1
Conventional and
Un-Conventional Partial Discharge
Detection Methods in High Voltage
XLPE Cable Accessories
Presented By:
Harshit Bhandari8th Sem Electrical
Guided by:
Prof. Harish Khyani
![Page 2: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/2.jpg)
CONTENTS
2
What Is XLPE ? Problem with XLPE cables Detection of Faults Partial discharge What causes partial discharge ? Partial discharge detection methods Classification Conventional MethodConclusion
![Page 3: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/3.jpg)
3
What is XLPE ?
XLPE stands for Cross-linked Polyethylene cables .
These are most extensively used power cables for transmission of High voltages
They are frequently used for both overhead and underground high voltage transmission system
![Page 4: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/4.jpg)
XLPE Cable
4
![Page 5: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/5.jpg)
5
Power cable system basically consists of cables themselves and their accessories.
Cable accessories consist of joint and termination.
As the extensive application of Cross-linked Polyethylene (XLPE) cable in power grid, power accidents caused by insulation faults in cable equipments are increasing constantly.
![Page 6: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/6.jpg)
6
Insulation faults occur more often in cable accessories and the existence of insulation faults, can lead internal partial discharge (PD) to occur.
The cable laying method is mainly concerned with underground, which brings. problems on state testing and fault localization in cable systems
Therefore, how to judge the cable insulationsituation effectively and locate the fault site accurately is ofgreat practical significance
![Page 7: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/7.jpg)
Partial Discharge Partial discharges are in general a consequence of local electrical stress concentrations in the insulation or on the surface of the insulation.
Generally, such discharges appear as pulses having a duration ofmuch less than 1 ps.
More continuous forms can, however, occur, such as the so-called pulse-less discharges ingaseous dielectrics.
For eg:- Corona Discharge7
![Page 8: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/8.jpg)
8
![Page 9: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/9.jpg)
What causes Partial Discharge?
After installation or long time use, the insulation of cable or accessories may include small voids and cavities, conductive or insulating contaminants, or conductive protrusions in different interfaces.
The installation may also cause other defects like mechanical cuts.
During the service the temperature variation and other environmental stresses as well as electric filed and heating due to load current may enlarge these defects, and partial discharges may be incepted.
9
![Page 10: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/10.jpg)
These effects may also introduce cavities in originally sound cable insulation or enlarge original micro voids.
Partial discharge measurement methods are most important and preferred and they have received much attention in recent years.
Cont…
10
![Page 11: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/11.jpg)
11
Partial discharge (PD) measurement methods are most important and preferred in testing of underground high voltage cables and they have received much attention in recent years.
Apparent charge, partial discharge inception voltage as well as number and distribution of PD pulses are most important quantities for the determination of the insulation quality.
Identification with certain PD patterns and localization of PD are most important aspects.
![Page 12: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/12.jpg)
Classification
Partial discharge detection method can be classified into two techniques
Conventional and
Un-conventional
12
![Page 13: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/13.jpg)
Conventional Method Conventional PD detection is a standardized method for PD measurement as described in IEC 60270.
This method based on measurement of apparent charge displacement q in the leads of the sample. This charge is usually expressed in Pico-Coulombs (pC)
Unconventional Method
Un-conventional PD measurement is based on detection of high frequency PD activities.
![Page 14: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/14.jpg)
Conventional MethodPartial discharges that occur in the test object will produce
current or voltage pulses.
Output PD pulse magnitude is more or less a measure of the PD current amplitude and not for the apparent charge
This method based on measurement of the charge
displacement q, expressed in (pC), from the pulses which generated from partial discharge
14
![Page 15: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/15.jpg)
The tests are carried out in the Extra High Voltage Research Centre (EHVRC) PD Lab. In these PD measurements, 50Hz continuous AC voltage is used as an energizing method.
Using this PD detector several important parameters of PD occurrence can be obtained such as:
• PD inception voltage (PDIV) • PD magnitude in pC at PDIV • PD magnitude as a function of voltage applied • PD pattern
The PD measurements have been carried out according to IEC
for the XLPE cable sample 220 kV -1600 mm2 with two different type of joint and termination as shown in figure
15
![Page 16: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/16.jpg)
PD measurement is carried out in 2 minutes for each test voltage. During this period three quantities are recorded:
The number of PD pulses,The maximum value of PD magnitudes and The average value of PD magnitudes . These three quantities are plotted as a function of phase
angle of sinusoidal AC voltage. 1 and the PD measurements results as shown in next Figure
16
![Page 17: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/17.jpg)
17
Phase-position quantities Hqmax (φ), Hqn(φ) and Hn(φ)processed for discharges at a test voltage 190 kV for 2 minutes
![Page 18: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/18.jpg)
18
3D distribution as obtained at 190 kV
![Page 19: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/19.jpg)
PD pattern for a joint at 127 kV
19
![Page 20: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/20.jpg)
Unconventional MethodUn-conventional PD detection is used to provide result with
suppressed noise or high signal to noise ratio.
Basically there are two main methods, High Frequency/Very High Frequency/ Ultra High Frequency (HF/
VHF/ UHF) Acoustic method.
20
![Page 21: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/21.jpg)
Fault Detection in Cable
21
Fault Detection in Undergroundcable
![Page 22: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/22.jpg)
This methods use HFCT (High Frequency Current Transformer).
Using ultrasonic detector acoustic waves due to partial discharge are detected .
This method does not requires any testing lab or heavy equipments
On-site detection of faults can be done easily with a semi skilled person
22
Unconventional Method
CB Link with mounted three HFCT (PD Sensor)
![Page 23: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/23.jpg)
23
![Page 24: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/24.jpg)
24
![Page 25: Seminar on Partial Discharge detection methods](https://reader034.vdocuments.mx/reader034/viewer/2022042602/55aae5951a28ab8a1b8b47c7/html5/thumbnails/25.jpg)
Query??
25