dse 2548 - hipower · dse 2548 dsenet ® output expansion ... 4.2 schematic interconnection diagram...

13
DSE2548 DSENET ® OUTPUT EXPANSION MODULE DSEGenset ® The DSE2548 is an LED expansion module that can be used with all DSENet ® compatible control modules. The module has been designed to display a maximum of eight individual LED indications up to a maximum distance of 1 KM (0.6miles). The DSE2548 is presented in a vertical enclosure. It includes an alarm sounder that is triggered when the host controller detects an alarm condition. The alarm can be muted directly from the DSE2548 using the front push button. The DSE2548 includes individual LEDs for each channel and a ‘Power On’ LED that flashes when the link with the host controller is lost. ENVIRONMENTAL TESTING STANDARDS ELECTRO-MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 o C BS EN 60068-2-2 Bb/Be Dry Heat +70 o C VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn HUMIDITY BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 o C @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 o C @ 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 mS DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 60529 IP65 - Front of module when installed into the control panel with the supplied sealing gasket. HOST MODULE (1) 1 ISSUE 3 DSENET ® EXPANSION DC POWER SUPPLY 8-35V COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS 7 OTHER DSE2548 CONFIGURABLE LEDS AUDIBLE ALARM 8 DSENET ® 2157 2130 2510/20 2548 COMPATIBLE WITH DSE7310/20, DSE8610/60/80 & DSE8710/60 HOST MODULE

Upload: vokien

Post on 31-Aug-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548DSENET® OUTPUT EXPANSION MODULE

DSEGenset

®

The DSE2548 is an LED expansionmodule that can be used with allDSENet® compatible controlmodules. The module has beendesigned to display a maximum ofeight individual LED indications upto a maximum distance of 1 KM(0.6miles).

The DSE2548 is presented in avertical enclosure. It includes analarm sounder that is triggeredwhen the host controller detects analarm condition. The alarm can bemuted directly from the DSE2548using the front push button.

The DSE2548 includes individualLEDs for each channel and a‘Power On’ LED that flashes whenthe link with the host controller islost.

ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn

HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS

DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.

HOST MODULE (1)1

ISSUE 3

DSENET®

EXPANSIONDC POWER SUPPLY 8-35V

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETYOF GEN-SET APPLICATIONS

7

OTHER

DSE2548

CONFIGURABLE LEDS AUDIBLE ALARM

8

DSENET®

2157 2130 2510/20 2548

COMPATIBLE WITH DSE7310/20, DSE8610/60/80 & DSE8710/60

HOST MODULE

Page 2: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

055-062/10/10 (3)

KEY FEATURES• Eight configurable LEDs• Works up to 1 KM (0.6 miles)from the host controller

• 10 modules can be linkedtogether to one host controller

ID SWITCHThe rotary ID switch is used toselect the address of the DSE2548expansion module, as the hostcontrol module is capable of givinginstructions to a number ofDSE2548 expansion modules atthe same time.

RELATED MATERIALSTITLE PART NO’SDSE2548 Installation Instructions 053-032DSE2548 Operator Manual 057-084

DSE2548DSENET® OUTPUT EXPANSION MODULE

®

DSEGenset

Registered in England & Wales No.01319649VAT No.316923457

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.

SPECIFICATION

DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous

CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropoutand supply recovers to 5 V. This isachieved without the need for internalbatteries. LEDs and backlight will not bemaintained during cranking.

MAXIMUM OPERATING CURRENT112 mA at 12 V, 53 mA at 24 V

MAXIMUM STANDBY CURRENT74 mA at 12 V, 35 mA at 24 V

DIMENSIONSOVERALL180 mm x 116 mm x 42.7 mm 7.07” x 4.57” x 1.68”

PANEL CUT-OUT154 mm x 98 mm6.06” x 3.86”

MAXIMUM PANEL THICKNESS8 mm0.3”

Page 3: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DEEP SEA ELECTRONICS

DSEEXTRA®

DSE2548 LED expansion module

057-084

Author : Anthony Manton

COMPLEX SOLUTIONS MADE SIMPLE

Page 4: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

2 057-084 Issue 1 DSE2548 LED expansion operator manual

Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail : [email protected] Website : www.deepseaplc.com DSE2548 relay output expansion module © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

Page 5: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

057-083 Issue 1 DSE2548 LED expansion operator manual 3

1 BIBLIOGRAPHY ...................................... ............................................................ 4

2 INTRODUCTION .................................................................................................. 4

3 SPECIFICATIONS ............................................................................................... 5

3.1 PART NUMBERING .................................... ............................................................................. 5

