DS110
OUTSULATION® PLUS MD SYSTEM®
An Exterior Wall Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier
Outsulation Plus MD System Installation Details
NOTE
DETAIL
TABLE OF CONTENTSDETAIL
OUTSULATION PLUS MD SYSTEM OPMD 0.0.01
OUTSULATION PLUS MD SYSTEM OPMD 0.0.01a
STARTER BOARD OPTION
AWRB APPLICATION OPMD 0.0.02
OPENING PREPARATION- OPMD 0.0.03
AQUAFLASH® SYSTEM OPTION
OPENING PREPARATION- OPMD 0.0.04
BACKSTOP® NT™ OPTION
OPENING FLASHING INTEGRATION OPMD 0.0.05
INSIDE/OUTSIDE CORNERS OPMD 0.0.06
OUTSIDE CORNER - HIGH IMPACT OPMD 0.0.07
GRADE TERMINATION OPMD 0.0.08
TERMNATION AT CONCRETE CURB OPMD 0.0.09
TERMINATION AT ADA COMPLIANT OPMD 0.0.10
SIDEWALK
EPS PREPARATION AT OPMD 0.0.11
WALL PENETRATIONS
STOREFRONT WINDOW SILL - JAMB OPMD 0.0.12
SELF FLASHING WINDOW SILL - JAMB OPMD 0.0.13
STOREFRONT AND FLANGED OPMD 0.0.14
WINDOW HEAD
HEAD J-TRACK OPTION OPMD 0.0.15
TERMINATION AT OPMD 0.0.16
WOOD FRAMED DECK
TERMINATION AT OPMD 0.0.17
WATERPROOF DECK
PREPARATION AT PARAPET/ OPMD 0.0.18
WALL INTERSECTION
TERMINATION AT PARAPET - OPMD 0.0.19
CAP FLASHING
TERMINATION AT PARAPET - OPMD 0.0.20
SOLID SUBSTRATE
TERMINATION AT SLOPED ROOF OPMD 0.0.21
TERMINATION AT ROOF STOP OPMD 0.0.22
FLASHING
VERTICAL WALL/ SUSPENDED OPMD 0.0.23
SOFFIT TRANSITION
TRANSITION AT SOFFIT/ OPMD 0.0.24
FASCIA INTERSECTION
FASCIA/ UNINSULATED SOFFIT OPMD 0.0.25
TRANSITION
TERMINATION AT OPMD 0.0.26
UNINSULATED SOFFIT VENT
HORIZONTAL SLIP JOINT OPMD 0.0.27
WITHOUT WEEPS
HORIZONTAL SLIP JOINT OPMD 0.0.28
WITH WEEPS
HORIZONTAL JOINT - OPMD 0.0.29
SUBSTRATE CHANGE
HORIZONTAL TERMINATION OPMD 0.0.30
AT STONE VENEER
HORIZONTAL TERMINATION OPMD 0.0.31
AT STUCCO
HORIZONTAL TERMINATION OPMD 0.0.32
AT WOOD SIDING
VERTICAL EXPANSION JOINT- OPMD 0.0.33
EIFS
THROUGH-WALL EXPANSION JOINT OPMD 0.0.34
VERTICAL EXPANSION JOINT - OPMD 0.0.35
FLUSH OPTION
VERTICAL EXPANSION JOINT - OPMD 0.0.36
RECESSED OPTION
VERTICAL EXPANSION JOINT - OPMD 0.0.37
DOUBLE SEAL OPTION
VERTICAL TERMINATION OPMD 0.0.38
AT STONE VENEER
PENETRATIONS OPMD 0.0.39
SIGN ATTACHMENT OPMD 0.0.40
AESTHETIC REVEALS OPMD 0.0.41
RECESSED GRAPHICS OPMD 0.0.42
PROJECTING GRAPHICS OPMD 0.0.43
EPS SHAPES OPMD 0.0.44
DRYVIT MAKES NO REPRESENTATION REGARDING
CONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDING
CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,
OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED
IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE
REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE
DESIGNED, DETAILED, AND ENGINEERED BY
REPRESENTATIVES OF THE ARCHITECT, OWNER, OR
CONTRACTOR TO BE IN CONFORMANCE WITH MODEL
CODES, ARCHITECTURAL, AND ENGINEERING
REQUIREMENTS PERTAINING TO SPECIFIC BUILDING
PROJECTS.
DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,
AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR
WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS
OR PRODUCTS.
THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE
OUTSULATION PLUS MD LIMITED COMMERCIAL
WARRANTY. CONTACT DRYVIT FOR A FULL AND
COMPLETE COPY OF THE WARRANTY.
Outsulation® Plus MD System®The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
©
Dryvit Systems, Inc.
Issued: 7/2018
DRYVIT ADHESIVE IN VERTICAL NOTCHED
TROWEL CONFIGURATION APPLIED TO
BACK OF EPS
Outsulation® Plus MD System®
OPMD 0.0.01
Outsulation Plus MD System
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD OR
STANDARD PLUS MESH. LOCATION OF
HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
2. AS AN OPTION DRYVIT DRAINAGE
TRACK™ CAN BE USED AT SYSTEM
TERMINATION AT GRADE, REFER TO
OPMD 0.0.08 FOR CONFIGURATION.
