www.max.us.com DSP Arm Controller Control Box SETTINGS Overview © 2018 Maximum Controls LLC. All rights reserved. Maximum Controls LLC. 10530 Lawson River Ave Fountain Valley, Ca 92708 Tel: (949) 699-0220 EXIT PWR ALARM POWER / SOLAR IN BATTERY INPU T OPENIN G C LOSIN G MOTOR 2 MOTOR 1 ER D OBD PORT BLACK BO X PROGRAMMING SOLAR MODE MOTO R OVER LOAD ER D MOTO R OVER LOAD MIN M AX OF F MA X SENSE MA X SENS E BATTERY BACKUP MODE ERD SENSITIVITY MOTION CONTRO L OPEN CLOSING GATE SPEED MOTOR 2 LIMITS MA G LOC K UL ENTRAP STOP CLOS E CLOS E TIMER MAGLOC K DELA Y JOG BATTERY TEST BATTERY INPU T ERRO R BATTERY IN US E POWER REPLAC E BATTERY LEAVE CLOSED LEAVE OPEN OPEN 1 TIME BATTERY VOLTAGE E F 1/2 RESET ID PLU G MODUL E POR T GATE OPEN GN D OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN / CLS NC GN D 12VDC OU T GN D GN D GN D GN D GN D JOG CLOS E JOG OPEN TAMPER IN TAMPER NO GATE DISABL E KEYPAD/CARD GN D GN D MAX OPEN FIRE DEPT RADIO GN D RADIO SIGNAL STRIKE CLOS E CO M CO M STOP OPEN PHOTO CLS 10K OPEN / CLS 10K 12VDC OU T NO CO M NC CO M GATE CLOSED LIMIT 1 GN D LIMIT 2 MOTOR 1 LIMITS MOTOR 1 MOTOR 2 LIMIT 1 GN D LIMIT 2 LIMIT 1 LIMIT 2 LIMIT 1 LIMIT 2 ID PLUG ERRO R 24VDC OUTPU T 12VDC OUTPU T GN D GN D GN D LOOP LOOP PWR LOOP CENTER SAFETY OFF SINGLE OPEN ON/OFF BATTERY CLOS E DUAL ON ANTI - TAILGATE PUSH OPEN PULL OPEN GATE OFF 1 2 3 4 5 6 7 8 9 10 OFF 1 2 3 4 5 6 MIN MIN MA X MA X ON OFF 2.5 sec 1.5 sec FAULTS OPERATOR DSP ARM CONTROLLER OFF EXIT LOOP 16 MIN 16 MIN 3 1 14 12 9 7 3 1 14 12 9 7 UL SENSOR 10K UL SENSOR N.C. MODE A M ODE B PROGRAM MOTOR 1 INPUTS [+ ] [-] [+ ] [-] MOTOR 2 INPUTS MAXIMUM CONTROLS DSP ARM CONTROLLER Battery Back-Up Mode LEAVE OPEN - After a power failure, gate will continue to operate until battery power is drained. At this point, the next open command, gate will remain OPEN. Gate will automatically close after AC power is restored if close timer is ON. LEAVE CLOSED - After a power failure, gate will continue to operate until battery power is drained. At this point, gate will remain CLOSED. OPEN 1 TIME - After a power failure, gate automatically OPENS and REMAINS OPEN. When power is restored, gate will automatically close. Maglock Delay Turned OFF - NO Maglock installed. Set to 1.5 sec or 2.5 sec - You MUST select a time delay when using a maglock. Maglock power disengages 1.5 sec or 2.5 sec before gate starts opening. Dual Gate Operators using Maglock: Primary gate opens FIRST. Install maglock accordingly to account for this. MAGLOCK LED (Monitors Maglock): ON - Locked OFF - Unlocked Flashing - Problem with Maglock Power. Operator Switch SINGLE - Single operator installed (Motor 1). DUAL - Dual operators installed (Motor 1 & Motor 2). Close Timer 1st click clockwise - Knob at MIN: 1/2 sec... 2nd click clockwise: 1 sec... 3rd click: 4 sec... 4th click: 8 sec... etc up to 60 sec. MAX. LED turns ON for MAX setting ONLY Anti-Tailgate Turned OFF - Close timer will close the gate at its selected time. Turned ON - (In-ground loops required) Gate will close after all the in-ground loops have been cleared no matter how long the close timer is set for. When an in-ground safety loop gets activated during the close cycle, gate will PAUSE and NOT reopen. When loop is cleared, gate will continue to close preventing UNAUTHORIZED entry. Solar Mode Turned OFF - AC input Power ONLY. Turned ON - Solar panels installed. Unit draws min power to extend battery life. obd port ODB Port Black Box 1. Plug MAX USB flash drive into OBD port on circuit board. OBD LED will flash while file is downloading. Remove flash drive after LED stops flashing (up to 5 minutes to download). 