3.2 POWER SUPPLY ..................................................................................................................... 5

3.3 TERMINAL SPECIFICATION ............................ ...................................................................... 5

3.4 DSENET® ................................................................................................................................. 6

3.5 DIMENSIONS ........................................................................................................................... 6

3.6 APPLICABLE STANDARDS .............................. ..................................................................... 7

4 INSTALLATION ...................................... ............................................................. 7

4.1 USER CONNECTIONS ............................................................................................................ 7

4.1.1 CONNECTOR A ................................................................................................................ 7

4.2 SCHEMATIC INTERCONNECTION DIAGRAM ................. ..................................................... 7

4.3 TYPICAL WIRING DIAGRAM ............................ ...................................................................... 8

5 CONTROLS AND INDICATIONS .......................... .............................................. 9

5.1 LED INDICATIONS ................................... ............................................................................... 9

5.2 SOUNDER ................................................................................................................................ 9

5.3 PUSH BUTTON ........................................................................................................................ 9

5.4 ID SWITCH ............................................................................................................................. 10

6 FAULT DIAGNOSIS ................................... ....................................................... 11

7 MAINTENANCE, SPARES, REPAIR AND SERVICING ......... .......................... 11

8 WARRANTY .......................................... ............................................................ 11

9 DISPOSAL .......................................... ............................................................... 11

9.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) .. ................................... 11

9.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES.......... ......................................... 11

Page 6: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

4 057-084 Issue 1 DSE2548 LED expansion operator manual

1 BIBLIOGRAPHY This document refers to and is reffered to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com DSE PART DESCRIPTION 057-074 7000 series operators manual 057-077 7000 series configuration software manual

2 INTRODUCTION This document details the installation requirements of the DSE2548 LED expansion module part of the DSEExtra® range of ancilliary modules. DSE2548 LED expansion module is used in conjunction with compatible DSE controllers to provide additional LED indication functionality. The LEDs are configured in the ‘host controller’, the DSE2548 module is not itself configured aside from the ‘ID switch’ detailed below. For further details on configuring the ‘host controller’ you are referred to the relevant configuration software manual.

Page 7: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

057-083 Issue 1 DSE2548 LED expansion operator manual 5

3 SPECIFICATIONS 3.1 PART NUMBERING

2548 - 001 - 00 At the time of this document production, there are no variants of this product and there have been no revisions of the module hardware. 3.2 POWER SUPPLY Minimum supply voltage 8V continuous, 4V for up to 5 minutes. Cranking dropouts Able to survive 0V for 50mS providing the supply was at least 10V before

the dropout and recovers to 5 volts afterwards. Maximum supply voltage 35V continuous (protection to 60V) Maximum operating current

112mA at 12V, 53mA at 24V Conditions: All LED’s lit and sounder active.

Maximum standby current 74mA at 12V, 35mA at 24V Conditions:All LED’s off and sounder inactive.

3.3 TERMINAL SPECIFICATION Connection type Screw terminal, rising clamp, no internal spring Min cable size 0.5mm² (AWG 20) Max cable size 2.5mm² (AWG 14) Recommended cable size

Refer to table below

Product type

DSE 2548 relay expansion module

2548

Variant

Standard product

00

Hardware revision

Revision 1 001

Page 8: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

6 057-084 Issue 1 DSE2548 LED expansion operator manual

3.4 DSENET® DSEnet is the interconnection cable between the host controller and the expansion module(s) and must not be connect to any device other than DSE equipment designed for connection to the DSEnet. Cable type Two core screened twisted pair Cable characteristic impedance 120Ω Recommended cable Belden 9841

Belden 9271 Maximum cable length 1000m (1km) when using Belden 9841 or direct equivalent.

500m (0.5km) when using Belden 9271 or direct equivalent. DSEnet topology Bus with no stubs (spurs) DSEnet termination 120Ω. Fitted internally to host controller. Must be fitted externally

to the ‘last’ expansion module by the customer . Maximum expansion modules Refer to host controller documentation

NOTE : As a termination resistor is internally fitt ed to the host controller, the host controller must be the ‘first’ unit on the DSEnet. A terminati on resistor MUST be fitted to the ‘last’ unit on the DSEnet. See the section entitled ‘Typical Wiring Diagram’ elsewhere in this manual for details. 3.5 DIMENSIONS Overall size 180.0mm x 116.0mm x 42.7mm

(7.07” x 4.57” x 1.68”) Mounting type Panel mounting Panel cutout 154mm x 98mm

(6.06” x 3.86”)

