Transformer
The transformer is a static device, (the
one which does not contain anyrotating or moving parts) which is usedto transfer electrical energy from oneac circuit to another ac circuit, with
increase or decrease in voltage/currentbut without any change in frequency.
-
8/13/2019 Transformer (Mumbai University)
2/87
8/14/2013 unit 4-Transformer
-
8/13/2019 Transformer (Mumbai University)
3/87
8/14/2013 unit 4-Transformer
Ac input Ac output
I1, V1 I2, v2
Transformer
-
8/13/2019 Transformer (Mumbai University)
4/87
8/14/2013 unit 4-Transformer
Application of a Transformer
-
8/13/2019 Transformer (Mumbai University)
5/87
8/14/2013 unit 4-Transformer
Transformer Symbol
(Iron core)
5
Schematic symbol for transformer consists of twoinductor symbols, separated by lines indicating aferromagnetic core.
The two inductor coils are easily distinguished in the symbol. Thepair of vertical lines represent an iron core common to bothinductors. While many transformers have ferromagnetic corematerials, there are some that do not, their constituent inductorsbeing magnetically linked together through the air.
-
8/13/2019 Transformer (Mumbai University)
6/87
8/14/2013 unit 4-Transformer
Laboratory transformer
6
-
8/13/2019 Transformer (Mumbai University)
7/87
8/14/2013 unit 4-Transformer
Generator transformer
7
-
8/13/2019 Transformer (Mumbai University)
8/87
8/14/2013 unit 4-Transformer
Substation transformer
8
-
8/13/2019 Transformer (Mumbai University)
9/87
8/14/2013 unit 4-Transformer
3 Phase 3 wire transmission / 3 phase 4 wire utilization
-
8/13/2019 Transformer (Mumbai University)
10/87
8/14/2013 unit 4-Transformer
Transformer can be step up or stepdown transformer. The principle ofoperation is same.
In step up the secondary coil consistsof large no of turns of insulated copper
wires Low voltage high current ac
high voltage low current
-
8/13/2019 Transformer (Mumbai University)
11/87
8/14/2013 unit 4-Transformer
AUTO-TRANSFORMER
11
-
8/13/2019 Transformer (Mumbai University)
12/87
8/14/2013 unit 4-Transformer
ISOLATION TRANSFORMER
12
P i i ti
-
8/13/2019 Transformer (Mumbai University)
13/87
8/14/2013 unit 4-Transformer
Princip e o operation examEnergy is being transferred from the primary coil tothe secondary coil by means of a mutual magneticfields.
-
8/13/2019 Transformer (Mumbai University)
14/87
8/14/2013 unit 4-Transformer
-
8/13/2019 Transformer (Mumbai University)
15/87
8/14/2013 unit 4-Transformer
-
8/13/2019 Transformer (Mumbai University)
16/87
8/14/2013 unit 4-Transformer
Can D.C. Supply be used forTransformer?
No The transformer works on the principle of mutual
induction, for which current in one coil must changeuniformly. If d.c. supply is given, the current will notchange due to constant supply and transformer will
not work. Practically winding resistance is very small. Ford.c., the inductive reactance XL is zero as d.c. has nofrequency. So total impedance of winding is very lowfor d.c. Thus winding will draw very high current ifd.c. supply is given to it. This may cause the burningof windings due to extra heat generated and may
cause permanent damage to the transformer. There can be saturation of the core due to which
transformer draws very large current from the supplywhen connected to d.c.
-
8/13/2019 Transformer (Mumbai University)
17/87
8/14/2013 unit 4-Transformer
Construction of transformer
-
8/13/2019 Transformer (Mumbai University)
18/87
8/14/2013 unit 4-Transformer
Construction contd.
