Risks and Opportunities of Reactive Power Compensators in Environ-ments with HarmonicsStefan FassbinderDKI German Copper InstituteAm Bonneshof 5D-40474 DüsseldorfTel.: +49 / 211 / 4796-323Fax: +49 / 211 / [email protected]
The German Copper Institute, DKI, is the central information and advisory service dealing with all uses of copper and copper alloys.We offer our services to:
Commercial companiesThe skilled tradesIndustryResearch institutesUniversitiesArtists and craftsmenStudentsPrivate individuals
We can be contacted by: postphonefaxe-mailinternetonline database, orpersonally
Everybody knows reactive power
But what do we really mean by it?
But what do we really mean by it?
Generation of leading reactive power = Absorption of lagging reactive powerGeneration of lagging reactive power = Absorption of leading reactive power
But what do we really mean by it?
Reactive power is the share of the power which does notcontribute to the transmission of energy (work)
So what then is reactive energy?
If the voltage is sinusoidal, the current is sinusoidal too – right?
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20mst
u
-20A
-15A
-10A
-5A
0A
5A
10A
15A
20A
i
Sine voltageL current with sine voltageC current with sine voltage
L = 55 mHC = 175 µFf = 50 Hz
t)sin(*û)( ω=tu t)cos(*î)( ω−=tiL
t)cos(*î)( ω=tiC
And what about other voltage-current profiles?
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20mst
u
-20A
-15A
-10A
-5A
0A
5A
10A
15A
20A
i
Sine voltageL current with sine voltageC current with sine voltage
L = 55 mHC = 175 µFf = 50 Hz
t)sin(*û)( ω=tu t)cos(*î)( ω−=tiL
t)cos(*î)( ω=tiC
E. g. when a square-wave voltage with small conductive angle is applied to an inductor?
-100V
-80V
-60V
-40V
-20V
0V
20V
40V
60V
80V
100V
0ms 5ms 10ms 15ms 20ms
t
u L
-100A
-80A
-60A
-40A
-20A
0A
20A
40A
60A
80A
100A
i L Rectangular
voltage
L current withrectangularvoltage
Conductive angle = 30 %Peak value = 100 V
L = 3 mHf = 50 Hz
Or when a triangular voltage with a small conductive angle is applied to a capacitor?
-100V
-80V
-60V
-40V
-20V
0V
20V
40V
60V
80V
100V
0ms 5ms 10ms 15ms 20ms
t
u C
-100A
-80A
-60A
-40A
-20A
0A
20A
40A
60A
80A
100A
i C
Triangularvoltage
C current withtriangularvoltage
Conductive angle = 30 %Peak value = 100 V
C = 1500 µFf = 50 Hz
Or when a triangular current profile with a small conductive angle is driven through a capacitor?
-100A
-80A
-60A
-40A
-20A
0A
20A
40A
60A
80A
100A
0ms 5ms 10ms 15ms 20mst
i C
-100V
-80V
-60V
-40V
-20V
0V
20V
40V
60V
80V
100V
u C Triangular current
C voltage with triangular current
Conductive angle = 75 %Peak value = 100 V
C = 3750 µFf = 50 Hz
But fortunately:
-400 %
-300 %
-200 %
-100 %
0 %
100 %
200 %
300 %
400 %
0ms 5ms 10ms 15ms 20ms
t
i/I
itot i1i3 i5i7 i9i11 i13i15 i17
Every periodic waveform can be written as the finite sum of sinusoidal waves whose frequencies are integer multiples of the fundamental frequency
Harmonic reactive power
Currents are no longer sinusoidal Voltages are no longer sinusoidal Voltages and currents contain higher-frequency constituents
Risk that capacitors will overload
Capacitors can help to eliminate this high
frequency contamination
Static var compensators in such an environment – a threat and an opportunity!
fLX L π2=
fCXC π2
1=
2222 )( CLCuSCu XXRXRZ −+=+=
fCfLXXX CLS π
π2
12 −=−=
The real-life behaviour
Why detune?To prevent the occurrence oftransformer resonances, for example.
Why detune?To prevent the occurrence oftransformer resonances, for example.
Why detune?To prevent the occurrence oftransformer resonances, for example.
Why detune?To prevent the occurrence oftransformer resonances, for example.
So it’s quite natural to ask:What is harmonic reactive power?Well, it all depends on how you see things and how you measure them...
