Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJT100
Special CollectionsRoom - Title Page
SP #1028
Rowan University
Campbell Library
2017-3-7
Entrance from Library1
Reception to Reading Area2
Reception to Reading Rm3
Along Windows4
ARCHITECTURAL DRAWINGS
Sheet Number Sheet NameCurrentRevision
CurrentRevision Date
T100 Special Collections Room - Title Page
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
Building Code Analysis - ArchitecturalInternational Building Code/2015, NJ Ed. - NJAC 5:23 - 3.14Pertinent Sections:304.1 - Occupancy classification = A (assembly)Table 1004.1.2 - Library Occupancy, load factor = 50 NSF per occupant(N/A) Table 1006.2.1 - Spaces with One Exit, A occ.: 49 = max occ. load & 75 FT max. common path of egress travel distanceTable 1017.2 - Exit access travel distance, A occ., sprinklered = 250 FT. See A101 for egress path-of-travel.
1994 Code Compliance - BOCA National Building Code 1994 - NJAC 5:23 - 3.14 :Use Group A-3 (Table 302.4)Construction Classification - Type IIIEgress width per occupant (with sprinkler system) - .15 inches per person at doors, ramps & corridorsLength of exit access travel (with sprinklekr system) - 250 FTWidth of corridors 44 inches; Minimum door width required 32" - 36" used
AD100 Special Collections Room - Demo. PlanAD200 Special Collections Room - Demo. RCP
A100 Special Collections Room - 3rd Fl. PlanA200 Special Collections Room - 3rd Fl. RCPA600 Special Collections Room - 3rd Fl. Elev.A900 Details & Wall Types
100% CD
NJDCA electronic release stamp
Entrance to 3rd FloorBook Stacks Area
WOMENMEN
ROOM 333COLLECTIONSDEVELOPMENT
ROOM 341
PROJECT BOUNDARY
3' -
8"
Salvage & re-use 8WD/MTL end panels
Retain 30 ranges ofshelving and8 end panels for use inSpecialCollections Room
Remove carpetthroughoutproject area
Retain 270 shelves fromremoved shelving for adifferent project atCampbell Library.- Uprights not needed- Some shelves to bebottom shelf with lip(Susan Fink to confirmqty)
Approximately 8 study carrels - remove and salvage for Owner re-use
Remove MTL libraryshelving whereindicated. Retainranges as describedbelow. All othershelves to bedisposed of byContractor. At floor,cut anchor bolts andgrind smooth and flushwith concrete floor.Re-grout any cracksand spalls in adjacentconcrete.
3' -
0"
1' - 8"
18' -
0"
21' -
0"
Remove walls and doors.Walls stop below ACT CLG.Protect ETR ceiling grid andACT tiles. Repair wall atprior attachment locations.Protect ETR carpet tile.
3RD FLOOR BOOK STACKSAREA, NORTHEAST CORNER
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
1/4" = 1'-0"Glassboro, NJ
AD100
Special CollectionsRoom - Demo. Plan
SP #1028
Rowan University
Campbell Library
2017-3-7
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
100% CD
NJDCA electronic release stamp
WOMENMEN
ROOM 333COLLECTIONSDEVELOPMENT
ROOM 341
PROJECTBOUNDARY
High Hat Light Fixture, TYP3 lampsWattage, remaining useful life& potential to convert to LED
ETR Speaker
ETR 2X2 FT Light Fixture,TYP. F17, TA, 17W, 3 lamps
ETR Sprinkler head, TYP
CL
ETR sconces at COL
ETR diffusers, SMD. Existingdiffusers: (4) 10" DIA VAVSupply Diffuser 300 CFM
ETR: (3) 24X8" VAV SupplyDiffuser 600 CFM
ETR, SED: 4X7" Cable Tray(above ceiling)
Maintain ceiling & light fixturesin place within Room 341
9'-10"9'-10"
8'-5 1/2"
ETR ceiling grid and ACT tilesto be cut along new walls.Protect and re-support ceilinggrid and re-use ACT tiles.
ETR ceiling grid and ACT tilesto be cut along new walls.Protect and re-support ceilinggrid and re-use ACT tiles.
Lighting and supply diffusers tobe modified in this room only.SED, SMD. ACT Celing grid andtiles to remain in place.
