RESIDENTIAL HORIZONTAL CLADDING
T-Rib
0800 ROOFNZ (0800 766 369)www.metalcraftroofing.co.nz
Architectural / Specification EnquiriesPh: 09 274 0408
Mobile: 027 603 1096Email: [email protected]
00 / 23 COVER SHEET01 / 23 PARAPET AND BALUSTRADE CAPPING02 / 23 SOFFIT03 / 23 FLUSH WINDOW HEAD04 / 23 FLUSH WINDOW SILL05 / 23 FLUSH WINDOW JAMB06 / 23 RECESSED WINDOW HEAD07 / 23 RECESSED WINDOW SILL08 / 23 RECESSED WINDOW JAMB09 / 23 BUTT WINDOW HEAD10 / 23 BUTT WINDOW SILL11 / 23 BUTT WINDOW JAMB12 / 23 METERBOX HEAD13 / 23 METERBOX SILL14 / 23 METERBOX JAMB15 / 23 INTERNAL CORNER16 / 23 EXTERNAL CORNER17 / 23 INTERNAL CORNER BOX TYPE18 / 23 EXTERNAL CORNER BOX TYPE19 / 23 SOAKER FLASHING20 / 23 VERTICAL BUTT JOINT21 / 23 BOTTOM OF CLADDING (FLUSH)22 / 23 BOTTOM OF CLADDING (RECESSED)23 / 23 3D WINDOW FLASHINGS
DETAIL LIST
PRE-FINISHED PARAPET CAP FLASHINGNO FIXINGS ON TOP OF FLASHING
BUILDING PAPER SHOWN DASHED
CONTINUOUS H3.1 TIMBER PACKING
METALCRAFT T-RIB HORIZONTALCLADDING
WALL FRAMING
PRE-FINISHED SELF DRILLING / TAPPINGSCREW WITH RUBBER WASHER
MIN
. 5.00 °
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED
CLE
ARAN
CE
25m
m
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
20mm CAVITY
CLE
ARAN
CE
25m
m
10mm GAP
5mm GAP5mm GAP
10mm G
AP
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 01 / 23
PARAPET AND BALUSTRADE CAPPING
2014
BUILDING PAPER SHOWN DASHED
20mm CAVITY
WALL FRAMING
METALCRAFT T-RIB HORIZONTALCLADDING
PRE-FINISHED SOFFIT FLASHINGFLY RAFTER
BARGE BOARD
SOFFIT LINING
PURLIN
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
INTERNAL CEILING LINING
CO
VER
CLA
DD
ING
50m
m( M
IN. 3
5mm
)
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
EXTRA NOG FOR TOP FIXING OFWALL CLADDING
BUILDING PAPER TO PROVIDE SEPARATIONOF METAL CAPPING AND CLADDING WITHTIMBER SHOWN DASHED
STST OR GALV. FLAT HEAD NAIL FORFLASHING
INTERNAL WALL LININGMIN. 50mm
SQUARE STOP CORNICE 5mm GAP
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 02 / 23
SOFFIT
2014
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD
TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING
EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED
INTERNAL WALL LINING
WINDOW LINTEL FRAMING
METALCRAFT T-RIB HORIZONTALCLADDING
PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
DOUBLE GLAZING WINDOW JOINERY
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WINDOW HEAD LINER
LINE OF WINDOW JAMB LINER BEHIND
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND
5mm
GAP M
IN. 7
5mm
WIT
HO
UT
HE M
ED
GE
MIN
.50m
m C
OVE
R
STST OR GALV. FLAT HEAD NAIL FORFLASHING
PVC CAVITY CLOSER
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED
DR
IP E
DG
E TO
CLA
DD
I NG
MIN
.15m
m G
AP
MIN
.10m
m C
OVE
R
SU
GG
EST
MIN
.50m
m
DIM
ENS
ION
TO
SU
IT
COMPRESSIBLE FOAM SEALBEHIND TO FILL OVERLAP OF FLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 03 / 23
FLUSH WINDOW HEAD
2014
METALCRAFT T-RIB HORIZONTALCLADDING
INTERNAL WALL LINING
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW JAMB LINER BEHIND
WINDOW SILL LINER
MIN. 8mm PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL
PRE-FINISHED WINDOW SILL FLASHING
WALL FRAMING