Detuned Static VAR Compensator (SVC)
0Ω
2Ω
4Ω
6Ω
8Ω
10Ω
12Ω
14Ω
16Ω
18Ω
20Ω
100Hz 200Hz 300Hz 400Hz 500Hz 600Hz
f
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Reactor reactanceCapacitor reactanceSerial impedancePhase angle
R Cu = 1 Ω
L = 8 mH
C = 50 µF
Detuned Static VAR Compensator (SVC)
0Ω
2Ω
4Ω
6Ω
8Ω
10Ω
12Ω
14Ω
16Ω
18Ω
20Ω
100Hz 200Hz 300Hz 400Hz 500Hz 600Hz
f
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Reactor reactanceCapacitor reactanceSerial impedancePhase angle
R Cu = 1 Ω
L = 4 mH
C = 100 µF
Parallel resonant bandpass filter(‘rejection circuit’)
0Ω
20Ω
40Ω
60Ω
80Ω
100Ω
120Ω
140Ω
160Ω
100Hz 200Hz 300Hz 400Hz 500Hz 600Hz
f
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Reactor reactanceCapacitor reactanceParallel impedace Phase angle
R Cu = 1 Ω
L = 8 mH
C = 50 µF
Parallel resonant bandpass filter(‘rejection circuit’)
0Ω
20Ω
40Ω
60Ω
80Ω
100Ω
120Ω
140Ω
160Ω
100Hz 200Hz 300Hz 400Hz 500Hz 600Hz
f
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Reactor reactanceCapacitor reactanceParallel impedace Phase angle
R Cu = 1 Ω
L = 4 mH
C = 100 µF
Parallel resonant bandpass filter(‘rejection circuit’)
0Ω
20Ω
40Ω
60Ω
80Ω
100Ω
120Ω
140Ω
160Ω
100Hz 200Hz 300Hz 400Hz 500Hz 600Hz
f
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Reactor reactanceCapacitor reactanceParallel impedace Phase angle
R Cu = 0.25 Ω
L = 8.00 mH
C = 50.00 µF
Trying to save money byTrying to save money byskimping on skimping on coppercopperusually turns out to be a costlymistake. And in the case of power factor cor-rection circuits, you can end up paying twice!According to the experts at ElectroniconKondensatoren GmbH in Gera:‘Most customers aren’t even aware that by focusing solely on cutting costs, the money they saved through reactive power com-pensation measures is lost via active power losses in the compensation circuit.’
VArWWVAPSQ 146)858()160( 2222 ≈+−=−=
VAAVS 16067,0*230 ==
Example: a 58-W tube with a low-loss ballast Example: an 11-W tube with a
conventional magnetic ballast
Fluorescent lamps with magnetic ballasts:A classic source of reactive power that
requires compensation
-350V
-250V
-150V
-50V
50V
150V
250V
350V
0ms 5ms 10ms 15ms 20ms
t
u
-1.0A
-0.5A
0.0A
0.5A
1.0A
i
Systems voltageLamp voltageCurrent
or in the so-called ‘duo’or lead-lag configuration
either in a conventional
parallel configuration
Compensation is best done right at the source – as is in fact often the case in fluorescent lamps –
Two 58W lamps with two ballasts and one capacitor
0Ω
50Ω
100Ω
150Ω
200Ω
250Ω
300Ω
350Ω
400Ω
450Ω
500Ω
40Hz 50Hz 60Hz 70Hz 80Hz 90Hz
f
Z
X(L)
X(C)
Z(ser)
Correctlydimensioned
RCu =13.8 ΩL =878 mHC = 5.7 µF
22RLC )
212(Z CuRfC
fL +−=π
π
fCπ21XC =
Fπ2XL =
Two 58W lamps with two ballasts and one capacitor
0Ω
50Ω
100Ω
150Ω
200Ω
250Ω
300Ω
350Ω
400Ω
450Ω
500Ω
40Hz 50Hz 60Hz 70Hz 80Hz 90Hz
f
Z
X(L)
X(C)
Z(ser)
RCu =13.8 ΩL =878 mHC = 6.8 µF
Dimensioning is 20% in error: Reactance is 32% in
error!