Entrance to 3rd FloorBook Stacks Area
3RD FLOOR BOOK STACKS AREA,NORTHEAST CORNER. AREA
WITHIN PROJECT BOUNDARY TOBE ENCLOSED AS NEW SPECIAL
COLLECTIONS ROOM 340
FUTURE ROOM 340DSPECIAL COLLECTIONS
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
1/4" = 1'-0"Glassboro, NJ
AD200
Special CollectionsRoom - Demo. RCP
SP #1028
Rowan University
Campbell Library
2017-3-7
(1) Maintain ACT in place UON.(2) Maintain lighting fixtures in place UON.
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
100% CD
NJDCA electronic release stamp
5' -
0"
Entrance to OpenStacks
ETR standpipe
WOMENMEN
A600
2
-N
E
ROOM 333COLLECTIONSDEVELOPMENT
PROJECT BOUNDARY
-
7'-0" tall X3'-0" longBook Shelf,TYP
4
A600
15 1/2"
Install salvagedWD/MTL end panelsat all shelf ends.
(N) 1-hr opaque wall to6" above ACT ceiling,flush with inside of ETRCONC columns. 3 5/8"MTL stud; 5/8" GWBeach side. Coordinatetop of wall with ETRducts above ACT grid.Anchor wall with 3/8"DIA grouted anchorbolts @ 24" OC toCONC columns.
ETR
3' - 0"
515 SF
Collection
340D
551 SF
Office
341
Copier by Owner
2860 SF
Special CollectionsReading Room
340
All new electrical andemergency devices to belocated on walls adjacent tocolumns, not on CONC columns.
ETR soffit (overhead)
(30 occ.)
ETR soffit (overhead)
ETR soffit (overhead)
A600
175 FT to Stair 3 85 FT to Stair 4
*95 FT egresspath to Sp.Col.Rm. Main Door*
Re-install30 MTLbookshelfranges
*109 FTegress path toSp.Col. Rm.Main Door*
3' - 6" 4' - 2"
Map Case
5"
Reverse swingon ETR DR
5' - 10"5'
- 7
"
1A900
1
1
with lock
14' -
3 1
/4"
A600-
No (N) light switch atRoom 340. Lights to beon general circuit forBook Stacks main area.
CPTMannington CPT tile; Antron 6,6Nylon: Canopy II Sydney (35295)Installation pattern: brick ashlar
ETR CPT
Vinyl Tile
2
3
by OwnerContractorto place.
4" straight roll vinyl wall baseat all new walls
Blackout film overETR full-height glasslites in metal frameassembly
4' - 4"
PT-1: SW6243'DISTANCE' - Semi-gloss
- at all walls in 340D
PT-2, entire window wallSW 6244 'Naval' Semi-Gloss
PT-3 all other walls this room,SW 6805 'Glass Bead' Semi-gloss
PT-4 SW Semi-gloss, color tomatch surrounding library walls.4" rubber wall base to matchsurrounding library walls.
1
(N) 1-hr opaque wall to6" above ACT ceiling,flush with inside of ETRCONC columns. 3 5/8"MTL stud; 5/8" GWBeach side. Coordinatetop of wall with ETRducts above ACT grid.
(N) 1-hr opaque wall 8'-5 1/2" high, terminatingat soffit overhead. Wall to be flush with face ofETR CONC columns. 3 5/8" MTL stud; 5/8" GWBeach side. Anchor wall with 3/8" DIA groutedanchor bolts @ 24" OC to CONC columns andstud track above.
Light switch & switch-plate, SED. (N) lightingzone for this room.
12' - 0"
2
1
CL
2 2 22
3
MTL transition strip atCPT (3-7mm) / Vinyl(2mm): SchluterSCHIENE E20stainless steel, 2mm.Set vinyl intotransition strip.
2A900
48' -
10"
Light switch - SED
Vinyl tile: ASI QuarryStone Vinyl Flooring: FLRGB106 12"X24"; 2.5mm with 28mil wear layer,7-layer construction. Finish: G88 Ceramic Infused Coating - Anti-bacterial and Anti-fungal.Glue-down over prepared concrete surface with manufacturer's recommended glue, DryTacvinyl adhesive. See specification for additional information.
22' - 4"8' - 2"
A A A A A A
A
A
8' - 2"22' - 4"
41' -
1 3
/4"
13' - 1"
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
1/4" = 1'-0"Glassboro, NJ
A100
Special CollectionsRoom - 3rd Fl. Plan
SP #1028
Rowan University
Campbell Library
2017-3-7100% CD
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
(1) See specifications for additional information on all products.
