VENTILATION-PSYCHROMETRICS-AHUBased on ASHRAE 62
![Page 2: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/2.jpg)
Purpose
¨ Set minimum Outdoor Air ventilation Rates ¨ Air Quality acceptable for human occupants and
minimize negative effects on Health ¨ Systems & Equipment ¨ Psychrometrics ¨ Operation-Maintenance
![Page 3: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/3.jpg)
Standard 62.1 ¨ Applies to for all buildings except low-rise
residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates for Smoking
![Page 4: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/4.jpg)
Standard 62.2
¨ Applies to low-rise residential buildings. ¨ All Air Systems may be suited ¨ Thermal Comfort based on Standard 55 should be
considered.
![Page 5: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/5.jpg)
62.1
¨ A building is compliant with the standard as long as it is designed constructed operated and maintained to meet the requirements of §4, §5, §6, §7 and §8 regardless of the level of occupant satisfaction or dissatisfaction.
![Page 6: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/6.jpg)
Outdoor Air Quality
Regional Air Quality ¨ Ozone ¨ Particulate matter ¨ Carbon monoxide ¨ Sulfur oxides ¨ Nitrogen dioxide and ¨ Lead
![Page 7: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/7.jpg)
Outdoor Air Quality
Local Air Quality ¨ Toilet/kitchen exhaust ¨ Exhaust from smoking lounges ¨ Exhaust from restaurants ¨ Print shop/photo developing exhaust ¨ Cooling towers ¨ Automobile traffic
![Page 8: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/8.jpg)
¨ Parking garages; ¨ Dumpsters; ¨ Loading docks; ¨ Helicopter pads; ¨ Emergency generators; ¨ Manufacturing plants; ¨ Industrial facilities; ¨ Landfills.
![Page 9: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/9.jpg)
Systems & Equipment
¨ Ventilation Air Distribution ¨ Designing for Air Balancing ¨ Exhaust Duct Location
![Page 10: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/10.jpg)
Ventilation System Controls
¨ Constant Volume Systems ¨ Variable Volume Systems (VAV)
![Page 11: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/11.jpg)
Air Ducts ¨ Resistance to Mold Growth ¨ Resistance to Erosion ¨ Exhaust Duct Location ¨ Outdoor Air Intakes Location for Rain,Snow,Birds
![Page 12: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/12.jpg)
Air Handling Units (AHU)
¨ Fans ¨ Coils (Heating,Cooling,DX) ¨ Humidifiers, Water Spayers ¨ Mixing Plenums ¨ Filters ¨ Drains ¨ Casing
![Page 13: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/13.jpg)
Procedures
¨ Ventilation Rate Procedure (VRP) ¨ Indoor Air Quality Procedure (IAQP) ¨ Natural Ventilation Procedure (NVP).
![Page 14: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/14.jpg)
VRP
¨ for various space types ¨ based on contaminant sources and source emission
rates ¨ to dilute and exhaust odorous bioeffluents from
occupants and odorous and sensory irritant contaminants from other sources
¨ LEED suitable
![Page 15: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/15.jpg)
IAQP
¨ is a performance based procedure ¨ Rates are calculated based on contaminant source
emission rates and desired indoor concentrations
![Page 16: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/16.jpg)
NVP
¨ ventilation through openings (e.g. windows) ¨ manual control of the occupants of a space ¨ specifies minimum opening size for the space to be
ventilated
![Page 17: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/17.jpg)
¨ Vbz = Vp +Va
¨ Vp : ventilation rate required to control both people-related sources
¨ Va : ventilation rate required for building-related or area-based sources
¨ Vbz : breathing zone ventilation
![Page 18: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/18.jpg)
¨ Vbz = Rp Pz + Ra Az
¨ Rp = outdoor airflow rate required per person ¨ Pz = zone population: the number of people in the
ventilation zone during typical usage. ¨ Ra = outdoor airflow rate required per unit area ¨ Az = zone floor area: the net occupiable floor area
of the ventilation zone
![Page 19: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/19.jpg)
Ventilation Efficiency
![Page 20: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/20.jpg)
Ventilation Rate Procedure Flow Chart
![Page 21: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/21.jpg)
Zone Air Distribution Effectiveness (Ez)
![Page 22: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/22.jpg)
Construction & Start up
¨ Application ¨ Air Balancing ¨ Testing of Drain Pans ¨ Testing of Outdoor Air Dampers ¨ System Documentation
![Page 23: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/23.jpg)
Operation & Maintenance
¨ Operation-Maintenance Manual
![Page 24: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/24.jpg)
62.2
¨ standard applies to all residential spaces intended for human occupancy in single family houses or in multifamily buildings up to three stories.