1) Magnetic circuit consisting of limbs(core), yokes and clamping structures(providing the flux path)
2) Electric circuit consisting of primaryand secondary windings
3) Dielectric circuit consisting ofinsulation in different forms and used
at different places in the transformeri.e core to primary winding, primarywinding to secondary winding, etc)
-
8/13/2019 Transformer (Mumbai University)
19/87
8/14/2013 unit 4-Transformer
Types of Transformers
Depending on construction:
Core type ,Shell type
Depending on transformation ratio: Step-up ,Step-down,Isolation
&Auto-Xmer
Depending on supply:
Single phase & three phase
19
-
8/13/2019 Transformer (Mumbai University)
20/87
8/14/2013 unit 4-Transformer
Core type and shell typetransformer
http://en.wikipedia.org/wiki/File:Transformer_winding_formats.jpg -
8/13/2019 Transformer (Mumbai University)
21/87
8/14/2013 unit 4-Transformer
Core Type Transformer
21
-
8/13/2019 Transformer (Mumbai University)
22/87
8/14/2013 unit 4-Transformer
Shell Type Transformer
22
-
8/13/2019 Transformer (Mumbai University)
23/87
8/14/2013 unit 4-Transformer
Core type transformer
-
8/13/2019 Transformer (Mumbai University)
24/87
8/14/2013 unit 4-Transformer
Core type transformer
A single phase core type transformer consists ofa magnetic frame with two cores, upper yokeand bottom yoke. The primary and secondarycoils are split into two half turns of the primaryand half the secondary turns are placed on each
core (limb) A 3-phase core type transformer consists of
minimum 3 cores, each provided with theprimary and secondary coils of one phase.
Circular coils (windings) are used in the coretype transformer, which indicate theoretically
that a circular core should be used. It is very complicated to manufacture circular
core as a result, the stepped core is generallyused.
-
8/13/2019 Transformer (Mumbai University)
25/87
8/14/2013 unit 4-Transformer
Shell type Transformer
-
8/13/2019 Transformer (Mumbai University)
26/87
8/14/2013 unit 4-Transformer
Shell type transformer
It consists of magnetic frame with a central core(limb) and two side cores, completing the pathof magnetic flux.
Primary and secondary coils (windings) are
placed on the central core in a particular fashionas shown in figure. Such an arrangement formsa shell of iron around copper.
The central leg flux is divided at the yokesection, half i.e. /2 towards each side leg.
As the flux in the section of yoke and side coresis only half, the cross section of the yokes andside cores is approximately half the section ofthe central limb
-
8/13/2019 Transformer (Mumbai University)
27/87
8/14/2013 unit 4-Transformer
Comparison
Core Type
1. The windingsenclose the wholecore.
2. Average length ofthe core is more.
3. Magnetic flux hasonly one continuouspath.
4. More suitable forHV transformers.
5. Easy to repair.
Shell Type
1. The core enclosesthe windings.
2. Average length ofthe core is less.
3. Magnetic flux isdistributed into twoparts.
4. More suitable for LVtransformers.
5. Difficult to repair.
27
-
8/13/2019 Transformer (Mumbai University)
28/87
8/14/2013 unit 4-Transformer
Ideal Transformer (exam)
An Ideal transformer is an imaginary transformerstudied to understand the concept easily.
Characteristics
1) An ideal transformers core is highly permeable
so that it requires very small magneto motiveforce (mmf) to set up the flux in the core.
2) Its leakage flux is zero, that is the entire flux isconfined to the core and links with both thewindings
3) The resistance of the primary and secondarywinding is negligible (zero).
Therefore E1=V1 and E2= V2
-
8/13/2019 Transformer (Mumbai University)
29/87
8/14/2013 unit 4-Transformer
Characteristics of idealtransformer
4) There are no losses due toresistance, hysteresis and eddycurrents.
5) Efficiency of an ideal transformeris 100% as no losses takes place.
6) Voltage regulation is 0 %. Thatmeans secondary voltage willremain constant irrespective ofthe load current.
-
8/13/2019 Transformer (Mumbai University)
30/87
8/14/2013 unit 4-Transformer
Practical Transformer
A practical transformer possesses the
following characteristics:
1. There are Cu & Iron losses.2. There is leakage flux.
3. Its windings contain ohmic
resistance.
30
-
8/13/2019 Transformer (Mumbai University)
31/87
8/14/2013 unit 4-Transformer
Comparison
Practical Transformer
1. There are Cu & ironlosses.
2. There is leakage flux.
3. Its windings containohmic resistance.
4. Voltage regulation isnever 0%.
5. Efficiency is 93-97 %.
6. All constructedtransformers arepracticaltransformers.
Ideal Transformer1. There is no loss.
