WHY DRY AIR ?
The air given off by any compressor always contains water
vapour, the amount of which depends on the temperature and
the relative degree of humidity.
When the air is compressed, the volume decreases
proportionately, but the exhaust water vapour still remains in
the air. When temperature deceases and reaches a value at
which the air becomes saturated, the water vapour in the air
begins to condense. This is called DEW POINT. With an
appropriate aftercooling unit which reduces the temperature of
the air produced by the compressor, approximately 60‐ 70% of
the water gets condensed.
FUNCTIONING PRINCIPLE
The UE / UR series dryers are basically made of two different circuits ‐ a
compressed air circuit, divided into two heat exchangers and a
refrigerating circuit. The hot and humid inlet compressed air passes
through the air ‐ air heat exchanger and then reaches the evaporator
(air‐freon heat exchanger), where it is cooled by the refrigerating
circuit until it reaches the preset dew point, thus condensing the
moisture it contains. In the separator the condensed moisture is then
separated and removed.
The advantages of such a system are essentially two, first of all the inlet
air is pre‐cooled, so the refrigerating system can be sized in order to
guarantee a more limited thermal jump, with an energy saving of about
40‐50%, and secondly no cold air is conveyed through the compressed
air line, thus preventing the overall formation of condensate on the
external surface of the piping.
DAMAGES CAUSED BY THE CONDENSATE
Condensate corrodes piping, solenoid valve
and pneumatic tooling, forcing the user to
withstand expensive repair interventions,
especially the expensive “down‐time”‐ heavy
Costs which Cannot be easily controlled.
When compressed air is used as “process air”
for paint ing equipment, in chemical
industries, food processing industries, glass
factories and in plants for conveying and
handling hygroscopic raw materials, the
installation of ultrafilter dryer is essential to
eliminate the condensate which pollutes the
production cycle.
FEATURES
Non‐cyclic operation
Constant Pressure Dew Point 3°C
Hot gas by‐pass valve for freeze protection
High efficiency centrifugal moisture separator with timer controlled electronic auto drain to remove condensate
Easy to install, operate and maintain
Low noise
Low power consumption
Low maintenance costs
In addition to the above ultrafilter India also supplies controller with multiple temperature displays and controllers upon request, for dryer models UE/UR 1000 & Above.
For an optimal operation of its dryers, ultrafilter (india)
provide reliable and state‐of‐the‐art microprocessor
based controllers to monitor and control the operation of
the dryers.
ELECTRONIC CONTROLS
Following are the different functions of the dryer controllers:
Display of dew point temperature
Operation of hot gas bypass valve
Operation of condensate drain valve
URD2 Controller also controls the operation of condenser fan motor
Technical Specifications
Model Capacity
cfm
Inlet/outlet
Connection
Power
Supply
V AC/Ph/Hz
DimensionsWeight
KgAmm
Bmm
Cmm
1020355075
100125150200
UE 10UE 20UE 35UE 50UE 75UE / UR 100UE / UR 125UE / UR 150UE / UR 200
1/2” BSP(F)3/4” BSP(F)3/4” BSP(F)1” BSP(F)1” BSP(F)
1 1/4” BSP(F)1 1/2” BSP(F)
2” BSP(F)2” BSP(F)
450450450450540590590590590
540540540540670820820820820
505505505505635805805805805
34414345577694
102105
220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50
Model Capacity
cfm
Inlet/outlet
Connection
Power
Supply
V AC/Ph/Hz
DimensionsWeight
KgA
mmB
mmC
mm
250300400500600700800
1000
UE / UR 250UE / UR 300UE / UR 400UE / UR 500UE / UR 600UE / UR 700UE / UR 800UE / UR 1000
2” BSP(F)2 1/2” BSP(F)
65 NB65 NB80 NB80 NB80 NB
80/100 NB
600600800800800800800800
11501150160016001600160016001600
900900
110011001100110011001100
210240290300320350350400
220/1/50220/1/50415/3/50415/3/50415/3/50415/3/50415/3/50415/3/50
* Above Dryers are designed at 7 bar operating pressure, 40�C Inlet temp., 40�C Ambient temp.