3. DRYVIT DRAINAGE TRACK SHALL ONLY
BE USED AT GRADE LEVEL TERMINATIONS.
NORMAL IMPACT
HIGH IMPACT
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL
CONFIGURATION APPLIED TO BACK OF EPS
DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS
OF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER - RESISTIVE BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT FINISH
FRAMING BY OTHERS
DRYVIT DRAINAGE STRIP ADHERED WITH DABS
OF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)
DRYVIT PANZER REINFORCING MESH
DRYVIT BASE COAT
OUTSULATION
PLUS MD SYSTEM
BY OTHERS
FRAMING BY OTHERS
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.
Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.01a
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD OR
STANDARD PLUS MESH. LOCATION OF
HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
NORMAL IMPACT
ULTRA HIGH
IMPACT
BY OTHERS
FRAMING BY OTHERS
©
Dryvit Systems, Inc.
Issued: 07/2018
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Outsulation Plus MD System
Starter Board Option
APPROVED SUBSTRATE
DRYVIT BASE COAT
OUTSULATION
PLUS MD SYSTEM
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL
CONFIGURATION APPLIED TO BACK OF EPS
DRYVIT SHAPES BY ACROCORE PRE-BASE
COATED STARTER BOARD OR APPROVED EQUAL
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER - RESISTIVE BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING BY OTHERS
DRYVIT ADHESIVE IN VERTICAL NOTCHED
TROWEL CONFIGURATION APPLIED TO
BACK OF EPS
DRYVIT PANZER REINFORCING MESH
DRYVIT BASE COAT
DRYVIT SHAPES BY ACROCORE PRE-BASE
COATED STARTER BOARD OR APPROVED EQUAL
DRYVIT BACKSTOP® NT™ - TEXTURE
APPROVED SUBSTRATE
FRAMING BY OTHERS
Outsulation® Plus MD System®
OPMD 0.0.02
NOTE:1. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.
DRYVIT BACKSTOP NT - TEXTUREOVER DRYVIT GRID TAPE™
AWRB Application
DRYVIT AIR/WATER - RESISTIVEBARRIER COATING
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
STEP #1 STEP #2
STEP #4STEP #3
Opening Preparation -AquaFlash® System OptionOutsulation® Plus MD System®
OPMD 0.0.03
NOTE:1. DRYVIT AQUAFLASH SHALL EXTEND TOINTERIOR FACE OF OPENING.
2. REFER TO HEAD, SILL AND JAMB DETAILSFOR FLASHING INTEGRATION.
3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTS ANDPROJECT DOCUMENTS.
5. AQUAFLASH SYSTEM CONSISTS OF AQUAFLASHMESH AND AQUAFLASH LIQUID.
6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIERDETAILS, REFER TO DRYVIT PUBLICATION DS840.
5
INSTALL DIAGONAL STRIP OF DRYVITAQUAFLASH MESH AT CORNERSAND EMBED IN AQUAFLASH LIQUID(SEE NOTES 1 AND 3)
APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 1 AND 3)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
INSTALL DRYVIT AQUAFLASHSYSTEM AT HEADS(SEE NOTES 1, 3 AND 4)
INSTALL DRYVIT AQUAFLASHSYSTEM AT JAMBS(SEE NOTES 1 AND 3)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.04
STEP #1
Outsulation® Plus MD System®
STEP #2
APPLY DRYVIT GRID TAPE™(SEE NOTES 1 AND 2)
TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)
6" (153 MM) MIN.(TYP.)
STEP #3
APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 2, 3 AND 5)
STEP #4
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING APPLIED TOFACE OF WALL (SEE NOTE 5)
NOTE:1. APPLY DRYVIT GRID TAPE ON HEAD, JAMB, ANDCORNERS OF OPENINGS AND SHEATHING JOINTS.
2. TROWEL APPLY DRYVIT BACKSTOP NT-TEXTUREOVER THE DRYVIT GRID TAPE ALL THE WAY TO INSIDEFACE OF OPENING. ALL VOIDS MUST BE FILLED;MULTIPLE PASSES MAY BE REQUIRED. AS AN OPTION,DRYVIT GRID TAPE AND DRYVIT BACKSTOP NT-TEXTUREMAY ALSO BE APPLIED AT THE SILL PRIOR TO DRYVITAQUAFLASH SYSTEM OR FLASHING TAPE APPLICATION.
3. DRYVIT FLASHING TAPE SURFACE CONDITIONER™AND DRYVIT FLASHING TAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM AT SILL, INCLUDINGCORNER SPLICES.
4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.
5. REFER TO HEAD, SILL, AND JAMB DETAILSFOR FLASHING INTEGRATION.
6. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.