2. Plug flash drive into any computer USB port OR smart phone using a USB phone adapter. The most recent 8000 events can be viewed. No special software required. USB Phone Adapter Required OR Computer Smart Phone obd port MAX Flash Drive DIP-Switches Closing Gate Speed After gate positions have been “Learned”, the gate will cycle at the speed set on “CLOSING GATE SPEED” settings. Typically set to MAX, LEDs ON. MOTOR 2 MOTOR 1 CLOSING GATE SPEED MIN MIN MIN MIN MIN MI M M MIN MIN MIN MI M M MA M X AX MOTION CONTROL OPEN STO P CLOS E JOG OPEN CLOS E Programming Assistant Buttons Next Back Up Down Program Button Press PROGRAM and STOP buttons together to start programming. Follow instructions on screen using the 4 buttons shown below to program with. Press ONLY PROGRAM button again to end programming when finished. “Date and Time” MUST be programmed in along with other desired features. PROGRAM INSTRUCTIONS ARE ON SCREEN ERD SENSITIVITY MIN 16 3 1 14 12 9 7 MA X SENSE ERD SENSITIVITY MIN 16 3 1 14 12 9 7 A. Turn knob until blue LED lights up. Maximum sensitivity reached, Position 1 - Too sensitive for most gates. B. Turn knob counter-clockwise to reduce gate sensitivity while testing ERD until desired results is attained. (LED remains OFF for all but position 1) NOTE: Cycle the gate 3 or 4 times to make sure that the ERD sensor does not falsely trigger. 16 sensitivity setting positions for EACH direction. NO mechanical hard stops for knobs. 16 N 16 N 16 IN 1 MIN MIN MIN MIN MIN 1 If alarm sounds while adjusting ERD, press STOP BUTTON to shut-off alarm. IMPORTANT: Adjust the ERD to avoid injury as well as to minimize vehicle damage. MOTION CONTRO L OPEN STOP CLOS E ERD Sensitivity Setting MA X SENSE 2. LEDs WILL turn ON for each detected “LEARNED” sensor that has been wired to the inputs. If a sensor’s LED is NOT on, that sensor has a problem and it MUST be corrected before continuing. Possible problems: Photocells are out of alignment Photocells are wired wrong - N.C. or N.O. depending on which photocells are used. Sensor is bad When all LEDs are ON that should be ON, proceed to next step. 3. Press STOP button again within 5 min. to learn sensors and end learn mode, beeping stops. Wired “Learned” Inputs will now be MONITORED. NOTE: If STOP button is not pressed within 5 min., learn mode terminates. If no “LEARNED” sensors are detected then factory default setting is restored (Inputs will NOT be Monitored). MOTION CONTRO L OPEN STOP CLOSE MOTION CONTRO L OPEN STOP CLOSE OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN/CLS NC GN D 12VDC OU T GN D PHOTO CLS 10K OPEN/CLS 10K 12VDC OU T UL SENSOR N.C. UL SENSOR 10K O R N.C. O R N.C. O R N.C. O N.C. O N.C. N.C. N.C. N.C. .C SENSO R SENSO SENSO SENSO SENSO ENSO EN S EN S NS O R 10K O R 10K O R 10K O 10K O 10K 10K 10 10 1 H NSOR R R R R 1 1 1 SO R H R R R R R 1 SO H R R R R R R R SO P P O R R R R R R R SO P P O P O R R R R R R SO P P O P O O R R R R O P P O P O P O R R O P P O P O O O O O O O O L SEN N NS S S S P S P S P SO P O O O L SEN N N NS S S S S P S P S L SEN N N N NS S S S S L