(2) Verify all existing conditions and dimensions in field.
(3) Attach (N) MTL stud walls to ETR CONC columns with 1/4" X 1" Hilti HIT metal drive anchors @ 30" max OC - at all locations marked "A"
NJDCA electronic release stamp
WOMENMEN
ROOM 333COLLECTIONSDEVELOPMENT
PROJECTBOUNDARY
ETR High Hat LightFixture, TYP
ETR Speaker
ETR 2X2 FT LightFixture, TYPF17, TA, 17W, 3 lamps.All light fixtures to remainin existing locationsexcept in Room 340D.
ETR Sprinkler head, TYP
CL
ETR sconces at COL
ETR: (3) 24X8" VAV SupplyDiffuser 600 CFM
ETR 4X7" Cable Tray (aboveceiling), SED
Maintain ACT & 2X2 light fixturesin place, this room. SMD for newdiffuser layout & spec.
9'-10"
9'-10"
8'-5.5"
Remove & re-install 2X2 lightfixtures, this room. Install re-usedACT in former light fixture location.(N) light fixture layout as shown.SMD for new diffuser layout & spec.
ACT, light fixtures, diffusersand sprinkler heads to remainin Room 340, UON. Seeengineering drawings fordeviations.
551 SF
Office
341
2860 SF
Special CollectionsReading Room
340
515 SF
Collection
340D
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
1/4" = 1'-0"Glassboro, NJ
A200
Special CollectionsRoom - 3rd Fl. RCP
SP #1028
Rowan University
Campbell Library
2017-3-7
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
100% CD
(1) See specifications for additional information on all products.
(2) Verify all existing conditions and dimensions in field.
NJDCA electronic release stamp
CONC column GWB PTD - PT-2
ROOM 341, OFFICE ROOM 340, SPECIAL COLLECTIONS
6' -
9 1
/2"
6' - 10"
10"
ETR continuous baseboard hot water fin-tube radiation heating ETR 1" continuous power outlet strip13"
7' -
10
1/2"
NB, NO devices to be mounted on ETR CONC columns.
PROJECTBOUNDARY
Wall Type 1
ETR COL
PT-2
PT-2, entire window wallSW 6244 'Naval' Semi-Gloss
PT-2PT-2 PT-2 PT-2 PT-2 PT-2 PT-2
ETR CONC column, TYP
GWBPTD
ETRCOL
ETRCOL
ETRCOL
6" straight roll vinyl wallbase, TYP this wall
3' - 0"
6' - 6" HM frame
6' - 0"
1
8' -
5 1
/2"
8' -
2 1
/2"
ETR soffit
3' - 3"
4" 28" 4"
3"
3"
4"88
1/2
"6"
Glass doors
36"
Best lever HW to match, no lock
SW Semi-gloss to match library walls GWBPTD
SW Semi-gloss to match library walls
HW: Best Lock 9K - 3 (backset) - 7 (core housing) -S (function) - 16K (lever) - K (rose style) - S3 (strike)- 619 (finish)
Satin nickel plated finish on HM DR
HW: Best Lock 9K - 3 (backset) - 7 (core housing) -R (function) - 16K (lever) - K (rose style) - S3 (strike)- 619 (finish)
2
7' -
3"
HM
fram
e
7' -
0"
3"36"3"
WD hollow core door. PT-2
36"
PT GWB 8' -
9"
Satin nickel plated finish on HM DR
ET
R
9' -
10"
ET
R
8' -
9"
10' -
0"
11' -
0"
ETR MTL stud-framed ceiling, cross-braced every 3rd stud
(N) Wall Type 2 flush with face ofETR CONC column. See 2/A900 forWall Type 2 attachment details.
6"
NB, GWB extends 6" past ceiling @ Wall Type 1 (not shown in this view).See 1/A900 for Wall Type 1 attachment details.
2' -
6 1
/2"
27"
ETR 23" X 45" Supply air ductETR 14" X 34" Supply air duct
ROOM 340
TYP @ Wall Type 1
Face of CONC floor slab for 4th Fl
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
1/4" = 1'-0"Glassboro, NJ
A600
Special CollectionsRoom - 3rd Fl. Elev.
SP #1028
Rowan University
Campbell Library
2017-3-7
1/4" = 1'-0"
Special Collections - EAST2
1/4" = 1'-0"
Special Collections - MAIN1
50% CD
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
1/4" = 1'-0"
Collections - Exterior Wall3 1/4" = 1'-0"
Section (Transverse)4
(1) See specifications for additional information on all products.