2. There is no leakageflux.
3. Its windings consist of
purely inductive coils,wound on a losslesscore.
4. Voltage regulation is0%.
5. Efficiency is 100%.6. It is impossible toconstruct an idealtransformer.
31
-
8/13/2019 Transformer (Mumbai University)
32/87
8/14/2013 unit 4-Transformer
EMF equation of a transformer (e)
-
8/13/2019 Transformer (Mumbai University)
33/87
8/14/2013 unit 4-Transformer
EMF equation of a transformer
The various quantities which affect themagnitude of the induced e.m.f. are :
= Fluxm = Maximum value of flux
N1 = Number of primary winding turnsN2 = Number of secondary winding turns
f = Frequency of the supply voltageE1 = R.M.S. value of the primary induced
e.m.f.E2 = R.M.S. value of the secondary induced
e.m.f.
-
8/13/2019 Transformer (Mumbai University)
34/87
8/14/2013 unit 4-Transformer
refer notes
-
8/13/2019 Transformer (Mumbai University)
35/87
8/14/2013 unit 4-Transformer
Losses in transformer
An ideal transformer has no loss.
But in practical transformercopper losses (Pcu ) and ironlosses (Pi) takes place. Iron lossis further classified into two typesnamely hysteresis loss and eddy
current loss.
-
8/13/2019 Transformer (Mumbai University)
36/87
8/14/2013 unit 4-Transformer
Copper Loss
Copper losses occur in all those parts of atransformer that carry electric current.
It is the total power loss taking place in the
winding resistances of a transformer Copper Loss = Power loss in the primary
resistance + Power loss in the secondaryresistance.
Cu loss can be calculated by conducting
SC test on the transformer.
36
-
8/13/2019 Transformer (Mumbai University)
37/87
8/14/2013 unit 4-Transformer
Copper Loss
Should be kept as low as possible toincrease efficiency.
To reduce this reduce R1 & R2.
Also called as variable loss-dependenton square of load current.
37
-
8/13/2019 Transformer (Mumbai University)
38/87
8/14/2013 unit 4-Transformer
Iron Losses (or Core Losses)
Hysteresis loss occurs in the magneticframe of the transformer.
Due to time varying flux, there isinduced emf in the core which causeseddy currents to flow through the corebody.
Iron loss can be calculated byconducting OC test on transformer.
38
-
8/13/2019 Transformer (Mumbai University)
39/87
8/14/2013 unit 4-Transformer
Losses in a Transformer
Hysteresis loss depends on area of hysteresis loopof magnetic material used for frame, volume ofcore, frequency of magnetic flux reversal. Thisloss can be minimized by selecting a material forthe core that has a low hysteresis coefficient(silicon steel)
Eddy current loss depends on thickness of lamination of core, frequency of flux reversal,maximum value of flux density in core, volume ofcore, quality of magnetic material used for themagnetic frame. This loss can be minimized byusing laminated core.
39
-
8/13/2019 Transformer (Mumbai University)
40/87
8/14/2013 unit 4-Transformer
Ideal Transformer(no load)
40
-
8/13/2019 Transformer (Mumbai University)
41/87
8/14/2013 unit 4-Transformer
Conditions for an ideal or loss freetransformer
The primary and secondary windingsdo not have any resistance i.e.winding resistance of primary and
secondary should be zero.
The losses taking place in the corei.e. hysteresis loss and eddy current
loss should be zero. There should not be any leakage flux
-
8/13/2019 Transformer (Mumbai University)
42/87
8/14/2013 unit 4-Transformer
Phasor Diagram
42
-
8/13/2019 Transformer (Mumbai University)
43/87
8/14/2013 unit 4-Transformer
Ideal transformer on load
Refer notes
Practical transformer on no load
Refer notes
-
8/13/2019 Transformer (Mumbai University)
44/87
8/14/2013 unit 4-Transformer
Ideal transformer on load
When some load is connected between thesecondary terminals of the transformer, thetransformer is said to be loaded or on load.