SEN N N N N NS S S S SE N N N N N NS S S SE EN N N N N N N SE E N N N N N SE E E N N N E E E 1. Press and HOLD the STOP button & then the OPEN button together until beeping is heard, learn mode begins. DO NOT press the OPEN button before the STOP button or learn mode will NOT begin (no beeping). MONITORED UL sensors Input “Learned” monitored “Learned” monitored “Learned” monitored “Learned” monitored “Learned” monitored Automatically monitored 7A FUSE POWER 115VAC 3A max 115V AC 3A max On Of f WARNING: For continued protection against fire, replace only with the same type and rating of fuse. AV ERTISSEMENT : pour ne pas compromettre la protection contre les risques d’incendie, utiliser un fusible de mêmes type et caractéristiques nominales. Select Input Vo ltage 11 5VAC or 230V AC (AC) POWER IN 115V MAX Toroid Box Turn off ALL Power IMPORTANT: This procedure must be followed whenever ALL power must be turned OFF on operator. ON/OFF BATTERY 1 Turn OFF POWER Switch on MAX Toroid Box. Battery power will remain ON. 2 Press and HOLD the RED ON/OFF BATTERY button until beep is heard, then release button. Closed Gate Open Open INSIDE Property OUTSIDE Property PULL OPEN PUSH OPEN Wall Gate Opening Direction Minimum of ONE Entrapment protection sensor MUST be installed or operator will NOT function. It MUST be MONITORED and NORMALLY CLOSED (N.C.)/10K. All entrapment zones should be protected by MONITORED sensors. UL 325 2018 Standard JO G OPEN CLOSE Push and HOLD to Open or Close (release button to stop gate). Helps when “Fine tuning” gate limit positions. Jog Buttons MOTOR 1 MOTOR 2 LIMIT 1 LIMIT 2 LIMIT 1 LIMIT 2 Sensor Learn Mode: POWER Switch A sensor wired to the PHOTO CLS NC will “AUTOMATICALLY be MONITORED” (Factory default). All other inputs MUST be learned before they will be monitored. DSP Arm Overview-Rev A Reserved Battery Beep Mode 2 3 4 5 6 7 8 9 10 Gate in Motion Alert Strobe Light Relay Control Quick-Close Unused Stop Input Polarity Open Relay Polarity UL Closing Photo ON PHOTO CLS NC Anti-tailgate OFF OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON ON 1 3 4 & 5 6 Open Relay Pulsed 1 2 MODE B Switches MODE A Switches Short Gate < 7 FT - shorter ramp down Long Gate > 10 FT - longer ramp down Gate < 7 FT 7 FT < Gate < 10 ft 10 FT < Gate < 13 ft Gate > 13 FT MAX Strong arm MAX Super arm Secondary Opposite Direction Lock on Close Choose Actuator Type Select Gate Length OFF ON OFF ON OFF ON OFF ON 5-OFF 4-OFF 5-OFF 4-ON 5-ON 4-OFF 5-ON 4-ON REQUIRED SETTING Open Relay ON when gate open Open Relay Pulsed when gate open Secondary moves same as primary Secondary moves opposite of primary Stop at close limit switch (see page 33) Stop on overload condition after seeing close limit switch No beeping when ONLY battery power and gate is in motion. Beeping when ONLY battery power and gate is in motion. No alarm while gate in motion Alarm while gate in motion Tamper Relay NO/C Triggered while gate in motion for strobe light control. No quick-close Quick-close ON Stop Input NO-connect to GND to activate Stop Input NC-disconnect from GND to activate Open Relay CLOSED when gate is open Open relay OPEN when gate is open UL Closing Photo anti-tailgate OFF UL Closing Photo anti-tailgate ON MUST be OFF DO NOT turn ON ON No Close Tamper Detect Trigger Tamper Relay (alarm for slider only) Close Tamper Detect OFF ON