Opening Preparation -Backstop® NT™ Option
4" (102 MM) MIN.(TYP.)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.05
STEP #1
Opening Flashing IntegrationOutsulation® Plus MD System®
REFER TO OPMD 0.0.03, AND OPMD 0.0.04FOR PREPARATION OF OPENING PRIORTO FLASHING INSTALLATION
STEP #2 STEP #3
REFER TO OPMD 0.0.12 &OPMD 0.0.13 FOR JAMBDETAIL
NOTE:1. REFER TO OPMD 0.0.12 AND OPMD 0.0.13FOR INTEGRATION OF FLASHING.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.
INSTALL WINDOW UNIT ANDASSOCIATED FLASHINGS ANDAPPLY DRYVIT AQUAFLASHSYSTEM OVER VERTICAL LEG OFFLASHING (SEE NOTES 1 AND 2)
APPLY DRYVIT AQUAFLASH®SYSTEM SPLICES LAPPING OVERLIP OF SILL PAN FLASHING.(SEE NOTES 1 AND 2)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.06
Inside/Outside CornersOutsulation® Plus MD System®
8"(203 MM)
MIN. MUST OVERLAP8" (203 MM) MIN.
(SEE NOTE 3)
MUST OVERLAP8" (203 MM) MIN.
(SEE NOTES 2, 3 AND 4) 8"(203 MM)
MIN.
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DOUBLE WRAP OUTSIDE CORNERS WITHREINFORCING MESH OR USE CORNER MESH.
3. DO NOT LAP REINFORCING MESH WITHIN8" (203 MM) OF A CORNER.
4. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
EPS INSULATION
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
DRYVIT BACKSTOP NT-TEXTUREOVER DRYVIT GRID TAPE
DRYVIT FINISH
DRYVIT BASE COAT
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.07
Outside Corner-High Impact
8"(203 MM)
MIN.
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.
DRYVIT FINISH
DRYVITBACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIEDTO BACK OF EPS
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT PANZER 20REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
DRYVIT STANDARDREINFORCING MESHOVERLAP 8" (203 MM) MIN.AT CORNER
EPS INSULATION
DRYVIT BASE COAT
DRYVIT CORNER MESH™
8"(203 MM)
MIN.
Outsulation® Plus MD System®
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
8" (203 MM)MIN.
Outsulation® Plus MD System® Grade Termination
2'-0" (610 MM)MAX.
(SEE NOTE 2)
OPMD 0.0.08
OUTSULATION PLUSMD SYSTEM
BY OTHERS
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 2'-0" (610 MM) DIMENSION IS EXCEEDED.
3. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
EPS INSULATION
DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 4)
SLOPE GRADE AWAYFROM FOUNDATION WALL
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE(SEE NOTE 3)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO
BACK OF EPS
APPROVED SUBSTRATE
5. DRAINAGE TRACK USAGE IS LIMITED TOTHE BASE OF THE SYSTEM AT FINISHEDGRADE LEVEL.
6. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.
8" (203 MM)MIN.
DRAINAGETRACK OPTION
2'-0" (610 MM)MAX.
(SEE NOTE 2)
SEE NOTES 4,5 & 6)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
Outsulation® Plus MD System® Termination At Concrete Curb
OPMD 0.0.09
BY OTHERS
DRYVIT FINISH
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
EPS INSULATION
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO
BACK OF EPS
APPROVED SUBSTRATE
NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. ENSURE BOTTOM EDGE OF DRAINAGE STRIP ISLEFT FREE TO DRAIN.
3. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
5. DRYVIT DRAINAGE TRACK SHALL ONLY BEUSED AT GRADE LEVEL TERMINATIONS.
DRAINAGETRACK OPTION
DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTURE OVER
GRID TAPE (SEE NOTES 3, 4 AND 5)
DRYVIT DRAINAGE TRACKSET IN DRYVIT AP ADHESIVE
OUTSULATIONPLUS MD SYSTEM
DRYVIT BASE COAT
2" (51 MM) MIN.
DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE (SEE NOTE 2)
DRYVIT AQUAFLASH® SYSTEM
DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT
GRID TAPE™
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
Termination At ADA Compliant Sidewalk
OPMD 0.0.10
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND FLOOR
APPLICATIONS AND ALL FACADES EXPOSED TO
ABNORMAL STRESS, HIGH TRAFFIC, OR
DELIBERATE IMPACT HAVE THE BASE COAT
REINFORCED WITH PANZER® MESH PRIOR TO
STANDARD OR STANDARD PLUS MESH.
LOCATION OF HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
2. USE OF THIS DETAIL IS LIMITED TO
SLAB-ON-GRADE APPLICATIONS.
3. INCORPORATE MEASURES TO PROTECT
STRUCTURE FROM MOISTURE INTRUSION,
DAMPNESS, AND FROST HEAVE.