Due to load on the secondary , a finitesecondary current starts flowing.
If the load is R+L type the I2 will lagbehind V2 by an angle 2.
As per the lenzs law, the secondary currentI2 will oppose the cause producing it.Hence it opposes the magnetic flux. This iscalled demagnetizing effect of I2
-
8/13/2019 Transformer (Mumbai University)
45/87
8/14/2013 unit 4-Transformer
Ideal transformer on load
I2 = I2 * N2/N1 =kI2 I2 = kI2 is 180 degree out of phase
with I2.
The net primary current is 1 =2 + mag Thus due to load on secondary side,
the primary current of thetransformer increases to supply theadditional power to the load
-
8/13/2019 Transformer (Mumbai University)
46/87
8/14/2013 unit 4-Transformer
Practical transformer on NO load
When the practical transformer is onNo load, the secondary current will bezero. Hence the copper loss in the
secondary winding is zero. However a small primary current does
flow under the no load condition. Dueto small primary resistance, a small
primary copper loss takes place evenat no load
-
8/13/2019 Transformer (Mumbai University)
47/87
8/14/2013 unit 4-Transformer
Practical transformer on NO load
The primary current under no loadcondition has to supply the ironlosses and a small primary copper
loss. The primary current under the no
load condition is denoted by o. o =m +c m is the magnetizing component c is the active component
-
8/13/2019 Transformer (Mumbai University)
48/87
8/14/2013 unit 4-Transformer
Practical transformer no No load
Im is the purely reactive component.
It magnetizes the core and producesflux in the core.
This component is at 90 degree w.r.tto E1.
Im is also called as wattlesscomponent.
-
8/13/2019 Transformer (Mumbai University)
49/87
8/14/2013 unit 4-Transformer
Practical transformer no No load
Ic is the active component of no loadcurrent Io.
Its job is to supply the total loss
under no load conditions. It is therefore called as the power
component or core less component ofIo.
It is at 90 degree w.r.t themagnetizing current Im.
-
8/13/2019 Transformer (Mumbai University)
50/87
8/14/2013 unit 4-Transformer
Practical Transformer(no load)
50
-
8/13/2019 Transformer (Mumbai University)
51/87
8/14/2013 unit 4-Transformer
o =m +c Im and Ic are 90degree phase shifted
w.r.t each other and Io is the resultantof the two.
No laod power factor = coso
Im = Io sino
Ic= Io coso
Io=Im2 + Ic2 o = tan-1(Im/Ic)
-
8/13/2019 Transformer (Mumbai University)
52/87
8/14/2013 unit 4-Transformer
Total input power on No load
Wo = V1 Io coso
Io coso =Ic
Wo= V1 Ic primary current Io is very small therefore
primary copper loss is very very small. Icis called as core loss or iron losscomponent.
Wo represents the core loss or iron loss ascopper is small.
Wo- iron loss= V1 Ic
-
8/13/2019 Transformer (Mumbai University)
53/87
8/14/2013 unit 4-Transformer
Practical Transformer(on load)-w/o resistance and leakage
53
-
8/13/2019 Transformer (Mumbai University)
54/87
8/14/2013 unit 4-Transformer
Practical transformer on load
When some load is connected between thesecondary terminals of the transformer, itis said to be on load.
Due to the load on secondary, a finitesecondary current starts flowing.Depending on the type of load (resistive,inductive , capacitive) the secondary
current I2 will be in phase, or lag or leadthe load voltage V2.
-
8/13/2019 Transformer (Mumbai University)
55/87
8/14/2013 unit 4-Transformer
Due to loading of the transformer, the primary currentincreases above its no load value due to the followingfactors:
1) when the transformer is loaded, the load current I2 willstart flowing. Due to increase in load current I2 thesecondary ampere turns N2I2 will also increase.
2)This increased secondary (mmf) N2I2 will increase theflux 2 set up by the secondary current.
3) This flux opposes the main flux 1 set up in the core bythe current flowing through the primary winding. Hence thesecondary mmf N2 I2 is called as the demagnetizingampere turns.