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL
STOPENDS TO SILL FLASHING
LINE OF JAMB FLASHING BEHIND
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
20mm CAVITY
5mm GAP
MIN
. 8m
m C
OV
ER
WINDOW SUPPORT BAR CO
VER
CLA
DD
ING
50m
m(M
IN. 3
5mm
)
PRE-FINISHED SECONDARY FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 04 / 23
FLUSH WINDOW SILL
2014
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER SHOWN DASHED
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW SILL LINER BELOW
WINDOW JAMB LINER
TIMBER PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
20mm JAMB BATTEN
INTERNAL WALL LINING
LINE OF SILL FLASHING BELOW
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL
20mm CAVITY
LINE OF SILL FLASHING BELOW
PRE-FINISHED WINDOW JAMBFLASHING
COMPRESSIBLE FOAM SEALBEHIND TO FILL OVERLAP OF FLASHING
MIN. 10mm COVER
5mm
GAP
PRE-FINISHED SECONDARY FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW
STST OR GALV. FLAT HEAD NAIL FORFLASHING
SUGGEST MIN. 50mm
DIMENSION TO SUIT
LINE OF HEAD FLASHING ABOVE
CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER. SHOWNDASHED
LINE OF HEAD FLASHING ABOVE
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 05 / 23
FLUSH WINDOW JAMB
2014
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD
TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING
EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED
INTERNAL WALL LINING
WINDOW LINTEL FRAMING
METALCRAFT T-RIB HORIZONTALCLADDING
PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
DOUBLE GLAZING WINDOW JOINERY
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WINDOW HEAD LINER
LINE OF WINDOW JAMB LINER BEHIND
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND
DR
IP E
DG
E TO
CLA
DD
I NG
MIN
. 15m
m G
APM
IN. 1
0mm
CO
VER
5mm
GAP M
IN. 7
5mm
WIT
HO
UT
HE
M E
DG
E
MIN
. 50m
m C
OVE
R
SU
GG
EST
MIN
.50m
m
DIM
ENS
ION
TO
SU
IT
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED
PVC CAVITY CLOSER
STST OR GALV. FLAT HEAD NAIL FORFLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 06 / 23
RECESSED WINDOW HEAD
2014
5mm
GAP
MIN
. 8m
m C
OV
ER
5mm GAP
METALCRAFT T-RIB HORIZONTALCLADDING
INTERNAL WALL LINING
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW JAMB LINER BEHIND
WINDOW SILL LINER
MIN. 8mm PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
PRE-FINISHED WINDOW SILL FLASHING
WALL FRAMING
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL
STOPENDS TO SILL FLASHING
LINE OF JAMB FLASHING BEHIND
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
20mm CAVITY
WINDOW SUPPORT BAR
PRE-FINISHED SECONDARY FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
CO
VER
CLA
DD
ING
50m
m(M
IN. 3
5mm
)
FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 07 / 23
RECESSED WINDOW SILL
2014
PRE-FINISHED WINDOW JAMBFLASHING
BUILDING PAPER SHOWN DASHED
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW SILL LINER BELOW
WINDOW JAMB LINER
TIMBER PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
20mm JAMB BATTEN
INTERNAL WALL LINING
LINE OF SILL FLASHING BELOW
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL
CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION 2.2/2012 FOR REQUIRMENT.