fCπ21XC =
fLπ2XL =
22RLC )
212(Z CuRfC
fL +−=π
π
58W lamp with a class B1 magnetic ballast
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20ms
t
u
-1,4A-1,2A-1,0A-0,8A-0,6A-0,4A-0,2A0,0A0,2A0,4A0,6A0,8A1,0A1,2A1,4A
i
U
I(L)
Two 58W lamps, one in series with a 5.3 µF capacitor
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20ms
t
u
-1,4A-1,2A-1,0A-0,8A-0,6A-0,4A-0,2A0,0A0,2A0,4A0,6A0,8A1,0A1,2A1,4A
i
U
I(L)
I(C=5.3µF)
Two 58W lamps, one in series with a 5.3 µF capacitor
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20ms
t
u
-1,4A-1,2A-1,0A-0,8A-0,6A-0,4A-0,2A0,0A0,2A0,4A0,6A0,8A1,0A1,2A1,4A
i
UI(L)I(C=5.3µF)I(C+L)
Two 58W lamps, one with reduced 4.6µF capacitor
-350V-300V-250V-200V-150V-100V
-50V0V
50V100V150V200V250V300V350V
0ms 5ms 10ms 15ms 20ms
t
u
-1,4A-1,2A-1,0A-0,8A-0,6A-0,4A-0,2A0,0A0,2A0,4A0,6A0,8A1,0A1,2A1,4A
i
UI(L)I(C=4.6µF)I(tot)(C=4.6µF)
Possible overloading of capacitors attached directly to the mains due tohigher frequenciespresent in thesupply system
Dealing with side effectsof the first kind:
Filter capacitor current into a PC power supply
while switched of
Risk with parallel compensation:
Higher frequencies cause capacitor to overload, as shown here for an 11W fluorescent lamp with magnetic ballast
A reliable concept:Conventional power factorcompensation system detunedto draw off the strongest harmonics
Dealing with side effectsof the second kind:
Rejection circuits ensure that ripple-control signals don’t get lost
Cleaning effect of a 250Hz filterrecorded in a residential areain Germany, June 30, 2002, 14:30
The advantageous dual passive filtercan reduce e. g. the harmoniccontent of a dimmer current substantially
Well, this was just a model
Here come three real-life examplesof detuned static var compensators withthree different ratings, actually built and sold by a specialized companyReactive
power rating
Detuning factor
Reactor losses per
phase
I(in delta wiring)
X C
50 HzX L
50 HzC L R Cu
kVAr % W A Ω Ω µF mH mΩ10.0 7% 15.7 8.33 51.360 3.360 62.0 10.695 225.622.5 7% 24.3 18.75 22.827 1.493 139.4 4.753 69.267.4 7% 52.3 56.17 7.620 0.499 417.7 1.587 16.6
The values are convincing, losses areminimal!
Dimensioning a twin filter made of 2 acceptor circuits operating in parallel – input valuesHarmonics in the mains voltage: Ratings of your system and the filters:
No. f U f U 240.000 V Rated TRMS mains voltage1 50Hz 239.49V f 50.000 Hz Rated mains frequency2 100Hz 0.00V R 5 16.600 mΩ Ohmic winding resistance of lower frequency reactor (usually tuned to or near the 5th harmonic)3 150Hz 12.00V L 5 1.587 mH Inductance of lower frequency reactor (usually tuned to or near the 5th harmonic)4 200Hz 0.00V C 5 417.700 µF Capacitance of lower frequency reactor (usually tuned to or near the 5th harmonic)5 250Hz 8.00V R 7 16.600 mΩ Ohmic winding resistance of higher frequency reactor (usually tuned to or near the 7th harmonic)6 300Hz 0.00V L 7 0.810 mH Inductance of higher frequency reactor (usually tuned to or near the 7th harmonic)7 350Hz 4.00V C 7 213.112 µF Capacitance of higher frequency reactor (usually tuned to or near the 7th harmonic)8 400Hz 0.00V f 0(5) 195.479 Hz Resonance frequency of the 5th order filter9 450Hz 3.00V f 0(7) 383.138 Hz Resonance frequency of the 7th order filter
10 500Hz 0.00V11 550Hz 2.50V12 600Hz 0.00V13 650Hz 2.00V14 700Hz 0.00V15 750Hz 1.50V16 800Hz 0.00V17 850Hz 1.00V18 900Hz 0.00V19 950Hz 0.50V20 1000Hz 0.00V21 1050Hz 0.00V22 1100Hz 0.00V23 1150Hz 0.00V24 1200Hz 0.00V25 1250Hz 0.00V26 1300Hz 0.00V27 1350Hz 0.00V
X L-X
C
RCu
Z
C5
L5 U
RCu5
C7
L7
RCu7
A calculation template is available at:
www.leonardo-energy.org/drupal/dimensioning-passive-filter-tool
Behaviour of said dual filter
0Ω
1Ω
2Ω
3Ω
4Ω
5Ω
0Hz 450Hz 900Hz 1350Hzf
Z
-90°-75°-60°-45°-30°-15°0°15°30°45°60°75°90°
φ
Z5Z7Ztotφ5φ7φtot
Complementary behaviourCCCurrent is proportional to the rate of change of voltage.