OUTSULATION PLUS
MD SYSTEM
BY OTHERS
DRYVIT FINISH
DRYVIT STANDARD REINFORCING
MESH EMBEDDED IN DRYVIT BASE
COAT
EPS INSULATION
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT ADHESIVE APPLIED IN
VERTICAL NOTCHED TROWEL
CONFIGURATION TO BACK OF EPS
APPROVED SUBSTRATE
DRYVIT BASE COAT
3/4" (19 MM) MIN. (SEE NOTE 4)
DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TO
BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT AQUAFLASH® SYSTEM
METAL PROTECTION SHEET,
BY OTHERS
ADA COMPLIANT SIDEWALK SLOPED
AWAY FOR POSITIVE DRAINAGE
FULLY ADHERED FOUNDATION
WATERPROOFING MEMBRANE,
BY OTHERS
COMPRESSIBLE FILLER BOARD,
BY OTHERS
2" (51 MM) MAX.
OVERLAP
DRYVIT DRAINAGE STRIP™ ADHERED WITH
DABS OF DRYVIT AP ADHESIVE
Outsulation® Plus MD System®4. TO PREVENT DEBRIS ACCUMULATION, IT IS
RECOMMENDED TO TERMINATE SYSTEM 2"
ABOVE SIDEWALK.
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.
Issued: 10/2016
EPS INSULATION(SEE NOTE 2)
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DETAIL REINFORCING MESH9 1/2" (241 MM) X 12" (305 MM) (TYP.)(SEE NOTE 3)
OPMD 0.0.11
EPS Preparation At Wall PenetrationsOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. LOCATE INSULATION BOARDS SUCHTHAT BOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.
3. APPLY A PIECE OF 9 1/2" (241 MM) X 12"(305 MM) DETAIL REINFORCING MESHDIAGONALLY AT EACH CORNER.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Storefront Window Sill - JambOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. DRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ IS AN ALTERNATIVE OPTIONAT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.
4. EDGE WRAPPING METHOD ISACCEPTABLE AT SILL AND JAMB IN LIEUOF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND MUST EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.
OPMD 0.0.12
2 1/2"(64 MM) MIN.
1/2" (12.7 MM)
SILL PAN FLASHINGDETAIL
AIR SEAL PER MANUFACTURER'SREQUIREMENTS, BY OTHERS
DRYVIT COMPATIBLESEALANT, BY OTHERS
WRAP DRYVIT DETAILMESH® 2" (51 MM) MIN.
AT BACKSIDE OF EPS(SEE NOTE 4)
CONTINUOUS FLASHING, BYOTHERS, TURN UP 1/2" (12.7 MM) MIN.AT JAMBS - SEE DETAIL BELOW
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT COMPATIBLESEALANT, BY OTHERS
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)
EPS INSULATION BOARD
EPS SHAPE (OPTIONAL)
DRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVITAIR/WATER-RESISTIVE
BARRIER COATING
WRAP DRYVIT DETAIL MESH® 2" (51 MM) MIN. AT BACKSIDE OF EPS(SEE NOTE 4)
SLOPED SHIM ASREQUIRED, BY OTHERS
3/4" MIN.(19 MM )DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2 AND 3)
FRAMING BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.13
Self Flashing Window Sill - Jamb
FRAMING BY OTHERS
DRYVIT AQUAFLASH® SYSTEM(SEE NOTES 2 AND 3)
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. DRYVIT BACKSTOP® NT™-TEXTURE OVERDRYVIT GRID TAPE™ IS AN ALTERNATIVEOPTION AT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.
4. ADHESIVE ONLY APPLICATION IS ACCEPTABLEWHEN USING DRYVIT AQUAFLASH SYSTEM.
5. EDGE WRAPPING METHOD IS ACCEPTABLE INLIEU OF BACK WRAPPING. DRYVIT REINFORCINGMESH MUST BE FULLY EMBEDDED IN DRYVITBASE COAT AT EPS EDGE AND EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.
APPROVED SUBSTRATE
SILL PAN FLASHING,BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANT,BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT DETAIL MESHWRAPPED TO BACKSIDE
OF EPS MIN. 2" (51 MM)
EPS INSULATION
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
3/4" (19 MM ) MIN.
3/4"(19 MM) MIN.
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL
CONFIGURATION
EPS SHAPE (OPTIONAL)
TRANSITION FLASHING,BY OTHERS
DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)
DRYVIT COMPATIBLESEALANT, BY OTHERS
PROVIDE AIR SEAL, BY OTHERS,AROUND INTERIOR OF WINDOW
PER WINDOW MANUFACTURER'SREQUIREMENTS
Outsulation® Plus MD System®
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
OPMD 0.0.14
Storefront and Flanged Window Head
APPROVED SUBSTRATE
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS
SEALANT AND FLASHING,BY OTHERS
3/4" (19 MM)
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID
TAPE™ (SEE NOTE 2)
DRYVIT AQUAFLASH® SYSTEMOVER CONTINUOUS FLASHINGWITH END DAMS
AIR SEAL PERMANUFACTURER'SREQUIREMENTS,BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT(SEE NOTE 1)
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT FINISH
EPS SHAPE (OPTIONAL)
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
FLANGED WINDOW
WINDOWINTEGRALFLASHING
STOREFRONT WINDOW
DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM.