METALCRAFT T-RIBHORIZONTAL CLADDING
5mm
GAP
MIN. 10mm COVER
PRE-FINISHED SECONDARYFLASHING
5mm GAP
PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED
STST OR GALV. FLAT HEAD NAILFOR FLASHING
SEPARATE BATTEN AND FLASHINGWITH EPDM AS REQUIRED
SUGGEST MIN. 50mm
DIMENSION TO SUIT
LINE OF HEAD FLASHING ABOVE
LINE OF HEAD FLASHING ABOVE
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 08 / 23
RECESSED WINDOW JAMB
2014
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD
TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING
EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED
INTERNAL WALL LINING
WINDOW LINTEL FRAMING
PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
DOUBLE GLAZING WINDOW JOINERY
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WINDOW HEAD LINER
LINE OF WINDOW JAMB LINER BEHIND
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND
MIN
.75m
m W
ITH
OU
T H
EM
ED
GE
MIN
. 50m
m C
OVE
R
DR
IP E
DG
E TO
CLA
DD
ING
MIN
. 15m
m G
APM
IN.1
0mm
CO
VER
5mm
GAP
SU
GG
EST
MIN
. 50m
m
DIM
ENS
ION
TO
SU
IT
PVC CAVITY CLOSER
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHEDPRE-FINISHED SELF DRILLING/TAPPING SCREW
WITH RUBBER WASHER
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 09 / 23
BUTT WINDOW HEAD
2014
5mm
GAP
MIN
. 8m
m C
OV
ER
CO
VER
CLA
DD
ING
50m
m(M
IN. 3
5mm
)
METALCRAFT T-RIB HORIZONTALCLADDING
INTERNAL WALL LINING
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW JAMB LINER BEHIND
WINDOW SILL LINER
MIN. 8mm PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL
PRE-FINISHED WINDOW SILL FLASHING
WALL FRAMING
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT SILL
STOPENDS TO SILL FLASHING
LINE OF JAMB FLASHING BEHIND
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
20mm CAVITY
WINDOW SUPPORT BAR
PRE-FINISHED SECONDARY FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 10 / 23
BUTT WINDOW SILL
2014
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER SHOWN DASHED
DOUBLE GLAZING WINDOW JOINERY
LINE OF WINDOW SILL LINER BELOW
WINDOW JAMB LINER
TIMBER PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB
20mm JAMB BATTEN
INTERNAL WALL LINING
LINE OF SILL FLASHING BELOW
PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER
FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL
CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.
PRE-FINISHED WINDOW JAMBFLASHING
5mm GAP 5mm GAP
MIN. 50mm
MIN. 10mm COVER
5mm
GAP
STST OR GALV. FLAT HEAD NAILFOR FLASHING
BUILDING PAPER TO PROVIDESEPARATION OF METALCAPPING AND CLADDING WITHTIMBER SHOWN DASHED
SUGGEST MIN.50mm
DIMENSION TO SUIT
LINE OF HEAD FLASHING ABOVE
LINE OF HEAD FLASHING ABOVE
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 11 / 23
BUTT WINDOW JAMB
2014
BUILDING PAPER DRESSED INTO OPENINGWITH FLEXIBLE FLASHING TAPE INSTALLEDOVER WRAP TO CORNERS AT HEAD
TEMPORARY PACKER IF REQUIRED, REMOVEDAFTER FIXING
PRE-FINISHED HEAD FLASHING WITH 15° FALL
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
METER BOX
STOPENDS TO HEAD FLASHING
LINE OF JAMB FLASHING BEHIND
METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.
DR
IP E
DG
E TO
CLA
DD
ING
MIN
. 15m
m G
AP
MIN
. 5m
m G
AP
MIN
. 75m
m W
ITH
OU
T H
E M E
DG
E
MIN
. 50m
m C
OVE
R
PRE-FINISHED 'U' BRACKET FIXED TOMETERBOX BEFORE INSTALLATION
EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED
INTERNAL WALL LINING
PVC CAVITY CLOSER
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHEDPRE-FINISHED SELF DRILLING/TAPPING SCREW WITH
RUBBER WASHER
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 12 / 23
METERBOX HEAD
2014
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER SHOWN DASHED
METER BOX
INTERNAL WALL LINING
MIN. 8mm PACKER
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
WALL FRAMING
20mm CAVITY
LINE OF JAMB FLASHING BEHIND
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL
METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.