Upload: others

Post on 10-Dec-2021

22 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DSP Arm Controller Control Box SETTINGS Overview

www.max.us.com

DSP Arm Controller Control Box SETTINGS Overview

© 2018 Maximum Controls LLC. All rights reserved.

Maximum Controls LLC.10530 Lawson River Ave

Fountain Valley, Ca 92708Tel: (949) 699-0220

EXIT PWR

ALARM

POWER /SOLAR IN

BATTERYINPU T

OPENIN G C LOSIN G

MOTOR 2MOTOR 1

ER D

OBD PORTBLACK BO X

PROGRAMMING

SOLAR MODE

MOTO ROVERLOAD

ER D

MOTO ROVERLOAD MIN M AX

OF F

MA XSENSE

MA XSENS E

BATTERYBACKUP MODE

ERD SENSITIVITY

MOTION CONTRO L

OPEN

CLOSING GATE SPEED

MOTOR 2LIMITS

MA GLOC K

ULENTRAP

STOP CLOS E

CLOS ETIMER

MAGLOC KDELA Y

JOG

BATTERYTEST

BATTERY

INPU TERRO R

BATTERYIN US E

POWER

REPLAC EBATTERY

LEAVECLOSED

LEAVEOPEN

OPEN1 TIME

BATTERY VOLTAGEE F1/2

RESET

IDPLU G

MODUL EPOR T

GATE OPEN

GN D

OPEN ONLY NC

OPEN ONLY 10K

PHOTO CLS NCOPEN / CLS NC

GN D12VDC OU T

GN D

GND

GND

GND

GND

JOG

CLOS

EJO

G OP

EN

TAM

PER

IN

TAM

PER

NO

GATE

DISA

BLE

KEYP

AD/CA

RD

GND

GND

MAX

OPE

N

FIRE

DEP

T

RADI

O GN

DRA

DIO

SIGN

AL

STRI

KE

CLOS

ECO

M

COM

STOP

OPEN

PHOTO CLS 10KOPEN / CLS 10K

12VDC OU T

NOCO M

NC

CO MGATE CLOSED

LIMIT 1GN D

LIMIT 2

MOTOR 1LIMITS

MOTOR 1

MOTOR 2

LIMIT 1GN D

LIMIT 2

LIMIT 1LIMIT 2LIMIT 1LIMIT 2

ID PLUGERRO R

24VDC OUTPU T

12VDC OUTPU T

GN D

GN D

GN D

LOOPLOOP PWR

LOOP

CENTER

SAFETY

OFF

SINGLE

OPEN

ON/OFFBATTERY

CLOS E

DUAL

ON

ANTI -TAILGATE

PUSHOPEN

PULLOPEN

GATEOFF

123456789

10OFF

123456

MIN MIN

MA X MA X

ON

OFF 2.5 sec1.5 sec

FAULTSOPERATOR

DSP ARM CONTROLLER

OFF

EXIT LOOP

16MIN

16MIN

3

1

14 12

9

7 3

1

14 12

9

7

UL S

ENSO

R 10

KUL

SEN

SOR

N.C.

MOD

E A

MOD

E B

PROGRAM

MOTOR 1INPUTS

[+ ][-]

[+ ][-]

MOTOR 2INPUTS

MAXIMUM CONTROLSDSP ARM CONTROLLER

Battery Back-Up ModeLEAVE OPEN - After a power failure, gate will continue to operate until battery power is drained. At this point, the next open command, gate will remain OPEN. Gate will automatically close after AC power is restored if close timer is ON.

LEAVE CLOSED - After a power failure, gate will continue to operate until battery power is drained. At this point, gate will remain CLOSED.

OPEN 1 TIME - After a power failure, gate automatically OPENS and REMAINS OPEN. When power is restored, gate will automatically close.

Maglock DelayTurned OFF - NO Maglock installed.

Set to 1.5 sec or 2.5 sec - You MUST select a time delay when using a maglock. Maglock power disengages 1.5 sec or 2.5 sec before gate starts opening.Dual Gate Operators using Maglock: Primary gate opens FIRST. Install maglock accordingly to account for this.

MAGLOCK LED (Monitors Maglock):ON - LockedOFF - UnlockedFlashing - Problem with Maglock Power.

Operator SwitchSINGLE - Single operator installed (Motor 1).DUAL - Dual operators installed

(Motor 1 & Motor 2).

Close Timer1st click clockwise - Knob at MIN: 1/2 sec... 2nd click clockwise: 1 sec... 3rd click: 4 sec...4th click: 8 sec... etc up to 60 sec. MAX.LED turns ON for MAX setting ONLY

Anti-TailgateTurned OFF - Close timer will close the gate at its selected time.Turned ON - (In-ground loops required) Gate will close after all the in-ground loops have been cleared no matter how long the close timer is set for. When an in-ground safety loop gets activated during the close cycle, gate will PAUSE and NOT reopen. When loop is cleared, gate will continue to close preventing UNAUTHORIZED entry.

Solar ModeTurned OFF - AC input Power ONLY.Turned ON - Solar panels installed. Unit draws min power to extend battery life.

obd

port

ODB Port Black Box1. Plug MAX USB flash drive into OBD port on circuit board.

OBD LED will flash while file is downloading. Remove flashdrive after LED stops flashing (up to 5 minutes to download).

