high concentration can affect the product performance. Make sure the work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local electrical standards and approved codes. This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions.
Avoid contacts with energised electrical parts; always treat the product as if it is live. Always disconnect the power supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use appropriate wire size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these should be disposed of in accordance with local and national legislation / regulations.
In case there are any questions that are not answered, please contact our technical support or consult a professional.
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 4 - 10
back to the table of contents
PRODUCT DESCRIPTION
The DSTHX-2 series are dual duct transmitters which measure temperature and relative humidity. They feature a wide range of low voltage power supply and two analog / modulating outputs. All parameters are accessible via Modbus RTU.
ARTICLE CODES
Code Supply
DSTHG-2 18—34 VDC / 15—24 VAC ±10 %
DSTHF-2 18—34 VDC
INTENDED AREA OF USE
Monitoring duct temperature and relative humidity in HVAC applications
TECHNICAL DATA
■ Selectable temperature range: 0—50 °C ■ Selectable relative humidity range: 5—85 % ■ Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (5—85 % rH), depending on the selected parameter ■ Modbus RTU communication ■ Maximum power consumption:
► DSTHF-2: 1,68 W ► DSTHG-2: 1,8 W (VAC) / 1,68 W (VDC)
■ Nominal power consumption in normal operation: ► DSTHF-2: 1,26 W ► DSTHG-2: 1,35 W (VAC) / 1,26 W (VDC)
■ Imax: ► DSTHF-2: 70 mA ► DSTHG-2: 75 mA (VAC) / 70 mA (VDC)
■ Bootloader for updating the firmware via Modbus RTU communication ■ Minimum airflow velocity required: 1 m/s ■ Enclosure and probe material:
► ASA, grey (RAL9002) ■ Protection standard: Enclosure: IP54, Probe: IP20 ■ Operating ambient conditions:
► temperature: 0—50 °C ► rel. humidity: 5—85 % rH, (non-condensing)
■ Storage temperature: -10—60 °C
STANDARDS
■ EMC Directive 2014/30/EC: ► EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements
► EN 61326-2-3:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 2-3: Particular requirements - Test configuration, operational conditions and performance criteria for transducers with integrated or remote signal conditioning
■ WEEE Directive 2012/19/EC ■ RoHs Directive 2011/65/EC
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 5 - 10
back to the table of contents
OPERATIONAL DIAGRAMS
Analog Output 1 [%]
100
0 Min Range
Max Range
50 T [°C]
Analog Output 2 [%]
100
0 5 Min Range
Max Range
85 rH [%]
WIRING AND CONNECTIONS
Article type DSTHF-2 DSTHG-2
VIN 18—34 VDC 18—34 VDC 15—24 VAC ±10%
GND Ground Common ground* AC ~*
A Modbus RTU (RS485), signal A Modbus RTU (RS485), signal A
/B Modbus RTU (RS485), signal /B Modbus RTU (RS485), signal /B
AO1 Analog / modulating output 1 for temperature measurement (0—10 VDC / 0—20 mA / PWM)
Analog / modulating output 1 for temperature measurement (0—10 VDC / 0—20 mA / PWM)
GND Ground AO1 Common ground*
AO2Analog / modulating output 2 for relative
humidity measurement (0—10 VDC / 0—20 mA / PWM)
Analog / modulating output 2 for relative humidity measurement (0—10 VDC / 0—20 mA / PWM)
GND Ground AO2 Common ground*
Connections Spring contact terminal blocks, cable cross section: 1,5 mm2
* Caution: Never connect the common ground of G type articles to other devices powered by a DC voltage. If an AC power supply is used with a unit on a Modbus network, the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT-USB-RS485 converter. This may cause permanent damage to the communication semiconductors and / or the computer!
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the DSTH -2 duct transmitter, read carefully “Safety and Precautions”.
Follow these steps:1. When preparing to mount the DSTH -2, bear in mind that the unit itself must be
installed onto the outer surface of the duct both via fixing the flexible flange or directly the unit enclosure, while the probe must be inserted inside the duct, see Fig. 1 and Fig. 2 below.
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 6 - 10
back to the table of contents
Fig. 1 Mounting dimensions
With flange Without flange
60
Ø 122x Ø 5
86,8
18,5
42,3
50
285
34,5
4x Ø 4,470
66
100
105 80
Fig. 2 Mounting position
Correct Incorrect
AIR FLOW AIR FLOW
2. Having selected the appropriate mounting location, proceed with the following steps:2.1 Drill a Ø 13 mm hole into the duct and insert the probe. Apply an air-tight
sealing between probe and duct. 2.2 Fix the flange onto the duct outer surface using the self-drilling screws
delivered with the unit. If you do not intend to use the flange, insert the tube and fix the enclosure onto the duct. Mind the airflow direction (see Fig. 2 and Fig. 3).