Page 9: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

057-083 Issue 1 DSE2548 LED expansion operator manual 7

3.6 APPLICABLE STANDARDS BS EN 60068-2-1 (Minimum temperature) -30°C (-22°F)

BS EN 60068-2-2 (Maximum temperature) +70°C (158°F)

BS EN 60950 Safety of information technology equipment, including electrical business equipment

BS EN 61000-6-2 EMC Generic Immunity Standard (Industrial) BS EN 61000-6-4 EMC Generic Emission Standard (Industrial) BS EN 60529 (Degrees of protection provided by enclosures)

IP65 when mounted into panel with optional gasket IP42 when mounted into panel WITHOUT gasket

UL508 NEMA rating

Enclosure type 2 when mounted into panel WITHOUT gasket Enclosure type 12 when mounted into panel with gasket

In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.

4 INSTALLATION 4.1 USER CONNECTIONS 4.1.1 CONNECTOR A Terminal Function Recommended size 1 DC supply positive 1.0mm² (AWG 18) 2 DC supply negative 1.0mm² (AWG 18) 3 Screen DSEnet only 4 A 0.5mm² (AWG 20) DSEnet only 5 B 0.5mm² (AWG 20) DSEnet only 4.2 SCHEMATIC INTERCONNECTION DIAGRAM

Page 10: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

8 057-084 Issue 1 DSE2548 LED expansion operator manual

4.3 TYPICAL WIRING DIAGRAM

Page 11: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

057-083 Issue 1 DSE2548 LED expansion operator manual 9

5 CONTROLS AND INDICATIONS

5.1 LED INDICATIONS Function Colour Action Power on / Link lost RED Steady when DC supply is connected and data is being received

from the host controller. Flashing when the DC supply is connected and the data connection to the host controller is not operating.

Status 1-8 RED Lit when the corresponding channel is active 5.2 SOUNDER The 2548 LED expansion module has an integral sounder, activated upon a signal from the ‘host controller’. The controller will activate the sounder when an alarm becomes active and silence the sounder when an alarm mute button (local or remote) is pressed. 5.3 PUSH BUTTON

Pressing the button will signal to the host controller that the button is pressed. The controller will respond by lighting all LEDs on the 2548 module (lamp test) and silencing the sounder (alarm mute). If configured to do so, the host controller will also perform a lamp test and alarm mute function.

Address Switch

Lamp test/alarm mute

Page 12: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

10 057-084 Issue 1 DSE2548 LED expansion operator manual

5.4 ID SWITCH The rotary ID switch is used to select the ‘Identification’ of the 2548 expansion module as the host controller is capable of giving instructions to a number of 2548 expansion modules at the same time (consult relevant modules instructions for further details on number of supported expansion units). The switch (located at the rear of the module) should be operated using a small screwdriver and set to match the required ID.

NOTE : The ID MUST be a unique number, different fr om the ID of any other 2548 module connected to the host controller. If two or more 2548 controllers are required to ‘mi mic’ each other then they should be configured with different IDs, and both configured the same in the host controller.

NOTE : The selection of the ID of other types of expansion modules WILL NOT interfere/clash with the ID of the 2548. For instance if the 2548 i s set to ID4, it is acceptable to have a different type of expansion module (for instance 2130) set to ID4 also.

Page 13: DSE 2548 - Hipower · DSE 2548 DSENET ® OUTPUT EXPANSION ... 4.2 SCHEMATIC INTERCONNECTION DIAGRAM ... Connection type Screw terminal, rising clamp, no internal spring

DSE2548 relay output expansion module

057-083 Issue 1 DSE2548 LED expansion operator manual 11

6 FAULT DIAGNOSIS Nature of problem Suggest ion LEDs don’t activate on the 2548 module Ensure the host controller is correctly

configured to send signals to the 2548 Power LED indication does not illuminate Check polarity and size of the connected DC

supply are within the specifications of the DSE2548

Power LED flashes This means the the communications link to the host controller has been lost. Check the connection of the DSEnet paying particular attention to the cable type being used and the positioning of the termination resistors.

7 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE2548 is designed to be Fit and Forget. As such, there are no user serviceable parts. In the case of malfunction you should contact your original equipment supplier (OEM).

8 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, you are referred to your original equipment supplier (OEM).

9 DISPOSAL 9.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT ) Directive 2002/96/EC If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of WEEE separately from your other waste. 9.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES Directive 2002/95/EC:2006 To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB & PBDE´s) Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s Department of Trade and Industry RoHS REGULATIONS Guide (Para 11). Despite this exemption DSE has been carefully removing all non RoHS compliant components from our supply chain and products. When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into DSE production. This is a process that is almost complete and is being phased through different product groups.