2. Plug flash drive into anycomputer USB port ORsmart phone using a USBphone adapter. The mostrecent 8000 events can be viewed.No special software required.

USB Phone

Adapter

Required

OR

Computer

Smart Phoneo

bdpo

rtMAX Flash Drive

DIP-Switches

Closing Gate SpeedAfter gate positions have been “Learned”, the gate will cycle at the speed set on “CLOSING GATE SPEED” settings.

Typically set to MAX, LEDs ON.

MOTOR 2MOTOR 1

CLOSING GATE SPEEDMIN MINMINMINMINMIMM MINMINMINMIMM

MA MX AX

MOTION CONTROL

OPEN STO P CLOS E

JOG

OPEN CLOS E

Programming Assistant Buttons

NextBack Up Down

Program ButtonPress PROGRAM and STOP buttons together to start programming. Follow instructions on screen using the 4 buttons shown below to program with.Press ONLY PROGRAM button again to end programming when finished.“Date and Time” MUST be programmed in along with other desired features.

PROGRAM INSTRUCTIONSARE ON SCREEN

ERD SENSITIVITY

MIN16

3

1

14 12

9

7

MA XSENSE

ERD SENSITIVITY

MIN16

3

1

14 12

9

7

A. Turn knob until blue LED lights up.Maximum sensitivity reached,Position 1 - Too sensitive for most gates.

B. Turn knob counter-clockwise toreduce gate sensitivity while testingERD until desired results is attained.(LED remains OFF for all but position 1)

NOTE: Cycle the gate 3 or 4 times to make sure that the ERD sensor does not falsely trigger.

• 16 sensitivity setting positions for EACH direction.• NO mechanical hard stops for knobs.

16N

16N

16IN

1MINMINMINMINMIN

1

If alarm sounds while adjusting ERD, press STOP BUTTON to shut-off alarm.

IMPORTANT: Adjust the ERD to avoid injury as well as to minimize vehicle damage.

MOTION CONTRO L

OPEN STOP CLOS E

ERD Sensitivity Setting

MA XSENSE

2. LEDs WILL turn ON for each detected “LEARNED” sensor thathas been wired to the inputs. If a sensor’s LED is NOT on, thatsensor has a problem and it MUST be corrected beforecontinuing.

Possible problems:• Photocells are out of alignment• Photocells are wired wrong - N.C. or N.O. depending on

which photocells are used.• Sensor is bad

When all LEDs are ON that should be ON, proceed to next step.

3. Press STOP button again within 5 min. to learn sensors and end learn mode,beeping stops. Wired “Learned” Inputs will now be MONITORED.

NOTE: If STOP button is not pressed within 5 min., learn mode terminates.If no “LEARNED” sensors are detected then factory default setting isrestored (Inputs will NOT be Monitored).

MOTION CONTRO L

OPEN STOP CLOSE

MOTION CONTRO L

OPEN STOP CLOSE

OPEN ONLY NC

OPEN ONLY 10K

PHOTO CLS NC

OPEN/CLS NC

GN D

12VDC OU T

GN D

PHOTO CLS 10K

OPEN/CLS 10K

12VDC OU T

UL S

ENSO

R N.

C.UL

SEN

SOR

10K

O

R N.

C. O

R N.

C. O

R N.

C. O

R N.

C. O

N.C.

N.C.

N.C.

N.C..C

SENS

OR

SENS

OSE

NSO

SENS

OSE

NSO

ENSO

ENS

ENSNS

O

R10

K

O

R 10

K

O

R 10

K

O

R 10

K

O10K

10K

10101

H

NSOR

RRRRR111

SOR

H

RRRRRR1

SO PHORRRRRRRR

SO PPOORRRRRRR

SO PPO POORRRRRR

SO PPO POOORRRR

SO PPO PO POOORR

O PPO POOOOOOOO

O

L SEN

NNSSSS

PS PS PSO PSOO

O

L SEN

NNNSSSSS

PS PSL S

ENNNNNSSSSSS

L SEN

NNNNNSSSSL S

EENNNNNNSSS

SEENNNNNNN

SEEENNNNN

SEEEENNN

SEEEE

1. Press and HOLD the STOP button & then the OPEN button togetheruntil beeping is heard, learn mode begins. DO NOT press the OPENbutton before the STOP button or learn mode will NOT begin (no beeping).

