![Page 1: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/1.jpg)
Foundation Performance AssociationDecember 10, 2008 – Houston, Texas
![Page 2: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/2.jpg)
1st Edition Manual (1980)
2 d Editi M l (1996)2nd Edition Manual (1996)● Included minor changes to structural equations
(shear for example)
2
(shear for example)
● Included Compressible Soils and Uniform Thickness Foundation analysis
![Page 3: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/3.jpg)
3rd Edition Manual 3 Edition Manual (December 2004)
Two standalone “standards” (written in mandatory code language) were also published. The “standards”, not the manual, e sta da ds , ot t e a ua ,are referenced by IBC
3
![Page 4: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/4.jpg)
In addition to major changes in the geotechnical i i th 3rd Editi i l d d i ifi t provisions, the 3rd Edition included significant
changes to the structural provisions:
Differential Deflection replaced by MINIMUM STIFFNESS requirement.
Added CRACKED SECTION CAPACITY requirement. Requires tendons or rebar in the bottom of ribs.
Part of slab area permitted to be included in bearing area. May not be appropriate for Houston due to soft surface soils and required penetration (typically 12-
4
surface soils and required penetration (typically 1218 inches).
![Page 5: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/5.jpg)
The original 3rd Edition procedure The original 3rd Edition procedure was found to be conservative and widely misapplied (for a variety of widely misapplied (for a variety of
reasons).
As a result, two Addenda were ,issued to provide clarification and reduce the level of conservatism.
5
![Page 6: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/6.jpg)
IN GENERAL, em AND ym WERE REDUCED.
Significant changes to the structural Significant changes to the structural provisions include:
• Allowable shear stress of concrete • Allowable shear stress of concrete increased (approx. 40%)
S iff ffi i d d 12 000 • Stiffness coefficient reduced to 12,000 from 18,000
• Cracked Section Capacity coefficient reduced to 0.5 from 0.9 in Addendum #1
6
Note: Major errata regarding definition of suction profiles was introduced in Addendum #1
![Page 7: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/7.jpg)
IN GENERAL, em WAS REDUCED.
Only minor changes to the structural provisions:Only minor changes to the structural provisions:
• Decreased minimum rib width to 6 inches (primarily to accommodate stay-in-place form (primarily to accommodate stay in place form systems)
• Clarified use of ribs spaced closer than 6 feet p(primarily to accommodate stay-in-place form systems)
• Removed Esoil from the structural equations. Hard coded to 1,000 psi.
7
Note: Modifications to Soil Fabric Factor table included in Addendum #2 to address issues identified during testing of Houston soils.
![Page 8: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/8.jpg)
2008 Supplementpp
Includes the Addenda, errata and the two “standards”and the two standards
8
![Page 9: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/9.jpg)
Design is performed based on “trial and Design is performed based on trial and error” procedure. Assumptions are made and then assumed design checked for “ li ” If d d i i “ t f “compliance”. If assumed design is “out of compliance” or over-designed the assumptions should be modified and assumptions should be modified and analysis performed analysis.
9
![Page 10: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/10.jpg)
Trial foundation checked for compliance with the following:
• Flexural Stresses• Tension• Compression
• Shear Stress• Minimum Stiffness Requirementq• Cracked Section Capacity• Soil Bearing
10
Soil Bearing
![Page 11: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/11.jpg)
11
![Page 12: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/12.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate versus Beam analysisPlate versus Beam analysis
• Foundation Shape
• Center Lift Shear
12
![Page 13: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/13.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate versus Beam analysisPlate versus Beam analysis
• Foundation Shape
• Center Lift Shear
13
![Page 14: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/14.jpg)
• Type I – Unreinforced
• Type II Lightly reinforced against • Type II – Lightly reinforced against shrinkage and temperature cracking Can be used for sites with Weighted PI<15Can be used for sites with Weighted PI<15
• Type III – Reinforced and stiffenedPTI Design procedure (Weighted PI>15)
• Type IV – StructuralType IV StructuralShould be considered for sites with ym > 4 inches, steep slopes, deep fills
14
![Page 15: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/15.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate versus Beam analysisPlate versus Beam analysis
• Foundation Shape
• Center Lift Shear
15
![Page 16: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/16.jpg)
The PTI design procedure requires determination of:determination of:
Perimeter Load – Used in determination of applied moment and shearof applied moment and shear
Total Superimposed Load – Used only for b i l i ( i lifi d bearing analysis (very simplified approach)
Built into procedure is a 40 PSF live load applied directly to first floor slab AND a 65 PSF dead load
16
to account for the weight of a 4 inch thick slab and first floor partitions.