Outsulation® Plus MD System®
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.15
OUTSULATION PLUSMD SYSTEM
BY OTHERS
Head J-Track OptionOutsulation® Plus MD System®
EPS INSULATION
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
APPROVED SUBSTRATE
J-TRACK ATTACHED WITHDRYVIT AP ADHESIVE (SEE NOTE 2 AND 3)
SEALANT, BY OTHERS
DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID
TAPE™ (SEE NOTE 4)
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS
DRYVIT FINISH
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT BASE COAT
3/4" (19 MM) MIN.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3/4" (19 MM)
6" (152 MM)
6" (152 MM)
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. LIGHTLY SAND SURFACE OF J-TRACK TOMAXIMIZE ADHESION.
3. LENGTH OF TRACK NOT TO EXCEED 10 FT.(3.O M)
DRYVIT DEMANDIT® ORCOLOR PRIME ON SURFACESTO RECEIVE SEALANT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.16
Termination at Wood Framed DeckOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. DETAIL DOES NOT APPLY TO CANTILEVEREDDECKS. CANTILEVERED DECKS REQUIRE JOBSPECIFIC FLASHING DETAILS.
2" (51 MM)MIN.
FLASHING NO. 2, BY OTHERS
FLASHING NO. 3, BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
1" (25 MM)MIN.
2-1/2"(64 MM)MIN.
DRYVIT COMPATIBLESEALANT, BY OTHERS
FLASHING NO. 1,BY OTHERS
DECK BOARD
END JOIST
DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TORECEIVE SEALANT
2" (51 MM) MIN.
DRYVIT COMPATIBLESEALANT WITH BOND
BREAKER, BY OTHERS
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE
DRYVIT FINISH
DRYVIT AQUAFLASH® SYSTEM OVERCONTINUOUS FLASHING (NOTE 2)
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
EPS INSULATION BOARD
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System® Termination at Waterproof Deck
OPMD 0.0.17
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM )
SLOPE CONCRETE DECK SURFACEAWAY FROM VERTICAL WALL
2" (51 MM)MIN.
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 2)
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
COMPATIBLE WATERPROOF DECKCOATING, BY OTHERS
CANT STRIP, BY OTHERS
FRAMING BYOTHERS
APPROVEDSUBSTRATE
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
Outsulation® Plus MD System® Preparation At Parapet/ Wall Intersection
OPMD 0.0.18
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
APPROVED SUBSTRATE
FRAMING BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
FLASHING SLEEVE,BY OTHERS
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)
8"(203 MM)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)
STEP #1 STEP #2
STEP #3
6"(152 MM)
6"(152 MM)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System® Termination At Parapet - Cap Flashing
ROOFASSEMBLY
OPMD 0.0.19
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
EPS SHAPE OPTION(SEE NOTE 4)
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)(SEE NOTE 3)
DRYVIT FINISH
ROOF ASSEMBLY, BY OTHERS
2 1/2" (64 MM) MIN.
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
FRAMING,BY OTHERS
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)
METAL CAP FLASHING,BY OTHERS
DRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANT,BY OTHERS
3. EDGE WRAPPING METHOD IS ACCEPTABLEIN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND EXTEND ONTO SUBSTRATE 2"(51 MM) MIN.
4. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM) ATANY POINT MEASURED FROM THESUBSTRATE.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
2"(51 MM)
MIN.
OPMD 0.0.21
Termination at Sloped RoofOutsulation® Plus MD System®
3/4"(19 MM)
MIN.
110
100
ROOF DIVERTER(SEE NOTE 2)
12"(305 MM)
6"(152 MM)
6"(152 MM)
DRYVIT FINISH
NOTE:1. EXTEND DIVERTER FLASHING (KICKOUT)A MINIMUM OF 1" (25 MM) BEYOND FACEOF THE SYSTEM.
2. ROOF DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN.24 GAGE WITH WATER TIGHT SEAMS.
3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.
4. METAL FLASHINGS ARE 10" (254 MM) X2" (51 MM) LONGER THAN THE EXPOSEDPORTION OF THE ROOFING SHINGLE AND AREBENT IN HALF TO ALLOW FOR TWO 5" (127 MM)LEGS. ALTHOUGH NOT SHOWN, METALFLASHINGS ARE STEP FLASHED(INTERWOVEN) WITH ROOFING SHINGLES.
5. FOR ADDITIONAL SLOPED ROOF DETAILS,REFER TO DRYVIT PUBLICATION DS106.
6. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
DRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPSEPS INSULATION BOARDDRYVIT BASE COAT
DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OVER FLASHING (SEE NOTE 6)DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVEDRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
ROOF STEP FLASHING, BY OTHERS (SEE NOTE 4)
ROOFING SHINGLES
ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)
DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
GUTTER SYSTEM SLOPED AWAY FROM WALL
ROOF DIVERTER FLASHING, BY OTHERS(SEE NOTE 1 & 2)
FRAMING BYOTHERS
APPROVEDSUBSTRATE
OUTSULATION PLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
2" (51 MM) MIN.
OPMD 0.0.22
Termination at Roof Stop Flashing
3/4"(19 MM)
MIN.