![Page 25: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/25.jpg)
This includes:¨ living rooms, ¨ bedrooms, ¨ kitchens, ¨ bathrooms, ¨ hallways, ¨ closets ¨ store rooms, ¨ laundries, ¨ garages, ¨ basements
![Page 26: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/26.jpg)
Requirements
¨ control strategies, ¨ sound levels, ¨ duct design, ¨ maximum flow rates for unbalanced systems, ¨ isolation of garages, ¨ duct tightness.
![Page 27: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/27.jpg)
Required (mechanical) ventilation rate
¨ standard assumes that the first bedroom will have two occupants, with one additional occupant for each additional bedroom
¨ L/s = Floor Area /20 + (Number of Bedrooms + 1) x 3.5
¨ The required ventilation rates are 0.05 L/s per m² (1 L/s per 20 m²) plus 3.5 L/s per occupant.
![Page 28: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/28.jpg)
Exceptions
1) the building has no air-conditioning and is located in a warm climate, then it is likely that the windows will be open much of the time.
2) the building is heated or cooled for human occupancy for less than 876 hours per year. (876 hours is 10% of the year, or 36½ days.) ie vacation home etc
![Page 29: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/29.jpg)
Infiltration
¨ A value of 10 L/s per 100 m2 is based on a fairly tight house, built with good attention to air sealing.
¨ If it is determined by testing that the house has a higher infiltration rate then we use ASHRAE Standard 136
L/s = L/s from Table - ½ x (Measured Infiltration in L/s/m² – 0.10 L/s/m2) x Floor Area in m²
![Page 30: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/30.jpg)
Combination ventilation Systems
¨ Heat Recovery core or wheel to move heat or an Energy Recovery core or wheel
¨ Heat Recovery Ventilators (HRVs) used in cold climates to preheat the incoming air or in hot climates to cool the incoming air with the cooled air from the house
![Page 31: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/31.jpg)
¨ Energy Recovery Ventilators (ERVs) recover the sensible heat from the temperature difference as well as the latent heat of evaporation when the moisture condenses from the warmer air stream as it is cooled by the other air stream. ERV’s also transfer moisture between the air streams, from higher water vapor concentration to lower
![Page 32: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/32.jpg)
Minimum Filtration
¨ filtration of no less than MERV 6 efficiency
![Page 33: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/33.jpg)
Sound Ratings
![Page 34: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/34.jpg)
¨ Acoustical insulation [dB]: Sound insertion lo ¨ In-duct sound power level [dB]: Sound power level
per octave band, radiated in the duct. ss value of the Air Handling Unit.
¨ Airborne sound power level [dB(A)]: Sound power level radiated through the envelope of the Air Handling Unit.
![Page 35: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/35.jpg)
Psychrometrics
![Page 36: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/36.jpg)
ASHRAE SUMMER comfort range
![Page 37: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/37.jpg)
ASHRAE WINTER comfort range
![Page 38: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/38.jpg)
Heating
![Page 39: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/39.jpg)
Heating + Steam
![Page 40: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/40.jpg)
Heating + Water Humidifier (incorrect)
![Page 41: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/41.jpg)
Heating + Water Humidifier (correct)
![Page 42: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/42.jpg)
Recuperative Heat Recovery
![Page 43: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/43.jpg)
Regenerative Heat Recovery
![Page 44: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/44.jpg)
Cooling (only sensible)
![Page 45: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/45.jpg)
Cooling (Sensible + Latent)
![Page 46: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/46.jpg)
Recu + Cooling (incorrect)
![Page 47: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/47.jpg)
Recu + Cooling (correct)
![Page 48: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/48.jpg)
Regen + Cooling
![Page 49: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/49.jpg)
Recu + Dehumification
![Page 50: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/50.jpg)
Mixing (if allowed)
![Page 51: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/51.jpg)
Air Handling Units (AHU)
![Page 52: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/52.jpg)
Fans (Belt Driven)
![Page 53: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/53.jpg)
Fans (direct drive)
![Page 54: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/54.jpg)
Coils (water or dx)
![Page 55: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/55.jpg)
Recuperators
![Page 56: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/56.jpg)
Regenerators
![Page 57: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/57.jpg)
Humidifiers (water)
![Page 58: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/58.jpg)
Humidifiers (steam)
![Page 59: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/59.jpg)
Dampers
![Page 60: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/60.jpg)
Casing
¨ Deflection [mm/m]: The largest deformation of the sides of the unit under pressure, positive or negative, given as a difference in distance from a reference plane outside the unit to the external unit surface with and without test pressure. The deflection, related to the span, defines the casing strength.