MONITORED UL sensors Input

“Learned” monitored

“Learned” monitored

“Learned” monitored“Learned” monitored“Learned” monitored

Automatically monitored

7AFUSE

POWER115VAC3A ma x

115V AC3A ma x

On

Of f

WARNING: For continued protection against fire, replace only with the

same type and rating of fuse.

AV ERTISSEMENT : pour ne pas compromettre la protection contre les risques d’incendie, utiliser un

fusible de mêmes type et caractéristiques nominales.

Select Input Vo ltage115VAC or 230V AC

(AC)

POWER IN

115V

MAX Toroid Box

Turn off ALL PowerIMPORTANT: This procedure must be followed whenever ALL power must be turned OFF on operator.

ON/OFFBATTERY

1 Turn OFF POWER Switch on MAX Toroid Box.Battery power will remain ON.

2 Press and HOLD the RED ON/OFFBATTERY button until beep is heard,then release button.

Closed Gate

OpenOpen

INSIDEProperty

OUTSIDEProperty

PULL OPEN

PUSH OPEN

Wall

Gate Opening Direction

Minimum of ONE Entrapment protection sensor MUST be installed or operator will NOT function.It MUST be MONITORED and NORMALLY CLOSED (N.C.)/10K.All entrapment zones should be protected by MONITORED sensors.

UL 325 2018 Standard

JO G

OPEN CLOSE

Push and HOLD to Open or Close (release button to stop gate). Helps when “Fine tuning” gate limit positions.

Jog Buttons

MOTOR 1

MOTOR 2

LIMIT 1LIMIT 2LIMIT 1LIMIT 2

Sensor Learn Mode:

POWER Switch

A sensor wired to the PHOTO CLS NC will “AUTOMATICALLY be MONITORED”(Factory default). All other inputs MUST be learned before they will be monitored.

DSP Arm Overview-Rev A

Reserved

Battery Beep Mode

2

3

4

5

6

7

8

9

10

Gate in Motion Alert

Strobe Light Relay Control

Quick-Close

Unused

Stop Input Polarity

Open Relay Polarity

UL Closing Photo ONPHOTO CLS NC

Anti-tailgate

OFF

OFFON

OFFON

OFFON

OFFON

OFFON

OFFON

ON1

3

4&5

6

Open Relay Pulsed1

2

MOD

E B

Switc

hes

MOD

E A

Switc

hes

Short Gate < 7 FT - shorter ramp downLong Gate > 10 FT - longer ramp down

Gate < 7 FT7 FT < Gate < 10 ft10 FT < Gate < 13 ftGate > 13 FT

MAX Strong armMAX Super arm

SecondaryOpposite Direction

Lock on Close

Choose ActuatorType

Select GateLength

OFFON

OFFON

OFFON

OFFON

5-OFF 4-OFF5-OFF 4-ON5-ON 4-OFF5-ON 4-ON

REQUIRED SETTING

Open Relay ON when gate openOpen Relay Pulsed when gate openSecondary moves same as primarySecondary moves opposite of primaryStop at close limit switch (see page 33)Stop on overload condition after seeing close limit switch

No beeping when ONLY battery power and gateis in motion.Beeping when ONLY battery power and gate isin motion.No alarm while gate in motionAlarm while gate in motionTamper Relay NO/C Triggered while gate in motionfor strobe light control.No quick-closeQuick-close ON

Stop Input NO-connect to GND to activateStop Input NC-disconnect from GND to activateOpen Relay CLOSED when gate is openOpen relay OPEN when gate is open

UL Closing Photo anti-tailgate OFFUL Closing Photo anti-tailgate ON

MUST be OFFDO NOT turn ON

ON

No Close Tamper Detect Trigger Tamper Relay (alarm for slider only)Close Tamper Detect OFF

ON

Page 2: DSP Arm Controller Control Box SETTINGS Overview

www.max.us.com

DSP Arm Controller Control Box WIRING OverviewMaximum Controls LLC.10530 Lawson River Ave