NOTE:1. EXTEND ROOF STOP FLASHING 1" (25 MM)MINIMUM BEYOND FACE OF THE SYSTEM.
2. ROOF STOP TO BE MADE FROM CORROSIONRESISTANT MATERIAL MIN. 24 GAGE WITHWATER TIGHT SEAMS.
3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.
DRIP EDGE FLASHING, BY OTHERS
DRYVIT FINISH
DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEM OVER FLASHINGS (SEE NOTE 4)
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
ROOF/WALL FLASHING, BY OTHERS
ROOFING, BY OTHERS
DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
ROOF STOP FLASHING, BY OTHERS(SEE NOTE 2)
ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)
DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE
Outsulation® Plus MD System®4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
OUTSULATION PLUS MDSYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.23
Vertical Wall/ Suspended Soffit TransitionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT.
3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES.APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.
4. SEALANT JOINT IS REQUIRED FOR SUSPENDEDSOFFITS. OPTIONAL FOR RIGIDLY FRAMED.
3/4" (19 MM) MIN.
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVEAPPLIED TO BACK OF EPS
DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 3)
APPROVED SUBSTRATE
FRAMING BY OTHERS
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 2 AND 4)
DRYVIT AQUAFLASH® SYSTEM
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,
BY OTHERS (SEE NOTE 2 AND 4)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.24
Transition At Soffit/ Fascia IntersectionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.
3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES,APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVE BARRIERCOATING (SEE NOTE 3)
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT FINISH
DRYVIT ADHESIVEAPPLIED TO BACK
OF EPS
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVIT
AP ADHESIVE (SEE NOTE 2)
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.25
Outsulation® Plus MD System® Fascia/ Uninsulated Soffit Transition
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. SOFFITS WITHOUT EPS INSULATIONREQUIRE EXPANSION JOINTS EVERY20 FT (6 M).
3. REFER TO DRYVIT PUBLICATION DS 173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.
4. BOTTOM EDGE OF DRYVIT DRAINAGE STRIPSHALL BE MASKED DURING INSTALLATION TOPREVENT CLOGGING OF DRAINAGE CHANNELS.
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 4)
DRYVIT BACKSTOP® NT-TEXTURE™OVER DRYVIT GRID TAPE™
FRAMING BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
1" (25 MM) MAX.
CASING BEAD, BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.26
Termination at Uninsulated Soffit VentOutsulation® Plus MD System®
FRAMING, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVIT FINISH
NOTE:1. CONTROL JOINTS ARE RECOMMENDEDEVERY 20 FT (6.1 M).
2. REFER TO DRYVIT PUBLICATION DS173FOR SPECIFIC REQUIREMENTS FORSOFFIT AREAS.
3. SEAL ALL BUTT JOINTS,INTERSECTIONS, AND ENDS OF VENTSWITH COMPATIBLE SEALANT.
4. SEE DRYVIT PUBLICATION DS842 FORADDITIONAL DIRECT APPLIED DETAILS.
DRYVIT BASE COAT
DRYVIT BASE COAT
SOFFIT VENT, BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
BY OTHERS
Outsulation® Plus MD System®
OPMD 0.0.27
Horizontal Slip Joint without WeepsNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF BREAK IN SHEATHING.
3. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM OVER PREPARED JOINT.
5. SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT IS INTENDEDTO ACCOMMODATE CROSS GRAIN SHRINKAGEFOR FLOOR BEAMS.
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS MIN. 2" (51 MM)
CLOSED CELL BACKERROD, BY OTHERS
(SEE NOTE 2)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 4)
SLIP TYPECONNECTION(SEE NOTE 6)
3/4" (19 MM) MIN.
OUTSULATIONPLUS MD SYSTEM
DRYVIT BASE COAT
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT FINISH
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
SLOPE SURFACEOUTSIDE OF SEALANT 1:5MIN. OUTWARD TO DRAIN
DRYVIT COMPATIBLESEALANT WITH CLOSEDCELL BACKER ROD, BYOTHERS (SEE NOTE 5)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVEALONG TOP OF STRIP ONLY
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.28
Horizontal Slip Joint with Weeps
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4 AND 5)
CLOSED CELL BACKERROD, BY OTHERS
(SEE NOTE 3) DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
WEEPS AT 2'-0" O.C., BY OTHERS
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.
3. LOCATE EXTERNAL SEALANT JOINTWITHIN 2" (51 MM) OF BREAK IN SHEATHING.
4. STOP AQUAFLASH SHORT OF SEALANTBOND LINE.
5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT ISINTENDED TO ACCOMMODATE CROSSGRAIN SHRINKAGE FOR FLOOR BEAMS.
SLIP TYPECONNECTION(SEE NOTE 6)
SLOPE SURFACE 1:5 MIN.OUTWARD TO DRAIN
OUTSULATIONPLUS MDSYSTEM
BY OTHERS
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE
OF EPS MIN. 2" (51 MM) DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT FINISH
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
3/4" (19 MM) MIN.