![Page 17: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/17.jpg)
PTI 4.5.4.3 - “In the edge lift mode, designers are permitted however to use designers are permitted, however to use dead load and sustained live load, or to use dead load only.”
PTI 4.5.4.3 – “When P varies significantly g yaround the slab perimeter, and the ratio of largest to smallest exceeds 1.25, the
flargest value should be used for center lift design and the smallest value should be used for edge lift design
17
be used for edge lift design.
![Page 18: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/18.jpg)
Siding Assume Hip Roof
Use representative (weighted average)
1-Story
g(Lightest)
Stone
Hip Roofloads.
Use of localized
2-Story 1-Story
extreme values (high or low) that are not representative of the
Stone
Stone (Heaviest)
overall loading conditions will result in conservative d iStone
Stone (Heaviest)
designs.
18
(Heaviest)
![Page 19: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/19.jpg)
Since the foundation behavior is a function of the creep modulus of both the soil and o t e c eep odu us o bot t e so a dconcrete, long term sustained loads should be used.
Short-durations live loads (wind, seismic, snow, etc.) should not be used.
19
![Page 20: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/20.jpg)
Including short-duration loads in the perimeter load may be over-conservative
for the Center Lift Mode.
20
![Page 21: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/21.jpg)
Including short-duration loads in the perimeter load may be unconservative for perimeter load may be unconservative for
Edge Lift mode.
21
![Page 22: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/22.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate on Uneven SurfacePlate on Uneven Surface
• Foundation Shape
• Center Lift Shear
22
![Page 23: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/23.jpg)
Unlike other foundation design Unlike other foundation design procedures, the PTI procedure
is based on a plate on an is based on a plate on an uneven surface.
As a result, thinking about foundation behavior in terms of foundation behavior in terms of
beam mechanics is not i t
23
appropriate.
![Page 24: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/24.jpg)
Center Lift
24Edge Lift
![Page 25: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/25.jpg)
The PTI procedure was developed using rectangular plates (not beams) with the soil mo ement occ ing along all fo sides movement occurring along all four sides simultaneously resulting in interaction between the two orthogonal directions (short between the two orthogonal directions (short and long). This assumption resulted in the “worst case conditions.”
25
![Page 26: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/26.jpg)
From Rifat Bulut’s Dissertation
26
![Page 27: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/27.jpg)
27
![Page 28: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/28.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate on Uneven SurfacePlate on Uneven Surface
• Foundation Shapes
• Center Lift Shear
28
![Page 29: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/29.jpg)
Si th PTI d d l d i t l Since the PTI procedure was developed using rectangular shaped plates, irregular shaped foundations can result in
stresses significantly higher than determined by the parametric equations.
29From Rifat Bulut’s Dissertation
![Page 30: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/30.jpg)
Shape Factor (SF)(defined as perimeter2/area) (defined as perimeter2/area)
If the SF is greater than 24 then the designer should consider:should consider:
• modifications to the foundation footprint
• Use strengthened foundation system
• Soil treatment to reduce shrink / swell /potential
• Use additional non-prestressed reinforcement
30
p
• Provide additional beams
![Page 31: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/31.jpg)
PTI 6.3 – “Slabs of irregular shape should be divided into overlapping rectangles so be divided into overlapping rectangles so that the resulting boundary provides reasonable congruence with the foundation reasonable congruence with the foundation perimeter.”
PTI 6.3 –“Long narrow rectangles may not appropriately model the overall foundation and generally should not govern the design.”