Fountain Valley, Ca 92708Tel: (949) 699-0220

EXIT PWR

ALARM

POWER /SOLAR IN

BATTERYINPUT

OPENING CLOSING

MOTOR 2MOTOR 1

ERD

OBD PORTBLACK BOX

PROGRAMMING

SOLAR MODE

MOTOROVERLOAD

ERD

MOTOROVERLOAD MIN MAX

OFF

MAXSENSE

MAXSENSE

BATTERYBACKUP MODE

ERD SENSITIVITY

MOTION CONTROL

OPEN

CLOSING GATE SPEED

MOTOR 2LIMITS

MAGLOCK

ULENTRAP

STOP CLOSE

CLOSETIMER

MAGLOCKDELAY

JOG

BATTERYTEST

BATTERY

INPUTERROR

BATTERYIN USE

POWER

REPLACEBATTERY

LEAVECLOSED

LEAVEOPEN

OPEN1 TIME

BATTERY VOLTAGEE F1/2

RESET

IDPLUG

MODULEPORT

GATE OPEN

GND

OPEN ONLY NC

OPEN ONLY 10K

PHOTO CLS NCOPEN / CLS NC

GND12VDC OUT

GND

GND

GND

GND

GND

JOG

CLOS

EJO

G OP

EN

TAMP

ER IN

TAMP

ER N

O

GATE

DISA

BLE

KEYP

AD/C

ARD

GND

GND

MAX

OPEN

FIRE

DEP

T

RADI

O GN

DRA

DIO

SIGN

AL

STRI

KE

CLOS

ECO

M

COM

STOP

OPEN

PHOTO CLS 10KOPEN / CLS 10K

12VDC OUT

NOCOM

NC

COMGATE CLOSED

LIMIT 1GND

LIMIT 2

MOTOR 1LIMITS

MOTOR 1

MOTOR 2

LIMIT 1GND

LIMIT 2

LIMIT 1LIMIT 2LIMIT 1LIMIT 2

ID PLUGERROR

24VDC OUTPUT

12VDC OUTPUT

GND

GND

GND

LOOPLOOP PWR

LOOP

CENTER

SAFETY

OFF

SINGLE

OPEN

ON/OFFBATTERY

CLOSE

DUAL

ON

ANTI-TAILGATE

PUSHOPEN

PULLOPEN

GATEOFF

123456789

10OFF

123456

MIN MIN

MAX MAX

ON

OFF 2.5 sec1.5 sec

FAULTSOPERATOR

DSP ARM CONTROLLER

OFF

EXIT LOOP

16MIN

16MIN

3

1

14 12

9

7 3

1

14 12

9

7

UL S

ENSO

R 10

KUL

SEN

SOR

N.C.

MODE

AMO

DE B

PROGRAM

MOTOR 1INPUTS

[+][-]

[+][-]

MOTOR 2INPUTS

MAXIMUM CONTROLSDSP ARM CONTROLLER

AC Power Input

BatteriesTwo 12VDC

Batteries-7Ahr

(located on side of control box)Jog Gate Open/Close

SAFETYCENTEREXIT

J3

J2

J4 J5

In-GroundLoops

Factory Wired

Loop Detector Rack

Safety loops wired in series.

CenterLoop

SafetyLoop

SafetyLoopExitLoop

Plug-In Loop DetectorsCard Reader

Separate power fordevices if required.KeypadKey Switch

Telephone Entry

Emergency OPEN(Overrides gatedisable switch)

MAX OPEN(Overrides gatedisable switch)

Dry Contact NO

Dry Contact NO

NO

NO

Radio Signal

Radio SignalRadio Gnd

250 mA Max.

4-WireRadio

3-WireRadio

Stop

StopClose

Open

Tamper NO

Tamper IN

Com

Com

Com

Gate Disable

Com

Gnd

Gnd

Gnd

Gnd

Gnd

Gnd

Gnd

NO

+

+

--

NC

12 VDC OUT Monitored

Power

Power

NC

Jog CloseJog Open

External AlarmReset ButtonDry Contact

PRESS

to RESET

ID PlugSpecific for operator

model REQUIRED.

MAX

ACTU

ATOR

ARM

Maglock

Motion Sensor

Opening Direction

SecurityCamera

Gate Disable SwitchON

OFF

SirenWarning

Light

PowerPower

Pow

er

ExistingBuildingAlarm

System

Timer

Normally Closed Photocells

Closing Direction

Opening Direction

Closing Direction10K

SensingEdges

IMPORTANT: NC MONITORED sensors MUST be powered by the 12VDC OUT on the UL Sensor N.C.

IMPORTANT: Photocells MUST be in alignment or fault will occur.

GATE OPEN

GATE CLOSED

Gate StatusMonitoring Device

Pow

er

ONE entrapment protectionsensor MUST be installedor operator will NOT function.

EDILoop Detector

ON

12

34

56

78

5 = Optimum Sens.

= Increase Sens.

= Decrease Sens.