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 5)
DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONG TOP OF STRIP ONLY
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OUTSULATION PLUSMD SYSTEM
BY OTHERS
Outsulation® Plus MD System®
OPMD 0.0.29
Horizontal Joint - Substrate ChangeNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OVER PREPAREDJOINT AT CHANGE IN SUBSTRATE.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.
4. REFER TO DETAIL OPMD 0.0.28 FORCONFIGURATION REQUIRING WEEPS.
3/4" (19 MM ) MIN.
4
DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONGTOP OF STRIP ONLY
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)
SLOPE SURFACE OUTSIDE OFSEALANT 1:5 MIN. OUTWARDTO DRAIN
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO
BACK OF EPS
APPROVED SUBSTRATE
DRYVIT BACKSTOP® NT™-TEXTUREOVER GRID TAPE™
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.30
Horizontal Termination at Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.
CONTINUOUS FLASHING,BY OTHERS
SEALANT WITH BOND BREAKER,BY OTHERS
FRAMING BY OTHERS
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
APPROVED SUBSTRATE
PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS
DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS
STONE VENEER SYSTEM,BY OTHERS
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)
3/4" (19 MM) MIN.
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.31
Horizontal Termination at StuccoNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIERCOATING BENEATH CLADDINGS OTHERTHAN DRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT
DRYVIT FINISHDRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER RODAND WEEP TUBES EVERY24" (610 MM), BY OTHERS
CONTINUOUS FLASHING,BY OTHERS
FRAMING BY OTHERS
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
APPROVED SUBSTRATE
SEALANT WITH BOND BREAKER,BY OTHERS
CEMENT PLASTER,BY OTHERS
PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS
3/4" (19 MM) MIN.
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.32
Horizontal Termination at Wood Siding
FRAMING BY OTHERS
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
APPROVED SUBSTRATE
SEALANT WITH BOND BREAKER,BY OTHERS
LAP SIDING, BY OTHERS
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS
CONTINUOUS FLASHING,BY OTHERS
DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT
3/4" (19 MM) MIN.
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.33
Outsulation® Plus MD System® Vertical Expansion Joint - EIFS
3/4" (19 MM) MIN.
NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. EIFS EXPANSION JOINTS ARE REQUIRED INCONTINUOUS ELEVATIONS AT INTERVALS NOTEXCEEDING 75 FT (23 M).
3
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OPMD 0.0.34
Outsulation® Plus MD System® Through-Wall Expansion Joint
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER DRYVIT FLASHINGTAPE LAPS WITH POLYETHYLENE TAPE ORBACKER ROD.
4. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF SUBSTRATE JOINT.
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)
FRAMING BY OTHERS
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM )
EPS INSULATION BOARD
DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
OPTIONAL SECONDARY SEAL, BY OTHERS
DRYVIT DEMANDIT OR COLOR PRIME ONSURFACES TO RECEIVE SEALANT
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)
DRYVIT DETAIL MESH WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)
OPTIONAL SECONDARY SEAL, BY OTHERS
CLOSED CELL BACKER ROD, BY OTHERS (SEE NOTE 4)
DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)
3/4" (19 MM) MIN.
3/4" (19 MM ) MIN.
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.35
Outsulation® Plus MD System® Vertical Expansion Joint - Flush Option
3/4" (19 MM) MIN.
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD OR
STANDARD PLUS MESH. LOCATION OF
HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACE
CONDITIONER™ AND DRYVIT FLASHING
TAPE™ MAY BE USED IN LIEU OF DRYVIT
AQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECT
CONTACT WITH ASPHALTIC ADHESIVE ON
DRYVIT FLASHING TAPE. COVER DRYVIT
FLASHING TAPE LAPS WITH POLYETHYLENE
TAPE OR BACKER ROD.
DRYVIT AQUAFLASH®
SYSTEM (SEE NOTE 2)
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH®
WRAPPED TO BACKSIDE
OF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLOR
PRIME™ ON SURFACES TO
RECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLE
SEALANT WITH CLOSED CELL
BACKER ROD, BY OTHERS
(SEE NOTE 3)
DRYVIT BACKSTOP® NT™-
TEXTURE OVER DRYVIT
GRID TAPE™
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT ADHESIVE IN
VERTICAL NOTCHED TROWEL
CONFIGURATION APPLIED TO
BACK OF EPS
EPS INSULATION BOARD
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.
Issued: 10/2016
OPMD 0.0.36
Outsulation® Plus MD System® Vertical Expansion Joint - Recessed Option
3/4" (19 MM) MIN.
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
FRAMING BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)
DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT
GRID TAPE™
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.37
Outsulation® Plus MD System®
3/4" (19 MM) MIN.
Vertical Expansion Joint - Double Seal Option
REAR SEAL
FACE SEAL
VENT
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)
REAR SEAL
FACE SEAL
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
EPS INSULATION BOARD
VENT
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)
FRAMING BY OTHERS
DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT
GRID TAPE™
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.38
Outsulation® Plus MD System®
3/4" (19 MM) MIN.