PRE-FINISHED FLASHING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
STOPENDS TO SILL FLASHING
CO
VER
CLA
DD
ING
50m
m(M
IN.3
5mm
)
PRE-FINISHED SECONDARY FLASHING
STST OR GALV. FLAT HEAD NAIL FOR FLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 13 / 23
METERBOX SILL
2014
METALCRAFT T-RIBHORIZONTAL CLADDING
BUILDING PAPER SHOWN DASHED METER BOX
TIMBER PACKER
20mm JAMB BATTEN
INTERNAL WALL LINING
LINE OF SILL FLASHING BELOW
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FLEXIBLE FLASHING TAPE OVER BUILDING
PAPER FOR FULL WIDTH/DEPTH SILL
LINE OF HEAD FLASHING ABOVE
PRE-FINISHED WINDOW JAMB FLASHING FIXEDTO METERBOX BEFORE INSTALLATION
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
METAL ANGLE TO BE CONTINUOUS AROUNDMETER BOX WITH PRE-FINISHED SELFDRILLING/TAPPING SCREW WITH RUBBERWASHER
CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED
STST OR GALV. FLAT HEAD NAILFOR FLASHING
PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
SUGGEST MIN. 50mm
DIMENSION TO SUIT
AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILL AND JAMB
LINE OF HEAD FLASHING ABOVE
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 14 / 23
METERBOX JAMB
2014
METALCRAFT T-RIB HORIZONTALCLADDING
WALL FRAMING
20mm CAVITY
PRE-FINISHED INTERNALCORNER FLASHING
INTERNAL WALL LINING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
BUILDING PAPER SHOWN DASHED
SU
GG
EST
MIN
. 75m
m
DIM
ENS
ION
TO
SU
IT
SUGGEST MIN. 75mm
DIMENSION TO SUIT
CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.
STST OR GALV. FLAT HEAD NAIL FORFLASHING
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED
PRE-FINISHED SECONDARY FLASHING
PRE-FINISHED POP RIVETBEDDED IN SILICONE ORPRE-FINISHED 8g WAFER-TEK SCREW
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 15 / 23
INTERNAL CORNER
2014
20mm CAVITY
METALCRAFT T-RIB HORIZONTALCLADDING
INTERNAL WALL LINING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
WALL FRAMING
PRE-FINISHED EXTERNALCORNER FLASHING
BUILDING PAPER SHOWN DASHED
SUGGEST MIN. 75mm
DIMENSION TO SUIT
SU
GG
EST
MIN
. 75m
m
DIM
ENS
ION
TO
SU
IT
CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.
BUILDING PAPER TO PROVIDESEPARATION OF METALCAPPING AND CLADDING WITHTIMBER SHOWN DASHED
PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW
STST OR GALV. FLAT HEAD NAIL FORFLASHING
PRE-FINISHED SECONDARYFLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 16 / 23
EXTERNAL CORNER
2014
METALCRAFT T-RIB HORIZONTALCLADDING
WALL FRAMING
20mm CAVITY
PRE-FINISHED INTERNAL CORNERFLASHING
INTERNAL WALL LINING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
BUILDING PAPER SHOWNDASHED
MIN. 50mm COVER
MN
. 50m
m C
OVE
R
5mm
GAP
5mm GAP
CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.
BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED
STST OR GALV. FLAT HEAD NAIL FORFLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 17 / 23
INTERNAL CORNER BOX TYPE
2014
20mm CAVITY
METALCRAFT T-RIB HORIZONTALCLADDING
INTERNAL WALL LINING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
WALL FRAMING
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED
MIN. 50mm COVER
MIN
. 50m
m C
OVE
R5mm
GAP
5mm GAP
BUILDING PAPER SHOWN DASHED
PRE-FINISHED EXTERNAL CORNERFLASHING
CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.