DEFLECTOMETER

POWERON = Normal Power

OFF= No Power

LED INDICATORSDETECTON = DetectOFF= No Detect

2 Hz Flash=Delay Timing

SW1 SW2 Frequency

ON ON = Low

ON OFF = Medium-Low

OFF ON = Medium-High

OFF OFF = HighSW4 SW5 Output B

ON ON = Pulse on Entry

ON OFF = B same as A

OFF ON = Pulse on Exit

OFF OFF = Loop Fault

SW3ON = Fail Secure

OFF = Fail Safe

SW6ON = 2 Second Delay

OFF = No Delay

SW7ON = Normal Presence

OFF = Infinite Presence

SW8ON = Sensitivity Boost

OFF = No Sensitivity Boost

Loop Fault1 Flash = Open Loop

2 Flashes= Shorted Loop

3 Flashes=25% change

of Inductance

Both LED’s Flashing=

Current Loop Fault

PWR LED Flashing=

Previous Loop Fault

EDITel: 480.968.6407

DEFLECTOMETER

SENS

RESET

POWER

DETECTEDI

SENSLMA1800

OPTIONS

12

34

56

78

ON

EDILoop Detector

Low CurrentDraw

OPTIONS

ON

12

34

56

78

5 = Optimum Sens.

= Increase Sens.

= Decrease Sens.

DEFLECTOMETER

POWERON = Normal Power

OFF= No Power

LED INDICATORSDETECTON = DetectOFF= No Detect

2 Hz Flash=Delay Timing

SW1 SW2 Frequency

ON ON = Low

ON OFF = Medium-Low

OFF ON = Medium-High

OFF OFF = HighSW4 SW5 Output B

ON ON = Pulse on Entry

ON OFF = B same as A

OFF ON = Pulse on Exit

OFF OFF = Loop Fault

SW3ON = Fail Secure

OFF = Fail Safe

SW6ON = 2 Second Delay

OFF = No Delay

SW7ON = Normal Presence

OFF = Infinite Presence

SW8ON = Sensitivity Boost

OFF = No Sensitivity Boost

Loop Fault1 Flash = Open Loop

2 Flashes= Shorted Loop

3 Flashes=25% change

of Inductance

Both LED’s Flashing=

Current Loop Fault

PWR LED Flashing=

Previous Loop Fault

EDITel: 480.968.6407

DEFLECTOMETER

SENS

RESET

POWER

DETECTEDI

SENSLMA1800-LP

12

34

56

78

ON

3-Button Control StationDry Contact

Solenoid Lock

Bi-parting gates using locks: Primary gate opens FIRST. Install lock accordingly to account for this.

External

Loop

Detector

External LoopDetectors

Wire directly to7-PIN terminal

7AFUSE

POWER115VAC3A max

115VAC3A max

On

Off

WARNING: For continued protection against fire, replace only with the

same type and rating of fuse.

AVERTISSEMENT: pour ne pas compromettre la protection contre les risques d’incendie, utiliser un

fusible de mêmes type et caractéristiques nominales.

Select Input Voltage115VAC or 230VAC

(AC)

POWER IN

115V

DANGERHIGH VOLTAGE!

Line (Black)

Neutral (White)

Chassis (Green)

Line (Black)

Neutral (White)

Chassis (Green)

Power Terminal

Chassis Ground(located at the bottomof the inside back panelof the control box)

Choose:Single Phase 115VAC

ORSingle Phase 230VAC

CAUTION: If input AC power selector switch is set for 115V but input power is actually 230 V, 7 Amp Fuse will blow.

MAX Toroid Box(located inside of control box)

Proper Ground

Reset Alarm(located on side of control box)

Alarm

12

45

3

12

354

WhiteYellow

RedBlackGreen

MAX Super Arm 2300

MAX Arm

Motor 2 connects the same as Motor 1 for EACH model of operator.(Bi-Parting Gates ONLY)

Motor 1

Motor 1

Proper grounding of control box is required for LIGHTNING PROTECTION in lightning prone areas. Minimum 12 AWG, 600 volt insulated wire to a proper ground point within 10 feet of the control box.

GroundingRod

NOTES:DO NOT select the PULSED outputoption for Loop Detectors.

DO NOT set Loop Detectors toHIGH sensitivity to avoid false trigger.

115 OR230VAC

Single PhaseInput Power

Wire

12 VDCOR

24 VDCRadioPower 12

V Po

wer

Stand-Alone Keypadless than 200 mA

DSP Arm Overview-Rev 5