Vertical Termination At Stone Veneer
NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THANDRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS
BEDDING COAT AND STONEVENEER SYSTEM, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN BASE COAT
PAPER BACKED EXPANDEDMETAL LATH, BY OTHERS
ANGLE STOP FOR STONEVENEER SYSTEM, BY OTHERS
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND ANGLE STOP (SEE NOTE 2)
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.39
PenetrationsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.
3/4" (19 MM) MIN.
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
OPTIONAL SECONDARY SEAL, BY OTHERS
FRAMING BY OTHERS
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 3)
DRYVIT DEMANDIT OR COLOR PRIMEON SURFACES TO RECEIVE SEALANT
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2"(51 MM)
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
OUTSULATION PLUS MDSYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
OPMD 0.0.40
Sign AttachmentOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. PERIMETER OF PIPE SLEEVE IS SEALED TOPREVENT WATER ENTRY INTO WALL.
1/2" (12.7 MM) MIN.
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT FINISH
SCREW/BOLT ATTACHMENT TO BUILDINGFRAMING/BLOCKING, BY OTHERS
NEOPRENE WASHER, BY OTHERS
SIGN FIXTURE, BY OTHERS
DRYVIT COMPATIBLE SEALANT AND BONDBREAKER TAPE, BY OTHERS (SEE NOTE 2)
NON-CORROSIVE PIPE SLEEVE, BYOTHERS, SET IN SEALANT
BLOCKING, SECURED TO FRAMING
FRAMING BY OTHERS
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
OUTSULATIONPLUS MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.41
Aesthetic Reveals
NOTE:
1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADES
EXPOSED TO ABNORMAL STRESS, HIGH
TRAFFIC, OR DELIBERATE IMPACT HAVE
THE BASE COAT REINFORCED WITH
PANZER® MESH PRIOR TO STANDARD OR
STANDARD PLUS MESH. LOCATION OF
HIGH IMPACT ZONES SHOULD BE
INDICATED ON CONTRACT DRAWINGS.
2. SLOPE BOTTOM EDGE OF REVEAL FOR
POSITIVE DRAINAGE.
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT REINFORCING MESH EMBEDDED
IN DRYVIT BASE COAT
DRYVIT FINISH
3/4" (19 MM) MIN.
DRYVIT DETAIL MESH® EMBEDDED IN DRYVIT BASE
COAT. OVERLAP REINFORCING MESH 2 1/2" (64 MM)
DRYVIT BASE COAT
2 1/2" (64 MM)
2 1/2" (64 MM)
DRYVIT DETAIL MESH® OVERLAPED 2 1/2" (64 MM)
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWEL
CONFIGURATION APPLIED TO BACK OF EPS
OUTSULATION PLUS MD
SYSTEM
BY OTHERS
FRAMING BY OTHERS
APPROVED SUBSTRATE
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.
Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.42
Recessed Graphics
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING BY OTHERS
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
BY OTHERS
3/4" (19 MM) MIN.OUTSULATION
PLUS MD SYSTEM
OVERLAP 2 1/2" (64 MM)
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
SLOPE GRAPHIC FORPOSITIVE DRAINAGE
BY OTHERS
OUTSULATION PLUSMD SYSTEM
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
Outsulation® Plus MD System®
OPMD 0.0.43
Projecting Graphics
NOTE:
1. MAXIMUM THICKNESS OF EPS BUILT
OUT SHAPES SHALL NOT EXCEED
13 INCHES (330 MM) AT ANY POINT
MEASURED FROM THE SUBSTRATE.
BY OTHERS
OUTSULATION PLUS MD
SYSTEM
OVERLAP MESH
2 1/2"(64 MM )
SLOPE GRAPHIC FOR
POSITIVE DRAINAGE
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICAL
NOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT ADHESIVE
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE
BARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING BY OTHERS
DRYVIT ADHESIVE IN VERTICAL
NOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
EPS SHAPE (SEE NOTE 1)
OUTSULATION PLUS
MD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.
Issued: 10/2016
OPMD 0.0.44
EPS Shapes
BYOTHERS
OUTSULATION PLUS MDSYSTEM
OVERLAP MESH2 1/2" (64 MM) MIN.
DRYVIT ADHESIVE APPLIED TO BACKOF EPS SHAPE
EPS SHAPE MEETING DRYVITSPECIFICATION DS131 (SEE NOTE 1)
FRAMING BY OTHERS
DRYVIT ADHESIVE APPLIED IN VERTICALNOTCHED TROWEL CONFIGURATION TO BACK OF
INSULATION BOARD
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DETAIL MESH OVERLAPONTO EXISTING TO BEFEATHERED OUT FLAT PRIOR TOFINISH APPLICATION
NOTES:1. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM)AT ANY POINT MEASURED FROM THESUBSTRATE.
DRYVIT FINISH
SLOPE SURFACE 6:12MIN. FOR POSITIVEDRAINAGE. MAXIMUMLENGTH OF SLOPEDSURFACE IS 12" (305 MM)
Outsulation® Plus MD System®
OUTSULATION PLUSMD SYSTEM
BY OTHERS
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. Issued: 10/2016