Due to reduction in the main flux 1, the induced emf in theprimary winding E1 will also reduce. Hence the differencebetween Vi and E1 will increase and the primary current willincrease.
-
8/13/2019 Transformer (Mumbai University)
56/87
8/14/2013 unit 4-Transformer
Effect of additional primary current
The additional current drawn by the primary windingdue to the loading is called as the load component I2
I2 is 180 degree out of phase with load current I2.The current I2 develop its own magnetic flux 2.
2 is in opposite direction to that of 2. Hence it helps the main flux 1.
1 and 2 are in the same direction Thus the reduction in the main flux due to 2 is
compensated by 2 and the core flux 1 will almost
remain constant. Therefore for any load between no load to full load,
the core flux will always remain constant.
-
8/13/2019 Transformer (Mumbai University)
57/87
8/14/2013 unit 4-Transformer
Phasor Diagram
57
-
8/13/2019 Transformer (Mumbai University)
58/87
8/14/2013 unit 4-Transformer
Effect of leakage reactance
http://en.wikipedia.org/wiki/File:Transformer_flux.gif -
8/13/2019 Transformer (Mumbai University)
59/87
8/14/2013 unit 4-Transformer
notes
P ti l T f ( l d)
-
8/13/2019 Transformer (Mumbai University)
60/87
8/14/2013 unit 4-Transformer
Practical Transformer(on load)-with resistance and leakage
60
Ph di f it
-
8/13/2019 Transformer (Mumbai University)
61/87
8/14/2013 unit 4-Transformer
Phasor diagram for unitypower factor load
61
Ph di f l i
-
8/13/2019 Transformer (Mumbai University)
62/87
8/14/2013 unit 4-Transformer
Phasor diagram for laggingpower factor
62
Ph di f l di
-
8/13/2019 Transformer (Mumbai University)
63/87
8/14/2013 unit 4-Transformer
Phasor diagram for leadingpower factor
63
T f P t
-
8/13/2019 Transformer (Mumbai University)
64/87
8/14/2013 unit 4-Transformer
Transformer Parameters1. Effect OF Winding Resistances
High voltage side Low current side High resistancesideLow voltage side High current side Low resistanceside
Sejal Chopra,DBIT,Kurla 64
-
8/13/2019 Transformer (Mumbai University)
65/87
8/14/2013 unit 4-Transformer
Equivalent Impedance
65
i l d
-
8/13/2019 Transformer (Mumbai University)
66/87
8/14/2013 unit 4-Transformer
Equivalent Impedance
66
-
8/13/2019 Transformer (Mumbai University)
67/87
8/14/2013 unit 4-Transformer
Rules for Transferring Parameters and Quantities
Sejal Chopra,DBIT,Kurla 67
-
8/13/2019 Transformer (Mumbai University)
68/87
8/14/2013 unit 4-Transformer
Rules for Transferring Parameters andQuantities
Sejal Chopra,DBIT,Kurla 68
-
8/13/2019 Transformer (Mumbai University)
69/87
8/14/2013 unit 4-Transformer
Rules for Transferring Parameters andQuantities
69
Equivalent circuit of
-
8/13/2019 Transformer (Mumbai University)
70/87
8/14/2013 unit 4-Transformer
qTransformer
70
No load equivalent circuit
Equivalent circuit of
-
8/13/2019 Transformer (Mumbai University)
71/87
8/14/2013 unit 4-Transformer
qTransformer
71
Exact equivalent circuit
-
8/13/2019 Transformer (Mumbai University)
72/87
8/14/2013 unit 4-Transformer
Exact equivalent circuitreferred to primary
72
R2'= R2/K2 , X2' = X2/K
2' , Z2' = Z2/K2
While E2' = E2/K' I2' = K I2Where K = N2 /N1
Exact equivalent circuit
-
8/13/2019 Transformer (Mumbai University)
73/87
8/14/2013 unit 4-Transformer
Exact equivalent circuitreferred to secondary
73
R1' = K2 R1 , X1' = K
2 X1, Z1' = K2 Z1
E1'= K E1, Io' = I1 /K' Io' = Io /K
-
8/13/2019 Transformer (Mumbai University)
74/87
8/14/2013 unit 4-Transformer
Calculation of Regulation
74
-
8/13/2019 Transformer (Mumbai University)
75/87
8/14/2013 unit 4-Transformer
Efficiency of a Transformer Power output = Power input Total
losses
Power input = Power output + Totallosses
Power input = Power output + Pi + Pcu = Power output/power input
= Power output/(power output + Pi +Pcu )
Now power output = V2 I2 cos
where cos = Load power factor75
-
8/13/2019 Transformer (Mumbai University)
76/87
8/14/2013 unit 4-Transformer
Efficiency of a Transformer
Sejal Chopra,DBIT,Kurla 76
This is full load percentage efficiency with,
I2 = Full load secondary current
-
8/13/2019 Transformer (Mumbai University)
77/87
8/14/2013 unit 4-Transformer
Efficiency of a Transformer
Let n =Fraction by which load is lessthan full load = Actual load/Full load
when load changes, the load current
changes by same proportion. new I2= n (I2) F.L.Similarly the output V2 I2 cos2 also
reduces by the same fraction. new Pcu = n
2 (Pcu ) F.L.
