Objectives
• Finish up discussion of cycles
• Differentiate refrigerants• Identify qualities of a good refrigerant
• Compare compressors
• Describe expansion valves
![Page 2: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/2.jpg)
Homework Assignment 3
![Page 3: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/3.jpg)
Administrative
• Reminder Oral Presentations
• Monday December 5th
• 6 – 8:30 pm
• Location TBA
• Annotated bibliography due 10/25 (two weeks)• No homework for a week+
![Page 4: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/4.jpg)
Compressor
• Workhorse of the system
• Several types – all compress gas with varying degrees of efficiency• Far from isentropic (our assumption earlier)
• Wshaft = work done by shaft
• Welec = electric power requirements
![Page 5: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/5.jpg)
Reciprocating Compressor
• Figures 4.4, 4.6
![Page 6: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/6.jpg)
![Page 7: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/7.jpg)
Rotary Compressors
• Higher efficiency, lower noise and vibration
• Cylinder rotating eccentrically in side housing
![Page 8: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/8.jpg)
Scroll Compressors
• One scroll is fixed
• The other scroll “wobbles” inside compressing refrigerant
• Often requires heat transfer from refrigerant to cool scrolls
![Page 9: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/9.jpg)
Scroll Compressors
• Constant displacement
• Higher efficiency, but harder to manufacture
• Close tolerance between scrolls
• Ugly to analyze – see text for details
![Page 10: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/10.jpg)
Screw Compressors
• Rotating meshed screws
• One or two screws
![Page 11: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/11.jpg)
Summary
• Many compressors available• ASHRAE Handbook is good source of more
detailed information• Very large industry
![Page 12: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/12.jpg)
Expansion Valves
• Throttles the refrigerant from condenser temperature to evaporator temperature
• Connected to evaporator superheat• Increased compressor power consumption• Decreased pumping capacity• Increased discharge temperature
• Can do it with a fixed orifice (pressure reducing device), but does not guarantee evaporator pressure
![Page 13: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/13.jpg)
Thermostatic Expansion Valve (TXV)
• Variable refrigerant flow to maintain desired superheat
![Page 14: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/14.jpg)
AEV
• Maintains constant evaporator pressure by increasing flow as load decreases
![Page 15: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/15.jpg)
Summary
• Several compressor options• Dramatically impacts energy use of air conditioner
• Expansion valves make a big difference in refrigeration system performance
• Trade-offs• Cost, critical refrigerant amount
![Page 16: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/16.jpg)
Real Data• An evaluation of superheat-based refrigerant charge diagnostics for
residential cooling systems
Siegel, Jeffrey A. (Lawrence Berkeley Natl. Laboratory); Wray, Craig P. Source: ASHRAE Transactions, v 108 PART 2, 2002, p 965-975
Abstract: Although refrigerant charge has an important influence on the performance of residential cooling systems with fixed orifice metering devices, there has been little research to quantify the effects of incorrect charge or design new diagnostics for evaluating charge level. The most common diagnostic for charge level in these systems is the superheat test. In this paper, we examine three superheat technologies/techniques. Two of the diagnostics are appropriate for detecting incorrect charge, one is not. Additionally, measurements at four houses indicate that it is important to measure the condenser air entering temperature with a high degree of accuracy. Measurement of the wet-bulb temperature in the return plenum and the suction line temperature are equally important but seemingly easier than measuring the condenser air temperature, as several measurement technologies yielded similar results for these quantities. The importance of refrigerant charge to energy use and capacity of residential cooling systems, the limitations of the superheat test, and the variations in the test method results and interfaces necessitate the development of a standard method or methods to determine refrigerant charge level. (8 refs.)
![Page 17: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/17.jpg)
Motivation
• Demonstrate importance of refrigerant charge
• Evaluate technologies for assessing refrigerant charge with superheat method
• Stimulate discussion on new technologies and approaches for measuring charge levels
![Page 18: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/18.jpg)
Refrigerant Charge
Ref: Farazad and O’Neal, 1988
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
1.10
-20% -10% 0% 10% 20%Deviation from Full Charge
Nor
mal
ized
Cap
acity
[Ful
l, 95
°F w
et =
34.
0 kB
tu/h
]
100°F (38°C) wet95°F (35°C) wet90°F (32°C) wet82°F (28°C) wet82°F (28°C) dry
![Page 19: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/19.jpg)
How Much of a Problem?
• Proctor (2002) studied 13,258 residential central air conditioners• 55% of residential units out of specification• 42% undercharged by more than 10%• 13% overcharged by more than 10%
• Commercial air conditioners showed similar patterns
![Page 20: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/20.jpg)
Superheat
• Thermodynamic metric• Difference between refrigerant temperature in
suction line and its saturation temperature
Undercharge Overcharge
Superheat too large Superheat too small
Poor heat transferPotential coil icing
Slug compressor
![Page 21: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/21.jpg)
Superheat Test
OrificeControl
Compressor
Condenser AirAMB=85F
Evaporator AirTdb=81F, Twb=68F Suction Line
ST=84F
SH=57FSP=51 psig (Tsat=27F)
![Page 22: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/22.jpg)
Charging Chart
Target = 19°F Actual = 57°F Undercharge
5
10
15
20
25
30
35
40
65 70 75 80 85 90 95 100 105 110 115
OUTDOOR DRY-BULB TEMPERATURE [ºF]
TA
RG
ET
SU
PE
RH
EA
T [
ºF]
7674
7270
68
66
64
6260
58
INDOOR WET-BULB TEMPERATURE [ºF]
19
![Page 23: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/23.jpg)
Caveats
• Orifice-controlled systems• TXV-controlled devices are much less sensitive to
charge level
• Small sample size
• Imperfect truth method• Insufficient time to do gravimetric procedure
![Page 24: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/24.jpg)
Test Houses
Site
House Location
Cooling Equipment
Age [Years]
Condensing Unit
Rated Capacity [Tons]
Evaporator Rated
Capacity [Tons]
A Larkspur, CA 17 3 Unknown B Sacramento, CA < 1 3.5 4 C Sacramento, CA < 1 3 4 D Concord, CA > 15 3.5 Unknown
![Page 25: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/25.jpg)
Field Testing
![Page 26: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/26.jpg)
Temperature Profiles (Site C)
40
50
60
70
80
90
100
110
120
11:30 12:00 12:30 13:00Time of Day
Tem
pera
ture
[°F
]
4.4
10.0
15.6
21.1
26.7
32.2
37.8
43.3
48.9
Tem
pera
ture
[°C
]
AC On
Charge Added
Liquid Line Temperature
Outdoor Temperature
Suction Line Temperature
![Page 27: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/27.jpg)
Results
Site A Site B Site C Site D
Charge Added [oz]
Fraction of Total
15
17%
11
13%
20.5
33%
19
Unknown
EER Increase 19% 7% 20% N/A
Capacity Increase 33% 18% 38% 35%
![Page 28: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/28.jpg)
Summary
• Refrigerant charge matters a lot• Particularly with orifice (i.e. cheap and simple)
expansion valves
• Superheat is desirable• Prevents slugging of compressor with liquid• Manufacturer provides target superheat
• Function of evaporator entering t* (for air) and outside temperature
– Why?
![Page 29: Objectives Finish up discussion of cycles Differentiate refrigerants Identify qualities of a good refrigerant Compare compressors Describe expansion valves](https://reader030.vdocuments.mx/reader030/viewer/2022032414/56649ef05503460f94c00c19/html5/thumbnails/29.jpg)
Next class
• Heat exchangers (evaporators and condensers)