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 7 - 10
back to the table of contents
Fig. 3 Mounting requirements
7,5*D(1) 3,5*D
(1)D = Duct diameter
ATTENTION Installation requirements: The DSTH -2 must not be installed in turbulent air zones. Ensure sufficiently long settling zones upstream and downstream of the tapping point. A settling zone consists of a straight section of pipe or duct with no obstructions. Avoid installation near filters, cooling coils, fans, etc. The sensor will achieve the optimal result when the measurement is taken at least 7,5 duct diameters downstream and at least 3 duct diameters upstream from any turns or flow obstructions.
ATTENTION Installation of the unit near high EMI-emitting devices may lead to faulty measurements. Use shielded wiring in areas with high EMI.
ATTENTION Keep at least 15 cm distance between the sensor lines and the 230 VAC power lines.
2.3 Install the tube at the desired depth and, in case you use the flange, fix it via the plastic white screw in the flexible flange.
2.4 Unscrew the cover of the unit to remove it and insert the connecting cables through the cable gland of the unit.
2.5 Do the wiring according to the information in section “Wiring and connections” adhering to Fig. 4 below.
Fig. 4 Wiring and connections
Analog / modulating 1 (0—10 VDC / 0—20 mA / PWM)
Modbus RTU
A/B
Supply voltage
DSTHF-2: 18—34 VDC
DSTHG-2: 18—34 VDC / 15—24 VAC ±10 %
Analog / modulating output 2 (0—10 VDC / 0—20 mA / PWM)
ATTENTION Do not exceed the maximum power supply rating! Measure before installation! Unregulated 24 VAC supply units provide higher nominal output voltage and activate the integrated fuse protection.
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 8 - 10
back to the table of contents
3. Customise the factory settings to the desired ones via the 3SModbus software or Sensistant (if necessary). For the default factory setting see Table Modbus register maps.
Optional settings If your unit is the first or the last unit on the Modbus RTU network (see Example 1 and Example 2), enable the NBT resistor via 3SModbus or Sensistant (Holding Register 30). If your device is not an end device, leave the NBT disabled (default Modbus setting).
Example 1 Example 2
RX
ТX
NBT
NBT
NBT
Slave 2Master
Slave n
Slave 1
Slave 2Slave 1
RX
ТX
NBT
NBT
Master
Slave n
4. Close the enclosure and secure the cover. 5. Switch on the power supply.
CAUTION Do not expose to direct sunlight!
OPERATING INSTRUCTIONS
Calibration procedure:Both the relative humidity and temperature sensor elements are factory calibrated. Recalibration is not necessary.
BootloaderThanks to the bootloader functionality, the sensor firmware can be updated via Modbus RTU communication. To enter “Boot mode”, put a jumper onto pins 3 and 4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is activated, the firmware can be updated via SM Boot application (part of 3SModbus software suite) or Sensistant.
Fig. 5 P1 header
1 2 3 4 5
Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus
communication parameters
1 2 3 4 5Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 9 - 10
back to the table of contents
MODBUS REGISTER MAPS
INPUT REGISTERSData type Description Data Values
1 Temperature signed int. Actual temperature level -300—700 500 = 50,0 °C
2 Relative humidity unsigned int. Actual relative humidity level 0—1.000 1.000 = 100,0 % rH
3 Dew point signed int. Calculated dew point -700—700 200 = 20,0 °C
4—10 Reserved, return ‘0’.
11 Output value 1 (temperature) unsigned int. Output value for temperature (T) 0—1.0000 =
1.000 = 0 %
100 %
12 Output value 2 (relative humidity) unsigned int. Output value for relative humidity (rH) 0—1.0000 =
1.000 = 0 %
100 %
13 Reserved, returns ‘0’.
14 Temperature alert flag unsigned int.Flag indicates that measured temperature is outside set alert values. Set to ‘1’ when the measured value is outside the temperature alert values defined by holding registers 20 and 21.
0—10 = 1 =
Measured temperature is OKMeasured temperature is too high/ low
15 Relative humidity alert flag unsigned int.Flag indicates that measured relative humidity is outside set alert values. Set to ‘1’ when the measured value is outside the relative humidity alert values defined by holding registers 22 and 23.
0—10 = 1 =
Measured rH is OKMeasured rH is too high/ low
16 Reserved, returns ‘0’.
17 Temperature range limit flag unsigned int.
Flag indicates that measured temperature is outside set range limit values. Set to ‘1’ when the measured value is outside the temperature range limit values defined by holding registers 14 and 15.
0—10 = 1 =
Temperature range is OKTemperature range is too high/ low
18Relative humidity range limit flag
unsigned int.
Flag indicates that measured relative humidity is outside set range limit values. Set to ‘1’ when the measured value is outside the relative humidity limit range values defined by holding registers 16 and 17.