(2) Verify all existing conditions and dimensions in field.
NJDCA electronic release stamp
5/8" GWB, PTD
3 5/8" MTL studs @ 16" OC
Top of ETR or (N) ACT
4" straight roll vinyl wall base,color by Architect
Cut ACT & extend wall 6" above
4" straight roll vinyl wall base, colorto match main stack area wall base
CONT slip-track top stud
(N) CPT tile; wall base toCONC floor behind
ETR CPT cut at (N) wall
1/4" X 1" Hilti HIT metal driveanchors @ 30" max OC toMTL STUD track & CONC floor
(N) ACT grid at (N) wall edge
Ceiling attachment at ribs:1/4" X 1" Hilti HIT metal driveanchors @ 30" max OC
6"
Extend GWB & MTL studsto 6" above ACT. Extendevery 3rd stud to undersideof MTL deck above.
between ribs:PL 8" WIDE, 10 GA.1/4" X 1" Hilti HITmetal drive anchors@ 30" max OC
5/8" GWB, PTD
3 5/8" MTL studs @ 16" OC
6" straight roll vinyl wall base,color by Architect
4" straight roll vinyl wall base, colorto match main stack area wall base
CONT slip-track top stud
(N) CPT tile; wall base toCONC floor behind
ETR CPT cut at (N) wall
1/4" X 1" Hilti HIT metal driveanchors @ 30" max OC to MTLSTUD track & CONC floor
7/16" MTL framing screws toMTL soffit framing above.
ETR soffit
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
3" = 1'-0"Glassboro, NJ
A900
Details & Wall Types
SP #1028
Rowan University
Campbell Library
2017-3-7
3" = 1'-0"
Wall Type - 11
Miller-Remick LLCM.E.P. & Structural Engineering1010 Kings Highway SouthCherry Hill, NJ 08034(856) 429-4000
100% CD
3" = 1'-0"
Wall Type - 22
Inside SpecialCollections Room
Inside SpecialCollections Room
Library BookStack Area
Library MainHallway
(1) See specifications for additional information on all products.
(2) Verify all existing conditions and dimensions in field.
NJDCA electronic release stamp
M-001
MECHANICALINDEX SHEET
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
WOMENMEN
ROOM 333COLLECTIONS
DEVELOPMENT
ROOM 341
PROJECT BOUNDARY
MD101
MECHANICALDUCTWORK
DEMOLITION PLAN
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
PROJECT BOUNDARY
Collection
340D
Special CollectionsReading Room
340
Office
341
MH101
MECHANICALDUCTWORK PLAN
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
M-601
MECHANICALSCHEDULES &
DETAILS
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
1FLEXIBLE DUCT CONNECTION
3VOLUME DAMPER DETAIL
2FLEXIBLE AIR DUCT CONNECTOR
E-001
ELECTRICALSYMBOLS AND
ABBREVIATIONS
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
E-002
ELECTRICALDEMOLITION ANDGENERAL NOTES
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
WOMENMEN
ROOM 333COLLECTIONS
DEVELOPMENT
ROOM 341
PROJECT BOUNDARY
ED101
ELECTRICALDEMOLITION PLAN
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
PROJECT BOUNDARY
WOMENMEN
ROOM 333COLLECTIONS
DEVELOPMENT
551 SF
Office
341
2860 SF
Special CollectionsReading Room
340
515 SF
Collection
340D
WOMENMEN
ROOM 333COLLECTIONS
DEVELOPMENT
551 SF
Office
341
2860 SF
Special CollectionsReading Room
340
515 SF
Collection
340D
WOMENMEN
ROOM 333COLLECTIONS
DEVELOPMENT
551 SF
Office
341
2860 SF
Special CollectionsReading Room
340
515 SF
Collection
340D
E-101
ELECTRICALPLAN - NEW WORK
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
CL
9'-10"
9'-10"
8'-5.5"
Scale
Date
Project Number
Sheet General Notes & LegendsSORENSEN PARTNERS
15 Remington St. #1 | Cambridge, MA 02138
Marie S.A. Sorensen AIA NCARB LEED AP | T: 917.215.5796
ARCHITECTS + PLANNERS
Revisions
Consultant Architect
Consultants
Glassboro, NJ
#1028
Rowan University
Campbell Library
2017-03-08100% CD
FX101
FIRE PROTECTIONFLOOR PLAN