31
![Page 32: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/32.jpg)
A
BB
32
![Page 33: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/33.jpg)
SF = 20.3
33
![Page 34: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/34.jpg)
SF = 41.7
34
![Page 35: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/35.jpg)
SF = 31.8
35
![Page 36: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/36.jpg)
Sl b T• Slab Types
• Foundation Loads• Foundation Loads
• Plate on Uneven SurfacePlate on Uneven Surface
• Foundation Shapes
• Center Lift Shear
36
![Page 37: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/37.jpg)
140%
Center Lift Analysis (PI = 22 Soil)Em = 9', Ym = 0.9", Perimeter Load = 2000 plf, Rib 12x24"
100%
120%
able
NOTE: Values over 100% exceed allowable criteriaNOTE: Values over 100% exceed allowable criteria
60%
80%
age
of A
llow
a
40%
60%
Perc
enta
0%
20%
Bending Stress (Tension) - Short Bending Stress (Compression) - Short
37
Stiffness - Short Shear - ShortCracked Section - Short Bending Stress (Tension) - LongBending Stress (Compression) - Long Stiffness - LongShear - Long Cracked Section - Long
![Page 38: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/38.jpg)
140%
Center Lift Analysis (PI = 22 Soil)Em = 9', Ym = 0.1", Perimeter Load = 2000 plf, Rib 12x24"
NOTE: Values over 100% exceed
100%
120%
able
allowable criteria
60%
80%
age
of A
llow
a
40%
60%
Perc
enta
0%
20%
Bending Stress (Tension) - Short Bending Stress (Compression) - Short
38
Stiffness - Short Shear - ShortCracked Section - Short Bending Stress (Tension) - LongBending Stress (Compression) - Long Stiffness - LongShear - Long Cracked Section - Long
![Page 39: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/39.jpg)
140%
Center Lift Analysis (PI = 22 Soil)Em = 7', Ym = 0.9", Perimeter Load = 2000 plf, Rib 12x24"
NOTE: Values over 100% exceed
100%
120%
able
allowable criteria
60%
80%
age
of A
llow
a
40%
60%
Perc
enta
0%
20%
Bending Stress (Tension) - Short Bending Stress (Compression) - Short
39
Stiffness - Short Shear - ShortCracked Section - Short Bending Stress (Tension) - LongBending Stress (Compression) - Long Stiffness - LongShear - Long Cracked Section - Long
![Page 40: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/40.jpg)
140%
Center Lift Analysis (PI = 22 Soil)Em = 5', Ym = 0.9", Perimeter Load = 2000 plf, Rib 12x24"
NOTE: Values over 100% exceed
100%
120%
able
allowable criteria
60%
80%
age
of A
llow
a
40%
60%
Perc
enta
0%
20%
Bending Stress (Tension) - Short Bending Stress (Compression) - Short
40
Stiffness - Short Shear - ShortCracked Section - Short Bending Stress (Tension) - LongBending Stress (Compression) - Long Stiffness - LongShear - Long Cracked Section - Long
![Page 41: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/41.jpg)
The original plate analysis indicated that for small ym values, the maximum center lift h l i bl if lift shear value is reasonably uniform or decreases for em>5ft
P=~1 500 lb P=~1,500 lbP=~1,500 lb ,
41
![Page 42: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/42.jpg)
For large ym values, the center lift shear value increases for em>5 ft.
P=~1,500 lb P=~1,500 lb
42
![Page 43: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/43.jpg)
Short Direction Center Lift Shear versus em
Lift
Shea
rtio
n C
ente
r Sh
ort D
irect
3 4 5 6 7 8 9
S
em
43
(feet)
![Page 44: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/44.jpg)
The original plate analysis indicated that for small ym values, the maximum center lift h l i bl if lift shear value is reasonably uniform or decreases for em>5ft
P=~1 500 lb P=~1,500 lbP=~1,500 lb ,
44
![Page 45: Foundation Performance Association December 10, 2008](https://reader031.vdocuments.mx/reader031/viewer/2022012502/617ba003151ada750e51df6d/html5/thumbnails/45.jpg)
140%
Center Lift Analysis (PI = 22 Soil)Em = 9', Ym = 0.9", Perimeter Load = 2000 plf, Rib 12x24"
NOTE: Values over 100% exceed Limit em to 5 ft for Short
100%
120%
able
allowable criteriaLimit em to 5 ft for Short Direction Center Lift Shear
60%
80%
age
of A
llow
a
40%
60%
Perc
enta
0%
20%
Bending Stress (Tension) - Short Bending Stress (Compression) - Short
45
Stiffness - Short Shear - ShortCracked Section - Short Bending Stress (Tension) - LongBending Stress (Compression) - Long Stiffness - LongShear - Long Cracked Section - Long