¨ Air leakage factor [l.s-1.m-2]: The air leakage in volume per unit of time, related to the external casing area.
¨ Thermal transmittance [W.m-2.K-1]: The heat flow per area and temperature difference through the casing of the air handling unit.
¨ Thermal bridging factor [-]: The ratio between the lowest temperature difference between any point on the external surface and the mean internal air temperature and the mean air-to-air temperature difference.
![Page 61: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/61.jpg)
Energy Efficiency Classification
¨ Based on Eurovent: ¨ Two main Groups
![Page 62: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/62.jpg)
Thermal Energy for Heating
¨ Thermal Energy for Heating considering the Heat Recovery System (HRS) efficiency
¨ The climate dependency ¨ The difference in primary energy between thermal
energy and electrical energy is taken into account to evaluate the impact of the pressure drops across the HRS
![Page 63: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/63.jpg)
Thermal Energy for Cooling
¨ Thermal energy for cooling is not considered because it will have less impact (negligible for most of Europe) ?????
![Page 64: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/64.jpg)
Electrical Energy (for fans only*)
![Page 65: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/65.jpg)
European Standard EN13053
¨ “Ventilation for buildings – Air handling units – Rating and performance for units, components and sections.”
![Page 66: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/66.jpg)
Some Prerequisites
¨ Air density = 1.2 kg/m³ ¨ Design Conditions for air flows, outdoor
temperature, mixing ratio, heat recovery efficiency, etc
¨ Velocities based on the area of the filter section of the respective unit, or if no filter is installed, it is based on the area of the fan section
![Page 67: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/67.jpg)
¨ The relationship between velocity in the cross section of the unit and internal static pressure drop is considered to be exponential to the power of 1.4
¨ The heat recovery dry efficiency at balanced air volume flows shall be used.
¨ Pressure drop evaluation of the heat recovery
![Page 68: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/68.jpg)
Air Handling Unit subgroups
¨ Units for full or partial outdoor air at design winter temperature ≤ 9°C.
¨ recirculation air is less than 85 %. ¨ If more recirculation is claimed, the calculation value
for 85% shall be used in the applicable equation for pressure correction Δpz
¨ This subgroup will consider the velocity in the filter cross section, the HRS efficiency and pressure drop and the mains power consumption to the fan(s)
¨ The class signs are A to <E.
![Page 69: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/69.jpg)
Air Handling Unit subgroups
¨ Recirculation units or units with design inlet temperatures always > 9°C.
¨ This subgroup will only consider the cross section velocity of the filter section and mains power consumption to the fan(s).
¨ The class signs are from
![Page 70: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/70.jpg)
Air Handling Unit subgroups ¨ Stand-alone extract air units ¨ pure extract air units ¨ they could include heat recovery ¨ design outdoor temperature has no relevance for
such units ¨ This subgroup will consider the cross section velocity
of the filter section and mains power consumption to the fan(s)
¨ The class signs are from
![Page 71: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/71.jpg)
Table for energy efficiency calculations
![Page 72: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/72.jpg)
Methodology
¨ The principle is to establish whether the selected unit with different energy parameters will consume no more energy than a unit that would exactly meet the requirements for the aimed class in Table above
![Page 73: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/73.jpg)
Conclusions
¨ For High Rise buildings Mechanical Ventilation is not just an “extra” feature to do but a necessity.
¨ A good design in Mechanical Ventilation can increase the comfort acceptance of indoors climate and reduce sizing of the Equipment.
¨ For Low Rise Buildings Mechanical Ventilation can be avoided but going towards NZEB will become a necessity too.
![Page 74: VENTILATION- PSYCHROMETRICS- · PDF fileStandard 62.1 ¨ Applies to for all buildings except low-rise residential. ¨ No Retroactive Application ¨ No Recommended Ventilation Rates](https://reader033.vdocuments.mx/reader033/viewer/2022051522/5a7019287f8b9a9d538ba3dd/html5/thumbnails/74.jpg)
Conclusions
¨ In Europe and especially in Mediterranean countries (like Greece-Italy-Spain etc) Cooling Loads for Ventilation are more than Heating and need to be Calculated.
¨ Except from the an Energy efficient Ventilation system we also need to include a High Performance Heat Recovery (sensible/latent) system for most ventilations systems