STST OR GALV. FLAT HEAD NAIL FORFLASHING
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 18 / 23
EXTERNAL CORNER BOX TYPE
2014
BUILDING PAPERSHOWN DASHED
METALCRAFT T-RIBHORIZONTAL CLADDING
PRE-FINISHED FLAT HEADWAFER-TEK SCREW FORFLASHING
INTERNAL WALL LINING
20mm CAVITY
WALL FRAMING
PRE-FINISHED SOAKERFLASHING BELOWWINDOW JAMBS
BUILDING PAPER TOPROVIDE SEPARATION OFMETAL CAPPING ANDCLADDING WITH TIMBERSHOWN DASHED
SOAKER FLASHING ONLY REQUIRED TOLINE UP WITH WINDOW JAMB ABOVE.REFER TO MRM CODE OF PRACTICEVERSION 2.2 /2012 FOR REQUIRMENT.
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 19 / 23
SOAKER FLASHING
2014
BUILDING PAPERSHOWN DASHED
METALCRAFT T-RIBHORIZONTAL CLADDING
PRE-FINISHED SELFDRILLING / TAPPING SCREWWITH RUBBER WASHER
INTERNAL WALL LINING
WALL FRAMING
PRE-FINISHED JOINTERFLASHING
5mm GAP
MIN. 50mm COVER
BUILDING PAPER TO PROVIDESEPARATION OF METALCAPPING AND CLADDING WITHTIMBER SHOWN DASHED
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 20 / 23
VERTICAL BUTT JOINT
2014
20mm CAVITY
INTERNAL WALL LINING
WALL FRAMING
METALCRAFT T-RIB HORIZONTALCLADDING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
PRE-PRIMED SKIRTING
CONCRETE SLAB
MIN
. 15m
m D
RIP
ED
GE
MIN
. 50m
m L
AP
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBERSHOWN DASHED
PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL
VEN
TILA
TIO
N G
AP
3-5m
m
STST OR GALV. FLAT HEAD NAIL FORFLASHING
BUILDING PAPER OVER FLASHINGSHOWN DASHED
PVC CAVITY CLOSER
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 21 / 23
BOTTOM OF CLADDING (FLUSH)
2014
INTERNAL WALL LINING
WALL FRAMING
PVC CAVITY CLOSER
MIN
. 75m
m C
OV
ER
VEN
TILA
TIO
N G
AP
3 - 5
mm
PRE-PRIMED SKIRTING
CONCRETE SLAB
MIN
. 50m
m L
AP
20mm CAVITY
METALCRAFT T-RIB HORIZONTALCLADDING
BUILDING PAPER OVER FLASHINGSHOWN DASHED
STST OR GALV. FLAT HEAD NAIL FORFLASHING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPINGAND CLADDING WITH TIMBER SHOWNDASHED
ALTERNATIVE OPTIONBIRDS BEAK EDGE
5 GAP
20
15
PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL
HEMMED EDGE
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
1 : 2 22 / 23
BOTTOM OF CLADDING (RECESSED)
2014
ScaleDate SheetReference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
RESIDENTIAL HORIZONTAL CLADDINGT-Rib
RHTRI 23 / 23
3D WINDOW FLASHINGS
2014
HEAD FLASHING
JAMB FLASHING
SILL FLASHING
METALCRAFT T-RIBHORIZONTALCLADDING
ALUMINIUMWINDOWJOINERY
COMPRESSIBLEFOAM SEALBEHIND TO FILLOVERLAP OFFLASHING
FLUSH WINDOW FLASHINGS RECESSED WINDOW FLASHINGS
HEAD FLASHING
JAMB FLASHING
ALUMINIUMWINDOWJOINERY
SILL FLASHING
METALCRAFT T-RIBHORIZONTALCLADDING