Download - Grounding & Bonding
Grounding & Bonding
Hazardous Materials Certification Study Guide
2
Definition of Terms (continued)
• Static Electricity - Electricity present on a surface of a non conductive body where electricity is trapped or prevented from escaping.
Hazardous Materials Certification Study Guide
3
Definition of Terms (continued)
• Static Transfer - Equalization of electrical charges. Nature wants to balance electrical charges. When there are excessive negative or positive charges they will seek ways to become neutral, which is what gives us the “shock”. This is the charges equalizing.
Hazardous Materials Certification Study Guide
4
Definition of Terms (continued)
• Grounding - The connection of the conductive objects to the earth.
• Bonding - The connection of two or more conductive objects together by the means of a conductor (wire cable).
Hazardous Materials Certification Study Guide
5
Source of Static Electricity• Static electricity can be created in all
states of matter. Conveyor belts, moving vehicles & pulverized materials through chutes are examples of solids that can generate static electricity. Liquids moving through constricted areas like pipe or transfer hoses do the same.
Hazardous Materials Certification Study Guide
6
Source of Static Electricity (continued)
• Gaseous generators are steam or gases flowing from an opening in a pipe. Other sources are contamination such as rust, dirt or dust in the transfer system.
Hazardous Materials Certification Study Guide
7
Conditions For Ignition
• Four conditions must be fulfilled in order for static electricity to be a source of ignition.– Generation of static electricity– Accumulation of static charge with no means to
discharge– Spark discharge of adequate energy– Spark discharge in an ignitable atmosphere
Hazardous Materials Certification Study Guide
8
Equipment Needed to Control Static Electricity
• 3 - 3/4” copper grounding rods - 4-6’
• 3 - 1/8” stainless steel grounding cables with a single point clamp at one end and an alligator clamp at the other end - 50’ length
• 2 - 1/8” stainless steel grounding cables with a single point clamp at both ends - 50’ length
• 1 ohm meter
Hazardous Materials Certification Study Guide
9
Ways to Control Static Electricity Hazards
• Remove the flammable mixture– Use foam or fog to reduce the ignitable
atmosphere.
• Slow down the transfer– This option probably will not be practical
Hazardous Materials Certification Study Guide
10
Ways to Control Static Electricity Hazards (continued)• Release or relax the charge after it has
been generated. (Ground & Bond)– By grounding & bonding, we are giving the
static charge a path in which to travel to earth without creating a spark. Ideally, the grounding rods should be 10’ in length & 5/8” in diameter. The clamps used should be screw clamps or pressure point clamps.
Hazardous Materials Certification Study Guide
11
Recommended Practices For Cable/Rod Connection
• Be certain to attach the cables to a part of the vehicle that is connected directly to the vessel holding the contents that you are going to transfer or otherwise work with.
Hazardous Materials Certification Study Guide
12
Recommended Practices For Cable/Rod Connection
• NEVER connect the grounding cables to the following:– Bolted-on-Ladders– Bumpers– Container Jackets– Strapping holding the container to the
vehicle
Hazardous Materials Certification Study Guide
13
Recommended Practices For Cable/Rod Connection
• ALWAYS connect the grounding cables to something welded to or part of the tanker itself.– Since the flow of materials through a
constricted carrier such as a pipe or transfer hose can cause static electricity to be generated, ALWAYS ground.
Hazardous Materials Certification Study Guide
14
General Procedures for Grounding & Bonding
• Test the area with a CGI to establish the limits of the hot zone and find a flammable atmosphere free area to connect the “ground”.
Hazardous Materials Certification Study Guide
15
Bonding & Grounding Sequence
NURS
ECALF
12
3
4
A
B
BOND
GROUND RODS
Make connections in sequence shown to avoid sparks in potentially flammable areas
Connection A-Bcan be made anytimeprior to off-loading
Hazardous Materials Certification Study Guide
16
Grounding the Leaking Vehicle (Nurse)
• Place the grounding rod as far away from the vehicle as possible.
• Attach the single point clamp to the tanker.• Attach the alligator clamp to the grounding
rod.– This should be as low as possible so that it
is in the foam blanket.– The tanker is now grounded.
Hazardous Materials Certification Study Guide
17
Grounding the Receiving Vehicle (Calf)
• Place the grounding rod
• Attach the single point clamp
• Attach the alligator clamp to the grounding rod
• Test resistance
Hazardous Materials Certification Study Guide
18
Bonding the Nurse & Calf• A single point clamp is placed on the
leaking vehicle (nurse).• A single point clamp is placed on the
receiving vehicle (calf).• Test resistance.
– A delay of a minimum of 5 minutes should occur after bonding & grounding has been accomplished before any offloading should start.
Hazardous Materials Certification Study Guide
19
Offloading From a Damaged Tank Truck to Another Truck
• Test the area with CGI to establish the limits of the hot zone and find a flammable atmosphere free area in which to park the vehicle that will be receiving the product.
• Connect your wire (at least 8 AWG) to the leaking vessel, tank truck or other potential static source first. DO NOT hook up the receiving vehicle before you connect to the potential static source.
Hazardous Materials Certification Study Guide
20
Offloading From a Damaged Tank Truck to Another Truck
• Connect your wire to the receiving vehicle (in the “safe” zone). If you connect to your receiving vehicle first, the difference in electrical potential might cause a spark when you hook up to the leaking truck causing ignition of flammable vapors.
• Remember that stingers & pumps used in offloading MUST also be bonded & grounded.
Hazardous Materials Certification Study Guide
21
Bonding & Grounding To Off-Load a Flammable Material
Wind
Hot Zone
Cold Zone
CALF
NURSE
Grounding Cable
Bonding Cable
Hazardous Materials Certification Study Guide
22
306 Cargo Tank Involved Fire
• Aluminum tank
• Gasoline
• Decision to allow fire to burn
• Estimate that the rate of fuel burn to be 1 foot of fuel per hour