77
-
8/13/2019 Transformer (Mumbai University)
78/87
8/14/2013 unit 4-Transformer
Efficiency of a Transformer
78
Condition for Maximum
-
8/13/2019 Transformer (Mumbai University)
79/87
8/14/2013 unit 4-Transformer
Condition for MaximumEfficiency
79
Condition for Maximum
-
8/13/2019 Transformer (Mumbai University)
80/87
8/14/2013 unit 4-Transformer
Condition for MaximumEfficiency
for maximum efficiency,
d /d I2 = 0
Now = (V2I2cos
2)/(V
2I2cos
2+ Pi + I22 R2e)
80
Condition for Maximum
-
8/13/2019 Transformer (Mumbai University)
81/87
8/14/2013 unit 4-Transformer
Condition for MaximumEfficiency
81
Condition for Maximum
-
8/13/2019 Transformer (Mumbai University)
82/87
8/14/2013 unit 4-Transformer
Condition for MaximumEfficiency
(V2 I2 cos 2 + Pi + I22 R2e)(V2 cos 2)- (V2 I2 cos 2)(V2 cos 2 + 2I2 R2e) =0
Cancelling (V2 cos 2) from both theterms we get,
V2 I2 cos 2 + Pi +I22 R2e - V2 I2 2 - 2I22
R2e = 0... Pi - I2
2 R2e= 0
... Pi = I22 R2e = Pcu
82
Load Current I2m at Maximum Efficiency
-
8/13/2019 Transformer (Mumbai University)
83/87
8/14/2013 unit 4-Transformer
For max, I22 R2e = Pi but I2 = I2mI2m
2 R2e = PiI2m = (Pi/ R2e)
This is the load current at max,
Let (I2)F.L. = Full load current
... I2m/(I2) F.L.= (1/(I2) F.L.)(Pi/ R2e)
... I2m/(I2) F.L.= (Pi )/({(I2) F.L.}2
R2e)
= (Pi )/((Pcu) F.L.)
... I2m = (I2 )F.L.(Pi )/((Pcu) F.L.)
\ This is the load current at max intermsof full load current.
83
-
8/13/2019 Transformer (Mumbai University)
84/87
8/14/2013 unit 4-Transformer
KVA supplied at maximum Efficiency
For constant V2 the KVA supplied isthe function of.
KVA at max = I2m V2= V2 (I2) F.L. x
(Pi)/((Pcu)F.L.)KVA at max = (KVA rating) x (Pi)
/((Pcu)F.L.)
84
KVA supplied at maximum
-
8/13/2019 Transformer (Mumbai University)
85/87
8/14/2013 unit 4-Transformer
KVA supplied at maximumEfficiency
85
-
8/13/2019 Transformer (Mumbai University)
86/87
8/14/2013 unit 4-Transformer
Open Circuit Test (O.C. Test)
86
-
8/13/2019 Transformer (Mumbai University)
87/87
Short Circuit Test (S.C. Test)