TABLE ‐ I
TABLE ‐ II
TABLE ‐ III* Above Dryers are designed at 7 bar operating pressure, 45�C Inlet temp., 40�C Ambient temp.
* Above Dryers are designed at 7 bar operating pressure, 45�C Inlet temp., 40�C Ambient temp.
UE / UR 1200UE / UR 1500UE / UR 1800UE / UR 2000UE / UR 2500UE / UR 3000UE / UR 3500UE / UR 4000
12001500180020002500300035004000
100 NB100 NB150 NB150 NB150 NB200 NB200 NB200 NB
32 NB32 NB32 NB40 NB40 NB50 NB50 NB50 NB
7895
110125150180210245
ModelCapacity
cfm
Inlet/outlet Connection
WaterAir
Water consumption
LPM Width Depth Height
Dimensions (in mm)
16801980229019802240254025402540
290920920
10201020122012201380
16501650165018101810204020402040
Weight
Kg
10501250150016002000250026003100
TYPICAL INSTALLATION
Other Products in our RangeCompressed Air Filters Process Filters Desiccant Dryers LDO Filtration Kits| | |
| | |Air Intake Filters Moisture Separators Condensate Drains
Accessories shown in the picture are not a port of standard equipment. All right reserved. Technology data shown here are subject to change without prior notice.
1. Air compressor
2. Aftercooler unit
3. Condensate separator
4. Air receiver
5. Pre filter
6. UE/UR Dryer
7. Final filter
8. Condensate drain
Plot No. 70, Bommasandra Indl. Area, Bangalore ‐ 560 099.Tel. : +91 ‐ 080 ‐ 4142 9900, 2783 2051Fax : +91 ‐ 080 ‐ 4142 9903, E‐mail : [email protected] : www.ultrafilterindia.com
Authorised Representative
• • • • • • • Bangalore Chennai Delhi Orissa Mumbai Pune Secunderabad Indonesia Sri Lanka Bangaladesh Nepal• • • •
ultrafilter Sales Network
UIP
L/H
NS/
08
/20
14
C R
FLOW DIAGRAM FOR DRYER MODEL UE 10 TO 200
1. REFRIGERATION COMPRESSOR
2. CONDENSER UNIT
3. DEHYDRATION FILTER
4. CAPILLARY TUBE
5. EVAPORATOR
6. LIQUID SEPARATOR
7. HOT GAS BY‐PASS VALVE
8. AIR‐AIR HEAT EXCHANGER
9. CONDENSATE SEPARATOR
10. CONDENSATE DRAIN VALVE
11. Y TYPE STRAINER
12. COND. DRAIN SOLENOID VALVE
13. CONDENSER UNIT FAN
14. ELECTRONIC CONTROLLER
15. PROBE (DEW POINT)
16. PROBE (CONDENSATION)
REFRIGERATION COMPRESSOR
CONDENSER UNIT
LIQUID RECEIVER
SOLID FILTER DRYER
SIGHT GLASS
THERMOSTATIC EXPANSION VALVE
EVAPORATOR
AIR / AIR HEAT EXCHANGER
LIQUID SEPARATOR
MOISTURE SEPARATOR
HOT GAS BYPASS SOLENOID VALVE
FAN & MOTOR
FAN PRESSURE SWITCH
HP & LP PRESSURE SWITCH
DRAIN VALVE
AUTOMATIC DRAIN SOLENOID VALVE
DEW POINT TEMPERATURE PROBE
MECHANICAL FILTER
1.
2.
3.
4.
5.
6.
7.
8.
9
10.
11.
12.
13.
14.
15.
16.
17.
18.
17
10
8
7
1
9
14 11
12
2
456 13
31815
16
15 18
16
CONDENSATE
DRAIN
AIR FLOW
REFRIGERANT FLOW
WET AIR
DRY AIR
FLOW DIAGRAM FOR DRYER MODEL UE/UR 250 AND ABOVE