LLVoltage is proportional to the rate of change of current.
Reactance decreases with increasing frequency.
Energy content proportional to the square of the voltage.
Large current spikes when switching on, unless switching occurs when voltage is passing through zero.
Reactance increases with increasing frequency.
Energy content proportional to the square of the current.
Large voltage spikes when switching off, unless switching occurs when current is passing through zero.
Series LC resonant circuit (‘acceptor circuit’)
Parallel LCresonant circuit (‘rejector circuit’)
Switch on anytime(soft switching)
Zero-current switch-off (otherwise: hard switching generates voltage transients)
Zero-voltage switch-on (otherwise: hard switching generates current transients)Switch off anytime(soft switching)
Complementary behaviour
gave a total of 3 million Euros from within the frameworkgave a total of 3 million Euros from within the frameworkof their LEONARDO of their LEONARDO programmeprogramme to establish to establish thethe European website European website dealing with dealing with allall aspects of power quality with the help of adequate aspects of power quality with the help of adequate partners! Just go topartners! Just go towww.lpqi.orgwww.lpqi.orgfrom time to time and watch the from time to time and watch the Leonardo Power Quality InitiativeLeonardo Power Quality Initiativegrowing! We want to develop and provide vocational training mategrowing! We want to develop and provide vocational training material on rial on the mitigation of power quality problems inthe mitigation of power quality problems in 11 languages!11 languages!We address all electrical experts working in the field: EngineerWe address all electrical experts working in the field: Engineers, s, handicraftsmen, building maintenance technicians, architectural handicraftsmen, building maintenance technicians, architectural and and planning consultants as well as trainers and trainees.planning consultants as well as trainers and trainees.So long, we are 86 partners from Europe, North and South AmericaSo long, we are 86 partners from Europe, North and South America, , among them commercial companies, institutes, universities and 5 among them commercial companies, institutes, universities and 5 national national copper copper centrescentres. Participation and contributions of further partners from . Participation and contributions of further partners from industry and academics is possible at any time and even desired industry and academics is possible at any time and even desired by the by the existing project partners.existing project partners.Just give us a click!Just give us a click!
www.lpqi.org
The European Union
The European Union
3 projects out of about 4000 awarded – one of them was:
gave a total of 3 million Euros from within the frameworkgave a total of 3 million Euros from within the frameworkof their LEONARDO of their LEONARDO programmeprogramme to establish to establish thethe European website European website dealing with dealing with allall aspects of power quality with the help of adequate aspects of power quality with the help of adequate partners! Just go topartners! Just go towww.lpqi.orgwww.lpqi.orgfrom time to time and watch the from time to time and watch the Leonardo Power Quality InitiativeLeonardo Power Quality Initiativegrowing! We want to develop and provide vocational training mategrowing! We want to develop and provide vocational training material on rial on the mitigation of power quality problems inthe mitigation of power quality problems in 11 languages!11 languages!We address all electrical experts working in the field: EngineerWe address all electrical experts working in the field: Engineers, s, handicraftsmen, building maintenance technicians, architectural handicraftsmen, building maintenance technicians, architectural and and planning consultants as well as trainers and trainees.planning consultants as well as trainers and trainees.So long, we are 86 partners from Europe, North and South AmericaSo long, we are 86 partners from Europe, North and South America, , among them commercial companies, institutes, universities and 5 among them commercial companies, institutes, universities and 5 national national copper copper centrescentres. Participation and contributions of further partners from . Participation and contributions of further partners from industry and academics is possible at any time and even desired industry and academics is possible at any time and even desired by the by the existing project partners.existing project partners.Just give us a click!Just give us a click!