0—10 = 1 =
rH range is OKrH range is too high/ low
19 Reserved, returns ‘0’.
20Humidity / temperature sensor fault
unsigned int.Flag indicates if the communication with the temperature and humidity sensor is lost.
0—10 = 1 =
NoYes
HOLDING REGISTERSData type Description Data Default Values
1 Device slave address unsigned int. Modbus device address 1—247 1
2 Modbus baud rate unsigned int. Modbus communication baud rate 0—6 2
0 =1 = 2 = 3 = 4 =5 =6 =
4.8009.600
19.20038.400 57.600
115.200230.400
3 Modbus parity mode unsigned int. Parity check mode 0—2 10 =1 = 2 =
8N1 8E18O1
4 Device type unsigned int. Device type (Read only) DSTHX-2 = 1095
5 HW version unsigned int. Hardware version of the device (Read only) XXXX 0x0100 = HW version 1.00
6 FW version unsigned int. Firmware version of the device (Read only) XXXX 0x0100 = FW version 1.00
7 Reserved, returns “0”.
8 Output 1 overwrite (T) unsigned int. Enables the direct control over the temperature output 0—1 0
0 =1 = 3 =
DisabledEnabled
9 Output 2 overwrite (rH) unsigned int. Enables the direct control over the relative humidity output 0—1 0
0 =1 = 3 =
DisabledEnabled
10 Reserved, returns “0”.
11 Output 1 type (T) unsigned int. Select analog / modulating output 1 (T)type 1—3 11 =2 = 3 =
1—10 VDC0—20 mA3 = PWM
12 Output 2 type (rH) unsigned int. Select analog / modulating output 2 (rH) type 1—3 11 =2 = 3 =
1—10 VDC0—20 mA3 = PWM
13 Reserved, returns “0”.
14 Minimum temperature range unsigned int.Minimum value of the temperature range; cannot be set higher than max. temperature range minus 5ºC
0 — (Max. range - 50) 0 100 = 10,0 °C
15 Maximum temperature range unsigned int.Maximum value of temperature range; cannot be set lower than min. temperature rang e plus 5ºC
(Min. range + 50) – 500 500 500 = 50,0 °C
16 Minimum relative humidity range unsigned int. Minimum value of the rH range; cannot be set
higher than max. rH range minus 5 % 50 — (Max. range — 50) 50 200 = 20,0 % rH
17 Maximum relative humidity range unsigned int. Maximum value of rH range; cannot be set
lower than min. rH range plus 5% (Min. range + 50) – 850 850 850= 85,0 % rH
18—19 Reserved, return “0”.
20 Minimum temperaturealert unsigned int. Minimum temperature alarm value Min. temperature range — Max.
temperature alarm 0 100 = 10,0 ºC
DSTHX-2 COMBINED T AND rH DUCT TRANSMITTER
www.sentera.euMIW-DSTHX-2-EN-000 - 29 / 11 / 2018 10 - 10
back to the table of contents
HOLDING REGISTERS
21 Maximum temperature alert unsigned int. Maximum temperature alarm value Min. temperature alarm — Max. temperature range 500 500 = 50,0 ºC
22 Minimum relative humidity alert unsigned int. Minimum relative humidity alarm value Min. relative humidity range —
Max. relative humidity alarm 50 200 = 20,0 % rH
23 Maximum relative humidity alert unsigned int. Maximum relative humidity alarm value Min. relative humidity alarm —Max.
relative humidity range 850 850 = 85,0 % rH
24—26 Reserved, return “0”.
27Internal voltage source selectionOutput 1 (T)
unsigned int. Selection of internal voltage source for PWM output 1 0—1 0 0 =
1 = 3,3 VDC12 VDC
28Internal voltage source selectionOutput 1 (rH)
unsigned int. Selection of internal voltage source for PWM output 2 0—1 0 0 =
1 = 3,3 VDC12 VDC
29 Reserved, returns ‘0’.
30 Modbus network resistor termination (NBT) unsigned int. Set device as ending the line or not by
connecting NBT 0—1 0 0 = 1 =
NBT disconnectedNBT connected
31 Output 1 overwrite value (T) unsigned int. Overwrite value for output 1. Active only if Holding register 8 is set to 1 0—1.000 0 0 =
1.000 = 0%
100%
32 Output 2 overwrite value (rH) unsigned int. Overwrite value for output 2. Active only if
Holding register 9 is set to 1 0—1.000 0 0 = 1.000 =
0%100%
33—35 Reserved, return “0
36 Modbus registers reset unsigned int.Resets Modbus Holding registers to default values. When finished this register is automatically reset to ‘0’
0—1 0 0 = 1 =
IdleReset Modbus registers
37—40 Reserved, return “0”
If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
VERIFICATION OF INSTALLATION INSTRUCTIONS
If your unit does not function as expected, please check the connections.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; store in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry.