H20
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
Specifications
Voltage Range [V] 6,300 – 11,000
Poles 4
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class F
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
75
0 –
2 0
00
kV
A
1171
15
49
1920min – 2270max
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Hig
hV
oltag
e
75
0-2
00
0kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency1) Rotating speed
speed
Temperature rise/Running Mode at 40 °C
40 °C[kV] [Hz] [rpm]
105 K/Continuous 80 K/Continuous
H20-4-pole
H1 1250/1000 1100/880 6.3/6.6 50 1500
I1 1500/1200 1320/1056 6.3/6.6 50 1500
J1 1750/1400 1540/1232 6.3/6.6 50 1500
J2 2000/1600 1760/1408 6.3/6.6 50 1500
H1 1000/800 880/704 10,5/11 50 1500
I1 1250/1000 1100/880 10,5/11 50 1500
J1 1500/1200 1320/1056 10,5/11 50 1500
J2 1750/1400 1540/1232 10,5/11 50 1500
H1 1250/1000 1100/880 6.3/6.6 60 1800
I1 1500/1200 1320/1056 6.3/6.6 60 1800
J1 1750/1400 1540/1232 6.3/6.6 60 1800
J2 2000/1600 1760/1408 6.3/6.6 60 1800
H1 1000/800 880/704 13,8 60 1800
I1 1250/1000 1100/880 13,8 60 1800
J1 1500/1200 1320/1056 13,8 60 1800
J2 1750/1400 1540/1232 13,8 60 1800
H20-6pole
H2 1000/800 880/704 6.3/6.6 50 1000
I2 1250/1000 1100/880 6.3/6.6 50 1000
J2 1500/1200 1320/1056 6.3/6.6 50 1000
H2 750/600 660/528 10,5/11 50 1000
I2 1000/800 880/704 10,5/11 50 1000
J2 1250/1000 1100/880 10,5/11 50 1000
H2 1000/800 880/704 6.3/6.6 60 1200
I2 1250/1000 1100/880 6.3/6.6 60 1200
J2 1500/1200 1320/1056 6.3/6.6 60 1200
H2 750/600 660/528 13,8 60 1200
I2 1000/800 880/704 13,8 60 1200
J2 1250/1000 1100/880 13,8 60 1200
H30
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektriche Maschinen | Power Portfolio
Hig
hV
olta
ge
1370
15
50
2100min – 2800max
Specifications
Voltage Range [V] 3,300 – 13,800
Poles 4, 6, 8 ,10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class F
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
62
5 –
3 7
50
kV
A
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise running Mode at 40 °C [kV] [Hz] [rpm]
105 K/Continuous 80 K/Continuous
H30-4-Pole
H2 2250/1800 1980/1584 6.3/6.6 50 1500
J1 3000/2400 2640/2112 6.3/6.6 50 1500
K1 3500/2800 3080/2464 6.3/6.6 50 1500
K2 3750/3000 3300/2640 6.3/6.6 50 1500
H2 2000/1600 1760/1408 10,5/11 50 1500
I2 2500/2000 2200/1760 10,5/11 50 1500
J2 3000/2400 2640/2112 10,5/11 50 1500
K2 3500/2800 3080/2464 10,5/11 50 1500
H2 2250/1800 1980/1584 6.3/6.6 60 1800
I2 2750/2200 2420/1936 6.3/6.6 60 1800
J1 3000/2400 2640/2112 6.3/6.6 60 1800
K2 3750/3000 3300/2640 6.3/6.6 60 1800
H2 2000/1600 1760/1408 13,8 60 1800
I2 2500/2000 2200/1760 13,8 60 1800
J2 3000/2400 2640/2112 13,8 60 1800
K2 3500/2800 3080/2464 13,8 60 1800
H30-6-pole
H2 1750/1400 1540/1232 6.3/6.6 50 1000
J2 2250/1800 1980/1584 6.3/6.6 50 1000
K2 2500/2000 2200/1760 6.3/6.6 50 1000
H2 1500/1200 1320/1056 10,5/11 50 1000
J2 2000/1600 1760/1408 10,5/11 50 1000
K2 2250/1800 1980/1584 10,5/11 50 1000
H2 1750/1400 1540/1232 6.3/6.6 60 1200
J2 2250/1800 1980/1584 6.3/6.6 60 1200
K2 2500/2000 2200/1760 6.3/6.6 60 1200
H2 1500/1200 1320/1056 13,8 60 1200
J2 2000/1600 1760/1408 13,8 60 1200
K2 2250/1800 1980/1584 13,8 60 1200
H30-8-pole
H1 1000/800 880/704 6.3/6.6 50 750
I2 1500/1200 1320/1056 6.3/6.6 50 750
J2 1750/1400 1540/1232 6.3/6.6 50 750
H1 750/600 660/528 10,5/11 50 750
I2 1250/1000 1100/880 10,5/11 50 750
J2 1500/1200 1320/1056 10,5/11 50 750
H1 1000/800 880/704 6.3/6.6 60 900
I2 1500/1200 1320/1056 6.3/6.6 60 900
J2 1750/1400 1540/1232 6.3/6.6 60 900
H1 750/600 660/528 13,8 60 900
I2 1250/1000 1100/880 13,8 60 900
J2 1500/1200 1320/1056 13,8 60 900
H30-10-pole
H2 875/700 770/616 6.3/6.6 50 600
I2 1250/1000 1100/880 6.3/6.6 50 600
L2 1750/1400 1540/1232 6.3/6.6 50 600
H2 625/500 550/440 10,5/11 50 600
I2 875/700 770/616 10,5/11 50 600
L2 1500/1200 1320/1056 10,5/11 50 600
H2 875/700 770/616 6.3/6.6 60 720
I2 1250/1000 1100/880 6.3/6.6 60 720
L2 1750/1400 1540/1232 6.3/6.6 60 720
H2 625/500 550/440 13,8 60 720
L2 1500/1200 1320/1056 13,8 60 720
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Hig
hV
oltag
e
62
5 –
3 7
50
kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
H40
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
Specifications
Voltage Range [V] 3,300-13,800
Poles 6
Coil and insulation Bar Wound
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Double
SAE Adaptors 0, 00
Terminals 6
Material Insulation Class F
Excitation Power Supply Auxiliary Winding
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve Bearings
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
1 7
50
–4
50
0 k
VA
1830
15
50
2470min - 3470max
Bayerische Elektrische Maschinen | Power Portfolio
Model Core length
Power at cos ϕ=0.8 [kVA/kW]
Voltage Frequency1) Rotating speedTemperature rise/Running Mode at 40 °C
105 K/Continuous 80 K/Continuous
H40-4-Pole
K1 4000/3200 3520/2816 6.3/6.6 50 1500
L1 4500/3600 3960/3168 6.3/6.6 50 1500
L2 4750/3800 4180/3344 6.3/6.6 50 1500
K1 3750/3000 3300/2640 10,5/11 50 1500
L2 4500/3600 3960/3168 10,5/11 50 1500
K1 4000/3200 3520/2816 6.3/6.6 60 1800
L1 4500/3600 3960/3168 6.3/6.6 60 1800
L2 4750/3800 4180/3344 6.3/6.6 60 1800
K1 3750/3000 3300/2640 13,8 60 1800
L2 4500/3600 3960/3168 13,8 60 1800
H40-6-pole
I2 2750/2200 2420/1936 6.3/6.6 50 1000
K2 3250/2600 2860/2288 6.3/6.6 50 1000
K2 3500/2800 3080/2464 6.3/6.6 50 1000
I2 2500/2000 2200/1760 10,5/11 50 1000
K2 3250/2600 2860/2288 10,5/11 50 1000
I2 2750/2200 2420/1936 6.3/6.6 60 1200
K2 3250/2600 2860/2288 6.3/6.6 60 1200
K2 3500/2800 3080/2464 6.3/6.6 60 1200
I2 2500/2000 2200/1760 13,8 60 1200
K2 3250/2600 2860/2288 13,8 60 1200
H40-8-pole
I2 2000/1600 1760/1408 6.3/6.6 50 750
K2 2500/2000 2200/1760 6.3/6.6 50 750
I2 1750/1400 1540/1232 10,5/11 50 750
K2 2250/1800 1980/1584 10,5/11 50 750
I2 2000/1600 1760/1408 6.3/6.6 60 900
K2 2500/2000 2200/1760 6.3/6.6 60 900
I2 1750/1400 1540/1232 13,8 60 900
K2 2250/1800 1980/1584 13,8 60 900
H40-10-pole
J2 2000/1600 1760/1408 6.3/6.6 50 600
M1 2750/2200 2420/1936 6.3/6.6 50 600
J2 1750/1400 1540/1232 10,5/11 50 600
M1 2500/2000 2200/1760 10,5/11 50 600
J2 2000/1600 1760/1408 13,8 60 720
M1 2750/2200 2420/1936 13,8 60 720
J2 1750/1400 1540/1232 13,8 60 720
M1 2500/2000 2200/1760 13,8 60 720
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Hig
hV
oltag
e
1 7
50
–4
50
0 k
VA
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
H50
Hig
hV
olta
ge
Specifications
Voltage Range [V] 3,300 – 13,800
Poles 4, 6, 8 ,10
Coil and insulation Bar Wound
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 0, 00
Terminals 6
Material Insulation Class F
Excitation System Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
2 7
50
–7
12
5 k
VA
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
2900min – 3800max
1630
20
90
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
1630
20
90
2900min – 3800max
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise/ Running Mode at
40 °C[kV] [Hz] [rpm]
105 K/Continuous 80 K/Continuous
H50-4-Pole
K1 5000/4000 4400/3520 6.3/6.6 50 1500
L1 6000/4800 5280/4224 6.3/6.6 50 1500
L2 6250/5000 5500/4400 6.3/6.6 50 1500
N2 7125/5700 6270/5016 6.3/6.6 50 1500
K1 4750/3800 4180/3344 10,5/11 50 1500
L2 6000/4800 5280/4224 10,5/11 50 1500
N2 6875/5500 6050/4840 10,5/11 50 1500
K1 5000/4000 4400/3520 6.3/6.6 60 1800
L1 6000/4800 5280/4224 6.3/6.6 60 1800
N2 7125/5700 6270/5016 6.3/6.6 60 1800
K1 4750/3800 4180/3344 13,8 60 1800
L2 6000/4800 5280/4224 13,8 60 1800
N2 6875/5500 6050/4840 13,8 60 1800
H50-6-pole
K1 3750/3000 3300/2640 6.3/6.6 50 1000
N1 5625/4500 4950/3960 6.3/6.6 50 1000
K1 3500/2800 3080/2464 10,5/11 50 1000
N1 5000/4000 4400/3520 10,5/11 50 1000
K1 3750/3000 3300/2640 6.3/6.6 60 1200
M1 5000/4000 4400/3520 6.3/6.6 60 1200
N1 5625/4500 4950/3960 6.3/6.6 60 1200
K1 3500/2800 3080/2464 13,8 60 1200
M1 4375/3500 3850/3080 13,8 60 1200
N1 5000/4000 4400/3520 13,8 60 1200
H50-8-pole
K1 2750/2200 2420/1936 6.3/6.6 50 750
N1 4250/3400 3740/2992 6.3/6.6 50 750
O1 4750/3800 4180/3344 6.3/6.6 50 750
K1 2500/2000 2200/1760 10,5/11 50 750
N1 3750/3000 3300/2640 10,5/11 50 750
O1 4250/3400 3740/2992 10,5/11 50 750
K1 2750/2200 2420/1936 6.3/6.6 60 900
O1 4750/3800 4180/3344 6.3/6.6 60 900
K1 2500/2000 2200/1760 13,8 60 900
N1 3750/3000 3300/2640 13,8 60 900
O1 4250/3400 3740/2992 13,8 60 900
H50-10-pole
K1 3000/2400 2460/2112 6.3/6.6 50 600
M2 3750/3000 3300/2640 6.3/6.6 50 600
K1 2750/2200 2420/1936 10,5/11 50 600
M2 3500/2800 3080/2464 10,5/11 50 600
K1 3000/2400 2460/2112 6.3/6.6 60 720
M2 3750/3000 3300/2640 6.3/6.6 60 720
K1 2750/2200 2420/1936 13,8 60 720
M2 3500/2800 3080/2464 13,8 60 720
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Hig
hV
oltag
e
2 7
50
–7
12
5 k
VA
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
H60
Hig
hV
olta
ge
Specifications
Voltage Range [V] 3,300 – 13,800
Poles 4, 6, 8 ,10
Coil and insulation Bar Wound
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 0, 00
Terminals 6
Material Insulation Class F
Excitation System Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
30
00
-95
00
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
2900min – 3800max
1630
20
90
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise/ Running Mode at
40 °C[kV] [Hz] [rpm]
105 K/Continuous 80 K/Continuous
H60-4-Pole
M1 7200/5760 6335/5070 6.3/6.6 50 1500
N2 8400/6720 7390/5910 6.3/6.6 50 1500
P1 9400/7520 8270/6610 6.3/6.6 50 1500
M1 7000/5600 6150/4920 10,5/11 50 1500
N2 8300/6640 7300/5840 10,5/11 50 1500
P1 9300/7440 8180/6540 10,5/11 50 1500
M1 8500/6800 7480/5980 6.3/6.6 60 1800
M2 9100/7280 8000/6400 6.3/6.6 60 1800
K2 6400/5120 5630/4500 13,8 60 1800
M2 8500/6800 7480/5980 13,8 60 1800
H60-6-pole
K2 5600/4480 4930/3945 6,3/6,6 50 1000
Q1 8500/6800 7480/5985 6.3/6.6 50 1000
K2 5500/4400 4840/3870 10,5/11 50 1000
Q1 8500/6800 7480/5980 10,5/11 50 1000
H60-8-pole
L2 5100/4080 44903590 6.3/6.6 50 750
N2 6400/5120 5630/4500 6.3/6.6 50 750
O1 6600/5280 5810/4650 6.3/6.6 50 750
K2 4650/3720 4090/3270 10,5/11 50 750
M2 5600/4480 4930/3940 10,5/11 50 750
O1 6700/5360 5900/4720 10,5/11 50 750
L2 6200/4960 5450/4360 6.3/6.6 60 900
N2 7500/6000 6600/5280 6.3/6.6 60 900
K2 5200/4160 4570/3660 13,8 60 900
N2 7000/5600 6160/4930 13,8 60 900
H60-10-pole
J2 3550/2840 3120/2500 6.3/6.6 50 600
P2 5900/4720 5190/4150 6.3/6.6 50 600
K2 3700/2960 3250/2600 10,5/11 50 600
P2 5500/4400 4840/3870 10,5/11 50 600
J2 4100/3280 3600/2880 6.3/6.6 60 720
P2 7000/5600 6160/4930 6.3/6.6 60 720
J2 2690/2150 2360/1890 13,8 60 720
P2 4550/3640 4000/3200 13,8 60 720
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Hig
hV
oltag
e
30
00
-95
00
kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
H70
Hig
hV
olta
ge
Specifications
Voltage Range [V] 3,300 – 13,800
Poles 4, 6, 8 ,10
Coil and insulation Bar Wound
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 0, 00
Terminals 6
Material Insulation Class F
Excitation System Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
2 7
50
–7
12
5 k
VA
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
2900min – 3800max
1630
20
90
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
H80
Hig
hV
olta
ge
Specifications
Voltage Range [V] 3,300 – 13,800
Poles 4, 6, 8 ,10
Coil and insulation Bar Wound
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 0, 00
Terminals 6
Material Insulation Class F
Excitation System Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
90
00
-20
00
0kV
A
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
2900min – 3800max
1630
20
90
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
L08
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Lo
wV
olta
ge
Specifications
Voltage Range [V] 400 - 690
Poles 4, 6, 8, 10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class H
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
75
0 –
34
00
kV
A
1171
15
49
1920min – 2270max
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
00
-6
,00
0 k
VA
Hig
hV
olta
ge
Lo
wV
oltag
e
75
0 –
34
00
kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise/ Running Mode at 40 °C [kV] [Hz] [rpm]
125
K/Continuous
105
K/Continuous80 K/Continuous
L08-4-Pole
I2 2060/1648 1875/1500 1648/1318 0,4 50 1500
N2 8400/6720 7390/5910 400 50 1500
L1 2840/2272 2584/2068 2272/1818 0,4 50 1500
I2 2470/1976 2250/1800 1976/1580 0,48 60 1800
L1 3400/2720 3100/2480 2720/2176 0,48 60 1500
I1 2020/1616 1838/1471 1616/1293 0,69 50/60 1500/1800
L1 2990/2392 2721/2177 2392/1914 0,69 50/60 1500/1800
L08-6-pole
H2 1500/1200 1365/1092 1200/960 0,4 50 1000
K1 1900/1520 1730/1390 1520/1220 0,4 50 1000
H2 1800/1440 1638/1310 1440/1152 0,48 60 1200
K1 2290/1833 2085/1667 1833/1467 0,48 60 1200
H2 1240/992 1128/903 992/794 0,69 50/60 1000/1200
K1 1910/1528 1738/1390 1528/1222 0,69 50/60 1000/1200
L08-8-pole
H1 900/720 819/655 720/576 0,4 50 750
N2 6400/5120 5630/4500 6.3/6.6 50 750
J2 1350/1080 1229/983 1080/864 0,4 50 750
H1 1240/993 1129/904 993/792 0,48 60 900
M2 5600/4480 4930/3940 10,5/11 50 750
J2 1780/1424 1620/1296 1424/1139 0,48 60 900
H1 900/720 819/655 720/576 0,69 50/60 750/900
K2 1430/1144 1301/1041 1144/915 0,69 50/60 750/900
L08-10-pole
H1 670/536 610/488 536/429 0,4 50 600
J2 1110/888 1010/808 888/710 0,4 50 600
H1 800/640 728/582 640/512 0,48 60 720
K2 1330/1064 1210/968 1064/851 0,48 60 720
H1 720/576 655/524 576/461 0,69 50/60 600/720
K2 1110/888 1010/808 888/710 0,69 50/60 600/720
L09
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Lo
wV
olta
ge
Specifications
Voltage Range [V] 400 - 690
Poles 4, 6, 8, 10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class H
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
13
00
-42
00
kV
A
1171
15
49
1920min – 2270max
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
0 -
6,0
00
kV
A
Hig
hV
olta
ge
Lo
wV
oltag
e
13
00
-42
00
kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise/ Running Mode at 40 °C [kV] [Hz] [rpm]
125 K/Continuous 105 K/Continuous 80 K/Continuous
L09-4-Pole
K1 3450/2760 3410/2512 2760/2208 0,4 50 1500
K1 4140/3312 3767/3014 3312/2650 0,48 60 1800
K1 3510/2808 3194/2555 2808/2246 0,69 50/60 1500/1800
M1 4700/3760 4277/3422 3760/3008 0,69 50/60 1500/1800
L09-6-pole
H2 2240/1792 2038/1631 1792/1434 0,4 50 1000
K2 3050/2440 2776/2220 2440/1952 0,4 50 1000
H2 2688/2150 2446/1957 2150/1720 0,48 60 1200
K2 3660/2928 3331/2664 2928/2342 0,48 60 1200
I1 2050/1640 1866/1492 1640/1312 0,69 50/60 1000/1200
L1 3200/2560 2912/2330 2560/2048 0,69 50/60 1000/1200
L09-8-pole
I1 1650/1320 1502/1201 1320/1056 0,4 50 750
L1 2530/2024 2302/1842 2024/1619 0,4 50 750
I1 2080/1664 1893/1514 1664/1331 0,48 60 900
L1 3190/2552 2903/2322 2552/2042 0,48 60 900
J1 1930/1544 1756/1405 1544/1235 0,69 50/60 750/900
L2 2530/2024 2302/1842 2024/1619 0,69 50/60 750/900
L09-10-pole
H2 1220/976 1110/888 976/781 0,4 50 600
L1 1830/1464 1665/1332 1464/1171 0,4 50 600
H2 1464/1171 1332/1066 1171/937 0,48 60 720
L1 2196/1757 1998/1599 1757/1405 0,48 60 720
H2 1220/976 1110/888 976/781 0,69 50/60 600/720
L2 2000/1600 1820/1456 1600/1280 0,69 50/60 600/720
L10
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power PortfolioLo
wV
olta
ge
Specifications
Voltage Range [V] 400 - 690
Poles 4, 6, 8, 10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class H
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
20
00
-60
00
kV
A
1171
15
49
1920min – 2270max
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Hig
hV
olta
ge
1,0
0 -
6,0
00
kV
A
Hig
hV
olta
ge
Lo
wV
oltag
e
20
00
-60
00
kV
A
1) All products are designed for 50Hz and 60Hz.
Bayerische Elektrische Maschinen | Power Portfolio
Model Core length
Power at cos ϕ=0.8 [kVA/kW] Voltage Frequency Rotating speed
Temperature rise/ Running Mode at 40 °C [kV] [Hz] [rpm]
125 K/Continuous 105 K/Continuous 80 K/Continuous
L10-4-Pole
K1 4000/3200 3720/2976 3280/2624 0,4 50 1500
K1 4800/3840 4464/3571 3936/3149 0,48 60 1800
L10-6-pole
J1 3400/2720 3162/2530 2788/2230 0,4 50 1000
M2 4950/3960 4604/3683 4059/3247 0,4 50 1000
J1 4080/3264 3794/3036 3346/2676 0,48 60 1200
M2 5940/4752 5524/4419 4871/3897 0,48 60 1200
J2 3500/2800 3255/2604 2870/2296 0,69 50/60 1000/1200
N1 5000/4000 4650/3720 4100/3280 0,69 50/60 1000/1200
L10-8-pole
J2 2900/2320 2697/2158 2378/1902 0,4 50 750
M2 4030/3223 3748/2998 3305/2644 0,4 50 750
J2 3480/2784 3236/2589 2854/2283 0,48 60 900
M2 4836/3869 4497/3598 3966/3172 0,48 60 900
K2 2700/2160 2511/2009 2214/1771 0,69 50/60 750/900
N1 3800/3040 3534/2827 3116/2493 0,69 50/60 750/900
L10-10-pole
K1 2150/1720 2000/1600 1763/1410 0,4 50 600
N2 3120/2496 2902/2321 2558/2047 0,4 50 600
K1 2580/2064 2399/1920 2116/1692 0,48 60 720
N2 3744/2995 3482/2786 3070/2456 0,48 60 720
J2 2080/1664 1934/1548 1706/1364 0,69 50/60 600/720
O1 3250/2600 3023/2418 2665/2132 0,69 50/60 600/720
L11
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Lo
wV
olta
ge
Specifications
Voltage Range [V] 400 - 690
Poles 4, 6, 8, 10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class H
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
25
00
-90
00
kV
A
1171
15
49
1920min – 2270max
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
L12
Cummins Generator Technologies | Power Portfolio
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Lo
wV
olta
ge
Specifications
Voltage Range [V] 400 - 690
Poles 4, 6, 8, 10
Coil and insulation Bar Wound / GVPI
AVR Digital
Voltage sensing 3-Phase
Bearing Arrangement Single/Double
SAE Adaptors 1, 0, 00
Terminals 6
Material Insulation Class H
Excitation Power Supply Auxiliary Winding /
PMG
Protection IP23
Temperature monitoring Winding RTDs
Connection with other machines Paralleling capability
Optional Features
Bearing Arrangement Sleeve/Antifriction
Bearing
Ingress Protection IP23 Air Filters
Ingress ProtectionIP44 / 54 / 55 / 56
Totally enclosed
Cooling Options CACA / CACW
Environment protection Anti-condensation
Heaters
Designed for
Power Plant
Grid Code Compatible
Marine Propulsion
Oil & Gas
Combined Heat & Power
Continuous Power & Standby
Prime Mover
Diesel Engine
Gas Engine
Gas Turbine
Steam Turbine
50
00
-90
00
kV
A
1171
15
49
1920min – 2270max
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
DIMENSIONSDrawings represent standard design
All dimensions in millimetres (mm)
Cummins Generator Technologies | Power Portfolio
H80 BEMPower®
De
ratin
gBayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portfolio
Bayerische Elektrische Maschinen | Power Portofolio
Alternator selection: Rated load vs Type load (de-rating factors)
To select the right alternator, the following conditions should be taken into consideration:
(1) Environment conditions
• Derating and uprating for allowable temperature rise compared to allowable temperature rise acc.
IEC 60034 or other classification
• Derating regarding altitude above sea level
• Derating due to air inlet filters
• Derating due to non-standard rated voltages
• Derating due to extended voltage zone
(2) Divergent operation modes
• Derating for power factor range 0.7 to 1.0
• Derating due to converter load
• Uprating for Stand by mode
• Unbalanced load
• Voltage rise due to load switch off
• Wide voltage range
• Wide frequency range
• Stator pitch requirements
*For divergent operation de-rating factors, please contact applications engineering.
Cummins Generator Technologies | Power Portfolio
H80 BEMPower®
De
ratin
g
Bayerische Elektrische Maschinen | Power Portfolio
Alternator selection: Rated load vs Type load (de-rating factors)
Ambient temperature
• If the ambient (alternator air inlet temperature) exceeds 40 ºC then the alternator output rating must be
reduced using the following tables.
*For ambient temperatures above 60 ºC please consult applications
engineering.
Altitude
All ratings are based on altitude up to 1000 metres above sea level. If the altitude exceeds 1000m then
the alternator output ratings must be de-rated using the following table.
*For ambient temperatures above 60 ºC please consult applications engineering.
Utilisation Class H Class F Class B
Temperature ºC Multiplying Factor Multiplying Factor Multiplying Factor
45 0.968 0.963 0.955
50 0.935 0.925 0.910
55 0.903 0.888 0.865
60 0.870 0.850 0.820
Altitude above sea
level in metres
Multiplying Factor
1500 0.95
2000 0.9
2500 0.85
3000 0.8